LESSON 34

BUSBAR PROTECTION

Page 2: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 2/41

OUTLINE OF THE LESSON

• INTRODUCTION

• BUSBAR FAULTS

• PROTECTION REQUIREMENTS• TYPES OF PROTECTION SYSTEMS

 –FRAME EARTH PROTECTION

 –DIFFERENTIAL 

PROTECTION

Page 3: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 3/41

INTRODUCTION

• The protection scheme for a

power system should cover thewhole system against all

probable type s of fault.

Page 4: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 4/41

• Unrestricted forms of line protection

such as overcurrent and distance

systems,meet this requirement,

although faults in the Busbar zone

are cleared only after some time

delay.

Page 5: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 5/41

•   If unit protection is applied to

feeder and plant the busbars are

not inherently protectected

Page 6: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 6/41

• Busbars have been left without

specific protection for one or more of 

the following reasons:

 – The busbars and switchgear have high

degree of reliability ,to the point of 

being regarded as intrinsically safe.

Page 7: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 7/41

• It was feared that accidental

operation of busbar protection might

cause wide spread dislocation of the

power system ,which ,if not quickly

cleared ,would cause more loss than

would the very infrequent actual busfaults

Page 8: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 8/41

• It was hoped that system protection

or back-up protection would provide

sufficient bus protection

Page 9: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 9/41

BUSBAR FAULTS

• Majority of bus faults involve one

phase and earth, but faults arise

from many causes and a significant

number are inter-phase clear of earth.

Page 10: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 10/41

With fully phase -segregated metalclad gear ,only earth faults are

possible ,and a protective scheme

need have earth fault sensitivity only.

Page 11: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 11/41

• For outdoor busbars , protection

schemes ability to respond to inter-

phase faults clear of earth is an

advantage

Page 12: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 12/41

BUSBAR FAULT STATISTICS

• For a particular system in which total

faults equal to 129 , the distribution is :

 – PHASE TO EARTH 87

 – TWOPHASE TO EARTH 15

 – THREE PHASES TO EARTH 19

 – THREE PHASE 6

 – UNKNOWN 2

Page 13: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 13/41

PROTECTION EQUIREMENTS

• Although not basically different from

other circuit protections,the key

position of busbars intensifies the

emphasis put on the essential

requirements of speed and stability

Page 14: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 14/41

SPEED

• High speed operation is required for 

limiting the damage due to fault.

• Removal of bus faults in less time

than could be achieved by back  –up

protection ,with the object of maintaining system stability.

Page 15: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 15/41

• Most of the modern busbar 

protection are based on low

impedance biased or high impedance

unbiased differential protectionsystems.The operating time is of the

order of one cycle .

Page 16: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 16/41

STABILITY

• The stability of bus protection is of 

paramount importance

• In order to maintain the high order of 

integrity needed for bus protection,it

is an almost invariable practice to

make tripping depend on twoindependent measurements of fault

quantities .

Page 17: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 17/41

• Security of both stability and

operation is obtained by providing

three independent discriminating

channels,the trip outlets of which areconnected in series and in pairs as

shown below:

Page 18: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 18/41

TWO OUT OF THREE PRINCIPLE

FIG: Two out of three principle

Page 19: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 19/41

• Three channels x,y and z from three

independent trip circuits ,x+ y,y+z,and

z+x. This means that any kind of 

failure can occur in any one channel

without prejudging either stability or 

ability to operate for the scheme as a

whole.

Page 20: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 20/41

TYPES OF PROTECTION

SCHEMES

• System protection used to cover 

bus bars• Frame  –earth protection

• Differential protection

Page 21: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 21/41

SYSTEM PROTECTION

• A system protection that includes

overcurrent or distance systems will

inherently give protection cover to the

busbars.

Page 22: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 22/41

• Overcurrent protection will only be

applied to relatively simple distributionsystems,or as a back-up protection set

to give considerable time

delay.Distance protection will provide

cover with its second zone.

• In both cases,therefore ,the busbar protection so obtained is slow

Page 23: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 23/41

FRAME-EARTH ROTECTION

This is purely an earth faultsystem,and ,in principle ,involves

simply measuring the fault current

flowing from the switchgear frame toearth.To this end a current

transformer is mounted on the

earthing conductor and is used toenergize a simple instantaneous

relay.

Page 24: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 24/41

FRAME – EARTH PROTECTION

Page 25: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 25/41

DIFFERENTIAL PROTECTION

• BASIC PRINCIPLE

 –Basic Principle

 –Summation scheme

Page 26: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 26/41

BASIC PRINCIPLE

• The merz-price principle is applicable

to multi-terminal zone such as a

busbar.The principle is the directapplication of  kirchhoff’s first

law.Usually the circulating current

arrangement is used.

Page 27: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 27/41

BASIC CIRCULATING CURRENT

SCHEME

Fig Basic Circulating Current Scheme

Page 28: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 28/41

SUMMATION SCHEME

• By using current transformers of 

different ratios, for example

300/1,400/1and 500/1in each three

phase group,connected in parallel

and interconnected between groups

,by two bus wires only a response isobtained to all types of fault.

Page 29: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 29/41

Page 30: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 30/41

Page 31: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 31/41

Page 32: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 32/41

• An alternate arrangement to that

above is obtained by using current

transformers of equal ratio but cross

-connecting two of them and taking a

centre tap from the third.

Page 33: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 33/41

Page 34: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 34/41

Page 35: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 35/41

Page 36: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 36/41

Page 37: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 37/41

RECOMMENDATIONS ON BUSBAR

PROTECTION

(Reference: Manual on PROTECTION

of GENERATOR, GENERATORTRANSFORMER, and 220 KV and

400KV NETWORKS, Publication No.

274(revised) CBIP New Delhi).

Page 38: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 38/41

1. Busbar protection must be

provided in all new 400 kV and 200

kV substations as well as

generating station switchyards.

2. It shall be of 3-phase type and

operate selectively for each busbar section.

Page 39: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 39/41

3. It shall operate on differential

principle and provide independent

zones of protection for each bus.

4. It shall be stable for through fault

conditions up to maximum 40KA fault

level.

Page 40: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 40/41

5. It shall incorporate continuous

supervision for C.T. secondariesagainst any possible open circuits. In

case of detection of any open circuit of 

C.T. secondaries, after a time delay, the

affected zone of protection shall be

rendered inoperative and an alarm willbe initiated

Page 41: 109713451 Busbar Protection

7/29/2019 109713451 Busbar Protection

http://slidepdf.com/reader/full/109713451-busbar-protection 41/41

6. It shall include D.C. supply

supervision.

7. Include adequate number of high

speed tripping relays.