    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    I SOLAR ARRAYS

    1 Installed Capacity 5 MWp - Grid interactive

    2 Type of SPV module Mono/ Multicrystalline

    3 Rating of SPV module Minimum 200 wp

    4 PCU(Inverters) Highly efficient as specified

    (Section- D)5 SCADA for diagnosing & monitoring As per latest technology

    6 Schematics and layout drawings As specified(As per drawing)

    7 Total capacity of modules to be installed 5.25MW (50KW extra for each MW)

    8 Array rating 250 kw

    9 HT Transformers 1.25 MVA and 6.3 MVA

    10 Area required 25 acres

    11 Minimum Annual energy generation 8.322 mu(19% CUF)

    II MOUNTING STRUCTURE

    1, Type Ground Mounting-Fixed Type

    2 Material Mild Steel

    3 Overall dimensions Design As suitable

    4 Coating Dip (galvanized)/Anodized Hot

    5 Wind speed rating 150 Km/hr.

    6 Tilt angle 15 degree (as required)

    7 Foundation PCC (1:2:4)

    8 Number of Module structure Adequate

    9 Fixing type SS 304 fasteners

    III POWER CONDITIONING UNIT

    I Input Data

    1 Max PV power (recommended) 250 kWp

    2 DC voltage range 450 820 V3 Max permissible DC voltage 900 V

    4 Max permissible DC current 591 A

    II Output Data

    1, Nominal Ac power 250 kW

    2 Operating grid voltage -20% TO 15%

    3 Utility type 4 wire

    4 Operating frequency grid 50 Hz +OR 3%5 Voltage ripple PV voltage < 3%

    6 Efficiency 95 % AND ABOVE

    IV LT INTERFACING PANEL As per the Specifications in section D

    V

    a) Normal system voltage 11kV

    b) Corresponding highest system voltage 12 kV

    c) Frequency 50 Hz ( + 3%, - 5%)

    d) N umber of phases 3

    e) Neutral earthing As per requirements

    f) Class indoor/outdoor outdoor

    11KV SWITCHGEAR CUBICLE

    Page 1 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    2/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    g) Rated short circuit withstand of the panels As per requirements

    Free standing, Floor mounted,

    metal clad, fully compartmenta-

    lized draw-out type

    h) Switchgear

    Page 2 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    3/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    VI 11 KV CIRCUIT BREAKER DETAILS

    a) SF6 / Vacuum circuit Breaker re-strike

    free, trip free, stored energy operated

    and with electrical anti-pumping features

    Draw out type

    b) Number of poles 3

    c) Rated voltage 12 kVd) Rated normal current As per system requirements

    e) Rated frequency 50 Hz + 3%/-5%

    f) Rated short circuit breaking current As per requirements

    g) Rated short time As per requirement

    h) Rated Operating Duty 0-3 min co 3 min - coi) Rated insulation level rated/min. power

    frequency withstand voltage (Rms value)

    28 kV

    j) Rated lightning impulse withstand voltage

    (peak value)

    75 kV

    k) Rated duration 1 second short circuit

    110 V DC Control supply closing

    and opening 230 V AC Aux

    m) Supply devices & auxiliary circuits out

    door type

    Class indoor/outdoor

    n) No. of Auxiliary contacts 4No+4NC Contacts

    o) Current transformers rated Insulation

    level28 kV frequency withstand

    voltage (rms value)

    75 kV impulse withstand

    voltage (peak value)

    p) Class of insulation Class E

    q) Instrument Safety Factor(ISF) less than 3

    r) Minimum creepage 25 mm/kV of highest system voltage

    distanceC.T. details

    i) Ratio- Primary : As per requirement (Refer Section-D)

    -Secondary

    t) Class of Accuracy

    i) Core I 1.0

    ii) Core II 5P20

    u) Purpose of each corei) Core I Metering

    ii) Core II Protection

    v) Burden

    i) Core I 30 VA

    ii) Core II 30 VA

    VII 11 kv ISOLATORS REFER SECTION D

    ii) Rated lightning

    l) Rated supply voltage

    i) Rated/min power

    s)

    Note: CTs shall be of reputed make with proven experience.

