1227982- manual- performa filter series
TRANSCRIPT
-
8/7/2019 1227982- Manual- Performa Filter Series
1/24
440i Control
940F Control
960F Control
Water Conditioning Control SystemInstallation, Operation and Maintenance Manual
Autotrol Performa Filter Valve Series TM
-
8/7/2019 1227982- Manual- Performa Filter Series
2/242
Table of Contents
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Location Selection
Water Line Connection
Drain Line Connection
Placing Conditioner into Operation . . . . . . . . . 4
Electrical Connection
400 Series Control Settings. . . . . . . . . . . . . . . 5
440i
Programming
900 ProSeries Control Settings . . . . . . . . . . . . 5
940F
Programming
Manual Regeneration
960F
ProgrammingLevel I Parameters
Level II Parameters
Regeneration . . . . . . . . . . . . . . . . . . . . . . . . . 11
Manual Regeneration
Automatic Regeneration
Removing the Valve Assembly or Servicing . 12
Removing 440i Control for Servicing. . . . . . . 12
Removing the 940F and 960F Controls for
Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Preventative Maintenance . . . . . . . . . . . . . . . 14Water Meter Maintenance
Specifications . . . . . . . . . . . . . . . . . . . . . . . . 15
Control Valving Identification . . . . . . . . . . . . . 17
Valve Disc Principle of Operation . . . . . . . . . 17
Flow Diagrams. . . . . . . . . . . . . . . . . . . . . . . . 17
Replacement Parts . . . . . . . . . . . . . . . . . . . . 19
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 22
-
8/7/2019 1227982- Manual- Performa Filter Series
3/243
Installation
All plumbing and electrical connections must conform
to local codes.
Inspect unit carefully for carrier shortage or shipping
damage.
Location Selection
1. The distance between the unit and a drain should be
as short as possible.
2. If it is likely that supplementary water treatment
equipment will be required, make certain adequate
additional space is available.
3. Do not install any unit closer to a water heater than
a total run of 10 feet (3 m) of piping between the
outlet of the conditioner and the inlet to the heater.
Water heaters can sometimes overheat to the
extent they will transmit heat back down the cold
pipe into the unit control valve.
Hot water can severely damage the conditioner. A
10-foot (3-m) total pipe run, including bends,
elbows, etc., is a reasonable distance to help
prevent this possibility. A positive way to prevent
hot water flowing from heat source to the
conditioner, in the event of a negative pressure
situation, is to install a check valve in the soft
water piping from the conditioner. If a check valve
is installed, make certain the water heating unit
is equipped with a property rated temperature
and pressure safety relief valve. Also, be
certain that local codes are not violated.4. Do not locate unit where it or its connections
(including the drain) will ever be subjected to room
temperatures under 34oF (1oC) or over 120oF
(49oC).
5. Do not install unit near acid or acid fumes.
Water Line Connection
The installation of a bypass valve system is
recommended to provide for occasions when the water
conditioner must be bypassed for hard water or for
servicing.
The most common bypass systems are the Autotrol
Series 1265 bypass valve (Figure 1) and plumbed-in
globe valves (Figure 2). Though both are similar in
function, the Autotrol Series 1265 bypass offers
simplicity and ease of operation.
Figure 1
Figure 2
Drain Line Connection
Note: Standard commercial practices are expressedhere. Local codes may require changes to the following
suggestions.
1. Ideally located, the unit will be above and not more
than 20 feet (6.1 m) from the drain. For such
installations, using an appropriate adapter fitting,
connect 1/2-inch (1.3-cm) plastic tubing to the drain
line connection of the control valve.
2. If the backwash flow rate exceeds 5 gpm
(22.7 Lpm) or if the unit is located more than 20 feet
(6.1 m) from drain, use 3/4 -inch (1.9-cm) tubing for
runs up to 40 feet (12.2 m). Also, purchase
appropriate fitting to connect the 3/4-inch tubing tothe 3/4-inch NPT drain connection.
3. If the unit is located where the drain line must be
elevated, you may elevate the line up to 6 feet
(1.8 m) providing the run does not exceed 15 feet
(4.6 m) and water pressure at conditioner is not less
than 40 psi (2.76 bar). You may elevate an
additional 2 feet (61 cm) for each additional 10 psi
(0.69 bar).
4. Where the drain line is elevated but empties into a
drain below the level of the control valve, form a
Not in Bypass In Bypass
BYPASS BY
PASS
BYPASS
BYPASS
WaterConditioner
In Out
WaterConditioner
In Out
Not in Bypass In Bypass
WaterConditioner
WaterConditioner
-
8/7/2019 1227982- Manual- Performa Filter Series
4/244
7-inch (18-cm) loop at the far end of the line so that
the bottom of the loop is level with the drain line
connection. This will provide an adequate siphon
trap.
5. Where the drain empties into an overhead sewer
line, a sink-type trap must be used.
IMPORTANT: Never insert drain line into a drain, sewer
line or trap. Always allow an air gap between the drain
line and the wastewater to prevent the possibility of
sewage being back-siphoned into the conditioner.
Figure 3
Note: Standard commercial practices have been
expressed here. Local codes may require changes to
these suggestions.
Placing Conditioner into Operation
After all previous steps have been completed the unit is
ready to be placed into operation. Follow these stepscarefully.
1. Remove control valve cover.
Note: The following steps will require turning the
indicator knob (Figure 4 and Figure 5) or the cycle
indicator (Figure 7) to various positions. Manually
rotate the camshaft COUNTERCLOCKWISE only
until indicator knob and cycle indicator points to
desired position. (See manual regeneration
sections for each controls manual operation.)
2. Rotate indicator knob or cycle indicator
COUNTERCLOCKWISE until it points directly to
the word BACKWASH.
3. Fill media tank with water.
a. With water supply off, place the bypass valve(s)
into the service position.
b. Open water supply valve very slowly to
approximately the 1/4 open position.
