    BLIND/ROLLER SHUTTER CONTROL

    Special notes concerning 1-pole systems

    Roller shutter switch

    For a roller shutter with one operating point. Roller shutter moves until

    the limit switch is activated.

    Roller shutter push-button

    For a roller shutter with one operating point. Roller shutter continues to

    move on as long as the button is pressed, at the longest until the limit

    switch is reached.Roller shutter switch and push-button

    For a roller shutter and the use of a selector switch Manual/automa-

    tic in connection with time switches, sun detectors, storm detectors

    etc.

    Normal push-button

    For a circuit with reclosing relay (switching sequence: Up, Stop, Down,

    Stop) a make contact is used.

    Switch and push-button

    according to the manufacturers specifications. When central control

    units, time switches, sun detectors, storm detectors etc. are used.

    Use of rocker with reverse lock-out:

    Rocker roller shutter switches and push-buttons produced after 1981

    have a reverse lock-out in addition to the electrical locking system. The

    appliances can be recognised by a symbol on the black upper

    side of the base.

    Operating principle of the reverse lock-out:

    It ensures that the roller shutter switchs first selected direction of

    movement must be switched off before the new direction can be swit-

    ched on. It ensures that the roller shutter push-buttons first selected

    directional rocker must be released before the new directional rocker

    can be pressed. The interval between forward and backward move-

    ment is thereby sufficiently long, so that no damage can be caused to

    the drive.

    Special notes concerning 2-pole systems

    Momentary/maintained-contact switch for roller shutters

    For two roller shutters with one operating point. Roller shutters conti-

    nue to move until they are switched off or reach the limit switch.

    Roller shutter push-button

    For two roller shutters with one operating point. Roller shutters conti-

    nue to move as long as the button is pressed, at the longest until the

    limit switch is reached.

    Switch or push-button

    according to the manufacturers specifications. When central

    control units, time switches, sun detectors, storm detectors etc. are

    used.

    Roller shutter push-button Roller shutter switch

    Momentary/maintained-contact switch for roller shutters or roller shutter push-button insert 2-pole for controlling

    2 alternating voltage drives 1 direct voltage drive

    2-pole changeo-ver switch

    Drive 1 Drive 2

    Roller shutter switches and push-buttons

    Switch and push-button for semi-cylinder locks

    applies to art. no. 3185.., 3186.., 3187.., 3188.., 3189.., 347639 and

    347939. The switches and push-buttons are to be used for semi-cylin-

    der locks with a total length of approx. 40 mm.

    Locks with 90135 and 225 key bit positions:

    Lock and switch are interlocked, i.e. they cannot be removed without a

    key. The key can be removed in all switched positions. The key bit must

    be nextto the fork.

    Locks with 315 key bit position:

    Lock and switch are not locked, i.e. removal is possible without a key.

    The key can only be removed in zero position. The key bit for roller

    shutter switches and push-buttons must lie in the fork.

    0

    315

    135225

    90

    lockedlo

    ck

    ed

    Interlocking of lock and switch

  • 8/12/2019 #01 Merten Shutter Controls

    2/1239

    3

    2006 |TECHNICAL INFORMATION

    www.m

    erten.c

    om

    BLIND/ROLLER SHUTTER CONTROL

    Installation

    Blind control system

    The blind control system is easy to install and has many uses. Two cen-

    tral flush-mounted inserts are combined with various inserts, following

    a modular conception. Blinds or roller shutters can be controlled

    manually, remotely, in groups or automatically, using the blind control

    system. Additional functions such as sun protection, twilight or wind

    alarm are possible.

    The blind control insert is the systems basic component

    The standard blind control insert, art. no. 580698 is only designed for

    the individual operation of blind or roller shutter motors. The standard

    insert has no extension input and cannot be connected to group or

    central control. A wind monitoring function is not possible with the

    standard blind control insert.

    For a blind/roller shutter motor with limit switch

    Individual control

    Standard blind control insert (art. no. 580698)

    Standard blind control insert (art. no. 580698)

    The blind control insert has 4 connecting terminals. Two terminals are

    for the power supply (L, N) with AC 230 V mains voltage, another two

    are for controlling the blind or roller shutter motor in the up or down

    direction.

    For blind control systems with central/group control or wind monito-

    ring, the blind control insert with extension input, art. no. 580699 is

    required. Group or central control can be implemented via the integra-

    ted extension input. For a blind/roller shutter motor with limit switch

    Individual control

    Extension input for group/central control

    Wind monitoring function can be implemented

    Blind control insert insert with extension input (art. no. 580699)

    Blind control insert with extension input (art. no. 580699)

    The blind control insert with extension input has 6 connecting termi-

    nals. Two terminals are for the power supply (L, N) with AC 230

    V mains voltage, another two are for controlling the blind or roller shut-

    ter motor in the up or down direction. Additionally, there are two termi-

    nals 1 and 2 for the extension input. If 230 V mains voltage is swit-

    ched at one of these inputs, the motor is triggered for the relevant

    direction of movement. The motor continues to run as long as the

    extension input has mains voltage. The extension input enables the

    simultaneous operation of several inserts, so that it is ensured that the

    motors run at the same time.