    Page 3 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    4/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    Page 4 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    5/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    VIII 11 KV POTENTIAL TRANSFORMERS

    1

    a, Rated/min power 28 kV frequency withstand

    voltage(rms value)b. Rated lightning 75 kV impulse withstand voltage (peak

    value)2 Class of insulation Class E

    3 Rated voltage factor 1.2 continuous & 1.9 for 30 seconds

    4 Clear height of bushing 370 mm

    5 Minimum creepage 25 mm/kV of highest system voltage

    distance6 Applicable standard IS: 3156

    7 PT details

    8 Rating 11KV/ 3 / 110V/ 39 Burden 100 VA

    10 Class of Accuracy 1.0/3P

    11 Purpose Metering & protection

    12 Connection Star/Star

    Note :

    IX

    X 1250 KVA TRANSFORMER

    Designation step up transformer

    1, Installation outdoor Out door

    2 Degree of protection as per IP 55 IS:2147

    3 Rating in KVA 1250KVA

    4 Number of Phases 3 Phase

    5 Frequency 50 Hz

    6 Type of cooling ONAN

    7 No-load voltage

    8 a) HV 11000V

    9 b) LV 415V

    10 Vector group Dyn1111 % impedance 5

    12 System voltage

    Nominal system voltage

    a) HV 11000 V

    b) LV 415V

    TEMPERATUE RISE

    1, Reference ambient 40oc

    2 Oil by thermometer 35oc

    Rated Insulation level.

    i) Potential transformers shall be single phase units. PTs shall be of reputedmake with proven experience.

    ii) Each secondary shall be protected by 3 Amps. HRC fuse.

    Details of auxiliary supply for operation/control, protection, alarm,

    indication etc.DC supply - 110Volts +10% / - 15%

    AC supply 415 Volts + or-10% Three phase 4 wire system

    Page 5 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    6/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    3 Winding by resistance method 40oc

    Page 6 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    7/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    TAP CHANGING GEAR

    1, Taps ( Off load) : Required

    2 Tappings on windings: HV

    3 Total tappings range: 5%

    4 Steps 2.50%

    1, Dial type thermometer with two contacts

    for oil tempr.

    Required

    2 Magnetic oil level gauge with low oil level

    alarm contacts

    Required

    3 Gas and oil actuated ( i.e. Bucholz ) relay Required

    4 Gas sampling device Required

    5 Winding temperature indicator Required

    6 Off circuit tap changing mechanism

    valves

    Required

    7 Four plain rollers in place of fixing

    channels

    Required

    XI

    1

    1.1 Application / Designation Neutral Grounding Resistors

    1.2 Type & Quantity a. Cast Grid

    b Wire wound

    1.3 . Installation Outdoor/Indoor OUTDOOR

    1.4 Enclosure Tank Type, Weather proof with

    Aluminium covers2 RATING

    2.1 Rating KW: As suitable2.2 Ohmic Value As suitable

    2.3 Taps % 50,25

    2.4 Rated Current in Amps As suitable

    2.5 Duration of rating CONTINUOUS

    2.6 Voltage Class V Bidders to specify

    3

    suitable for conductor of

    3.1 Material GS

    3.2 Size As suitable

    XII DC BATTERIES

    XIII

    1 Co2 cylinder(Big size) 25 Nos.

    3 sets of 110 VOLTS Batteries each 100 AH capacity of Plante make.

    Each set conisting of One main and one Stand by Battery bank with 1 nos each

    of float and boost chargers confirming to standards as detailed in section

    D.One set to be installed for each inverter room.

    GENERAL

    Resistor earth, bushing terminal

    OTHER FITTINGS REQUIRED FOR 1250 KVA TRANSFORMER

    NEUTRAL GROUNDING RESISTOR FOR TRANSFORMERS

    FIRE FIGHTING EQUIPMENTS: 1 set consisting of following:

    Page 7 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    8/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    2 Sand buckets 30 Nos.

    3 Foam type fire extinguishers 20 Nos.

    4 Dry chemecal powder type extinguishers 20 Nos.

    5 Smoke sensors 20 Nos.(for control rooms)

    Page 8 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    9/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    XIV

    1Solar yard lights along pepiphery on poles

    sodium vapour lamps70 Nos.

