  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    1/12

    Electric Utility GradeElectric Utility GradeElectric Utility Grade

    PACScladACScladACSclad Metalclad.Metalclad.Metalclad.

    Distribution Switchgearistribution Switchgear4160 Volts to 27 kV160 Volts to 27 kV60 kV BIL0 kV BIL

    95 kV BIL5 kV BIL110 kV BIL10 kV BILFor: Electric Utilities

    Wind GenerationIndustrialsDistribution

    Marine...etc.

    Including PACSafeACSafeACSafe Arc Resistant Switchgear

    61 Steamboat Road, Great Neck, New York 11024 U.S.A.Tel: 516-829-9060 Fax: 516-829-9557 E-mail: sales@pacsindustr ies.com Web: pacsindustr ies.com

    IEC ANSI

    Facilities in Great Neck, New York and Mount Vernon, Ohio

    Standard & Custom

    Since 1972 The Experienced Company

    50 Hertz or 60 Hertz

    125 kV BIL25 kV BILDrawout Switchgear

    To 6,000 Amperes

    ISO 9001-2000

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    2/12

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    PACS Industries, Inc., has been in business since 1972, and has concentrated on the manufacture ofMedium Voltage Metalclad Switchgear in the range of 2400 Volts, to 41 kV, and to Standards of IEEEC37.20.2 and IEC 298. Our 170,000 square foot factory is in Mount Vernon, Ohio.In the range of 2400 Volts to 15 kV (17.5 kV IEC), PACS will use circuit breaker elements manufacturedby G.E., Cutler-Hammer, Siemens, or other reputable companies. For 27 kV Class circuit breakers,

    PACS manufactures a proprietary series of drawout circuit breakers, utilizing Vacuum Interrupters , orSF6 Interrupters . Circuit breaker trucks and cells are built to the standards of IEEE C37.20.2, and in-clude all required ANSI C37.20.2 features such as metal shutters, automatic secondary plugs, auto-matic trip upon breaker movement in the cell, etc. Type Test data is available to the standards of IEEEC37.20.04, 06, 09 for circuit breakers, to C37.20.2 for distribution switchgear, C37.013 for generatorSwitchgear, and to C37.20.07 for Arc Resistant switchgear (as well as relevant I.E.C. Standards).Short circuit Type Tests are usually performed at KEMA. The PACS Laboratory includes a 230 kV BILImpulse generator, a 9,000 Amp Heat run facility, Partial Discharge Test Equipment, Hi-pots, Meggers,etc. Switchgear available as PACSafe Arc Resistant switchgear.Ground switches are available.PACS can provide streaming video services of switchgear being manufactured or tested, as an option.

    As an independent company, we respond much faster to your requests for proposal, service, information, design assistance and deliv-ery. We at PACS Industries, Inc., are proud to be able to design standard and special switchgear to suit a customers requirements. Weprovide designs and manufacturing methods that reflect the highest Electric Utility Grade switchgear. Change orders are pleasantlyand efficiently handled, and are usually integrated into production, without extending the promised delivery date. During all phases ofthe order, you can directly contact the PACS engineering department to discuss various issues.After-order service is as important to PACS personnel, as is before-order promises. We at PACS continually ask ourselves, Why shoulda customer purchase PACS products?...and we are continuously striving to develop new reasons for you, our customer, to do so.

    Why Specify PACS Switchgear?

    This catalog has combined in one issue,drawout metalclad switchgear from theoperating ranges of 2400 Volts, through27kV. Although the dielectric character-istics of these ratings vary between thevoltage classes (5 kV, 8.25 kv, 15 kV &27 kV), the dimensions, features andoperation have sufficient in common, tolist them together.

    Switchgear is available in two high(circuit breaker) construction to 2000Amps. Above 2000 Amps, there shouldbe only one circuit breaker per verticalcell. Drawout potential transformers canbe installed over a circuit breaker onlyup to 2000 Amps.

