1. REFERENCE LS-1 FOR NOTES AND LEGEND.
SHEET NOTES:
FIRE EXTINGUISHER TABLE
TYPE RATING HAZARD QTY ROOM # ROOM NAME
DRY
CHEMICAL
4A:80B-C CLASS A/B/C
1 R101 STORAGE
2 R102 WAREHOUSE
1 R103 WAREHOUSE
2 R104 WAREHOUSE
TOTAL 6
OCCUPANT LOAD:
USE/ROOM AREA SF/PERSON LOAD
STORAGE (R104)
4459 500 9
STORAGE (R101, R102, R103)
4375 500 9
TOTAL 18
OCCUPANCY CLASSIFICATION:
STORAGE OCCUPANCY "S-2"
CONSTRUCTION TYPE: V-B NON-RATED COMBUSTIBLE CONSTRUCTION
STRUCTURAL FRAME: 0 HR. RATED
BEARING WALLS: 0 HR. RATED
NON-BEARING WALLS: 0 HR. RATED, INTERIOR
0 HR. RATED, EXTERIOR
FLOOR: 0 HR. RATED
ROOF: 0 HR. RATED
FIRE SUPPRESSION: NOT REQUIRED TO BE SPRINKLERED THROUGHOUT ACCORDING TO UFC 3-600-01.
ALLOWABLE AREA (S.F.) S-2
BASE ALLOWABLE 13,500
OPEN YARD INCREASE (70%) 9,450
TOTAL/FLOOR: 22,950
ACTUAL AREA (S.F. ±): 8,834
BUILDING DIVIDED BY 2-HOUR FIRE WALL.
ALLOWABLE & ACTUAL EGRESS DISTANCES (FT.):
ALLOWABLE ACTUAL
TRAVEL DISTANCE 250 65
COMMON PATH 100 26
DEAD END CORRIDOR 20 NA
BUILDING HEIGHT (ACTUAL / ALLOWABLE):
STORIES: 1 / 2 (BASED ON NON-SPRINKLERED V-B CONSTRUCTION)
FEET: 21 + / 40 (BASED ON NON-SPRINKLERED V-B CONSTRUCTION)
EXITS (ACTUAL/REQUIRED):
GROUND: 7 / 2 (BASED ON 18 OCCUPANTS)
TRAVEL DISTANCE TO AN EXIT
TWO PATHS OF EGRESS AVAILABLE
COMMON PATH TO POINT WHERE
CEILING MOUNT EXIT SIGN
WALL MOUNT LIGHTED EXIT SIGN
DIRECTION ARROW
LIGHTED / SIDE FACE
MANUAL PULL STATION
EGRESS ELEMENT (DOOR, STAIR, ETC.)
EGRESS WIDTH (CLEAR)
EXIT WIDTH PER PERSON (IN.)
ACTUAL (PEOPLE)
FIRE EXTINGUISHERFE
CAPACITY (PEOPLE)
F
FMCP
BASED ON: 2018 NFPA 101 LIFE SAFETY CODE
2018 INTERNATIONAL BUILDING CODE
2018 NFPA 10 PORTABLE FIRE EXTINGUISHER
2020 NFPA 70 NATIONAL ELECTRICAL CODE
2019 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
7 EXTERIOR DOORS AT 33" EACH
TOTAL EXIT WIDTH PROVIDED = 231"
TOTAL EXIT WIDTH REQUIRED (18 X 0.2) = 2.6"
NOTE: OCCUPANT LOAD BASED ON BUILDING AREA
CODE ANALYSIS:
LEGEND:
EXIT CAPACITY:
EXIT SIGNS
SMOKE DETECTORS
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
EMERGENCY LIGHT
EMERGENCY LIGHT AND EXIT SIGN
DUAL FIRE WALL: 2 HOUR RATED
tt
IN
RT
NJE
NO
L.
TE
NA
040804E NG
F NI EER
OL
V
SEAL
S
ASFORP
EH C
IAL
OI N
OR L
T
E R
12-20-2019
P:\TAS\Bldg. M255 - 4841.00\Dwg\Working Dwg\Bound\60025427.dwg, 2/19/2020 11:38:13 AM, DWG To PDF.pc3
SHEET
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. K. AVOLIS, P.E.
J. C. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
NAVFAC DRAWING NO.DATE
DATEOF
T. H. BURTON, P.E.
SPEC. 05-19-0091 354
60025429NEW BERN, NC 28561(252) 633-0068
P.O. BOX 15564
LICENSE NO. C-0706
TNPN
RENOVATEBLDG M255Digitally signed by John K Avolis
SHEET
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. K. AVOLIS, P.E.
J. C. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
NAVFAC DRAWING NO.DATE
DATEOF
T. H. BURTON, P.E.
SPEC. 05-19-0091 355
RENOVATEBLDG M255
60025430NEW BERN, NC 28561(252) 633-0068
P.O. BOX 15564
LICENSE NO. C-0706
TNPN
Digitally signed by John K Avolis
SHEET
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. K. AVOLIS, P.E.
J. C. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
NAVFAC DRAWING NO.DATE
DATEOF
T. H. BURTON, P.E.
SPEC. 05-19-0091 356
60025431NEW BERN, NC 28561(252) 633-0068
P.O. BOX 15564
LICENSE NO. C-0706
RENOVATEBLDG M255Digitally signed by John K Avolis
END OF LINE RESISTOREOL
1. THE FIRE ALARM /MASS NOTIFICATION CONTROL PANEL (FMCP) SHALL BE A SITE PROGRAMMABLE
ADDRESSABLE SYSTEM WITH VOICE EVACUATION.
2. THE FMCP SHALL BE LOCATED IN AN YEAR-ROUND ENVIRONMENTALLY CONDITIONED SPACE.
3. THE FMCP SHALL HAVE AN 80 CHARACTER (MIN.) LCD ALPHANUMERIC DISPLAY AND A 400 EVENT
NON-VOLATILE HISTORY LOG MEMORY
4. ALL CONTROL FUNCTIONS SHALL BE ACCESSIBLE ONLY BY USER CODE OR SECURED BEHIND A LOCKED
CABINET.
CONTROL PANEL:
1. THE INITIATING CIRCUITS SHALL BE CLASS "B".
2. ALL SMOKE DETECTORS CONNECTED TO THE FMCP SHALL HAVE AN ADJUSTABLE ALARM VERIFICATION
FEATURE, INITIALLY SET AT 20 SECONDS.
3. ALL SMOKE DETECTORS SHALL BE PHOTO-ELECTRIC UNLESS NOTED OTHERWISE.
4. MANUAL PULL STATIONS SHALL BE ADDRESSABLE DOUBLE ACTION TYPE WITH MECHANICAL RESET FEATURES.
IF RESET BY KEY, IT SHALL BE THE SAME AS REQUIRED FOR THE FMCP.
INITIATING CIRCUITS (SLC):
1. THE NOTIFICATION CIRCUITS SHALL BE A CLASS "B".
2. THE AUDIBLE ALARM NOTIFICATION SHALL BE BY VOICE EVACUATION SYSTEM. SPEAKERS SHALL HAVE
MANUALLY SELECTABLE MULTI/VARIABLE WATTAGE, 0.25 TO 1.0 WATTS IN 0.25 WATT INCREMENTS. INITIAL
SETTING TO BE AT 0.50 WATTS.
3. VOICE MESSAGES SHALL BE FEMALE, AND UTILIZE THE INSTALLATION'S STANDARD SIGNALS AND MESSAGES.
MESSAGES SHALL BE APPROVED BY THE SERVING FIRE DEPARTMENT OR AHJ.
4. THE NUMBER AND PLACEMENT OF SPEAKER(S) TO BE SUFFICIENT TO PROVIDE 0.70 (CIS SCORE) AUDIBILITY
RATING WITHIN THE AREA WITH ALL DOORS, FIRE SHUTTERS, MOVABLE PARTITIONS, AND SIMILAR DEVICES
CLOSED.
