8/13/2019 14 Section-D-A1 Data Sheets
1/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
I SOLAR ARRAYS
1 Installed Capacity 5 MWp - Grid interactive
2 Type of SPV module Mono/ Multicrystalline
3 Rating of SPV module Minimum 200 wp
4 PCU(Inverters) Highly efficient as specified
(Section- D)5 SCADA for diagnosing & monitoring As per latest technology
6 Schematics and layout drawings As specified(As per drawing)
7 Total capacity of modules to be installed 5.25MW (50KW extra for each MW)
8 Array rating 250 kw
9 HT Transformers 1.25 MVA and 6.3 MVA
10 Area required 25 acres
11 Minimum Annual energy generation 8.322 mu(19% CUF)
II MOUNTING STRUCTURE
1, Type Ground Mounting-Fixed Type
2 Material Mild Steel
3 Overall dimensions Design As suitable
4 Coating Dip (galvanized)/Anodized Hot
5 Wind speed rating 150 Km/hr.
6 Tilt angle 15 degree (as required)
7 Foundation PCC (1:2:4)
8 Number of Module structure Adequate
9 Fixing type SS 304 fasteners
III POWER CONDITIONING UNIT
I Input Data
1 Max PV power (recommended) 250 kWp
2 DC voltage range 450 820 V3 Max permissible DC voltage 900 V
4 Max permissible DC current 591 A
II Output Data
1, Nominal Ac power 250 kW
2 Operating grid voltage -20% TO 15%
3 Utility type 4 wire
4 Operating frequency grid 50 Hz +OR 3%5 Voltage ripple PV voltage < 3%
6 Efficiency 95 % AND ABOVE
IV LT INTERFACING PANEL As per the Specifications in section D
V
a) Normal system voltage 11kV
b) Corresponding highest system voltage 12 kV
c) Frequency 50 Hz ( + 3%, - 5%)
d) N umber of phases 3
e) Neutral earthing As per requirements
f) Class indoor/outdoor outdoor
11KV SWITCHGEAR CUBICLE
Page 1 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
2/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
g) Rated short circuit withstand of the panels As per requirements
Free standing, Floor mounted,
metal clad, fully compartmenta-
lized draw-out type
h) Switchgear
Page 2 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
3/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
VI 11 KV CIRCUIT BREAKER DETAILS
a) SF6 / Vacuum circuit Breaker re-strike
free, trip free, stored energy operated
and with electrical anti-pumping features
Draw out type
b) Number of poles 3
c) Rated voltage 12 kVd) Rated normal current As per system requirements
e) Rated frequency 50 Hz + 3%/-5%
f) Rated short circuit breaking current As per requirements
g) Rated short time As per requirement
h) Rated Operating Duty 0-3 min co 3 min - coi) Rated insulation level rated/min. power
frequency withstand voltage (Rms value)
28 kV
j) Rated lightning impulse withstand voltage
(peak value)
75 kV
k) Rated duration 1 second short circuit
110 V DC Control supply closing
and opening 230 V AC Aux
m) Supply devices & auxiliary circuits out
door type
Class indoor/outdoor
n) No. of Auxiliary contacts 4No+4NC Contacts
o) Current transformers rated Insulation
level28 kV frequency withstand
voltage (rms value)
75 kV impulse withstand
voltage (peak value)
p) Class of insulation Class E
q) Instrument Safety Factor(ISF) less than 3
r) Minimum creepage 25 mm/kV of highest system voltage
distanceC.T. details
i) Ratio- Primary : As per requirement (Refer Section-D)
-Secondary
t) Class of Accuracy
i) Core I 1.0
ii) Core II 5P20
u) Purpose of each corei) Core I Metering
ii) Core II Protection
v) Burden
i) Core I 30 VA
ii) Core II 30 VA
VII 11 kv ISOLATORS REFER SECTION D
ii) Rated lightning
l) Rated supply voltage
i) Rated/min power
s)
Note: CTs shall be of reputed make with proven experience.
