10eer w090ap-w150ap series mega-tec...1.5 to 3 ton 208v to 460v 60hz air conditioner speci˜cations...
TRANSCRIPT
1 1 E E R W A S E R I E S W A L L - M O U N T T M P A G E 1 O F 2 7 FO R M N O. S3573 -1118 • S U P E R S E D E S N E W
1.5 to 3 Ton 208V to 460V 60hz Air Conditioner Speci�cations
11EER WA Series WALL-MOUNT™ 1.5 to 3 Ton208V to 460V 60hz Air Conditioner Specifications.
The Bard Wall-Mount Air Conditioner is a selfcontained energy efficient system, which is designedto offer maximum indoor comfort at a minimal costwithout using valuable indoor floor space or outsideground space. This unitis the ideal productforversatile applications such as: new construction,modular offices, school modernization,telecommunication structures, portable structures orcorrectional facilities. Factory or field installedaccessories are available to meet specific jobrequirements for your unique application.
W36AB-A Wall-Mount™
11EER WA Series WALL-MOUNT™ 1.5 to 3 Ton208V to 460V 60hz Air Conditioner Specifications.
The Bard Wall-Mount Air Conditioner is a selfcontained energy efficient system, which is designedto offer maximum indoor comfort at a minimal costwithout using valuable indoor floor space or outsideground space. This unitis the ideal productforversatile applications such as: new construction,modular offices, school modernization,telecommunication structures, portable structures orcorrectional facilities. Factory or field installedaccessories are available to meet specific jobrequirements for your unique application.
W36AB-A Wall-Mount™
11EER WA Series WALL-MOUNT™ 1.5 to 3 Ton208V to 460V 60hz Air Conditioner Specifications.
The Bard Wall-Mount Air Conditioner is a selfcontained energy efficient system, which is designedto offer maximum indoor comfort at a minimal costwithout using valuable indoor floor space or outsideground space. This unitis the ideal productforversatile applications such as: new construction,
offices, school modernization,telecommunication structures, portable structures orcorrectional facilities. Factory or field installedaccessories are available to meet specific jobrequirements for your unique application.
W36AB-A Wall-Mount™
11EER WA Series WALL-MOUNT™ 1.5 to 3 Ton208V to 460V 60hz Air Conditioner Specifications.
The Bard Wall-Mount Air Conditioner is a selfcontained energy efficient system, which is designedto offer maximum indoor comfort at a minimal costwithout using valuable indoor floor space or outsideground space. This unitis the ideal productforversatile applications such as: new construction,
offices, school modernization,telecommunication structures, portable structures orcorrectional facilities. Factory or field installedaccessories are available to meet specific jobrequirements for your unique application.
W36AB-A Wall-Mount™
W090AP - W150AP SERIES 7.5 to 12.5 Ton 208V to 460V 60hz MEGA-TEC Air Conditioner
Bard Manufacturing’s revolutionary MEGA-TEC WALL-MOUNT sets the industry standard for flexibility. Engineered to cool virtually any equipment building or shelter, the PLC technology inside the unit and controller provides unmatched cooling and unparalleled control over your critical application. The MEGA-TEC is AHRI certified, meets or exceeds DOE efficiency requirements, and delivers industrial grade service at the Highest possible level of efficiency. The MEGA-TEC moves seamlessly between three different compressor cooling capacities based on need and peak efficiency, and thanks to our Programmable Logic Control (PLC) technology, you’ll be able to control up to fourteen units with a single controller.• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2016• Certified to ASNI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units)• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05 Fourth Edition• Commercial Product - Not intended for residential application• Bard is an ISO 9001:2015 Certified Manufacturer
10EER W090AP-W150AP Series MEGA-TECTM
Climate Control Solutions
BARDHVAC.COM
FO R M N O. S3565 - 012 0
1 0 E E R M E G A - T E C T M S E R I E S P A G E 2 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
WALL-MOUNT NOMENCLATURE///////
W 120 A P B 0Z E P I X X X
NOMINAL TOTAL CAPACITY090 - 7.5 Ton120 - 10 Ton
150 - 12.5 Ton
UNIT SERIESWall Mount
CONTROL LOGIC AND CLIMATE OPTIONSP- PLC Logic BoardE- Electric Reheat Dehumidification
VOLTS & PHASEB- 208/230-60-3C- 460-60-3Q- 575-60-3E- 240/220-50-3V- 415/380-50-3
REVISIONA
KW
0Z- 0kw electric heat09- 9kw electric heat18-18kw electric heat
VENTB- No VentE- Economizer - DB & WB
FILTERM- MERV 11 2" PleatedP- MERV 8 2" PleatedN- MERV 13 2" Pleated
COLOR1- White4- Gray
OUTLETX- Standard
COIL AND UNIT COATING OPTIONSX- Standard1- Coated Evaporator2- Coated Condenser3- Coated Evaporator & Condenser
PACKAGING OPTIONS X- None- Standard wood skid 1- White steel skid/platform 2- Wood skid with crate 3- White steel skid/platform with crate. 6- Gray steel skid/platform 7- Gray steel skid/platform with crate.
1 0 E E R M E G A - T E C T M S E R I E S P A G E 3 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
ENGINEERED FEATURES - EXTERIOR///////
Durable Cabinet Construction: Galvanized 16 gauge Zinc coated cabinet with an applied polyure-thane primer. Cabinet is finished with a baked on, white textured
enamel which allows it to withstand 1000 hours of salt spray tests per
ASTM B117-03.
Lockable Breaker Access: Circuit breaker door is hinged and
lockable for tamper resistance.
Evaporator Fan Access: Evaporator Fan is easily accessi-
ble through service panel.
Optional Drain Location: Condensate drains for upper
evaporator coil pans can be rout-ed through the front of the unit or
through the base.
Low Voltage Power Entrance: Weather resistant plugs are provided
on both the left and right sides for power access.
Condenser Section Access: Easy to remove panel for com-
pressor, condenser fan, condenser coil, and filter drier access.
Control Panel Access: Control panel is accessed through separate panel for ease of service-
ability.
Outdoor Temperature Sensor: Outdoor sensor measures tempera-
ture and humidity for unit operation and to indicate when conditions are
favorable for free cooling, standard on all models.
Filter Replacement Light: Easy to see external light illuminates to indicate a filter change is needed.
Optional Economizer Vent Intake: Free cooling vent intake pre-filters and
damper motors are easily accessed.
High Voltage Power Entrance: Weather resistant plugs are provided
on both the left and right sides for power access
Service Port Access: Service ports are accessed without
removing fan or door assembly.
Condenser Coil Intake Access: Side panels are easy to remove for condenser coil cleaning. Debris is easily seen on entering surface of
condenser coils.
Easy Filter Access: Hinged filter door is provided for easy ac-
cess to filter, electric heat, and evaporator area.
Lifting Lug Plates: Standard heavy duty plates on each
side allow unit to be lifted and installed on a structure. Plates are
removable after installation.
The exterior of the MEGA-TEC™ provides installation features including lifting lugs. Cabinet construction uses 16 gauge and 14 gauge components for strength and durability. Service features includes exterior service ports, a filter replacement light, and Hinged upper filter
access door.
1 0 E E R M E G A - T E C T M S E R I E S P A G E 4 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
ENGINEERED FEATURES - INTERIOR///////
Non-fiberglass Insulation: Extremely durable closed cell foam insulation used throughout the product.
(2) Refrigeration Circuits: Separate refrigeration circuits use individual compressors for service-ability and reliability
Industrial Grade Evaporator Fan: Evaporator Fan uses ECM technolo-gy for efficient, dependable service. Modbus communication used for motor feedback.
Liquid Line Filter/Drier: Filter driers protect refrigeration equipment and are standard in all models.
PLC Technology: Control board uses Modbus to communicate with components and controller.
Optional Free Cooling: Economizer option allows for free cooling utilizing outdoor air when conditions are acceptable.
Industrial Grade Controls: Control panel is clean, organized, and easy to service.
Dirty Filter Indicator: Filter pressure switch with filter change indicator light standard on all models.
Fan Pressure Switch: Fan pressure switch to indicate blower failure standard on all models
Electronic Expansion Valves: Electronic expansion valves are used in all models for precise super-heat control.
Phase Rotation Monitor: Protects against compressor reverse rotation. Standard on all 3 phase models.
Service Port Access: Service ports are accessed without removing fan or door assembly.
Pressure Transducers: High and low side system pressures are monitored to provide refrigera-tion data including superheat.
Industrial Grade Outdoor Fan: Outdoor fan uses ECM technology for efficient, dependable service. Modbus communication used for motor feedback.
2” Pleated Filter: Large filter area and 2” pleated design allow for better unit indoor airflow.
The interior of the MEGA-TEC™ provides easily serviceable areas for routine maintenance and is designed for years of trouble free service. A Hinged upper filter access door and slide out condenser fan assembly are a few of the features that make the MEGA-TEC easy to service. Industrial grade fans and components provide dependable service in outdoor work environments. Electronic expansion valves and Modbus controls use the latest technology to provide the best indoor environment for electronics and industrial equipment.
Slide-out Fan Assembly: Slide out condenser section fan assembly allows fan to be pulled forward. Hinges allow fan to be rotated out of the way for compres-sor access.
Scroll Compressors: Each refrigeration circuit uses a separate scroll compressor. Three cooling stages provide efficient ca-pacity control for applications with lower heat loads.
Note: Circuit 1 two-stage on left. Circuit 2 single-stage on right facing front.
Enhanced Latent and High Sensible Cooling Modes:PLC Logic is used for High sensible cooling where humidity inside the area is at average or low condi-tions. Balanced Climate operation allows for additional humidity to be removed when moisture levels are High in the area being conditioned.
1 0 E E R M E G A - T E C T M S E R I E S P A G E 5 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
UNIT MODES OF OPERATION
Cooling Operation: The Bard MEGA-TEC Series products offer three stage cooling operation using R410A refrigerant. Cooling is achieved by two
independent cooling circuits containing independent scroll compressors (one single stage, one two stage), filter driers, electronic expansion valves
(EEV’s), condenser coils and evaporator coils. The unit PLC monitors indoor humidity levels, and uses High sensible cooling operation to increase
unit airflow when moisture levels do not require an average or substantial amount of latent capacity.
Heating Operation: The Bard MEGA-TEC Series products offer optional two stage heating operation using resistance heaters. Circuit breaker
disconnect protection is standard in all 200V to 230V units equipped with electric heat.