    2

    Control room, office, Amphitheater, Toilet,

    Building illumination(24Watts CFL) Quantity as per building design

    3

    Yard Flood lights

    3 nos

    4ODY illumination - Sodium Vapour lamps

    20 Nos.

    XV

    1

    Suitable software and adequate database

    with suitable memory for all parameters

    of the plant

    1 set

    2Computers/ servers of latest version

    (Branded make ) with accessories 3 Nos.

    3 Laser Jet colour Printer-A3 2 Nos

    4Devices for web based communication

    system As required

    5 LAN networking As required

    6 UPS As required

    XVI 6300 KVA, 11/66 KV TRANSFORMER

    Sl.No. Technical Particulars

    1 Type Out door/Step Up2 No. of windings Two

    3 No. of Phases Three

    4 System frequency 50 Hz+3%& - 5%

    5 a) Rating of HV winding 6.3 MVA

    b) Rating of LV winding 6.3 MVA

    6 a)Low Voltage Winding 11 kV

    b)High Voltage Winding 66 kV

    7 a) H.V. Winding Star

    b) L.V. Winding Delta

    c) Neutral Effectively earthed.

    8 Vector Group YNd11

    b)H.V. Terminals : 72.5 kV OIP condenser type bushing

    suitable for Lynx ACSR conductor

    c) H.V.Neutral Bushing of suitable rating, solid

    porcelain type

    10 a) High Voltage Winding Graded insulation

    b) Low Voltage Winding Uniform insulation

    12 KV Solid Porcelain bushings.

    Bushings shall be suitable for

    connecting 11 KV XLPE cables.

    ILLUMINATION SYSTEM: 1 set consisting of following:

    9 a) L.V. Terminals :

    SCADA SYSTEM: 1 set consisting of following:

    Page 9 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    10/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    11 Type of cooling ONAN

    12 Impedance Voltage at normal tap 8.35%

    13 Insulating Medium Mineral Oil (as per IEC:60296 and bid

    specification)

    Page 10 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    11/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    14 Tap changing gear Details

    A Type OCTC on HV side

    B Tapping range as % of off load Rated

    KVA

    +/- 5 % (5 Steps of 2.5% each tap)

    C No. of tapping 5 Steps of 2.5% (including normal)

    XVII 200 KVA, 11/0.440 KV AUXILIARY TRANSFORMER

    Sl. No. Technical Particulars

    1 Type Indoor/ Outdoor/Step-down

    2 No. of windings Two

    3 No. of Phases Three

    4 System frequency 50 Hz+3%& - 5%

    5 Rating 200KVA

    6 a) HV Voltage 11kV

    b) LV Voltage 0.440kV

    7 a) HV Winding Delta

    b) LV Winding Star c) Neutral Effectively earthed

    8 Vector Group Dyn11

    9 Type of cooling AN

    10 Impedance Voltage at normal tap 4.50%

    11 Tap changing gear

    a) Type Off circuit

    b) Tapping range as % of off load Rated

    KVA

    -5% to +5% in steps of 2.5%

    12 Power frequency withstand voltage for 1

    minute

    For HV winding 28kV rmsFor LV winding 3kV rms

    For HV winding 75kV peak

    For LV winding NA

    14 Insulation Class F

    15 The maximum permissible temperature

    rise over maximum ambient temperature

    of 40oC

    a) Winding (measured by resistance

    method)

    90C

    b) Core, metallic parts and adjacent

    materials

    The temperature shall in no case reach

    a value that will damage the core itself,

    other parts or adjacent materials

    16 Terminal connections

    HV terminals HV terminals shall be suitable for 11 kV

    bus

    13 Rated lightning impulse withstand voltage

    for 1.2/50 microsecond

    Page 11 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    12/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    LV terminals The LV terminals shall be suitable for

    PVC / XLPE cables

    17 Insulation grading HV & LV winding shall be uniformly

    insulated18 Ability to withstand short circuit & duration

    of short circuit

    According to IS 2026/ IS:11171

    19 Overloads According to IEC:60905

    Page 12 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    13/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    XVIII 66 KV POTENTIAL TRANSFORMER

    Sl. No. Technical Particulars

    1 Rated voltage 72.5 kV

    2 Rated frequency 50 c/s

    3 Accuracy class of Winding as required

    4 Voltage ratio 66 kV/3/110V/35 Grade of oil As per IS: 335

    6 Maximum phase angle error with 25%

    and 110% of rated burden at 0.8 p.f.

    lagging at any voltage between 80% and

    120%

    40 min.