Page 3 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
4/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
Page 4 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
5/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
VIII 11 KV POTENTIAL TRANSFORMERS
1
a, Rated/min power 28 kV frequency withstand
voltage(rms value)b. Rated lightning 75 kV impulse withstand voltage (peak
value)2 Class of insulation Class E
3 Rated voltage factor 1.2 continuous & 1.9 for 30 seconds
4 Clear height of bushing 370 mm
5 Minimum creepage 25 mm/kV of highest system voltage
distance6 Applicable standard IS: 3156
7 PT details
8 Rating 11KV/ 3 / 110V/ 39 Burden 100 VA
10 Class of Accuracy 1.0/3P
11 Purpose Metering & protection
12 Connection Star/Star
Note :
IX
X 1250 KVA TRANSFORMER
Designation step up transformer
1, Installation outdoor Out door
2 Degree of protection as per IP 55 IS:2147
3 Rating in KVA 1250KVA
4 Number of Phases 3 Phase
5 Frequency 50 Hz
6 Type of cooling ONAN
7 No-load voltage
8 a) HV 11000V
9 b) LV 415V
10 Vector group Dyn1111 % impedance 5
12 System voltage
Nominal system voltage
a) HV 11000 V
b) LV 415V
TEMPERATUE RISE
1, Reference ambient 40oc
2 Oil by thermometer 35oc
Rated Insulation level.
i) Potential transformers shall be single phase units. PTs shall be of reputedmake with proven experience.
ii) Each secondary shall be protected by 3 Amps. HRC fuse.
Details of auxiliary supply for operation/control, protection, alarm,
indication etc.DC supply - 110Volts +10% / - 15%
AC supply 415 Volts + or-10% Three phase 4 wire system
Page 5 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
6/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
3 Winding by resistance method 40oc
Page 6 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
7/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
TAP CHANGING GEAR
1, Taps ( Off load) : Required
2 Tappings on windings: HV
3 Total tappings range: 5%
4 Steps 2.50%
1, Dial type thermometer with two contacts
for oil tempr.
Required
2 Magnetic oil level gauge with low oil level
alarm contacts
Required
3 Gas and oil actuated ( i.e. Bucholz ) relay Required
4 Gas sampling device Required
5 Winding temperature indicator Required
6 Off circuit tap changing mechanism
valves
Required
7 Four plain rollers in place of fixing
channels
Required
XI
1
1.1 Application / Designation Neutral Grounding Resistors
1.2 Type & Quantity a. Cast Grid
b Wire wound
1.3 . Installation Outdoor/Indoor OUTDOOR
1.4 Enclosure Tank Type, Weather proof with
Aluminium covers2 RATING
2.1 Rating KW: As suitable2.2 Ohmic Value As suitable
2.3 Taps % 50,25
2.4 Rated Current in Amps As suitable
2.5 Duration of rating CONTINUOUS
2.6 Voltage Class V Bidders to specify
3
suitable for conductor of
3.1 Material GS
3.2 Size As suitable
XII DC BATTERIES
XIII
1 Co2 cylinder(Big size) 25 Nos.
3 sets of 110 VOLTS Batteries each 100 AH capacity of Plante make.
Each set conisting of One main and one Stand by Battery bank with 1 nos each
of float and boost chargers confirming to standards as detailed in section
D.One set to be installed for each inverter room.
GENERAL
Resistor earth, bushing terminal
OTHER FITTINGS REQUIRED FOR 1250 KVA TRANSFORMER
NEUTRAL GROUNDING RESISTOR FOR TRANSFORMERS
FIRE FIGHTING EQUIPMENTS: 1 set consisting of following:
Page 7 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
8/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
2 Sand buckets 30 Nos.
3 Foam type fire extinguishers 20 Nos.
4 Dry chemecal powder type extinguishers 20 Nos.
5 Smoke sensors 20 Nos.(for control rooms)
Page 8 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
9/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
XIV
1Solar yard lights along pepiphery on poles
sodium vapour lamps70 Nos.
