HEP - New Control Centers for Croatia’s Distribution Grid Project Realization, Transition Phase to Network Manager Boris Krstulja, Krunoslav Slivaric (HEP ODS), Zagreb Boris Njavro (Koncar), Zagreb

Upload: borbor

Post on 10-Jun-2015

561 views

Category:

Documents


11 download

DESCRIPTION

NEW CONTROL CENTERS IN HEP

TRANSCRIPT

Page 1: Hep

HEP - New Control Centers for Croatia’s Distribution GridProject Realization, Transition Phase to Network Manager

Boris Krstulja, Krunoslav Slivaric (HEP ODS), Zagreb

Boris Njavro (Koncar), Zagreb

Page 2: Hep

CROATIAN DSO (HEP – ODS d.o.o.)

21 distribution areas from 400.000 to 40.000 customers Zagreb area 25% of consumption 4 biggest areas (Zagreb, Rijeka, Split and Osijek) 50% of

consumption Total:

– 2,3 mil customers, – 17 TWh of consumption

Page 3: Hep

PARTNERS IN PROJECT

HEP – ODS as Investor

KONČAR as Main Supplier

ABB Sweden as subsupplier for Network Manager SCADA/DMS system (Release 2.3)

HP Hardware equipment (Alpha and Proliant servers)

Page 4: Hep

OLD SCADA SYSTEMS

PDP 11/44 computers supplied and installed by Končar in 1980s

ADLP 80 (SINDAC) communication protocol Mostly DS -8 family of RTUs produced in KONČAR Only SCADA functions (PROZA D/R)

Page 5: Hep

PROJECT FOR NEW CENTERS

Long story started in 1994 and ended in 2004

Features:– SCADA with DMS functions for 110, 30(35) and 10(20) kV

network– Protocol conversion ADLP and IEC 101 to IEC 104– ICCP connections– Uninterupted operation – paralel opeartion of old and new

center

Page 6: Hep

TIME SHEDULE

SITE FAT SAT 1 SAT 2Warranty

start

Zagreb Feb. 06 Sept. 06 March 06 June 07

Rijeka July 06 Feb. 07 Oct. 07 Dec. 07

Split Nov. 06 March 07 Oct. 07 Dec. 07

Osijek Feb. 07 May 07 Oct. 07 Dec. 07

Page 7: Hep

CONFIGURATION

Page 8: Hep

IMPORT PROCEDURE

MDF files from PDP computers (ADLP 80 communication) CSV files with process data and new ASDU and IOA

information Plausibility and uniqueness checks Import to DE database

Protocol Communication addressADLP 80 No. of comm. unit (1-9) RTU address (1-15)

IEC 101 No. of serial port (1-9) Device link address (1-255)

Protocol Default ASDU address in new systemADLP 80 No. of comm. unit * 100 + address of RTU (101-915)

IEC 101 No. Of serial port * 1000 + link address of device (1001-9255)

Page 9: Hep

9

TESTING (SAT1 AND SAT2)

Communication (interoperability)

Functions (SCADA, NMS, ICCP)

User interface Historical DB Reports Performance

2200 hours Point to point testing – NO

ERRORS! No interuptions of

operations with old system

Page 10: Hep

CONFIGURATION FOR TESTING

SCADA SERVERS

COMM. INTERFACEPROTOCOL CONVERSION

PDP COMPUTER RTUS OR SAS

FIREWALL

IEC 60870-5-104

IEC 60870-5-101 OR ADLP-80

«PC» CONNECTION

IEC 60870-5-104

Page 11: Hep

Control Center Zagreb

Page 12: Hep

Control Room Rijeka

Page 13: Hep
Page 14: Hep

DMS FUNCTIONS

Dynamic Network coloring Load Calibration Load Flow Short Circuit Analisys Load Forecast

Page 15: Hep

DATA ENGINEERING FOR MV NETWORK

Limitation of 8096 substations– 2500 MV substations + connections of cables and OH lines (ZG)

Introduction of Site concepts and Feeder lines inside one big substation representing area of MV network

Development of Wireless connectors from HV to MV substation Overview pictures (limit of 29 subpictures with 1000 dynamic

elements) - maximum of 500 sites in one substation Modelling of grounding of transformer neutral point! Technical data must be very detailed:

– tap changers on transformers– Parallel susceptance on lines– Compensators,…

Page 16: Hep

DE CONCEPT

Page 17: Hep

DECLUTERING

Page 18: Hep

DECLUTER LEVEL 6-22

Page 19: Hep

DMS MODELLING

Page 20: Hep

THE RESULT AFTER 2 YEARS!