14pe1.pdf

Upload: chetan-soni

Post on 07-Aug-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/21/2019 14PE1.pdf

    1/12

    IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 1, JANUARY 2014 201

    Maximum Power Transfer Tracking forUltralow-Power Electromagnetic Energy Harvesters

    Gyorgy D. Szarka, Stephen G. Burrow, Plamen P. Proynov, and Bernard H. Stark 

     Abstract  —This paper describes the design and operation of power conditioning system with maximum power transfer track-ing (MPTT) for low-power electromagnetic energy harvesters. Thesystem is fully autonomous, starts up from zero stored energy, andactively rectifies and boosts the harvester voltage. The power con-ditioning system is able to operate the harvester at the maximumpower point against varying excitation and load conditions, re-sulting in significantly increased power generation when the loadcurrent waveform has a high peak-to-mean ratio. First, the papersets out the argument for MPTT, alongside the discussion on thedynamic effects of varying electrical damping on the mechanicalstructure. With sources featuring stored energy, such as a resonantharvester, maximum power point control can become unstable in

    certain conditions, and thus, a method to determine the maximumrate of change of electrical damping is presented. The completepower conditioning circuit is tested with an electromagnetic en-ergy harvester that generates 600 mVrm s  ac output at 870 µW un-der optimum load conditions, at 3.75 m·s−2 excitation. The digitalMPTT control circuit is shown to successfully track the optimumoperating conditions, responding to changes in both excitation andthe load conditions. At 2 Vdc  output, the total current consumptionof the combined ancillary and control circuits is just 22  µA. Thepower conditioning system is capable of transferring up to 70% of the potentially extractable power to the energy storage.

     Index Terms —AC–DC converter, energy harvesting, low power,maximum power tracking, rectification.

    I. INTRODUCTION

    THE output of small electromagnetic energy harvesters typ-

    ically requires rectification and boosting in order to pro-

    duce an output voltage that falls within the allowable operating

    range of the load electronics. In some applications, there is also

    a need to buffer energy in high capacity storage elements, such

    as supercapacitors, in order to supply loads with a higher peak 

    demand than the harvester output [1]. Several circuit architec-

    tures have been reported in published literature, which meet

    these requirements, including single-stage ac–dc switch-mode

    power converters [2]. Efficiencies up to 75%–80% at 500  µW

    Manuscript received October 11, 2012; revised December 21, 2012 andJanuary 23, 2013; accepted February 19, 2013. Date of current version July18, 2013. Recommended for publication by Associate Editor S. Y. (Ron) Hui.

    G. D. Szarka, P. P. Proynov, and B. H. Stark are with the Depart-ment of Electrical and Electronic Engineering, University of Bristol, Bristol,BS2 8BB, U.K. (e-mail: [email protected]; [email protected];[email protected]).

    S. G. Burrow is with the Department of Aerospace Engineering, Universityof Bristol, Bristol, BS2 8BB, U.K. (e-mail: [email protected]).

    Color versions of one or more of the figures in this paper are available onlineat http://ieeexplore.ieee.org.

    Digital Object Identifier 10.1109/TPEL.2013.2251427

    level have been reported [3]. However, in order to achieve the

    maximum potential power of an energy harvester, it is important

    that the power conditioning system provides the optimum load

    for the generator for the particular input and output conditions.

    Vibration harvesters have a “peak-power”-type response:

    power variation with changing load damping is not monotonic,

    displaying a peak at a damping level determined by harvester pa-

    rameters [4]. Negative-feedback voltage regulation for switch-

    ing converters cannot provide a stable operation at the peak 

    power point as the operating conditions required violate Middle-

    brook’s stability criterion [5]. The optimum damping level of an

    ideal harvester driven at resonance is independent of excitationamplitude; hence, one solution is to employ a converter emulat-

    ing a fixed impedance to the harvester, as reported in [5] and [6].

    However, fixed input impedance places restrictions on converter

    design (principally requiring discontinuous conduction), and

    this is difficult to maintain over the full range of input and out-

    put conditions. The challenge for the power converter is then

    to provide the basic functionality of rectification and voltage-

    level shifting, while loading the harvester with the optimum

    impedance, independently of its input and output conditions. In

    this paper, the electromagnetic energy harvester is assumed to

    be operating at its mechanical resonance frequency, making its

    effective output impedance dominantly resistive [7], and con-stant over time. By contrast, the apparent input impedance of 

    the power converter depends on the input and output voltage

    conditions. As these vary over time, dynamic control is required

    to maintain the desired converter input impedance.

    Maximum power point tracking (MPPT) schemes employ an

    algorithm, such as gradient descent, to locate a peak power point

    for the prevailing operating conditions. They are commonly used

    to maintain temperature-dependent photovoltaic cells at their

    peak power point [8], [9], and offer the ability to optimally load

    an energy harvester, compensating for both variations in opti-

    mal load and variations in converter output conditions. However,

    when used with systems with significant stored energy (like the

    kinetic energy harvesters investigated here) extra care must be

    taken to ensure correct operation. The literature on maximum

    power point tracking solutions for energy harvesting is relatively

    sparse. Elmes et al. [10] reported a maximum energy harvesting

    control scheme for an energy harvesting backpack generating

    tens of watts of power. In [11], a microcontroller-based power

    point tracker is reported for a rotational generator producing dc

    output up to 10 mW; the circuit employs a resistance matching

    strategy, similar to the approach adapted in [12] for submilliwatt

    RF energy harvesting. One of the first authors to publish on peak 

    power control in the energy harvesting literature was Ottman;

    the presented power converter architecture differed from the

    0885-8993/$31.00 © 2013 IEEE

  • 8/21/2019 14PE1.pdf

    2/12

    202 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 1, JANUARY 2014

    work here as the rectifier of the two-stage topology fed into a

    stiff dc link, which itself was controlled to provide the power

    tracking capability. Additionally, the paper focused on piezo-

    electric transducers. Low-power solutions offering regulation

    of the buffered output voltage of the rectification stage for max-

    imum power point operation have been demonstrated in the lit-

    erature: for piezoelectric harvesters using an off-the-shelf buck 

    converter operated intermittently [14], or for electromagnetic

    generators using a low-power integrated boost converter [15].