IMPORTANT: If opened too rapidly or too far, media
may be lost. In the 1/4 open position, you should hear
air escaping slowly from the drain line.
c. When all of the air has been purged from the
tank (water begins to flow steadily from the
drain), open the main supply valve all the way.
d. Allow water to run to drain until clear.
e. Turn off water supply and let the unit stand for
about five minutes. This will allow all trapped air
to escape from the tank.4. Place the conditioner into operation.
a. Advance the indicator knob or cycle indicator
COUNTERCLOCKWISE to the SERVICE
position and run water from a nearby faucet
until the water is clear.
Electrical Connection
100 VAC, 115 VAC, and 230 VAC units: Remove twist
tie from the power cord and extend cord to its full
length. Make sure the power source matches the rating
printed on the control. Be certain a wall switch does not
control the outlet.
12 VAC: Connect the plug of the transformer (supplied)
secondary cable to the mating socket at the rear or
bottom of the timer housing. Be certain the transformer
is secure and is plugged into a power source of correct
voltage that is not controlled by a wall switch.
Right Way
-
8/7/2019 1227982- Manual- Performa Filter Series
5/245
400 Series Control Settings
440i Control
Figure 4
Programming
1. Set days of regeneration on skipper wheel (Figure 4).
Pull all skipper pins outward (away from
control).
Rotate skipper wheel until day arrow points tocurrent day or number 1.
Depress skipper pin(s) at day(s) for whichregeneration is desired.
2. Set the time of day.
Grasp timer knob and pull outward.
Rotate in either direction until the timer arrowpoints to the actual time of day.
Release timer knob.
Note: with the time of day properly set, the conditioner
will regenerate at about 2:30 a.m. If you prefer to have
the unit regenerate at an earlier or later time, simply set
current time-of-day accordingly (e.g., to have the unit
regenerate at 4:30 a.m. - two hours later - set the clock
two hours earlier than the actual time of day.)
Note: The timer locking pin should always be horizontal
(Figure 4) during operation.
Guest Cycle
When abnormally high water usage exhausts your
water conditioners capacity ahead of schedule, an
extra regeneration can be achieved. Depress the
indicator knob on the 440i (Figure 4) with a wide-blade
screwdriver and turn COUNTERCLOCKWISE to
START to initiate a regeneration. It will take a few
minutes for regeneration to start. A normal regeneration
will take approximately two hours.
Manual Regeneration
Electricity is used only to run the control and to rotate
the camshaft. All other functions are operated by water
pressure. Therefore, in the event of a power outage, all
the regeneration positions may be dialed manually by
depressing the indicator knob and turning
COUNTERCLOCKWISE (Figure 4). The following
cycle times should be used for proper regeneration:
BACKWASH - 20 minutes
PURGE - 10 minutes
900 ProSeries Control Settings940F Control
Figure 5
Programming
1. Set days of regeneration (Figure 5).
Pull all day pins outward (away from control).
Depress day pin(s) for which regeneration isdesired.
Note: The NEXT DAY day pin is noted on the timer
face. Depressing this pin will insure a regeneration the
next day at approximately 2:00 a.m. Since the calendar
cap progresses CLOCKWISE, depressing the day pin
immediately COUNTERCLOCKWISE will insure a
regeneration the following day at 2:00 a.m. This
progression is noted on the timer face as FUTURE
DAYS.
Day Arrow Skipper PinsSkipper Wheels
Indicator KnobTimer Locking Pin
Time ArrowTimer Knob
FASTRINSE
BACKWASH
SERVICE
FOR MANUAL
BACKWASH
ROTATE POINTER
COUNTER
CLOCKWISE TO
START POSITION
TO ADJUST BACKWASH
MINUTES, ROTATESMALL DIAL COUNTER
CLOCKWISE.
DO NOT ADJUST
DURING BACKWASH
TO SET
REGENERATION
DAYS PRESS PINS IN
Performa FilterTM
BACKWASH COMPLETE
Indicator Knob
Clock Dial Day Pins
-
8/7/2019 1227982- Manual- Performa Filter Series
6/246
2. Set the time of day.
Rotate Clock Dial CLOCKWISEuntil the pointeris directed at the current time.
Note: With the time of day properly set, the conditioner
will regenerate at about 2:00 a.m. If you prefer to have
the unit regenerate at an earlier or later time, simply set
the current time-of-day accordingly (e.g., to have theunit REGENERATE at 4:00 a.m. - two hours later - set
the clock two hours earlier than the actual current time).
Note: Do not rotate the Calendar Cap by hand; the
clock dial indexes it daily. To manually index the
Calendar Cap, rotate the Clock Dial CLOCKWISE one
complete turn for every day to be indexed.
Figure 6
How to Adjust the Backwash Time
With the indicator knob in the BACKWASH COMPLETE
position (Figure 6), rotate the Backwash DialCOUNTERCLOCKWISEat least one full turn to cancel
the previous setting. A light clicking will be replaced by
a heavier clicking when the previous setting is
cancelled. Then, rotate the Backwash Dial to the
desired backwash time. The numbers are minutes of
backwash per regeneration.
Manual Regeneration
Electricity is used only to run the control and to rotate
the camshaft. All other functions are operated by water
pressure. Therefore, in the event of a power outage, all
regeneration positions may be dialed manually. Grasp
the indicator knob and turn COUNTERCLOCKWISEtoeach regeneration cycle (rotation is much easier if you
grasp the camshaft with your free hand and turn it at
the same time). The following cycle times should be
used for proper regeneration.
BACKWASH - 20 minutes
PURGE - 10 minutes
960F Control
Figure 7
Programming
This section covers all aspects of programming the
control. The control is shipped from the factory with
default values for most parameters. These default
values will result in a system capacity of 100 gallons
(1 cubic meter). While the control may operate with
these values, the following parameters must be
changed to meet the actual operating conditions:
Refill Controller Value, Brine Draw Rate, and Slow Rinse
Time parameters are not required for 960F operation,
but should be adjusted as instructed to achieve the
shortest possible backwash cycle time.
