07915a0211-po

Upload: venky123456789

Post on 05-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 07915a0211-po

    1/26

    R. Shankar Raju

    Roll No: 07915A0211IV / IV II Semester

    EEE, V.J.I.T

    POWERFORMER

  • 7/31/2019 07915a0211-po

    2/26

    INTRODUCTION

    Powerformer is a 3 phase AC

    generator which is capable of

    generating output voltage ranging from

    30 kv to 400 kv that can be directlyconnected to the high voltage

    transmission grid by replacing the

    generator and step-up power

    transformer used in todays powerplant.

  • 7/31/2019 07915a0211-po

    3/26

    FEATURES

    It can produce high output voltage rangingfrom 30 kv to 400 kv

    High efficiency, Highly reliable

    Improves reactive power output andoverload capacity of the system

    Robust in construction

  • 7/31/2019 07915a0211-po

    4/26

    Schematic Diagram

    a) Conventional plant with step uptransformer

    b) Same plant Using power former

  • 7/31/2019 07915a0211-po

    5/26

    Design Powerformer has a rotor design similar to a

    conventional generator

    The difference in design of stator of aPowerformer and a conventional generator

    lies in its stator windings

    Powerformer stator uses a high voltage

    cables instead of a square cross section

    wires for its winding.

  • 7/31/2019 07915a0211-po

    6/26

    Cables Used In Stator Winding Of

    Powerformer The power cable

    consists of a stranded

    conductor, solid

    insulation and two

    semi conducting layers

    The insulation material

    is cross-linked

    polyethylene (XLPE), a

    material successfully

    used in high-voltage

    power cables

  • 7/31/2019 07915a0211-po

    7/26

    Electric Field Distribution

    The two semi

    conducting layers, one

    surrounds the

    conductor and the

    other outside theinsulation, the semi

    conducting layers

    serves as an equi-

    potential surface thatforces the electric field

    to be uniform around

    the circumference

  • 7/31/2019 07915a0211-po

    8/26

    Stator ViewSectional View

  • 7/31/2019 07915a0211-po

    9/26

    Type Faults And Their Behaviour

    There are mainly two type of faults internal andexternal

    For a conventional system the internal fault refers

    to a fault that occurs at the terminals of thegenerator, and an external fault is a fault thatoccurs at the high-voltage side of the step-uptransformer

    For a Powerformer system, internal and externalfaults are basically the same as a Powerformer thatis connected directly to the high-voltage bus-bar inthe generating station

  • 7/31/2019 07915a0211-po

    10/26

    External Faults

    The fault currents from a Powerformer at externalthree-phase short circuits will be of the samemagnitude as the fault current from theconventional unit.

    External single-phase ground faults will be lowerthan that from the conventional unit. The reason isthat the neutral point of a Powerformer is isolatedfrom ground while the neutral point of the step-up

    transformer of the conventional generator is solidlygrounded.

  • 7/31/2019 07915a0211-po

    11/26

    Internal Faults

    The internal three-phase short-circuit current of aPowerformer is less than that of the conventionalgenerator due to its higher output voltage.

    In the case of the internal two-phase-to-groundand the internal phase-to-phase faults, the faultcurrent in a conventional generating unit will besubstantially higher than the fault current in thePowerformer.

    For the internal single phase-to-ground internalfault, the fault current in a conventional generatingunit is much lower than that of the Powerformerdue to the high impedance grounding of theneutral of the conventional generator

  • 7/31/2019 07915a0211-po

    12/26

    Comparision Of Fault Currents

  • 7/31/2019 07915a0211-po

    13/26

    Cooling System

    The cooling system of the Powerformer stator core is alsobased on a new concept . This is due to the low current in thecables of the stator winding and the lower ratio betweenohmic and iron losses than that for a conventional generator.Accordingly, most of the heat is generated in the stator core,which is grounded. This fact greatly simplifies the cooling

    system. The new cooling system is an indirect system thatcools the stator core by axially inserted water pipes made ofhigh density XLPE. Thus, the stator has no radial air coolingducts, and this leads to a homogeneous stator core. Thismakes the gross length of the stator shorter, the efficiencyimproves, and the stator assembly is more convenient,

    especially with respect to the cable installation through theslots. As the water cooling is carried out at ground potential,there is no need for de-ionized water as in the conventionalwater-cooled stator windings. Ordinary tap water may beused for the cooling of the Powerformer stator core.