    The blind control insert is mounted in a 60 mm flush-mounted box. If

    extension units and/or flush-mounted sensor cables are installed, then

    the use of a deep box is recommended, due to the increased amount

    of cabling. The application is plugged into the insert together with the

    design frame.

    An insert is provided for

    each blind motor. Each

    motor can then be ope-

    rated locally either

    manually or automati-

    cally (depending on the

    insert used).

    Individual control

    Individual control

    By interconnecting inserts (580699) via the extension inputs, a cen-

    tral/group control system can be set up, with little installation work

    involved. Every blind receives its own blind control insert with the requi-

    red application.

    Group control of several inserts

    Inserts 2 and 3 control the roller shutter or blind motors. Insert 1

    (master) controls the extension inputs of the other inserts and thereby

    forms a central/group control unit, e.g. both motors are driven simulta-

    neously via insert 1. A motor may not be connected to a blind control

    insert (master) which is simultaneously controlling other inserts via the

    extension inputs.

    1 2 N L

    L1

    N

    M

    1 2 N L

    L1

    N

    M

    1 2 N L1 2 N L

    M

    1 2 N L

    L1

    N

    M

    1 2 N L1 2 N L

    N - 2+ 1L

    Central control with wind monitoring and group control

    Central/group control via inserts (580699)

    In larger installations, it is not always possible to operate all compo-

    nents on the same phase. For example, insert 4 could be installed

    centrally in an office building in the gatehouse (here phase L2). After

    working hours, all blinds in the building are raised by time control or

    manually. The blind control inserts 1, 2 and 3 in the various offi-

    ces run on a separate phase (here phase 1). Insert 1 is switched

    with group control functions, i.e. blinds 2 and 3 are moved simulta-

    neously with insert 1.

    Connection of inserts to different phases

    Connection of inserts (580699) on two phases

    Interface to the application

    Phase

    Motor Up

    Motor Down

    Neutral conductor

    Interface to the application

    Phase

    Motor Up

    Motor Down

    Neutral conductor

    Sensor connection

    Extension unit UpExtension unit Down

    Up Down

    1 motor max.1000 VA

    Motor

    Sun sen-

    sor

    Sun sen-

    sor

    Wind monitoring unit

    Central control

    Group 1

    Group 2

  • 8/12/2019 #01 Merten Shutter Controls

    3/1240 TECHNICAL INFORMATION | 2006

    www.m

    erten.c

    om

    BLIND/ROLLER SHUTTER CONTROL

    Function

    Functions

    Design cover

    - For a blind/roller shuttermotor with limit switch

    - Individual control

    580698

    Standard blind controlinsert(max. 1 motor 1000 VA)Neutral conductor required

    - For a blind/rollershutter motor with limitswitch

    - Individual control- Extension input forgroup/central control

    - Wind monitoringfunction possible

    580699

    Blind control insert withextension input(max. 1 motor 1000 VA)Neutral conductor required

    - Sensor with suctionfixing for the window

    - Measurement ofbrightness

    580691

    Sun/twilight sensor

    Cable length 2 m

    - Manual operation

    - Slat adjustment

    - Manual operation

    - Slat adjustment

    - Sun protection function with sensor 580691

    - Manual operation

    - Slat adjustment

    - Memory function for automatic operation of drive at

    saved times

    - Sun protection function with sensor 580691

    - Manual operation

    - Slat adjustment

    - Can be remote controlled via radio transmitter of the

    radio system

    - Sun protection function with sensor 580691

    - Manual operation

    - Slat adjustment

    - Can be remote controlled via infrared

    (Distance 2010/2050)

    - Sun protection function with sensor 580691

    - Manual operation/slat

    - Clock function with time block Mon-Fri: (1 x Up time,

    1 x Down time) and time block Sat-Sun (1 x Up time,

    1 x Down time) can be programmed

    Blind push-button

    System M 5877.., 5862..

    System Design 5842..

    System Basis 5802..

    OCTOCOLOR 5822..

    Blind push-button with sensor

    connection

    System M 5878.., 5865..System Design 5845..

    System Basis 5805..

    OCTOCOLOR 5825..

    Blind push-button with memory fun-

    ction and sensor connection

    System M 5879.., 5863..

    System Design 5843..

    System Basis 5803..

    OCTOCOLOR 5823..

    Blind push-button with radio receiver

    and sensor connection

    System M 5936..

    System Design 5935..

    Blind push-button with IR receiver

    and sensor connection

    System M 5880.., 5864..

    System Design 5844..

    System Basis 5804..

    OCTOCOLOR 5824..

    Standard blind time switch

    System M 5814.., 5819..

    System Design 5859..

    System Basis 5809..

    OCTOCOLOR 5839..

    - Manual operation/slat

    - Clock function for complex switching programs- Astro function for automatically adjusting switching

    times according to the time of the year

    - Random function

    - Manual operation/slat

    - Clock function for complex switching programs

    - Astro function for automatically adjusting switching

    times according to the time of the year

    - Random function.

    - Sun protection function with sensor 580691

    - Twilight function with sensor 580691

    - The wind monitoring unit allows the blind to be raised

    or lowered depending on the wind force

    Blind time switch

    System M 5815.., 5861..System Design 5841..