    About PACS

    Generator Circuit Breakers Available To IEEE C37.013

    Contact us for international sales and service support

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    3/12

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    Standards & Specifications

    This class of switchgear is used to control discreet increments of electric power, gen-erally at operating voltagesof 2400 Volts, through 26 kV. 50 or 60 Hertz. A typicallineup would include circuit breaker cubicles, and required auxiliary cubicles.Arranged for indoor or outdoor service. Each vertical cubicle is segregated from its

    adjoining vertical cubicle by 11 gauge sheet steel (3.0 mm) , and within vertical cubi-cles, each compartment is further segregated by 11 gauge sheet steel partitions. Allexterior surfaces are safe-touch, dead front.

    Standards: All ANSI switchgear conforms to IEEE C37.20.2, and circuit breakersconform to IEEE C37,20, 04, 06, & 09. IEC switchgear conforms to the standards ofIEC 298 and IEC 56.

    Metalclad swi tchgear (see Fig 1) consists of segregated :A. Circuit breaker compartments.B. Drawout circuit breakers.C. Potential transformer drawout compartments.D. Front door(s) containing required protective relays, meters, and control

    switches.E. Main bus bar duct within the switchgear.

    F. Rear connection cable or bus duct compartments.G. Required auxiliary cubicles.H. Optional Grounding (Earthing) Switches.

    Metalclad switchgear is f urther characterized by t he following:

    All live parts are enclosed within grounded metal compartments.

    The circuit breaker compartment includes grounded metal shutters in front of theprimary (high voltage) plug-in connection bushings. The shutter position is auto-matically operated by circuit breaker movement.

    The circuit breaker is mounted on a truck that is drawout. The truck may beconnected or disconnected through closed front doors, via a racking mechanism.Available are remote racking motors for operator safety.

    Stored energy operation.

    Interlocks are provided to insure safe circuit breaker operation, such as discharg-ing all springs when the breaker is moved within the cell, preventing a closedbreaker from being moved into or within the cell, etc.

    All bus bars are insulated. Copper, with silvered connection pads.

    The circuit breaker control circuit (secondary), is automatically connected ordisconnected, depending upon the circuit breaker position.

    Control circuits are segregated from high voltage circuits by metallic barriers,(except for short lengths of certain devices, as permitted in IEEE standards).

    Every circuit breaker has Disconnect, Test, and Connect positions, with visibleindication.

    The control cubicle includes all necessary relays, terminal blocks, etc..

    Current transformers include shorting terminal blocks.

    Control conductors are SIS type switchgear wire.

    Circuit breaker automatically grounded when racked into position.

    Altitude Correction Factors

    Description of PACScladACScladACSclad Metalclad Switchgear

    Altitude Altitude B.I.L. & P.FCorrection

    CurrentCorrection

    To 1000 m 3300 ft 1.00 1.00

    1800m 6000 ft 0.92 0.99

    3000m 10000 ft 0.80 0.96

    Ambient Temperature Correction

    Maximum Ambient Correction Factor

    55 0.88

    50 0.92

    40 1.00

    30 1.07

    15 (ISO) 1.18

    Correction factors may be interpolated linearly

    Background & Services:PACS Industries, Inc., was founded in 1972, and since then has enjoyed growth commensurate with its service to large industri-als , Gas Turbine OEM manufacturers, Contractors & Electric Utility companies. In addition to domestic business, PACS has asignificant foreign business especially in the Middle East, and the Pacific Rim. Our customer engineering and administrativeoffices are in Great Neck, NY. Our 170,000 square foot factory is in Mount Vernon, Ohio. It is a vertically integrated factory, in-cluding a metal fabricating shop, a Powder Coat paint facility, and ample indoor assembly space Our test laboratory includes anImpulse Generator to 250 kV BIL, a heat run facility to 9000 Amps, Partial Discharge testing facilities, etc. PACS field supervisionservices are available as contracted for. All drawings and documentation are by AutoCad and Promis-e programs. PACS draw-ings, bills-of-material, and instruction manuals constitute a complete record of equipment we build.

    Fig 1. Typical cross section of circuit breaker cubicle, with P.Tcompartment on top. Includes optional Grounding Switch, asrequired by I.E.C. standards.

