    Synchrophasors:

    Improving Reliability &Situational Awareness

    Research & TechnologyManagement

    Clifton Black

  • 7/27/2019 163359248 Synchrophasors CRB

    2/23

    Outline

    What are PMUs?

    PMUs - Concept & Operation

    The Need for PMUs

    Synchrophasor Applications

    Southern Company PMU Activities

    PMUs Activities in North America

  • 7/27/2019 163359248 Synchrophasors CRB

    3/23

    What are PMUs?

    PMUs provide high resolution synchronized

    measurements of phasor voltages and currents

    They are placed at key locations like power plants

    and major substations

  • 7/27/2019 163359248 Synchrophasors CRB

    4/23

    Concept & Operation

    PhasorsPhase Angles have a reference

  • 7/27/2019 163359248 Synchrophasors CRB

    5/23

    Concept & Operation contd.

    ATTRIBUTE SCADA PHASOR

    Measurement Analog Digital

    Resolution 2-4 sam./sec. 60 sam./sec.

    Observability Steady State Transient

    Phase angle No Yes

    Measured |V|, MW, MVAR |V|,, MW,MVAR, |21|

    Synchronized No Yes

  • 7/27/2019 163359248 Synchrophasors CRB

    6/23

    Concept & Operation contd.

    Time Synchronization

    Time-skewed measurements introduce errors

    Average Angle Difference ~ 10

    Average Angle Difference ~ 5

  • 7/27/2019 163359248 Synchrophasors CRB

    7/23

    The Need for PMUs

    Investigation of August 14, 2003 Blackout revealed

    Lack of Wide Area Visibility

    Lack of Time Synchronized Data Inability to Monitor System Dynamic

    Behavior in Real-time

    http://www.google.com/imgres?imgurl=http://www.istockphoto.com/file_thumbview_approve/4055071/2/istockphoto_4055071-magnifying-glass-footprint.jpg&imgrefurl=http://www.istockphoto.com/stock-illustration-4055071-magnifying-glass-footprint.php&usg=__oXo64qX3IeRtP_qQVH4qtXHHEqk=&h=285&w=380&sz=19&hl=en&start=34&zoom=1&um=1&itbs=1&tbnid=9nCpgSfYgVP4eM:&tbnh=92&tbnw=123&prev=/images?q=magnifying+glass&start=20&um=1&hl=en&safe=active&sa=N&ndsp=20&tbs=isch:1,ic:gray&ei=ITE-Tb6cI8rGgAfBmrCqCA
  • 7/27/2019 163359248 Synchrophasors CRB

    8/23

    The Need for PMUs Contd.

    Wide-Area and Sub-SCADA

    Visibility

    Time Synchronization allows

    Dynamics not visible in

    SCADA

    Angular or Dynamic warning

    signs are usually present

    before major events

    Recent Major Blackouts

    August 14 Angular Separation

    -170

    -160

    -150

    -140

    -130

    -120

    -110

    -100

    -90

    -80

    -70

    -60-50

    -40

    -30

    -20

    -10

    0

    15:05:00 15:32:00 15:44:00 15:51:00 16:05:00 16:06:01 16:09:05 16:10:38

    Time (EDT)

    RelativePhaseAngle

    Cleveland West MI

    Normal Angle ~ -25

    Reference:

    Browns Ferry

    -170

    -160

    -150

    -140

    -130

    -120

    -110

    -100

    -90

    -80

    -70

    -60-50

    -40

    -30

    -20

    -10

    0

    15:05:00 15:32:00 15:44:00 15:51:00 16:05:00 16:06:01 16:09:05 16:10:38

    Time (EDT)

    RelativePhaseAngle

    Cleveland West MI

    Normal Angle ~ -25

    Reference:

    Browns Ferry

    August 14thAngular Separation

    12 Degrees

    25 Degrees

    45 Degrees

    115 Degrees

  • 7/27/2019 163359248 Synchrophasors CRB

    9/23

    The Need for PMUs Contd.

