Experience
with Custom
PowerApplications
for Critical
Manufacturing
Facilities
September 2003
-
8/12/2019 0309 Roberts
2/19
Medium Voltage UPS Systems
Systems commonly at 5, 1525 & 34.5 kV
Ratings up to 20,000 kVA / 16,000 kW
-
8/12/2019 0309 Roberts
3/19
PureWave Medium Voltage UPS
Configurations For 5,000 kVA and Larger
PES Available Ratings: 600 and 1200 ampsPES Available Ratings: 600 and 1200 amps
Available Voltages: 4.16, 6.6, 11.0, 13.8 and 22 kVAvailable Voltages: 4.16, 6.6, 11.0, 13.8 and 22 kV
-
8/12/2019 0309 Roberts
4/19
Building Block - 250 kW Power Module
-
8/12/2019 0309 Roberts
5/19
Merck Pharmaceutical Puerto RicoTypical Medium Voltage System Layout
4,000 kVA @ 4160V
Rating: 5000 kVA/ 4000 kW at 12.47 kV
-
8/12/2019 0309 Roberts
6/19
Power Electronic Switch
Modules stackedin series
Three modules per
pole for 15 kV
Three poles per
switchN+1 design for
reliability
-
8/12/2019 0309 Roberts
7/19
Medium Voltage System Power Electronic
Switch
Rating: 600 amps @ 5 or 15 kV
-
8/12/2019 0309 Roberts
8/19
Medium Voltage Source Transfer System
(STS)
Mechanical andElectro-Mechanical systems
Less than 3 seconds
Less than 2 cycles
Solid State Electronic systems 2-4 milliseconds (1/4 cycle)
-
8/12/2019 0309 Roberts
9/19
Electronic Source Transfer System
Seamlessly transfers in 1/4 cycle
Maintains load within CBEMA/ITIC
curve
Protects entire load from distribution
system disturbances
-
8/12/2019 0309 Roberts
10/19
Semiconductor FabAlbuquerque, NM
Rating: 2 x 10,000 kVA UPS @12.47 kV
With Source Transfer and Generators
-
8/12/2019 0309 Roberts
11/19
Semiconductor FabAlbuquerque, NM
Rating: 2 x 10,000 kVA UPS @12.47 kV
With Source Transfer and Generators
-
8/12/2019 0309 Roberts
12/19
Dynamic Voltage Restorer
(Sag Correction System)
Dynamic Voltage Restorers (DVRs) are being applied up
to protect loads up to 100 MVA
Capacitor energy storage provide voltage boost up to 50%
for up to 1 second on all three phases.
Most economical solution for voltage sags and swells forlarge loads
Ideal when only one source is available or with twosources when sags/swells are transmission related
-
8/12/2019 0309 Roberts
13/19
DVR Performance
Transmission
System Switching
or Fault Clearing
Fault occuring on
adjacent feed
Primary FeedersDistribution
Substation
DYNAMIC
VOLTAGE
RESTORER
RestoredVoltage
PU
+1
0
-1
=+
PU
+1
0
-1
Line VoltageWith Sag
CompensatingVoltage
PU
+1
0
-1
Protected
Sensitive Load
-
8/12/2019 0309 Roberts
14/19
Dynamic Voltage Restorer (DVR)
Semiconductor Fab Chandler, AZ
Worlds largest DVRinstallation
Two sets of twin 5- or 6-MVADVR systems
Substation dedicated to twomajor semiconductor fab
plants
12.5-kV substation fed bythree 69-kV overhead lines;five 50-MVA transformers
-
8/12/2019 0309 Roberts
15/19
Typical DVR Performance
-
8/12/2019 0309 Roberts
16/19
Dynamic Voltage Restorer (DVR)
Large Paper Mill Critical Load Bus ProtectionLarge Paper Mill Critical Load Bus Protection
UPM
Continuous process coated
paper production
47MVA total plant load;
8.3MVA critical
23 synchronized motor drives
Largest 1300 hp
DVR provides critical loadbus protection for orderly
shutdown to avoid costly web
damage.
Low Voltage PureWave UPS System
-
8/12/2019 0309 Roberts
17/19
Low Voltage PureWave UPS System
Single Line Diagram w/ Generator
-
8/12/2019 0309 Roberts
18/19
Precision ManufacturerNewark, NJ
2,500 kVA UPS @ 480Vwith backup generator
di l li i
-
8/12/2019 0309 Roberts
19/19
Medical ClinicSoutheastern US
313 kVA UPS @ 480V