    A

    B

    C

    D

    E

    F

    G

    H

    PACS Universal IEEE & IEC Switchgear

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    4/12

    to 15 kV Switchgear Detai

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: [email protected] web: pacsindustr ies.com

    A 1/4 x 2 CopperGrounding Bus iscarried through eachcubicle.

    PACS utilizes multifunction relays &controls manufactured by GE Multilin,ABB, Basler, Areva, Schweitzer, Sie-mens, etc. As required by customer.SCADA provisions or systems avail-able.

    15 & 27 kV

    Due to many similar physical construction features between 15 kV Class & 27 kV Class switchgear, we have identifiedcertain details that are available for all voltage classes in this bulletin with the mark

    15 & 27 kV

    PACScladmetalclad switchgear utilizes componentssuch as potential transformers, current transformers, etc., of

    the highest quality, conforming to the customers require-ments.Circuit breakers are provided with 4 Normally Open and 4Normally Closed auxiliary contacts as standard (MOC). Addi-tional contacts available. DC ratings are 10 Amps @ 125VDC.Cell contacts (TOC) are available as well. DC ratings are 10Amps @ 125 VDC.All circuit breakers are furnished with Through-Door (closeddoor) racking provisions from Disconnect to Connect posi-tions. Remote motorized racking is available. Manual tripprovisions are available on closed door.Interior cell lights and convenience receptacles are available.

    Following are recommendations regarding the selection ofdifferent BIL levels.

    95 kV BIL. Ideal for indoor, clean atmospheres.

    110 kV BIL. Ideal for outdoor use. Ideal for altitudesover 1000 meters (3300 feet) in order to maintain thesame BIL level as at lower altitudes. Also ideal for envi-ronmentally challenging atmospheres, or where cus-tomer wishes to maintain the 110 kV BIL requirementsof outdoor transformer & substations. Ideal for desertareas (as in the Middle East) with high salt atmosphereand high ambient temperatures.

    Typical 13.8 kV switchgear with two-high circuit breaker construction.

    Bottom breakers are available with

    either roll-in installation, or lift truck.

    Top located circuit breakers are

    installed via a lift truck.

    15 & 27 kV

    Remote Control Operators Available For

    Insertion and Withdrawal of Circuit Breakers.

    Typical Vacuum Circuit Breakers. To 15 kV. To 3500 Amps, 63 kA

    Grounding & Testing Accessories

    Grounding (earthing)fault-make switches.Manual or ElectricalInterlocked.

    Electrical or ManualGround & Test trucks.

    Ground Studs & Cables Available as Specified

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    5/12

    to 15 kV Switchgear Details

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    15 & 27 kV

    15 & 27 kV

    kV kV

    15 & 27 kV

    Rear View 2 High Front View. Breaker Top, PTs BottomView of Insulated Bus Bars

    Bus Duct Entry

    Typical Drawout PotentialTransformer Drawers.

    Fault-closing Grounding Switch interlockedwith circuit breaker in disconnect position.

    OPEN

    GROUNDED

    Negative SequenceCurrent Transformer.

    Typical Views of 15 kVVacuum Drawout

    Metalclad Switchgear.

    SF6 Circuit Breakers Available

    Arc Resistant Switchgear

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    6/12

    Vacuum Circuit Breaker Data

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    Continu-ous

    CurrentAmps(RMS)

    Maxi-mum

    Voltage

    V (kV)

    Operat-ing Volt-

    age

    V (kV)

    ObsoleteMVA

    Ratings

    MVA

    KFactor

    Sym-metrical

    Inter-ruptingRating

    kA RMS

    Momen-tary

    Close &Latch

    kA Peak

    BILCrest

    kV

    PowerFre-

    quencyWith-stand

    kV

    % DCInter-

    ruptingCurrent

    kA

    RatedInter-

    ruptingTime

    Cy / ms

    ShortTime

    CurrentWith-stand3 Sec

    1200 Amps2000 Amps3000 Amps

    4760 V(3300V)

    2400VTo 4160V

    250 1.0 36(10 kV)

    97 60(40 kV)

