Office: 22873121, 22875485 (() TeleFax: 22879664 Resi. : 23353749,23238013/4 No.3, Poorna Seshachar Lane, Chickpet Cross, BANGAWRE-560 053. Sub :- VIP Brand Rigid PVC conduits as per IS 9537 and in F.R.L.S. grade as per ASTM Standards Dear Sirs, We are pleased to introduce our selves as Manufacturersof 'VIP' brand rigid PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants / Contractors in all major projects of Bangalore. '.vIP' brand PVC pipes are tested in C.~R.I. and brand name is Registered vide Registration on 543440 dated 11.01.91. We enclose herewith the following for your kind information. 1. Company Profile 4. Trade Mark Reg. Certificate. 2. C.~R.I. Test Report. 5. Current Price List. 3. Test report on ER.L.S. 6. Catalogue. 'VIP' conduits are in mirror finish and having embossed printing of one feet Length at three places on each pipe in addition to a sticker and screen printing in order to have a distinct identity. Reference may please be made to any prominent consultant or contractor of Bangalore about the Consistencv of Oualitv and Consistencv of Supplv during last decade. We request you to kindly consider the approval/use of 'VIP' brand PVC Conduits in the projects being managed by you. Thanking you, Yours faithfully, For NATIONAL PIPE PRODUCTS, --It!I trawJ! HIRAWAT

Upload: voquynh

Post on 19-Apr-2018

218 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

Office: 22873121, 22875485(() TeleFax: 22879664

Resi. : 23353749,23238013/4

No.3, Poorna Seshachar Lane,Chickpet Cross, BANGAWRE-560 053.

Sub :- VIP Brand Rigid PVC conduits as per IS 9537and in F.R.L.S. grade as per ASTM Standards

Dear Sirs,

Weare pleased to introduceour selves as Manufacturersof 'VIP' brand rigidPVC conduits since 1990

'VIP' brand PVC pipes are recommended for use by most of the ElectricalConsultants / Contractors in all major projects of Bangalore.

'.vIP' brand PVC pipes are tested in C.~R.I. and brand name is Registeredvide Registration on 543440 dated 11.01.91.

We enclose herewith the following for your kind information.1. Company Profile 4. Trade Mark Reg. Certificate.2. C.~R.I. Test Report. 5. Current Price List.3. Test report on ER.L.S. 6. Catalogue.

'VIP' conduits are in mirror finish and having embossed printing of one feetLength at three places on each pipe in addition to a sticker and screen printingin order to have a distinct identity.

Reference may please be made to any prominent consultant or contractor ofBangalore about the Consistencv of Oualitv and Consistencv of Supplv duringlast decade.

We request you to kindly consider the approval/use of 'VIP' brand PVCConduits in the projects being managed by you.

Thanking you,

Yours faithfully,For NATIONAL PIPE PRODUCTS,

--It!I trawJ!

HIRAWAT

Page 2: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

Office: 22873121, 22875485(f) TeleFax: 22879664

Resi. : 23353749,23238013/4

No. 3, Poorna Seshachar Lane,Chickpet Cross, BANGAlDRE-560053.

COMPANY PROFILE

1. COMPANY NAME

2. PROPRIETOR

3. FACTORY ADDRESS

4. ACTIVITY

5. DATE OF INCORPORATION

6. REGISTERATIONS

7. BANKERS

8. TEST REPORT BY CPRI

9. SOURCE OF RAW MATERIALI. PVC RESIN

11 CHEMICALS

10. E-mail

NATIONAL PIPE PRODUCTSNo.3, P S Lane, Chickpet,Bangalore-560 053. .Phone:22873121,51222650Tclefax: 22879664, Mob. 31826383

Mr. Pradip Kumar Hirawat.

NATIONAL PIPE PRODUCTSR-t, KCG Industrial Estate65/2, Magadi Main Road,Bangalore -560 079.Phone: 23489740

Manufacturing of VIP Brand RigidPVC Conduits, Collars,Bends in Various Colours

March 1982.

S.S.I. 08/01/12287K.S.T 73618871, C.S.T. 73668874

BANK OF INDIA,No.tt, K.G. Road, Bangalore -.9.