    Recently, an integrated maximum power point tracking circuit

    has been presented in [16] that operates down to sub-100  µWlevels, using an approach referred to as power-optimal point of 

    charging for the control of a dc–dc charge-pump.

    These solutions are designed to maximize the power gener-

    ated by the harvester without considering the losses of power

    conversion or the quiescent power overheads of any control and

    ancillary circuits. Derivatives of the MPPT technique, referred

    to as maximum power transfer tracking (MPTT) [8], are de-

    signed to maximize the power transferred to the load and the

    energy storage element. Dayal and Parsa [17] proposed a low-power implementation for an MPTT scheme, but only simulated

    results are presented for the control circuit. In the reported pa-

    per, the output voltage is maximized by varying the duty ratio

    of the pulse width modulation (PWM) driving signal of a split-

    capacitor ac–dc converter. This technique assumes that the load

    is near constant and purely resistive; otherwise, maximizing

    the voltage would not yield maximum output power conditions.

    Also, it requires the energy storage element to be small in order

    to be able to monitor the effect of varying duty ratio. These

    assumptions pose impractical limitations on small-scale energy

    harvesting that is typically characterized by very low generated

    power levels, large energy storage elements, and load circuitswith highly dynamic power consumption.

    The effects of the stored energy within the mechanical os-

    cillator of the harvester on MPPT are alluded to in [10] and

    [11], by stating that the control loop has to be slow in or-

    der to avoid instability. However, the behavior of the har-

    vester under varying damping and the implications regarding

    the design of the control circuit has not been discussed in the

    literature.

    In this paper, the maximum response rate of the MPTT

    algorithm resulting in stable operation is investigated and a

    complete MPTT harvesting system is presented. Section II de-

    scribes an electromagnetic energy harvester with the governing

    equations of motion, investigating the harvester’s response todynamic electrical damping experimentally. Next, an analysis

    of the harvester’s response to a step change in the damping is

    described, which enables the derivation of the minimum settling

    time required between perturbations of the control parameter.

    Section III provides a description of the power conditioning

    circuit. Section IV presents the operating principles for the

    perturb-and-observe algorithm and describes the control circuit.

    Section V presents experimental results that show the steady-

    state performance of the MPTT and the behavior under transient

    load and excitation conditions. Finally, Section VI summarizes

    the key findings and concludes with suggestions for future

    work.

    Fig. 1. Small-scale electromagnetic energy harvester with a 3.4 g NdFeBmagnetactingas themovingmass withina coil woundusing600 turnsof 100 µmdiameter copper wire. The resonant frequency is 43.8 Hz. A piezoelectric thinfilm is bonded to the top of the cantilever for displacement monitoring.

    II. ENERGY HARVESTER: STEADY-STATE AND

    TRANSIENT CHARACTERISTICS

     A. Electromagnetic Energy Harvester 

    A cantilever-type vibration harvester is used in this paper,

    shown in Fig. 1. It features a BeCu beam with a 3.4 g Nd-

    FeB magnet acting as the tip mass. Energy from the motionis transferred to the electrical domain via the electromagnetic

    coupling between the moving magnet and a wound coil. The tip

    mass is large compared to the beam; hence, the generator can

    be modeled as a base excited, second-order, velocity-damped

    mass–spring system, where the response to external forcing is

    described by

    mz̈ + cż + kz  =  mω2 Y   sin ωt.   (1)

    The base displacement has an amplitude   Y   at an angularfrequency of  ω . The equivalent mass at the tip is given as  m,while c denotes theviscous damping within the system that is thecombination of the mechanical and the electrical damping. The

    spring constant of the compliant beam is k , and z  refers to themotion of the moving mass relative to the frame. The schematic

    illustrations of the electromagnetic energy harvester and the

    lumped element model of the spring-mass-damper system are

    presented in Fig. 2.

    The steady-state solution, referring to the condition where the

    amplitude of the periodic motion is constant, is given as [4]

    z(t) = Z  sin(ωt − ϕ)   (2)where the amplitude is given by

    Z  =  mω2 Y  

    (k − ω2 m)2 + c2 ω2(3)

    and the phase angle between the base and tip displacement is

    given by

    ϕ = tan−1  c ω

    k − ω2 m .   (4)

    At the natural resonance frequency, which is described by

    ω  =  ωn

     =   km

      (5)

  • 8/21/2019 14PE1.pdf

    3/12

    SZARKA  et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS 203

    Fig. 2. (a) Schematic illustration of the electromagnetic energy harvestershown in Fig. 1, and (b) illustration of the lumped elements of the spring–mass–damper system.

    Fig. 3. Load resistance profiles with various gradients, resulting in linear loadresistance sweeps between 1000  Ω  and 100  Ω  in 0.5, 1 s, 2, 4, and 8 s. Both(left) decreasing and (right) increasing resistance profiles are considered.

    (2) simplifies to

    z (t) = mωY 

    c  sin

    ωt −  π

    2.   (6)

    Depending on the application, both of the excitation fre-quency ω   and amplitude  Y  can vary over time. Furthermore,damping arising from the interfacing electronics affects the to-

    tal damping given by [4]

    c =  cm  +  θ2

    Rcoil +  Rload(7)

    where cm  represents the mechanical damping, θ the electromag-netic coupling coefficient, and  Rcoil   is the parasitic resistanceof the coil. Rload  is the load resistance, which is synthesized bythe input impedance of the power converter in a practical sys-

    tem. In typical small-scale electromagnetic energy harvesters,

    the impedance of the parasitic coil inductance at the excitationfrequency is several orders of magnitude lower than the com-

    bined equivalent mechanical resistive output impedance and ac

    coil resistance. Therefore, it is assumed that close to the theoret-

    ical, maximum power can be extracted using a purely resistive

    load at resonance.