    19 50 3 / 505 / 87

    36

    1200 Amps2000 Amps3000 Amps

    4760 V 2400VTo 4160V

    350 1.0 50 135 60 19 50 3 / 505 / 87

    50

    1200 Amps2000 Amps3000 Amps

    4760 V 2400VTo 4160V

    500 1.0 63 170 60 19 50 3 / 505 / 87

    63

    1200 Amps2000 Amps3000 Amps

    15.0 kV(17.5 kV)

    To13.8 kV

    500 1.0 25 97 95 kVOr

    110 kV

    36 ANSI(38 IEC)

    50 3 / 505 / 87

    25

    1200 Amps2000 Amps3000 Amps

    15.0 kV(17.5 kV)

    To13.8 kV

    750 1.0 36 135 95 kVOr

    110 kV

    36 ANSI(38 IEC)

    50 3 / 505 / 87

    36

    1200 Amps2000 Amps3000 Amps

    15.0 kV(17.5 kV)

    To13.8 kV

    1000

    1500

    1.0 50

    63

    135

    170

    95 kVOr

    110 kV

    36 ANSI(38 IEC)

    50 3 / 505 / 87

    50

    63

    HIGH CURRENT VACUUM CIRCUIT BREAKERS

    Normal width of all cubicles is 36 inches (914 mm), except for 4000 Amp Convection, 5000 Amp Convection & 6000 Amp Fan Cooled.

    Fan Cooled models utilize 2 sets of fans (one redundant) if requested.

    Interrupting current rating constant for all voltages less than the maximum voltage. MVA levels therefore decrease (MVA=A x V x 1.73).

    3 Cycle or 5 Cycle interrupting circuit breakers available. Contact us for back-to-back capacitor ratings.

    Maximum tripping delay is 2 seconds for all circuit breakers per IEEE/ANSI standards. Convection Cooling is natural cooling. Fan is forced cooling.

    5 kV to 15 kV Class. KA Rated Symmetrical Basis. (IEEE standards changed from MVA to KA . K factor is now 1.0 )

    IEEE/ANSI C37.20.06 (2000) (I.E.C. Data)

    1200 Amps2000 Amps3000 Amps

    8250 V To7200 V

    500 1.0 41 115 95 kV 95 50 5/87 41

    3500 AmpsConvection

    15.0 kV(17.5 kV)

    To13.8 kV

    1.0 36-63kA

    82-160kA

    95 kV 36 ANSI(38 IEC)

    50 3 / 505 / 87

    50-63kA

    4000 AmpsFan Cooled

    15.0 kV(17.5 kV)

    To13.8 kV

    1.0 36-63kA

    82-160kA

    95 kV 36 ANSI(38 IEC)

    50 3 / 505 / 87

    50-63kA

    4000 AmpsConvection

    15.0 kV(17.5 kV)

    To13.8 kV

    1.0

    5000 AmpsConvection

    15.0 kV(17.5 kV)

    To13.8 kV

    1.0

    5600 AmpsConv/Fan

    15.0 kV(17.5 kV)

    To13.8 kV

    1.0

    6000 AmpsConv/Fan

    15.0 kV(17.5 kV)

    To13.8 kV

    1.0

    40 kA50 kA63 kA

    108 kA132 kA160kA

    95 kV110 kV

    IEEE36 kV

    (IEC38 kV)

    50 5/87 IEEE36 kV

    (IEC38 kV)

    Numbers in (RED PARENTHESIS) are IEC 56 ratings. IEC are 50 Hz.

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    7/12

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    Dimensions & Data

    95kV BIL 15 kVWidth 36

    110 kV BIL 15 kVWidth 36

    125 kV BIL 27 kVWidth 36

    Top View

    Front View

    DEPTH95 kV BIL 95110 kV BIL 95 125 kV BIL 110

    For width see data to the left.

    HEIGHT:95 kV BIL . 95110 kV BIL. 95125 kV BIL 95

    Dimensions are for estimating purposes only. See PACS foractual dimensions of your requirements.

