07915a0211-po
TRANSCRIPT
-
7/31/2019 07915a0211-po
1/26
R. Shankar Raju
Roll No: 07915A0211IV / IV II Semester
EEE, V.J.I.T
POWERFORMER
-
7/31/2019 07915a0211-po
2/26
INTRODUCTION
Powerformer is a 3 phase AC
generator which is capable of
generating output voltage ranging from
30 kv to 400 kv that can be directlyconnected to the high voltage
transmission grid by replacing the
generator and step-up power
transformer used in todays powerplant.
-
7/31/2019 07915a0211-po
3/26
FEATURES
It can produce high output voltage rangingfrom 30 kv to 400 kv
High efficiency, Highly reliable
Improves reactive power output andoverload capacity of the system
Robust in construction
-
7/31/2019 07915a0211-po
4/26
Schematic Diagram
a) Conventional plant with step uptransformer
b) Same plant Using power former
-
7/31/2019 07915a0211-po
5/26
Design Powerformer has a rotor design similar to a
conventional generator
The difference in design of stator of aPowerformer and a conventional generator
lies in its stator windings
Powerformer stator uses a high voltage
cables instead of a square cross section
wires for its winding.
-
7/31/2019 07915a0211-po
6/26
Cables Used In Stator Winding Of
Powerformer The power cable
consists of a stranded
conductor, solid
insulation and two
semi conducting layers
The insulation material
is cross-linked
polyethylene (XLPE), a
material successfully
used in high-voltage
power cables
-
7/31/2019 07915a0211-po
7/26
Electric Field Distribution
The two semi
conducting layers, one
surrounds the
conductor and the
other outside theinsulation, the semi
conducting layers
serves as an equi-
potential surface thatforces the electric field
to be uniform around
the circumference
-
7/31/2019 07915a0211-po
8/26
Stator ViewSectional View
-
7/31/2019 07915a0211-po
9/26
Type Faults And Their Behaviour
There are mainly two type of faults internal andexternal
For a conventional system the internal fault refers
to a fault that occurs at the terminals of thegenerator, and an external fault is a fault thatoccurs at the high-voltage side of the step-uptransformer
For a Powerformer system, internal and externalfaults are basically the same as a Powerformer thatis connected directly to the high-voltage bus-bar inthe generating station
-
7/31/2019 07915a0211-po
10/26
External Faults
The fault currents from a Powerformer at externalthree-phase short circuits will be of the samemagnitude as the fault current from theconventional unit.
External single-phase ground faults will be lowerthan that from the conventional unit. The reason isthat the neutral point of a Powerformer is isolatedfrom ground while the neutral point of the step-up
transformer of the conventional generator is solidlygrounded.
-
7/31/2019 07915a0211-po
11/26
Internal Faults
The internal three-phase short-circuit current of aPowerformer is less than that of the conventionalgenerator due to its higher output voltage.
In the case of the internal two-phase-to-groundand the internal phase-to-phase faults, the faultcurrent in a conventional generating unit will besubstantially higher than the fault current in thePowerformer.
For the internal single phase-to-ground internalfault, the fault current in a conventional generatingunit is much lower than that of the Powerformerdue to the high impedance grounding of theneutral of the conventional generator
-
7/31/2019 07915a0211-po
12/26
Comparision Of Fault Currents
-
7/31/2019 07915a0211-po
13/26
Cooling System
The cooling system of the Powerformer stator core is alsobased on a new concept . This is due to the low current in thecables of the stator winding and the lower ratio betweenohmic and iron losses than that for a conventional generator.Accordingly, most of the heat is generated in the stator core,which is grounded. This fact greatly simplifies the cooling
system. The new cooling system is an indirect system thatcools the stator core by axially inserted water pipes made ofhigh density XLPE. Thus, the stator has no radial air coolingducts, and this leads to a homogeneous stator core. Thismakes the gross length of the stator shorter, the efficiencyimproves, and the stator assembly is more convenient,
especially with respect to the cable installation through theslots. As the water cooling is carried out at ground potential,there is no need for de-ionized water as in the conventionalwater-cooled stator windings. Ordinary tap water may beused for the cooling of the Powerformer stator core.