Latest Test Report Dated 23-5-2003Test Report on FRLS Dt. 02-02-2000

a. RelianceIndustries Ltd. (Gujrat)b. Indian Petrochemical Corporation

Baroda, Gurjat.c. DCW Ltd. (TamilNadu)

Pondy Oxides Ltd. (Chennai)

na [email protected]

Page 3: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

-

~ ELECTRICALSELECTRICALENGINEERS,GOVT.LICENCEDCLASS'I' ELECTRICALCONTRACTORS

SPECIALISTSIN "SOFTWAREFACILITIESINTERNALI EXTERNALE.H.T.H.T.,L.T."& ALL TYPESOF ELECTRIFICATIONWORKS

TO WHOMSOEVER IT MAY CONCERN

We are very much convinced to put on record that we have been using 'VIP'

brand RIGID PVC CONDUITS since IToma decade and we are satisfied

with the consistency of quality and supply. We enclose a list of major

projects ITom different spheres where the VIP PVC Conduits have been used

in recent past manufactured by M/s.NATIONAL PIPE PRODUCTS,

BANGALORE.

ER ELECTRICALS

Head Office: 41. Mosque Complex. M.M. Road. FraserTown. Bangalore - 560 005

Tel:080-5483296. 5484982. 5483983. 5485396.5485418.5483993 Fax: 080-5484236E-mail: [email protected]/[email protected]/[email protected]

K.SJ. No. 0090133-7 C.SJ. No. 0095133-0 Dated: 10-04-95

Branch: 5-4-87/6. 1sfCross. ModiComplex. M.G. Road. Secunderabad - 500003. Mobile: 98490 13423APGSTNo. PJT/08/01/2247 CSTNo. PJT/08/01/2020 Dated: 17-02-1997

Page 4: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

~ ELECTRICALS

LIST OF PROJECTS WHERE VIP PVC CONDUITS HASBEEN USED

SL NO1

2

3

4

5

6

7

8

9

10

11

12

13

14

PROJECTMls.Motorola (I) Electronics Pvt. LtdSenate Corporate Office, PagingMessaging Systems,Bangalore &T.S.R.Towers, HyderabadMls. Cisco Systems India Pvt. Ltd -Sona Towers, Prestige Waterford,Divya Sree Chambers, BangaloreMls. Lucent Technologies (I) LtdKodihalli, ITPL, Raheja Towers and SitLab, BangaloreMls. Tata Information Systems LtdGolden Enclave, Golden Towers,Bangalore and TTL, HyderabadMls.Hewlett Packard ISO (P) LtdHP Keonics City and ITPL, BangaloreMls. mM Global Services (I) Pvt. LtdPrestige Towers, Golden Enclave,BangaloreMls.Sun Micro Systems India (P) LtdDivya Sree Chambers, BangaloreMls.Birla 3M

Raheja Paramount and Electronic CityBangaloreMls.Deutsche Software&Deutsche BankRaheja Towers, BangaloreMls.Philips Software CentreSterling Square, BangaloreMls. Samsung ElectronicsPrestige Meridian-II andMls. Samsung SoftwareInfantry Road, BangaloreMls.BFL Software LtdAditya Chambers, BangaloreMls.Metamor Global SolutionsPunjagutta, HyderabadMls.Sonata Software LtdAPS Trust Building, Bangalore

NAME OF CONSULTANTSMls. Power Design, Bangalore /Mls.Potential Service Consultants

(P) Ltd, Bangalore

Mls.Potential Service Consultants(P) Ltd, Bangalore

Mls.Potential ServiceConsultants

(P) Ltd, Bangalore

Mls. Power Design, Bangalore

Mls.Ace Consultants, Bangalore

Mls.Ace Consultants, Bangalore

Mls.Akash Consultants,Bangalore

Mls.Sripeksha ConsultancyServices,BangaloreMls.Potential Service Consultants(P) Ltd, BangaloreMls.Potential Service Consultants

Ltd, Bangalore

2

Page 5: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

~ ELECTRICALS

-2-

SL NO PROJECT NAME OF CONSULTANTS15 Mls.Intel Asia Electronics

Salapuria Chambers, Cubbon Road,Bangalore

16 M/s.Amsoft Information Services IndiaPvt. Ltd Mls.Power DesignThe Senate Building, Bangalore

17 M/s.GE Capital International ServicesKhanijaBhavan, Race Course Road, Mls.Ace Consultants, BangaloreBangalore

18 M/s.Genisys Integrated Systems IndiaPvt. Ltd Mls.Ace Consultants, BangaloreWhitefield,Bangalore

19 M/s. Oracle Software Ltd Mls. Power Design, BangaloreEmbassy Point, Infantry Road, Bangalore

20 M/s. Usha Mullapadi Cardiac Centre Mls.Potential Service ConsultantsHyderabad (P) Ltd, Bangalore

21 M/s. Digital Equipments (I) LtdKhanijaBhavan, Race Course Road, Mls.Ace Consultants, BangaloreBangalore

22 M/s. Mallya Apollo Hospital Mls.Sanalec Consultants,Bangalore Bangalore

23 M/s. India Builders Corporation Mls.Potential Service ConsultantsDiamond District, Platinum City, (P) Ltd, BangaloreBangalore