Electric Reheat Dehumidification Operation: The Bard MEGA-TEC Series products offer optional electric reheat dehumidification operation that removes
moisture from air leaving the unit. The electric heat reheats the cooled supply air after it passes over the evaporator coils. This results in extended
compressor runtime and lowering of High indoor humidity levels.
Economizer Free Cooling Operation: The Bard MEGA-TEC Series products offer optional economizer ventilation operation that can achieve extremely
High cooling efficiencies by taking advantage of cooler outdoor conditions. Outdoor air is brought into the structure when conditions are acceptable
for free cooling through hoods located on both sides of the unit. A large room exhaust path allows room air to be vented outdoors when fresh air
is being brought into the structure. Minimum ventilation amounts are user selectable for continuous outdoor intake. Economizer operation allows
for free cooling at outdoor temperatures down to -40°F. Emergency cooling and ventilation are safety features that are available with the optional
economizer.
Balanced ClimateTM Operation: Balanced Climate™ is a great moisture removal feature that operates during cooling operation when moisture levels
inside the room are High. By reducing unit airflow and running in compressor cooling operation, latent capacity is increased and additional moisture
is removed from the air being conditioned. Balanced Climate is a standard feature for all MEGA-TEC products.
///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 6 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
CAPACITY AND EFFICIENCY RATINGS
Capacity is certified in accordance with ANSI/ARI Standard 390-2003. Meets or exceeds 10 EER DOE requirements. EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.
All ratings based on fresh air intake being 100% closed (no outside air introduction). IPLV = Integrated Part Load Value (IPLV) is a BTU/WATT efficiency measurement that combines staged cooling.
MODELS W090APB W090APC W090APE W090APV
Electrical Rating Voltage - Phase - Hz 230/208-60-3 460-60-3 220/200-50-3 415/380-50-3
Operating Voltage Range 197-253 414-506 198-254 342-456
2 Stage Compressor--Circuit 1
Nominal Voltage 230/208V 460V 220/200V 415/380V
Rated Load Amps 10.0/11.0 7.5 TBD TBD
Branch Circuit Selection Current 27.9 17.3 TBD TBD
Lock Rotor Amps 83.1/83.1 41 TBD TBD
Short Circuit Interrupt Rating (SCIR) 5KA 5KA 5KA 5KA
Compressor Type Scroll/2-Stage Scroll/2-Stage Scroll/2-Stage Scroll/2-Stage
Expansion Device Electronic (EEV) Electronic (EEV) Electronic (EEV) Electronic (EEV)
High Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Low Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
1 Stage Compressor--Circuit 2
Nominal Voltage 230/208V 460V 220/200V 415/380V
Rated Load Amps 10.0/11.0 7.3 TBD TBD
Branch Circuit Selection Current 27.9 17.3 TBD TBD
Lock Rotor Amps 83.1/83.1 41 TBD TBD
Short Circuit Interrupt Rating (SCIR) 5KA 5KA 5KA 5KA
Compressor Type Scroll/1-Stage Scroll/1-Stage Scroll/1-Stage Scroll/1-Stage
Expansion Device Electronic (EEV) Electronic (EEV) Electronic (EEV) Electronic (EEV)
High Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Low Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Outdoor Fan Assembly & Condenser
Fan Motor--HP-- MAX. RPM 3 (2238W)-1450RPM 3 (2238W)-1450RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM
Fan Motor--Amps 7.2 2.5 TBD TBD
Fan--DIA/CFM 28”(630mm) - 2900 28”(630mm) - 2900 28”(630mm) - 2900 28”(630mm) - 2900
Evaporator Fan Assembly & Evaporator
Blower Motor—HP-SPD 2 (1492W)-1500RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM
Blower Motor—Amps 3.6 1.9 TBD TBD
Fan - Motor Type Backward Curve - ECM Backward Curve - ECM Constant Torque ECM Constant Torque ECM
Filter Sizes inches (mm), 4 required20x24x2
(508x609x50)20x24x2
(508x609x50)20x24x2
(508x609x50)20x24x2
(508x609x50)
Unit Weight Unpackaged - lbs. (kg) 1302 1302 1302 1302
Additional lbs for Economizer (kg) 100 (45.4) 100 (45.4) 100 (45.4) 100 (45.4)
7.5 TON UNIT SPECIFICATIONS
///////
///////
MODELS W090AP W120AP W150AP
3rd Stage Cooling Capacity BTUH 92,000 BTUH 123,000 BTUH 146,000 BTUH
3rd Stage Cooling Rated CFM 3,000 CFM 4,000 CFM 4,600 CFM
2nd Stage Cooling Capacity BTUH 80,000 BTUH 114,000 BTUH 122,000 BTUH
Voltage 2nd Stage Cooling Rated CFM 3,000 CFM 4,000 CFM 4,600 CFM
1st Stage Cooling Capacity BTUH 30,000 BTUH 42,000 BTUH 44,000 BTUH
1st Stage Cooling Rated CFM 2,100 CFM 2,800 CFM 3,200 CFM
3rd Stage Cooling EER 11.2EER 10.0EER 10.0 EER
IPLV (Integrated Part Load Value) 11.5 12.3 10.6
1 0 E E R M E G A - T E C T M S E R I E S P A G E 7 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
MODELS W120APB W120APC W120APE W120APV
Electrical Rating Voltage - Phase - Hz 230/208-60-3 460-60-3 220/200-50-3 415/380-50-3
Operating Voltage Range 197-253 414-506 198-254 342-456
Compressor--Circuit 1
Nominal Voltage 230/208V 460V 220/200V 415/380V
Rated Load Amps 15.0/16.3A 8.33A 15.0/16.1A 7.1A
Branch Circuit Selection Current 17.6A 8.5A 17.7A 8.8A
Lock Rotor Amps 136A 66.1A 146A 67.1A
Short Circuit Interrupt Rating (SCIR) 5KA 5KA 5KA 5KA
Compressor Type Scroll/2-Stage Scroll/2-Stage Scroll/2-Stage Scroll/2-Stage
Expansion Device Electronic (EEV) Electronic (EEV) Electronic (EEV) Electronic (EEV)
High Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Low Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Compressor--Circuit 2
Nominal Voltage 230/208V 460V 220/200V 415/380V
Rated Load Amps 14.5/16.0A 7.3A 14.2A/15.7A 7.1A
Branch Circuit Selection Current 19.3A 8.8A 18.9A 8.8A
Lock Rotor Amps 136A 66.1A 146A 67.1A
Short Circuit Interrupt Rating (SCIR) 5KA 5KA 5KA 5KA
Compressor Type Scroll/1-Stage Scroll/1-Stage Scroll/1-Stage Scroll/1-Stage
Expansion Device Electronic (EEV) Electronic (EEV) Electronic (EEV) Electronic (EEV)
High Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Low Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Outdoor Fan Assembly & Condenser
Fan Motor--HP-- MAX. RPM 3 (2238W)-1450RPM 3 (2238W)-1450RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM
Fan Motor--Amps 5.5 2.7 5.5 2.7
Fan--DIA/CFM 28”(630mm) - 2900 28”(630mm) - 2900 28”(630mm) - 2900 28”(630mm) - 2900
Evaporator Fan Assembly & Evaporator
Blower Motor—HP-SPD 2 (1492W)-1500RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM
Blower Motor—Amps 3.6 1.7 3.6 1.7
Fan - Motor Type Backward Curve - ECM Backward Curve - ECM Constant Torque ECM Constant Torque ECM
Filter Sizes inches (mm), 4 required20x24x2
(508x609x50)20x24x2
(508x609x50)20x24x2
(508x609x50)20x24x2
(508x609x50)
Unit Weight Unpackaged - lbs. (kg) 1322 1322 1322 1322
Additional lbs for Economizer (kg) 100 (45.4) 100 (45.4) 100 (45.4) 100 (45.4)
10 TON UNIT SPECIFICATIONS///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 8 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
MODELS W150APB W150APC W150APE W150APV
Electrical Rating Voltage - Phase - Hz 230/208-60-3 460-60-3 220/200-50-3 415/380-50-3
Operating Voltage Range 197-253 414-506 198-254 342-456
Compressor--Circuit 1
Nominal Voltage 230/208V 460V 220/200V 415/380V
Rated Load Amps 17.4/19.2 9.4 17.4/19.2 9.4
Branch Circuit Selection Current 20.4 10 20.4 10
Lock Rotor Amps 167 69 167 69
Short Circuit Interrupt Rating (SCIR) 5KA 5KA 5KA 5KA
Compressor Type Scroll/2-Stage Scroll/2-Stage Scroll/2-Stage Scroll/2-Stage
Expansion Device Electronic (EEV) Electronic (EEV) Electronic (EEV) Electronic (EEV)
High Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Low Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Compressor--Circuit 2
Nominal Voltage 230/208V 460V 220/200V 415/380V
Rated Load Amps 17.9 9.1 17.9 9.1
Branch Circuit Selection Current 22.5 10.6 22.5 10.6
Lock Rotor Amps 149 75 149 75
Short Circuit Interrupt Rating (SCIR) 5KA 5KA 5KA 5KA
Compressor Type Scroll/1-Stage Scroll/1-Stage Scroll/1-Stage Scroll/1-Stage
Expansion Device Electronic (EEV) Electronic (EEV) Electronic (EEV) Electronic (EEV)
High Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Low Pressure Transducer 10K - J Curve 10K - J Curve 10K - J Curve 10K - J Curve
Outdoor Fan Assembly & Condenser
Fan Motor--HP-- MAX. RPM 3 (2238W)-1450RPM 3 (2238W)-1450RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM
Fan Motor--Amps 7.2 3.5 7.2 3.5
Fan--DIA/CFM 28”(630mm) - 2900 28”(630mm) - 2900 28”(630mm) - 2900 28”(630mm) - 2900
