15a_setting of protection
TRANSCRIPT
© A
BB
Gro
up -
1 -
May
3, 2
023
Setting of Protectiono/c & e/f relays
Protection Application Handbook
© A
BB
Gro
up -
2 -
May
3, 2
023
Setting of Protection
© A
BB
Gro
up -
3 -
May
3, 2
023
Setting of ProtectionPhase Overcurrent Protections Selectivity
Fault current
Time
t
© A
BB
Gro
up -
4 -
May
3, 2
023
Setting of ProtectionPhase Overcurrent Protections Pick-up and reset
The relay does not reset
t
I
I stI reset
© A
BB
Gro
up -
5 -
May
3, 2
023
Setting of ProtectionOvercurrent relays Current selectivity
Possible when impedance in between is substantial
Time selectivity Time starts adding and trip times will be very long
© A
BB
Gro
up -
6 -
May
3, 2
023
Setting of ProtectionShort circuit protection
Current setting shall be Higher than maximum load current Shall be lower than minimum fault current Margin to load to be set considering reset ratio
© A
BB
Gro
up -
7 -
May
3, 2
023
Setting of ProtectionInstantaneous stage for transformer
Setting shall be Higher than maximum inrush current
Should not reach > 80% of transformer
Complement to diff relay and buchholz
protection
© A
BB
Gro
up -
8 -
May
3, 2
023
Setting of ProtectionDirectional short circuit protection
Directional current relay shall have 60 degrees
angle lagging
© A
BB
Gro
up -
9 -
May
3, 2
023
Setting of ProtectionMargin to equipment capacity
Tripping should be before reaching thermal capacity of the object
© A
BB
Gro
up -
10 -
May
3, 2
023
Setting of ProtectionEarth fault relays in solidly earthed systems
© A
BB
Gro
up -
11 -
May
3, 2
023
Setting of ProtectionTime setting of inverse type relays
Margin 100-150 ms for short circuit protection 150-200 ms for earth fault relays
© A
BB
Gro
up -
12 -
May
3, 2
023
Setting of ProtectionNetwork for selectivity plan
© A
BB
Gro
up -
13 -
May
3, 2
023
Setting of ProtectionInformation required for selectivity plan
System diagram Maximum short circuit currents Minimum short circuit currents Maximum service currents Inrush currents for transformers, motors Relay characteristics Breaker characteristics
© A
BB
Gro
up -
14 -
May
3, 2
023
Setting of Protection
© A
BB
Gro
up -
15 -
May
3, 2
023
Setting of ProtectionPhase and Ground over current protections The phase over current protection offers both circuit
local back-up protection and remote back-up protection for multi phase faults. They also offer protection for many faults involving ground if fault current is high enough to allow relay operation.
To cater to low current ground faults as a result of high ground fault resistance the ground over current protections are applied. They might also be applied, as main protection for high resistance faults where main protection does not offer required coverage.
© A
BB
Gro
up -
16 -
May
3, 2
023
Setting of ProtectionPhase over current protections Settings
The protection must not operate for highest load current during both normal and abnormal power system operation.
The protection must operate for multiphase faults on the entire circuit under minimum plant conditions i.e. lowest fault current.
The protection should not operate before the main protection of the protected circuit
The protection must not operate before the circuit local back-up protection clears a fault in an adjacent circuit.
© A
BB
Gro
up -
17 -
May
3, 2
023
Setting of ProtectionGround over current protections Settings
The ground over current threshold should be set to ensure detection of all ground faults, but above any continuous residual current under normal system operation. Continuous residual current may arise because of
Unbalanced series impedances of un transposed transmission circuits
Unbalanced shunt capacitance of transmission circuits Third harmonic current circulation.
© A
BB
Gro
up -
18 -
May
3, 2
023
Setting of ProtectionDirectional Over current relays-radial feeders
© A
BB
Gro
up -
19 -
May
3, 2
023
Setting of ProtectionDirectional over current relays
© A
BB
Gro
up -
20 -
May
3, 2
023
Setting of Protection