1 detector electronics corporation eagle quantum premier system training july 2006
TRANSCRIPT
1
DETECTOR ELECTRONICS CORPORATION
EAGLE QUANTUM PREMIEREAGLE QUANTUM PREMIER
SYSTEM TRAININGSYSTEM TRAINING
July 2006July 2006
2
• WelcomeWelcome• AgendaAgenda• IntroductionsIntroductions• Systems OverviewSystems Overview
Systems Class 102
3
Day 1Day 1• EQP OverviewEQP Overview• EQP Flame DetectionEQP Flame Detection• EQP Gas DetectionEQP Gas Detection• Break for LunchBreak for Lunch• EQP SystemEQP System• Q & AQ & A• Hardware ExerciseHardware Exercise
Agenda
4
Day 2Day 2• S3 Software IntroductionS3 Software Introduction• S3 Software ExerciseS3 Software Exercise• Break for LunchBreak for Lunch• Logic ProgrammingLogic Programming• Product ApprovalProduct Approval• Q & AQ & A
Agenda
5
Day 3Day 3• Redundancy and DevelopmentRedundancy and Development• DiscussionDiscussion• SupportSupport
Agenda
6
• DefinitionDefinition• GoalsGoals• Market Structure & System TypesMarket Structure & System Types• Organization CapabilitiesOrganization Capabilities• Eagle Quantum Premier Brief OverviewEagle Quantum Premier Brief Overview
Systems Group Overview
7
Definition
• What is a Systems Project?What is a Systems Project?• An Engineered solution that includesAn Engineered solution that includes
• Any combination of flame and/or gas detectors or other Any combination of flame and/or gas detectors or other field devicesfield devices
• A signal receiver/controllerA signal receiver/controller• Any combination of output signals and/or devices required Any combination of output signals and/or devices required
by the customerby the customer• A system enclosure or panelA system enclosure or panel• Power source/battery back-upPower source/battery back-up• Custom DocumentationCustom Documentation
8
Group Goals
• To be the world’s leading supplier of-To be the world’s leading supplier of-• Conventional Fire & Gas Detection SystemsConventional Fire & Gas Detection Systems• Addressable Fire & Gas Detection SystemsAddressable Fire & Gas Detection Systems• Fire Suppression & Emergency Shutdown SystemsFire Suppression & Emergency Shutdown Systems• Special & Custom Systems Special & Custom Systems
9
F & G Systems Market Structure
BechtelBechtelBrown & RootBrown & Root
ABBABBSiemensSiemens
HoneywellHoneywell
Dooley TackeberryDooley TackeberryHillerHiller
WilsonWilson
Hima, TriconexHima, TriconexICS, WormaldICS, Wormald
SilvertechSilvertech
High HazardHigh HazardComponentComponentSuppliersSuppliers
MICC = Main Instrument Controls Contractor
TOTAL PROJECT/EPC
DEVICES
MICC
F & G SYSTEM
Supplied byDet-TronicsG
row
th w
ith
gre
ater
sys
tem
s o
ffer
ing
ESD SYSTEM
Growth with greater device offering
EPC = Engineering Procurement & Construction
Det-Tronics Systems MarketGrowth Plan
10
Typical Plant Control Systems
Plant SCADA or Distributed Control System
Plant ESD - Emergency Shut Down
Plant SIS - Fire Alarm, Flame Detection,Gas Detection & Suppression System
Stand-alone systems
11
Logic Solver/PLC/Panel by others
Conventional System Configurations
• Home-run Field Wiring
12
Addressable Fire & Gas System
North American Certifications
FM 3260-2000 Flame performance
FM 6310/6320 Gas performance
NFPA 72 1999 National Fire alarm code
CSA - gas performance and Haz locations
European Certifications
94/9/EC ATEX
EN50081-1 & 2 Electromagnetic compatibility
EN50130-4 Immunity of fire, intruder and social alarm systems
EN 50270 Detection and measurement of gases
Ports• RS-485 serial Link (Modbus RTU)• Configuration (serial port)• Redundant media ControlNet
MIR Fire Detection
UV/IR Fire Detection
IR Fire Detection
Supervised Inputs Heats, Smokes and MAC’s
Agent Release
DCIO Module
PRESS HERETRYKK HERKNUS GLASSET
BREAK GLASS
BN- 300BRANNALARM
Tilpasningsenhet
FIRE ALARM
Interface unit
Nr.
No.