24 M/s. Prestige Estate and PropertiesPrestige Meridian-II, Prestige Towers, Mls.Potential Service ConsultantsPrestige Terminus-11,Prestige Acropolis, (P) Ltd, BangalorePrestige Poseidon, Bangalore

25 M/s. L & T Limited Mls.Procon Engineers, BangaloreSubramanyaArcade, Bangalore

26 M/s. Purvankara Projects Limited Mls.Power DesignPurvankara Park, Bangalore

27 M/s.Tata Housing Development Co. Ltd Mls.Potential Service ConsultantsMarathalli, Bangalore (P) Ltd, Bangalore

28 M/s.Asiatic Properties Limites Mls.Power Design, BangaloreSai Garden, Bangalore

29 M/s.Unitech Limited Mls.Potential Service ConsultantsHeritage Estate, Yelahanka, Bangalore (P) Ltd, Bangalore

Page 6: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

M 4ffitirrnn ~l£rtrirttls

Phones: 3369776/785 -3315709

(3 lines hunting)F~ :091-080-3312487e-mail: [email protected]

Govt. Licenced Class 1 Electrical Contractors & EngineersSpecialists in all types of H. T. & L. T. Electrical Installations

K. S.T. No.70103148 C. S.T. No.701531401 Dated: 11-10-83

UNIT No. 101, 'BRIGADE LINKS'No. 54/1, FIRST MAINSE S HADRIPURAMBANGALORE-560 020

LicenceNo.20 (Class 1)

Dt.21/06/2001

TO WHOMSOEVER IT MAY CONCERN

This is to confirm that we have been using V.LP. Brand PVC Conduits and accessoriesmanufactured by M/s. National Pipe Products, Bangalore - 53 for more than 8 years invarious projects in Bangalore and Hyderabad.

V.LP Brand PVC Conduits are approved by all -leading Electrical Consultants inBangalore and we have used these conduits in the following projects in the recent past.

M/s. National Pipe Products, have the reputation of delivering the material on time andwe are a satisfied customer.

for MICRON ELECTRICALS,

~ . ~, \\S.K.~RAMU,PARTNER

1. Oracle Software India Ltd., Hyderabad 1 Bangalore.2. Tata Lucent Technologies, Bangalore.

(Salapuria Towers)3. Shri Satya Sai Convention Centre, Bangalore.4. Huei Burdan India Pvt.Ltd., Bangalore5. Hewlett Packard,

(Golfview Homes), Bangalore.6. Wipro Ltd., Bangalore7. PES Institute Of Medica & Research

Centre Kuppam, (Andhra Pradesh).8. Times Of India,

(Office Building) Hyderabad9. Karnataka Breweries Ltd., Bangalore.10. Digital Equipments India Ltd., Bangalore

Yeshwanthpur,11. India Builders Corporation,

(Diamond Districut) Bangalore.12. Hcl Perot Systems (P) Ltd., Bangalore.13. Atria Hotel Bangalore14. Du - Parc Trinity Bangalore15. Eden - Au - Lac Bangalore

Page 7: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

-

CPRI

TEST REPORT

Central Power Research Institute\

\

(A Govt. of India Society~)P.B. No. 8066, Sadashivanagar S.P.O,

Prof. Sir. C.V.Raman Road,Bangalore - 560 080

Page 8: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

DOMESTIC ELECTRICAL APPLIANCES LABORATORYELECTRICAL APPLIANCES TECHNOLOGY DIVSION

CENTRAL POWER RESEARCH INSITUTESIR CV RAMAN ROAD, POST BOX NO. 8066, BANGALORE - 560080

PHONE: 080- 3601442,3602525,3602526 Extn: 2345, 2346 Fax No 080 -3601213,3602277

SHEET 1 OF 6

TEST REPORT

Test Report Number 026EATDDEA03S001 Dated: 23-05-2003

Name & Address of the client National pipe products,#3,P.S.Lane, Chickpet,Bangalore - 560053

Same as aboveName & Address of the Manufacturer

Particulars of sample testedCondition of the sample on ReceiptTypeDesignationSerial NumberNumber of Samples TestedDate(s) of test (s)CPRI Sample Code No

Rigid Plain Conduits of Insulating material (PVC)New25 mm " Heavy"Rigid Plain Conduits of Insulating material (PVC)

