1 tecomat foxtrot & inels description, components, applications

19
1 Tecomat Foxtrot & INELS Description, Components, Applications

Upload: cecilia-whitting

Post on 29-Mar-2015

237 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 1 Tecomat Foxtrot & INELS Description, Components, Applications

1

Tecomat Foxtrot & INELS

Description, Components, Applications

Page 2: 1 Tecomat Foxtrot & INELS Description, Components, Applications

2

Suite of HW products Tecomat Foxtrot

Important features:

• High performance• Modularity• Installation module

„circuit-breaker” design• Two-wire „free” I/O topology• Connectivity of CIB components• Number of I/O up to 134 + I/O CIB elements• Ethernet, Web server• On-line programming• SW backup• OPC server• Slot for MMC card for secondary memory• MODBUS, PROFIBUS DP, CAN

Tecomat Foxtrot – small powerful modular PLC system for a wide range of small-size to medium-size applications in industry and building.

Inels – intelligent electrical system for building applications using CIB bus.

Page 3: 1 Tecomat Foxtrot & INELS Description, Components, Applications

3

Tecomat Foxtrot – description

Page 4: 1 Tecomat Foxtrot & INELS Description, Components, Applications

4

Tecomat Foxtrot – modules

Page 5: 1 Tecomat Foxtrot & INELS Description, Components, Applications

5

Tecomat Foxtrot – communication

Ethernet

Page 6: 1 Tecomat Foxtrot & INELS Description, Components, Applications

6

Tecomat Foxtrot – Communication modes

Channel CH1• Mode PC - communication with superior systems through the EPSNET protocol• Mode PLC - data sharing among PLCs in the EPSNET-F network• Mode UNI - common channel with arbitrary asynchronous communication• Mode MPC - data exchange with subordinated PLCs in the EPSNET multimaster network• Mode MDB- communication with superior systems through the MODBUS protocol• Mode PFB - master for the connection of stations PROFIBUS DP slaveChannel CH2• Mode PC - communication with superior systems through the EPSNET protocol• Mode PLC - data sharing among PLCs in the EPSNET-F network• Mode UNI - common channel with arbitrary asynchronous communication• Mode MPC - data exchange with subordinated PLCs in the EPSNET multimaster network• Mode MDB- communication with superior systems through the MODBUS protocol• Mode PFB - master for the connection of stations PROFIBUS DP slave • Mode UPD - operation of special submodules• Mode DPS - realization of station PROFIBUS DP slave • Mode CAN - connection of stations on the CANopen bus• Mode CAS - realization of station CANopen • Mode CAB - connection of the CAN bus• Mode CSJ -connection of CAN interface with SJA1000 driverEthernet ETH1 • Mode PC - communication with superior systems through the EPSNET UDP protocol in TCP/IP

networks• Mode PLC - data sharing among the PLCs in the TCP/IP network

Page 7: 1 Tecomat Foxtrot & INELS Description, Components, Applications

7

Tecomat Foxtrot – controlling with I/O

Energy monitoring

Direct controlling energy sources and consumption (IRC systems]

Process optimization.

All standard PLC functions,fast inputs for counters,incremental position encoders,measurement of pulse length,period and phase shift.

Page 8: 1 Tecomat Foxtrot & INELS Description, Components, Applications

8

What is an intelligent electro installation system?

System of sensors and actuators which are situated on one bus and connected to control system. They work as remote I/O.

Page 9: 1 Tecomat Foxtrot & INELS Description, Components, Applications

9

FOXTROT = communication + I/O

• Communication part – at the left part– Ethernet 10/100 (RJ45)– CH1-RS232

UART up to 340kbit/s– CH2 – optional for 1 submodule

– RS232 - MR0104– RS482– RS422– 1xCAN– 2xCAN– Profibus DP slave– …LON atd.