    System Basis 5801..

    OCTOCOLOR 5821..

    Blind time switch with sensor

    connection

    System M 5816.., 5867..

    System Design 5851..

    System Basis 5811..

    OCTOCOLOR 5831..

    Wind sensor interface

    580693 with wind sensor 580690

    or 580692

    via extensioninput

    Extension input out of

    service (nocentral/group control

    possible)

    Overview of functions and devices

    Blind push-button

    Blind time switch

    Wind monitoring unit

  • 8/12/2019 #01 Merten Shutter Controls

    4/12

  • 8/12/2019 #01 Merten Shutter Controls

    5/1242 TECHNICAL INFORMATION | 2006

    www.m

    erten.c

    om

    BLIND/ROLLER SHUTTER CONTROL

    Blind time switch

    Blind push-button with IR receiver and sensor connection Manual operation Slat adjustment

    Random function (time shift in the range of +/-15 min)

    Astro function (time shift in the range of +/- 2 hrs, depending on

    the time of the year)

    Complex clock functions:

    - 3 independent program memories

    - preset switching times

    - 18 switching times can be recorded

    - menu-assisted operation/programming

    - reserve power up to 24 hours (without battery)

    - can be reset to factory settings

    - easy switching from summer time to winter time

    and vice versa - individual running times can be programmed

    Apart from manual operation, up to 18 switching times can be divided

    among 3 independent program memories. In this way, varying pro-gramming options can be retrieved and carried out (e.g. for daily routi-

    nes, holidays, weekends, etc.). Functions such as the astro and ran-

    dom functions are not used globally for all switching times, but can be

    individually assigned to any Up or Down time. These functions can vary

    the Up and Down time, thereby creating the impression to outsiders

    that the flat/house is occupied. Astro and random functions can there-

    fore simulate presence. Travel times can be set for the blinds using

    special menu items.

    The astro function

    If the blind is to be opened at sunrise

    and closed again at sunset, then

    recorded switching times in automatic

    mode must be continuously adapted

    to the time of the year. For this pur-

    pose, the blind time switch calculates

    sunrise and sunset times for everyday of the year. The time control

    application carries out appropriate

    adjustments corresponding to the

    time of the year on a weekly basis.

    The random function

    If the random function has been

    activated for a certain switching time,

    then this time can vary by a maxi-

    mum of +/- 15 minutes. This random

    time is generated/modified on a daily basis in steps of 1 minute and

    used for all switching times for which the random function has been

    selected. If the astro function was also activated for this switching

    time, then the switching time is adapted to the relevant sunrise and

    sunset times and varied by 15 +/- minutes using the random function.

    System M System Design System Basis OCTOCOLOR5880.., 5864.. 5844.. 5804.. 5824..

    Manual operation

    Slat adjustment

    Can be remote controlled using IR remote control Distance 2010

    (art. no. 570222) or Distance 2050 (art. no. 570722)

    Sun protection function with sensor, art. no. 580691

    The blind push-button with IR receiver and sensor connection takes

    the place of a mechanical blind push-button and offers, in addition to

    the blind push-button functions, the remote control option with one of

    the IR remote controls Distance 2010 (art. no. 570222) or Distance

    2050 (art. no. 570722).

    The IR receiver in the blind push-button can demonstrate its advanta-

    ges in large offices or rooms. In the office, it is very convenient to

    move blinds to a position to stop the sun from dazzling you while wor-

    king, without having to get up to do so. For presentation purposes, lec-

    ture rooms can be darkened using an IR remote control. But it is also

    convenient for private use e.g. for elderly or handicapped persons, who

    are able to raise and lower roller shutters or blinds using the IR remote

    control from a central location.

    Sun protection function

    For the blind push-button with memory function and sensor connec-

    tion, the sun protection function (see Blind push-button with sensor

    connection) can be used by connecting a sun/twilight sensor (art. no.580691). The brightness value is fixed at approx. 20000 lux.

    System M System Design System Basis OCTOCOLOR5815.., 5861.. 5841.. 5801.. 5821..

    Standard blind time switch

    System M System Design System Basis OCTOCOLOR5814.., 5819.. 5859.. 5809.. 5839..

    The standard blind time switch enables the programmed, time-control-

    led switching of a blind motor, in conjunction with a blind control ins-ert.

    Manual operation

    Slat adjustment

    Simple clock functions:

    - Easy operation via 4 button panel

    - Programming without flush-mounted insert possible

    - Time block Mon Fri: 1 x Up time, 1 x Down time

    - Time block Sat Sun: 1 x Up time, 1 x Down time

    - Rapid programming function

    - Switching times programmed at the factory

    - Reserve power > 6 hrs via memory capacitor

    Programming

    If the memory capacitor is loaded (approx. 30 min after plugging it on

    the insert), the clock can be removed from the flush-mounted insert to

    make programming easier and programmed within approx. 6 hrs, inde-pendent of the flush-mounted insert.

    Caution:

    If the blind control insert with extension input, art. no. 580699, is used

    with the standard time switch, then the extension input has no func-

    tion.

    In addition to the functions of the blind push-button with sensor

    connection, blinds/roller shutters can be activated using all radio

    transmitters that are part of the Merten radio transmission system.