Note that some parameters have a single unit of
measure option. Other parameters have dual units
such as Capacity which can be entered in gallons or
cubic meters. To select which units are active, look for
a comment in the NOTES column of Tables 1 and 2. It
will reference another parameter that selects which
units are active. For example, parameter P12 (Table 2)
selects U.S. units if it is set to 0 and metric if it is set
to 1.
Backwash Dial
Indicator Knob
Time of Day
Time of Regen
Factor A
Factor B
Capacity
Regen TimeRemaining
REGENERATION COMPLETE
FASTRINSE
BACKW
ASH
PM
Performa Filter
TM
Cycle Indicator
-
8/7/2019 1227982- Manual- Performa Filter Series
7/247
Level I Parameters (Table 1)
Level I parameters are identified as those that have an
LED indicator on the front panel. The green indicator
illuminates next to the name of the active control
settings. The end user has access to all of these
parameters. In general, pressing the down arrow ()
button displays the Level I Parameters in the followingorder:
Time of Day
Time of Regen
Factor A
Factor B
Capacity
If you continue to press the down arrow () button, theparameters start over with Time of Day. Pressing the up
arrow () button displays the parameters in reverseorder. Refer to Table 1 for a description of these
parameters and the available ranges for eachparameter.
Press the SET button and the far right digit of the
display starts flashing. If you want to change this
number, press the up arrow () button to increase thenumber or the down arrow () button to decrease thenumber. To skip the number without changing, press
the left arrow () button. When you reach the far leftdigit, pressing the left arrow () button will return youto the far right digit.
Note: If you press and hold either the up arrow ()button or the down arrow () button for more than one
second, the flashing number will increment ordecrement at the rate of 10 counts per second.
When the number is correct, press the left arrow ()button. The far right digit stops flashing and the next
digit to the left starts flashing. You can only change
theflashing number. Continue changing numbers
until you reach the desired setting. Press the SET
button. The numbers stop flashing and the control
accepts the new setting. After approximately 30
seconds, the control starts alternating the display
between Time of Day and Capacity.
Note: If the new setting is not accepted because it was
outside the allowable range, the old value will bedisplayed.
Time of Day
Press the SET button. The display will show the Time
of Day with the minutes digit blinking. If you want to
change this number, press the up arrow () button toincrease the number or the down arrow () button todecrease the number. To skip the number without
changing, press the left arrow () button. The firstnumber stops flashing and the next number starts
flashing. Youcan only change the flashing number.
When you have reached the far left digit, pressing the
left arrow () button returns you to the far right digit.Continue changing numbers until you each the desired
setting. Press the SET button again to enter the value.
Time of Backwash
The next value displayed is the Time of Backwash. It is
similar to Time of Day programming. It has a default
value of 2:00 a.m. If 2:00 a.m. is acceptable, press the
down arrow () button. If this is not acceptable, pressthe SET button and change the numbers. Press the
SET button again to enter the value.
Factor A
Factor A is the next value displayed. The 960F control
uses this value to calculate the system capacity.Factor
A must be set to 10 (100 for metric units) for the
960F control to accurately calculate system
capacity. The default value is 10 (100 for metric units).
If the Factor A setting is not correct, press the SET
button and change the value. Press the SET button
again to enter the new value.
Factor B
Factor B is the next value displayed. This value is used
by the control to calculate the pause for the refill cycle.
Because the refill cycle is not required for 960F
operation, Factor B should be set to 0.2 (0.1 for metric
units). This is the minimum setting and will cause the
control to skip the refill cycle, thereby shortening the
backwash cycle time. The default value for Factor B is0.2 (0.1 for metric units). To change Factor B, press the
SET button and change to the correct value. Press the
SET button again to enter the new value.
Capacity
Capacity is the next value displayed and is used by the
960F control in combination with Factor A to determine
the capacity of the filter. The Capacity value should be
set to the actual capacity of the filter expressed as
gallons/100 (cubic meters/10 for metric units).
Example: If the actual filter capacity is 950 gallons,
enter 9.5 for the Capacity setting. The default value forCapacity is 1.0 (0.1 for metric units). To change the
Capacity setting, press the SET button and adjust the
correct value. Press the SET button again to enter the
new value.
At this time, all of the Level I parameters are
programed. The display will alternate between the Time
of Day and Capacity if no keys are pressed for 30
seconds. The Capacity value displayed is the volume
remaining in gallons (cubic meters for metric) before a
backwash is needed.
-
8/7/2019 1227982- Manual- Performa Filter Series
8/248
Note: The 960F control uses Factor A and Capacity
settings to calculate the actual system capacity. If the
actual system capacity is in excess of 9999 gallons
(99.99 cubic meters) the control will display 9999
(99.99) until the water usage has dropped the
remaining capacity below that number. When water is
flowing through the system, the colon in the Time of
Day display will blink.
To complete the initial programming of the 960F,
proceed to the Level II Parameters.
Table 1 - Level I Programming Parameters
Parameter Range of
Values
Minimum
IncrementsDefault
Units of
MeasureNotes
Name Description
P1Time of day
AM or PM
1:00 to 12:59
00:00 to 23:591 None Hour: minute
Range depends on value selected for
P13. Enter the current time.
P2Time of day of
backwash
1:00 to 12:59
AM or PM
00:00 to 23:59
1 2:00 AM Hour: minute
Range depends on value selected for
P13. Skip this parameter to accept the
default or enter a new time.
P3 Factor A3 to 250
30 to 2500
1
10
10
100
U.S.
Metric
Unit of measure depends on value
selected for P12. Set to 10 (100 for
metric units) for proper operation.
P4 Factor B0.2 to 51.0
0.1 to 25.5
0.2
0.1
0.2
0.1
U.S.
Metric
Unit of measure and default depends
on value selected for P12. Set to .5
(.1 for metric units) for proper 960i
operation.
P5Capacity of
unit
0.1 to 140.0
0.01 to 14.00
0.1
0.01
1.0
0.1
Gallons/100
Cubic Meters/
10
Unit of measure depends on value
selected for P12. Enter the unit
capacity in gallons/100 (cubic meters/
10 if metric units).