One batch of 6 lengths05-05-2003 to 23-05-2003EATDDEA03S001

Particulars of test ConductedTest in accordance withStandard/ SpecificationSampling PlanClient's requirementDeviations if any

As per Sheet 2 of 6

As per IS: 9537 (Part-3): 1983 & IS: 9537 (part 1): 1980Not Applic"able

Names of the witnessing personsClient's representativesOther than client's representativesTest Subcontracted with address of thelaboratory

None

Documents constituting this report (Inwords)Number of sheetsNumber of oscillogram/sNumber of graphsNumber of photosNumber of Test circuit DiagramsNumber of drawings

Six OnlyNil. "NilNilNilNil

1t~y(K MANOHARA)

(JOINT DIRECTOR)

Page 9: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

DOMESTIC ELECTRICAL APPLIANCES LABORATORYELECTRICAL APPLIANCES TECHNOLOGY DIVSION

CENTRALPOWERRESEARCHINSITUTE .

SIR CV RAMAN ROAD, POST BOX NO. 8066, BANGALORE - 560080PHONE: 080- 3601442,3602525,3602526 Extn: 2345, 2346 Fax No 080 -3601213,3602277

Test Report No.026EATDDEA03S001

Test requested: 1.2.3.4.5.6.7.8.9.10.11.

Test conducted:

Date 23-05-2003 SHEET 2 OF 6

TEST REPORT

ClassificationMarkingChecking of DimensionsConstructionBending testCompression testImpact testCollapse testResistance to heat.Resistance to burningElectrical Characteri~tics

1.2.3.4.5.6.7.8.9.10.

Classification

MarkingChecking of DimensionsConstructionBending testCompression testImpact testResistance to heat.Resistance to burningElectrical Characteristics

Note: Collapse Test at SI. No. 8 of Test requested not conducted since thefacilities are not available at present.

Page 10: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

DOMESTIC ELECTRICAL APPLIANCES LABORATORYELECTRICAL APPLIANCES TECHNOLOGY DIVSION

CENTRAL POWER RESEARCH INSITUTESIR Cv. RAMAN ROAD, POST BOX NO. 8066, BANGALORE - 560080

PHONE: 080- 3601442,3602525,3602526 Extn: 2345,2346 Fax No 080 -3601213,3602277

Test Report No. 026EATDDEA03S001

SI.1

TESTSNo. CONDUCTED

01 Classification.

02 I Marking.

Date 23-05-2003

TEST RESULTS

CLAUSE REFERANCEI SPECIFIEDREQUIREMENTS I CONDTIONS

Clause 5The conduits shall be classified as follows:-a) According to material:

i) Metal Conduits

ii) Insulating Conduitsiii) Composite Conduitsb) According to the method of Connection:

i) Threadable Conduits (Only for plainconduits)

ii) Non- threadable Conduits:a) Plain Conduitsb) Corrugated Conduits

c) According to mechanical properties:i) Conduits for very light mechanical Stresses,ii) Conduits for light mechanical stresses,iii) Conduits for medium mechanical Stresses,iv) Conduits for heavy mechanical stresses,

v) Conduits for very heavy mechanical stresses.

Clause 6Conduit of Insulating material shall be markedwith the following informations:~ Name of the manufacturer, trade -mark or

identification mark~ Nominal size of the conduitsc> Country of manufacture~ Information relating to classification$ BIS certification ma~Clause 6.3Markings shall be legible .and durable after thespecified test.

SHEET 3 OF 6

RESUL TSNALUESOST AINED

----

Insulating Conduit (pVC).-----

-----

1Rigid Plain Conduit-----

---------------

Conduits for heavyI

mechanical stresses

. J

"National Pipe Prodl!cts" (VIP)25 mm

Not marked.Extra thick.

Not marked.

Markings were legible after thetest

Page 11: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

. .DOMESTIC ELECTRICAL APPLIANCES LABORATORY

ELECTRICAL APPLIANCES TECHNOLOGY DIVSIONCENTRAL POWER RESEARCH INSITUTE

SIR CV RAMAN ROAD, POST BOX NO. 8066, BANGALORE - 560080PHONE: 080- 3601442, 3602525, 3602526 Extn: 2345, 2346 Fax No 080 -3601213, 3602277

Test Report No.026EATDDEA03S001

SI.I

TESTSNo. CONDUCTED

03 I Dimensions.

04 I Construction.

05 I Bending Test.

06 I Compressiontest.

Date 23-05-2003

TEST RESULTS

CLAUSE REFERANCEI SPECIFIEDREQUIREMENTS I CONDTIONS

Clause7The dimensionsof conduitsfor heavymechanicalstresses shall be as follows: .a) The inside diameter of the conduits shall not

be less than 20.6 mm

b) The out side diameter of the conduits shallnot be less than 24.6 mm.

c) The complete manufactured length shall notbe less than 3 metres.