Evaporator Fan Assembly & Evaporator
Blower Motor—HP-SPD 2 (1492W)-1500RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM 2 (1492W)-1500RPM
Blower Motor—Amps 5.5 2.7 5.5 2.7
Fan - Motor Type Backward Curve - ECM Backward Curve - ECM Constant Torque ECM Constant Torque ECM
Filter Sizes inches (mm), 4 required20x24x2
(508x609x50)20x24x2
(508x609x50)20x24x2
(508x609x50)20x24x2
(508x609x50)
Unit Weight Unpackaged - lbs. (kg) 1362 1362 1362 1362
Additional lbs for Economizer (kg) 100 (45.4) 100 (45.4) 100 (45.4) 100 (45.4)
12.5 TON UNIT SPECIFICATIONS///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 9 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
MODELSTAGE
RETURN AIR
(DB/WB)
COOLING CAPACITY 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F
W090APSTAGE 3
75/62Total Cooling
Sensible Cooling89,50073,200
87,30071,800
84,90070,600
82,50069,300
80,10068,100
77,70066,900
75,20065,700
72,70064,600
70,00063,500
67,40062,400
64,70061,400
80/67Total Cooling
Sensible Cooling95,60071,000
95,10070,400
94,30069,900
93,30069,300
92,00068,700
90,50068,100
88,70067,400
86,70066,800
84,30066,100
81,70065,400
78,90064,700
85/72Total Cooling
Sensible Cooling113,90072,700
111,20071,400
108,30070,200
105,30068,800
102,20067,400
99,00065,900
95,60064,200
92,20062,600
88,60060,900
84,90059,100
81,10057,200
W090APSTAGE 2
75/62Total Cooling
Sensible Cooling79,20068,300
76,90066,700
74,60065,300
72,20063,900
69,60062,500
67,20061,100
64,60059,800
61,90058,500
59,20057,300
56,50056,100
53,70053,700
80/67Total Cooling
Sensible Cooling84,60066,200
83,80065,400
82,80064,700
81,60063,900
80,00063,100
78,30062,200
76,20061,400
73,90060,500
71,30059,600
68,50058,700
65,40057,800
85/72Total Cooling
Sensible Cooling100,80067,800
98,00066,400
95,10065,000
92,10063,500
88,90061,900
85,60060,200
82,20058,500
78,60056,700
74,90054,900
71,20053,000
67,30051,100
W090APSTAGE 1
75/62Total Cooling
Sensible Cooling29,40024,600
28,80023,900
28,00023,300
27,10022,600
26,10021,900
25,20021,300
24,10020,800
22,80020,300
21,60019,600
20,20019,100
18,80018,600
80/67Total Cooling
Sensible Cooling31,40023,800
31,30023,400
31,10023,000
30,60022,600
30,00022,100
29,30021,700
28,40021,300
27,20020,900
26,00020,400
24,50020,000
22,90019,500
85/72Total Cooling
Sensible Cooling37,40024,400
36,60023,800
35,70023,100
34,60022,500
33,40021,700
32,10021,000
30,60020,300
29,00019,600
27,30018,800
25,50018,100
23,60017,300
W120APSTAGE 3
75/62Total Cooling
Sensible Cooling139,100109,800
129,500103,900
121,10098,800
113,70094,400
107,10090,600
101,50087,500
96,70085,100
92,80083,200
89,50081,800
87,10081,100
85,30081,000
80/67Total Cooling
Sensible Cooling148,500106,500
141,200101,900
134,50097,900
128,50094,400
123,00091,500
118,30089,100
114,20087,300
110,70086,000
107,80085,200
105,60085,000
104,00085,300
85/72Total Cooling
Sensible Cooling176,800109,000
165,000103,400
154,40098,300
145,00093,700
136,60089,700
129,40086,200
123,10083,200
117,70080,600
113,20078,400
109,70076,800
106,90075,400
W120APSTAGE 2
75/62Total Cooling
Sensible Cooling122,400100,300
116,00097,200
110,10094,200
104,50091,300
99,20088,600
94,40086,000
89,80083,600
85,50081,300
81,40079,200
77,60077,100
74,10074,100
80/67Total Cooling
Sensible Cooling130,70097,300
126,50095,300
122,30093,300
118,20091,300
114,00089,400
110,00087,600
106,00085,800
102,00084,100
98,00082,400
94,10080,800
90,30079,300
85/72Total Cooling
Sensible Cooling155,60099,600
147,90096,700
140,40093,700
133,40090,700
126,60087,700
120,30084,700
114,30081,700
108,50078,800
102,90075,900
97,70073,000
92,80070,100
W120APSTAGE 1
75/62Total Cooling
Sensible Cooling51,50038,400
47,00035,800
43,10033,500
39,70031,500
36,60029,800
34,10028,400
32,00027,200
30,30026,200
28,90025,600
28,00025,100
27,30024,900
80/67Total Cooling
Sensible Cooling55,00037,200
51,20035,100
47,80033,200
44,80031,500
42,00030,100
39,70028,900
37,70027,900
36,10027,100
34,80026,600
33,90026,300
33,30026,200
85/72Total Cooling
Sensible Cooling65,50038,100
59,90035,600
54,90033,400
50,60031,300
46,70029,500
43,40028,000
40,70026,600
38,40025,400
36,60024,500
35,20023,800
34,30023,200
W150APSTAGE 3
75/62Total Cooling
Sensible Cooling148,800116,700
143,000113,800
137,400110,900
132,100108,300
127,100105,600
122,300103,000
117,700100,500
113,30098,200
109,00095,800
105,00093,600
101,00091,300
80/67Total Cooling
Sensible Cooling158,900113,200
155,900111,600
152,700109,900
149,400108,300
146,000106,600
142,500104,900
138,900103,200
135,200101,500
131,30099,700
127,30098,000
123,20096,200
85/72Total Cooling
Sensible Cooling189,200115,900
182,200113,200
175,300110,400
168,600107,500
162,100104,500
155,800101,400
149,70098,300
143,80095,100
137,90091,800
132,20088,500
126,70085,100
W150APSTAGE 2
75/62Total Cooling
Sensible Cooling127,200102,200
121,40099,000
116,00096,100
111,00093,300
106,20090,600
101,80088,200
97,90085,800
93,80083,700
90,10081,600
86,70079,600
83,50074,100
80/67Total Cooling
Sensible Cooling135,80099,100
132,30097,100
128,90095,200
125,50093,300
122,00091,500
118,60089,800
115,30088,100
111,90086,500
108,50084,900
105,20083,400
101,80082,000
85/72Total Cooling
Sensible Cooling161,700101,500
154,60098,500
148,00095,600
141,60092,600
135,50089,700
129,70086,800
124,30083,900
119,00081,100
114,00078,200
109,30075,300
104,70072,500
W150APSTAGE 1
75/62Total Cooling
Sensible Cooling45,80033,300
43,90032,500
42,00031,500
40,10030,400
38,30029,400
36,70028,200
35,00026,900
33,40025,700
31,80024,300
30,20022,900
28,70021,500
80/67Total Cooling
Sensible Cooling48,90032,300
47,80031,800
46,60031,200
45,30030,400
44,00029,600
42,70028,700
41,30027,600
39,80026,500
38,20025,300
36,60024,000
35,00022,600
85/75Total Cooling
Sensible Cooling58,30033,100
55,90032,300
53,50031,400
51,20030,200
48,90046,70027,800
44,50026,300
42,40024,900
40,20023,300
38,00021,700
36,00020,000
50HZ CAPACITY MULTIPLIER FACTORS AIRFLOW CAPACITY MULTIPLIER FACTORS
Total BTUH multiplier for 50hz Sensible BTUH multiplier for 50hz
0.9100.910
Total BTUHSensible BTUH
0.9750.950
1.01.0
1.021.05
STANDARD COOLING BTU APPLICATION DATA - INDOOR/OUTDOOR TEMPERATURE F°
Low outdoor ambient programming allows for compressor operation down to -30°F. Outdoor temperatures shown are measured at the condenser section air inlet. l Return air temperature °F.
///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 0 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
MODELSTAGE
RETURN AIR
(DB/WB)
COOLING CA-PACITY 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F
W090APSTAGE 3
75/61.1Total Cooling
Sensible Cooling87,70079,800
87,70079,700
87,70079,600
87,70079,500
87,70079,300
86,30078,800
85,00078,200
83,60077,700
82,20077,100
80,80076,600
79,50076,000
80/62.9Total Cooling
Sensible Cooling97,60092,400
97,60092,200
97,60092,100
97,60091,900
97,60091,800
95,40089,600
93,20087,300
91,00085,100
88,70082,900
86,50080,600
84,30078,400
85/64.7Total Cooling
Sensible Cooling102,90098,400
102,80098,000
102,70097,600
102,60097,200
102,50096,800
100,20094,400
97,80092,100
95,50089,700
93,20087,300
90,80085,000
88,50082,600
W090APSTAGE 2
75/61.1Total Cooling
Sensible Cooling76,10069,800
75,70069,300
75,30068,700
74,90068,100
74,50067,600
73,50067,300
72,40066,900
71,40066,600
70,30066,300
69,30066,000
68,20065,700
80/62.9Total Cooling
Sensible Cooling86,90083,300
86,40082,600
86,00081,900
85,50081,300
85,00080,600
83,00078,300
81,00076,100
79,00073,800
77,00071,600
75,00069,300
73,00067,100
85/64.7Total Cooling
Sensible Cooling92,90087,700
92,60087,100
92,20086,500
91,90085,900
91,50085,300
89,40082,900
87,20080,500
85,10078,200
82,90075,800
80,70073,400
78,60071,000
W090APSTAGE 1
75/61.1Total Cooling
Sensible Cooling29,10027,500
29,10027,200
29,00026,900
29,00026,600
29,00026,300
28,00025,700
27,10025,200
26,20024,600
25,30024,100
24,30023,500
23,40023,000
80/62.9Total Cooling
Sensible Cooling31,90030,900
31,80030,500
31,80030,200
31,70029,800
31,70029,500
30,60028,600
29,40027,700
28,20026,800
27,10025,900
25,90024,900
24,70024,000
85/64.7Total Cooling
Sensible Cooling34,80032,200
34,70032,000
34,60031,800
34,50031,500
34,40031,300
33,10030,300
31,90029,400
30,60028,400
29,40027,400
28,10026,500
26,90025,500
W120APSTAGE 3
75/61.1Total Cooling
Sensible Cooling131,700115,000
128,900113,300
126,000111,600
123,100109,900
120,300108,200