5. VISUAL NOTIFICATION SHALL BE PROVIDED IN ALL NORMALLY OCCUPIED, PUBLIC, AND COMMON USE AREAS.
OFFICES DESIGNED FOR FOUR OR MORE PERSONS SHALL HAVE VISUAL NOTIFICATION.
6. VISUAL NOTIFICATION SHALL BE PROVIDED IN ALL NORMALLY UNOCCUPIED AREAS GREATER THAN 900 SQ. FT.
SUCH AS MECH., ELECTRICAL, STORAGE, COMMUNICATIONS, JANITORS ROOMS, AND SIMILAR SPACES.
7. STROBES SHALL HAVE MANUALLY SELECTABLE CANDELA RATINGS, 15 TO 110 CANDELA. CANDELA RATING
SHALL BE BASED ON LOCATION AND QUANTITY IN A ROOM IN ACCORDANCE WITH NFPA 72.
8. VISIBLE NOTIFICATION APPLIANCES SHALL HAVE A CLEAR LENS IN A WHITE HOUSING MARKED "ALERT" IN RED.
NOTIFICATION CIRCUITS (NAC):
1. ALL CONDUCTORS TO BE RUN IN 3/4" MINIMUM RIGID METAL CONDUIT (RMT). PROVIDE CONDUIT SIZES,
QUANTITIES, AND CONFIGURATION IN ACCORDANCE WITH LISTED DESIGN CRITERIA AND APPROVED SHOP
DRAWINGS.
2. ALL CONDUCTORS SHALL BE EITHER STRANDED OR SOLID COPPER. 18 AWG MIN FOR SLC AND 16 AWG MIN.
FOR NAC CIRCUITS.
3. ALL CONDUIT, WIRES, AND CABLES IN FINISHED SPACES SHALL BE CONCEALED IN WALLS, CEILING, AND
SIMILAR SPACES.
4. RUN ALL WIRING TO AND WITHIN THE CONTROL PANEL IN THE VERTICAL OR HORIZONTAL PLANE, MAKE ALL
TURNS AT 90 DEGREES ANGLES, AND TIGHTLY BUNDLED AND WRAPPED. IDENTIFY ALL CONDUCTORS
INDIVIDUALLY WITH PERMANENT PRINTED LABELS AFFIXED WITH SHRINK WRAP.
5. DEVICE CONNECTIONS SHALL BE THE DEVICE SCREW TERMINALS OR TERMINAL STRIPS MOUNTED WITHIN THE
JUNCTION BOX.
6. ALL CONDUIT, JUNCTION/BACK BOXES, COVERS, AND COUPLINGS ARE TO BE FACTORY PAINTED RED IN
UNFINISHED AREAS.
7. PROVIDE A SURGE SUPPRESSOR (SPD) ON ALL SLC AND NAC CIRCUIT THAT LEAVE OR ENTER THE FACILITY'S
EXTERIOR ENCLOSURE (EXCLUDING WALL MOUNTED DEVICES) (EG. WEATHERPROOF SPEAKER). LOCATE SPD
AT FIRST CONNECTION CLOSEST TO WHERE CIRCUIT ENTERS OR LEAVES THE FACILITY, PRIOR TO THE DEVICE.
8. 120 VAC CIRCUITS TO CONTROL PANELS, SUBPANELS, TRANSMITTERS, AMPLIFIER PANELS, AND BOOSTER
PANELS SHALL BE EQUIPPED WITH SPD. THE SPD SHALL BE LOCATED IN AN ADJACENT HINGED TERMINAL BOX.
WIRING, CONDUIT:
1. PRIMARY AC POWER TO THE FIRE ALARM/MASS NOTIFICATION CONTROL PANEL (FMCP) SHALL BE FED FROM A
DEDICATED CIRCUIT WITH A RED CIRCUIT BREAKER AND A LOCK OPEN DEVICE.
2. SECONDARY POWER SHALL BE BY RECHARGEABLE BATTERIES SIZED TO OPERATE THE SYSTEM FOR EITHER
48 HRS IN STANDBY/SUPERVISORY MODE WITH AN ADDITIONAL 15 MIN IN ALARM OR 60 MIN FULL ALARM
IMMEDIATELY AFTER LOSS OF PRIMARY POWER, WHICHEVER IS GREATER.
3. THE SYSTEM SHALL INCLUDE FULLY AUTOMATIC, SOLID STATE BATTERY CHARGER(S) UTILIZING A
TRICKLE-CHARGE OR A FLOAT-CHARGE. THE CHARGER(S) SHALL HAVE THE CAPACITY TO RECHARGE
BATTERIES TO 95% OF FULL CHARGE WITHIN 48 HOURS.
4. THE BATTERIES WITH CHARGER(S) SHALL BE HOUSED IN THE FMCP CABINET OR AN ADJACENT BATTERY
CABINET THAT IS LOCKED WITH THE SAME KEY AS THE FMCP.
5. PRIMARY POWER TO THE MASS NOTIFICATION TRANSCEIVER SHALL BE FED BY A DEDICATED CIRCUIT WITH A
RED CIRCUIT BREAKER AND LOCK OPEN DEVICE. CIRCUIT TO BE LOCATED IN THE SAME ELECTRICAL PANEL AS
THE FMCP CIRCUIT.
POWER/BATTERIES:
1. REFER TO FA-4 FOR DETAIL DIAGRAMS AND SEQUENCE OF OPERATIONS MATRIX.
2. THE LAYOUT SHOWN, IS TO CONVEY THE DESIGN INTENT. THE FINAL SYSTEM LAYOUT SHALL BE COMPLETED
BY THE SUBCONTRACTOR IN ACCORDANCE WITH LISTED DESIGN CRITERIA.
3. SUBCONTRACTOR RESPONSIBLE FOR SPEAKER LAYOUT PROVIDING THE REQUIRED CIS OF 0.7.
GENERAL:
DESIGN CRITERIA - FIRE ALARM/MASS NOTIFICATION SYS.
1. REMOVE EXISTING FIRE ALARM SYSTEM COMPLETE, REMOVE JUNCTION BOXES, AND ASSOCIATED WIRING.
2. REMOVE ABANDONED CONDUIT WHERE NOT EMBEDDED IN MASONRY WALLS OR CONCRETE SLABS.
3. FIELD VERIFY EXISTING CONDITIONS THAT MAY AFFECT THE SYSTEM OPERATION, INSTALLATION, OR
COMPLIANCE WITH THE DESIGN DRAWINGS AND NOTIFY THE CONTRACTING OFFICER PRIOR TO BEGINNING
WORK.
4. DAMAGE CAUSED BY DEMOLITION MUST BE REPAIRED (I.E. CEILING TILE, WALL FINISHES, SCREW HOLES,
HOLES LEFT FROM CONDUIT, DEVICE/EQUIPMENT REMOVAL, ETC.).
DEMOLITION NOTES:
MASS NOTIFICATION TRANSCEIVER
FIRE DEPARTMENT KNOX BOX
LEGEND
FIRE ALARM CONTROL PANEL
MANUAL PULL STATION
K
F
FACP
TRNS
SMOKE DETECTOR
FIRE ALARM/MASS NOTIFICATION CONTROL PANELFMCP
S
SPEAKER STROBE; # INDICATES CANDELA RATING
WALL MOUNT STROBE; # INDICATES CANDELA RATING
#
#
SPEAKER
HEAT DETECTOR
THE SYSTEM SHALL COMPLY WITH THE FOLLOWING CODES AND STANDARDS.
1. NFPA 70 NATIONAL ELECTRICAL CODE - 2020 ED.
2. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE - 2019 ED.
3. NFPA 101 LIFE SAFETY CODE - 2018 ED.
4. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS, 8 OCT 2019.
5. UFC 3-600-01 DESIGN FIRE PROTECTION ENGINEERING FOR FACILITIES WITH CHANGE 3, 10 MAY 2019.
6. UFC 3-520-01 INTERIOR ELECTRICAL SYSTEM WITH CHANGE 1, 20 MARCH 2019.
7. UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS WITH CHANGE 1, 1 JAN 2010.
SUBSCRIPTS
WEATHERPROOF
FIRE ALARM TRANSMITTERFATM
DUAL FIRE WALL: 2 HOUR RATED
tt
S/P SURGE PROTECTOR
IN
RT
NJE
NO
L.