     B. Illustration of Response to Dynamic Damping

    The transient response of the mechanical system is related

    to the energy stored in the oscillator and the total damping of 

    the system. To illustrate this experimentally, the load applied to

    the harvester of Fig. 1 is swept from 100 to 1000  Ω at differing

    rates (see Fig. 3), while the excitation is kept constant. Prior to

    Fig. 4. Generated output power versus time corresponding to the 0.5, 1, 2, 4,and 8 s load resistance sweep profiles of Fig. 3. Excitation amplitude is activelyheld at 3.75 m·s−2 and the frequency is 43.8 Hz.

    Fig. 5. Measured generated power profiles of Fig. 4 mapped onto correspond-ing load resistance sweeps and compared against steady-state measurements.

    each sweep, the harvester is in steady state. The instantaneous

    generated power is measured and averaged over one cycle. The

    resulting output power–time profiles are presented in Fig. 4.

    The output power mapped onto the corresponding load re-

    sistance is shown in Fig. 5, resulting in hysteretic trajectories

    of output power as the load is swept up and down at a particu-

    lar rate. The cycle-averaged power recorded under steady-state

    conditions is also shown for comparison. This reveals that the

    maximum power that can be sustained by the energy harvesterat the optimum resistance of 400  Ω   is around 870  µW; how-ever, during a sweep, much higher powers are available if the

    damping is rapidly increased and much lower powers while the

    damping is being reduced.

    This behavior can be understood by considering the energy

    stored in the mechanical components of the harvester. Most

    harvesters feature significant amplification of source vibrations,

    analogous to the quality factor or  “Q” of electrical resonant cir-cuits. Q also defines the ratio of energy stored in an oscillator tothat dissipated each cycle. Thus, for high-Q systems, a change inthe operating point requires significant energy to be either added

    or dissipated. At high load resistance, corresponding to low

  • 8/21/2019 14PE1.pdf

    4/12

    204 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 1, JANUARY 2014

    Fig. 6. (a) Generated rms current and voltage waveforms during the 4 s sweeptransients, and (b) current and voltage excursions mapped to the correspondingload resistance.

    damping, significant energy is stored in the system. Increasing

    the damping reduces the displacement of the mass, thereby re-

    ducing the stored energy, which is seen as transient additional

    output power. Conversely, reducing the damping leads to an

    increase in stored energy, which although is supplied by the

    vibration source, limits the rate at which the new steady state

    is approached. As the rate of change of the electrical damp-ing is reduced, the measured output power levels converge to

    the steady-state solution. The generated rms current and volt-

    age transients are illustrated in Fig. 6 for the 4-s sweep case.

    The curves show that during the increase of the damping, the

    corresponding transient voltage and current travels are higher

    than during decreasing damping, as some of the initial kinetic

    energy of the energy harvester is dissipated. The behavior illus-

    trated here is of great importance when implementing a power

    tracking scheme. If the controller does not take into account the

    transient component of the output power by allowing sufficient

    settling time of the harvester, the system can become unstable.

    C. Response to Step Change in Damping

    In this section, a step change in the damping is considered,

    as might be the case when a digital system steps a control refer-

    ence signal. The harvester is modeled as a highly underdamped,

    single-degree-of-freedom mass–spring–damper system, excited

    at its natural frequency with constant acceleration amplitude.

    Also, prior to the change, the mechanical structure is assumed

    to be in steady state. The damping as a function of time can be

    described as

    c(t) = co , t ≤ 0cs , t > 0

      .   (8)

    In the steady-state solution of (6), the amplitude of the tip

    displacement before the step change is

    Z o  =  mωY 

    co(9)

    and after the step change, the oscillation should settle to the new

    steady-state solution with a tip displacement amplitude of 

    Z s  =  mωY 

    cs.   (10)

    The initial conditions for the nonhomogeneous second-order

    differential equation of (1) are obtained by finding the steady-

    state displacement and velocity at time t = 0. Hence, the initialdisplacement is   z (0) = −Z o , and velocity is  ż (0) = 0. Thesolution of the differential equation is

    z (t) = (Z s −Z o ) e−(cs /2m )t cos (ωβt)

    + (Z s −Z o ) cs

    2mωβ   e−(cs /2m )t sin(ωβt) − Z s cos (ωt)   (11)

    where β  is given as 

    1 − ζ 2 , and the damping ratio ζ   is

    ζ  =  c

    2√ 

    mk.   (12)

    In a highly underdamped system (ζ <  0.1), such as typicalsmall-scale electromagnetic energy harvesters,  β  is assumed tobe 1. This simplifies the solution to

    −z (t) =

    Z s + (Z o − Z s ) e−(cs /2m )t

    cos(ωt)

    + (Z o −Z s ) cs

    2mω  e−(cs /2m )t sin(ωt) .   (13)

    This equation shows that the underlying sinusoidal oscillationwith initial amplitude of Z o decays exponentially to a sinusoidaloscillation with amplitude of  Z s , with a rate that is determinedby the total damping and the moving mass.

    This time-domain solution is validated (see Fig. 7) using

    measured output power for several step changes in the load

    resistance. The measurement results show a good correlation

    with the calculated waveforms.

    The second exponential term of (13) can be considered negli-

    gible in a highly underdamped system, where the damping coef-

    ficient is very small, as the denominator of multiplying fraction

    is typically greater than 1, and the product of  (Z o −Z s ) cs   issmall, in the order of 10−

    5

    . Hence, the amplitude of the sinu-soidal oscillation is dominated by

    |z| ∼= Z s  + (Z o −Z s ) e−(cs /2m )t (14)an exponential decay to the new tip displacement amplitude.