116,100105,700
112,000103,200
107,900100,700
103,80098,200
99,70095,800
95,50093,300
80/62.9Total Cooling
Sensible Cooling133,600123,500
130,700121,700
127,800119,900
124,900118,000
122,000116,200
119,700113,600
117,500111,000
115,200108,400
113,000105,800
110,700103,300
108,400100,700
85/64.7Total Cooling
Sensible Cooling140,400132,100
138,700130,300
136,900128,500
135,200126,600
133,400124,800
130,900122,000
128,500119,300
126,000116,500
123,500113,700
121,100110,900
118,600108,100
W120APSTAGE 2
75/61.1Total Cooling
Sensible Cooling113,40098,700
111,20097,400
109,00096,200
106,80094,900
104,70093,700
101,20091,500
97,80089,300
94,30087,100
90,90084,900
87,40082,600
84,00080,400
80/62.9Total Cooling
Sensible Cooling114,900105,900
112,700104,500
110,500103,200
108,300101,800
106,000100,500
103,90098,400
101,70096,200
99,50094,100
97,40092,000
95,20089,900
93,00087,700
85/64.7Total Cooling
Sensible Cooling123,000113,800
120,900112,400
118,800110,900
116,800109,500
114,700108,100
112,300105,800
110,000103,600
107,600101,300
105,30099,000
102,90096,700
100,60094,400
W120APSTAGE 1
75/61.1Total Cooling
Sensible Cooling48,40042,200
47,20041,500
45,90040,700
44,60040,000
43,40039,200
42,30038,300
41,20037,400
40,00036,500
38,90035,600
37,80034,700
36,70033,900
80/62.9Total Cooling
Sensible Cooling51,40046,300
50,10045,500
48,70044,700
47,40043,800
46,10043,000
44,90042,100
43,70041,200
42,60040,300
41,40039,400
40,30038,500
39,10037,500
85/64.7Total Cooling
Sensible Cooling54,75049,800
53,30048,800
51,90047,900
50,50047,000
49,10046,100
47,90045,100
46,60044,100
45,40043,200
44,20042,200
42,90041,200
41,70040,200
W150APSTAGE 3
75/61.1Total Cooling
Sensible Cooling145,000131,600
143,700130,300
142,400128,900
141,100127,600
139,800126,200
137,000123,700
134,200121,100
131,400118,600
128,600116,100
125,800113,600
123,000111,000
80/62.9Total Cooling
Sensible Cooling162,700145,100
161,200143,600
159,700142,100
158,300140,600
156,800139,100
152,500135,600
148,100132,000
143,700128,400
139,400124,800
135,000121,200
130,700117,600
85/64.7Total Cooling
Sensible Cooling173,600155,100
171,800153,300
169,900151,500
168,000149,700
166,100147,900
161,500144,100
156,900140,300
152,300136,500
147,700132,700
143,000128,900
138,400125,100
W150APSTAGE 2
75/61.1Total Cooling
Sensible Cooling125,100112,000
123,700110,800
122,200109,600
120,800108,300
119,300107,100
116,700104,600
114,000102,100
111,30099,600
108,60097,000
105,90094,500
103,30092,000
80/62.9Total Cooling
Sensible Cooling136,200123,200
134,700121,800
133,100120,500
131,500119,100
130,000117,800
127,000114,600
124,000111,500
121,000108,300
118,000105,100
115,000102,000
112,00098,800
85/64.7Total Cooling
Sensible Cooling143,200131,000
142,100129,800
140,900128,600
139,700127,400
138,500126,200
135,400122,800
132,200119,400
129,000116,000
125,800112,700
122,600109,300
119,400105,900
W150APSTAGE 1
75/61.1Total Cooling
Sensible Cooling46,40041,700
45,80041,200
45,20040,700
44,60040,200
44,10039,700
43,90038,900
43,70038,100
43,50037,300
43,40036,500
43,20035,700
43,00034,900
80/62.9Total Cooling
Sensible Cooling53,10046,600
52,50046,000
51,80045,400
51,10044,800
50,50044,300
49,60043,000
48,70041,800
47,80040,600
46,90039,300
46,00038,100
45,10036,900
85/64.7Total Cooling
Sensible Cooling59,00050,000
58,20049,300
57,40048,700
56,70048,100
55,90047,500
54,90046,200
53,90044,800
52,90043,500
51,90042,200
50,90040,900
49,90039,600
50HZ CAPACITY MULTIPLIER FACTORS AIRFLOW CAPACITY MULTIPLIER FACTORS
Total BTUH multiplier for 50hz Sensible BTUH multiplier for 50hz
0.9100.910
Total BTUHSensible BTUH
0.9750.950
1.01.0
1.021.05
HIGH SENSIBLE COOLING BTU APPLICATION DATA - INDOOR/OUTDOOR TEMPERATURE F°
Low outdoor ambient programming allows for compressor operation down to -30°F. Outdoor temperatures shown are measured at the condenser section air inlet. l Return air temperature °F.
///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 1 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
Low ambient operation disables Balanced Climate Operation. Outdoor temperatures shown are measured at the condenser section air inlet. l Return air temperature °F.
R410A UNIT CHARGE RATESUNIT CIRCUIT A - LBS. CIRCUIT B - LBS. BOTH COOLING CIRCUITS - LBS.
W090AP 8.44 LBS. 8.44 LBS. 16.875 LBS.
W120AP 8.44 LBS. 8.44 LBS. 16.875 LBS.
W150AP 10.25 LBS. 10.25 LBS. 20.50 LBS.
///////
MODELSTAGE
RETURN AIR
(DB/WB)
COOLING CAPACITY 65°F 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F
W090APSTAGE 3
75/68(70%RH)
Total CoolingLatent CoolingLbs H2O Hr.
94,50046,300
43.7
93,80045,900
43.3
90,70043,800
41.3
91,90044,700
42.2
91,60044,700
42.2
90,80044,300
41.8
89,90043,900
41.4
88,90043,300
40.8
87,90042,800
40.4
80/68(55%RH)
Total CoolingLatent CoolingLbs H2O Hr.
96,70037,900
35.8
96,00037,500
35.4
92,90035,400
33.4
94,10036,300
34.2
93,80036,400
34.3
93,00036,000
34
92,10035,500
33.5
91,10034,900
32.9
90,10034,400
32.5
W090APSTAGE 2
75/68(70%RH)
Total CoolingLatent CoolingLbs H2O Hr.
82,20038,900
36.7
81,70038,600
36.4
80,10037,300
35.2
80,40037,900
35.8
79,70037,500
35.4
78,90037,100
35
77,90036,500
34.4
77,00036,100
34.1
75,90035,500
33.5
80/68(55%RH)
Total CoolingLatent CoolingLbs H2O Hr.
83,40030,000
28.3
82,90029,800
28.1
81,30028,500
26.9
81,70029,100
27.5
80,90028,700
27.1
80,10028,200
26.6
79,20027,800
26.2
78,20027,200
25.7
77,10026,600
25.1
W090APSTAGE 1
75/68(70%RH)
Total CoolingLatent CoolingLbs H2O Hr.
29,90014,300
13.5
29,60014,300
13.5
28,90014,000
13.2
29,00014,100
13.3
28,60013,900
13.1
28,30013,900
13.1
28,00013,800
13
27,70013,700
12.9
27,40013,600
12.8
80/68(55%RH)
Total CoolingLatent CoolingLbs H2O Hr.
30,80011,500
10.8
30,40011,300
10.7
29,70011,100
10.5
29,80011,200
10.6
29,50011,100
10.5
29,20011,100
10.5
28,80010,900
10.3
28,50010,800
10.2
28,20010,600
10
W120STAGE 3
75/68(70%RH)
Total CoolingLatent CoolingLbs H2O Hr.
129,80064,300
60.7
129,40064,100
60.5
121,80059,500
56.1
123,60060,300
56.9
124,60061,600
58.1
121,80060,100
56.7
118,40058,300
55
114,50056,200
53
110,00053,900
50.8
80/68(55%RH)
Total CoolingLatent CoolingLbs H2O Hr.
134,30054,200
51.1
133,90054,000
50.9
126,30049,400
46.6
128,10050,200
47.4
129,10051,500
48.6
126,30050,000
47.2
123,00048,300
45.6
119,00046,100
43.5
114,50043,800
41.2
W120STAGE 2
75/68(70%RH)
Total CoolingLatent CoolingLbs H2O Hr.
108,90051,600
48.7
108,70051,400
48.5
108,40051,400
48.5
110,00052,100
49.2
111,50053,500
50.5
109,80052,800
49.8
107,10051,400
48.5
103,70049,500
46.7
99,80047,500
44.8
80/68(55%RH)
Total CoolingLatent CoolingLbs H2O Hr.
112,80041,400
39.1
112,60041,300
39
112,30041,200
38.9
113,90041,900
39.5
115,40043,300
40.8
113,70042,600
40.2
111,00041,200
38.9
107,60039,400
37.2
103,70037,300
35.2
W120STAGE 1
75/68(70%RH)
Total CoolingLatent CoolingLbs H2O Hr.
48,20024,400
23
47,90024,500
23.1
47,30024,600
23.2
46,50024,000
22.6
45,40023,500
22.2
44,10023,000
21.7
42,60022,300
21
40,80021,400
20.2
38,80020,400
19.2
80/68(55%RH)
Total CoolingLatent CoolingLbs H2O Hr.
51,10017,100
16.1
50,70017,000
16
50,10017,200
16.2
49,30016,500
15.6
48,30016,100
15.2
47,00015,60014.7
45,40014,800
14
43,60013,900
13.1
41,60013,000
12.3
W150APSTAGE 3
75/68(70% RH)
Total CoolingLatent CoolingLbs H2O Hr.
149,40073,000
68.9
148,60072,600
68.5
147,20071,800
67.7
146,00071,400
67.4
144,20070,500
66.5
142,00069,300
65.4
139,50068,000
64.2
136,70066,500
62.7
133,50064,800
61.1
80/68(55% RH)
Total CoolingLatent CoolingLbs H2O Hr.
150,40058,600
55.3
149,60058,300
55.0
148,20057,400
54.2
147,00057,100
53.9
145,20056,100
52.9
143,00055,000
51.9
140,50053,600
50.6
137,70052,200
49.2
134,50050,400
47.5
W150APSTAGE 2
75/68(70% RH)
Total CoolingLatent CoolingLbs H2O Hr.
129,70063,000
59.4
128,10062,000
58.5
127,50060,900
57.5
124,90060,200
56.8
123,30059,300
55.9
121,70058,400
55.1
120,10057,600
54.3
118,50056,700
53.5
116,90055,900
52.7
80/68(55% RH)
Total CoolingLatent CoolingLbs H2O Hr.
130,90050,600
47.7
129,30049,700
46.9
128,60048,400
45.7
126,10047,900
45.2
124,50047,000
44.3
122,90046,100
43.5
121,30045,200
42.6
119,70044,400
41.9
118,10043,500
41.0
W150APSTAGE 1
75/68(70% RH)
Total CoolingLatent CoolingLbs H2O Hr.
48,50024,100
22.7
46,10022,700
21.4
45,90022,500
21.2
47,10023,500
22.2
46,50023,300
22.0
45,50022,800
21.5
44,40022,300
21.0
43,10021,600
20.4
41,60020,900
19.7
80/68(55% RH)
Total CoolingLatent CoolingLbs H2O Hr.
