PLAN NO.: 2883.89.1

DRAWING: 1 OF 10

DRAWN BY: P. SIMMONSSCALE: 1/4” = 1’-0”

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED FOR CLARITY P.S.

FOUNDATION/BASEMENT

PLAN

1© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 3 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 2 OF 10

DRAWN BY: P. SIMMONSSCALE: 1/4” = 1’-0”

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED FOR CLARITY P.S.

FIRST FLOORPLAN

2© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 4 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 3 OF 10

DRAWN BY: P. SIMMONSSCALE: AS SHOWN

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED FOR CLARITY P.S.

SOUTHELEVATION &

WINDOW/DOORSCHEDULES

3© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 5 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 4 OF 10

DRAWN BY: P. SIMMONSSCALE: AS SHOWN

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED FOR CLARITY P.S.

EAST ELEVATION& INTERIORELEVATIONS

4© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 6 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 5 OF 10

DRAWN BY: P. SIMMONSSCALE: AS SHOWN

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED FOR CLARITY P.S.

NORTHELEVATION &PLOT PLAN

5© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 7 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 6 OF 10

DRAWN BY: P. SIMMONSSCALE: AS SHOWN

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED FOR CLARITY P.S.

2 11/01/13 REPLACED PANELBOARD SCHEDULES P.S.

WESTELEVATION

& ELECTRICALSCHEDULES

6

1

70AElectric furnace Central air conditioner45A

3

2

4

5

20AWater pump Water heater30A

6

7 8

1120AHeat – vent – light

Front Bedroom bathHeat – vent – lightMaster Bedroom bath

20A12

1315A

Freezer receptacle Bathrooms, hall lighting15A

14AG

915A

Master Bath hydromassage Attic exhaust fan15A

10G

These branch circuits arerequired to be protected bya listed combination typeAFCI device. NEC 210.12(A)

A G Receptacles on this circuit required to be GFCI protected. Install listed GFCI circuit breaker in panel, or listed GFCI receptacles at required locations. NEC 210.8(A)

1515A

Entry-Porch lighting Front Bedroom lighting& outside receptacle

15A16A, G A, G

1715AWorkshop lighting Workbench receptacles

20A18G

1915AMaster Bedroom lighting &

outside receptacle Workshop receptacleswindow wall

20A20G A, G

lighting 2115AStudy-Bedroom

Master Bath receptacle20A

22G A

2320A

Hall Bath receptacle Spare20A

24G

2515A

Spare Spare15A

26

27

Feeder Panelboard B

Space28100A

29 Space30

200 A MAIN

SERVICEDISCONNECT

EQUIPMENT GROUNDINGCONDUCTOR BUS

NEUTRAL BUS

1

30ADryer Counter-mounted range

40A3

2

4

5Dishwasher

Wall-mounted oven30A15A

20A

7

6

8

915AWet-bar lighting and

receptaclesLaundry, Rear Entry, Powder Room, Attic lighting

15A10

1115ARecreation Room

receptacles

Kitchen receptacles(west counter top)

Recreation Room lighting15A

12

1320A

Kitchen lighting

Garage receptacles

15A14

1520AKitchen wall

receptaclesKitchen receptacles (south countertop & island)

20A16

1715ALiving Room &

outside receptacle Clothes washer receptacle20A

18

1920A

Food waste disposer

Spare

Space

Spare

Spare

Space

Laundry Room receptacles& outside receptacle

20A20

2120A

Powder Room receptacle Refrigerator receptacle20A

22

23Electric Vehicle receptacle(optional)

Garage lighting and opener

20A24

125 AMain Lug Only (MLO)

A, G

A, G

A, G

A, G

A, G

A, G

A, G

A, G

G

A

A

G

G

A, G

A

A

A

Equipment groundingconductor bus

Neutral bus G Receptacles on this circuit required to be GFCI protected. Install listed GFCI circuit breaker in panel, or listed GFCI receptacles at required locations. NEC 210.8(A)

The outlets and devices onthis branch circuit arerequired to have AFCI protection by one of six methods. NEC 210.12(A)

A

2540A15A

26

2715A 15A

28

29 30

© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 8 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 7 OF 10

DRAWN BY: P. SIMMONSSCALE: AS SHOWN

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED FOR CLARITY P.S.

CROSS SECTIONA-A

7

CROSS SECTION A-ASCALE: 3/8" = 1'-0"

© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 9 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 8 OF 10

DRAWN BY: P. SIMMONSSCALE: 1/4” = 1’-0”

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED ELECTRICAL PLAN P.S.

2 11/01/13 REVISED AND ADDED NOTES P.S.

BASEMENTELECTRICAL

PLAN

8© 2015 Cengage Learning

®

. All Rights Reserved. May not be scanned, copied, or duplicated, or posted to a publicly accessible website, in whole or in part.

70954_BP_ptg01_001-012.indd 10 02/12/13 7:56 PM

PLAN NO.: 2883.89.1

DRAWING: 9 OF 10

DRAWN BY: P. SIMMONSSCALE: 1/4” = 1’-0”

CHECKED BY: R. MULLINNO. DATE REVISION BY

1 08/01/10 REVISED ELECTRICAL PLAN P.S.

2 11/01/13 REVISED ELECTRICAL PLAN P.S.

FIRST FLOORELECTRICAL

PLAN

9© 2015 Cengage Learning

®