2
Control room, office, Amphitheater, Toilet,
Building illumination(24Watts CFL) Quantity as per building design
3
Yard Flood lights
3 nos
4ODY illumination - Sodium Vapour lamps
20 Nos.
XV
1
Suitable software and adequate database
with suitable memory for all parameters
of the plant
1 set
2Computers/ servers of latest version
(Branded make ) with accessories 3 Nos.
3 Laser Jet colour Printer-A3 2 Nos
4Devices for web based communication
system As required
5 LAN networking As required
6 UPS As required
XVI 6300 KVA, 11/66 KV TRANSFORMER
Sl.No. Technical Particulars
1 Type Out door/Step Up2 No. of windings Two
3 No. of Phases Three
4 System frequency 50 Hz+3%& - 5%
5 a) Rating of HV winding 6.3 MVA
b) Rating of LV winding 6.3 MVA
6 a)Low Voltage Winding 11 kV
b)High Voltage Winding 66 kV
7 a) H.V. Winding Star
b) L.V. Winding Delta
c) Neutral Effectively earthed.
8 Vector Group YNd11
b)H.V. Terminals : 72.5 kV OIP condenser type bushing
suitable for Lynx ACSR conductor
c) H.V.Neutral Bushing of suitable rating, solid
porcelain type
10 a) High Voltage Winding Graded insulation
b) Low Voltage Winding Uniform insulation
12 KV Solid Porcelain bushings.
Bushings shall be suitable for
connecting 11 KV XLPE cables.
ILLUMINATION SYSTEM: 1 set consisting of following:
9 a) L.V. Terminals :
SCADA SYSTEM: 1 set consisting of following:
Page 9 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
10/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
11 Type of cooling ONAN
12 Impedance Voltage at normal tap 8.35%
13 Insulating Medium Mineral Oil (as per IEC:60296 and bid
specification)
Page 10 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
11/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
14 Tap changing gear Details
A Type OCTC on HV side
B Tapping range as % of off load Rated
KVA
+/- 5 % (5 Steps of 2.5% each tap)
C No. of tapping 5 Steps of 2.5% (including normal)
XVII 200 KVA, 11/0.440 KV AUXILIARY TRANSFORMER
Sl. No. Technical Particulars
1 Type Indoor/ Outdoor/Step-down
2 No. of windings Two
3 No. of Phases Three
4 System frequency 50 Hz+3%& - 5%
5 Rating 200KVA
6 a) HV Voltage 11kV
b) LV Voltage 0.440kV
7 a) HV Winding Delta
b) LV Winding Star c) Neutral Effectively earthed
8 Vector Group Dyn11
9 Type of cooling AN
10 Impedance Voltage at normal tap 4.50%
11 Tap changing gear
a) Type Off circuit
b) Tapping range as % of off load Rated
KVA
-5% to +5% in steps of 2.5%
12 Power frequency withstand voltage for 1
minute
For HV winding 28kV rmsFor LV winding 3kV rms
For HV winding 75kV peak
For LV winding NA
14 Insulation Class F
15 The maximum permissible temperature
rise over maximum ambient temperature
of 40oC
a) Winding (measured by resistance
method)
90C
b) Core, metallic parts and adjacent
materials
The temperature shall in no case reach
a value that will damage the core itself,
other parts or adjacent materials
16 Terminal connections
HV terminals HV terminals shall be suitable for 11 kV
bus
13 Rated lightning impulse withstand voltage
for 1.2/50 microsecond
Page 11 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
12/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
LV terminals The LV terminals shall be suitable for
PVC / XLPE cables
17 Insulation grading HV & LV winding shall be uniformly
insulated18 Ability to withstand short circuit & duration
of short circuit
According to IS 2026/ IS:11171
19 Overloads According to IEC:60905
Page 12 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
13/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
XVIII 66 KV POTENTIAL TRANSFORMER
Sl. No. Technical Particulars
1 Rated voltage 72.5 kV
2 Rated frequency 50 c/s
3 Accuracy class of Winding as required
4 Voltage ratio 66 kV/3/110V/35 Grade of oil As per IS: 335
6 Maximum phase angle error with 25%
and 110% of rated burden at 0.8 p.f.
lagging at any voltage between 80% and
120%
40 min.
