15 r_bufé new room pressure technology
TRANSCRIPT
AirSystem LabSystem Clean roomLabSystem AirSystem
Cleanroom Technologies
Welcome at
the ACHEMA 2009
Dipl.-Ing Rainer Bufe
AirSystem LabSystem Clean room
2
Founded in: 1958
Employees: 48
Products: Aircontrol
LabControl
Medicine electronic
Consumer electronic
Own research and development
Own production
All products made in Germany
Company details
AirSystem LabSystem Clean room
3Product overview LabSystem - AirSystem
1992 - SMD in line production
1995 - Fume hood monitor
1997 - Fume hood controller(1 st. generation)
1998 - Sash controller
1999 - VAV for supply and exhaust air (AirSystem)
2002 - Clean room controller
2006 - Fume hood controller(5 th. generation)
2008 - Airvolume priorised pressurecontroller VCP (EP-patent)
AirSystem LabSystem Clean room
Typical clean room 4
AirSystem LabSystem Clean room
material lock 5 Pa
changing room5 Pa 35 Pa
overpressure
equipment
clea
n ro
om
clea
n ro
om
clea
n ro
om
grey room
25 Pa
personnel lock 15 Pa
0 Pa
Room pressure and air change rate
Laboratory Clean roomAir change rate 8 times 60 - 600 timesRoom = 150 m3 1.200 m3/h 9.000 – 90.000 m3/h
5
AirSystem LabSystem Clean room
Room pressure with Air Volume Controller
Mechanical CAV
Tolerance ± 15 % (one CAV)
Tolerance ± 22 % (two CAV´s)
Electrically operated CAV/VAV
Tolerance ± 5 % (one CAV/VAV)
Tolerance ± 7,5 % (two CAV´s/VAV´s)35 Pa
overpressure
VAV or CAV
Clean room(+) = overpressure
VAV or CAV
Room height = 3,06 mRoom volume = 150 m3
Supply air 1.500 m3/h Exhaust air 1.300 m3/h
Room leakage200 m3/h
7,00 m
7,00
m
6
AirSystem LabSystem Clean room
7
A µ 3600 ∆p = ▬▬ ▬▬▬▬▬▬▬
Vρ
2
2
General views
Bernoulli - formula
ρ = air density 1,2 kg/m3
µ = constant value 0,72
AirSystem LabSystem Clean room
8
A µ 3600 ∆p = ▬▬ ▬▬▬▬▬▬▬
Vρ
2
2
Detailed view (with tolerances)
VSUPPLY – VEXHAUST = VDIFF
1500 m3/h - 1300 m3/h = 200 m3/h
=> 35 Pa with 0,01 m2 room leakage
With tolerances ± 7,5 %
1500 m3/h ± 7,5 % = ± 112,5 m3/h
VMAXDIFF = 200 + 112,5 = 312,5 m3/h
VMINDIFF = 200 - 112,5 = 87,5 m3/h
∆pMIN=6,8 Pa∆pMAX=87,2 Pa
pressure range 6,8…35…87,2 !!!
=> not acceptable!!!
AirSystem LabSystem Clean room
Room pressure with VAV - Controller
RESULT: Room pressure with CAV/VAV - ControllerEven with very low tolerances not suitable in airtight rooms (small room leakage)
air volume, room volume and room leakagehave strong impact on differential pressure
SOLUTION: Room pressure with pressure controller CRPBetter than CAV/VAV - Controller but even notsatisfying in airtight rooms (very small roomleakage)
be careful with high air volume and very small roomleakage
9
AirSystem LabSystem Clean room
Room pressure with CRP - Controller
Floor(-) = underpressure
Air lock(+) = overpressure
Roo
mex
haus
t air
(con
stan
t)
CAV
Roon
exha
ust a
ir(c
onst
ant)
Roomsupply air(variable)
CRP
- +dP
24V AC
Roomsupply air(variable)
CRP
- +dP
24V AC
Roomsupply air(variable)
CRP
-
+dP
24V AC
CAV
CAV
Roo
mex
haus
t air
(con
stan
t)
Room 1(+) = operpressure
against air lock
Room 2(+++) = overpressure
against floor
instable control
Very important:use common reference - --
---point for measuring the --------underpressure (-)
reference point must be --------nonventilated
use actuators without -------hystersis (instaed of -.-analogue input direct ------------drive actuator)
use actuators with high --- ----resolution (< 0,5 ° => 0,5 %)
10
AirSystem LabSystem Clean room
Room pressure with CRP - Controller
35 Pa overpressure
VAV or CAV
Clean room(+) = overpressure
CRP
Room height = 3,06 mRoom volume = 150 m3
Supply air1.500 m3/h
Exhaust air 1.300 m3/h
Room leakage200 m3/h
7,00 m
7,00
m
- +dP
Electrically operated CAV/VAV and CRP
Tolerance ± 5 % (one CAV/VAV)
Tolerance ± 1,11 % with actuatorresolution 1 ° (usual value)
Tolerance ± 0,5 % with CRP and directdrive actuator from SCHNEIDER (resolution < 0,5 ° and non hysteresis)
11
AirSystem LabSystem Clean room
12
A µ 3600 ∆p = ▬▬ ▬▬▬▬▬▬▬
Vρ
2
2
Room pressure controller CRP
=> 35 Pa with 0,01 m2 room leakage
With tolerances ± 0,5 % (CRP-resolution)
1500 m3/h ± 0,5 % = ± 7,5 m3/h
VMAXDIFF = 200 + 7,5 = 207,5 m3/h
VMINDIFF = 200 - 7,5 = 192,5 m3/h
∆pMIN=33,1 Pa∆pMAX=38,4 Pa
pressure range 33,1…35…38,4
=> acceptable with given room --------leakage ≥ 0,01 m2
AirSystem LabSystem Clean room
Room pressure with VAV - Controller
RESULT: Room pressure with pressure controller CRPAcceptable with high resolution actuator and non hysteresis actuator in airtight rooms(room leakage > 0,01 m2)
not suitable in airtight rooms(room leakage < 0,01 m2)
SOLUTION: Air volume priorised constant room pressurecontroller VCP (European-Patent)
Highest accuracy in the market with electricalcontroller
Very stable control even in airtight rooms withroom leakage < 0,001 m2
equals to 1mm clearance between door frame and door leave!!