-
8/7/2019 1227982- Manual- Performa Filter Series
9/249
Level II ParametersThe Level II parameters are P6 through P19 in Table 2.
The Home Owners Manual for this product does not
mention these parameters, so the end user does not
normally have access to these values. To access Level
II Parameters, simultaneously press and hold the down
arrow () and up arrow () button for three seconds.
If the control was alternating between Time of Day and
Capacity when the above button sequence is entered,
the display shows P1. If a different Level I Parameter
was displayed, the display, shows the P number for
that parameter. Refer to Table 2 to find the P number
associated with each parameter.
Use the up arrow () button or the down arrow ()button to move from one parameter to the next. The
display cycles through the P numbers shown in
Tables 1 and 2. When you reach P19, the display will go
back to P1.
When the parameter number you want to change is
displayed, press the left arrow () button to display thedata assigned to that parameter. Press the SET button
Table 2 - Level II Programming Parameters
Parameter Range of
Values
Minimum
IncrementsDefault
Units of
MeasureNotes
Name Description
P6Refill Control
Value1 to 99 1 99
Set to 99 for 960F operation. Skip for
default.
P7 Brine drawvalue
1 to 99 1 99 Set to 99 for 960F operation.
P8 Not used NA NA NA NA NA
P9Backwash
time3 to 30 1 14 Minutes
Enter the desired backwash time in
minutes. Skip for default.
P10Slow Rinse
time8 to 125 1 8 Minutes Set to 8 minutes for 960F operation.
P11Fast Rinse
time2 to 19 1 9 Minutes
Enter the desired fast rinse time in
minutes. Skip for default.
P12Units of
measure0 to1 1 0
0=U.S., 1=Metric. Skip this parameter
to accept U.S. or enter 1 for Metric.
P13 Clock mode 0 to 1 1 0
0=12-hour clock, 1=24-hour clock. Skip
this parameter for a 12-hour clock orenter 1 for a 24-hour clock.
P14Calendar
override0 to 30 1 0 Days
0=no calendar override. Skip this
parameter for no calendar override or
enter a value.
P15 Reserve type 0 to 3 1 0
0=variable reserve, 1=fixed reserve,
2=variable reserve with immediate
backwash, 3=fixed reserve with
immediate backwash. Skip this
parameter to accept the default or enter
a different reserve type.
P16
Fixed reserve
capacity or
initial averagevalue
0 to 70 1 30Percent of
capacity
Description depends on the value
entered for P15. Skip this parameter to
accept the default or enter a differentvalue.
P17Operation
type0 to 1 1 4 Set to 4 for 960F operation.
P18Factor B/
Capacity
0 to 1 change
lock out1 0
0=none, 1=Factor B/Capacity change
locked out. Skip this parameter to
accept the default or enter 1 to lock out
Factor B/capacity change.
P19Factory
defaults0 to 3 1 99
Loads in factory default values.
Do not change this parameter.
-
8/7/2019 1227982- Manual- Performa Filter Series
10/2410
and the far right digit on the display starts flashing. If
you want to change this number, press the up arrow ()button or the down arrow () button. To skip thenumber without changing, press the left arrow ()button. When the number is correct, press the SET
button. The numbers stop flashing and the control
accepts the new setting. If the new setting was not
accepted, the display will show the previous setting.
Refer to Table 2 for allowable values for that parameter.
To change or view other parameters, press the left
arrow () button to have the display show Pnumbers. Now use the up arrow () button or the downarrow () button to move to the parameter number youwish to change.
To exit the Level II programming mode, simultaneously
press and hold the down arrow () and up arrow ()buttons for three seconds, or wait 30 seconds without
pressing a button. The control starts alternating the
display between Time of Day and Capacity.
Refill Control
The Performa Valve with the 960F control is designed
for use as a three cycle filter valve and does not include
a refill control. However, the software program used in
the 960F control is also used for the five cycle softener
control, and requires a refill controller value to calculate
how long to pause the cam shaft in the refill position. In
general, a small refill control value results in a long
pause, and a large refill control value results in a short
pause. For 960F operation, the refill Control Value
should be set to 99 to avoid delays during backwash.
The default value for Refill Control Value is 99.
Brine Draw Value
Brine Draw Value P7 is used to calculate the amount of
time required for the brine draw cycle. Because the
960F does not require a brine draw cycle, the Brine
Draw Value should be set to 99 to avoid delays during
backwash.
This control does not use parameter P8. No entry isneeded for this parameter.
Backwash Time
Parameter P9 is used to set the backwash time in
minutes. The default in P9 is 14 minutes. If a different
backwash time is desired, press the SET button and
enter a new value.
Slow Rinse Time
Parameter P10 Slow Rinse Time is used to calculate
how long to pause the cam shaft for the slow rinse
cycle. For 960F operation, the Slow Rinse time should
be set to 8 minutes to avoid delays during backwash.
The default value for Slow Rinse Time is 8 minutes.
Fast Rinse Time
Parameter P11 determines the fast rinse time. The
default value is 9 minutes. If a different fast rinse time is
desired, press the SET button and enter a new value.
Parameter P12 selects the units of measure. Besure that this is set to the correct value before
entering any data for parameters P3, P4, or P5.
Parameter P13 selects the clock display mode. Ifthe 12 hour mode is selected, a PM indicator is
used. If the 24 hour mode is selected, the indicator
is not used.
Parameter P14 is used to set the calendar overridefeature. The default value is zero. If set to zero, the
feature is disabled. Refer to Calendar Override for
more information on the calendar override feature.
Parameter P15 selects a variable reserve type, 0 to3. For more information on reserve options, refer to
Reserve Options.
Parameter P16 is used to calculate the initialaverage daily water usage values. The control
multiplies the total capacity by the percentage
entered for Parameter P16 and uses that value as
the initial average daily usage for each day of the
week until water usage establishes new averages.
The default is set for 30% of the capacity. In most
installations this is acceptable.
Parameter P17 has been preset to 4. Do notchange this setting. P17 must be set to 4 for
proper 960F operation. Improper backwashes will
occur if P17 is set to something other than 4.