Clause 8The inside and outside surfaces of conduit shallbe reasonably smooth & free from burrs, flash& similar defects, in addition, the edges overwhich the conductors or cables are likely tobe drawn shall not damage the cable orconductors.

Clause 9.2The samples of Conduit, whe'n subjected forbending test at room temperature and also at- 5 :t 2°C:a) It shall be possible to remove the bending aid

without damage to the sample after bendingrollers released,

b) There shall be no signs of cracks on thesample of conduit visible to normal or correctedvision without magnification after the test.

Clause 9.3a) The difference between the initial diameter and

the diameter of the flattened conduits when acompression force of 1250 N is still appliedshall not exceed 25 percent of the initial"diameter.

b) The difference between the initial diameter andthe diameter of the flattened sample of conduitmeasured after 1 minute removal ofcompression force of 1250 N shall not exceed10 percent of the initial diameter..

SHEET 4 OF 6

RESUL TS/V ALUESOST AINED

Measured Values:.Inside Diameter =20,71 mm

Outside Diameter = 24.91mm

Length = 3 metres

Complied(No defects were observed)

Complied.

No signs of cracks were visibleto normal vision on the samplesafter the test.

Complied.Measured value =20.07 percent I

Complied.Measured value = 4.86 percent

Page 12: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

... .DOMESTIC ELECTRICAL APPLIANCES LABORATORY

ELECTRICAL APPLIANCES TECHNOLOGY DIVSIONCENTRAL POWER RESEARCH INSITUTE

SIR CV RAMAN ROAD, POST BOX NO. 8066, BANGALORE - 560080PHONE: 080- 3601442, 3602525, 3602526 Extn: 2345, 2346 Fax No 080 -3601213, 3602277

Test Report No.026EATDDEA03S001

SI./

TESTSNo. CONDUCTED

07 I Impact test.

08 Resistance toheat.

09 I Resistance toburning.

10 I ElectricalCharacteristics.

Date 23-05-2003

TEST RESULTS

CLAUSE REFERANCEI SPECIFIEDREQUIREMENTS I CONDTIONS

Clause 9.4There shall be no sign of disintegration, neither shallthere be any crack visible to the naked eye in atleast nine of the twelve samples. when the samplesof conduits subiected for impact test as specified.

Clause 10Conduits shall be adequately resistance to heat.The impression diameter measured shall notexceed 2.0 mm, when the sample of conduitsubiected for "Ball pressure test" as specified.

Clause 11Non-flame propagating insulating conduit shall notignite or, if ignited not continue to burn, when thesource of ignition is removed. If the sample burns itshall do so slowly and the flame shall not spreadappreciably; any flame shall have died out in lessthan 30 seconds after removal of the burner.

Clause 12Insulating conduits shall have adequate electricalstrength and insulation resistance.

a) Electric strength:There shall be no breakdown or flashover occurswhen the sample of conduit was subjected forhigh voltage test by applying 2000 V AC for 15 I',

minutes between the electrodes as specified.b) Insulation resistance:

The insulation resistance measured shall notbe less than 100 meg ohms when the sample ofconduit subjected for measurement of insulationresistance on application of 500 V DC betweenthe electrodes for 1 minute as specified.

SHEET 5 OF 6

RESUL TSIV ALUESOST AINED

Visible cracks were observedin three samples.Nine samples withstood thespecified impact.

Measured value = 0.6 mm

The sample of conduit didburn. The flame did not spreadappreciably. The flame diedout within five seconds afterremoval of the burner

No flashover or breakdownoccurred.

II

'--1

Measured value = >20 Go.

Page 13: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

"..... DOMESTIC ELECTRICAL APPLIANCES LABORATORY

ELECTRICAL APPLIANCES TECHNOLOGY DIVSIONCENTRAL POWER RESEARCH INSITUTE

SIR CV RAMAN ROAD, POST BOX NO. 8066, BANGALORE - 560080PHONE: 080- 3601442,3602525,3602526 Extn: 2345, 2346 Fax No 080 -3601213,3602277

Test Report No.026EATDDEA03S001 D~te 23-05-2003 SHEET 6 OF 6

NOTE

a) The test results relate only to the item(s) tested.

b) Publication or reproduction of this report / certificate in any form other than bycomplete set of the whole report and in the language written, is not permitted withoutthe written consent of CPRI. .

c) Any correction / erasure invalidates this test report / certificate.

d) Any anomaly / discrepancy in this test report! certificate should be brought to ournoticewithin45 daysfromthedateof issue. ,

e) The verification of the sample drawings by CPRI is limited to dimensional checksonly wherever possible.