    7 Temperature rise at 1-1 times rated

    voltage with rated burden (OC)

    As per IS: 3156

    8 Rated voltage factor & time (based on

    system studies)

    Continuous 1.2 ; 30 seconds-1.5

    i) 1 minute power frequency (wet/dry) :

    140 kV r.m.s. withstand test voltage (Asper IS: 3156)ii) 1.2/50 micro seconds impulse wave :

    325 kV (Peak) withstand test voltage

    11 Minimum creepage distance of bushings 1815 mm

    XIX 66 kV CIRCUIT BREAKER

    1 Number of poles 3

    2 Class Out Door Type

    3 Nominal System Voltage 66 kV

    4 Rated Voltage 72.5 kV

    5 Rated Insulation Level 350 kV(peak)

    6 Rated Frequency 50 Hz

    7 Rated normal current 1600 Amps.

    9 Rated Cable Charging breaking current 140 Amps

    10 Rated S.C. breaking current 31.5 kA11 First pole to clear factor 1.5

    12 S.C. making current 79 kAP

    13 Rated Operating Sequence O-0.3sec-CO-3min.-CO

    14 Duration of short circuit 3 sec.

    15 Rated out of phase breaking current 7.9 kAmps

    16 Automatic rapid re closing 3 Ph.

    9 Insulation Level (based on system

    insulation coordination)

    2 kV10 One minute power frequency withstand

    test voltage on secondaries

    Page 13 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    14/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    17 Total break time for any current up to the

    rated breaking current with limiting

    conditions of operating coil voltage,

    operating &quenching media pressures.

    < 60 ms

    18 No. of auxiliary contacts for purchasers

    use

    10 NO & 10 NC on each pole

    19 System neutral earthing Effectively earthed

    Page 14 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    15/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    Closing time(max.)

  • 8/13/2019 14 Section-D-A1 Data Sheets

    16/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    3 Rated frequency 50 Hz

    4 System neutral earthing Effectively earthed

    5 Installation Out door

    6 Type of disconnect Horizontal double break

    7 Number of poles 3

    Page 16 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    17/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    8 Rated normal current 1600 Amps

    9 Rated short time with-stand current (KA

    rms)a) For 1 sec 31.5

    b) For 3 sec 31.5

    10 Rated peak withstand current for both

    main and earth switch (KA) peak

    78.75

    11 Rated insulation level 1.2/50 micro

    second lightning impulse withstand

    voltage (kV) peaka)between live parts and ground 325 (kV)peak

    b)across the open terminal of the same

    phase

    375 (kV) peak

    One minute dry/wet power frequency

    withstand voltage for complete

    assembled isolator /isolator cum earthing

    switch.a) against ground (kV) rms 140

    b) across terminals of open isolator (kV) rms

    160

    Minimum clearance in open air (mm)

    a) Between phases 1000

    b) Live parts and ground 700

    Rated mechanical terminal load

    a) Straight load (KGS) 51

    b) Across load (KGS) 17.33

    16 Operating mechanism Motor operated

    17 Operating time 10 12 secParticulars of insulators

    a)Creepage distance (mm)

    i)Total 1815

    ii) Protected At least 50% of total Creepage distance

    b)Dielectric strength wet : 140

    dry : 160

    i)Minimum one minute power frequency

    withstand voltage (kV)rms

    325

    No. of auxiliary switch contacts 10 nos. each

    (NO , NC )

    XXI 66 KV CURRENT TRANSFORMER

    Sl. No. Particulars

    1 Nominal system voltage 66 KV

    2 Rated Voltage 72.5 KV

    3 Rated frequency 50 Hz

    4 System neutral earthing Effectively earthed

    12

    13

    14 0.5 Amps

    15

    18

    19

    Rated magnetizing current/ capacitive

    current make/break capacity

    Page 17 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    18/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    5 Installation Out door