TE
NA
040804E NG
F NI EER
OL
V
SEAL
S
ASFORP
EH C
IAL
OI N
OR L
T
E R
12-20-2019
P:\TAS\Bldg. M255 - 4841.00\Dwg\Working Dwg\Bound\60025445.dwg, 2/19/2020 11:39:08 AM, DWG To PDF.pc3
S
S
S
FACP
FATM
F
75
F
75
F
75
F
75
F
75
1. REFERENCE FA-1 FOR NOTES AND LEGEND.
2. ALL EXISTING FIRE ALARM DEVICES AND COMPONENTS TO BE
DEMOLISHED.
SHEET NOTES:
IN
RT
NJE
NO
L.
TE
NA
040804E NG
F NI EER
OL
V
SEAL
S
ASFORP
EH C
IAL
OI N
OR L
T
E R
12-20-2019
P:\TAS\Bldg. M255 - 4841.00\Dwg\Working Dwg\Bound\60025446.dwg, 2/19/2020 1:18:05 PM, DWG To PDF.pc3
F F F F
F F F
WP
75
FMCP
TRNS
S
K
WP WP
WP
75 75
75 75
75
75
110
tt
tt
tt
tt
1. REFERENCE FA-1 FOR NOTES AND LEGEND.
2. REFERENCE FA-4 FOR DETAILS AND DIAGRAMS.
3. ALL DEVICES AND COMPONENTS SHOWN ARE NEW.
SHEET NOTES:
IN
RT
NJE
NO
L.
TE
NA
040804E NG
F NI EER
OL
V
SEAL
S
ASFORP
EH C
IAL
OI N
OR L
T
E R
12-20-2019
P:\TAS\Bldg. M255 - 4841.00\Dwg\Working Dwg\Bound\60025447.dwg, 2/19/2020 11:40:09 AM, DWG To PDF.pc3
BATTERIES
S/P
ACU
S/PDACT
S/P
EOL
EOL
EOL
EOLS
MIC
F
F
LOC
BE
TW
EE
N 80"-96"
15"-48"
OP
ER
AB
LE
P
AR
T
SPEAKER/STROBE
STROBE OR
6" M
IN
.
FLOOR
EXIT
12" MAX.
4" MIN.
4"
MIN.
5'-0"
MIN.
SMOKE/HEAT
DETECTOR
CONDUIT
CEILING
O
F C
ON
TR
OLS
**
WALL MOUNTED
SUPPLY OR
RETURN GRILL
ST
RO
BE
LE
NS
DETECTOR
SMOKE/HEAT
TRNS
LOCFMCP
AC
TU
AT
E A
UD
IBLE
& V
ISU
AL
ALA
RM
SIG
NA
L IN
DIC
AT
OR
&A
LAR
M @
FM
CP
AC
TU
AT
E A
UD
IBLE
& V
ISU
AL
SU
PE
RV
ISO
RY
SIG
NA
LIN
DIC
AT
OR
& A
LAR
M @
FM
CP
AC
TU
AT
E A
UD
IBLE
& V
ISU
AL
TR
OU
BLE
SIG
NA
L IN
DIC
AT
OR
& A
LAR
M @
FM
CP
DIS
PLA
Y /
PR
INT
CH
AN
GE
OF
ST
AT
US
ON
FM
CP
TR
AN
SM
IT S
IGN
AL
TO
MO
NIT
OR
ING
ST
AT
ION
AC
TU
AT
E F
IRE
ALA
RM
AU
DIB
LE M
ES
SA
GE
AC
TIV
AT
E A
LER
T V
ISU
AL
AP
PLI
AN
CE
S
OV
ER
RID
E P
RE
-RE
CO
RD
ED
DIG
ITIZ
ED
VO
ICE
ME
SS
AG
E
OV
ER
RID
E F
IRE
ALA
RM
AU
DIB
LE S
IGN
ALS
BR
OA
DC
AS
T M
NS
AU
DIB
LEM
ES
SA
GE
MANUAL PULL STATION
GENERAL SMOKE DETECTOR
FIRE ALARM AC POWER FAILURE
FIRE ALARM SYS LOW BATTERY
OPEN CIRCUIT/GROUND FAULT
NOTIFICATION APPLIANCE SHORT
FIRE ALARM LIVE VOICE MESSAGE
MNS LIVE VOICE MESSAGE
MNS AUTONOMOUS CONTROL UNIT
X X X X X
X X X X X
X X X
X X X
X X X
X X X
X X X X X X
X X X X X X X
X X X X X X
ACTION TO BE INITIATED
DEVICE INITIATEDACTION
1. REFERENCE FA-1 FOR NOTES AND LEGEND.
2. REFERENCE FA-3 FOR FLOOR PLAN
SHEET NOTES:
SEE FLOOR PLAN FOR EXACT NUMBER AND LOCATION OF
DEVICES.
4 FEET ABOVE THE APEX OF THE ROOFLINE WITH A UL LISTED
WEATHERHEAD
CIRCUITS PROVIDED W/ RED BREAKERS, LOCK OPEN
DEVICE AND FED FROM THE SAME ELECTRICAL PANEL.
SEPARATE SLC CIRCUIT THAT WILL NOT BE PLACED ON TEST
MODE
KEY NOTES:
IN
RT
NJE
NO
L.
TE
NA
040804E NG
F NI EER
OL
V
SEAL
S
ASFORP
EH C
IAL
OI N
OR L
T
E R
12-20-2019
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266
www.cbhfengineers.com
cCopyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
UNITHEATER
6" M
IN
2' MIN 12"
SLOPE 1/4" PER FOOTDOWNWARD TOWARD OR FROMUNIT
4" MINNOTE: UNIT HEATER VENT DETAIL SHOWS GENERALGUIDANCE FOR HEATERS SCHEDULED, REFER TOMANUFACTURERS INSTALLATION MANUAL FOR COMPLETEREQUIREMENTS.
EXHAUST
COMBUSTION AIR
HORIZONTAL DISCHARGE
NOT TO SCALE3 GAS UNIT HEATER DETAIL
1. WALL ASSEMBLY - MIN 6 IN. (152 MM) THICK LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3)CONCRETE. WALL MAY ALSO BE OF ANY UL CLASSIFIED CONCRETE BLOCKS*. OPENING MAY BE ROUND, RECTANGULAROR IRREGULAR WITH A MAX DIAM OR DIMENSION OF 1 IN. (25 MM),WITH A MAX DIAM OF 1-1/8 IN. (29 MM).SEE CONCRETE BLOCKS (CAZT) IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. THROUGH PENETRANT — MAX ONE METALLIC PIPE, TUBING OR CONDUIT INSTALLED EITHER CONCENTRICALLY ORECCENTRICALLY WITHIN THE FIRESTOP SYSTEM.ANNULAR SPACE BETWEEN PENETRANT AND PERIPHERY OF THE OPENING SHALL BE MIN 0 IN. (POINT CONTACT). WHENOPENING DIMENSION EXCEEDSTHE MAX ANNULAR SPACE IS 3/8 IN. (9.5 MM). PIPE OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALLASSEMBLY. THE FOLLOWING TYPES PIPES, TUBING OR CONDUIT MAY BE USED:
A. STEEL PIPE — NORN 3/4 IN. (19 MM) DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE — NORN 3/4 IN. (19 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. COPPER TUBING — NORN 1/2 IN. (13 MM) DIAM (OR SMALLER) TYPE L AND TYPE K (OR HEAVIER) COPPERTUBING.