    1200 Amp C.B. & Main Bus 650 Watts

    2000 Amp C.B. & Main Bus 850 Watts

    2500 Amp C.B. & Main Bus 1100 Watts

    3000 Amp C.B. & Main Bus 1800 Watts

    4000 Amp C.B. & Main Bus 2200 Watts

    Estimated Heat Loss per CubicleMain Bus & 1 Breaker Per Cubicle.

    Bus Bar Size & Capacity.Based upon 65 deg C Heat Rise Over a 40 deg C Ambient.

    1200 Amps 1 each 1/4 x 4 Copper per ph.

    2000 Amps 1 each 1/2 x 6 Copper per ph.

    2500 & 3000 Amps 2 each 1/2 x 6 Copper per ph.

    4000 Amps Based upon arrangement

    A) Sheetmetal Finish Specifications

    High Voltage Cables

    Circuit Breaker

    Sectional View

    Interior switchgear sheet metal may be finished either in agalvanized finish, or a coated finish as described below.

    PACS utilizes a Powder Coat finish to coat sheet metal.This is a heat cured process, utilizing a Polyester powderthat is sprayed on, and then is cured at a high tempera-ture to create a virtually indestructible finish, that hasbeen tested to exceed 1000 hours of salt spray.

    Following is a bri ef procedure summary:A) Sheetmetal is cleaned and blemishes are removed.B) An Alkaline caustic cleaner is used to treat the metal,

    prior to preparing the Powder Coat process.C) The metal panels are preheated to a temperature of 450

    degrees F.D) The metal panel passes by conveyor to the Polyester

    powder spray-on area.E) The coated metal is conveyed to a curing oven at 450

    degrees F, and then to a cool-down area.F) Standard paint colors are ANSI 61 (grey) and Desert

    Tan. Other colors are available.G) Sheetmetal available in steel, aluminum, or stainless.

    Data For Estimating Purposes And Subject To Project Requirements

    Top Compartment.2 High.Auxiliary, PTs orCircuit Breaker

    To 15 kV also in 26

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    8/12

    27 kV Switchgear Details

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    1200 Amps2000 Amps3000 Amps

    27 kV 24 kV 1.0 25 68 125 50 50 5 / 87 25

    1200 Amps2000 Amps3000 Amps

    27 kV 24 kV 1.0 31.5 85 125 50 50 5 / 87 31.5

    1200 Amps2000 Amps3000 Amps

    27 kV 24 kV 1.0 40 108 125 50 50 5 / 87 40

    27 kv Class. 125 kV BIL (See our 38 kV bulletin for 150 kV to 200 kV BIL)

    Continu-ous

    Current

    Amps

    (RMS)

    Maxi-mum

    Voltage

    V (kV)

    Operat-ing Volt-

    age

    V (kV)

    KFactor

    Symmet-ricalInter-

    ruptingRating

    kA RMS

    Momen-tary

    Close &Latch

    kA Peak

    BILCrest

    kV

    PowerFre-

    quencyWith-stand

    kV

    % DCInter-

    ruptingCurrent

    RatedInter-

    ruptingTime

    Cy / ms

    ShortTime

    CurrentWith-stand

    3 Sec

    Typical 27 kV Drawout CircuitBreaker. Includes Automaticallycoupled Primary (M.V.) and Secon-dary connections

    27 kV Drawout cell with shuttersin closed position. Shutters auto-matically open as circuit breakeris inserted. Can be padlocked.

    View of same cell on left, withshutters opened, revealing cur-rent transformers installed overprimary bushings.

    Rear view of assembled 27 kVcircuit breaker. Note thatprimary (MV) connections areround tulips .

    15 & 27 kV

    kV kV

    15 & 27 kV

    kV kV

    Due to many similar physical construction features between 15 kV Class & 27 kV Class switchgear, we have identifiedcertain details marked are available for both ratings.

    15 kV and 27 kV circuit breakerracked through available closed door.

    View of 27 kV primary bushingsand current transformers.

    Drawout Potential Trans-formers over circuit breaker.