– Expansion by peripherals I/O modules - Bus TCL2

– Expansion INELS - Installation elements– Power supplying 24V/DC

Ethernet10/100baseTX

UTP

RS

23

2

Optional interface/for submodule MR

TC

L2

INELS

24

V D

C

Page 10: 1 Tecomat Foxtrot & INELS Description, Components, Applications

10

FOXTROT = communication + I/O

• CP-1004

Basic I/O – at the right– INPUTS - basic functions

• 8x DI 24V DC (DI0-DI7)– INPUTS - alternative functions

• DI4-DI7 = analog AI0-AI3– 0-10V– 10bit, – bez GO

• DI0-DI3 = special functions FI0-FI3– Fast counter, – Incremental sensor

– OUTPUTS• 6x DO/RO,

– Switching /NO/ contact relay– 230V AC/3A

Optical indication

DI0……………..….DI7

AI0…AI3FI0..FI3

RO0………………RO5

Page 11: 1 Tecomat Foxtrot & INELS Description, Components, Applications

11

FOXTROT = basic types of I/O

DI4……………..….DI11

DI0….DI3

SPI0..SPI3

IB -1301

12DI

0AI

0AO

0RO

3M

RO0………………RO7

DI0….DI3

FI0..FI3

IR -1501

4DI/FI

0AI

0AO

8RO

3M

AI0……………..AI7

IT -1601

0DI

0RO

3M

DO4……………DO11

DO0..DO3

0S -1401

0DI

0AI

0AO

12DO

3M

RO0………………RO5

DI0……………..….DI7

AI0…AI3FI0..FI3

CP -1004

4DI/FI

4DI/AI

0AO

6RO

6M

Page 12: 1 Tecomat Foxtrot & INELS Description, Components, Applications

12

FOXTROT – modularity, connection

24V DC

• Module address0-9

• System bus– 345kbit/s– BUS/RS485– 200-300m– Terminator is

required– Basic module

has to be at the left

• Power supplying 24VDC

Up to 300m

Page 13: 1 Tecomat Foxtrot & INELS Description, Components, Applications

13

Bus installation units for the CIB bus

• Individual work with remote I/O

• Free topology – two wires

• Mosaic libraries of function blocks for simple building installations– heating (air conditioning, ventilation), – illumination (dimming, time functions), – electronic alarm system functions– dim-out control, – …

• For sophisticated technologicalapplications in the field of building, source and heat distribution control.

Page 14: 1 Tecomat Foxtrot & INELS Description, Components, Applications

14

FOXTROT is expandable by CIB elements

24V DC

• CIB– Data + Power

supplying– 2 wires– Free topology– 24V DC– 32 units

• CIB MASTER– Next 2 buses– 2x32 units

• CIB is suitable for building IRC (Individual room control)– Lighting– Heating– Air-conditioning– Alarm system– …

230V AC

CIB

Page 15: 1 Tecomat Foxtrot & INELS Description, Components, Applications

15

FOXTROT – Expansion of CIB buses

Power 230V AC/

27.2V DC

CIB -1

CIB-2

CIB-3

CIB-4

CIB-5

CIB-6

CIB-7

CIB-8

CIB-9

9 x 32units = 288 units

288 x 14DI = 4032 DI = max.

Page 16: 1 Tecomat Foxtrot & INELS Description, Components, Applications

16

24V DC SELV

230V AC

CIB works with safety voltage SELV

Power 230V AC/27.2V DC

CIB -1

4 kV 4 kV

Page 17: 1 Tecomat Foxtrot & INELS Description, Components, Applications

17

Building Management System TECOMAT FOXTROT + CIB/INELS

For control panels

Roominstallation

Interiercomponents

Acces control

Security

CCTVVideo

INTEGRATION DIRECT CONTROL

Eth

ern

et

RS

48

5

Electricity supply DDC/PLC

Cooling DDC/PLC

Heating DDC/PLC

IntelligentInstallation

Fire signalization

Page 18: 1 Tecomat Foxtrot & INELS Description, Components, Applications

18

Web server & client, File server

• Embedded web server

• It uses XML, which is more structured than HTML and doesn't spend the capacity of CPU.

• Foxtrot uses file system on Flash disc, internal or on MMC/SD card

Limitation is only the size of MMC/SD card

Page 19: 1 Tecomat Foxtrot & INELS Description, Components, Applications

19

INELS BUS DI (DI), DO/RO AI AO SpecialElements to installation box

ExternalTemperature

sensor

8x DIIM2-80B

1x DI, 1x DO 1x RO 2x RO LM2-11B SA2-01B SA2-02B

4x 0-10V DAC2-04B/04x 1-10V DAC2-04B/1

2x dimmingLM2-22B

DIN rail modules

1M, 3M-

14x DIIM2-140M

2x DI, 2x DO 2x RO 4x RO DA2-22M SA2-02M SA2-04M

4x 0-10V DAC2-04M/04x 1-10V DAC2-04M/1

2x dimmingLBC2-02M

Elements for interiors

ELEGANT

InternalTemperature

sensor

2 buttons 4 buttons 8 buttons Analog/DigitalWSB2-20 WSB2-40 WSB2-80 thermostats IART2

SOPHYSOPHY L

CIB Units - overview

Voice

Light

Infra

Button

Infra