    Differentiating this solution yields the approximate solution for

    the velocity

    v (t) = Z s ω sin(ωt) + (Z o − Z s )   cs2m

    e−(cs /2m )t cos(ωt)

    + (Z o − Z s ) ωe−(cs /2m )t sin(ωt) .   (15)Considering that the velocity amplitude in the steady-state

    solution is given as  V̂   = Z ω  and that ω  c/2m, the velocity

  • 8/21/2019 14PE1.pdf

    5/12

    SZARKA  et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS 205

    Fig. 7. Calculated, based on (13), and measured average output power duringthe transient response of the system that occurred after a step change in theload resistance. Initial load resistances are shown on the right; after the stepchange, the resistance is constant at 400  Ω. Excitation is a constant 3.75 m

    ·s−2

    acceleration at 43.8 Hz.

    amplitude during the transient response can be approximated

    with great fidelity in a highly underdamped systems as

    |v| =  V̂ s  +

    V̂ o −  V̂ s

    e−(cs /2m )t .   (16)

     D. Minimum Settling Time Selection

    The assumption is made that in order to avoid instability from

    any system condition, a digital control system should initiate a

    step change in damping c only once the system has settled. Thesettling time in this paper is defined as the time required for the

    output power to reach within 1% of its final value. In a typi-cal MPPT system, adjusting of the control parameter varies the

    apparent input resistance of the interfacing power electronics,

    resulting in discrete step perturbation of the generator damp-

    ing. Considering these steps, a harvester settling time can be

    defined and used as the lower limit on the time period between

    adjustments.

    The counterelectromotive force induced in the coil is propor-

    tional to the velocity of the moving magnet according to

    U (t) = Blv(t) = θv(t)   (17)

    where B is themagneticfield strength and l is the effective length

    of the conductor within the magnetic field. Thus, the amplitudeof the induced sinusoidal voltage is the coupling coefficient

    θ  times the velocity amplitude given in (16). The steady-stateinstantaneous current is dependent on the total load resistance

    of the circuit and is equal to

    i(t) =  U (t)

    Rcoil + Rload2(18)

    where Rload2  denotes the load resistance after the step change,and during the settling time. During the settling time, the ampli-

    tude of the generated current will decay exponentially toward

    the steady-state value

    I  (t) = I s  + (I o − I s ) e−(cs /2m )t

    (19)

    where I s  and I o  are given according to

    I  =  θmω2 Y 

    c (Rcoil + Rload2 )  (20)

    with c=cs  and c=co , respectively. The instantaneous generatedpower dissipated in the load resistance is given as

    P  (t) = i2 (t) ·Rload2 .   (21)Defining a common factor as

    A =  θ2 m2 ω4 Y  2

    (Rcoil +  Rload2 )2 Rload2   (22)

    allows us to write the current and power amplitudes as

    |I | = 

      A

    Rload2

     1

    cs+

     1

    co−   1

    cs

    e−(cs /2m )t

      (23)

    and

    |P |   = A  1

    c2s +

      2

    cs 1

    co −  1

    cs

    e−(cs /2m )t

    +

     1

    co−   1

    cs

    2e−(cs /m )t

    .   (24)

    According to the definition of the settling time, at  t  =  t s   theamplitude of the power for increasing damping should be

    |P | = P s (1 + ε)   (25)where P s  = A/c

    2s , and the error ε is 0.01. Substituting (25) into

    (24), then dividing both sides by A  and rearranging to one sideyields

    − ε  1c2s

    +   2cs

     1co−   1

    cs

    e−(cs /2m )ts

    +

     1

    co−   1

    cs

    2e−(cs /m )ts = 0   (26)

    Multiplying both sides by   ec sm   ts c

    2s co / (cs − co )   gives a

    quadratic equation in the form of 

    ε  co

    cs − co x2 − 2x −  cs − co

    co= 0   (27)

    where   x = exp[(cs /m)ts ]. Only the positive root of thequadratic equation yields a real solution

    e(cs /2m )ts =  1 + √ 1 + εεco /(cs − c0 )   (28)

    Isolating the settling time ts  gives

    ts  =  2m

    csln

     1 +√ 

    1 + ε

    εco|cs − co | .   (29)

    Equation (29) gives a conservative estimate that typically falls

    within 0.5% of the exact solution derived numerically from (13).

    Therefore, this formula provides a convenient means of esti-

    mating the minimum interval between perturbations in digital

    maximum power tracking control systems. It also shows the

    dependence on harvester parameters and tolerances.

  • 8/21/2019 14PE1.pdf

    6/12

    206 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 1, JANUARY 2014

    Fig. 8. System-level block diagram showing the main power electronics blocks and the power definitions within the main power flow of the system.

    III. POWER CONVERTER AND ANCILLARY CIRCUITRY

    The power conditioning system architecture is shown in

    Fig. 8. It builds on the low-power system reported by Szarka

    et al. [6], with the addition of low-power measurement and con-

    trol circuits for the MPTT control, and a modified low-power

    gate drive circuit design.

    The output voltage across the supercapacitor varies, therebyallowing the stored energy to be maximized; at the same time it

    is kept within the allowable dc supply voltage range of the load

    electronics, which avoids the losses of additional voltage reg-

    ulation. Zero-energy start-up is provided by a passive voltage

    multiplier circuit that is automatically disconnected when the

    active power converter circuit becomes operational. The main

    power converter is a nonsynchronous full-wave boost rectifier,

    as shown in Fig. 9, which provides rectification and voltage

    boosting in a single stage. The parasitic coil impedance, al-

    though considered to be negligible at the mechanical resonance

    frequency, is significant at the switching frequency of the power

    converter and can be used to eliminate the need for an additionalboost inductor. The MPTT control circuit adjusts the duty ratio

    δ   of the PWM gate drive signals. This controls the apparentinput impedance of the converter, preserving maximum output

    power Pstore. Consequently, near-optimum damping conditions

    for the energy harvester are maintained independently of vari-

    ations in the output voltage, the conduction mode, and the ex-

    citation magnitude; all of which are time-varying factors that

    influence the apparent input impedance of the power converter.

    The particular converter topology selected here does not support

    bidirectional power flow, thus restricting the control to resistive

    impedance matching only. This approach may be suboptimal

    when the generator is excited off resonance; however, it offers

    Fig. 9. Circuit schematic of a nonsynchronous, full-wave boost rectifier thatuses the parasitic coil inductance as the boost inductor. The semiconductordevices used are M1/M2—PMF-280UN and D1/D2— 1PS79SB30.

    high utilization when the source excitation is at the mechanical

    resonance frequency [3]. An example of typical input current

    and voltage waveforms are shown in Fig. 10.