D. COPPER PIPE — NORN 1/2 IN. (13 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
E. CONDUIT - NORN 3/4 IN. (19 MM) DIAM (OR SMALLER) RIGID OR FLEXIBLE STEEL CONDUIT.
F. CONDUIT — NORN 3/4 IN. (19 MM) DIAM (OR SMALLER) ELECTRICAL METALLIC TUBING (EMT).
3. FILL, VOID OR CAVITY MATERIAL* — NORN 60 MM DIAM BY 3 MM THICK PUTTY DISC WITH ONE SEAM ATRADIUS. PAPER-BACKER OF DISC TO BE REMOVED FIRMLY PRESSED AROUND THE PENETRANT LAPPING NOM 5 MMONTO PENETRANT TO COMPLETELY COVER OPENING AND FIRMLY PRESSED TO LAP ONTO THE PERIPHERY OFOPENING. DISC SEAM TO BE FIRMLY PRESSED AND SEALED TIGHT, DISC TO BE INSTALLED AT BOTH SURFACES OFWALL. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CFS-D 1" FIRESTOP CABLE DISC
* INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THEUL OR CUL CERTIFICATION
System No W J 1248
F Ratings - 2 Hr
T Ratings - 2 Hr
L Rating at Ambient - Less Than 1 CFM / Opening
L Ratings at 400 F - Less Than 1 CFM / Opening
ANSI / UL1479 (ASTM E814)
F Ratings - 2 Hr
FT Ratings - 2 Hr
FH Ratings - 2 Hr
FTH Ratings - 2 Hr
CAN / ULC S115
L Rating at Ambient - Less Than 1 CFM / Opening
L Rating at 400 F - Less Than 1 CFM / sq ft
A
A
SECTION A-A
3
2 1
3
2
NOT TO SCALE1 2 HOUR FIREWALL PENETRATION DETAIL
WA
LL-INTE
RIO
R-
-EX
TER
IOR
-
OSHAAPPROVEDGUARD
SHORT WALLHOUSING
WA
LL
BACKDRAFTDAMPER
WEATHER HOOD WITHBIRDSCREEN
EXHAUST FAN
115V POWERSUPPLY (BY E.C.)
BACKDRAFT DAMPER
WALL-MOUNTEDOVERRIDESWITCH(BY E.C.)
ABBREVIATIONSTERM ABBREVIATION TERM ABBREVIATIONABOVE FINISHED FLOOR AFF INCH OF WATER GAUGE INWGABOVE GROUND AG INDOOR UNIT IDUABOVE SEA LEVEL ASL IRON PIPE SIZE IPSACROSS THE LINE ACL KILOVOLT-AMP KVAAIR ADMITTANCE VALVE AAV KILOWATT KWAIR CONDITION(-ING, -ED) AIR COND KILOWATT HOUR KWHAIR-HANDLING UNIT AHU OR AH LEAVING AIR TEMPERATURE LATAIR FLOW MEASURING STATION AFMA LEAVING WATER TEMPERATURE LWTAMBIENT AMB LENGTH LGAMPERE (AMP, AMPS) AMP LINEAR FEET LFANALOG INPUT AI MAXIMUM MAXANALOG OUTPUT AO MAXIMUM OVERCURRENT PROTECTION MOCPAND & MEDIUM-PRESSURE STEAM MPSAPPARATUS DEW POINT ADP MILES PER HOUR MPHAPPROXIMATE APPROX MINIMUM MIN.ARCHITECT ARCH MINIMUM CIRCUIT AMPERES MCAATMOSPHERE ATM MINUTE MINAVERAGE AVG MANUFACTURER MFRBRAKE HORSEPOWER BHP MOTOR CONTROL CENTER MCCBROWN & SHARPE WIRE GAGE B&S NOISE CRITERIA NCBRITISH THERMAL UNIT BTU NON-STANDARD PART LOAD NPLVBRITISH THERMAL UNIT PER HOUR BTUH NORMALLY OPEN NO1000 BRITISH THERMAL UNIT MBH NORMALLY CLOSED NCBUILDING BLDG NOT APPLICABLE N/ABUILDING AUTOMATION SYSTEM BAS NOT IN CONTRACT N I CCELSIUS ºC NOT TO SCALE NTSCHILLED WATER RETURN CHWR NUMBER NOCHILLED WATER SUPPLY CHWS ON CENTER OCCOEFFICIENT, VALVE FLOW CV OUNCE OZCOEFFICIENT OF PERFORMANCE FACTOR COP OUTDOOR UNIT ODUCOMPRESSOR COMP OUTSIDE AIR OACONCRETE CONC PACKAGE UNIT PUCONDENS(-ER, -ING, -ATION) COND PACKAGE TERMINAL AIR CONDITIONER PTACCONNECTION CONN PARTS PER MILLION PPMCONTINUATION CONT PERCENT %COOLING LOAD CLG LOAD PHASE PHCUBIC FEET CU FT POUNDS LBSCUBIC INCH CU IN POUNDS PER SQUARE FOOT PSFCUBIC FEET PER MINUTE CFM POWER VENTILATOR PVCFM, STANDARD CONDITIONS SCFM PRESSURE PRESSDECIBEL DB PRESSURE REDUCING VALVE PRVDEGREE DEG OR º PRESSURE SAFETY VALVE PSVDEDICATED OUTDOOR AIR SYSTEM DOAS PUMPED CONDENSATE PCDEGREES FAHRENHEIT DEG. F QUANTITY QTYDETAIL DET RATED LOAD AMPS RLADEW-POINT TEMPERATURE DPT RECIRCULATE RECIRCDIAMETER DIA REDUCED PRESSURE BACKFLOW PREVENTER RPZDIAMETER, INSIDE ID REFRIGERANT (12, 22, ETC.) R22, R410DIAMETER, OUTSIDE OD REFRIGERANT LIQUID RLDIFFERENCE OR DELTA DIFF REFRIGERANT SUCTION RSDIGITAL INPUT DI REQUIRED REQD OR REQ'DDIGITAL OUTPUT DO RELATIVE HUMIDITY RHDOMESTIC HOT WATER DHW RETURN AIR RADOMESTIC HOT WATER RECIRCULATION DHWR REVOLUTIONS PER MINUTE RPMDRY-BULB TEMPERATURE DBT REVOLUTIONS PER SECOND RPSDUCTLESS SPLIT SYSTEM AIR HANDLER DAH ROOF VENTILATOR RVDUCTLESS SPLIT SYSTEM HEAT PUMP DHP ROOF TOP UNIT RTUENERGY EFFICIENCY RATING ERR SAFETY FACTOR SFEFFICIENCY EFF SEASONAL ENERGY EFFICIENCY RATIO SEERELECTRIC UNIT HEATER EUH SECOND SELEVATION EL SHADING COEFFICIENT SCENTERING ENT SPECIFICATION SPECENTERING WATER TEMPERATURE EWT SQUARE SQENTERING AIR TEMPERATURE EAT STANDARD STDEXISTING (X) STATIC PRESSURE SPEXTERNAL AMBIENT TEMPERATURE EAT SUPPLY SPLYEXTERNAL STATIC PRESSURE ESP SUPPLY AIR SAEXHAUST AIR EA TEMPERATURE TEMPEXHAUST FAN EF TEMPERATURE DIFFERENCE TDFACE VELOCITY FVEL THERMOSTAT T STATFAHRENHEIT ºF TONS OF REFRIGERATION TONSFEET PER MINUTE FPM TO BE DETERMINED TBDFEET PER SECOND FPS TOP OF STEEL TOSFLOOR FLR TOTAL DYNAMIC HEAD TDHFOOT OR FEET FT TYPICAL TYPFULL LOAD AMPS FLA U-FACTOR UGAGE OR GAUGE GA UNDER GROUND UGGALLONS GAL UNLESS OTHERWISE NOTED UONGALLONS PER HOUR GPH UNIT HEATER - ELECTRIC UHGALLONS PER MINUTE GPM VARIABLE AIR VOLUME VAVGALLONS PER DAY GPD VARIABLE FREQUENCY DRIVE VFDGAS UNIT HEATER GUH VELOCITY VELGRAINS GR VENTILATION, VENT VENTHEAD HD VENT THRU ROOF VTRHEAT EXCHANGER HX VERTICAL VERTHEATING AND VENTILATION UNIT HV VOLT VHEATING, VENTILATION AND AIR CONDITIONING HVAC VOLT AMPERE VAHEIGHT HGT VOLUME VOLHERTZ HZ WATER PRESSURE DROP WPDHIGH DENSITY POLYPROPYLENE HDPE WATER GAUGE WGHIGH-PRESSURE STEAM HPS WATT WHORSEPOWER, HEAT PUMP HP WATT-HOUR WHHOT WATER COIL HWC WITH W/HOUR(S) HR WEIGHT WTHUMIDITY, RELATIVE RH WET BULB WBINTEGRATED PART LOAD VALUES IPLV YARD YDINCH IN. YEAR YRNOTE: ALL ABBREVIATIONS MAY NOT BE USED IN PROJECT.
