02 advancedumi en

24
Sepam 1000+ Advanced UMI

Upload: sky-fall

Post on 02-Feb-2016

10 views

Category:

Documents


1 download

DESCRIPTION

advanced UMI

TRANSCRIPT

Page 1: 02 AdvancedUMI En

Sepam 1000+Advanced UMI

Page 2: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt2 /24

Integrated or remote Advanced UMI,

Entry of 2 passwords

Access toparameters

Accessto settings

Alarmdisplay

Switchgeardiagnosis

Metering

Lamp test

Reset

Graphic LCD display

Alarmacknowledgment

Page 3: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt3 /24

Advanced UMI9-key keypad

BLACK current operation keys BLUE parameter/protection setting keys 3 dual-function keys:

Operating functionsNavigation in parameter/protection setting mode

Universal icons, consistent with LV products

Page 4: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt4 /24

Advanced UMI3 categories of users

Operator:Access to all data in read mode onlyClear/Reset actions

Personnel qualified to set protection functionsKnow the «Setting» code (1 key)Operator + access to protection settings

Personnel qualified to set Sepam parametersKnow the «Parameters» code (2 keys)Operator + access to protection settings + access to

Sepam parameters

Page 5: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt5 /24

Advanced UMIGraphic LCD display

128 x 64 pixels, number of lines, size of characters and symbols according to language versions and screens

2 versions of screen backgrounds available:resident factory version: Englishadditional customized version (language / customer),

customization using SFT2840:of the position of the system zones of the content of the text zone

Page 6: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt6 /24

Advanced UMIAccess to measurements and parameters Series 20

Example: measurement loop

Page 7: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt7 /24

Current operation (blue keys) Series 20

I1 I2 I3 RMS current measurementIo residual current, digital and bargraphI1 I2 I3 phase current bargraphIav1 2 3 average current valueImax1 2 3 peak current demandT1 à T8 temperature sensorV1 V2 V3 phase-to-neutral voltageU12,32,13 phase-to-phase voltageVo residual voltageF frequency

I1=162A RMS

I2=161A RMS

I3=163A RMS

Page 8: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt8 /24

Current operation (white keys) Series 20

tripI1,I2,I3,Io tripping currents (phase and residual)unbalance unbalance ratio (negative sequence current)breaking dev. trip circuit supervision,nb of operation,

operating and charging timekA² cumulative breaking currentE thermal capacity percentage

time before starting authorizationst I stT motor starting current and timeNb st,waitT start inhibit time /nb of starts before inhibitionCh running hour counterVd positive sequence voltage

Page 9: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt9 /24

Current operation (white keys)

Series 20

The «Alarm» key may be used to consult the 16 most recent unacknowledged alarms.

N.B. The alarms are not saved in the event of a power outage.

Page 10: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt10 /24

Current operation (white keys)

Page 11: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt11 /24

Current operation (white keys)

Page 12: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt12 /24

Current operation (white keys)

I1=162A RMS

I2=161A RMS

I3=163A RMS

Page 13: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt13 /24

Parameter and protection setting (blue keys)

main lang.,frequency,active group,remote setting,settings setting mode,modif, passwordssepam info type, versionMES input/output module optionmodbus communication parameter settingMSA analog output module optionCT / VT nb , type, ratio of sensorsO1 parameter setting output O1I / O input reading, output reading and testingLDC CB control, logic discr., choice of use of inputs

Page 14: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt14 /24

Parameter and protection setting (blue keys)

Page 15: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt15 /24

Parameter and protection setting (blue keys)

Page 16: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt16 /24

Parameter and protection setting (blue keys)

Page 17: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt17 /24

Parameter and protection setting (blue keys)

Page 18: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt18 /24

Parameter and protection setting (blue keys)

Page 19: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt19 /24

Advanced UMI Series 40

The same as with Sepam series 20, themeasurements and parameters are accessed via the metering, diagnosis, status and protection keys, but through a first menu which is then used to select a series of screens as presented in the diagram opposite.

Example: Measurement loop

Page 20: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt20 /24

Advanced UMI Series 40 «Metering» menu

To begin with, thekey provides access to the metering menu.

The and keys are used to move the cursor up and down to select the chosen type of measurements.

Use the key again to scroll the chosen measurement loop.

Page 21: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt21 /24

Advanced UMI Series 40«General settings» menu

The key is used to access to the menu containing the different general settings entered in Sepam.

The and keys areused to move the cursor up and down to select the chosen type of parameter.

Use the key again to scroll the chosen measurement loop.

Page 22: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt22 /24

Advanced UMI Series 40«Protection» menu

The key provides access to the menu containing the different Sepam protection functions.

The and keys are used

to move the cursor up or down to

select the type of protection

function.

Use the key again to scroll

the chosen measurement loop.

Protections

I Phase

IDirectionnal

F.P

I Résidual

Voltage

Recloser

Page 23: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt23 /24

Advanced UMI Series 40«Diagnosis» menu

The key provides access to the Sepam diagnosis menu.

The and keys are used

to move the cursor up and down

to select the chosen type of data.

Use the key again to scroll

the chosen measurement loop.

Diagnosis

Diagnosis

Trip -1

Trip -3

Trip 0

Trip -2

Trip -4

Page 24: 02 AdvancedUMI En

Advanced UMI eng. S1000+.ppt24 /24

Advanced UMI Series 40«Alarms» menu

The key provides access to the list of alarms.

Use the key again to display the last 16 alarms that have not been erased yet (date/time andname of alarm and faulty phase)

N.B. The alarms are saved in the event of a power failure

Alarms

List Details