Parameter P18 allows the installer to lock theFactor B and Capacity values so they cannot be
changed. When Parameter 18 is set to 1, those two
settings can only be viewed when the control is in
the Level II mode. The settings will be skipped
when the control is in the Level I mode. WhenParameter 18 is set to zero, the Factor B and
Capacity can be viewed and changed in either
Level I or Level II.
Parameter P19 is used at the factory to enterdefault values. This parameter does not need to
bechanged. Using this parameter will erase the
values for all other parameters and replace them
with default values. P19 should be set at 99 and
should not be changed.
-
8/7/2019 1227982- Manual- Performa Filter Series
11/2411
Regeneration
When the control begins a regeneration, the display will
alternate between Time of Day and Regen Time
Remaining. The Regen Time Remaining is shown in
minutes. The control will start and stop an internal
motor which drives the cam gear through the various
backwash positions. The control uses the informationentered in the parameters shown in Table 2 to
determine how long each part of the cycle should last.
If power fails during a regeneration cycle, the cycle
completes normally when the power is restored.
Note: The REGEN button is only active when the
display is alternating between Time of Day and
Capacity. When programming Level I or II parameters,
the REGEN button is not active.
The Regen Time Remaining will continue to count
down until the cam gear reaches the Service position.
Manual Regeneration
To initiate a manual regeneration, press the REGEN
button. This button is located on the front of the control.
When you press the REGEN button, the control
performs a full regeneration of the filter.
If you press this button again more than one minute
after regeneration begins, but before the
regeneration is complete, a second regeneration
will start when the first regeneration is finished. The
display will freeze and only show the Regen Time
Remaining as an indication that the second
regeneration will be performed. When the first
regeneration is complete, the second one will begin
and the display will alternate between Time of Day and
Regen Time Remaining.
Automatic Regeneration
There are two ways to have the control automatically
initiate a regeneration: calendar override or normal
metered water usage.
Calendar Override
This feature is set in parameter P14. It can be set for 1
to 30 days. If it is set to zero, this feature is disabled.
When this feature is active, the control keeps track ofthe number of days since the last backwash and when
that number equals the value set in P14, a backwash is
automatically started at the Time of Backwash set in
P2.
Normal Metered Water Usage
The control compares the water usage to the
calculated volume capacity of the system. The control
uses the Capacity parameter P5 and the Factor A
parameter P3 to calculate the volume capacity of the
system. It also uses a reserve value to determine if a
backwash is necessary. If the water usage since thelast backwash is greater than the system capacity
minus the reserve, a backwash is needed.
Note: If the water usage exceeds 150% of the system
capacity between backwashes, the control will
automatically call for a second backwash the next day
even if no water used.
Reserve Options
There are two types of reserve options for this control:
fixed reserve and historical water usage pattern. They
are selected with parameter P15.
Fixed Reserve
When the fixed reserve is selected, the control
multiplies the maximum system capacity by the
percent value set in parameter P16 and uses the result
as a reserve.
Water Usage Pattern
The other reserve option allows the control to adjust the
reserve based upon the historical water usage pattern
of the system. The control keeps track of the water
usage for each day of the week and uses that days
average usage multiplied by 1.2 as the reserve for that
day. Every day at the Time of Backwash, the controlrecalculates the days average water usage. If less than
10% of a days average water usage is used, the
control will not change the days average. If more than
twice the days average is used, the control uses the
actual usage in the reserve calculation.
Since a new installation has no history of water usage,
the control multiplies the percent of capacity value set
in parameter P16 by the total system capacity to
determine starting average for each day of the week.
The factory set default value for P16 is 30 which means
that 30% of the total system capacity is used for the
starting average for each day.
Program parameter P15 is also used to select whether
the control waits until the Time of Backwash set in
parameter P2 to start a backwash, or if the control
should begin a backwash immediately when the
capacity remaining is less than the reserve.
-
8/7/2019 1227982- Manual- Performa Filter Series
12/2412
Removing the Valve Assembly forServicing
1. Unplug the power cord.
2. Shut off water supply or put bypass valves into
bypass position.
3. Remove cover and with screwdriver, relieve tankpressure by pushing open valve No. 7 (rear flapper)
on control as shown (Figure 8).
Figure 8
4. When used with a globe valve bypass, loosen and
detach the inlet, outlet, brine and drain lines from
the valve. If using the 1265 bypass, loosen and
remove valve from bypass as well as loosening and
removing the brine and drain lines.
5. Unscrew (counterclockwise) and remove valve
from tank.
6. To replace the control valve, reverse the above
procedure.
Removing 440i Control For Servicing
1. Unplug the power cord.
2. Remove cover.
3. Align the indicator arrow on the rear of the
camshaft with the top of the rear hoop of the top
plate (Figure 9).
Figure 9
4. Remove the camshaft by carefully pushing the
securing tab, located at the rear of the camshaft,away from the camshaft until the tab disengages
from the camshaft. Push the back of the camshaft
down and out to the inlet side of the valve
(Figure 10).
Figure 10
5. Disengage the front of the camshaft from the
output gear of the control.
6. Remove the timer locking pin and lift the control
straight up and off of the valve.
7. To reinstall the camshaft and control, reverse theabove procedures.
Indicator Arrow
-
8/7/2019 1227982- Manual- Performa Filter Series
13/2413
Removing the 940F and 960F Controls ForServicing
Complete the following steps to remove the 940F and
960F control for servicing:
1. Unplug the wall-mount transformer.
2. Shut off the water supply or put the bypass valve(s)into bypass position.
3. Remove the rear cover by depressing the two tabs
provided on the cover, (Figure 11). Lift the front of
the cover and remove to expose the valve body.
Figure 11
4. Relieve system pressure by opening the Backwash
Drain Valve (the seventh valve back from the
control) with a screwdriver, (Figure 12).
Figure 12
5. To remove the camshaft or to reinstall it, the arrow
on the shaft must be pointing at the line on the rear
hoop of the top plate. This occurs when the
indicator knob is rotated to the refill position. Press
down on the back of the camshaft to disengage it
from the rear hoop of the top plate, (Figure 13).