    15 V & 27 kV

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    9/12

    27 kV Switchgear Details

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    Protective Relay Panels

    Typical Views of 27 kV Switchgear.Available with Vacuum or SF6

    Circuit Breakers.

    Protective Relay Panels for Switchgear orSubstation service. Available in variousenclosures such as Simplex, Duplex,Walk-in, & buildings. Protective Relaybrands of customers choice. SCADA &PLCs available.

    Lineup in construction

    NEMA 3R Non-Walk-In

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    10/12

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    Power & Control Centers

    PACS manufactures all Power & Control Centers (PCC) inour 170,000 Square Foot factory. As such, we can inte-

    grate allPACSclad switchgear into the required PCC,under one roof. The PACS assembly areas can accommo-date over 30 - 36 x 12 buildings simultaneously. For largerswitchgear buildings, we have accommodated 100 x 30buildings with ease. Buildings can be equipped with climatesystems, can be pressurized, and can include ancillary roomsfor batteries, controls, etc. Buildings that need to be split forover-the-road transport, are first assembled completely, priorto disassembly for shipment. Customers are welcome toobserve.

    The PACS manufacturing process inc ludes:Structural Underframes:

    The PACS structural welding shop includes 140 ofwelding jigs. Underframe skids are welded on these jigsby certified welders. Average beam size would be 10 to

    15 depending on application. A steel plate floor is thenwelded to the skid.

    After welding is complete, the skid is moved to an adja-cent sand blasting room, then to an undercoating room,and then to the shop floor.

    Wall & Roof Types:PACS manufactures different wall & roof types to accommo-date various PCC applications.

    Interlocking Panel walls utilize 16 to 18 gauge exteriorwalls, and 16 to 18 gauge interior walls. Generally free-standing, self-framing, and thermally insulated.

    Shelter-Clad type, is like the traditional switchgearbuildings, fabricated of 11 gauge metal pans. May bethermally insulated or not. Integrated with switchgear

    cubicles. Monobloc panels are of molded sandwich formed

    construction, outer & inner surfaces are of 22 gauge to26 gauge painted metal . The interior of the panel is aminimum of 3 of structural foam bonded to the metalsurfaces. The thermal insulating qualities are superior.Various wall & roof types can be combined as required.

    Steel, aluminum, and stainless cladding available.Accessories:

    Rear removable panels, or doors as required.

    All required & exterior lighting, convenience outlets, etc.

    Required building utility step-down transformers, andcircuit breaker panels.

    Required air conditioning, heating, ventilating, andpressurization systems..etc.

    Power & Control Center Summary

    Combined 13.8 kV & 34.5 kV Building

    34.5kV 13.8 kV

    Views of Outdoor Switchgear

    108 Feet x 34 Feet

    80 Feet x 30 Feet In Production

    44 Feet x 30 Feet

    Interior View

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    11/12

    High Current Drawout Switchgear. 4,000 to 6,000 Amperes

    Special Switchgear

    4,000 to 6,000 AmpereVacuum Circuit Breaker.Drawout, to 63 kA S.C.

    Vacuum Circuit Breaker can be easily movedby use of a fifth wheel accessory4,000 to 6,000 Amp Vacuum Circuit Breakermoved by use of a fifth wheel accessory.

    Upper photo of cell with closedshutters. Lower photo shuttersopen , and current transformers.

    Upper photo of cell with closedshutters. Lower photo shuttersopen , and current transformers.

    PACS Industries are the leading manufacturer of4,000 to 6,000 Ampere Vacuum Circuit Breakersand drawout metalclad switchgear, at 13.8 kVoperating voltage, for Distribution or Generatorswitchgear,Generator Circuit Breakers have been TypeTested to IEEE C37.013 requirements. Over 250are in use with throughout the USA and over-seas. Available to 63 kA Interrupting & 3 secondS.C., 160 kA Momentary. Available at 95 kV &110 kV BIL.

