1 isat 413 - module iii: building energy efficiency topic 3:refrigeration, heat pumps and air...

30
1 ISAT 413 - Module III: Building Energy Efficiency Topic 3: Refrigeration, Heat Pumps and Air Conditioning Evaporating Cooling Vapor-Compression Refrigeration Vapor-Absorption Refrigeration Other Refrigeration Systems The Heat Pump Air Conditioning

Upload: dorthy-gregory

Post on 23-Dec-2015

222 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

1

ISAT 413 - Module III: Building Energy Efficiency

Topic 3: Refrigeration, Heat Pumps and Air Conditioning

Evaporating Cooling

Vapor-Compression Refrigeration

Vapor-Absorption Refrigeration

Other Refrigeration Systems

The Heat Pump

Air Conditioning

Page 2: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

2

Evaporative Cooling (Eastop, Example 4.8)

In a cooling tower the water to be cooled enters near the top of the tower and flows down through packing in counter flow to an air stream as shown diagrammatically in Fig. 4.34. Air is induced from the base of the tower by a fan mounted on the top of the tower. Using the data given below and neglecting heat losses and pressure losses, calculate:

(i) the required mass flow rate of air induced by the fan for the given cooling duty;

(ii) the mass flow rate of make-up water required.

Page 3: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

3

Cooling Tower (Evaporative Cooling)

Page 4: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

4

Data:

Water: Mass flow rate, 15 kg/s; temperature of water at entry, 27oC; temperature of water at exit, 21oC; mean specific heat, 4.18 kJ/kg.K.

Air: Ambient conditions, 1,01325 bar, 23oC dry bulb (DB), 17oC wet bulb (WB); air at exit, saturated with water vapor at 25oC; mean specific heat of dry air, 1.005 kJ/kg.K; fan air power input, 5 kW.

Assumptions: For air at standard atmospheric pressure it can be assumed that the vapor pressure is given by:

For water vapor at low vapor pressure it is a good approximation to assume that the enthalpy is equal to the saturated value at the same dry bulb temperature.

Ktt.barPbarp WBDBgWBs 4107486

Page 5: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

5

(i) the required mass flow rate of air induced by the fan for the given cooling duty

airdrykg

waterkg.

..

..

PP

P.

kPa...

TT.PP

airdrykg

waterkg.

kPa..

kPa..

PP

P.

kPa..PP

s

s

WBDBWBT@gs

s

s

Co@sats

009537053011325101

5301162206220Therefore

5301117231074869351

107486

intakeat air For the

0200801693325101

169362206220

169316931904) pg. (Cengel 4-A TABLE From

11

11

2

21

22

22

252

Page 6: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

6

kg/s.m.mm

kg/s.m.m mm

s/kg.m

kJ....hhh

kJ....hhh

kg

kJ.h

kg

kJ.hhs/kgm

hmmhmhmhmhmhmhmhm

mmmmmmm

mmm

aamakeup

aaaa

a

ga

ga

wCo@fww

awaaww

aaww

aw

aaw

aaa

1440010540 required water up-make of rate flow mass theand (ii)

89130200811fan by the induced rate flow mass Therefore,

)(3Equation from 6213for solvecan Weairdry kg

277622547020080250051

airdry kg3847325440095370230051

0588 ;1113 and , 15 Knowing

)(3 (3) :balanceEnergy

(2) :balance massWater

(1) . :balance massair Dry

12

22

2222

1111

327

31221

332211

123

22311

21

Page 7: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

7

Vapor-Compression Refrigeration

P-h Diagram of an Ideal Vapor-Compression Refrigeration CycleP-h Diagram of an Ideal Vapor-Compression Refrigeration Cycle

Page 8: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

8

Schematic and T-s Diagram for Ideal Vapor-Compression Refrigeration CycleSchematic and T-s Diagram for Ideal Vapor-Compression Refrigeration Cycle

Page 9: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

9

Schematic and T-s Diagram for Actual Vapor-Compression Refrigeration CycleSchematic and T-s Diagram for Actual Vapor-Compression Refrigeration Cycle

Page 10: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

10

The performance of refrigerators and heat pumps is expressed in terms of coefficient of performance (COP), defined as

Page 11: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

11

The standard of comparison for refrigeration cycles is the reversed Carnot cycle. A refrigerator or heat pump that operates on the reversed Carnot cycle is called a Carnot refrigerator or a Carnot heat pump, and their COPs are

Page 12: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

12

The transfer of heat from lower temperature regions to higher temperature ones is called refrigeration. Devices that produce refrigeration are called refrigerators, and the cycles on which they operate are called refrigeration cycles. The working fluids used in refrigerators are called refrigerants. Refrigerators used for the purpose of heating a space by transferring heat from a cooler medium are called heat pumps.

Page 13: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

13

The most widely used refrigeration cycle is the vapor-compression refrigeration cycle. In an ideal vapor-compression refrigeration cycle, the refrigerant enters the compressor as a saturated vapor and is cooled to the saturated liquid state in the condenser. It is then throttled to the evaporator pressure and vaporizes as it absorbs heat from the refrigerated space.

Page 14: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

14

Very low temperatures can be achieved by operating two or more vapor-compression Systems in series, called cascading. The COP of a refrigeration system also increases as a result of cascading.