Slide the camshaft back to disengage it from the
timer, (Figure 14).
Figure 13
Figure 14
6. Disconnect the turbine probe from the turbine
assembly.
7. Lift the control off the valves, Figure 15. To replacethe control, reverse the above procedure. Note that
the camshaft needs to be positioned correctly
before it can be inserted into the back of the
control. There is a locating rib on the camshaft.
Position the rib on the top of the shaft and slide the
camshaft into the control. Push up on the end of
the camshaft, furthest from the timer, snapping it
into place.
Figure 15
Tab
-
8/7/2019 1227982- Manual- Performa Filter Series
14/2414
Preventive Maintenance
Figure 16
Water Meter Maintenance
Note: A water meter is used only with the 960F control.
If you are using the 440i or 940F control, this section
does not pertain to your conditioner.
The metering device used with the 960 demand
controls may require simple maintenance. In rare
instances, the turbine wheel of the water meter can
collect small particles of oxidized iron, eventually
preventing the wheel from turning.
1. Shut off the water supply or put the bypass valve(s)
into the bypass position.
2. Relieve pressure by opening the Backwash Drain
Valve (the seventh back from the control) with ascrewdriver (Figure 12).
3. Loosen and remove the pipe/tube adapters or
1265 bypass from the inlet and outlet of the valve
body.
4. Using a needle-nose pliers, remove the turbine
from the outlet housing. Grasp one of the four
vanes of the outer gland and pull straight out to
remove turbine assembly from the outlet of thevalve (Figure 16).
5. Carefully remove the turbine wheel from the
housing. Use a toothbrush to lightly scrub the iron
off the magnet. Iron buildup on the surfaces can be
removed by soaking the wheel in a mild sodium
hydrosulfite (such as RoVer*) solution for a few
minutes. Flush thoroughly with water.
6. Carefully reinstall the turbine wheel into the turbine
cage housing. Make sure that the shaft of the wheel
seats into the bearing of the cage. Reassemble the
turbine cage and check that the wheel rotates
freely.
7. Reinstall the turbine cage into the outlet of the
valve.
8. Reinstall the pipe/tube adapters or 1265 bypass to
the inlet and outlet of the valve.
9. Turn on the water supply or put the bypass valve(s)
into the service position and purge the air out of the
system.
To check for proper meter operation, open a
downstream faucet and observe the water flow
indication on the control display.
Injector
Injector Screen
Cap
Turbine
-
8/7/2019 1227982- Manual- Performa Filter Series
15/2415
Specifications
263/440i Drawings
Hydrostatic Test Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 psi (20.69 bar)
Working Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-125 psi (1.38 - 8.62 bar)
Standard Electrical Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115V 60 Hz
Optional Electrical Rating . . . . . . . . . . . . . . . . . . . . . . 115V 50 Hz, 230V 50 Hz, 200V 60 Hz, 24V 60 Hz, 24V 50 Hz,
100V 60 Hz, 100V 50 Hz, 12V 50 Hz/transformer, 12V 60 Hz/transformer
Electrical Cord (standard rating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 inch (1.5 m) 3-wire with plug
Pressure Tank Thread . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1/2 inch-8 male
Riser Pipe Diameter Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.050 inch OD (26.7 mm)
Riser Pipe Length . . . . . . . . . . . . . . . . . . . . . . . . . .1-1/8 1/8 inches (31.8 mm) higher than the top of mineral tankStandard Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-inch (25.4-mm) copper tube adapters
Optional Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3/4-inch, 22-mm, and 28-mm copper tube adapters
3/4-inch BSPT, 1-inch BSPT, 1-inch NPT brass pipe adapters
3/4-inch, 1-inch, 25-mm CPVC tube adapters
Drain Line Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4-inch NPT male
Optional Bypass Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Rotating handles, full 1-inch porting, reinforced Noryl
Control Module, Tank Adapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reinforced Noryl
Rubber Goods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Compounded for cold water service
Program Clock (Timer). . . . . . . . 440i: Available in 6 - or 7-day English, German, French, Italian, Spanish, Japanese
940F: Available in 7 - or 12-day English, German, French, Italian, Spanish, Japanese
960F: Available in English, German, French, Italian, Spanish, Japanese
Internal Backwash Controllers. . . . . . . . . . . . . . . . 7- through 14-inch (17.8- though 35.6-cm) diameter media tanks
All sizes to flow 4.5 gpm/sq ft (183 L/m/m2) of bed area. For tank sizes above 14 inches in diameter,use an external flow control.
3.37-inch (86 mm) 3.66-inch (93 mm)5.76 inch (146 mm) 5.82 inch (148 mm)
2.88 inch (73 mm)
2.5 inch (63 mm)
2.5 inch (63 mm)
11.59 inch (294 mm)
1.356 inch (34 mm)
8.74inch(222mm)
Inlet
Outlet
Drain
1
2
3
4
5
6
-
8/7/2019 1227982- Manual- Performa Filter Series
16/2416
263/900 Series Drawings
-
8/7/2019 1227982- Manual- Performa Filter Series
17/2417
Control Valving Identifications
2 Bypass Valve
3 Inlet Valve
4 Outlet Valve
7 Backwash Drain Valves
6 Rinse DrainValve
Brine TankMineral Tank
Drain
Inlet
Outlet
Hard Water
Soft Water
5
4
1
32
6 7
Plug
Plug1
Flow Diagrams
Brine TankMineral Tank
Drain
Inlet
Outlet
Hard Water
Soft Water
5
4
1
32
6 7 BackwashFlow
Control
Plug
Plug
Valve
No.
1 - Closed
2 - Closed
3 - Open
4 - Open
5 - Closed
6 - Closed
7 - Closed
1 Service Position 2 Backwash Position
Valve
No.