    PMUs allow us toseethe dynamic behavior

    of the grid which

    models sometimes

    incorrectly predict.

    Post Disturbance Analysis of August 10, 1996 Blackout

  • 7/27/2019 163359248 Synchrophasors CRB

    10/23

    Synchrophasor Applications

    Wide-Area Visualization &Monitoring

    Frequency Stability Monitoring

    & Trending

    Voltage Monitoring & Trending State Estimation

    Oscillation Monitoring

    Resource Integration

    Equipment Failure Detection

    Real-time Applications

    Power System Model Verification Event Analysis & Reconstruction

    Equipment Failure Detection

    Fault Location

    Baselining Power SystemPerformance

    Load Characterization

    Off-line Applications

    Synchrophasors facilitates improvement in Situational Awareness,

    Modeling Accuracy & System Reliability

    http://rds.yahoo.com/_ylt=A0PDoYBEZnFNm1QALXiJzbkF;_ylu=X3oDMTBqMjRpazg1BHBvcwMxMARzZWMDc3IEdnRpZAM-/SIG=1ibmo391j/EXP=1299306180/**http:/images.search.yahoo.com/images/view?back=http://images.search.yahoo.com/search/images?p=dollar&ei=UTF-8&vm=r&fr=yfp-t-946&w=500&h=500&imgurl=www.cksinfo.com/clipart/money/symbols/dollar/money.png&rurl=http://www.cksinfo.com/money/symbols/dollar/index.html&size=39KB&name=free+picture+of+...&p=dollar&oid=973395c5cff3a2abd7212bebba14479d&fr2=&no=10&tt=6100000&sigr=11mil5gkq&sigi=11mhdv3k0&sigb=12gjo6tem&.crumb=NH5KeOCZOy8
  • 7/27/2019 163359248 Synchrophasors CRB

    11/23

    Synchrophasor Applications contd.

    CAISO, BPA, AEP incorporating phasor data into State

    Estimation tools

    Entergy used phasor data to manage system separation,islanding and restoration during Gustav (2008)

    CAISO & ERCOT will be using phasor data to monitor andintegrate intermittent generation

    SCE using phasor data for automated control of SVC forreactive power support

    Phasor systems being used for WAMS in North America,

    Quebec, Brazil, China and Europe

    A Few of the Current Implementations

  • 7/27/2019 163359248 Synchrophasors CRB

    12/23

    Southern Company PMU Locations

    Plant Miller

    Plant Farley

    Plant Daniel

    Plant Bowen

    Norcross

    South Hall

    Plant Hatch

    West

    McIntosh

    Thallman

    Plant Barry

  • 7/27/2019 163359248 Synchrophasors CRB

    13/23

    Southern Companys PMU Architecture

    HATCH

    VggVee

    Vd

    d

    Vb

    b

    ViiDANIEL

    SOUTH HALL

    BOWEN

    MILLER

    Phasor Data Concentrator

    (PDC) - Local

    Regional PDC

    Vff

    NORCROSS

    Vcc

    BARRY

    Vaa

    FARLEY

    THALMANN

    Vjj

    WEST MCINTOSH

    Vhh

    Local

    Historian

    Local

    Applications

    Local PDC and Historian facilitates flexibility, security and data accessibility

  • 7/27/2019 163359248 Synchrophasors CRB

    14/23

    Current Use of PMU data

    Wide Area Monitoring and

    Situational Awareness

    Research

    Post Event Analysis &

    Model Validation

    Transmission Planning

  • 7/27/2019 163359248 Synchrophasors CRB

    15/23

    Example of Wide-area Monitoring Tool

    GAUGES: Quantify the worst performing metric

    LOCATION INDICATORS: Provide information

    about specific locations w.r.t. the metric

    TRAFFIC LIGHTS: Provide status of specific metrics

    across all locations

    Real-time Dynamics Monitoring System (RTDMS)

  • 7/27/2019 163359248 Synchrophasors CRB

    16/23

    Synchrophasor Research

    Project with PNNL:Multi-Variable Statistical Analysis

    Identifying atypical events and precursors to proactivelymanage the grid

    AREVA PMU Project:Impact of PMU data on StateEstimation & State Estimation Metrics

    NEETRAC Project:Next Generation PMUs/Evaluation

    CEATI:Prediction of Power System Instability based on

    PMU data: Utilizing the Region of Stability Existence(ROSE) Approach.