Page 14: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

CPRI

INSULATION DIVISIONFRLS LABORATORY Page 1 of 6

1

TEST REPORT

CC-6469 dated 02-02-2000Test Report No. &Date

2 Client ,his referenceand address

",

3 Manufacturer,and address

his reference:

4 Particulars of apparatus tested

DesignaNon(DescripNon/Name plate details)TypeIdentification NumberSI. No.

5 Date(s) of Test

6 No. of Samples tested

7 Particulars of tests conducted

8. Test in accordance withstandard/SpecificationClient's requirementDeviation if anyName of the witnessingPersonsClient'srepresentativesOther than Client'srepresentatives

9

10 Document constituting thisreport(lnwords) .

No. of pagesNo. of Oscillograms

Z~:~r;;;s () >LTestEngin*:.&f~~ WCU

M/s National Pipe ProductsNo.3, Poorna Seshachar LaneChickpet Cross,Banglore 560 053Ref: Nil dated 31-12-1999

M/s National Pipe ProductsR-3, KCG Industrial Estate63/2, Magadi Main Road,Bangalore 560 079RefNiI

VIP BRAND PVC PIPES

PVC pipes

NilCPRI Code No.: INS/FRLS/99/S 00010Nil

th and 8thJanuary 2000

One PVC pipe

Oxygen index test, Temperature index test,Halogen acid, Smoke index test, Flammabilitytest (ASTM D 635)

As per ASTM D 2863-1987; IEC 754 PART 11994; ASTM E 662 1982; ASTM D 635 1991NilNil

NilNil

SIXNilNilNil

/bn~J,- It?JointD~

Page 15: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

INSULATION DIVISIONFRLS LABORATORY Page 2 of 6

CPRI

TEST REPORT

Test Report No CC-6469 Date: 02-02-2000

Identification: CPRI Code No. INS/FRLS/99/ S 0010

TEST RESULTS

1. OXYGEN INDEX TEST

Reference SpecificationDescription of the material

ASTM-D-2863-1987.VIP BRANDPVCPIPES

No. of specimens tested Three.

TEST RESULTS

",

Sample dimensions Oxygen IndexSample number value at

Length 150 mm ambient temp 27Width Thickness degree C

1 6.61 mm 2.53 mm 34.0

2 0.59 mm 2.55 mm 34.0

3 6.57 mm 2.58 mm 34.0

Page 16: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

INSULATION DIVISION

FRLS LABORATORY Page 3 of 6

CPRI

TEST REPORT

Test Report No CC-6469 Date: 02-02-2000

Identification: CPRI Code No. INS/FRLS/99/ S 0010

2. TEMPERATUREINDEX TEST

Reference SpecificationDescription of the material

Generally as per ASTM-D-2863-1987.VIP BRAND PVC PIPES

No. of specimens tested Three.

TEST R~SUL TS

Result

...

Temperature index obtained by extrapolation method: Greater than 250 degree C

sPecr:1iUn~:C9cw .Test Enginee0

Sample dimensionsSample Temperature in Oxygen Index

Number Length 150 mm degree C valueWidth Thickness

1 6.59 mm 2.59 mm 50 33.2

2 6.57 mm 2.60 mm 75 32.6

3 6.60 mm 2.54 mm 100 31.3

Page 17: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

INSULATION DIVISIONFRLS LABORATORY Page 4 of 6

CPRITEST REPORT

Test Report No CC-6469 Date: 02-02-2000

3. SMOKE DENSITY TEST using NBS Chamber (Non-flammable mode)Identification: CPRI Code No. INS/FRLS/99/ S 0010Sample details: VIP BRAND PVC PIPESReference Specification: ASTM E 662-1983

No. of Pipes testedNo. of specimens tested

One.Three.

Operating conditions:

Radiometer readingFurnace temperatureChamber temperaturepre-conditioning temperature of thechamber.Chamber surfaceconditions

8.62 mV @ 2.5 W/sq.cm1085 deg.C.22 deg C.

32 deg C.Smooth & Clean (with no carbondepositions)

-------------------------------------------------------------------------------------------------------...----------------------RESULTS Average value of three

Samples------------------------------------------------------------------------------------------------------------------------------

Sample thickness (in mm)Minimum transmittance in percent(at the end of the test)Specific Optical density(as per table X2 of ASTM E 662)

DmaxDcorr.

