02 advancedumi en
DESCRIPTION
advanced UMITRANSCRIPT
Sepam 1000+Advanced UMI
Advanced UMI eng. S1000+.ppt2 /24
Integrated or remote Advanced UMI,
Entry of 2 passwords
Access toparameters
Accessto settings
Alarmdisplay
Switchgeardiagnosis
Metering
Lamp test
Reset
Graphic LCD display
Alarmacknowledgment
Advanced UMI eng. S1000+.ppt3 /24
Advanced UMI9-key keypad
BLACK current operation keys BLUE parameter/protection setting keys 3 dual-function keys:
Operating functionsNavigation in parameter/protection setting mode
Universal icons, consistent with LV products
Advanced UMI eng. S1000+.ppt4 /24
Advanced UMI3 categories of users
Operator:Access to all data in read mode onlyClear/Reset actions
Personnel qualified to set protection functionsKnow the «Setting» code (1 key)Operator + access to protection settings
Personnel qualified to set Sepam parametersKnow the «Parameters» code (2 keys)Operator + access to protection settings + access to
Sepam parameters
Advanced UMI eng. S1000+.ppt5 /24
Advanced UMIGraphic LCD display
128 x 64 pixels, number of lines, size of characters and symbols according to language versions and screens
2 versions of screen backgrounds available:resident factory version: Englishadditional customized version (language / customer),
customization using SFT2840:of the position of the system zones of the content of the text zone
Advanced UMI eng. S1000+.ppt6 /24
Advanced UMIAccess to measurements and parameters Series 20
Example: measurement loop
Advanced UMI eng. S1000+.ppt7 /24
Current operation (blue keys) Series 20
I1 I2 I3 RMS current measurementIo residual current, digital and bargraphI1 I2 I3 phase current bargraphIav1 2 3 average current valueImax1 2 3 peak current demandT1 à T8 temperature sensorV1 V2 V3 phase-to-neutral voltageU12,32,13 phase-to-phase voltageVo residual voltageF frequency
I1=162A RMS
I2=161A RMS
I3=163A RMS
Advanced UMI eng. S1000+.ppt8 /24
Current operation (white keys) Series 20
tripI1,I2,I3,Io tripping currents (phase and residual)unbalance unbalance ratio (negative sequence current)breaking dev. trip circuit supervision,nb of operation,
operating and charging timekA² cumulative breaking currentE thermal capacity percentage
time before starting authorizationst I stT motor starting current and timeNb st,waitT start inhibit time /nb of starts before inhibitionCh running hour counterVd positive sequence voltage
Advanced UMI eng. S1000+.ppt9 /24
Current operation (white keys)
Series 20
The «Alarm» key may be used to consult the 16 most recent unacknowledged alarms.
N.B. The alarms are not saved in the event of a power outage.
Advanced UMI eng. S1000+.ppt10 /24
Current operation (white keys)
Advanced UMI eng. S1000+.ppt11 /24
Current operation (white keys)
Advanced UMI eng. S1000+.ppt12 /24
Current operation (white keys)
I1=162A RMS
I2=161A RMS
I3=163A RMS
Advanced UMI eng. S1000+.ppt13 /24
Parameter and protection setting (blue keys)
main lang.,frequency,active group,remote setting,settings setting mode,modif, passwordssepam info type, versionMES input/output module optionmodbus communication parameter settingMSA analog output module optionCT / VT nb , type, ratio of sensorsO1 parameter setting output O1I / O input reading, output reading and testingLDC CB control, logic discr., choice of use of inputs
Advanced UMI eng. S1000+.ppt14 /24
Parameter and protection setting (blue keys)
Advanced UMI eng. S1000+.ppt15 /24
Parameter and protection setting (blue keys)
Advanced UMI eng. S1000+.ppt16 /24
Parameter and protection setting (blue keys)
Advanced UMI eng. S1000+.ppt17 /24
Parameter and protection setting (blue keys)
Advanced UMI eng. S1000+.ppt18 /24
Parameter and protection setting (blue keys)
Advanced UMI eng. S1000+.ppt19 /24
Advanced UMI Series 40
The same as with Sepam series 20, themeasurements and parameters are accessed via the metering, diagnosis, status and protection keys, but through a first menu which is then used to select a series of screens as presented in the diagram opposite.
Example: Measurement loop
Advanced UMI eng. S1000+.ppt20 /24
Advanced UMI Series 40 «Metering» menu
To begin with, thekey provides access to the metering menu.
The and keys are used to move the cursor up and down to select the chosen type of measurements.
Use the key again to scroll the chosen measurement loop.
Advanced UMI eng. S1000+.ppt21 /24
Advanced UMI Series 40«General settings» menu
The key is used to access to the menu containing the different general settings entered in Sepam.
The and keys areused to move the cursor up and down to select the chosen type of parameter.
Use the key again to scroll the chosen measurement loop.
Advanced UMI eng. S1000+.ppt22 /24
Advanced UMI Series 40«Protection» menu
The key provides access to the menu containing the different Sepam protection functions.
The and keys are used
to move the cursor up or down to
select the type of protection
function.
Use the key again to scroll
the chosen measurement loop.
Protections
I Phase
IDirectionnal
F.P
I Résidual
Voltage
Recloser
Advanced UMI eng. S1000+.ppt23 /24
Advanced UMI Series 40«Diagnosis» menu
The key provides access to the Sepam diagnosis menu.
The and keys are used
to move the cursor up and down
to select the chosen type of data.
Use the key again to scroll
the chosen measurement loop.
Diagnosis
Diagnosis
Trip -1
Trip -3
Trip 0
Trip -2
Trip -4
Advanced UMI eng. S1000+.ppt24 /24
Advanced UMI Series 40«Alarms» menu
The key provides access to the list of alarms.
Use the key again to display the last 16 alarms that have not been erased yet (date/time andname of alarm and faulty phase)
N.B. The alarms are saved in the event of a power failure
Alarms