MECHANICAL LEGENDPV# POWER VENTILATOR UNIT NUMBERL# INTAKE LOUVER NUMBER
GUH# GAS UNIT HEATER NUMBEREUH# ELECTRIC UNIT HEATER NUMBER
GM GAS METER
THERMOSTAT
2 HOUR RATED FIRE WALL
INDICATES TO BE DEMOLISHED
T
NOT TO SCALE4 EXHAUST FAN MOUNTING DETAIL
NOT TO SCALE2 EXHAUST FAN CONTROL DETAIL
M
LOUVER ASSCHEDULED
1/2" MESHSCREEN
MOTORIZEDDAMPER; CONTROLAS SPECIFIED INDRAWINGS
WALL; VERIFYCONSTRUCTION
MOUNT TO WALL PERMANUFACTURER'SINSTRUCTIONS
NOT TO SCALE5 INTAKE LOUVER WITH MOTORIZED DAMPER DETAIL
M
120V MOTOROPERATED INTAKEDAMPER
INTAKE LOUVER
MECHANICAL DEMOLITION NOTES1. THE MECHANICAL CONTRACTOR SHALL REVIEW THE DRAWINGS AND SPECIFICATIONS
FOR DEMOLITION REQUIREMENTS AND LAYOUT HIS WORK IN A COMPATIBLE ANDCOMPLEMENTARY MANNER. REMOVE ALL EQUIPMENT, DUCTWORK, SUPPORTS,CONTROLS, ACCESSORIES, ETC..., AND MECHANICAL ITEMS MADE OBSOLETE BY THESEALTERATIONS AS SHOWN IN THE MECHANICAL DRAWINGS. ALL ITEMS TO BE REMOVEDOR MODIFIED MAY NOT BE SHOWN, HOWEVER, THIS CONTRACTOR SHALL REMOVE ANYMECHANICAL WORK AS REQUIRED BY THE CONSTRUCTION.
2. PREPARE A DEMOLITION PLAN AND SUBMIT PROPOSED DEMOLITION, AND REMOVALPROCEDURES FOR APPROVAL BEFORE WORK IS STARTED. PLAN SHALL BE APPROVEDBY CONTRACTING OFFICER PRIOR TO WORK BEGINNING. DO NOT BEGIN DEMOLITIONUNTIL AUTHORIZATION IS RECEIVED FROM THE CONTRACTING OFFICER.
3. BEFORE BEGINNING ANY DEMOLITION WORK, SURVEY THE SITE AND EXAMINE THEDRAWINGS AND SPECIFICATIONS TO DETERMINE THE EXTENT OF THE WORK. RECORDEXISTING CONDITIONS IN THE PRESENCE OF THE CONTRACTING OFFICER SHOWING THECONDITION OF STRUCTURES AND OTHER FACILITIES ADJACENT TO AREAS OFALTERATION OR REMOVAL. PHOTOGRAPHS SIZED 4 INCH WILL BE ACCEPTABLE AS ARECORD OF EXISTING CONDITIONS. INCLUDE IN THE RECORD THE ELEVATION OF THETOP OF FOUNDATION WALLS, FINISH FLOOR ELEVATIONS, POSSIBLE CONFLICTINGELECTRICAL CONDUITS, PLUMBING LINES, ALARMS SYSTEMS, THE LOCATION ANDEXTENT OF EXISTING CRACKS AND OTHER DAMAGE AND DESCRIPTION OF SURFACECONDITIONS THAT EXIST PRIOR TO BEFORE STARTING WORK. IT IS THE CONTRACTOR'SRESPONSIBILITY TO VERIFY AND DOCUMENT ALL REQUIRED OUTAGES WHICH WILL BEREQUIRED DURING THE COURSE OF WORK, AND TO NOTE THESE OUTAGES ON THERECORD DOCUMENT. SUBMIT SURVEY RESULTS.
4. EXCEPT FOR SALVAGED ITEMS, AND FOR MATERIALS OR EQUIPMENT SCHEDULED FORSALVAGE, ALL MATERIALS AND EQUIPMENT REMOVED AND NOT REUSED OR SALVAGED,SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROMGOVERNMENT PROPERTY. TITLE TO MATERIALS RESULTING FROM DEMOLITION ANDDECONSTRUCTION, AND MATERIALS AND EQUIPMENT TO BE REMOVED, IS VESTED INTHE CONTRACTOR UPON APPROVAL BY THE CONTRACTING OFFICER OF THECONTRACTOR'S DEMOLITION, DECONSTRUCTION, AND REMOVAL PROCEDURES, ANDAUTHORIZATION BY THE CONTRACTING OFFICER TO BEGIN DEMOLITION ANDDECONSTRUCTION. THE GOVERNMENT WILL NOT BE RESPONSIBLE FOR THE CONDITIONOR LOSS OF, OR DAMAGE TO, SUCH PROPERTY AFTER CONTRACT AWARD. SHOWINGFOR SALE OR SELLING MATERIALS AND EQUIPMENT ON SITE IS PROHIBITED.
5. THESE DRAWINGS ARE COMPILED BY THE ENGINEER FROM THE OWNER'S RECORDDRAWINGS AND LIMITED FIELD VERIFICATION OF EXISTING CONDITIONS FOR THEPURPOSE OF INDICATING THE WORK REQUIRED AND ARE BELIEVED TO BE CORRECT.NOTWITHSTANDING, THE CONTRACTOR SHALL VERIFY ALL DUCTWORK, EQUIPMENTLOCATIONS, DIMENSIONS AND ALL FIELD CONDITIONS AFFECTING HIS WORK.
6. WHERE MECHANICAL SYSTEMS PASS THROUGH THE DEMOLITION AREAS TO SERVEOTHER PORTIONS OF THE PREMISES, THEY SHALL REMAIN OR BE SUITABLY RELOCATEDAND THE SYSTEM RESTORED TO NORMAL OPERATION. ADVISE THE CONTRACTINGOFFICER IMMEDIATELY IF SUCH CONDITIONS ARE UNCOVERED BEFORE PROCEEDINGWITH ADDITIONAL WORK.
7. DO NOT INTERRUPT EXISTING UTILITIES SERVING OCCUPIED OR USED FACILITIES,EXCEPT WHEN AUTHORIZED IN WRITING BY THE CONTRACTING OFFICER. DO NOTINTERRUPT EXISTING UTILITIES SERVING FACILITIES OCCUPIED AND USED BY THEGOVERNMENT EXCEPT WHEN APPROVED IN WRITING AND THEN ONLY AFTERTEMPORARY UTILITY SERVICES HAVE BEEN APPROVED AND PROVIDED. DO NOT BEGINDEMOLITION OR DECONSTRUCTION WORK UNTIL ALL UTILITY DISCONNECTIONS HAVEBEEN MADE. SHUT OFF AND CAP UTILITIES FOR FUTURE USE, AS INDICATED.TEMPORARY SERVICES INCLUDING BUILDING HEAT AND HEATING OF DOMESTIC WATERSHALL BE REQUIRED WHEN ANY INTERRUPTION OF SUCH SERVICES EXCEEDS 12 HOURSEXCEPT WHEN AUTHORIZED IN WRITING BY THE CONTRACTOR OFFICER.
1. SCOPE OF WORK: THESE DRAWINGS AND ACCOMPANYING SPECIFICATIONS DESCRIBETHE SCOPE OF WORK REQUIRED FOR PROJECT MECHANICAL HEATING, VENTILATINGAND AIR CONDITIONING SYSTEMS. CONTRACTOR SHALL PROVIDE ALL LABOR ANDMATERIAL REQUIRED FOR COMPLETE, FULLY FUNCTIONING MECHANICAL SYSTEMSCOMPLYING WITH THE INTENT OF THE DRAWINGS AND SPECIFICATIONS.
