1 system design. 2 primary detection secondary detection standards pipe design

26
1 System Design

Upload: lenard-porter

Post on 19-Jan-2016

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

1

System Design

Page 2: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

2

System Design

• Primary Detection

• Secondary Detection

• Standards

• Pipe Design

Page 3: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

3

Primary Detection

Where smoke will travel when air

conditioning is operating

• Air handling units

• Duct detection

Page 4: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

4

Primary Detection

Page 5: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

5

Primary Detection

Page 6: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

6

Secondary Detection

Where Smoke is likely to travel when air conditioning is

shut down or not installed

• Ceiling level detection

• In cabinet detection

• Void detection

Page 7: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

7

Secondary Detection

Page 8: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

8

Standards

• BS5839 Pt 1 CoP for Fire Alarm Systems in Buildings

• BS6266 CoP for Fire Protection for Electronic Data Processing installations

• BFPSA CoP for Category 1 Aspirating Detection Systems

Page 9: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

9

Siting Conventional Detectors toBS5839 Pt1 (Secondary Detection)

7.5m• Maximum size for fire zone is 2000m2

• Maximum area coverage per detector 100m2

• Grid overlay design concept gives spacing 5 m from walls - detector spacing 10m maximum

Page 10: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

10

Conventional Detector Layout (Secondary Detection) BS5839

5m 10m 10m 10m 10m 5m

5m

FIRE ZONE PLAN

10m

10m

10m

5m

Page 11: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

11

HSSD Layout (Secondary Detection) BS5839

Sample Holes

Sampling pipes

5m 10m

10m 10m 10m 5m

5m

FIRE ZONE PLAN

10m

10m

10m

5m

Page 12: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

12

Siting Conventional Detectors toBS6266 EDP Areas & High Airflow

Application Recommended coverage per detector Remarks and recommendationsEDP equipmentroom (ceilingheight about3m)

15 m sq. to 25 m sq. (see note) In the extreme case where theearliest possible warning of firein a cabinet is required, there isno substitute for detectors withinthe cabinet.

Without ventilation:20 m sq. to 30 m sq. (see note)

In false ceilings with beams thelower figure should be taken. Ifthe beams are deep so as tocompartmentalize the space, adetector should be fitted in eachsuch compartment

False floors,false ceilings

With Ventilation:(a) between 15 m sq. and 20 m sq. (see

note) for air velocities of 4 m sq. orless

(b) 10 m sq. for air velocities greater than 4 m/s

Tape stores Room protection, 10 m sq. to 30 m sq.(see note)

Electricaldistributionboards andemergencypower supplies

Room protection, 10 m sq. to 30 m sq.(see note)

In installations with enclosedemergency power cabinets,consideration should be given toproviding additional protectionby the installation of detectorsinside the cabinet.

Page 13: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

13

Siting Conventional Detectors toBS6266 EDP Areas & High Airflow

NOTE: Where the risk justifies the extra cost involved, or the maximum response to fire is required, or as ventilation rates increase, the area of coverage per detector should be reduced.However, under these circumstances, the higher area coverage may still be acceptable if the point - type smokedetectors are supplemented by a high sensitivityaspirating system that forms part of the fire alarm system.

Page 14: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

14

Siting Conventional Detectors toBS6266 EDP Areas & High Airflow

• Maximum size for fire zone is 500 to 750m2

• Maximum area cover per detector 25m2

• Grid overlay design concept gives 2.5 m from walls - detector spacing 5m maximum

5m

5m

Page 15: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

15

Conventional Detector Layout (Secondary Detection) BS6266

2.5m 5m 5m 5m 5m 2.5m

2.5m

FIRE ZONE PLAN

5m

5m

2.5m

Page 16: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

16

HSSD Layout (Secondary Detection) BS6266

Sampling pipes

FIRE ZONE PLAN

Sample Holes

2.5m

5m

5m

2.5m

2.5m 5m 5m 5m 5m 2.5m

Page 17: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

17

HSSD Duct samplingReturn air pipe

HARTDetector

Page 18: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

18

AIRTIGHT FITTING(EG. GROMMET)

2mm DIAMETER SAMPLING HOLES

SAMPLE TUBE

RETURN TUBE

AIRFLOWDetailed view of Duct pipework

Page 19: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

19

HSSD Air Handling Unit Sampling (primary)Samplingpipe

HARTDetector

Page 20: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

20

Sampling pipe centred on grilleEnd Cap

Grille

Distance from grille must be such that air velocity less than 6 m/s

Air Handling Unit Sampling

Page 21: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

21

Air Handling Unit

To HARTdetector

Samplingholes

Airflow out

False floor

Airflow in

Page 22: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

22

Air Handling Unit

Sampling holes

False floor

To HARTdetector

Page 23: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

23

Balanced sampling system

AHU Cabinets

Page 24: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

24

In Cabinet sampling

Page 25: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

25

In-cabinet Sampling from Underfloor Void

Equipment

cabinet

Sample tube can detect at different heights

Sample tube enters cabinet from underfloor trunk sampling pipe

Page 26: 1 System Design. 2 Primary Detection Secondary Detection Standards Pipe Design

26

Sampling a Ventilated Equipment Rack

Sampling Pipe

Ventilation grille

Sampling points (Facing into airflow)

Equipment Rack

Airflow Direction