UV Fire Detection
HC Gas Detection
DCIO Module
4-20mA input
Toxic Gas Detection
Premier Controller
13
Capabilities
• Project ManagementProject Management
• USA, Singapore, and UKUSA, Singapore, and UK
• Project EngineeringProject Engineering
• USA, SingaporeUSA, Singapore
• Systems StagingSystems Staging
• USA (Minneapolis and Houston), SingaporeUSA (Minneapolis and Houston), Singapore
• Field ServiceField Service
• USA (Minneapolis and Houston), London, France USA (Minneapolis and Houston), London, France Singapore, & China plus representative Singapore, & China plus representative organizationorganization
14
Capabilities
• Total Safety SolutionsTotal Safety Solutions• Fire Detection /Mitigation systems:Fire Detection /Mitigation systems:
• Fire DetectionFire Detection• Gas DetectionGas Detection• Fire Suppression systemsFire Suppression systems
• COCO22, Water Mist, FM200, Water Mist, FM200
• Emergency Shutdown (ESD) SystemsEmergency Shutdown (ESD) Systems• Safety controllersSafety controllers
• Triconex, HIMA, others• Fire Alarm SystemsFire Alarm Systems
• Eagle Quantum PremierEagle Quantum Premier• Fire alarm panels (Fire alarm panels (Pegasys, KI 1019, FENWAL, Vega)Pegasys, KI 1019, FENWAL, Vega)
15
Capabilities
• System SupportSystem Support• Power Supply systems (batteries…etc)Power Supply systems (batteries…etc)• Human Machine Interface (HMI) systemsHuman Machine Interface (HMI) systems
• Documentation - Documentation - • Non-standard/custom requirementsNon-standard/custom requirements• Manufacturing Record Books, Test Plans,Manufacturing Record Books, Test Plans,
• SupportSupport• Field ServiceField Service• Installation SupervisionInstallation Supervision• FAT/SATFAT/SAT• In-house ExpertiseIn-house Expertise
16
Organization Chart
Simion PateDirector of Projects &
Systems
Jon HodappManager of
Projects
Peter RousseauManager of
ProjectEngineering
Steve WeihrauchManager of
Proposals andContracts
Gary WittnebelSoftware Engineer
(MN)
Kevin EliasonProject Engineer
(MN)
Jeff AltProject Engineer
(MN)
Peter WilkeProject Manager
(MN)
Barbara SorichProjects
Administrator(MN)
Mike SealyProposals (MN)
Jon DamonProposals (MN)
ContractorT&C's Review
Proposals and Contracts Project ManagementProject Engineering
Chris TaylorProposals (Tx)
Carter WhiteFire ProtectionEngineer (Tx)
Steve Moore PEFire ProtectionEngineer (MN)
Ed MenchacaProject Engineer
(Tx)
Randy ScottCAD operator
(Tx)
MNHoward AndersonSteve Silverthorn
TXRandy Hardy
Jarred ThibedeuxProject Engineer
(Tx)
Richard SkoneBusiness Development
Manager
Jim VogelVP Sales and Marketing
Brett Noblet(U.K.)
Proposals
CC Goh(Singapore)Proposals
Cliff AndersonGlobal Marketing Manager
Roger ThompsonSnr.Project
Manager (MN)
Field Service
Mike BraggSystems Marketing
Manager (MN)
Mike PolingSolutions Marketing
Manager (TX)
Technical SupportBernie Stinger
U.K.Dave Barrett
SingaporeClarence Peck
Nick Eleda
TBDProject Manager
(UK)
TBDProject Manager
(Singapore)
ChinaHuang Zhao Yang
17
Systems Support
Minneapolis
CAPABILITIESWorldwide Coordination• Sales• Proposals• Proj. Mgmt• System Integration• FAT
Singapore
CAPABILITIES• Sales• Proposals• Proj. Mgmt• System Integration
• Subcontract• FAT
UK
CAPABILITIES• Sales •Proposals•Proj. Mgmt• FAT
Houston
CAPABILITIES• Sales• Proposals• Proj. Mgmt• System Integration• FAT
18
Eagle Quantum Premier
System Overview and FeaturesSystem Overview and Features
Addressable - Hazardous Location
20
Det-Tronics - Eagle Systems Evolution
• Evolved to meet our customer’s needsEvolved to meet our customer’s needs• Eagle2000™ Hazardous Event Monitoring SystemEagle2000™ Hazardous Event Monitoring System
• Introduced 1993Introduced 1993• Eagle Quantum Eagle Quantum
• Introduced 1996Introduced 1996• Eagle Quantum PremierEagle Quantum Premier
• Introduced 2003Introduced 2003