2. DRAWINGS: DRAWINGS ARE DIAGRAMMATIC AND MAY NOT COMPLETELY DESCRIBEEVERY DETAIL OF THE INSTALLATION. HOWEVER, CONTRACTOR IS RESPONSIBLE FORFURNISHING COMPLETE SYSTEMS INCLUDING ALL REQUIRED EQUIPMENT ANDACCESSORIES TO OBTAIN FULLY FUNCTIONING HVAC SYSTEMS.
3. MANUFACTURER'S RECOMMENDATIONS - INSTALL ALL EQUIPMENT IN STRICTACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
4. WORKMANSHIP - UTILIZE SKILLED MECHANICS TO OBTAIN A HIGH QUALITYPROFESSIONAL FINISH INSTALLATION WHEN COMPLETED. WORK OF UNACCEPTABLEQUALITY SHALL BE REMOVED AND REWORKED AT NO ADDITIONAL COST. CONTRACTINGOFFICER SHALL BE THE JUDGE OF WORKMANSHIP AND THEIR OPINION WILL BE FINAL. INADDITION, ANY EXISTING CONSTRUCTION DAMAGED BY THE CONTRACTOR SHALL BEREPAIRED OR REPLACED TO THE SATISFACTION OF THE CONTRACTING OFFICER BY THECONTRACTOR AT NO ADDITIONAL COST.
5. SUPERVISION: PROVIDE SKILLED SUPERINTENDENTS TO SUPERVISE THE WORK FROMTHE BEGINNING TO COMPLETION AND FINAL INSPECTION.
6. PROGRESS OF WORK: PERFORM WORK IN ACCORDANCE WITH SCHEDULE ANDREQUIREMENTS OF THE OWNER. UNDER NO CIRCUMSTANCES SHALL THIS CONTRACTORDELAY THE OVERALL PROJECT SCHEDULE.
7. COORDINATION: COORDINATE MECHANICAL WORK WITH THE WORK OF OTHER TRADES.LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE UNLESS SPECIFICALLYDIMENSIONED. LAYOUT MECHANICAL WORK SO AS NOT TO INTERFERE WITH THE WORKOF OTHER TRADES. VERIFY ACTUAL BUILDING STRUCTURE PRIOR TO DUCT FABRICATIONAND ADJUST ARRANGEMENT AS REQUIRED. INCLUDE ALL OFFSETS IN DUCTS, FITTINGS,PIPING, ETC. AS REQUIRED TO PROPERLY INSTALL EQUIPMENT.
8. EQUIPMENT LOCATIONS: DETERMINE EXACT EQUIPMENT AND MATERIALS LOCATIONSTO PROVIDE BEST ARRANGEMENT AND TO FACILITATE PROPER MAINTENANCE ANDSERVICING OF EQUIPMENT.
9. LISTING AND LABELING: ALL EQUIPMENT SHALL BE LABELED OR LISTED BY UL OR OTHERAPPROVED TESTING AGENCY WHERE REQUIRED.
10.CLEANUP: REMOVE ALL DEBRIS GENERATED IN THE ACCOMPLISHMENT OF WORKUNDER THIS PROJECT. CLEAN, REPLACE OR REPAIR ALL SURFACES SOILED ORDAMAGED DURING THE COURSE OF THE WORK. REMOVE DEBRIS DAILY SO TO MAINTAINSAFE WORKING CONDITIONS.
11.DEMOLISH EXISTING EQUIPMENT PADS AS REQUIRED TO ACCOMMODATE NEWEQUIPMENT LAYOUT.
MECHANICAL GENERAL NOTES
NOTE: SEE NATURAL GAS USAGE SCHEDULE FORQUANTITY USED BY FACILITY
GAS COMPANY TO CONNECT TOPLUG VALVE
SWING JOINT BYCONTRACTOR
FINISHED GRADE
MAGNETIC WARNING ANDIDENTIFICATION TAPE BY GAS COMPANY
GAS METER BY GAS COMPANY
ANODELESS RISER BY GAS COMPANYPOLYETHYLENE PIPING BY GASCOMPANY
PLUG VALVE BY GAS COMPANY
PLUGGED TEE W/ BUSHING AND 3/8"PLUG BY GAS COMPANY
INSULATING UNION BY GAS COMPANY
GAS PRESSURE REGULATOR BY GASCOMPANY
TEE W/ BUSHING AND 3/8" PLUG BY GASCOMPANY
LOCKOUT TYPE PLUGVALVE
~
AGA APPROVED GASVALVE
PRESSUREREGULATOR
PRESSURE PORT
GAS PIPING
DIRT LEG AGA APPROVED GAS VALVE
AGA APPROVED FLEXIBLE CONNECTOR
NOT TO SCALE6 GAS METER DETAIL
NOT TO SCALE7 GAS APPLIANCE CONNECTION DETAIL
uu
HANGERS ATTACHTO FRONT AND REAROF UNIT WITH #10 X1/2" SCREWS
UNI-STRUT
3/8"THREADEDROD
NUT &WASHERS ONBOTH SIDESOF BRACKET
DEMOLITION KEYED NOTESDEMOLISH AND DISPOSE OF GAS UNIT HEATERS, ASSOCIATED CONTROLS, PIPING AND ROOF VENTS.
DEMOLISH AND DISPOSE OF EXISTING FURNACE, ASSOCIATED DUCTWORK, DIFFUSERS, CONTROLS, VENTPIPING AND ROOF VENTS.
DEMOLISH AND DISPOSE OF EXISTING AIR COMPRESSOR AND ASSOCIATED PIPING AND CONTROLS INENTIRETY.
DEMOLISH AND DISPOSE OF EXHAUST FAN AND EXHAUST DUCTWORK INCLUDING EXISTING ROOF VENTS.
1
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266
www.cbhfengineers.com
cCopyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
1/8" = 1'-0" 0 8' 16'4'1 DEMOLITION FLOOR PLAN
PLANNORTH
2
3
4
4
1 1 1
11
1
2
3
tt
tt
tt
tt
tt
tt
tt
tt
tt
EUH1
GUH1 GUH2 GUH3
GUH4
GM
PV01
PV02
PV03
PV04
L1 L2 L3 L4
NG NG NG NG NG NG NG NG NG NG
NG
NG
NG
NG
NG
~
T1/2" 1/2" 1/2"
1/2"
GAS SERVICE
1/2"
1/2"
1/2"
1/2"
TT
T
CONSTRUCTION KEYED NOTESSUSPEND ELECTRIC UNIT HEATER FROM STRUCTURE ABOVE WHILE MAINTAINING MANUFACTURESRECOMMENDED CLEARANCES.
PROVIDE SIDE WALL POWER VENTILATORS AS SCHEDULED, COORDINATE MOUNTING HEIGHT WITHARCHITECTURAL ELEVATIONS.
PROVIDE INTAKE LOUVER WITH 120 VOLT MOTORIZED DAMPER INTERLOCKED TO FAN.
SUSPEND GAS UNIT HEATER FROM STRUCTURE ABOVE, ROUTE 4Ø INTAKE AND EXHAUST DUCT THROUGHEXTERIOR WALL.
1
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266
www.cbhfengineers.com
cCopyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
2
3
4
1/8" = 1'-0" 0 8' 16'4'1 HVAC PLAN
PLANNORTH
1
2
2
2
2
3 3 3
4
444
NG NGNG
GUH0130MBH
1/2"
GAS METER BYUTILITY
NG
NG
GUH0230MBH
1/2"1/2"
NG
GUH0330MBH
1/2"
1/2"
2PSI AGA APPROVED REGULATOR(120 MBH TOTAL LOAD) BY UTILITY
1/2"
1/2"
NOTE: GAS PIPING SIZED PER TABLE 402.4(5) OF THE 2018 NC FUEL GASCODE FOR A TOTAL DEVELOPED LENGTH OF 200 LINEAR FEET OF SCH.40 PIPE, INLET PRESSURE OF 2 PSI AND A 1.0 IN WC PRESSURE DROP.