    The gate drive circuit generates two-variable duty ratio PWM

    signals for the twolow-side transistors. Theswitching frequency

    is constant 32.768 kHz, determined by the output of the low-

    power oscillator chip (OV-7604), as shown in Fig. 11. Polarity

    of the input voltage is sensed by a thin-film piezoelectric sensorbonded to the cantilever beam.

    A saw-tooth signal is created using a one-shot circuit and a

    modified RC  filter that provides a slow discharge of the 15 pF

    capacitor. The duty ratio is determined by the “Reference”

    input, which is the common interface to the control circuits.

    The logic output stage, which directly drives the gates of the

    MOSFETS, receives polarity information from the detection

    circuit. At any moment in time, only one of the outputs is tog-

    gled at the switching frequency, while the other PWM signal is

    kept high. The only exception to this is during a blanking period

    around the zero-crossing of the generator’s output voltage, when

    both outputs are low.

  • 8/21/2019 14PE1.pdf

    7/12

    SZARKA  et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS 207

    Fig. 10. Measured typical input current I in  and voltage V in  waveforms. A period of 100 µs at 5 ms point is shown on the right for increased resolution. The dutyratio of the converter is 67% and the output voltage is 3.2 V. The energy harvester is excited with 43.8 Hz, 3 m·s−2 acceleration, producing a little over 450  µW.

    The printed circuit board implementation of the power condi-

    tioning system is shown in Fig. 12, corresponding to the block 

    diagram presented in Fig. 12.

    IV. CURRENT-SHUNT-BASED MAXIMUM POWER

    TRANSFER TRACKING

     A. Operating Principles and Measurement 

    A typical low-power energy harvesting system requires large

    capacity storage in order to be able to supply the high peak-to-mean ratio power demand required by load electronics such as

    wireless sensor nodes. The combination of low output power

    and large storage capacitance results in slow charge up of the

    supercapacitor. This enables the MPTT control to rely solely on

    output current measurement. The reference signal that sets the

    duty ratio of the boost rectifier is perturbed, and the effect of 

    this on the power transferred to the supercapacitor is observed

    by measuring the output current while the output voltage is as-

    sumed to be near constant. This implementation requires the rate

    of change of the output voltage to remain low enough to ensure

    a near-constant voltage between successive measurements. In

    the presented system, this limits the minimum capacitor size to

    20 mF, when the worst-case voltage increase between measure-ments is 5 mV.

    The measurement circuit is an operational amplifier based

    circuit (see Fig. 13) that is designed to measure the voltage

    drop across a 150 Ω precision shunt resistor. The current ripple,both at the switching and at the excitation frequency, must be

    minimized to ensure correct measurement.

    This is achieved by a combination of parallel capacitance

    introduced before the shunt resistor in the circuit, and an ac-

    tive low-pass Sallen–Key [18] architecture employed in the de-

    sign of the amplifier circuit. The 30  µF capacitor smoothes theswitching frequency current ripple without adding any signif-

    icant delay to the response of the system to the perturbation.

    Fig. 11. Gate drive circuit generating 32.768kHz output PWMsignals. “Pos,”“Neg,” and “Blank” are digital signals from the polarity detection circuit [6].“Reference” is an analogue signal from the control circuit to set the duty ratio.

    Fig. 12. Printed circuit board implementation of the main power conditioningsystem blocks, corresponding to Fig. 12.

    The second-order Butterworth filter has a cutoff frequency of 

    20 Hz, approximately half the excitation frequency, in order to

    provide a close to dc current measurement at the output of the

    amplifier. The micropower operational amplifier MCP6031 is

    selected because of its low input offset voltage that is typically

  • 8/21/2019 14PE1.pdf

    8/12

    208 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 1, JANUARY 2014

    Fig. 13. Shunt-resistor-based current-sense amplifier using a low-passSallen–Key architecture [18].

    Fig. 14. Digital MPTT circuit using a low-power MSP430 microcontrollerthat samples the output current using a 10-b ADC and controls the referencevoltage of the duty ratio by an 8-bit 0–450 mV output R–2R ladder. The samplereadings are synchronizedto the generator’s displacement cycle using the outputof the piezoelectric displacement sensor.

    around 150 µV [19], its low current consumption, and rail-to-rail input/output signal support. The gain of 30 V/V is selected,

    in order to maintain a sufficient signal-to-noise ratio.

     B. Digital Implementation of MPTT 

    The well-known perturb-and-observe algorithm is imple-

    mented on a MSP430F1132 microcontroller: the PWM dutyratio of the boost converter is altered and the consequent change

    in the output power is measured when the mechanical struc-

    ture has settled. Based on the measured outcome, the direction

    of the subsequent alteration is determined and the process re-

    peated. The controller’s CPU is clocked at 5 MHz frequency

    in order to minimize the power hungry on-time. The 10-b on-

    board analogue-to-digital converter (ADC) converts the current

    amplifier’s output, and the reference voltage for the duty ratio is

    set by an R–2R ladder, shown in Fig. 14. The top two bits of theladder are connected to ground, while the remaining eight bits

    are controlled via a full output port of the controller. This pro-

    vides a 1.75 mV resolution with a maximum output of 450 mV.

    Fig. 15. Steady-state characterization of power conditioning system in open-loop configuration. Voltage reference is stepped using an external signal at>5 s intervals. Excitation is held at 3.75 m·s−2 and 43.8 Hz. Output voltage isregulated using a shunt regulator circuit as a load (LM4041).

    The reference voltage is therefore changed in discrete steps of 

    1.75 mV, corresponding to a 0.6% change in the duty ratio.

    The worst-case minimum time required between perturbations,

    using (29), is approximately 350 ms, roughly 15 displacement

    cycles. The output of a level-crossing detection circuit that mon-

    itors the piezoelectric sensor output is used as a nonmaskable

    interrupt (NMI) that wakes the microcontroller up from “sleep

    mode.” This approach not only circumvents the need for a power

    hungry timer circuit but also ensures that the sample readings are

    synchronized to the displacement, which was shown to improve

    the control circuit’s stability [10].

    Under this configuration, the microcontroller is active for atotal of 90 µs, plus an additional 25  µs when only the internalADC is ON, in every 342.5 ms period. This results in an average

    power consumption of approximately 750 nW.