21
EQP - Description
• Eagle Quantum Premier (EQP) System-Eagle Quantum Premier (EQP) System-• is the latest generation in the Eagle addressable system familyis the latest generation in the Eagle addressable system family• combines “fire detection and extinguishing agent release” and combines “fire detection and extinguishing agent release” and
“hazardous gas monitoring” in one complete package“hazardous gas monitoring” in one complete package• is intended for use in hazardous locationsis intended for use in hazardous locations• is designed to meet the requirements of global approval agenciesis designed to meet the requirements of global approval agencies• supports up to 246 devicessupports up to 246 devices• supports a LON length of 2000 meters with base systemsupports a LON length of 2000 meters with base system• can be expanded using network extenders to a max LON distance can be expanded using network extenders to a max LON distance
of 10,000 metersof 10,000 meters
22
EQP Addressable Fire & Gas System246 node maximum
North American Certifications
FM 3260-2000 Flame performance
FM 6310/6320 Gas performance
NFPA 72 1999 National Fire alarm code
CSA - gas performance and Haz locations
European Certifications
94/9/EC ATEX
EN50081-1 & 2 Electromagnetic compatibility
EN50130-4 Immunity of fire, intruder and social alarm systems
EN 50270 Detection and measurement of gases
UV/IR Fire Detection X5200
IR Fire DetectionX9800
Supervised Inputs Heats, Smokes and MAC’s
Agent ReleasePRESS HERETRYKK HER
KNUS GLASSET
BREAK GLASS
BN- 300BRANNALARM
Tilpasningsenhet
FIRE ALARM
Interface unit
Nr.
No.
UV Fire DetectionX2200
Premier Controller
Operator Interface Station
running S3 softwareVer 2.8
Ports• Configuration (serial port) • RS-485 serial Link (Modbus RTU)• Redundant media ControlNet
OPC option
MIR Fire DetectionX3301
24 vdc power supply
Battery PSM
DCIOModule
I/O Modules•Relay•AIM•IPM
HC Gas DetectionEclipse
NetworkExtender
ARM
Signal / Audible Devices
SAM
IDC
SupervisedDigitalinputs
Toxic Gas DetectionDCU / DCUEX
23
EQP - Controller
• The system consists of a The system consists of a “multi-channel programmable “multi-channel programmable controller” and a number of controller” and a number of addressable microprocessor addressable microprocessor based field devices.based field devices.
• Scrolling alphanumeric display Scrolling alphanumeric display provides status informationprovides status information
• Flexible communication optionsFlexible communication options• Significantly smaller, yet far Significantly smaller, yet far
more powerful than Eagle more powerful than Eagle Quantum system controllerQuantum system controller
24
EQP - Field Devices - Legacy
• Supports Eagle Quantum “Legacy” Supports Eagle Quantum “Legacy” field devices.field devices.
• EQ2500ARM Agent Release Module.EQ2500ARM Agent Release Module.• EQ2500SAM Signal Audible module.EQ2500SAM Signal Audible module.• EQ2200IDC Initiating Device Circuit EQ2200IDC Initiating Device Circuit
module.module.• EQ2200IDCGF Ground Fault monitor.EQ2200IDCGF Ground Fault monitor.• EQ2200DCU & EQ2200DCUEX EQ2200DCU & EQ2200DCUEX
Digital Communication Units.Digital Communication Units.• EQ2400 Network ExtenderEQ2400 Network Extender• EQ2100 Power Supply MonitorEQ2100 Power Supply Monitor
25
EQP Field Devices - Gas Detector
• PIRECL Pointwatch EclipsePIRECL Pointwatch Eclipse
• Combustible hydrocarbon detectorCombustible hydrocarbon detector
• Software programmable for various Software programmable for various gases: Methane,Ethanegases: Methane,Ethane
Propane, Butane, Ethylene, Propane, Butane, Ethylene, PropylenePropylene
• Supports handheld interrogator Supports handheld interrogator connection in field using HART connection in field using HART protocol.protocol.