Page 15: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

15

Another way of improving the performance of a vapor-compression refrigeration system is by using multistage compression with regenerative cooling. A refrigerator with a single compressor can provide refrigeration at several temperatures by throttling the refrigerant in stages. The vapor-compression refrigeration cycle can also be used to liquefy gases after some modifications

Q: Cycles? Components? Working Fluids?

Page 16: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

16

The designation of CFCs (ChloroFluoroCarbons)

is by a two or three digit number:

• The digit on the right represents the number of fluorine (F) atoms;

• The middle digit represents one more than the number of hydrogen (H) atoms;

• The digit on the left represents one less than the number of carbon (C) atoms and omitted when there is only one carbon atom.

Working Fluids – Refrigerants

CHClF2 (R22) or called HCFC 22

Page 17: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

17

(Notice that researches are now underway to develop acceptable alternatives.)

CCl3F (R11), CCl2F2 (R12), and CHClF2 (R22), HFC 134a,

CCl2FCClF2 (R113) and CClF2CClF2 (R114)

R502 which is an azeotropic mixture (acts as a single substance and cannot be separated into its components by distillation.) of R22 and R115

The commonly accepted designation for refrigerants other than halocarbons (compounds containing carbon, fluorine and chlorine in varying proportions, known as CFCs) is to put the digit 7 in front of the relative molecular mass (e.g. NH3 (R717), CO2 ( R744).)

Some Common CFC, HCFC Refrigerants:

Page 18: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

18

Vapor-Absorption Refrigeration

Ammonia Absorption Refrigeration CycleAmmonia Absorption Refrigeration Cycle

Page 19: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

19

Another form of refrigeration that becomes economically attractive when there is a source of inexpensive heat energy at a temperature of 100 to 2000C is absorption refrigeration, where the refrigerant is absorbed by a transport medium and compressed in liquid form. The most widely used absorption refrigeration system is the ammonia-water system, where ammonia serves as the refrigerant and water as the transport medium. The work input to the pump is usually very small, and the COP of absorption refrigeration systems is defined as

Page 20: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

20

The maximum COP an absorption refrigeration system can have is determined by assuming totally reversible conditions, which yields

where T0, TL, and Ts are the absolute temperatures of the environment, refrigerated space, and heat source, respectively.

Page 21: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

21

Other Refrigeration Systems

Schematic of Simple Thermoelectric Power Generator

Schematic of Simple Thermoelectric Power Generator

Page 22: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

22

A Thermoelectric RefrigeratorA Thermoelectric Refrigerator

(Fig. 10-28)

10-13

Page 23: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

23

A refrigeration effect can also be achieved without using any moving parts by simply passing a small current through a closed circuit made up of two dissimilar materials. This effect is called the Peltier effect, and a refrigerator that works on this principle is called a thermoelectric refrigerator.

Page 24: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

24

Refrigerator and Heat Pump ObjectivesRefrigerator and Heat Pump Objectives

The objective of a refrigerator is to remove heat (QL) from the cold medium; the objective of a heat pump is to supply heat (QH) to a warm medium.

The Heat Pump

Page 25: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

25

Heat Pump Heats a House in Winter and Cools it in Summer

Heat Pump Heats a House in Winter and Cools it in Summer

Page 26: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

26

Air Conditioning (Eastop, Example 4.11)

An air conditioning plant is designed to maintain a room at 20oC, percentage saturation 50%, which an air supply to the room of 1.8 kg/s at 14oC, percentage saturation 60%. The design outside air conditions are 27oC,percentage saturation 70%. The plant consists of a mixing chamber for re-circulated and fresh air, a cooling coil supplied with chilled water, heating coil, and a supply fan. The ratio of re-circulated air to fresh air is 3; the cooling coil has an apparatus dew point of 5oC, and the refrigeration unit supplying the chilled water has an overall coefficient of performance 2. Neglecting all losses and fan and pump work, calculate:

Page 27: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

27

(i) the total air conditioning load for the room;

(ii) the required total energy input;

(iii) the required energy input if the energy to the heating coil is supplied from the refrigeration plant condenser cooling water.

Page 28: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

28

kW.kg

kJ..

s

kg.hhm

kg

kJ.h

kg

kJ.h

%,CoT

%,CoT

217232983881

838

2329

12

502022

601411

room on load Total

(i) the total air conditioning load for the room;

Page 29: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

29

(ii) the required total energy input;

kWWhhm

kWkg

kJ

s

kghhm

kg

kJh

kg

kJhhh

kg

kJh

comp

CoT

CoT

9332 isinput energy Total

14272214681

is water chilled thefrom load Cooling

5 intoA and 4 Mixing 722

4) into 3 and 2 (Mixing 1464

3

068

51

54

15855

324

702733

.

....

.

.

.

.,

%,

Page 30: 1 ISAT 413 - Module III: Building Energy Efficiency Topic 3:Refrigeration, Heat Pumps and Air Conditioning  Evaporating Cooling  Vapor-Compression Refrigeration

30

(iii) the required energy input if the energy to the heating coil is supplied from the refrigeration plant condenser cooling water.

water.

coolingcondenser plant ion refrigerat thefrom supplied is

coil heating theenergy to theif0521 i.e, ,compressor

theinput topower just the be dinput woulenergy Total

15632

142142

is water cooling torejectedHeat

kW

kWWW comploadcooling

.

..

.