  • 7/31/2019 07915a0211-po

    14/26

    First Powerformer Installation

    The worlds first powerformer was installed

    at porjus hydropower centre on the lule

    river in northern Sweden rated at 11 MVA,

    45 kV, and 600 rpm

    The data from the two units installed at

    porjus is shown below

  • 7/31/2019 07915a0211-po

    15/26

    Compared Parameters Generator Powerformer

    App. Power (MVA) 11 11

    Voltage (kV) 10 45Current (A) 635 141

    Speed (rpm) 429 600

    Length (mm) 750 1450

    Stator Outer d (mm) 3100 3050No of Cables per Slot - 12

    Weight of Stator (ton) 11.5 34.5

    Weight of Rotor (ton) 23.0 22.8

    Xdi 0.98 0.79Xdu 0.25 0.22

    Xdu 0.16 0.17

    Efficiency 97.2% 97.6%

  • 7/31/2019 07915a0211-po

    16/26

    Development Of Powerformer Rated

    Voltage

  • 7/31/2019 07915a0211-po

    17/26

    Existing Powerformer Generators

  • 7/31/2019 07915a0211-po

    18/26

    Advantages

    High efficiency.

    Reactive power capability.

    Low maintenance cost.

    Reduced environmental impact.

  • 7/31/2019 07915a0211-po

    19/26

    Efficiency

    Powerformer plants have 0.5-1.5 % less activelosses than conventional plants.

    In general, a power plant with Powerformer has

    0.5-1.5 % higher efficiency than a conventionalpower plant.

    For example a 120 MW plant with Powerformerplant with 1.5 efficiency will produce 1.8 MW morepower than a conventional plant which increasesthe overall economy of the plant.

  • 7/31/2019 07915a0211-po

    20/26

    Reactive Power Capability

    The generation of reactive power is needed

    to compensate for the reactive power losses

    in the transmission networks. WithPowerformer the reactive power losses in

    the step-up transformer is eliminated.

  • 7/31/2019 07915a0211-po

    21/26

    Low Maintenance Cost

    With Powerformer, every thing tothe right of plane A-A can beeliminated, leading to powerplants with fewer components,For example Powerformer

    technology eliminates the step-uptransformer, the handling of oils,generator circuit breaker andpart of the bus-bar system. Fewercomponents means fewer sourcesof potential faults and thusconsiderably lower maintenanceand maintenance costs.

  • 7/31/2019 07915a0211-po

    22/26

    Reduced Environmental Impact

    A 150 MVA Powerformerversus a conventional 136MVA generator, breaker andtransformer system. Alifetime of 30 years wasassumed, the environmental

    impact is expressed inEnvironmental Load Unit(ELU), a high impact on theenvironment gives large ELUnumber. The results areshown in Figure (6), whichshows that the Powerformersystem has lowerenvironmental impact than atraditional system during allof its life time phases, this ismainly because Powerformerhas less energy losses.

  • 7/31/2019 07915a0211-po

    23/26

    Comparison between a conventional

    system and a power former systemConventional system Powerformer system

    Transformer None

    MV bus-bar None

    Generator switches None

    Space & volume = 1 Space & volume < 1

    Many parts Few parts

    Weight = 1 Weight < 1

    Overload capacity = 1 Overload capacity > 1

    Reactive power capability = 1 Reactive power capability > 1

  • 7/31/2019 07915a0211-po

    24/26

    Disadvantages

    Powerformer output voltage is limited by the

    AC power cable and the cable accessories

    (terminations and joints) used in stator

    winding

  • 7/31/2019 07915a0211-po

    25/26

    Conclusion

    Powerformer (high-voltage generator) has

    been studied through out this seminar; this

    new concept provides the possibility to

    directly connect a rotating machine to thehigh-voltage power grid without going via a

    step-up transformer resulting in higher

    efficiency. Powerformers enable very clean

    and compact power plants that are not onlyeconomical, reliable, and environment

    friendly but also more efficient than

    conventional ones.

  • 7/31/2019 07915a0211-po

    26/26

    ThankYou