    Provide Operators with fast and accurate solutions inorder to predict system instability and prevent wide-

    spread blackouts using PMU data.

  • 7/27/2019 163359248 Synchrophasors CRB

    17/23

    Demonstration Project w/ GaTech

    Distributed State Estimator, Generator Parameter Estimation

    and Stability Monitoring

    Distributed State Estimator for two substation subsystem

    Develop Generator parameter Estimator for a generating unit

    Develop transient stability monitoring system for generating plant

  • 7/27/2019 163359248 Synchrophasors CRB

    18/23

    PMUs in North America

  • 7/27/2019 163359248 Synchrophasors CRB

    19/23

    PMU Activities in North America

    North America

    North American Synchrophasor Initiative (NASPI) www.naspi.org

    SPDC evolving to regional PDCs

    PhasorGatewayCommunications & Traffic ManagementInfrastructure

    Tremendous boost from ARRA funding

    NASPI Structure

    http://www.naspi.org/http://www.naspi.org/
  • 7/27/2019 163359248 Synchrophasors CRB

    20/23

    Where Are We Going?

    1. Angle/Freq. Monitoring

    12. Post-mortem Analysis

    2. Voltage Stability Monitoring

    5. State Estimation (Improv.)

    13. Model Benchmarking;

    Parameter Estimation

    16. DG/IPP Applications

    11. Power system restoration

    10. Congestion management

    14. Model Benchmarking;

    Parameter Estimation

    15. Planned Power SystemSeparation

    6. State Estimation

    (Boundary Conditions)

    7. State Measurement (linear)

    4. Real-Time Control

    9. Adaptive Protection

    8. WA Stabilization (WA-PSS)

    Necessary

    Additional Benefits

    More Investigation

    Role of PMUs

    1-3 Years 3-5 Years > 5 Years

    Recommended Industry Deployment Roadmap

    3. Thermal Overload Monitoring

    CIEE Report

  • 7/27/2019 163359248 Synchrophasors CRB

    21/23

    SGIG PMU ProjectsProject Lead # of PMU

    (Stations)

    Key Applications

    ISO New England 30 Real-time situational awareness, Congestion management

    New York ISO 39 Real-time situational awareness, Voltage monitoring and control

    Communications system

    PJM Interconnection 80+ Real-time situational awareness including trending, Oscillation detection,

    Islanding detection

    Midwest ISO 150+ Real-time situational awareness, Voltage monitoring

    Renewable integration, Congestion management, State estimation, Oscillation

    monitoring, EMS alarms

    Western ElectricCoordinating Council 250+ Wide-area real-time situational awareness and visualization, Alarming, Oscillationmonitoring, Voltage monitoring, Renewable integration, Congestion

    management, Automatic controls, Power system performance analysis, System-

    wide model validation, Post-event analysis

    Entergy Services 18 Increase grid monitoring, train and educate grid operators and engineers on

    phasor technology

    Duke Energy 102 Wide-area real-time situational awareness, enhanced state estimator and

    Renewables integration

  • 7/27/2019 163359248 Synchrophasors CRB

    22/23

    What Do We Need Now?

    Demarcation where currents tools end and PMU tools begin

    Development and Deployment of Applications

    Practical tools for Operators

    Actionable Information

    Killer Apps

    Knowledge/Experience from SGIG implementations

    More Research

  • 7/27/2019 163359248 Synchrophasors CRB

    23/23

    Questions