7 Temperature rise at 1-1 times rated
voltage with rated burden (OC)
As per IS: 3156
8 Rated voltage factor & time (based on
system studies)
Continuous 1.2 ; 30 seconds-1.5
i) 1 minute power frequency (wet/dry) :
140 kV r.m.s. withstand test voltage (Asper IS: 3156)ii) 1.2/50 micro seconds impulse wave :
325 kV (Peak) withstand test voltage
11 Minimum creepage distance of bushings 1815 mm
XIX 66 kV CIRCUIT BREAKER
1 Number of poles 3
2 Class Out Door Type
3 Nominal System Voltage 66 kV
4 Rated Voltage 72.5 kV
5 Rated Insulation Level 350 kV(peak)
6 Rated Frequency 50 Hz
7 Rated normal current 1600 Amps.
9 Rated Cable Charging breaking current 140 Amps
10 Rated S.C. breaking current 31.5 kA11 First pole to clear factor 1.5
12 S.C. making current 79 kAP
13 Rated Operating Sequence O-0.3sec-CO-3min.-CO
14 Duration of short circuit 3 sec.
15 Rated out of phase breaking current 7.9 kAmps
16 Automatic rapid re closing 3 Ph.
9 Insulation Level (based on system
insulation coordination)
2 kV10 One minute power frequency withstand
test voltage on secondaries
Page 13 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
14/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
17 Total break time for any current up to the
rated breaking current with limiting
conditions of operating coil voltage,
operating &quenching media pressures.
< 60 ms
18 No. of auxiliary contacts for purchasers
use
10 NO & 10 NC on each pole
19 System neutral earthing Effectively earthed
Page 14 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
15/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
Closing time(max.)
-
8/13/2019 14 Section-D-A1 Data Sheets
16/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
3 Rated frequency 50 Hz
4 System neutral earthing Effectively earthed
5 Installation Out door
6 Type of disconnect Horizontal double break
7 Number of poles 3
Page 16 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
17/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
8 Rated normal current 1600 Amps
9 Rated short time with-stand current (KA
rms)a) For 1 sec 31.5
b) For 3 sec 31.5
10 Rated peak withstand current for both
main and earth switch (KA) peak
78.75
11 Rated insulation level 1.2/50 micro
second lightning impulse withstand
voltage (kV) peaka)between live parts and ground 325 (kV)peak
b)across the open terminal of the same
phase
375 (kV) peak
One minute dry/wet power frequency
withstand voltage for complete
assembled isolator /isolator cum earthing
switch.a) against ground (kV) rms 140
b) across terminals of open isolator (kV) rms
160
Minimum clearance in open air (mm)
a) Between phases 1000
b) Live parts and ground 700
Rated mechanical terminal load
a) Straight load (KGS) 51
b) Across load (KGS) 17.33
16 Operating mechanism Motor operated
17 Operating time 10 12 secParticulars of insulators
a)Creepage distance (mm)
i)Total 1815
ii) Protected At least 50% of total Creepage distance
b)Dielectric strength wet : 140
dry : 160
i)Minimum one minute power frequency
withstand voltage (kV)rms
325
No. of auxiliary switch contacts 10 nos. each
(NO , NC )
XXI 66 KV CURRENT TRANSFORMER
Sl. No. Particulars
1 Nominal system voltage 66 KV
2 Rated Voltage 72.5 KV
3 Rated frequency 50 Hz
4 System neutral earthing Effectively earthed
12
13
14 0.5 Amps
15
18
19
Rated magnetizing current/ capacitive
current make/break capacity
Page 17 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