Time to reach Ds 16 (in seconds)75% of transmittance)Clear beam reading (in percent)(After flushing out smokefrom the chamber)

__m ~_:;jj=-~----------------------------------------------------------------------Test EngineerJ

2.53

0.0%

396391

64 secs

92.5 %

Page 18: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

INSULATION DIVISIONFRLS LABORATORY Page 5 of 6

CPRI

TEST REPORT

Test Report No CC-6469 Date: 02-02-2000

Identification: CPRI Code No. INS/FRLS/99/ S 0010

4. HALOGEN ACID GAS GENERATION TEST:

Reference Specification IEC 754 part 1, 1994

Temperature during the test 800 deg. C

Duration of Test 20 minutes

Specified Amount ofHydrochloric Acid in mg/ gm

The HCllevel evolved shall notexceed 20 % by weight (200 mg/gm)

Observed Amount ofHydrochloric Acid in mg/ gm 217.9 mg/gm

200 mg/gm (maximum)

Page 19: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

,

INSULATION DIVISIONFRLS LABORATORY Page 6 of 6

CPRITEST REPORT

Test Report No CC-6469 Date: 02-02-2000

Identification: CPRICode No. INS/FRLS/99/ S 0010

5.0 FLAMMABILITYTESTTo determine the rate of burning and/or extent and time of burning of self supporting plastics in ahorizontal position

Reference SpecificationDescription of the materialNo. of samples tested

ASTM- D- 635- 1981.VIP BRAND PVC PIPETen

RESULTS

Sample dimensions: Length 125 mm, Width 12.5 mm, Average thickness 2.45 mm

Result :.

~erage extent of burning 22.23 mm

Test Engineer () nJ~WOA ~

Sample Time taken to reach Time taken to reach Extent of burningNumber 25 mm mark 100 mm mark (mm)

...

minutes seconds minutes seconds

1 Not applicable20.35

2 Not applicable22.48

3 Not applicable21.59

4 Not applicable22.12

Flame extinguishes

5 before reaching 25 Not applicable21.68

mm mark6 Not applicable

22.72

7 Not applicable23.12

8 Not applicable22.49

9 Not applicable22.78

-, 23.1410 Not applicable

Page 20: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

CPRI

INSULATION DIVISIONFRLS LABORATORY Page 1 of 2

TEST REPORT

1 Test Report No. & Date CC-6508 Dated 02-03-2000

2 Mls National Pipe ProductsNo.3, Poorna Seshachar LaneChickpet Cross,Banglore 560 053Ref: Nil dated 28.02.2000

Client ,his referenceand address

3 Mls National Pipe ProductsR-3, KCG Industrial Estate63/2, Magadi Main Road,Bangalore 560 079RefNil

Manufacturer,and address

his reference:

4 Particulars of apparatus tested VIP BRAND RIGID PVC CONDUIT

Designation(Description/Name plate details)TypeIdentification NumberSI. No.

PVC pipe

NilCPRI Code No.: INS/FRLS/2000/S00017Nil

5 291h Feb and 1si March 2000Date(s) of Test

6 No. of Samples tested One PVC pipe

7 Particulars of tests conducted Halogen acid determination test

8.

9

Test in accordance withstandard/SpecificationClient's requirementDeviation if anyName of the witnessingPersonsClient's representativesOther than Client'srepresentatives

NilNil

IEC 754 PART 1 -1994

NilNil

10 Document constituting thisreport(ln words)No. of pagesNo. of OscillogramsNo. of drawings

f\'J' ofgraphs

~I~~~~Test Engineer

TwoNilNilNil

~~ ---Joint Director

Page 21: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

INSULATION DIVISIONFRLS LABORATORY Page 2 of 2

CPRI

TEST REPORT

Test Report No CC-6508 Date: 02-03-2000

Identification: CPRI Code No. INS/F.RLS/2000/S 0017

1. HALOGEN ACID GAS GENERATION TEST:

Reference Specification IEC 754 part 1, 1994

Temperature during the test 800 deg. C

Duration of Test 20 minutes

Specified Amount ofHydrochloric Acid in mg/ gm

The HCllevel evolved shall notexceed 20 % by weight (200 mg/gm)

ObservedAmount ofHydrochloric Acid in mg/ gm 188.98 mg/gm

sp~

~'~ruRw~Test Engineerl

200 mg/gm (maximum)

Page 22: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

<-.~ <i":>J-t{1~ rJll"Q1?Ct~ C"l.I iet.>ri ~Center for T~sting And Eval':lation ofWoo.d Composites ~

. ~~,14 ~ ~ ~ 3tR "5I"fu&fUT~

~'l1"~q)

INDIAN PLYWOOD INDUSTRIES RESEARCH AND TRAINING INSTITtJTE.~,('Iimf~, ~~q;:r~<!>T~~) .. - ~I

(Autonomous Body of the Ministry of Envirorunent & Forests, Government of India) II~ ~(Il, I!:fiR~ n. 2273, ~ -&5,~ - 560022 .