    V. EXPERIMENTAL RESULTS

     A. Steady-State Performance

    In order to evaluate the effectiveness of the MPTT circuitry,

    the power P store as a function of the duty ratio is measured. Thisis the useful output power after subtracting lossesincurred dueto

    nonideal loading of the generator, during the power conversion

    process, and the quiescent power overheads of the ancillary and

    control circuits. In this test, the output voltage is kept constantusing a micropower shunt regulator (LM4041) and the reference

    voltage is stepped using an external source in 5 s intervals to

    create quasi-steady-state measurements. During all of the tests

    presented in this section, a 68 mF supercapacitor is used as the

    main energy storage element. The combined current consump-

    tion of the ancillary circuits and the leakage current drawn by

    the start-up circuits is 19 µA at 2 V output voltage and increasesto 22  µA at 4.5 V output. The digital control circuit adds anadditional 3  µA, amounting to a total of 44  µW of minimumquiescent power loss.

    Fig. 15 presents the results measured at 3.75 m·s−2 excitationmagnitude, corresponding to a maximum extractable power of 

  • 8/21/2019 14PE1.pdf

    9/12

    SZARKA  et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS 209

    Fig. 16. Measured duty ratio samples and their modal values compared withthe range of duty ratios (shaded region) that correspond to over 99% of themaximum useful output power based on the measurements of Fig. 15.

    870 µW under optimum load conditions. The maximum trans-ferred power is 615 µW at 2 V at the optimum duty ratio. Thiscorresponds to a power conversion efficiency of 78.5%, and an

    overall system efficiency of 70.7%, where 100% is the maxi-

    mum extractable power from the energy harvester. As the output

    voltage is increased, the optimum duty ratio is also increased.

    The maximum useful power is, however, reduced due to the

    increased power overheads of the power conditioning circuits.

    It is worth noting that a small dip in the power level can be

    observed in the 4.5 V line around 80% duty ratio, creating two

    local maxima that could result in the failure of a perturb-and-observe MPTT algorithm. During normal operation however,

    this situation would not arise, as the output voltage rises slowly

    across the large capacity storage element, allowing the algorithm

    to track the correct peak. Starting the tracking at high duty ratios

    would also reduce the risk of finding the wrong local maximum.

    Fig. 16 shows duty ratio at discrete output voltages, held con-

    stant by the adjustable shunt regulator circuit. As the duty ratio is

    constantly changing, even in these steady-state conditions, 100

    recordings of the duty ratio are plotted, as dots, for each voltage,

    showing a range of around ±2.5%. The solid black line is fittedover the statistical modal value of each group of 100 samples,

    representing the most frequent duty ratio. The shaded region

    in Fig. 16 represents the duty ratio range over which in excessof 99% of the maximum transferred power is obtained. This

    region widens toward the low output voltage levels, as can also

    be seen in Fig. 15. The modes of the duty ratio measurements

    fall within the 99% power region for most of the output voltage

    points, which shows that the control circuit can effectively track 

    the optimum power point.

    Duringthe measurementsof theduty ratio samples, theenergy

    harvester’s generated power, the transferred power, and the qui-

    escent power overhead of the power conditioning system were

    also recorded. The 100 measurement points were averaged, to

    take into account that the duty ratio ranges around an optimum

    value. These values are plotted in Fig. 17 against output volt-

    Fig. 17. Average power obtained from 100 measurements per output voltage.Output voltage is regulated by an adjustable shunt regulator. Constant frameacceleration of 3.75 m·s−2 at 43.8 Hz.   P m ax   is the maximum extractableharvester power under optimum load conditions.

    age, along with the maximum extractable power from the energy

    harvester under optimum load conditions for comparison.

    The difference between the measured generated power and

    the transferred power are due to a combination of three major

    loss mechanisms: 1) a nonideal power conversion process; 2)

    quiescent power overheads of the control and ancillary circuits;

    and 3) the conduction loss in the shunt resistor used for the

    monitoring of the output current.

    The ratio between the generated power of the nonideally

    loaded harvester and the maximum potentially extractable

    power under optimum load conditions is referred to as the uti-lization factor. The utilization of the energy harvester peaks

    above 89% at 1.8 V output, and remains over 86% over the en-

    tireoutput voltage range. Less than 100% utilization is primarily

    due to the increased conduction losses within the coil that result

    from switching frequency current ripple. The power conversion

    efficiency is calculated as the ratio of the useful output power

    (P store ) of the converter to the generated power of the harvester,while the overall system effectiveness is defined as the useful

    output power normalized to the maximum extractable power

    from the energy harvester under optimum load conditions. The

    conversion efficiency is at its maximum of 76.5% at low voltage

    levels where the quiescent power overhead is at its minimum,

    dropping down to 66% at 4.5 V. The peak overall effective-

    ness reaches almost 70%, which when compared against the

    maximum of 70.7% recorded under the steady-state characteri-

    zation (see Fig. 15) shows a highly effective control.

     B. Transient Response to Step Change in Excitation and 

    Output Voltage

    The dynamic performance and stability is evaluated by

    recording the transient behavior of the power conditioning cir-

    cuit, monitored by the duty ratio of the converter, in response

    to a step change in the frame excitation magnitude and in the

    output voltage under the worst-case considerations.

  • 8/21/2019 14PE1.pdf

    10/12

    210 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 1, JANUARY 2014

    Fig. 18. Outputcurrentand duty ratioin response toa step change in excitationmagnitude from 3 to 4 m·s−2 at a constant 2.5 V output. The frequency isconstant at 43.8 Hz. The current is inferred from the output of the current-senseamplifier circuit.

    First, a step change in the acceleration magnitude from 3

    to 4 m·s−2 is considered (see Fig. 18) potentially providingtwice the generated power. The output voltage is maintained at

    a constant 2.5 V for the test. The increase in excitation ampli-

    tude results in increased generated power and voltage, which,

    in turn, affects the emulated resistance of the power converter.

    The control adjusts the duty ratio of the rectifier, and is seen to

    reestablish optimum damping conditions within around 4.5 s.