26
EQP – Field Devices - Flame
• X-Series is EQP readyX-Series is EQP ready• UV/IR (X5200)UV/IR (X5200)• UV (X2200)UV (X2200)• IR (X9800)IR (X9800)• Multispectrum IR (X3301)Multispectrum IR (X3301)
27
• Improved ARC rejection Improved ARC rejection algorithmalgorithm
• 1850 –2450 Angstroms solar 1850 –2450 Angstroms solar blindblind
• Multiple fuel verifiedMultiple fuel verified
Ultraviolet Flame Detector (X2200)
28
Single Frequency Infrared Flame Detector (X9800)
• Time Domain Signal Time Domain Signal Analysis, IR signal Analysis, IR signal processingprocessing• Analyzes the raw IR Analyzes the raw IR
sensor signal sensor signal “randomness”“randomness”
• Rejects signals that do Rejects signals that do not meet randomness not meet randomness criteriacriteria
• 4.45 micron solar blind4.45 micron solar blind• Quick fire responseQuick fire response• Heated opticHeated optic• Multiple fuel verifiedMultiple fuel verified
29
• Dual signal processing UVIRDual signal processing UVIR• ARC rejection algorithm, UV ARC rejection algorithm, UV
signalsignal• Time Domain Signal Analysis, Time Domain Signal Analysis,
IR signal processingIR signal processing
• 1850-2450 angstroms solar 1850-2450 angstroms solar blindblind
• 4.45 micron solar blind4.45 micron solar blind• Quick fire responseQuick fire response• Heated opticHeated optic• Multiple fuel verifiedMultiple fuel verified
Ultraviolet Infrared Flame Detector (X5200)
30
• Multiple PatentsMultiple Patents• WavelengthWavelength• AlgorithmAlgorithm• Digital signal ProcessingDigital signal Processing
• Heated opticsHeated optics• Extended Cone of Vision Extended Cone of Vision • Combines the longest Combines the longest
detection range with the best detection range with the best false alarm rejection false alarm rejection capabilitiescapabilities
• Multiple fuel verified, lowest Multiple fuel verified, lowest cost of coverage all fuelscost of coverage all fuels
X3301 Multispectrum Infrared Flame Detector
31
Flame Detectors Optical Integrity
• Calibrated MAG-Oi, no test lamp required! Calibrated MAG-Oi, no test lamp required! • Automatic and manual optical integrity test verified to perform a Automatic and manual optical integrity test verified to perform a
calibrated test of the detector operation.calibrated test of the detector operation.• Manual and MAG-Oi perform system activationManual and MAG-Oi perform system activation
32
EQP – Field Devices - Flexible
• EQ3700DCIOEQ3700DCIO• Eight channel Direct Current Eight channel Direct Current
Input/Output module.Input/Output module.• EQ 3720RMEQ 3720RM
• Eight channel relay output moduleEight channel relay output module• EQ3710AIMEQ3710AIM
• Eight channel Analog input Eight channel Analog input modulemodule
• EQ3720IPMEQ3720IPM• Intelligent Protection ModuleIntelligent Protection Module
33
EQP CONTROLLER
Dual Media
ControlNet
Interface
(Optional)
Future
Expansion
Capabilities
Onboard
Serial
Interface
8 Dry Contact Inputs
8 Relay Outputs
Configuration
PC
Modbus RTU
Master
Field Device Network (LON)
Field Device Network (LON)
RS-232
RS-485
EQP – Controller Details
• Controller logic processing 10X faster Controller logic processing 10X faster than LCU.than LCU.
• New LON transceivers process field New LON transceivers process field data 2X faster than LCU.data 2X faster than LCU.
• 8 onboard dry contact inputs.8 onboard dry contact inputs.
• 8 onboard relay outputs.8 onboard relay outputs.
• Dedicated fault relay.Dedicated fault relay.
• Dual media Control-Net option for Dual media Control-Net option for Allen-Bradley compatibility.Allen-Bradley compatibility.
• Future Expansion capability.Future Expansion capability.
• 2 onboard serial interfaces for 2 onboard serial interfaces for configuration and data exchange.configuration and data exchange.
Fault Relay
34
EQP System Overview
• EQP Controller is the start and end of the network.EQP Controller is the start and end of the network.
• Local Operating Network & Signaling Line Circuit Local Operating Network & Signaling Line Circuit (LON/SLC)(LON/SLC)
• Up to 2000 meters and 60 devices in base Up to 2000 meters and 60 devices in base configuration.configuration.
• Power Supply Monitor, power supplies, battery Power Supply Monitor, power supplies, battery charger, etc.charger, etc.
EQPCONTROLLER
AB MB
DI DO
Power SupplyMonitor
BatteryCharger & PS
35
EQP System Overview - Loop
EQPCONTROLLER
AB MB
DI DO
• LON Diagnostics and Integrity testing done by LON Diagnostics and Integrity testing done by the controller.the controller.
• Network extenders allow for the LON/SLC to Network extenders allow for the LON/SLC to grow.grow.• An additional 2000 meters distance per An additional 2000 meters distance per
extender.extender.• An additional 60 devices per extenderAn additional 60 devices per extender
NetworkExtender
Power SupplyMonitor
BatteryCharger & PS
36
EQP System Overview - Flame
• Flame detection from a full range of technologies.Flame detection from a full range of technologies.
