Presentation to:SWEDE Conference
Austin, TXMay 2, 2013
Tom Weaver, PE
Historical VoltageRange
VVO Range
120
124
128
116
112
108
104
“A”
Se
rvic
e
“A” U
tilizatio
n
“B” U
tilizatio
n
“B” S
erv
ice
American Electric Power’s Experience with
Volt/Var Optimization
![Page 2: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/2.jpg)
2
Volt VAR Impacts on Customer’s Motors
Real Power consumption is 8% lower @ 115V than at
125V
kVAR ↓ ~ 20%
kW ↓ ~ 8%
![Page 3: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/3.jpg)
3
Volt VAR Optimization Architecture
3
Volt VAR Controllers
Mesh Network
Mesh Master
EOL Monitors
Line Regulators
Line Capacitors
DMS - GENe
Fiber or Mesh
![Page 4: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/4.jpg)
4
AEP’s Volt / VAR Optimization Technology Deployments
• AEP Ohio :– 17 circuits in service– Additional circuits being considered to meet EE State Targets
• Indiana & Michigan Power Co.:– 9 circuits in service– Planning to include VVO as an EE Program
• Public Service Company Oklahoma :– 11 circuits in service
• Kentucky Power Co. :– 25 circuits going in service in 2013– Planning to include VVO as an EE Program
![Page 5: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/5.jpg)
55
AEP Ohio: Gahanna – 4505 Voltage Profile
Substation
EOL 2CAP 2 CAP 3
Without AdaptiVolt™ = 6-7-11 @ 4:30 pm With AdaptiVolt™ = 6-6-11 @ 4:30pm
REG
Flatter voltage profile, lower voltage, reduced tap changer operations
![Page 6: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/6.jpg)
6
AEP Ohio: East Broad 1406 Voltage Profile
Normal Operation = 7-23-10 @4:44pmVolt / Var Control Operating = 7-24-10 @4:44pm
Substation
EOL 55CAP 1 CAP 3 CAP 4REG 1 REG 2CAP 2
116.0
118.0
120.0
122.0
124.0
126.0
Normal Operation With VVC
![Page 7: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/7.jpg)
7
Demand and Energy Reduction Results
• VVO technology works as-expected Testing demonstrates ~2-4% energy and demand reduction is
achievable.
![Page 8: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/8.jpg)
8
Example of Energy Savings on Circuit 4503
![Page 9: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/9.jpg)
9
SCADA / PI View
![Page 10: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/10.jpg)
10
SCADA / PI View
![Page 11: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/11.jpg)
11
“Value” of VVO Compared to
Generation Alternatives
Levelized cost of VVO is in the low part of the Energy Efficiency range due to low initial capital cost and no on-going fuel cost
“LEVELIZED COST OF ENERGY ANALYSIS “– VERSION 3.0 Lazard, February 2009
![Page 12: 1 Presentation to: SWEDE Conference Austin, TX May 2, 2013 Tom Weaver, PE Historical Voltage Range VVO Range 120 124 128 116 112 108 104 “A” Service “A”](https://reader036.vdocuments.net/reader036/viewer/2022062720/56649efa5503460f94c0c814/html5/thumbnails/12.jpg)
12
VVO for Energy Efficiency / Capacity Reduction
• Energy Efficiency (24/7 Operation)– Help meet state Energy Efficiency targets– Receive incentives / participate in DR markets – TRCs 2 to 3 – better than many current programs– Reduce Energy Consumption by Customers– Not limited by “participation rates”– Reduce Emissions – Relieve Transmission Congestion
• Capacity (Demand Reduction Only )– Reduce amount of capacity required at peak / critical times– Short payback period if generation charges are based on peak demand– Defer investment in capacity replacement or upgrades– Engage in DR Market– Relieve Transmission Congestion