    At the instant of the step change in the frame acceleration mag-

    nitude (just before the 2 s mark), the available generated power

    and thus the useful output power increases at a rate that is dom-inated by the mechanical response of the energy harvester, i.e.,

    the time required by the tip mass to build up its momentum.

    The duty ratio of the power converter, as a means of moni-

    toring the control trajectory of the algorithm, is also presented

    in Fig. 18. The results show the clearly distinguishable duty

    ratio steps that characterize the digital implementation of the

    perturb-and-observe algorithm, and the tracking around a new

    “optimum” point.

    A worst-case step change in the load conditions is also con-

    sidered in this study: a rapid discharge of the energy storage

    element from its maximum rated output voltage of 4.5 to 2 V, as

    shown in Fig. 19. This situation mimics the burst release of en-

    ergy from the storage that may occur as a result of the executionof a power hungry task by the load electronics. Small dynamic

    variations in the power consumption of the load do not affect

    the output power performance of the power conditioning circuit

    as the 68 mF supercapacitor provides a buffer between the load

    and the power converter that smoothes these changes.

    The output current waveform is also presented in Fig. 19.

    During the discharge of the output capacitor, the output of the

    current-sense amplifier is saturated, and then the current starts

    to increase as a result of the changing duty ratio of the power

    converter. The duty ratio drops from around 84% to below 70%

    and converges to a new optimum condition in approximately

    8.5 s after the start of the discharge.

    Fig. 19. Rapid discharge of the 68 mF supercapacitor from its maximumrated voltage of 4.5 to 2 V via an adjustable shunt regulator (LM4041), thusmimicking a burst release of the stored energy for the load application.

    Fig. 20. Charging of a 68-mF supercapacitor over 500 s, showing zero-energystart-up and active MPTT. The overall system efficiency is normalized to themaximum extractable power of 870 µW. Measurements were taken at constantframe acceleration of 3.75 m·s−2 at 43.8 Hz.

    This reaction time represents the worst-case scenario as it

    corresponds to the largest optimum duty ratio difference that

    can occur under normal operation conditions and is a function

    of the maximum rate of change of the duty ratio of the control

    circuit and, thus, of the calculated settling time. An energy

    harvesting system with smaller tip mass, for example, would

    have a smaller settling time and the control could be set to react

    more quickly to rapid changes in the environmental conditions

    or in the power drawn by the load electronics.

    C. Overall System

    The last test is aimed to present the capability of the power

    conditioning system to start-up from zero-energy conditions

    and then track the maximum power transfer point actively while

    charging a 68 mF supercapacitor.

    At a constant excitation of 3.75 m·s−2 , the charging of thesupercapacitor is recorded over 500 s (see Fig. 20) along with

  • 8/21/2019 14PE1.pdf

    11/12

    SZARKA  et al.: MAXIMUM POWER TRANSFER TRACKING FOR ULTRALOW-POWER ELECTROMAGNETIC ENERGY HARVESTERS 211

    Fig. 21. Comparison of charge up times of a 68 mF supercapacitor using: 1)passive voltage quadrupler circuit; 2) full-wave boost rectifier in an open-loopwith constant duty ratio of δ  =  0.67; and 3) full-wave boost rectifier with MPTTcontrol. Excitation is regulated to be 3.75 m·s−2 at 43.8 Hz.

    the duty ratio (inferred from the reference voltage of the control

    circuit). The measured output voltage and useful output current

    of the power converter are used to calculate the transferred

    power. Theratio of this to the maximum extractable power under

    optimum load conditions provides the overall system efficiency

    ηover (see Fig. 20).The passive quadrupler circuit provides zero-energy start-

    up, charging the supercapacitor to 1.85 V at which point the

    active boost rectifier circuit starts to operate. The duty ratio,

    starting from a high initial value, quickly finds and tracks the

    optimum power transfer point over the charging of the capacitor.

    The overall efficiency is highest at low output voltages with anaverage value of close to 70%, as presented in Section V-A.

    The recorded instantaneous efficiency may exceed this due to

    the inertial effects of the mechanical structure resulting in short

    burst of power when the damping is increased.

    Fig. 21 presents the transient accumulation of energy in the

    68 mF supercapacitor when charged by differing power condi-

    tioning solutions: 1) passive voltage quadrupler; 2) the full-wave

    nonsynchronous boost rectifier in open loop with a constant duty

    ratio of  δ  = 0.67; and 3) full-wave boost rectifier with MPTTcontrol. The start-up phase is common for all approaches, pro-

    vided by the passive voltage multiplier circuit, during which the

    capacitor is charged from 0 to 1.85 V.

    The results illustrate that the overall output power gain of the

    system when MPTT control is employed: The total charge-up

    time, corresponding to 0.5 J of energy stored, is reduced by

    26.5% and by 8.6% as compared to the passive circuit and the

    open-loop systems, respectively. A summary of the key system

    metrics is presented in Table I.

    VI. CONCLUSION

    The work presented in this paper aimed to address the chal-

    lenges that arise from implementing MPTT for low-power, ki-

    netic electromagnetic energy harvesters. The transient response

    of the single-degree-of-freedom mechanical system is presented

    TABLE IKEY SYSTEM METRICS

    and discussed using experimental results and analytical deriva-

    tions. A method that aids the design of perturb-and-observe

    algorithm-based control with discrete perturbations of the con-

    trol parameter is presented: the minimum time required between

    perturbations in order to allow the mechanical structure to set-

    tle is calculated for highly underdamped mass–spring–damper

    systems under the assumption of a constant, sinusoidal, nondi-

    rect excitation that occurs at the natural resonance frequency of 

    the mechanical structure.A complete power conditioning circuit for a low voltage, sub-

    milliwatt electromagnetic energy harvester has been presented

    that requires no external power and is capable of self-starting

    from zero-energy conditions. In contrast with previous work,

    the transferred power is maximized instead of the generated

    power, thus accounting for the losses suffered during the power

    conversion process and the due to the quiescent power over-

    heads. Good peak power tracking effectiveness is demonstrated

    despite of the lack of accurate regulation of the apparent input

    impedance of the boost rectifier, thus allowing the use of a slow

    feedback control, and consequently, a reduced quiescent power

    implementation. The total power consumption of the power con-

    ditioning system is 44 µW at 2 V output.Steady-state and transient measurements show that the system