    Particularly when cables for group and central control are missing,

    requirements can still be met by wireless control. Each blind push-but-

    ton with a radio receiver can be programmed to react to up to 16 radio

    transmitters, individually, in groups or scenes.

    Blind time switch with sensor connection

    System M System Design System Basis OCTOCOLOR5816.., 5867.. 5851.. 5811.. 5831..

    15 16

    3

    4

    5

    6

    7

    8

    9

    5 10 15 20 25 30 35 40 45 50

    4

    5

    6

    7

    8

    9

    10

    Jan. Jul. Dez.Apr. Okt.WZ SZ

    KW

    Tageslicht

    16

    17

    18

    19

    20

    21

    17

    18

    19

    20

    21

    22

    5 10 15 20 25 30 35 40 45 50

    Jan. Jul. Dez.Apr. Okt.WZ SZ

    KW

    Dunkelheit

    Dunkelheit

    Manual operation

    Slat adjustment

    Random function (time shift in the range of +/-15 min) Astro function (time shift in the range of +/- 2 hrs, depending on

    the time of the year)

    Daylight

    Darkness

    Darkness

  • 8/12/2019 #01 Merten Shutter Controls

    6/12

  • 8/12/2019 #01 Merten Shutter Controls

    7/1244

    BLIND/ROLLER SHUTTER CONTROL

    TECHNICAL INFORMATION | 2006

    www.m

    erten.c

    om

    Before entering data, carry out a RESET.

    |When a reset is carried out, all settings are deleted and

    default standard settings are restored.

    QUICK USER GUIDE TO THE BLIND TIME SWITCH / BLIND TIME SWITCH WITH SENSOR CONNECTION

    System M System Design System Basis OCTOCOLOR

    5815.., 5861.., 5816.., 5867.. 5841.., 5851.. 5801.., 5811.. 5821.., 5831..

    Setting winter/summer time, date, day of week and time

    Dat.Uhr

    Set

    W S

    MoDiMiDoFrSaSo

    A

    B

    C

    Mode

    Prog Zufall Astro

    7 s

    1 Hold the [Mode] and [Set] buttons down forapprox. 7 seconds until all displays briefly

    light up.

    1 2 0 0 flashes in the display.

    The device has now been restored to the default

    settings.

    Preparing to set basic data (winter/summer time, date, day of week,

    time)

    1 Hold down the [Set] button until prog appears in the display.The device is now in set mode.

    2 Press the [Set] button.

    W flashes in the display (winter time).

    Performing a RESET

    Dat.

    Uhr

    Prog Zufall Astro

    Mo

    Di

    Mi

    Do

    Fr

    Sa

    SoW

    1 Press [ ] or [ ] to alternate between W (winter time) and S(summer time).

    2 To confirm, press [Set].

    Setting winter/summer time

    W (winter time) flashes.

    Dat.

    Uhr

    Prog Zufall Astro

    Mo

    Di

    Mi

    Do

    Fr

    Sa

    So

    1 Press [ ] or [ ] to set the current month.

    2 To confirm, press [Set].

    Setting the month

    The 0 1 (00 - 12) display flashes.

    Dat.

    Uhr

    Prog Zufall Astro

    Mo

    Di

    Mi

    Do

    Fr

    Sa

    So

    1 Press [ ] or [ ] to set the current calendar day.

    2 To confirm, press [Set].

    Setting the calendar day

    The 0 1 (00 - 31) display flashes.

    Dat.

    Uhr

    P ro g Zufall Astro

    Di

    Mi

    Do

    Fr

    Sa

    So

    Mo

    1 Press [ ] or [ ] to set the current day of the week.

    2 To confirm, press [Set].

    Setting the day of the week

    In the top right corner of the display, a black

    bar flashes next to Montag (Monday).

    P ro g Zufall Astro

    Mo

    Di

    Mi

    Do

    Fr

    Sa

    SoDat.

    Uhr

    1 Press [ ] or [ ] to set the current hour.

    2 To confirm, press [Set].

    Time: Setting the hour

    The 1 2 (00 - 23) display flashes.

    P ro g Zufall Astro

    Mo

    Di

    Mi

    Do

    Fr

    Sa

    SoDat.

    Uhr

    1 Press [ ] or [ ] to set the current minute.

    2 To confirm, press [Set].

    The device now shows the current time, day of the week and summer

    or winter time.

    Setting the basic data is now completed.

    Time: Setting the minutes

    The 00 (00 - 59) display flashes.

    |The blind time switch features three program memories ,

    and . The memories and have been prepro-

    grammed at the factory with Up and Down times. You can

    change or delete these times. The memory has not been

    preprogrammed. You can program your personal Up and Down

    times immediately.

    C

    BC

    B

    Programming the Up and Down times

    Choosing memory slot C

    1 Hold down the [Set] button until prog appears in the display.

    2 Press [ ] again and again until appears.

    3 To confirm, press [Set].

    The memory is selected, in the display appears - - : - -

    |The display - - : - - indicates a free memory slot in the selec-

    ted memory ( , or ).CB

    C

    C

    Programming Up and Down times in the memory C

    The following display lights up: - - : - -

    1 Press the [Set] button.

    The symbol flashes (Up direction).