50,90020,500
19.3
48,50019,100
18.0
48,40019,000
17.9
49,50019,900
18.8
48,90019,700
18.6
48,00019,300
18.2
46,80018,700
17.6
45,50018,000
17.0
44,00017,300
16.3
BALANCED CLIMATE BTU APPLICATION DATA - INDOOR/OUTDOOR TEMPERATURE F° ///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 2 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
W090AP EVAPORATOR FAN DRY/WET COIL CFM W120AP EVAPORATOR FAN DRY/WET COIL CFM W150AP EVAPORATOR FAN DRY/WET COIL CFM
In H2O Cooling Operation CFM In H2O Cooling Operation CFM In H2O Cooling Operation CFM
0.0 3390 / 3260 0.0 4520 / 4320 0.0 5000 / 4850
0.1 3230 / 3100 0.1 4400 / 4220 0.1 4900 / 4740
0.2 3070 / 2940 0.2 4300 / 4100 0.2 4780 / 4640
0.3 2890 / 2760 0.3 4160 / 3980 0.3 4680 / 4520
0.4 2700 / 2570 0.4 4030 / 3850 0.4 4570 / 4400
0.5 2480 / 2350 0.5 3900 / 3700 0.5 4440 / 4280
0.6 2260 / 2130 0.6 3770 / 3540 0.6 4310 / 4160
0.7 2010 / 1880 0.7 3610 / 3380 0.7 4170 / 4010
0.8 1580 / 1450 0.8 3410 / 3220 0.8 4020 / 3860
0.9 N/A 0.9 3220 / 3050 0.9 3860 / 3710
1.0 N/A 1.0 3040 / N/A* 1.0 N/A*
* Cooling operation not recommended at 1.0” static.
INDOOR AIRFLOW CFM @ STATIC PRESSURES - EC EVAPORATOR FAN MOTOR WITH MODBUS CONTROL///////
DUCT FREE INDOOR COOLING OPERATION @ 5 FT. INDOOR COOLING OPERATION @ 10 FT. OUTDOOR @ 10 FT.
Unit Cooling Stage 3 Cooling Stage1 Cooling Stage 3 Cooling Stage 1 Cooling Stage 3
W090A TBD TBD TBD TBD TBD
W120A 64.4 62.7 63.1 58.2 75
W150A TBD TBD TBD TBD TBD
SOUND DATA - DBA @ 5 FT. AND 10 FT.///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 3 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
MODEL Rated Volts & Phase
No. Field Power
Circuits
Single Circuit Multiple Circuit
lMinimum
Circuit Ampacity
Maximum External Fuse or
Ckt. Brkr.
Field Power Wire Size
Ground
Wire
Minimum Circuit
Ampacity l
MaximumExternal Fuse or Ckt. Breaker
Field Power Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
W090AP, B0ZB09B18
230/208-60-3111
464659
606060
666
101010
W090AP, C0ZC09C18
460-60-3111
262626
404040
888
101010
W090AP, Q0ZQ09Q18
575-60-3111
TBD TBD TBD TBD
W090AP, E0ZE09E18
220/200-50-3111
TBD TBD TBD TBD
W090AP, V0ZV09V18
415-50-3111
TBD TBD TBD TBD
W120AP, B0ZB09B18
230/208-60-31 or 21 or 21 or 2
565659
707070
666
888
323232
252828
404040
404040
888
888
101010
101010
W120AP, C0ZC09C18
460-60-3111
272730
404040
888
101010
W120AP, Q0ZQ09Q18
575-60-3111
TBD TBD TBD TBD
W120AP, E0ZE09E18
220/200-50-3111
555559
606070
666
10108
W120AP, V0ZV07V14
415-50-3111
272730
404040
888
101010
W150AP, B0ZB09B18
230/208-31 or 21 or 21 or 2
676767
909090
444
888
393939
292929
505050
404040
888
888
101010
101010
W150AP, C0ZC09C18
460-3111
323232
404545
888
101010
W150AP, E0ZE09E18
220-3-50111
676767
909090
444
888
393939
292929
505050
404040
888
888
101010
101010
W150AP, V0ZV14V18
415-3-50111
323232
404545
888
101010
W150AP, Q0ZQ09Q18
575-3111
242430
353540
888
101010
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors. Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.l These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor
sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.
ELECTRICAL SPECIFICATIONS — W***AP SERIES///////
ELECTRICAL SPECIFICATIONS — W***AE SERIES///////
MODEL Voltage Kw Rated Volts & Phase
No. Field Power
Circuits
Single Circuit Multiple Circuit
Minimum Circuit
Ampacity
Maximum External Fuse or
Ckt. Brkr.
Field Power Wire Size
Ground Wire
Minimum Circuit
Ampacity
MaximumExternal Fuse or
Ckt. Breaker
Field Power Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
W120AE B 09 230/208-60-3 1 or 2 83 90 3 8 59 25 60 30 6 10 10 10C 18 460-60-3 1 or 2 110 120 1 6 59 52 60 60 6 6 10 10
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 4 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
NOMINALKW
AT 240V (1) AT 208V (1) AT 480V (2) AT 460V (2)
KW 3-PH AMPS BTUH KW 3-PH
AMPS KW KW 3-PH AMPS KW KW 3-PH
AMPS KW
9.0 9.0 21.7 30,717 6.75 18.7 23,038 9.0 10.8 30,717 8.28 10.4 28,260
18.0 18.0 43.3 61,434 13.50 37.5 46,076 18.0 21.7 61,434 16.56 20.8 56,519
(1) These electric heaters are available in 230/208V units only.(2) These electric heaters are available in 480V units only.
ELECTRIC HEAT TABLE - REFER TO ELECTRICAL SPECIFICATIONS FOR AVAILABILITY BY UNIT MODEL///////
VENT CODE
DESCRIPTION UNIT OPERATION DESCRIPTION
B Blank Off Plate W090A, W120A No Ventilation Unit does not include intake and exhaust openings.
E Economizer W090A, W120A Free CoolingFull flow Economizer that uses the logic board and included sensors to operate free cooling. Enthalpy, Dew Point, or Dry Bulb operation is user selectable. A field installed 7” hood is required on each side of the unit.
/////// MEGA-TEC SERIES WALL MOUNTTM VENTILATION OPTION SELECTION CHART
* Note: Ventilation options are not field installable.
“B” Vent Code Option – No Vent This unit is constructed without the economizer vent option and the air intake and exhaust openings are removed. The no vent option may be utilized when outside air intake is not desired or required by local codes.
WALL MOUNTTM VENTILATION OPTIONS SPECIFICATIONS///////
“E” Vent Code Option – Free Cooling EconomizerThe free cooling economizer uses multiple 2-10V High torque actuators to independently control each intake and exhaust damper. Outdoor intake air enters the left and right sides of the unit through intake hoods. Intake air is pre-filtered before entering the unit. Room air is exhausted using one or more separate dampers into the condenser section partition of the unit. A large exhaust air path is provided to reduce room pressure to slight positive pressurization during economizer operation. All dampers include rubber seals for positive shutoff when the economizer is not being operated.
All operation is controlled by the unit logic board. Magnetic proximity sensors attached to each economizer blade indicate a damper failure. A dust sensor is provided to monitor particulates in the outdoor air being brought into the structure, and disable economizer use when the particulate level is too High. Outdoor conditions are monitored through a temperature/humidity sensor located on the side of the unit.
Unit Software Economizer Features:• Standard dry bulb outdoor temperature control of economizer operation.• Optional wet bulb outdoor enthalpy control of economizer operation. Enthalpy measured in either %RH or Dewpoint.• Passive Dehum: Economizer operation can be disabled if humidity levels measured by the LC6000 reach the indoor maximum humidity setpoint. The default passive indoor humidity setpoint is 70%RH*.• Emergency Vent: When NO/NC* contacts are energized in the LC6000, the economizer blades are fully opened and the evaporator Fan is activated.• Emergency Off: When NO/NC* contacts are energized in the LC6000, the economizer blades are closed, and unit operation is disabled.• Emergency Cool: When High temp alarm 2 is active in the LC6000 due to a High temperature event in a zone, the economizer blades are fully opened and the Evaporator Fan is activated. *Default setting.
Note: Fire suppression systems that use gases to flood an area normally require economizer shutdown within 30 seconds of a smoke/fire event. A signal from the LC6000 controller to close all dampers and disable unit operation can take over a minute (time will vary based on daisy chain connections). A relay must be installed to break the 24VAC power supply output from the low voltage transformer in each unit in order to shorten the blade closure time and disable unit operation.
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 5 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
Cabinet Finish OptionsUnit models are available in White and Gray. Painted cabinet construction is comprised of 16 gauge Zinc coated steel. Parts are cleaned, rinsed, sealed, and dried before a polyurethane primer is applied. The cabinet coating is completed with a baked on textured enamel. The resulting finish is designed to withstand 1000 hours of salt spray tests per ASTM B117-03. 1—White
CABINET OPTIONS///////
Hydrophilic Green Coil(standard)
Aluminum Fin (standard coil) AeroMarine Fin (optional coil coating)
Evaporator and Condenser Coil Technicoat Coating OptionsAll models utilize a copper/aluminum evaporator and condenser coil. An additional corrosion resistant TechniCoat 10-2™ coating may be ordered for the evaporator coil (option 1), condenser coil (option 2) or both evaporator and condenser coils (option 3). TechniCoat is a proprietary epoxy-modified phenolic dip coating. Total Immersion ensures complete coverage with no significant loss of thermal efficiency. The 4-step coating system consist of (1) a multi-step cleaning process, (2) chemical etch primer, (3) epoxy-modified phenolic, and (4) phenolic sealer. The result is a corrosion resistant coil that outperforms a copper finned coil, is less expensive, and is also nearly 3 times lighter. ASTM B117 salt spray tests conducted show over 4500 hours with “no fin corrosion or degradation.”
TechniCoat(optional)
EVAPORATOR AND CONDENSER COIL COATING OPTIONS///////
Green Fin Hydrophilic Evaporator Coils Standard On All UnitsBard WALL MOUNT products include a green protective coating applied to the aluminum fin stock used for the evaporator coil. The evaporator coil coating is hydrophilic (attracts water) and allows for proper condensate drainage along with mild corrosion protection. Resistance to corrosive agents include ammonia, sodium hydroxide, sodium chloride, acidic solutions and solvents.
The MEGA-TEC unit can be shipped using a standard wood skid, or can be ordered with a metal platform under the unit. The metal platform supports the unit resting on the ground after wall attachment. Platform construction is 16ga. primered white painted steel. Platform size is 55” wide by 48” deep and is a height of 3.7”.