    PACS Industries, inc., is the leading manufac-turer of 4,000 to 6,000 Ampere Vacuum CircuitBreakers and drawout metalclad switchgear, at13.8 kV operating voltage, for Distribution orGenerator switchgear,Generator Circuit Breakers have been TypeTested to IEEE C37.013 requirements. Over 250are in use throughout the USA and overseas.Available to 63 kA Interrupting & 3 second S.C.,160 kA Momentary. Available at 95 kV & 110 kVBIL.

    Special Switchgear Construction ( We can build what other companies ignore..try us)

    Tel: 516-829-9060 Fax: 516-829-9557 e-mail: sales@pacsindustr ies.com web: pacsindustr ies.com

    Generator & Paralleling SwitchgearTo C37.013 Standards1200 Amps through 6000 AmpsPACS manufactures generatorswitchgear that includes circuit break-ers to the IEEE C37.013 Standard.This Standard will now cover smallgenerators up to 100 MVA, as well aslarger generators. Contact us forappropriate bulletins.

    Arc Furnace Switchgearfor Steel Mills. Through 40.5 kV

    Typical 4000-6000 Amp Outdoor

    comPACSwgr Compact switchgear 26 wide.

    Including 2 high circuit breakers.

    3 high switchgear to 15 kV.

    Front-Access-Only metalcladswitchgear that can mountagainst a wall.

    A.C . Railway Switchgear. 25 or 60 HzTrolley switchgear to 52 kV, 250 KV BIL. Fixed stationclass or drawout construction. One or two pole.

    Iso-Phase Switchgear

    Drawout tractionbreaker.

    Typical trackside switchgear.Also available in singlestation class cubicles.

    Accessory switchgear forIsolated-Phase bus ductsystems, such as P.T.cubicles, AuxiliaryTransformer cubicles,etc.

  • 8/3/2019 005_5kV to 27 kV Swgr (W Rev 1)

    12/12

    Avoid Arc -Flash Fai lu res

    The best way to avoid a destructive electrical Arc-

    Fault blast is through preventive means. PACSafecontinuously monitors live bus bars for corona andvoltage, and detects deteriorating insulation systems.Level adjustments include warning or shutdown set-points, allowing repairs, avoiding Arc-Flash explo-sions. Can be fed to a computer for long time analysis& event recording.

    For retrofit of existing switchgear, or newswitchgear.

    PARTIAL DISCHARGE ANALYZERS:

    In the event that an Arc-Flash does occur in sw itchgear, it is imperative thatthe fault source be disconnected as quickly as possible, to avoid or miti-gate damage to equipment or personnel.

    The PACSafe Type Arc Detection system, immediately senses a lightflash in a switchgear cubicle when an Arc-Flash occurs, and simultane-ously senses for Rate-of-Rise of current. A signal is sent to targetedbreaker trip coils, bypassing Protective relays, tripping in as low as 57ms,mitigating Arc-Fault damage. This compares to over 300 ms trip time inSelective Coordination relay systems. Damage to the switchgear is propor-tional to the time duration of the Arc-Fault. The shorter the duration, the

    less damage will occur.For retrofit of existing switchgear, or new switchgear.

    ARC-MITIGATION SYSTEM:

    PACSafeArc-resistant switchgear is available, designed andtested in accordance with IEEE C37.20.7 standards. PACShas successfully tested single high and 2 high switchgear.IEEE Types 1, 2, 1C & 2C, at the KEMA laboratori es.

    The PACSafe Arc-Resistant designs include available topmounted Collector Plenums, to safely duct the Arc-Faultflames, heat, pressure, smoke & debris out of the switchgear

    room, into a safe disposal area.For new & replacement applications.

    ARC-RESISTAN T SWITCHGEAR:

    Arc-Flash Avoidance PACSafe

    Additional Products Available From PACS

    See our web. pacsindustries.com Outdoor Structural Substations to 230 kV. Arc-Furnace circuit breakers & switchgear. Railway catenary circuit breakers & switchgear. Single phase. 4,000 to 6,000 Amp Generator Switchgear per IEEE C37.013. Drawout Metalclad switchgear through 40.5 kV. 6000 A BreakersStation Class CBSwitchyards

    v 0

    Request PACSafe Catalog

    Request PACSafe Catalog

    Request PACSafe Catalog