    2 Press [ ] or [ ] to determine the Up or Down direction ofmovement for which your switching time is to be carried out.

    3 To confirm, press [Set].

    at.

    Uhr

    Prog Zufall Astro

    C

    MoDi

    Mi

    Do

    FrSaSo

    1 Press [ ] or [ ] to set the hour at which the blinds are to be rai-sed/lowered.

    2 To confirm, press [Set].

    Switching time: Setting the hours

    The first two digits 00 flash in the

    display.

  • 8/12/2019 #01 Merten Shutter Controls

    8/12

    BLIND/ROLLER SHUTTER CONTROL

    45

    3

    2006 |TECHNICAL INFORMATION

    www.m

    erten.c

    om

    at.

    Uhr

    Prog Zufall Astro

    C

    MoDiMi

    DoFrSaSo

    1 Press [ ] or [ ] to set the minutes.

    2 To confirm, press [Set].

    Switching time: Setting the hours

    The last two digits 00 flash in the dis-

    play.

    at.

    Uhr

    Prog Zufall Astro

    MoDiMi

    Do

    FrSaSo

    C

    1 Press [ ] or [ ] to move the flashing frame to the required dayof the week.

    2 Press [Mode] to select or deselect the day of the week marked by

    the frame.

    A day of the week has been selected when a bar appears next to it.

    When you have finished selecting or deselecting days:

    3 To confirm, press [Set].

    Switching time: Setting the day(s) of the week

    In the display, bars appear next to each

    day of the week (Monday to Sunday).

    Also, there is a frame around the first bar

    (Monday) that flashes. The flashing frame

    shows that you can select or deselect this

    day of the week. The switching times are

    only carried out for selected days of the

    week.

    Dat.

    Uhr

    Prog Zufall Astro

    A

    MoDi

    Mi

    DoFrSaSo

    1 Press [ ] or [ ] to switch the random function on or off.

    2 To confirm, press [Set].

    Setting the random function

    A point flashes under Zufall (random).

    A flashing point indicates that the random

    function is off.

    A point that doesnt flash indicates that

    the random function is on.

    at.

    Uhr

    Prog Zufall Astro

    C

    MoDi

    Mi

    DoFr

    SaSo

    1 Press [ ] or [ ] to switch the astro function on or off.

    2 To confirm, press [Set].

    The following display appears: - - : - -

    To program further switching times, proceed as before beginning from

    the section Programming Up and Down times in memory .C

    Setting the astro function

    A point flashes under Astro.

    A flashing point indicates that the astro

    function is off.

    A point that doesnt flash indicates that

    the astro function is on.

    Ending programming

    When you have stored all the switching times in the program memory:

    1 Press [Set] for at least 3 seconds.

    The device now shows the current time, day of the week and summer

    or winter time.

    2 Let go of the [Set] button again.

    Selecting program memory , or CB

    The device now shows the current time, day of the week and summer

    or winter time.

    1 Press the [Mode] button to switch between the individual programmemories , or .

    |If there is no program memory shown in the display, no pro-

    grammed Up and Down times will be carried out.

    CB

    Deleting switching times

    The device now shows the current time, day of the week and summer

    or winter time.

    1 Hold down the [Set] button until prog appears in the display.

    2 Press [ ] or [ ] again and again until the required programmemory , or flashes in the display.

    3 To confirm, press [Set].

    4 Press [ ] or [ ] to select the switching time that you want todelete.

    5 Press [Mode] for at least 3 seconds to delete the switching time.

    The symbol - - : - - indicates that the memory slot is empty.

    To delete other switching times:

    6 Select the required time by pressing [ ] or [ ].

    7 Press [Mode] for at least 3 seconds to delete the switching time.

    To end the Deleting switching times procedure:

    8 Press [Set] for at least 3 seconds.

    The device now shows the current time, day of the week and summer

    or winter time.

    CB

    |If you press the [Set] button for too long, the blind time switch

    switches back into the prog mode.

    Hold the [Set] button down again for at least 3 seconds until

    the display shows the current time, day of the week and a W

    for winter time or an S for summer time. Let go of the

    [Set] button.

    Select memory so that the blinds are automatically raised/lowered

    at the times you have set.

    1 Press the [Mode] button again and again until the display showsthe memory selected.

    Programming the switching times is now completed.

    C

    C

    Switching between winter and summer times

    The device now shows the current time, day of the week and summer

    or winter time.1 Press [Set] to switch between:

    Dat.

    Uhr

    Prog Zufall Astro

    W

    Dat.

    Uhr

    Prog Zufall Astro

    S

    Dat.

    Uhr

    Prog Zufall Astro

    WDat.Uhr

    Prog Zufall Astro

    S

    Set

    Set

    Set

    Set

    Winter time W

    Winter time and individual

    raising or lowering time

    W

    Summer time S

    Summer time and individual

    raising or lowering time S

    |If the individual blind raising or lowering time is not activated,

    the blinds will operate for the default time of 2 minutes.

    |Further information about the blind time switches can be

    found in the operating instructions.