Optional crates are available to help protect your valuable MEGA-TEC investment during shipping. Constructed from OSB sheathing with steel corner posts, and sized for standard truck transportation. Treated for pests in accordance with the International Plant Protection Convention, Publication 15, Annex 1. Packaging is acceptable for international shipments.
PACKAGING OPTION UNITS USING OPTION DESCRIPTION
X W090A, W120A, W150A Standard wooden skid. The wooden skid is 5” in height.
1 W090A, W120A, W150A Unit ships attached to a white prepaint metal platform. The platform is 4” in height.
2 W090A, W120A, W150A Standard wooden skid. The wooden skid is 5” in height. A wood crate offers additional shipping protection.
3 W090A, W120A, W150A Unit ships attached to a white prepaint metal platform. The platform is 4” in height. Includes wood crate.
6 W090A, W120A, W150A Unit ships attachesd to a Gray prepaint metal platform. Theplatform is 4” in height.
7 W090A, W120A, W150A Unit ships attached to a Gray prepaint metal platform. The platform is 4” in height. Includes wooden crate.
PACKAGING OPTIONS INCLUDING SHIPPING SKIDS, PLATFORMS, AND CRATES///////
4—Gray
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 6 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
Programmable Logic Board (PLC) - Each unit uses a programmable logic board located in the unit control panel to communicate with the LC6000 controller. By using a 2-wire connection, alarm functionality and unit operational commands are communicated. If communication is lost, the unit is able to run by using the logic in the unit controller in orphan mode.
High Pressure Transducer (HPT) - The high pressure transducer provides a means of monitoring high side system pressures. High pressure measurements can be accessed through the unit software. The outdoor fan uses the high pressure transducer to control High system pressure during hot weather compressor cooling operation.
Low Pressure Transducer (LPT) - The low pressure transducer provides a means of monitoring low side system pressures. Low pressure measurements can be accessed through the unit software. At extremely low pressure because of a refrigeration leak, compressor operation is disabled until the alarm is reset. The low pressure transducer is used for low ambient outdoor temperature conditions. The outdoor fan uses the low pressure transducer to control low system pressure during cold weather compressor cooling operation.
High Pressure Control (HPC) - The high pressure control provides a means of protecting each individual refrigeration circuit when extremely high system pressures occur. It is a auto-reset device that is connected to the Compressor Control Module. When activated, the compressor in the refrigeration circuit is disabled until the alarm is cleared in the controller, or power to the unit is reset.
Compressor Control Module (CCM) - Each refrigerant circuit uses an individual compressor control module. The compressor control module locks out compressor operation to protect the refrigeration system based on signals from the High pressure switch. It provides diagnostics to indicate when a refrigerant pressure event occurs, and also sends a signal to the PLC. Low incoming voltage protection suspends compressor operation when incoming voltage is too low. Suspending compressor operation avoids reverse scroll operation. The voltage protection feature includes adjustable timing. An adjustable delay on break timer is provided. Delay on make is 2 mins. plus 10% of delay on break setting.
Crankcase Heater (CCH) - The heater is a belly band that is installed around the base of the compressor that applies heat when the refrigeration system is not operational. This heat is meant to prevent refrigerant oil migration when the unit is not running.
Outdoor Air Temp/Humidity Sensor (OAT) (OAH)- The outdoor sensor measures outdoor temperature and humidity. This information is used for economizer and unit operation. It is located on the upper side of the unit.
Dirty Filter Switch Indicator (DFS) - The switch is adjustable and measures pressure drop across the unit filter surface. When pressure drop is Higher than the switch setting a signal is sent to the PLC to indicate a filter change is necessary. A light is located on the exterior of the unit to indicate filters need to be replaced.
Discharge (Supply) Air Sensor (SAT) - The discharge air sensor provides a temperature reading of the supply air leaving the unit. The sensor is a 10K OHM @ 77°F measuring device. It is installed in the return airstream after the evaporator coils.
Return Air Temperature Sensor (RAT) - The return air sensor provides a temperature reading of the room air entering the unit. The sensor is a 10K OHM @ 77°F measuring device. It is installed in the return airstream behind the return grille.
Mixed Air Temperature Sensor (MAT) - The mixed air sensor provides a temperature reading of the room air entering the unit after it is mixed with outdoor air entering the economizer. The sensor is a 10K OHM @ 77°F measuring device. It is installed in the Evaporator Fan area.
Freeze Sensor (FS) - The 10K freeze sensor provides a way to monitor the evaporator coil temperatures, and help protect the system from a evaporator frost buildup/freeze event. Each evaporator coil has a sensor attached to the coldest location of the coil circuitry.
Evaporator Fan Airflow Switch (AFS) - The airflow switch measures the pressure differential between the Evaporator Fan inlet and outlet. A signal is sent to the PLC to indicate if the Evaporator Fan is not functioning.
Door Switch (DS) - Switches are provided to disable unit operation when service panels are removed from the front of the unit.
Electronic Expansion Valve (EEV) - The EEV controls the unit superheat by using low side system pressure and temperature. The PLC uses unit sensors including low side pressure and temperature to control each refrigerant circuit independently. The EEV has a coil that can be removed and replaced without circuit refrigerant removal. During maintenance, the EEV can be opened or closed through the unit software or with a manual adjustment tool.
FACTORY SUPPLIED STANDARD UNIT COMPONENT DEFINITIONS///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 7 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
Programmable Logic Board: Each unit uses a programmable logic board located in the unit control panel to communicate with the LC controller. By using a 2-wire connection, alarm functionality and unit operational commands are communicated. If communication is lost, the unit is able to run by using the logic in the unit controller in orphan mode.
ADVANCED LOGIC BOARD SPECIFICATIONS
DAISY CHAIN LC6000 AND MEGA-TEC CONNECTION
///////
///////
Power Supply Specifications:24Vac/Vdc +10%/-15% 50/60 HzMax power input: 28 VAInsulation between power supply and instrument:• Mod. 24Vac: reinforced ensured by the use of external safety(class 2) transformer (mandatory)External fuse: 3.15 AT (mandatory)Minimum section of wires of all other connectors: 0.5mm2
Product Specifications:Program memory (FLASH): 128MBData memory: 16MB/8MBInternal clock precision: 100 ppmBattery type: Lithium button battery (removable), BR2032, 3 VdcBattery lifetime characteristics of removable battery: Min. 8 years in normal operating conditions.
User Interface:Type: all the pGD terminals with telephone connector J10.
Operating Conditions:Storage: -40T70 °C, 90% rH non-condensingOperating: -40T60 °C, 90% rH non-condensing
Other Specifications:Environmental pollution degree: 3Index of protection: IP00Class according to protection against electric shock: to be incorporated into Class 1 and/or Class 11 appliancesPTI of the insulating materials PCB: PTI 250'Insulation material: PTI 175Period of stress across the insulating parts: longType of action: 1C; 1Y for SSR versionsType of disconnection or micro interruption: micro interruptioncategory of resistance to heat and fire: Category D (UL94 - VO)Immunity against voltage surges: Category IIIRated impulse voltage: 4000V;Temperature for Ball Pressure Test: 125 °CCommunication Lines Available: 1 shielded RJ45 Ethernet line.Maximum Ethernet port connection cable length: 100M CAT-5 STP
Access to compressors, filter-driers, the economizer exhaust damper motor/linkage, and evaporator drain hoses are behind the condenser fan. Access to the interior condenser section is also recommended for condenser coil cleaning. The condenser fan is on a sliding carriage for easy access to the interior of the condenser section. A safety switch is also installed in the condenser section. Follow all safety instructions provided in the unit installation and service manual provided with the MEGA-TEC.
CONDENSER SECTION ACCESS FEATURE///////
The MEGA-TEC uses modbus control to communicate between the logic board in the units and the logic board in the LC6000. Units and controller are connected using a 2-wire daisy chain connection with a drain. Wires are polarity sensitive. The drain is connected to the LC6000 terminal block.
The LC6000 can be connected anywhere in the daisy chain. EMI line filters are used on the ends of the daisy chain. Only (2) EMI filters are required for the daisy chain, and are supplied with the LC6000 controller.
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 8 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
The EC indoor industrial fan assembly maintains its High efficiency across a wide operating range. Modbus allows accurate fan control by the unit logic board. The result is a significant reduction in energy use when the motor is ran at reduced speeds. The motor uses ball bearing construction, temperature protection, soft start, and an integrated PID controller. Aluminum impeller with steel frame construction for strength.
EVAPORATOR FAN SPECIFICATIONS///////
SPECIFICATION UNITS DESCRIPTION
DEGREE OF PROTECTION W090A, W120A, W150A IP55
MOISTURE/ENV. CLASS W090A, W120A, W150A F4-1
INSULATION CLASS W090A, W120A, W150A F
PROTECTION CLASS W090A, W120A, W150A 1
EMC IMMUNITY W090A, W120A, W150A EN61000-6-2
WEIGHT W090A, W120A, W150A 66lbs. (30kg)
The valves are certified in accordance with the main national and international standards. Accurate control is achieved with communication between the valve and the unit logic control board. The valve is designed especially to optimize management of air conditioning and refrigeration systems, with special focus on energy savings. In addition, Highly precise control is assured by the special shape of the movable elements, the stroke length, stainless steel ball bearings, and High precision mechanical components.
ELECTRONIC EXPANSION VALVE (EEV) SPECIFICATIONS///////
SPECIFICATION UNITS DESCRIPTION
EEV VALVES USED W090A, W120A, W150A 2
POWER SUPPLY VOLT. W090A, W120A, W150A 12V
DRIVE FREQUENCY W090A, W120A, W150A 50HZ
PHASE RESISTANCE W090A, W120A, W150A (25°C/77°F) 40 OHM
INDEX OF RESISTANCE W090A, W120A, W150A IP67
STEP ANGLE W090A, W120A, W150A 7.5°
LINEAR ADVANCE/STEP W090A, W120A, W150A .02MM (.001IN)
CLOSING STEPS W090A, W120A, W150A 500
CONTROL STEPS W090A, W120A, W150A 480
The EC outdoor industrial fan assembly maintains its High efficiency across a wide operating range. Modbus allows accurate fan control by the unit logic board. The result is a significant reduction in energy use when the motor is ran at reduced speeds. The motor contains reverse polarity and locked motor protection. Aluminum blade sprayed with PP plastic. Steel grille coated with PP plastic. Fan has a black gloss paint finish.