-
7/31/2019 07915a0211-po
14/26
First Powerformer Installation
The worlds first powerformer was installed
at porjus hydropower centre on the lule
river in northern Sweden rated at 11 MVA,
45 kV, and 600 rpm
The data from the two units installed at
porjus is shown below
-
7/31/2019 07915a0211-po
15/26
Compared Parameters Generator Powerformer
App. Power (MVA) 11 11
Voltage (kV) 10 45Current (A) 635 141
Speed (rpm) 429 600
Length (mm) 750 1450
Stator Outer d (mm) 3100 3050No of Cables per Slot - 12
Weight of Stator (ton) 11.5 34.5
Weight of Rotor (ton) 23.0 22.8
Xdi 0.98 0.79Xdu 0.25 0.22
Xdu 0.16 0.17
Efficiency 97.2% 97.6%
-
7/31/2019 07915a0211-po
16/26
Development Of Powerformer Rated
Voltage
-
7/31/2019 07915a0211-po
17/26
Existing Powerformer Generators
-
7/31/2019 07915a0211-po
18/26
Advantages
High efficiency.
Reactive power capability.
Low maintenance cost.
Reduced environmental impact.
-
7/31/2019 07915a0211-po
19/26
Efficiency
Powerformer plants have 0.5-1.5 % less activelosses than conventional plants.
In general, a power plant with Powerformer has
0.5-1.5 % higher efficiency than a conventionalpower plant.
For example a 120 MW plant with Powerformerplant with 1.5 efficiency will produce 1.8 MW morepower than a conventional plant which increasesthe overall economy of the plant.
-
7/31/2019 07915a0211-po
20/26
Reactive Power Capability
The generation of reactive power is needed
to compensate for the reactive power losses
in the transmission networks. WithPowerformer the reactive power losses in
the step-up transformer is eliminated.
-
7/31/2019 07915a0211-po
21/26
Low Maintenance Cost
With Powerformer, every thing tothe right of plane A-A can beeliminated, leading to powerplants with fewer components,For example Powerformer
technology eliminates the step-uptransformer, the handling of oils,generator circuit breaker andpart of the bus-bar system. Fewercomponents means fewer sourcesof potential faults and thusconsiderably lower maintenanceand maintenance costs.
-
7/31/2019 07915a0211-po
22/26
Reduced Environmental Impact
A 150 MVA Powerformerversus a conventional 136MVA generator, breaker andtransformer system. Alifetime of 30 years wasassumed, the environmental
impact is expressed inEnvironmental Load Unit(ELU), a high impact on theenvironment gives large ELUnumber. The results areshown in Figure (6), whichshows that the Powerformersystem has lowerenvironmental impact than atraditional system during allof its life time phases, this ismainly because Powerformerhas less energy losses.
-
7/31/2019 07915a0211-po
23/26
Comparison between a conventional
system and a power former systemConventional system Powerformer system
Transformer None
MV bus-bar None
Generator switches None
Space & volume = 1 Space & volume < 1
Many parts Few parts
Weight = 1 Weight < 1
Overload capacity = 1 Overload capacity > 1
Reactive power capability = 1 Reactive power capability > 1
-
7/31/2019 07915a0211-po
24/26
Disadvantages
Powerformer output voltage is limited by the
AC power cable and the cable accessories
(terminations and joints) used in stator
winding
-
7/31/2019 07915a0211-po
25/26
Conclusion
Powerformer (high-voltage generator) has
been studied through out this seminar; this
new concept provides the possibility to
directly connect a rotating machine to thehigh-voltage power grid without going via a
step-up transformer resulting in higher
efficiency. Powerformers enable very clean
and compact power plants that are not onlyeconomical, reliable, and environment
friendly but also more efficient than
conventional ones.
-
7/31/2019 07915a0211-po
26/26
ThankYou