    6 Rated short circuit current 31.5 KA

    Page 18 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    19/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    Rated insulation level

    i)Impulse With stand voltage 350 KVP

    ii)1 minute power frequency

    withstand voltage

    160 KV rms

    8 Cont. Current Rating 120% of rated primary current

    Description Core 1 Core -2 Core 3

    1 Ratio 150-100-75-50/1

    2 Rated primary current 50 50 50

    3 Rated sec. current 1 1 1

    4 Purpose Protection Protection Metering

    5 Adopted ratio 75/1 75/1 75/1

    6 Accuracy Class 5P20 PS 0.2

    7 Rating of VA burden 20 20

    8 Min Knee point voltage

    9 RCT @ 75 deg cen

    10 ISF

  • 8/13/2019 14 Section-D-A1 Data Sheets

    20/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    XXIII ACSR conductor

    Sl. No Code Name ACSR Lynx

    1 Complet dia of the conductor Stranding in

    mm

    19.53

    2 Aluminium

    Number 30

    Dia of Each 2.79

    3 Steel

    Number 7

    Dia of each strand 2.79

    Minimum ultimate tensile strength (kG) 7945

    Greasing required Yes/No NO

    4 SYSTEM DATA

    Voltage (kV) 110

    No. of Phases & 3

    Frequency (Hz) 50

    Ambient Temp.(oC) : 50

    Continuous Current Of the conductor 475

    Short Time Current per Sub-Conductor 31.5

    Seconds 1

    XXIV

    1 PV Modules Required Nos.

    2 Inverter- power rating 10KW 1 Nos

    3 Battery Bank- 12 Volts, 150 AH,20 cells 1 set

    4 Charge Controller 1 Nos.

    XXV

    A PV Modules

    1 Solar PV Modules of 230W capacity 125 Nos.

    2 Junction Boxes 5 Nos.

    3 Terminal Boxes 120 Nos.

    B Power Conditioning Unit

    1 Main Unit AFC 500-48 3 Nos.2 Main Contactor 3 Nos.

    3 Power supply unit 3 Nos.

    4 Axial ventilator 3 Nos.

    5 Rotary operating mechanism 3 Nos.

    6 Over voltage protection 3 Nos.

    7 PV Fuses 25 Nos.

    10KW System- One set shall consist of

    ESSENTIAL SPARES : 1 set shall consist of following items and during 3

    year O&M period any additional spare required shall be supplied with no

    extra cost.

    Page 20 of 21

  • 8/13/2019 14 Section-D-A1 Data Sheets

    21/21

    CE(GSW)/SPV/BELAKAVADI SOLAR PV POWER PLANT SECTION-DDATA SHEETS-A1

    C 6300 MVA Transformer

    1 HV Bushing. 1set of 3 Nos.(One for each phase)

    2 Neutral bushing. 1 No.

    3 LV cable box complete with bushing- 1 set

    4 Gaskets 1 set

    5 Silical gel breather 1 No.

    6 Buchholz relay 1 No.7 MOG 1 No.8 WTI with repeater 1 No.

    9 OTI 1 No.

    10 NCT 1 No.

    11 Contacts of OFF circuit tap switch2 Set (Both fixed and moving contacts

    suitable one phase)

    12 Pressure relief device 1 No.

    D Breaker1 Spare pole with operating mechanism 1 No.

    2 Closing coil 4 Nos

    3 Tripping coil 4 Nos

    4

    Spring charging motor for spring charging

    mechanism1 No.

    5

    Gaskets & o ring for one set of 3 polebreaker

    1 set

    6

    Gas filling unit comprising regulator with

    manometer and necessary coupling hose

    for filling of SF6 gas

    1 No.

    E Isolator

    1 Fixed contact assembly 6 Nos. (1 set)

    2 Moving contact blade 3 Nos.3 Closing contactor 2 Nos.

    4 Opening contactor 2 Nos.

    5 Operating motor 1 No

    6 Solid core insulators 9Stacks(1set)

    F Control and Protection panel

    1 Numerical integrated multifunctionalTransformer protection relay

    1 No.

    2 Numerical O/C & E/F transformer protection relay

    1 No.

    3 Numerical E/F transformer protectionrelay

    1 No.

    4 High speed trip relay 1 No.

    5 Breaker trip coil supervision relay 1 set

    6High speed trip relay coil supervision

    relay1 set

    7 Auxiliary relay 1 each type

    8Contact multiplication relay for Breaker

    and Isolator1 each type