1 - Open
2 - Open
3 - Closed
4 - Open
5 - Open
6 - Closed
7 - Open
Valve Disc Operation
-
8/7/2019 1227982- Manual- Performa Filter Series
18/2418
3 Purge Position
Brine TankMineral Tank
Drain
Inlet
Outlet
Hard Water
Soft Water
5
4
32
6 7
Plug
Plug1
Valve
No.
1 - Open
2 - Open
3 - Open
4 - Closed
5 - Closed
6 - Open
7 - Closed
-
8/7/2019 1227982- Manual- Performa Filter Series
19/2419
Performa Valve Replacement Parts
Performa Valve
5
16
11
1
7
8
12
13
9
10
14
15
17
15
2
4
3
18
6
-
8/7/2019 1227982- Manual- Performa Filter Series
20/2420
Parts List
Code
Part
No. Description Qty. Code
Part
No. Description Qty.10 1030334 Plugged Brine Refill Control 1
1 1035807 Valve Assy, w/o Flow Controls (940F, 960F) 1 11 1002449 Drain Fitting Elbow (3/4 hose barbed) 12 1035606 Valve Assembly, w/o Flow Controls (440i) 1 12 1000226 Cap Assembly 1
3 1031391 Timer Locking Pin 1 13 1010429 O-Ring 1
4 1035624 440i Filter Camshaft (Grey) 1 14 1035622 Tank Ring 1
5 1030380 940F, 960F Filter Camshaft 15 Plumbing Adapter Kits: 1
6 Drain Control Assembly: 1 1001606 3/4-inch Copper Tube Adapter Kit
1000209 No. 7 (1.2 gpm; 4.5 Lpm) 1001670 1-inch Copper Tube Adapter Kit
1000210 No. 8 (1.6 gpm; 6.1 Lpm) 1041210 1-1/4-inch copper Tube Adapter Kit
1000211 No. 9 (2.0 gpm; 7.6 Lpm) 1001608 22-mm Copper Tube Adapter Kit
1000212 No. 10 (2.5 gpm; 9.5 Lpm) 1001609 28-mm copper Tube Adapter Kit
1000213 No. 12 (3.5 gpm; 13.2 Lpm) 1001613 3/4-inch CPVC Tube Adapter Kit
1000214 No. 13 (4.1 gpm; 15.5 Lpm) 1001614 1-inch CPVC Tube Adapter Kit
1000215 No. 14 (4.8 gpm; 18.2 Lpm) 1001769 3/4-inch NPT Plastic Pipe Adapter Kit
7 1030502 Ball, Flow Control 2 1001603 1-inch NPT Plastic Pipe Adapter Kit
8 1032978 Plugged Injector Assembly 1 1001604 3/4-inch BSPT Plastic Pipe Adapter Kit
9 1000218 Injector Cap Assembly 1 1001605 1-inch BSPT Plastic Pipe Adapter Kit
1001611 3/4-inch BSPT Brass Pipe Adapter Kit
1001610 1-inch NPT Brass Pipe Adapter Kit
1001612 1-inch BSPT Brass Pipe Adapter Kit
16 1033444 Turbine Assembly (960F only) 1
17 1001580 Spring, Flapper Valve
* Valve Disc Kit:
1041174 Standard
1041175 Severe Service
* 1000062 I-Lid Cover 1
-
8/7/2019 1227982- Manual- Performa Filter Series
21/2421
FASTRINSE
BACKWASH
SERVICE
FOR MANUAL
BACKWASH
ROTATE POINTER
COUNTER
CLOCKWISE TO
START POSITION
TO ADJUST BACKWASH
MINUTES, ROTATE
SMALL DIAL COUNTER
CLOCKWISE.
DO NOT ADJUST
DURING BACKWASH
TO SET
REGENERATION
DAYS PRESS PINS IN
Performa FilterTM
BACKWASH COMPLETE
Time of Day
Time of Regen
Factor A
Factor B
Capacity
Regen TimeRemaining
REGENERATION COMPLETE
FASTRINSE
BACKW
ASH
PM
Performa FilterTM
440i Control 940F Control
960F Control 1265 Bypass
BYPASS
BYPASS
Code
Part
No. Description Qty.
1 440i Control (6 day or 7 day) 1
2 940F Control (7 day or 12 day) 1
3 960F Control 1
4 1040930 1265 Bypass 1
* 1000811 Transformer (440i, 460i, 960): 1
*1000907
Transformer Extension Cord
15 feet (4.6 m) 1
*1034264
Y-Splitter (run 2 units from 1 trans-
former) 1
*Not Shown
1 2
3 4
-
8/7/2019 1227982- Manual- Performa Filter Series
22/2422
Troubleshooting
The technology upon which the Autotrol Performa
control valve is based is well established and proven in
service over many years. However, should a problem or
question arise regarding the operation of the system,
the control can very easily be serviced. For parts
mentioned, refer to exploded views in theReplacementParts section of this manual.
IMPORTANT: Service procedures that require the
water pressure to be removed from the system are
marked with a ! after the possible cause. To remove
water pressure from the system, put the bypass valve
or three-valve bypass into the bypass position and
open the backwash drain valve (the seventh valve back
from the control) with a screwdriver. Restore system
water pressure when the service work is completed.
Valve Troubleshooting
Problem Possible Cause Solution
1. Control backwashes at
excessively low or high rate.
a. Incorrect backwash controller used.
b. Foreign matter affecting controlleroperation !
a. Replace with correct size controller.
b. Remove controller and ball. Flush with water.
2. Untreated water leakageduring service.
a. Improper regeneration.
b. Leaking of bypass valve !
c. O-ring around riser tube damaged !
a. Repeat regeneration making certain that the
correct salt dosage is set.
b. Replace O-ring.c. Replace O-ring.
440i and 940F Control Troubleshooting
Problem Possible Cause Solution
1. Control will not regenerate
automatically.
a. Transformer or motor not connected.
b. Defective timer motor.
c. Skipper pins not down on timer skipper
wheel.
d. Binding in gear train of timer.
a. Connect power.
b. Replace motor.
c. Depress pins for days regeneration required.
d. Replace timer.
2. Control regenerates at wrong
time of day.
a. Time set incorrectly. a. Correct t ime setting according to instructions.