    is stable and capable of tracking the maximum power transfer

    point by optimizing the duty ratio of the PWM signals of the

    boost converter over the entire output voltage range. A harvester

    utilization of up to 89% is achieved. Overall system effective-

    ness up to 70% is recorded, corresponding to approximately

    600 µW of useful output power. The transient responses showthat the calculated settling time provides a reasonable choice for

    the minimum time between perturbations. The power converter

    topology used in this study can only synthesize resistive load

    conditions, limiting the maximum achievable utilization when

    the harvester is not in resonance as the optimum load required

  • 8/21/2019 14PE1.pdf

    12/12

    212 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 1, JANUARY 2014

    can have a significant reactive component. A natural extension

    of the work would be to apply MPPT control to converters

    capable of synthesizing complex load impedances.

    REFERENCES

    [1] B. H. Stark, G. D. Szarka, and E. D. Rooke, “Start-up circuit with low

    minimum operatingpower for microwatt energy harvesters,” IET Circuits,

     Devices Syst., vol. 5, no. 4, pp. 267–274, 2011.[2] G. D. Szarka, B. H., “Review of power conditioning for kinetic energy

    harvesting systems,” Trans. Power Electron., vol. 27, no. 2, pp. 803–815,2012.

    [3] G. D. Szarka, P. P. Proynov, B. H. Stark, S. G. Burrow, and N. McNeill,“Experimental investigation of inductorless, single-stage boost rectifica-tion for sub-mW electromagnetic energy harvesters,” in Proc. Int. Symp. Low Power Electron. Design (ISLPED), Fukuoka, Japan, 2011, pp. 361–366.

    [4] N. G. Stephen, “On energy harvesting from ambient vibration,” J. Sound Vibration, vol. 293, pp. 409–425, 2006.

    [5] S. G. Burrow and L. R. Clare, “Open-loop power conditioning for vibra-tion energy harvesting,”   IEEE Electron. Lett., vol. 45, no. 19, pp. 999–1000, Sep. 2009.

    [6] G. D. Szarka, S. G. Burrow, and B. H. Stark, “Ultra-low power, fully-autonomous boost rectifier for electromagnetic energy harvesters,” vol. 28,

    pp. 3352–3362, Jul. 2013.[7] C. B. Williams, C. Shearwood, M. A. Harradine, P. H. Mellor, T. S. Birch,

    and R. B. Yates, “Development of an electromagnetic micro-generator,” IEE Proc. Circuits Devices Syst., vol. 148, no. 6, pp. 337–342, 2001.

    [8] Y. Kim,C. Naehyuck, W. Yanzhi, andM. Pedram, “Maximumpowertrans-fer tracking for a photovoltaic-supercapacitor energy system,” in   Proc. 2010 ACM/IEEE Int. Symp. Low-Power Electron. Des., Austin, TX, USA,2010, pp. 307–312.

    [9] A. S. Weddell, G. V. Merrett, and B. M. Al-Hashimi, “Ultra low-powerphotovoltaic MPPT technique for indoor and outdoor wireless sensornodes,” in  Proc. Design, Autom. Test Europe, Grenoble, France, Mar.14–18, 2011, pp. 905–908.

    [10] J. Elmes,V.Gaydarzhiev, A. Mensah, K. Rustom, andJ. Shen,“Maximumenergy harvesting control for oscillating energy harvesting systems,” in Proc. IEEE Power Electron. Specialists Conf., Orlando, FL, USA, 2007,pp. 2792–2798.

    [11] T. T. Toh, P. D. Mitcheson, A. S. Holmes, and E. M. Yeatman, “A contin-uously rotating energy harvester with maximum power point tracking,” J. Micromech. Microeng., vol. 18, no. 10, 104008, 2008, doi: 10.1088/0960-1317-18-/10/104008.

    [12] T. Paing, J. Shin,R. Zane, andZ. Popovic,“Resistor emulationapproach tolow-power RF energy harvesting,” IEEE Trans. Power Electron., vol. 23,no. 3, pp. 1494–1501, May 2008.

    [13] G. K. Ottman, H. F. Hofmann,and G. A. Lesieutre,“Optimized piezoelec-tric energy harvesting circuit using step-down converter in discontinuousconduction mode,” IEEE Trans. Power Electron., vol. 18, no. 2, pp. 696–703, Mar. 2003.

    [14] C. K. Lee, P. K. Chan, and S. W. Or, “Loosely power flow control schemefor piezoelectric energy harvesting,” IEEE Electron. Lett., vol. 46, no. 25,pp. 1689–1691, Dec. 2010.

    [15] J. Leicht, D. Maurath, and Y. Manoli, “Autonomous and self-starting effi-cient micro energy harvesting interface with adaptive MPPT, buffer mon-itoring, and voltage stabilization,” in  Proc. ESSCIRC, Bordeaux, France,2012, pp. 101–104.

    [16] D. Maurath, P. F. Becker, D. Spreeman, and Y. Manoli, “Efficient en-ergy harvesting with electromagnetic energy transducers using activelow-voltage rectification and maximum power point tracking,”  IEEE J.

    Solid-State Circ., vol. 47, no. 6, pp. 1–12, Jun. 2012.[17] R. Dayal and L. Parsa, “Low power implementation of maximum energyharvesting scheme for vibration-based electromagnetic microgenerators,”in Proc. IEEE Appl. Power Electron. Conf. Expo., Fort Worth, TX, USA,2011, pp. 1949–1953.

    [18] J. Karki. (2000, Oct.). Active Low-Pass Filter Design [Online]. Available:http://www.science.unitn.it/ ∼bassi/Signal/TInotes/sloa049.pdf 

    [19] Microchip Technology, Inc. (2008). [Online]. Available MCP6031Datasheet: http://ww1.microchip.com/downloads/en/DeviceDoc/22041b.pdf 

    Authors’ photographs and biographies not available at the time of publication.