1/2" 1/2"
NG
GUH0430MBH
1/2"
1/2"
NG
1/2"
NOT TO SCALE2 GAS PIPING RISER DIAGRAM
3
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266
www.cbhfengineers.com
cCopyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
GAS LOAD SCHEDULEFIXTURE TAG DESCRIPTION BTUH RATING QUANTITY TOTALGUH1 GAS UNIT HEATER 30,000 1 30,000
GUH2 GAS UNIT HEATER 30,000 1 30,000
GUH3 GAS UNIT HEATER 30,000 1 30,000
GUH4 GAS UNIT HEATER 30,000 1 30,000
TOTAL LOAD 120,000
BUILDING SERVICE GAS PRESSURE 2 psi
LOUVER SCHEDULEDRAWING CODE TYPE FRAME DESCRIPTION MATERIAL LOUVER
DEPTHSIZE (Wx H)
SERVICE AIRFLOW(CFM)
PERFORMANCE RATINGS NOTES ACCESSORIESFREE AREA S.P. LOSS WATER PENETRATION
(IN.) (IN.) (SF) (IN.H20) (OZ./SF)
L1 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 6 12 x 12 INTAKE 100 0.30 0.02 0 1 A, B
L2 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 6 18 x 15 INTAKE 600 0.77 0.1 0 1 A, B
L3 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 6 18 x 15 INTAKE 500 0.77 0.1 0 1 A, B
L4 FIXED CHANNEL HORIZONTAL, DRAINABLE-BLADE ALUMINUM 6 24 x 20 INTAKE 1,200 1.52 0.1 0 1 A, B
NOTES: 1. REFER TO SPECIFICATION FOR FURTHER INFORMATION.ACCESSORIES: A. BIRD SCREENING (MATERIAL TO MATCH LOUVER MATERIAL).
B. PROVIDE 120 VOLT MOTORIZED DAMPER WITH END PROVING SWITCH.
POWER VENTILATOR SCHEDULEDRAWING CODE FAN TYPE SERVICE CAPACITIES ELECTRICAL SONES WEIGHT
(LBS.)NOTES ACCESSORIES
AIRFLOW(CFM)
ESP(IN. WG.)
DRIVEARRANGEMENT
FAN RPM MOTORRPM
MOTORTYPE
MOTORSIZE (HP)
V/PH/HZ FLA MOCP
PV01 AXIAL SIDEWALL FAN EXHAUST 100 0.25 DIRECT 758 1350 ECM 0.25 115/1/60 3.5 15 5 71 1,2 A,B,C,D,E
PV02 AXIAL SIDEWALL FAN EXHAUST 600 0.25 DIRECT 1209 1725 ECM 0.25 115/1/60 3.5 15 5.9 62 1,2 A,B,C,D,E
PV03 AXIAL SIDEWALL FAN EXHAUST 500 0.25 DIRECT 1157 1725 ECM 0.25 115/1/60 3.5 15 5.3 62 1,2 A,B,C,D,E
PV04 AXIAL SIDEWALL FAN EXHAUST 1,200 0.25 DIRECT 1256 1725 ECM 0.25 115/1/60 3.5 15 6.5 71 1,2 A,B,C,D,E
NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - FOR FURTHER INFORMATION.2. WALL MOUNTED.
ACCESSORIES: A. UNIT MOUNTED SPEED CONTROLLER.B. WEATHER HOOD, AUTO BACKDRAFT DAMPER AND BIRDSCREEN.C. ON/OFF SWITCH LOCATED PER ELECTRICAL PLANS.D. INTERLOCK TO OPEN LOUVER ON FAN START.E. ALUMINUM BLADE CONSTRUCTION.
ELECTRIC HEATER SCHEDULEDRAWING CODE DESCRIPTION ELECTRIC COIL SUPPLY AIR ELECTRICAL WEIGHT
(LBS)MOUNTINGHEIGHT(FT)
NOTES ACCESSORIESCAPACITY(KW)
STEPS TEMP RISE (F) POWER(V/PH/HZ)
FLA MOCPTYPE FAN DISCHARGE
EUH1 UNIT HEATER PROPELLER HORIZONTAL 3.0 1 27.0 240/1/60 12.5 - - 10 1 A,B
NOTES: 1. REFER TO SPECIFICATION SECTION 23 73 33 - FOR FURTHER INFORMATION.ACCESSORIES: A. FACTORY INSTALLED THERMOSTAT, OVERHEAT SWITCH AND FAN DELAY SWITCH.
B. WALL SURFACE MOUNT BRACKET
GAS-FIRED UNIT HEATER SCHEDULEDRAWING CODE FUEL TYPE GAS FLUE & MIN. AIRFLOW MOUNTING HEIGHT MOTOR VOLTAGE FLA MCA MOCP MAX. MTG. NOTES ACCESSORIES
FAN COMBUSTION / CONTROL VENTING INPUT (MBH) OUTPUT (MBH) EFF.(%) INTAKE (IN) (CFM) (FT) HP RPM (V/PH/HZ) (AMPS) (AMPS) (AMPS) HEIGHT (FT.)GUH01 NATURAL GAS PROPELLER ENCLOSED / SINGLE STAGE POWERED 30 25 83 4 370 10 1/20 1650 120/1/60 3.2 3.7 - 10 1,2 A,B,CGUH02 NATURAL GAS PROPELLER ENCLOSED / SINGLE STAGE POWERED 30 25 83 4 370 10 1/20 1650 120/1/60 3.2 3.7 - 10 1,2 A,B,CGUH03 NATURAL GAS PROPELLER ENCLOSED / SINGLE STAGE POWERED 30 25 83 4 370 10 1/20 1650 120/1/60 3.2 3.7 - 10 1,2 A,B,CGUH04 NATURAL GAS PROPELLER ENCLOSED / SINGLE STAGE POWERED 30 25 83 4 370 10 1/20 1650 120/1/60 3.2 3.7 - 10 1,2 A,B,CNOTES: 1. REFER TO SPECIFICATION SECTION 23 77 33 - FOR FURTHER INFORMATION.
2. VENT IN ACCORDANCE WITH BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS.ACCESSORIES: A. PROVIDE SINGLE STAGE THERMOSTAT AND AGA APROVED REGULATOR.
B. PROVIDE DOWNBLAST DISCHARGE VENT.C. PROVIDE WITH VERTICAL LOUVERS FOR 4-WAY DEFLECTION.
2246 Yaupon Drive
Wilmington, NC 28401
Phone: 910.791.4000
Fax: 910.791.5266
www.cbhfengineers.com
cCopyright 2019 CBHF Engineers, PLLC
Engineers, PLLC
NC# P-0506
DESCRIPTIONSYMBOL
2x4 LIGHT FIXTURE, RECESSED OR SURFACE MOUNTED
LETTER INDICATES FIXTURE TYPE (SEE FIXTURE SCHEDULE)
ELECTRICAL LEGEND
4FT LIGHT FIXTURE, SUSPENDED
LETTER INDICATES FIXTURE TYPE (SEE FIXTURE SCHEDULE)
WALL MOUNTED LIGHT FIXTURE
LETTER INDICATES FIXTURE TYPE (SEE FIXTURE SCHEDULE)
DESCRIPTIONSYMBOL
ELECTRICAL LEGEND
MANUAL MOTOR STARTER, ELECTRICAL CONTRACTOR SHALL COORDINATE POLES
AND SIZE WITH EQUIPMENT
## = AMPERAGE RATING WHEN INDICATED ON DRAWING
COMBINATION DATA/TELEPHONE OUTLET, MOUNTED 42" AFF UNLESS OTHERWISE NOTED.
WITH 4 DATA CONNECTIONS.