-
8/7/2019 1227982- Manual- Performa Filter Series
23/2423
960F Control Troubleshooting
Alarms
The Model 960 continuously monitors itself and sounds
an alarm if it detects something wrong. The alarm is a
beep that is on for one second and then off for nine
seconds. When the alarm sounds, the display showsthe letters Err with a number from 1 to 4. The table
below lists the Err numbers, a description of each error,
the cause of the error, and the solutions. To silence the
alarm, press any button on the control. If the error still
exists, the control will go back to the alarm condition
after 30 seconds.
Model 960 Alarms
Indication Description Cause Solution
Err 1 Electronics FailureControl settings need
reprogramming.
Press any key to load default values. Refer
to Programming the Model 960 Control.
Err 2
Improper start of
regeneration (limit switchclosed when it should be
open).
Valve camshaft has been
manually rotated during a
regeneration.
Valve camshaft has been
manually rotated out ofregeneration complete
position.
Faulty motor.
Faulty motor drive.
Faulty switch.
Press any key to silence the alarm. (Note:
Alarm automatically clears at TIME OF
REGEN.)
The control will turn the motor on and drive
the camshaft to the proper location.
Replace the control.
Replace the control.
Replace the control.
Err 3
Improper finish of
regeneration (limit switch
open when it should be
closed).
Valve camshaft has been
manually rotated out of
regeneration complete
position.
Faulty motor.
Faulty motor drive.
faulty switch.
The control will turn the motor on and drive
the camshaft to the proper location.
Replace the control.
Replace the control.
Replace the control.
Err 4
Improper control settings
(one or more settings out of
the allowable range).
One or more settings out of
the allowable range.
Hardness: Adjust range: 3 to 250.
Capacity: Adjust range: 0.1 to 140.0.
Refill control: Adjust range: 1 to 99.
Brine draw value: Adjust range per Table 2.
Problem Possible Cause Solution
1. Capacity Display stays at 9999
even though there is water
usage.
a. Total system capacity was calculated to
be a value greater than 9999.
a. As the water usage continues, the remaining
capacity will drop below 9999 and then other
values will be shown.
2. Timer beeps when left arrow
button is pressed.
a. Button is only active in the programming
mode.
a. Refer to the Programming section.
3. Timer does not respond to
REGEN button.
a. Button is not active in the programming
mode.
a. Refer to the Regeneration section.
4. Timer does not display time of
day.
a. Transformer is unplugged.
b. No electric power at outlet.
c. Defective transformer.
d. Defective circuit board.
a. Connect power.
b. Repair outlet or use working outlet.
c. Replace transformer.
d. Replace control.
5. Timer does not display correct
time of day.
a. Outlet operated by a switch.
b. Power outages.
a. Use outlet not controlled by switch.
b. Reset Time of Day.
-
8/7/2019 1227982- Manual- Performa Filter Series
24/24
6. No water flow display when
water is flowing (colon does
not blink).
a. Bypass valve in bypass position.
b. Meter probe disconnected or not fully
connected to meter housing.
c. Restricted meter turbine rotation due to
foreign material in meter !
d. Defective meter probe.e. Defective circuit board.
a. Shift bypass valve into service position.
b. Fully insert probe into meter housing.
c. Remove meter housing, free up turbine and
flush with clean water. Turbine should spin
freely, if not, refer to the Water Meter
Maintenance section.d. Replace control.
e. Replace control.
7. Control display is frozen at
Regen Time Remaining.
a. Back to back regenerations were
requested.
a. Refer to the Manual Regeneration section.
8. Control regenerates at wrong
time of day.
a. Power outages.
b. Time of day set incorrectly.
c. Time of regeneration set incorrectly.
a. Reset time of day to correct time of day.
b. Reset time of day to correct time of day.
c. Reset time of regeneration.
9. Timer stalled in regeneration
cycle.
a. Motor not operating.
b. Motor runs backwards.
c. No electric power at outlet.
d. Incorrect voltage or frequency (Hz).
e. Broken gear.
f. Defective switch.g. Air leak in brine connections (pressure
locked flapper).
h. Binding of camshaft.
i. Water pressure greater than 125 psi
during regeneration.
j. Defective circuit board.
a. Replace control.
b. Replace control.
c. Repair outlet or use working outlet.
d. Replace timer and/or transformer with one of
correct voltage and frequency (Hz).
e. Replace control.
f. Replace control.
g. Check all junction points and make
appropriate corrections.
h. Remove foreign object obstruction from valve
discs or camshaft.
i. Install pressure regulator to reduce pressure.
j. Replace control.
10. Continuous regeneration.
Camshaft does not stop at the
end of regeneration.
a. Broken projection on drive gear.
b. Defective switch.
a. Replace control.
b. Replace control.
11. Control does not regenerate
automatically or when REGEN
button is depressed.
a. Transformer unplugged.
b. No electric power at outlet.
c. Defective motor.
d. Broken gear.
e. Binding in gear train.
f. Defective switch.
a. Connect power.
b. Repair outlet or use working outlet.
c. Replace control.
d. Replace control.
e. Replace control.
f. Replace control.
12. Control does not regenerate
automatically but does
regenerate when REGEN
button is depressed.
a. If water flow display is not operative, refer
to item 5 in this table.
b. Incorrect program settings.
c. Defective circuit board.
a. Refer to item 5 in this table.
b. Set new control values. Refer to the
Programming section.
c. Replace control.
13. Run out of treated water
between regenerations
a. Improper regeneration.
b. Fouled resin bed.
c. Incorrect factor 1 or capacity settings.
d. Restricted meter turbine rotation due to
foreign material in meter housing !
e. Excessive water usage below 1/5 gallon
per minute.
a. Repeat regeneration making certain that
correct salt dosage is used.
b. Use resin cleaner.
c. Set to correct values. Refer to the
Programming section in this manual.
d. Remove meter housing, free up turbine, andflush with clean water. Turbine should spin
freely, if not, replace meter.
e. Repair leaky plumbing and/or fixtures.