18/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
5 Installation Out door
6 Rated short circuit current 31.5 KA
Page 18 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
19/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
Rated insulation level
i)Impulse With stand voltage 350 KVP
ii)1 minute power frequency
withstand voltage
160 KV rms
8 Cont. Current Rating 120% of rated primary current
Description Core 1 Core -2 Core 3
1 Ratio 150-100-75-50/1
2 Rated primary current 50 50 50
3 Rated sec. current 1 1 1
4 Purpose Protection Protection Metering
5 Adopted ratio 75/1 75/1 75/1
6 Accuracy Class 5P20 PS 0.2
7 Rating of VA burden 20 20
8 Min Knee point voltage
9 RCT @ 75 deg cen
10 ISF
-
8/13/2019 14 Section-D-A1 Data Sheets
20/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
XXIII ACSR conductor
Sl. No Code Name ACSR Lynx
1 Complet dia of the conductor Stranding in
mm
19.53
2 Aluminium
Number 30
Dia of Each 2.79
3 Steel
Number 7
Dia of each strand 2.79
Minimum ultimate tensile strength (kG) 7945
Greasing required Yes/No NO
4 SYSTEM DATA
Voltage (kV) 110
No. of Phases & 3
Frequency (Hz) 50
Ambient Temp.(oC) : 50
Continuous Current Of the conductor 475
Short Time Current per Sub-Conductor 31.5
Seconds 1
XXIV
1 PV Modules Required Nos.
2 Inverter- power rating 10KW 1 Nos
3 Battery Bank- 12 Volts, 150 AH,20 cells 1 set
4 Charge Controller 1 Nos.
XXV
A PV Modules
1 Solar PV Modules of 230W capacity 125 Nos.
2 Junction Boxes 5 Nos.
3 Terminal Boxes 120 Nos.
B Power Conditioning Unit
1 Main Unit AFC 500-48 3 Nos.2 Main Contactor 3 Nos.
3 Power supply unit 3 Nos.
4 Axial ventilator 3 Nos.
5 Rotary operating mechanism 3 Nos.
6 Over voltage protection 3 Nos.
7 PV Fuses 25 Nos.
10KW System- One set shall consist of
ESSENTIAL SPARES : 1 set shall consist of following items and during 3
year O&M period any additional spare required shall be supplied with no
extra cost.
Page 20 of 21
-
8/13/2019 14 Section-D-A1 Data Sheets
21/21
CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1
C 6300 MVA Transformer
1 HV Bushing. 1set of 3 Nos.(One for each phase)
2 Neutral bushing. 1 No.
3 LV cable box complete with bushing- 1 set
4 Gaskets 1 set
5 Silical gel breather 1 No.
6 Buchholz relay 1 No.7 MOG 1 No.8 WTI with repeater 1 No.
9 OTI 1 No.
10 NCT 1 No.
11 Contacts of OFF circuit tap switch2 Set (Both fixed and moving contacts
suitable one phase)
12 Pressure relief device 1 No.
D Breaker1 Spare pole with operating mechanism 1 No.
2 Closing coil 4 Nos
3 Tripping coil 4 Nos
4
Spring charging motor for spring charging
mechanism1 No.
5
Gaskets & o ring for one set of 3 polebreaker
1 set
6
Gas filling unit comprising regulator with
manometer and necessary coupling hose
for filling of SF6 gas
1 No.
E Isolator
1 Fixed contact assembly 6 Nos. (1 set)
2 Moving contact blade 3 Nos.3 Closing contactor 2 Nos.
4 Opening contactor 2 Nos.
5 Operating motor 1 No
6 Solid core insulators 9Stacks(1set)
F Control and Protection panel
1 Numerical integrated multifunctionalTransformer protection relay
1 No.
2 Numerical O/C & E/F transformer protection relay
1 No.
3 Numerical E/F transformer protectionrelay
1 No.
4 High speed trip relay 1 No.
5 Breaker trip coil supervision relay 1 set
6High speed trip relay coil supervision
relay1 set
7 Auxiliary relay 1 each type
8Contact multiplication relay for Breaker
and Isolator1 each type