  • 8/12/2019 #01 Merten Shutter Controls

    9/1246 TECHNICAL INFORMATION | 2006

    www.m

    erten.c

    om

    BLIND/ROLLER SHUTTER CONTROL

    Function:

    If a switching command is carried out by the cen-

    tral control device, the multiple control relay inter-

    rupts the power supply to the manual push-button

    and switches the drive directly. The manual push-

    button is reactivated after the central controldevice has been deactivated (2 - 3 minutes,

    depending on type).

    Multiple control relay insert for roller shutters,

    art. no. 576399

    Connection:

    Up to two drives

    can be connected to a multiple control relay (see connection dia-

    grams). The following rule applies:

    1.) Up to four drives can be operated with two multiple control relays.

    2.) If there are more than four drives, only one drive per multiple con-

    trol relay can be connected, because the motor

    outputs (M2) are supplied with power via the central input cables

    and further interconnections would produce too great a load for the

    central time switch.

    Devices that are compatible with the system:

    Central control:

    Roller shutter control (device with three conductors, art. no. 5760..,

    5780..)

    Roller shutter control insert (device with four conductors, art. no.

    576999)

    Roller shutter push-button (art. no. 315500)

    Roller shutter switch (art. no. 311501, keeps local operation locked

    as long as it remains switched on).

    Local operation:

    only with roller shutter push-button (art. no. 315500)

    Installation:

    The multiple control relay is a flush-mounted device with retaining ring

    and no claws for screw fixing to a switch (junction) box. It is completed

    with blanking covers of all flush-mounted ranges.

    By removing the retaining ring, the invisible installation in a switch box

    is possible with a box lid as a cover. (This is not recommended as the

    devices are then no longer accessible).

    Open board with 2 base relays, nine connection wires

    (flexible, 0.75 mm with wire end ferrules, length approx. 10 cm) are

    soldered directly to the device. There are no terminals on the device.

    Because of the large number of terminals, a combination of two switchjunction boxes (60 mm deep) should be installed, so that one box can

    be used as a terminal compartment.

    Two drives should be controlled together using one electronic roller

    shutter control. Also, it should be possible to control both motors indivi-

    dually using a manual push-button.

    Four drives should be controlled together using one electronic roller

    shutter control. Also, it should be possible to control the motors indivi-

    dually using a manual push-button.

    Any number of drives should be controlled together using a single electronic roller shutter control.

    Also, it should be possible to control all motors individually using a manual push-button.

    Notes:

    The phases do not necessarily have to

    be identical, but all poles must be swit-

    ched off in the case of a malfunction

    and when work is being done.

    If through-wiring is carried out, including

    incoming cable, then observe the per-

    mitted total load for the fuse/LS switch.

    As a general rule: approx. 10 drives per

    circuit.

    Technical data:

    Multiple control relay for installing in size 58

    flush-mounted box

    Nominal voltage: 250 V/50 Hz

    Nominal current: 5 A, cos = 1

    2 A, cos = 0.4

    Multiple control relay insert for roller shutters Multiple control relay inserts for roller shutters

    black

    blue

    green

    green

    violet

    brown

    brown

    red

    red

    L N AUp

    ADown

    Manual

    M1Up

    M1Down

    M2Up

    M2Down

    Push-button 1 Push-button 2

    L N AUp

    ADown

    Manua

    l

    M1Up

    M1Do

    wn

    M2Up

    M2Do

    wn

    black

    blue

    green

    green

    violet

    brown

    brown

    red

    red

    L N AUp

    ADown

    Manua

    l

    M1Up

    M1Down

    M2Up

    M2Down

    black

    blue

    green

    green

    violet

    brown

    brown

    red

    red

    P ush -but ton 1 P ush -but to n 2 Push-button 3 Push-button 4

    Multiple control relay inserts for roller shutters

    L N AUp

    ADown

    Manual

    M1Up

    M1Down

    M2Up

    M2Down

    black

    blue

    green

    green

    violet

    brown

    brown

    L N AUp

    ADown

    Manual

    M1Up

    M1Down

    M2Up

    M2Down

    black

    blue

    green

    green

    violet

    brown

    brown

    L N AUp

    ADown

    Manual

    M1Up

    M1Down

    M2Up

    M2Down

    black

    blue

    green

    green

    violet

    brown

    brown

    Push-button 1 Push-button 2 Push-button n

    1st configuration example 2nd configuration example

    3rd configuration example

  • 8/12/2019 #01 Merten Shutter Controls

    10/1247

    3

    2006 |TECHNICAL INFORMATION

    www.m

    erten.c

    om

    BLIND/ROLLER SHUTTER CONTROL

    Function:

    Conventional roller shutter motors may not be

    connected in parallel and operated by a conventio-

    nal roller shutter switch, otherwise an electrical

    feedback effect could result in the motor being

    destroyed.

    Multiple control relay for roller shutters, flush-mounted, art. no.

    576398

    1st configuration example

    The multiple control relay for flush-mounted roller shutters is installed

    in the switch box or junction box. Please use a moisture-proof box for

    the installation in the roller shutter box. The multiple control relay, with

    its special, flat design of just 22 mm will fit in a normal flush-mounted

    box. We recommend the installation to be carried out in a deep flush-

    mounted box. The flush-mounted box can also be covered using any ofthe blanking covers from the flush-mounted range.