13
AirSystem LabSystem Clean room
VCP-L
Floor(-) = underpressure
Clean room(+) = overpressure
VAV-L
-+ dP
24V AC
Building management system
R
LON-NETWORK, FTT-10A
room pressure
room air volume
Volume priorised pressure controller VCP
35 Pa overpressure
Electrically operated CAV/VAV and VCP
Tolerance ± 5 % (one CAV/VAV)
Tolerance ± 7,5 % (two CAV/VAV)
Tolerance ± 1,11 % with actuatorresolution 1 ° (usual value)
Tolerance ± 0,5 % with VCP and directdrive actuator from SCHNEIDER (resolution < 0,5 ° and non hysteresis)1500 m3/h
1500 m3/h± 7,5 %
14
± 0,5 %±112,5 m3/h
AirSystem LabSystem Clean room
15
=> 35 Pa with 0,001 m2 room leakage => Air volume VDIFFERENTIAL = 20 m3/h
With tolerances:
1. Air volume: 1500 m3/h ± 7,5 % = ± 112,5 m3/h
2. Room pressure: ± 112,5 m3/h ± 0,5 % (VCP-resolution) = ± 0,5625 m3/h
35 Pa => VDIFFERENTIAL = 20 m3/h
VMAXDIFF = 20 + 0,5625 = 20,56 m3/h
VMINDIFF = 20 – 0,5625 = 19,44 m3/h
∆pMIN=33,75 Pa ∆pMAX=37,75 Pa
pressure range 33,75…35…37,75
=> very good result with given ------ room leakage 0,001 m2 or ----------even smaller
Volume priorised pressure controller VCP
AirSystem LabSystem Clean room
Volume priorised pressure controller VCP
Very important:use common reference - --
---point for measuring the --------underpressure (-)
reference point must be --------nonventilated
use VCP for airtight rooms--- with small room leakage
use actuators with high --- ----resolution (< 0,5 ° => 0,5 %)
16
AirSystem LabSystem Clean room
17
Advantages of the VCP and room pressure control via bypass:very high resolution of the actuator in the bypass. Controlling of the roompressure via actuator with Direct-Drive-Modus (no hysteresis, resolution < 0,5 °)
avoids oscillating of the system
multitasking system with one common microprocessor unit and internalcommunicating between air volume control device and pressure controldevice
max. allowed range of ± 3 Pa always possible, even over different pressure steps
suitable for controlling of safety laboratory class S1-S4 as well as clean room class A-D
for controlling laboratory class S4 it is mandatory for safety reasonsto use redundant systems
Volume priorised pressure controller VCP
AirSystem LabSystem Clean room
18
More advantages of the VCP:sudden loss of room pressure (open of door or window) will berecongised and the damper gets „freezed“ for a certain time (max. 20 s)
no door contacts needed
very precise and stable room pressure control system
room pressure damper (bypass) always between 20…80 % => good control position
complete parametrising via service module SVM100 or PC-softwarePC2500
suitable for safety laboratory with very high airtight doors and rooms(e.g. animal laboratory)
suitable for supply or exhaust air systems
BMS controlling via network. LON, BACnet or Modbus available
Volume priorised pressure controller VCP
AirSystem LabSystem Clean room
Reference project with VCP 19
Reference project: Paul-Ehrlich-Institut, Langen – safety laboratoryclass S3, animal laboratory for BSE-research
AirSystem LabSystem Clean room
20
Reference project: Paul-Ehrlich-Institut, Langen – safety laboratory classS3, animal laboratory for BSE-research
Room specification:- Room volume 48,7 m³- Room air change rate 8/12/16 h-1 (Night-Day-Cleaning)- Exhaust air volume 390-585-780 m³/h- Pressure control value - 40 Pa - External differential pressure transmitter with 2------ analogue outputs (controlling and monitoring via LON-network to Honeywell-BMS)
Reference project with VCP
AirSystem LabSystem Clean room
21VCP- drawing with additional manual damper
AirSystem LabSystem Clean room
Remote maintenance and diagnosis via Internet/Intranet
Easy administrating of error- and maintenance reports
Building management systemIntranet Infranet Internet
22
AirSystem LabSystem Clean room
23LabSystem – Reference list
Chemie/Pharmacie■ AVENTIS AG
■ BASF AG
■ BAYER AG
■ BOEHRINGER Ingelheim
■ BYK GULDEN
■ CLARIANT
■ HOFFMANN LA ROCHE AG
■ GOEDECKE / PFIZER
■ GRÜNENTHAL
■ NOVARTIS AG
■ SCHERING AG
Universities■ Freiburg■ Potsdam/Golm
■ Regensburg
■ Tübingen
■ Wuppertal
■ Zürich
Instituts■ MAX-PLANCK-INSTITUT
■ FRAUNHOFER-INSTITUT
■ ADLERSHOF … and more
AirSystem LabSystem Clean room
24Our main customers - Fume cupboard maker
AirSystem LabSystem Clean room
25Our main customers – projects
AirSystem LabSystem Clean room
26
Thank you for your attention
More information www.schneider-elektronik.de