CONDENSER FAN SPECIFICATIONS///////
SPECIFICATION UNITS DESCRIPTION
DEGREE OF PROTECTION W090A, W120A, W150A IP55
MOISTURE/ENV. CLASS W090A, W120A, W150A F4-1
INSULATION CLASS W090A, W120A, W150A F
PROTECTION CLASS W090A, W120A, W150A 1
EMC IMMUNITY W090A, W120A, W150A EN61000-6-2
WEIGHT W090A, W120A, W150A 89lbs (40.2kg)
1 0 E E R M E G A - T E C T M S E R I E S P A G E 1 9 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
CABINET DIMENSIONS - W090A, W120A, AND W150A SERIES UNITS///////
CLEARANCE DIMENSIONS - W090A, W120A, AND W150A SERIES UNITS///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 2 0 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
FEATURE DESCRIPTION
Standard Cooling Mode
Standard Cooling mode provides sensible cooling capacity to lower the room temperature, and also provides latent capacity to reduce mois-ture content in the air. Standard Cooling mode is enabled by the LC6000 when humidity levels are normal in the area being conditioned, and provides a balance of sensible cooling operation and humidity control. Default standard cooling mode is 70%RH zone humidity and below. Default LC6000 cooling setpoint is 77°F.
High Sensible Cooing Mode
High Sensible Cooling mode offers a way to increase sensible capacity when moisture control does not require additional latent capacity. During High Sensible Cooling mode, the indoor blower CFM is increased to provide additional sensible cooling capacity inside the struc-ture. High Sensible Cooling mode is enabled by the LC6000 when humidity levels are low in the area being conditioned. High Sensible Mode is selectable for each zone of operation. High sensible mode is not enabled by default, and is enabled through the LC6000 controller. Default High Sensible Cooling mode (humidity control off) setting is 60%RH zone humidity and below.
Balanced Climate Cooling Mode
Balanced Climate mode offers a way to help control humidity in an area and reduce the need for electric reheat dehumidification which saves energy costs. During Balanced Climate mode, the indoor blower CFM is reduced to remove moisture inside the structure. Balanced climate operation is operated by the LC6000 when humidity levels are High in the area being conditioned. Balanced Climate is enabled by default, and operates during active dehumidification mode. Default LC6000 Balanced Climate (active dehumidification) setpoint is 70%RH zone humidity and above.
Compressor Cooling Staging
Three stages of cooling capacity are available in the MEGA-TEC unit. By using a 2 stage compressor in circuit 1 and a 1 stage compressor in circuit 2, 3 total cooling stages are available. Stage 3 provides full 100% cooling capacity. Stage 2 provides approximately 80% cooling capacity. Stage 1 provides approximately 33% cooling capacity. Unit staging is based on cooling capacity needs inside the zone. Standard, High Sensible, and Balanced Climate cooling operation is available in all compressor cooling stages.
Free Cooling Mode (Optional)
Free Cooling mode uses an optional economizer to take advantage of cooler temperature outdoor conditions to provide cooling in the zone. When the economizer is operational, total energy use of the unit during cooling is reduced significantly. Settings are provided to limit econ-omizer use to outdoor conditions the user feels are acceptable for bringing in outdoor air. Sensors for outdoor temperature, humidity, and dust are provided for monitoring outdoor conditions. Economizer use also provides emergency ventilation options (see economizer section on page 12). Default LC6000 economizer operation is temp/humidity settings of 70°F, 80%RH. Default dewpoint setting is 55°F if used instead of %RH.
Heating Mode (Optional)Heating mode uses optional 2 stage electric heat to warm the zone being conditioned when needed. By installing properly sized electric heat options, a zone can be heated when equipment or other heat sources inside the area are not producing enough heating capacity to overcome cold outdoor conditions. Default LC6000 heating setpoint is 60°F.
Electric Reheat Dehumidification Mode
(Optional)
Optional Electric Reheat Dehumidification mode offers an additional way to help control humidity in an area by allowing concurrent com-pressor and electric heat operation. By warming the supply air during compressor cooling mode, the unit can run for an extended period of time reducing humidity in the area. Electric Reheat operation is enabled by the LC6000 when humidity levels are High in the area being conditioned. Power requirements are increased in order to use Electric Reheat Dehumidification. Be sure to follow all electrical guidelines in the installation instructions and provide incoming power for concurrent heating and cooling operation. Default LC6000 electric reheat dehumidification setpoint is 80%RH zone humidity and above.
Emergency Cooling Mode
Emergency cooling provides a way to use economizer ventilation air for cooling, along with all available units on in compressor cooling mode when excessive heat is present in the zone. Optional economizers must be present in at least one of the units for outdoor air to be used for emergency cooling. Emergency cooling mode operates when the high temperature 2 alarm is present in the LC6000 controller. The default LC6000 high temperature 2 alarm setting is 90°F.
Stand Alone Mode
Stand Alone mode allows the MEGA-TEC unit to cool the structure if a LC6000 is not used. Setpoints are adjustable in the unit PLC for stand alone mode through the use of the TEC-EYE. The unit will use the return air temperature sensor to monitor indoor temperature con-ditions. The Evaporator Fan will run in continuous fan mode to provide room air circulation and allow the return air temperature sensor to monitor indoor room temperature. Room humidity is not monitored during stand alone mode operation, and balanced climate mode will not occur. Optional electric reheat operation is not available in this mode of operation.
Orphan Mode
Orphan mode allows the MEGA-TEC unit to continue to cool the structure if communication with the LC6000 is not available. Setpoints are adjustable in the unit PLC for orphan mode through the use of the TEC-EYE. The unit will use the return air temperature sensor to monitor indoor temperature conditions. The Evaporator Fan will run in continuous fan mode to provide room air circulation and allow the return air temperature sensor to monitor indoor room temperature. Room humidity is not monitored during orphan mode operation, and balanced climate mode or optional electric reheat operation will not occur until communication with the LC6000 controller is restored.
Alarm LoggingThe MEGA-TEC logs alarms that occur in the unit for diagnostic and maintenance purposes. Alarm logs can be displayed by connecting the TEC-EYE to the unit PLC board, or can be downloaded to a computer using a MicroUSB cable.
Software UpdatesThe MEGA-TEC unit software can be upgraded by using a computer and connecting to the unit PLC board with a MicroUSB cable. Software updates are accessible from the Bard website: www.bardhvac.com.
Self Test OperationMEGA-TEC startup commissioning and diagnostic troubleshooting features include a self test that is available through the unit PLC menu. During the self test, staged cooling operation of Circuit 1 and Circuit 2 can be energized for an adjustable time period. Economizer damper operation can be observed and verified, along with electric heat operation. Indoor and outdoor fan operation can also be verified.
A/C Circuit MonitoringMEGA-TEC startup commissioning and diagnostic troubleshooting features include A/C circuit monitoring that is available through the unit PLC menu. During A/C circuit monitoring, staged cooling operational pressures of Circuit 1 and Circuit 2 can be observed. High pressure, low pressure, superheat and subcooling information is displayed for both circuits.
Model and Serial NumberThe MEGA-TEC unit software saves the unit model and serial number for display inside the LC6000 controller software. Model number nomenclature of the unit is used by the LC6000 to identify the features available in the unit.
MEGA-TEC PLC UNIT SOFTWARE FEATURES///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 2 1 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
FEATURE DESCRIPTION
1 to 14 Unit OperationA single LC6000 controller can operate 1 to 14 PLC controlled units. Units connected to the LC6000 can include the MEGA-TEC, MULTI-TEC, and FUSION-TEC products in individual zones. Connection between the LC6000 and units is made with a 2-wire shielded cable with drain in a Daisy Chain configuration.
3 Zones of Operation
A single LC6000 controller can operate 1 to 3 zones with individual climate setpoints. Each zone can contain 1 to 14 units (cannot exceed a total of 14 units). MEGA-TEC, MULTI-TEC, and FUSION-TEC products can be used in individual zones, but cannot be combined in one zone. Appli-cations for zoning include separate battery rooms, offices for occupants, switch rooms, pump house equipment rooms, VFD areas, and large open floor plan structures.
Temperature and Humidity Measurement
Zone temperature measurement can be done using the return air sensors in the units and the remote sensors connected to the LC6000, or can be measured just using the remote LC sensors. An average temperature of all the unit and remote LC sensors (default), only the units in continuous fan mode and the remote LC sensors, or the remote LC sensors only can be used to control cooling and heating functionality. Zone 1 can contain (1) remote temperature/humidity sensor and (1) remote temperature sensor for a total of (2) remote sensors. Zone 2 and Zone 3 can contain (1) remote temperature/humidity sensor in each zone. The LC6000 controller ships with 1 temperature and humidity re-mote sensor. Additional zone temperature and humidity sensors must be purchased separately. Remote temperature/humidity sensors require 5-wire with drain shielded cable. Remote temperature sensors require 2-wire with drain shielded cable.
Lead/Lag Staging Operation
Lead/Lag allows for staged unit operation to help control heating and cooling capacity inside a zone. Staging is necessary to help save energy and reduce unit short cycling. Three staging strategies are available. First In First Out (FIFO) allows the first unit activated in cooling or heat-ing to be the first one de-activated as conditions reach set point. First In Last Out (FILO) allows the first unit activated in cooling or heating to be the last one de-activated as conditions reach set point. Demand Staging (DS) allows the unit sensing the Highest return air temperature to operate first in cooling mode or the lowest return air temperature unit to operate in heat mode. Default setting is FIFO.
Lead/Lag Unit RotationUnits in each zone of operation can use a rotational schedule to change the lead and lag unit priority. This feature, when used, will allow run time for all of the units to be similar in the zone. A time period of 0 to 30 days can be selected in the LC6000 controller to adjust the lead/lag unit priority. When set to 0, lead/lag priority will stay the same and the unit rotation schedule will be disabled. Default setting is 7 days.
Maximum Units Running
The maximum units running setting allows for a limitation of the number of units that run in free cooling, cooling, or heating operation. By using this feature, cooling and heating capacity can be limited by not allowing all units installed to operate in heating and cooling. Typical applications do not require the use of this feature, as units will normally stage up and down to meet heat load capacity needs. Default setting is 14 units.
Comfort Mode OperationComfort Mode is used to change room conditions inside a zone to comfortable temperature temporarily wHighle technicians, contractors, or other occupants are in the area. Comfort mode is easily activated from the LC6000. Once activated, a user selectable time period limits the amount of time the zone is conditioned to the user selected set point. The default setpoint is 72°F for 30 mins.
Humidifier Operation (Optional)
A field supplied humidifier can be connected to the LC6000 and used in each zone for a total of (3) humidifiers. A humidification setpoint can be used to increase humidity levels in each zone of operation when moisture levels are too low. ON/OFF relay connections are provided, or a communicating Carel Humidifier can be used. The default humidification setpoint is 45%RH.