PostBagNo. 2273,TunlkurRoad,Bangalorc- 560 022

TG/1273/Bio-153/2002-03TEST REPORT

One sample of VIP make rigid PVC electrical conduit of one meter length receivedtrom, Mls. National Pipe Products No. 3, Pooma Seshachar Lane, Chickpet Cross,Bangalore - 560 053 was tested for termite resistance test.

Ref: Let:,:':"No. nil, dated: 20.07.2002

~ ~

rpY. cZ:.,ook$udri'J<ro f;r~~:o

Uoint Direclor

~~):q ~rlfq~ ~~ -"1HDlANPLYWOODItJOUSTRIES

~T :rl~r:T I(r;f srr~m!!T 0;-:'01.'

RES~,;~J,I~ TO',1:11::3I.GTlTl'TE,.'( .,. :. r 1(. ")")"1., r T,-, .~..., 6 "( \. - - , J J ~ :1I "....

PQst nag tlo. 22/3. '1Lf,1KUCRoad.

. ~.:-;1' - 5.:) 0~1ElA~li.l.\L':;.1;:- bOOa2~

Note: Test results are relevant only to the material received for testing

grams. IPIR'.Ifax: 91-80-8396361

Phone: 8394341 Director8394231-32-33 Ext- 509 Coordinator-CENTEC

e.mall: [email protected]: hltp:/Iwww.lpirli.com

Sample Mark Termite Rcsistnnce Test1. One meter in

VIP No attacklength

Page 23: --It!ItrawJ! - VIP Pipevippipe.com/catalog/National_Pipe_Products.pdf · PVC conduits since 1990 'VIP' brand PVC pipes are recommended for use by most of the Electrical Consultants

cPll.O ~ \J11-q t!ci ,,!~icPrf ~Center for Testing And Evaluation of Wood Composites

'+il'<ct)~~ mfrT ~ 3tR ~lffUJ ~INDIAN PLYWOOD INDUSTRIES RESEARCH AND TRAINING INSTITUTE

('1mf mcPR"I ~ ~ CA" ~ 1f;T"{<Wffif.rcf;rlr)

(Autonomous Body of the Ministry of Envirorunent & Forests, Government of India)titR <trr~. 2273! Q"'1W{-as, ~ - 560 022

Post Bag No. 2273, Tumkur Road, BangaIore - 560 022

)

~ mRC2istcr Post

B.{No.TG/1273/Bio-153/2002-03 '-)19 (,~/Date: 24.01.2003

-wu.r/To, Mls. National Pipe ProductsNo. 3, Pooma Seshachar Lane,Chickpet Cross,Bangalore - 560 053

~~,Dear Sir,

~: ~~~~ISub: Test report for rigid PVC electrical conduit sample.

~: ~. 31TGCtiT~ ~ ............~. ~qft~~~ ... .........

Ref: 1. Your letter no.: nil Dated: 20.07.20022. This Institute's testing reference no.: TG/1273/Bio-153/2002-03

~ ~ "Cf;fCf)T~ -RIPlease refer to the above letter.

~ftq1t~~ I

Test report is enclosed.

~: "Ffilq:;

Encl. : ala

~,

~rs~fully, -

J-: J.~~ c.; >.1--}J)>', db~cJ. cJ. .xOC{Cl;'UC!

ugcrQf;:r~iT~ "

iJoint Director "',-";rr"ci\;q cmr.qG;:rW7f '

IHDIANPLYWOODINDUSTRIES

or~1j~Jr<t({<f >rf~~T!Jf(f"ertrrRESEARCH& TRAIIHtW INSTITUTE

qTi=cci'T cr. 2273, i11T~, .tt5',Post Bag No. 2273. 1 umkur Road..

ofrn'l, - j:i (I~2BANG/\LO:lE- GGC)022.

grams: IPIRTIfax: 9"1-80-8396361

Phone: 8394341 Director

"8394231-32-33 Ext. 509 Coordinator-CENTECe-mail: Iplrtl@glasbgO~.vsnl.nct.ln

web site: http://w\..iw.ipirti.com