• IDC Provides two channels for supervised inputs from heat IDC Provides two channels for supervised inputs from heat detectors, smoke detectors, etc.detectors, smoke detectors, etc.
• Quantum UV detector.Quantum UV detector.
• Quantum UV/IR detectorQuantum UV/IR detector
• X3301 Multi-spectrum IR detectorX3301 Multi-spectrum IR detector
• NFP IR detectorNFP IR detector
EQPCONTROLLER
AB MB
DI DO
Power SupplyMonitor
BatteryCharger & PS
Initiating DeviceCircuits (IDC)
X3301 FlameDetector
UV/IR FlameDetectorX5200
UV FlameDetectorX2200
NetworkExtender
IR FlameDetectorX9800
UV High TempDetectorX2200
37
EQP System Overview - Gas
• Gas detection from a full range of technologies.Gas detection from a full range of technologies.
• PIRECL provides IR hydrocarbon detectionPIRECL provides IR hydrocarbon detection
• OPECL open path OPECL open path
• DCU provides 4-20 ma input capability for toxics and DCU provides 4-20 ma input capability for toxics and special purpose detectors.special purpose detectors.
• DCUEX provides input capability for catalytic DCUEX provides input capability for catalytic sensors.sensors.
EQPCONTROLLER
AB MB
DI DO
Power SupplyMonitor
BatteryCharger & PS
Initiating DeviceCircuits (IDC)
X3301 FlameDetector
UV/IR FlameDetector
UV FlameDetector
NetworkExtender
IR FlameDetector
Digital Com. UnitDCU
Eclipse PIRGas Detector
Digital Com. UnitDCUEX
38
EQP System Overview - Flex I/O
• Supervised output capabilities for signaling and Supervised output capabilities for signaling and releasing requirements.releasing requirements.
• Signal Audible Module (SAM) provides two Signal Audible Module (SAM) provides two independent supervised output channels.independent supervised output channels.
• Agent Release Module (ARM) provides supervision Agent Release Module (ARM) provides supervision and control of one or two releasing solenoids.and control of one or two releasing solenoids.
EQPCONTROLLER
AB MB
DI DO
Power SupplyMonitor
BatteryCharger & PS
Initiating DeviceCircuits (IDC)
X3301 FlameDetector
UV/IR FlameDetector
UV FlameDetector
NetworkExtender
IR FlameDetector
Digital Com. UnitDCU
Eclipse PIRGas Detector
Digital Com. UnitDCUEX
Signal AudibleModule (SAM)
Agent ReleaseModule (ARM)
39
EQP System Overview - Flex I/O
• High density I/O Modules.High density I/O Modules.
– DCIO provides eight channels that can be DCIO provides eight channels that can be configured as either inputs or outputs.configured as either inputs or outputs.
– Relay module provides eight non-supervised Relay module provides eight non-supervised relay outputs.relay outputs.
– AIM eight channel analog input moduleAIM eight channel analog input module
– IPM intelligent protection moduleIPM intelligent protection module
EQPCONTROLLER
AB MB
DI DO
Power SupplyMonitor
BatteryCharger & PS
Initiating DeviceCircuits (IDC)
X3301 FlameDetector
UV/IR FlameDetector
UV FlameDetector
NetworkExtender
IR FlameDetector
Digital Com. UnitDCU
Eclipse PIRGas Detector
Digital Com. UnitDCUEX
Signal AudibleModule (SAM)
Agent ReleaseModule (ARM)
8 ChannelDCIO
Relay OutputModule(RM)
Intelligent Protection
Module (IPM)
Analog InputModule(AIM)
40
S3 Software Package
• PC-based System Software packagePC-based System Software package• Data Collection Distributor (DCD)Data Collection Distributor (DCD)• Configuration of field devicesConfiguration of field devices• Creation of user logic (IEC61131-3)Creation of user logic (IEC61131-3)
• offline simulation/testing of user logicoffline simulation/testing of user logic• on line logic monitoringon line logic monitoring• creates drawings of the logic creates drawings of the logic
• DiagnosticsDiagnostics• Alarm/Event loggingAlarm/Event logging• Custom GraphicsCustom Graphics
• customer specific graphics of plant layout, customer specific graphics of plant layout, etc.etc.
41
EQP – Questions & Answers
• SmallerSmaller
• FasterFaster
• SmarterSmarter