15a_setting of protection

20
ABB Group - 1 - ug 29, 2022 Setting of Protection o/c & e/f relays Protection Application Handbook

Upload: devbsl

Post on 13-May-2017

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 15a_Setting of Protection

© A

BB

Gro

up -

1 -

May

3, 2

023

Setting of Protectiono/c & e/f relays

Protection Application Handbook

Page 2: 15a_Setting of Protection

© A

BB

Gro

up -

2 -

May

3, 2

023

Setting of Protection

Page 3: 15a_Setting of Protection

© A

BB

Gro

up -

3 -

May

3, 2

023

Setting of ProtectionPhase Overcurrent Protections Selectivity

Fault current

Time

t

Page 4: 15a_Setting of Protection

© A

BB

Gro

up -

4 -

May

3, 2

023

Setting of ProtectionPhase Overcurrent Protections Pick-up and reset

The relay does not reset

t

I

I stI reset

Page 5: 15a_Setting of Protection

© A

BB

Gro

up -

5 -

May

3, 2

023

Setting of ProtectionOvercurrent relays Current selectivity

Possible when impedance in between is substantial

Time selectivity Time starts adding and trip times will be very long

Page 6: 15a_Setting of Protection

© A

BB

Gro

up -

6 -

May

3, 2

023

Setting of ProtectionShort circuit protection

Current setting shall be Higher than maximum load current Shall be lower than minimum fault current Margin to load to be set considering reset ratio

Page 7: 15a_Setting of Protection

© A

BB

Gro

up -

7 -

May

3, 2

023

Setting of ProtectionInstantaneous stage for transformer

Setting shall be Higher than maximum inrush current

Should not reach > 80% of transformer

Complement to diff relay and buchholz

protection

Page 8: 15a_Setting of Protection

© A

BB

Gro

up -

8 -

May

3, 2

023

Setting of ProtectionDirectional short circuit protection

Directional current relay shall have 60 degrees

angle lagging

Page 9: 15a_Setting of Protection

© A

BB

Gro

up -

9 -

May

3, 2

023

Setting of ProtectionMargin to equipment capacity

Tripping should be before reaching thermal capacity of the object

Page 10: 15a_Setting of Protection

© A

BB

Gro

up -

10 -

May

3, 2

023

Setting of ProtectionEarth fault relays in solidly earthed systems

Page 11: 15a_Setting of Protection

© A

BB

Gro

up -

11 -

May

3, 2

023

Setting of ProtectionTime setting of inverse type relays

Margin 100-150 ms for short circuit protection 150-200 ms for earth fault relays

Page 12: 15a_Setting of Protection

© A

BB

Gro

up -

12 -

May

3, 2

023

Setting of ProtectionNetwork for selectivity plan

Page 13: 15a_Setting of Protection

© A

BB

Gro

up -

13 -

May

3, 2

023

Setting of ProtectionInformation required for selectivity plan

System diagram Maximum short circuit currents Minimum short circuit currents Maximum service currents Inrush currents for transformers, motors Relay characteristics Breaker characteristics

Page 14: 15a_Setting of Protection

© A

BB

Gro

up -

14 -

May

3, 2

023

Setting of Protection

Page 15: 15a_Setting of Protection

© A

BB

Gro

up -

15 -

May

3, 2

023

Setting of ProtectionPhase and Ground over current protections   The phase over current protection offers both circuit

local back-up protection and remote back-up protection for multi phase faults. They also offer protection for many faults involving ground if fault current is high enough to allow relay operation. 

To cater to low current ground faults as a result of high ground fault resistance the ground over current protections are applied. They might also be applied, as main protection for high resistance faults where main protection does not offer required coverage.

Page 16: 15a_Setting of Protection

© A

BB

Gro

up -

16 -

May

3, 2

023

Setting of ProtectionPhase over current protections   Settings

The protection must not operate for highest load current during both normal and abnormal power system operation.

The protection must operate for multiphase faults on the entire circuit under minimum plant conditions i.e. lowest fault current.

The protection should not operate before the main protection of the protected circuit

The protection must not operate before the circuit local back-up protection clears a fault in an adjacent circuit.

     

              

Page 17: 15a_Setting of Protection

© A

BB

Gro

up -

17 -

May

3, 2

023

Setting of ProtectionGround over current protections Settings

The ground over current threshold should be set to ensure detection of all ground faults, but above any continuous residual current under normal system operation. Continuous residual current may arise because of

Unbalanced series impedances of un transposed transmission circuits

Unbalanced shunt capacitance of transmission circuits Third harmonic current circulation.

                          

Page 18: 15a_Setting of Protection

© A

BB

Gro

up -

18 -

May

3, 2

023

Setting of ProtectionDirectional Over current relays-radial feeders

Page 19: 15a_Setting of Protection

© A

BB

Gro

up -

19 -

May

3, 2

023

Setting of ProtectionDirectional over current relays

Page 20: 15a_Setting of Protection

© A

BB

Gro

up -

20 -

May

3, 2

023

Setting of Protection