Continuous Blower Operation
Continuous fan operation can be set for individual units in a zone. The available settings are None, Lead unit only, All units, or Custom. The custom command allows for fan selection of each individual unit. Default is None.
Remote Unit and Zone Monitoring
It is very important to monitor site conditions remotely when critical electronics, batteries, and other important equipment requires specific indoor conditions. The LC6000 contains many remote monitoring features that allow a technician or call center to remotely view the status of all zones and equipment being used. Wired alarm inputs allow for connecting generators and other equipment for remote monitoring. Wired alarm outputs allow for direct connection to a Network Operations Center (NOC). Modbus control and webpages are also provided via ethernet connection. See Remote monitoring features section.
Alarm LoggingThe LC6000 logs alarms that occur in the unit and events including generator and smoke/fire alarms for diagnostic, maintenance, and remote monitoring purposes. Alarm logs can be displayed through remote monitoring, on the LC6000 display, or exported using a computer and MicroUSB cable.
Password ProtectionUser, Technician, and Factory passwords can be set and used in the controller. The user password allows viewing of controller operation. The technician password allows viewing and setpoint adjustment. The factory password allows access to all functionality.
Software UpdatesThe LC6000 software can be upgraded by using a computer and connecting to the controller PLC board with a MicroUSB cable. Software updates are accessible from the Bard website: www.bardhvac.com.
MEGA-TEC LC6000 SOFTWARE FEATURES///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 2 2 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
FEATURE DESCRIPTION
Emergency Off Input
Wired NO/NC* contact inputs are provided for connection to field supplied equipment. During an emergency off input event, a modbus command to shut off unit operation is sent to units connected and communicating through the daisy chain. A emergency off event can be monitored remotely through a wired output and ethernet connection. It is important to follow all guidelines, codes, and requirements of smoke/fire suppression systems including the need to break power to the unit and close economizer dampers within a certain time period. Additional relays, wiring, or field supplied accessories may need to be added to the units and equipment to achieve all requirements for the use of a smoke/fire suppression system.
Emergency Vent Input
Wired NO/NC* contact inputs are provided for connection to field supplied equipment. During an emergency vent input event, a modbus command to open all unit economizer dampers is sent to units connected and communicating through the daisy chain. A emergency vent event can be monitored remotely through a wired output and ethernet connection. It is important to follow all guidelines, codes, and require-ments of hydrogen monitoring systems including the use of a separate ventilation fan system when necessary.
Generator Run Input
Wired NO/NC* contact inputs are provided for connection to a field supplied generator. During an generator input event, a modbus com-mand to limit the number of units that can be operated is sent to units connected and communicating through the daisy chain. A generator event can be monitored remotely through a wired output and ethernet connection. It is important to set the limitation of how many units can run during a generator event when using the generator run input (defaults to 0 units). Individual unit operation is selectable for a generator event.
Bard Guard InputWired contact inputs are provided for connection to a Bard Guard anti-theft security option. During an Bard Guard input event, an audible alarm is activated. A Bard Guard vent can be monitored remotely through a wired output and ethernet connection. The Bard Guard security option is not currently available for the MEGA-TEC product. *Currently available for Fusion-Tec products ONLY.
Indoor Space Pressure For future use only.
Outdoor Thermostat Input For future use only.
Outdoor Humidistat Input For future use only.
MEGA-TEC LC6000 WIRED INPUTS FOR SITE EQUIPMENT///////
FEATURE DESCRIPTION
Emergency Off Alarm Wired NO*/NC contact outputs are provided. During an emergency off input event, an alarm is sent to the contact output.
Emergency Vent Alarm Wired NO*/NC contact outputs are provided. During an emergency vent input event, an alarm is sent to the contact output.
Generator Run Alarm Wired NO*/NC contact outputs are provided. During an generator run input event, an alarm is sent to the contact output.
Bard Guard Alarm Wired NO*/NC contact outputs are provided. During an Bard Guard input event, an alarm is sent to the contact output.
Indoor Humidity AlarmWired NO*/NC contact outputs are provided. During a High humidity event where humidity levels have exceeded the maximum humidity alarm setting in any zone of operation, an alarm is sent to the contact output. The default low humidity alarm setting is 20%. The default High humidity alarm setting is 85%.
High Indoor Temperature Alarm
Wired NO*/NC contact outputs are provided. During a High temperature event where indoor temperature has exceeded the High tempera-ture alarm setting in any zone of operation, an alarm is sent to the contact output. The High temperature 2 alarm is set to 90°F by default.
Low Indoor Temperature Alarm
Wired NO*/NC contact outputs are provided. During a low temperature event where indoor temperature is below the low temperature alarm setting in any zone of operation, an alarm is sent to the contact output. The low temperature alarm is set to 45°F by default.
Zone 1 Unit Alarm
Wired NO*/NC contact outputs are provided. This feature allows the user to configure what unit alarm conditions are going to be sent to the alarm contacts for Zone 1. A zone unit alarm can contain any of the following unit alarms: Blower Failure, Dirty Condenser Coil, Economiz-er Dust Alarm, Economizer Fail, EEV Failure, Dirty Filter Alarm, Freezestat Active, High Refrigerant Pressure, Low Refrigerant Pressure, Return Air High/Low Alarm, Sensor Fail Alarm, Supply Air High/Low Alarm, and Unit Power Loss Alarm. The default configuration is to alarm on a unit High or low pressure event.
Zone 2 Unit Alarm
Wired NO*/NC contact outputs are provided. This feature allows the user to configure what unit alarm conditions are going to be sent to the alarm contacts for Zone 2. A zone unit alarm can contain any of the following unit alarms: Blower Failure, Dirty Condenser Coil, Economiz-er Dust Alarm, Economizer Fail, EEV Failure, Dirty Filter Alarm, Freezestat Active, High Refrigerant Pressure, Low Refrigerant Pressure, Return Air High/Low Alarm, Sensor Fail Alarm, Supply Air High/Low Alarm, and Unit Power Loss Alarm. The default configuration is to alarm on a unit High or low pressure event.
Zone 3 Unit Alarm
Wired NO*/NC contact outputs are provided. This feature allows the user to configure what unit alarm conditions are going to be sent to the alarm contacts for Zone 3. A zone unit alarm can contain any of the following unit alarms: Blower Failure, Dirty Condenser Coil, Economiz-er Dust Alarm, Economizer Fail, EEV Failure, Dirty Filter Alarm, Freezestat Active, High Refrigerant Pressure, Low Refrigerant Pressure, Return Air High/Low Alarm, Sensor Fail Alarm, Supply Air High/Low Alarm, and Unit Power Loss Alarm. The default configuration is to alarm on a unit High or low pressure event.
MEGA-TEC LC6000 WIRED ALARM OUTPUTS FOR REMOTE SITE MONITORING///////
* Default Setting
1 0 E E R M E G A - T E C T M S E R I E S P A G E 2 3 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
FEATURE DESCRIPTION
Ethernet Connection
Ethernet access to all connected equipment is available through the LC6000 controller. A integrated ethernet port is located on the programmable logic board located inside the LC6000. When connected to a network, the connection allows for remote monitoring using software from a remote location. The ethernet connection uses Internet Protocol Version 4 (IPV4). When using the ethernet connection, it is important for the user to provide appropriate ethernet network security measures.
Modbus Remote Access
By using the ethernet connection, the controller will respond to Modbus commands allowing access to setpoints, alarms, temperature measurements and humidity measurements for each zone. The measurement units (English/Metric) retrieved during communication are de-termined by the controller unit of measure setting. This is configured on-site and cannot be changed remotely. For more information about setting measurement units, please refer to the latest version of the 2100-669 LC6000 Service Instructions manual. Modbus addressing instructions and register points are available in the latest version of the Modbus Supplemental Manual 7960-791.
Webpage Remote AccessWebpages allow controller access with a computer using a standard web browser. The web browser grapHighcal interface provides a visual look at unit operation, viewing and adjustment of zone indoor conditions, alarm events, data trending, and a virtual interface of the display/buttons used on the LC6000 controller. By using the ethernet connection, the controller can be accessed through webpages.
MEGA-TEC LC6000 ETHERNET FEATURES FOR REMOTE SITE MONITORING///////
GRILLE NO. UNITS USING GRILLE DESCRIPTION OF LOUVER GRILLE WEIGHT
SG-10W W090A, W120A, W150A16" x 43" with 2" Flange 4 way deflection supply grille. Use for standard installations
6LBS (2.72KG)
RG-10W W090A, W120A, W150A22" x 43" with 2" Flange return grille with open egg-crate design. Use for standard installations.
12LBS (5.44KG)
NON-DUCTED SUPPLY AND RETURN GRILLES Supply and return louver grilles are of a brushed aluminum finish. 2” flange versions are recommended for standard installations to allow grille attachment when large wall openings are present.
///////
NON-DUCTED SUPPLY GRILLES - SPREAD AND THROW CHARACTERISTICS One of the most important setup procedures for non-ducted supply applications is to adjust the 4 way supply grille blade positions. Placement of equipment, occupants, the thermostat, and room size can all play an important role in deciding how the conditioned supply air must be directed in an indoor area. The chart below may be used as a reference tool to help with this process.
SUPPLY GRILLE AIRFLOW CFM DEFLECTION AK FACTOR TOTAL PRESSURE MAX. THROW
SG-10W
2682 CFM
0º 3.49 .044" WC 85 ft.
22.5º 3.35 .049" WC 68 ft.
45º 3.04 .074" WC 43 ft.
3129 CFM
0º 3.49 .060" WC 91 ft.
22.5º 3.35 .067" WC 73 ft.
45º 3.04 .101" WC 46 ft.
3576 CFM
0º 3.49 .078" WC 98 ft.
22.5º 3.35 .087" WC 78 ft.
45º 3.04 .132" WC 45 ft.
4470 CFM
0º 3.49 .122" WC 109 ft.
22.5º 3.35 .136" WC 87 ft.
45º 3.04 .207" WC 55 ft.
5364 CFM
0º 3.49 .175" WC 120 ft.
22.5º 3.35 .196" WC 96 ft.
45º 3.04 .298" WC 60 ft.
///////
1 0 E E R M E G A - T E C T M S E R I E S P A G E 2 4 O F 2 4 FO R M N O. S3565 - 012 0 • S U P E R S E D E S S3565 -819
Due to our continuous product improvement policy, all specifications subject to change without notice. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
MEGA-TEC UNIT NOTES:
Bard Manufacturing Company, Inc.1914 Randolph Dr., Bryan, OH 43506419-636-1194
www.bardhvac.com
///////