    In its most simple version, the multiple control relay for flush-mounted

    roller shutters enables the functionality of an isolation relay for motors.

    Extensive functions can be implemented using the flush-mounted mul-

    tiple control relay. Individual roller shutter motors can be combined in

    groups and subgroups which can again be combined into a central

    control unit. The entire unit is then controlled using only a single push-

    button.

    The central command operates in priority mode. For the individual ope-

    ration of the motors, only blind push-buttons may be used. If you use

    blind switches for individual operation, damage might be caused to the

    motor.

    Installation:

    2-motor operation and group control

    Two drives are connected to one roller shutter multiple control relay.

    The motors can be operated individually using a manual push-button.

    Group control components with a subgroup.

    Single motor operation

    Three drives can be priority controlled in combination using a push-but-

    ton or a blind time switch. Also, it should be possible to control the

    motors individually using a manual push-button.

    Connections:

    N: Neutral conductor

    L: Phase

    L: Switched phase

    Up: Motor Up direction

    Down: Motor Down direction

    PE: Protective conductor

    2nd configuration example

    To other multiple con-trol relays or motors orremains unassigned.

    Input for central com-mand, control voltage230 V

    Blind switch or

    roller shuttertimer

    Mains

    ! Only blind push-buttons may be used for single operation. Blind switches maynot be used. They could cause damage to the motor.

    Mains

    Mains

    Mains

    to other devices

    ! Only blind push-buttons may be used for single operation. Blind switches may notbe used. They could cause damage to the motor.

    ! Pay attention to the total phase load when planning the installation.

    Application example for the integration of a subgroup

    Multiple controldevice as a controldevice for groupoperation

    An additional multiple control device is required for each subgroup. In this exam-ple, one motor per multiple control device is controlled in the subgroup (singlemotor operation). Alternatively, two motors can also be operated using one multi-ple control device (2-motor operation), as shown above.

    to otherdevices

    Input for central com-mand, control voltage230 V

    Blind switch or

    roller shuttertimer

    Input for central com-

    mand, control voltage

    230 V

    Blind switch or roller

    shutter timer

    to other

    transfor-mersMains

  • 8/12/2019 #01 Merten Shutter Controls

    11/1248 TECHNICAL INFORMATION | 2006

    www.m

    erten.c

    om

    BLIND/ROLLER SHUTTER CONTROL

    Function:

    In its most simple version, the multiple control relay

    for roller shutters REG enables the functionality of

    an isolation relay for motors.

    With the multiple control relay for roller shutters REG

    you can combine roller shutter motors to form group

    installations. These can be single groups or cen-trally controlled subgroups.

    The central command operates in priority mode. For the individual ope-

    ration of the motors, only roller shutter rocker buttons may be used. If

    you use blind switches for individual operation, damage might be cau-

    sed to the motor.

    Caution:

    Conventional roller shutter motors may not be connected in parallel and

    operated by a conventional roller shutter switch, otherwise an electrical

    feedback effect could result in the motor being destroyed.

    Installation:

    The multiple control relay for roller shutters REG is designed as a DIN

    rail mounted device. Up to 2 motors can be operated using a multiple

    control relay.

    Multiple control relay for roller shutters REG, art. no. 576397

    1st configuration example

    Au

    f

    Ab

    L'

    (Einzelbedienung"vor

    Au

    f

    Ab

    N

    Ne

    tz

    L

    Au

    f

    Ab

    Ne

    tz

    N

    N

    M1

    M2

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    332000

    2AAC 230V/50Hz

    M

    PE

    PE

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz

    M

    2nd configuration example

    Central control of any number of motors using a central command,

    e.g. with a blind time switch or a blind push-button from Mertens

    blind control system or a roller shutter rocker switch.

    Individual operation of motors is carried out using a roller shutter

    rocker switch.

    Au

    f

    Ab

    Au

    f

    Ab

    N

    L

    Au

    f

    AbN

    N

    M1

    M2

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    3320002A

    AC 230V/50Hz M

    PE

    Netz

    PE

    L'

    Au

    f

    Ab

    Au

    f

    Ab

    N

    L

    Au

    f

    AbN

    N

    M3

    M4

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    3320002A

    AC 230V/50Hz M

    PE

    Netz

    PE

    L'

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz M

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz M

    Auf

    Ab

    Auf

    Ab

    N

    L

    Auf

    AbN

    N

    M1

    M2

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einze

    lbe

    d

    M2

    Au

    f

    Ab

    N

    332000

    2AAC230V/50Hz M

    PE

    Netz

    PE

    L'

    Auf

    Ab

    Auf

    Ab

    N

    L

    Auf

    AbN

    N

    M3

    M4

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einze

    lbe

    d

    M2

    Au

    f

    Ab

    N

    332000

    2AAC230V/50Hz M

    PE

    Netz

    PE

    L'

    Auf

    Ab

    Auf

    Ab

    N

    L

    Auf

    AbN N

    M5

    M6

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einze

    lbe

    d

    M2

    Au

    f

    Ab

    N

    332000

    2AAC230V/50Hz M

    PE

    Netz

    PE

    L'