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, 360 DEGREE COVERAGE
OS
DISCONNECT SWITCH, FUSED, HEAVY DUTY, SIZE AS INDICATED ON DRAWINGS (SIZE AS
INDICATED IN THE EQUIPMENT CONNECTION SCHEDULE)
##A = DISCONNECT SIZE / # = NUMBER OF POLES / # = NEMA RATING,
/##AF = FUSE SIZE
30A/3/3R,
W/ 30AF
PANELBOARD, SURFACE OR RECESSED MOUNTED AS SHOWN. SIZE, RATINGS, AND
MOUNTING AS INDICATED ON PANEL SCHEDULE. CONTRACTOR IS RESPONSIBLE FOR
REQUIRED CLEARANCE IN FRONT OF ELECTRICAL PANEL. SEE NEC TABLE 110.26
WORKING SPACES FOR ADDITIONAL CLEARANCE CONDITIONS.
240/120V
CONDUIT, HOME RUN TO PANEL BOARD
METER
ELECTRICAL MOTOR
GROUND BUS, " CG" INDICATES CAMERA GROUND BAR, " TG" INDICATES
TELECOMMUNICATIONS GROUND BAR, " E" INDICATES ELECTRICAL GROUND BAR
POWER & SWITCH LEG
UNSWITCHED LEG
EX
E-XXX
DETAIL, SECTION OR
PLAN NUMBER
DRAWING SHEET PLAN,
DETAIL OR SECTION
APPEARS ON
ENLARGED PLAN
M
S
M ##
LP
LTG
MCB
MCC
MCP
MDP
MFR
MH
MLO
MTD
MTG
MTS
MV
N, NEUT
NA
NC
NEC
NIC
NL
NO
NTS
P
PA
PB
PF
PH, ɸPLC
PNL
PP
PT
PWR
RECPT, RCP
REQ'D
RGS
RM
RTU
SCR
SH
SM
SPEC
SS
SST
SW
SWBD
SWGR
TEL
TPS
TVSS
TYP
UGND
UH
UON
UTIL
V
VFD
W
WH
WP
XFMR
(X)
LIGHTING PANEL, LIGHT POLE
LIGHTING
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
MAIN DISTRIBUTION PANEL
MANUFACTURER
MANHOLE
MAIN LUGS ONLY
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE
NEUTRAL
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE
PUBLIC ADDRESS
PULL BOX, PUSH-BUTTON
POWER FACTOR
PHASE
PROGRAMMABLE LOGIC CONTROLLER
PANEL
POWER PANEL, POWER POLE
POTENTIAL TRANSFORMER
POWER
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL CONDUIT
ROOM
REMOTE TELEMETRY UNIT
DC MOTOR DRIVE
SHEET
SURFACE MOUNTED
SPECIFICATION
SELECTOR SWITCH
STAINLESS STEEL
SWITCH
SWITCHBOARD
SWITCH GEAR
TELEPHONE
TWISTED PAIR SHIELDED
TRANSIENT VOLTAGE SURGE SUPPRESSER
TYPICAL
UNDERGROUND
UNIT HEATER
UNLESS OTHERWISE NOTED
UTILITY
VOLTS
VARIABLE FREQUENCY DRIVE
WIRE, WATT
WATT-HOUR
WEATHERPROOF
TRANSFORMER
EXISTING
A, AMP
AFF
AFG
AHU
AIC
ATS
AWG
BOF
BRKR
C, CND
CAB
CAT
CL
CB
CCTV
CKT
CLG
CP
CR
CS
CV
CT
CU
EF
EMER
EMT
ENCL
EQUIP
EWC
EWH
EPRF
FA
FAAP
FACP
FBO
FLA
FLUOR
FLR
FWE
GEN
G, GND
GFCI
HH
HID
HOA
HP
HPF
HPS
HTR
HV
Hz
IMC
INCAND
JB
K
KCMIL
KVA
KW
KWH
AMPERE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
BOTTOM OF FIXTURE
BREAKER
CONDUIT
CABINET
CATALOG
CHLORINE
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
CONTROL PANEL
CONTROL RELAY, CORROSION RESISTANT
CONTROL SWITCH
CONTROL VALVE
CURRENT TRANSFORMER
COPPER
EXHAUST FAN
EMERGENCY
ELECTRICAL METALLIC TUBING
ENCLOSURE
EQUIPMENT
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXPLOSION PROOF
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FURNISHED BY OTHERS
FULL LOAD AMPS
FLUORESCENT
FLOOR
FURNISHED WITH EQUIPMENT
GENERATOR
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
HANDHOLE
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTO
HORSE POWER
HIGH POWER FACTOR
HIGH PRESSURE SODIUM
HEATER
HIGH VOLTAGE
HERTZ
INTERMEDIATE METALLIC CONDUIT
INCANDESCENT
JUNCTION BOX
THOUSAND
THOUSAND CIRCULAR MILLS
KILOVOLT AMPERE
KILOWATTS
KILOWATT-HOURS
TYPICAL ABBREVIATIONS:
FINISHED CEILING
FLOOR
DOOR
ABOVE COUNTER
RECEPTACLE/DATA
3"
TV
NOTE:
DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED ON PLANS.
BACK SPLASH
SS
S
M
STRIKE
SIDE
HINGE
SIDE
COUNTER TOP
S3
S
D
S
LIGHT SWITCH
/DIMMER
CABLE, VOICE/DATA,
DUPLEX & QUADRAPLEX
RECEPTACLES
GANG
SWITCHING
CABLE &
TV
OUTLET
MECHANICAL
CASETTE
CABLE & TV OUTLETRECEPTACLE FOR
TV OUTLET
CLOCK HANGER
RECEPTACLE
+##" +##"
WALL MOUNTED EXIT SIGN
ABOVE DOOR (MAX. MT. HT.
OF 80" ABOVE TOP OF DOOR)
NOT TO SCALE
1 ELECTRICAL DEVICES - MOUNTING HEIGHT DETAIL
6"
6"
16"
46"
72"
84"
80"
46"
EQ
.E
Q.
EQ.EQ.EQ.
EXIT
LOW BAY LED SUSPENDED FIXTURE
LETTER INDICATES FIXTURE TYPE (SEE FIXTURE SCHEDULE)
EXIT SIGN W/EMERGENCY LIGHTING UNIT, WALL/END MOUNTED, ARROW INDICATES
DIRECTION.
INDICATES FIXTURE TYPE (SEE FIXTURE SCHEDULE)
EX
E-XXX
3-WAY SWITCH, SINGLE POLE 120/277 VAC, 20A, MOUNTED AT 46" AFF UNLESS OTHERWISE
NOTED
S3
SOLID STATE DIMMER SWITCH
S
D
RECEPTACLE, QUADPLEX, 120VAC, 20A, MOUNTED 6" ABOVE COUNTER TOP OR BACK SPLASH.
+##" - INDICATES MOUNTING HEIGHT OF DEVICE IN INCHES AFF (IF GIVEN) (SEE
ELECTRICAL MOUNTING HEIGHT DETAIL)
RECEPTACLE, DUPLEX, 120VAC, 20A, MOUNTED 6" ABOVE COUNTER TOP OR BACK SPLASH.
+##" - INDICATES MOUNTING HEIGHT OF DEVICE IN INCHES AFF (IF GIVEN) (SEE ELECTRICAL
MOUNTING HEIGHT DETAIL)
HATCHING INDICATES ITEMS TO BE DEMOLISHED. REMOVE DEVICE, EQUIPMENT,
FIXTURE INDICATED, CIRCUIT, AND CONDUIT BACK TO SOURCE UNLESS OTHERWISE
NOTED.
EMERGENCY LIGHTING UNIT, 2-HEAD WITH BATTERY BACK-UP, WALL MOUNTED, "NOT
SWITCHED"
LETTER INDICATES FIXTURE TYPE (SEE FIXTURE SCHEDULE)
RECEPTACLE, DUPLEX, 120VAC, 20A, MOUNTED 16" AFF, UNLESS OTHERWISE NOTED. (SEE
ELECTRICAL MOUNTING HEIGHT DETAIL)
WP - LISTED WEATHER-RESISTANT TYPE DEVICE WITH WEATHERPROOF IN USE COVER
GFI - GROUND FAULT CIRCUIT INTERRUPTER TYPE, 120VAC, 20A, MOUNTED 24" AFF