130531 what's watt
DESCRIPTION
TRANSCRIPT
Sharing our Guidance
What’s Watt?
X
What’s Watt
Wye Line-to-Neutral Voltage 120 120 277 374
Wye or Delta Line-to-Line Voltage 208 240 480 600
Electrical Service Voltages
04/10/23 2
What’s Watt
Single Phase
Single-Phase electrical service wires usually have a three wire configuration. This type of single phase wiring is most commonly found in the United States. It provides 120 Volts for lighting and conventional plug loads and 240 volts for single phase appliances.
04/10/23 3
What’s Watt
Common Electrical Services
04/10/23 4
Single Phase Three Wire
What’s Watt
Three-Phase
Three-phase electric power is the most common method of alternating-current electric power generation, transmission, and distribution. It is also used to power large motors and other heavy loads. A three-phase system is generally more economical than others because it uses less conductor material to transmit electric power than equivalent single-phase systems at the same voltage. There are two types: three phase, four-wire wye and three phase three-wire delta.
04/10/23 5
What’s Watt
Common Electrical Services
04/10/23 6
Three Phase, Four Wire Wye
What’s Watt
Common Electrical Services
04/10/23 7
Three Phase, Three Wire Delta
What’s Watt
So, What’s a Watt?
A Watt is a unit of power, named after Scottish Engineer James Watt, defined as one joule per second What’s a Watt mean to us? As a unit of power it remains constant as other variables change. Therefore, a watt is a watt is a watt.
Example- A 10kw electric heater is an electric heater rated 10kw whether the voltage available to is 120V, 208V, or 480V, and regardless of whether single or three phase are available.
04/10/23 8
What’s Watt
Basic Formulas
• Single PhaseWatts=Volts x Amps, KW=Volts x Amps /1000
• Three PhaseWatts=Volts x Amps x 1.73KW=Volts x Amps x 1.73/1000
04/10/23 9
What’s Watt
Determining Amperage
• Amperage is the amount of electricity flowing • Example: What is the amperage of a 12kw unit electric unit
heater @ 120v, single phase?• 12kw=12,000w = volts x amps• 12,000w = 120 x amps • amps = 100a• Using NEC, this heater would require a 125a/1p breaker &
#1 AWG wire• Huge wire and breaker for a relatively small piece of
equipment• What can we do? Raise the voltage! Make it 3 phase!
04/10/23 10
What’s Watt
Determining Amperage – 3 phase
04/10/23 11
Example: What is the amperage of a 12kw unit electric unit heater @ 208v, three phase?12kw=12,000w = volts x amps x 1.7312,000w = 208 x amps x 1.73 amps = 33aUsing NEC, this heater would require a 40a/3p breaker & #8 AWG wireMuch smaller wire and breaker for a relatively small piece of equipmentAlways spec higher voltages and three phase on large pieces of equipment
What’s Watt
04/10/23 12
X
What’s Watt
04/10/23 13