    Auf

    Ab

    Auf

    Ab

    N

    L

    Auf

    AbN N

    M7

    M8

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einze

    lbe

    d

    M2

    Au

    f

    Ab

    N

    332000

    2AAC230V/50Hz M

    PE

    Netz

    PE

    L'

    Auf

    Ab

    Auf

    Ab

    L

    Auf

    AbN

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einze

    lbe

    d

    M2

    Au

    f

    Ab

    N

    332000

    2AAC230V/50Hz M

    Netz

    L'

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einzelbed

    M2

    Au

    f

    Ab

    N

    5763 97

    2AAC230V/50Hz

    M

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einzelbed

    M2

    Au

    f

    Ab

    N

    5763 97

    2AAC230V/50Hz

    M

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einzelbed

    M2

    Au

    f

    Ab

    N

    5763 97

    2AAC230V/50Hz

    M

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einzelbed

    M2

    Au

    f

    Ab

    N

    5763 97

    2AAC230V/50Hz

    M

    Eingang,

    Zen

    tra

    lbe-

    fehl,230V

    ,

    Vorrang

    Au

    f

    Ab L

    '

    Au

    f

    Ab

    N

    M1

    Ne

    tz

    L

    Ne

    tz

    N

    Einzelbed

    M2

    Au

    f

    Ab

    N

    5763 97

    2AAC230V/50Hz

    M

    Central control of any number of motors, that are combined in

    decentralised groups.

    Additionally, a roller shutter rocker button can be used for the indivi-

    dual operation of the motors.

    The central command operates in priority mode.

    Input for central

    command, control

    voltage 230V, pri-

    ority

    ! Only blind push-buttons may be usedfor single operation. Blind switchesmay not be used. They could causedamage to the motor.

    Input for central

    command, control

    voltage 230V, prio-

    rity Input for central

    command, control

    voltage 230V, pri-

    ority

    Push-button,

    individual

    operation

    other applian-

    ces

    Push-button,

    individual

    operation

    Push-button,

    individual

    operation

    other applian-

    ces

    other applian-

    ces

    Push-button,

    individual

    operation

    Push-button,

    individual

    operation

    Push-button,individual

    operation

    Push-button,

    individual

    operation

    Push-button,

    individual

    operation

    Push-button,

    individual

    operation

    Push-button,

    individual

    operation

    Push-button,

    individual

    operation

    Push-button,

    individual

    operation

    Push-button

    group 1

    Push-button

    group 2

  • 8/12/2019 #01 Merten Shutter Controls

    12/12

    3

    www.m

    erten.c

    om

    BLIND/ROLLER SHUTTER CONTROL

    3

    3rd configuration example

    Au

    f

    Ab

    Au

    f

    Ab

    N

    L

    Au

    fAbN

    N

    M1

    M2

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    332000

    2AAC 230V/50Hz M

    PE

    Netz

    PE

    L'

    Au

    f

    Ab

    Au

    f

    Ab

    N

    L

    Au

    fAbN

    N

    M3

    M4

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    332000

    2AAC 230V/50Hz M

    PE

    Netz

    PE

    L'

    Au

    f

    Ab

    Au

    f

    Ab

    N

    L

    Au

    fAbN

    N

    M5

    M6

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    332000

    2AAC 230V/50Hz M

    PE

    Netz

    PE

    L'

    Au

    f

    Ab

    Au

    f

    Ab

    N

    L

    Au

    fAbN

    N

    M7

    M8

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    332000

    2AAC 230V/50Hz M

    PE

    Netz

    PE

    L'

    Au

    f

    Ab

    Au

    f

    Ab

    L

    Au

    f

    AbN

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    332000

    2AAC 230V/50Hz M

    L'

    L1 2

    L 1 2

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz

    M

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz

    M

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz

    M

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz

    M

    Eingang,

    Zentralbe-

    fehl,230V,

    Vorrang

    Auf

    Ab L

    '

    Auf

    Ab

    N

    M1

    Netz

    L

    Netz

    N

    Einzelbed

    M2

    Auf

    Ab

    N

    5763 97

    2AAC 230V/50Hz

    M

    Netz

    The entire installation is time-controlled using the blind time switch

    with sensor connection.

    Twilight function for the complete installation via a sun/twilight sen-

    sor.

    Wind monitoring functionality for the installation by means of a wind

    sensor and the wind sensor interface.

    The wind monitoring function operates in priority mode.

    Group control of motors that are combined in two subgroups via rol-ler shutter rocker switch.

    Single control of all motors of the installation via local roller shut-

    ter rocker switch.

    Wind monitoring unit

    - Wind sensor interface

    - Wind sensor

    Central time control and twilight

    function

    - Blind time switch with sensor

    connection

    - Blind control insert with exten-

    sion input

    - Sun/twilight sensor

    other appli-

    ances

    Push-button,

    single operation

    Push-button

    group 2

    Push-button,

    single operation

    Push-button,

    single operation

    Push-button,

    single operation

    Push-button,

    single operation

    Push-button,

    single operation

    Push-button,

    single operation

    Push-button,

    single operation

    Push-button

    group 1

    other appli-

    ances

    Motor