Publication 1797-IN015G-EN-P - August 2017 Installation Instructions ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Catalog Numbers 1797-RPA and 1797-RPFM Contents For Information About See Page Important User Information 2 About the ControlNet Ex Fiber Repeater Hub 4 DIN-Rail Mount the 1797-RPA and -RPFM 5 Installation in Zone 1 for CENELEC 8 Installation in Division 1/Zone 1 for UL, C-UL and FM 8 Electrostatic Charge 9 European Community (EC) Directive Compliance 9 Inputs/Outputs 12 Wire the Modules 13 Describing the ControlNet Ex System Diagram 15 Certification Specific ControlNet Ex System Diagrams 17 CENELEC Installation Label 18 CENELEC ControlNet Ex System Diagram 19 UL, C-UL ControlNet Ex System Diagram 20 FM ControlNet Ex System Diagram 22 Module Indicators 24 About the Mounting Kit 26 Repair 26 Specifications - 1797-RPA 27 Specifications - 1797-RPFM 29 Mounting Dimensions 31

Upload: others

Post on 09-Mar-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

Installation Instructions

ControlNet Ex Modular Repeater Adapter & Fiber Repeater ModuleCatalog Numbers 1797-RPA and 1797-RPFM

Contents

For Information About See PageImportant User Information 2About the ControlNet Ex Fiber Repeater Hub 4DIN-Rail Mount the 1797-RPA and -RPFM 5Installation in Zone 1 for CENELEC 8Installation in Division 1/Zone 1 for UL, C-UL and FM 8Electrostatic Charge 9European Community (EC) Directive Compliance 9Inputs/Outputs 12Wire the Modules 13Describing the ControlNet Ex System Diagram 15Certification Specific ControlNet Ex System Diagrams 17CENELEC Installation Label 18CENELEC ControlNet Ex System Diagram 19UL, C-UL ControlNet Ex System Diagram 20FM ControlNet Ex System Diagram 22Module Indicators 24About the Mounting Kit 26Repair 26Specifications - 1797-RPA 27Specifications - 1797-RPFM 29Mounting Dimensions 31

Publication 1797-IN015G-EN-P - August 2017

Page 2: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

2 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.Throughout this manual we use notes to make you aware of safety considerations.

WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be present.

BURN HAZARD Labels may be located on or inside the equipment to alert people that surfaces may be dangerous temperatures.

Publication 1797-IN015G-EN-P - August 2017

Page 3: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 3

ATTENTION Environment and Enclosure

This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

1 32 4

+V +V-V -V

1797-RPA

PWR

REPEATERADAPTER

COMMSTATUS

MODULESTATUS

41163

Repeater Backplane Connector

Module Locking Tab Power and Common Connections

Indicators

Backplane Connector Cover

1797-RPA

Label Here

Do not remove unless connecting to 1797-RPFM.

ControlNet Ex Tap Drop BNC Connector With Insulator Boot

Publication 1797-IN015G-EN-P - August 2017

Page 4: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

About the ControlNet Ex Fiber Repeater HubUse the repeater adapter (1797-RPA) and the fiber module (1797-RPFM) together to form a repeater hub within the hazardous area to extend the length of the ControlNet Ex segments to interlink systems all operating within the area.

The 1797-RPA repeater adapter, configured with at least one repeater adapter, functions as the intelligent starter block for a multiport repeater. The 1797-RPFM is a nonintelligent fiber-to-backplane conversion device, converting glass-fiber infrared LED media signals to backplane signals for use by the 1797-RPA.

A maximum of two 1797-RPFM modules may be used with one 1797-RPA adapter.

1797-RPFM

Recv XmitRecv Xmit

Chan 1 Chan 2

41267

Repeater Backplane Connector

Module Locking Tab

Backplane Connector Cover

1797-RPFM

Label Here

Do not remove unless connecting to 1797-RPFM.

Publication 1797-IN015G-EN-P - August 2017

Page 5: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 5

DIN-Rail Mount the 1797-RPA and -RPFMRefer to Mounting Dimensions on page 31. For panel mounting information,

see publication 1794-5.13.

1. Position the module on a 35 x 7.5 mm DIN rail (A-B part number 199-DR1) at approximately a 30o angle.

2. Hook the lip on the rear of the adapter onto the top of the DIN rail, and rotate the module onto the rail.

ATTENTION This product is grounded through the DIN rail to the dedicated intrinsic safety ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (such as aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.

ATTENTION The DIN rail or mounting bracket must be appropriately connected to the dedicated intrinsic safety ground.

41167

41166

Publication 1797-IN015G-EN-P - August 2017

Page 6: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

6 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

3. Press the adapter down onto the DIN rail until flush.

The locking tab should snap into position and lock the module to the DIN rail.

4. If the adapter does not snap into position, use a screwdriver or similar device to move the locking tab down while pressing the module flush onto the DIN rail.

Release the locking tab to lock the module in place. If necessary, push up on the locking tab to lock.

5. Remove the adapter backplane connector cover.

6. Follow steps 1 to 4 to attach fiber modules to the DIN rail.

7. Once attached to the DIN rail, slide fiber modules to the left to mate with the adapter.

ATTENTION Make certain that the adapter and fiber modules are secured together with DIN rail anchors. Failure to do so may result in the loss of communications, cause damage to the modules, or both.

41168

Publication 1797-IN015G-EN-P - August 2017

Page 7: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 7

8. Make sure the last fiber module has its backplane connector cover in place.

9. Connect the adapter wiring as shown below in the Wiring section.

IMPORTANT A DIN-rail end anchor (A-B part number 1492-EA35) must be used on the left side of the adapter and on the right side of the fiber module to keep the units from moving.

IMPORTANT You can only attach two media modules to the repeater adapter. If you exceed the module limit, you may cause damage to the adapter or fiber modules and void the IS certification.

41169

Publication 1797-IN015G-EN-P - August 2017

Page 8: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

8 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

Installation in Zone 1 for CENELECModules must not be exposed to the environment. Provide a suitable metal enclosure. A label with this system marking must be attached near the main components of the system. If the system is installed in a cabinet, this label must be fixed inside the cabinet.

Installation in Division 1/Zone 1 for UL, C-UL and FMThis adapter must not be exposed to the environment. Provide a suitable metal enclosure. This adapter has a protection factor of IP20.

WARNING Modules cannot be used in an intrinsically safe environment after they have been exposed to nonintrinsically safe signals.

The fiber optic adapter type 1797-RPFM may be used in combination with the ControlNet adapter type 1797-RPA.

WARNING This adapter cannot be used in an intrinsically safe environment after it has been exposed to nonintrinsically safe signals.

0102

ControlNet Ex System

Allen-Bradley

Attention!Avoid electrostatic charging!

-200C <= Ambient Temperature <= +700C

1 Allen-Bradley Dr.Mayfield Hts., OH USA

DMT 99 ATEX E 065 XII (1)2G Ex ia ib IIC

Publication 1797-IN015G-EN-P - August 2017

Page 9: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 9

Make certain that you only connect ControlNet Ex adapters to other intrinsically safe system modules to maintain the integrity of the intrinsically-safe backplane.

Electrostatic ChargeProtect the system against electrostatic charge. Post a sign near this module: WARNING Avoid electrostatic charging.

ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA ELETROSTÁTICA.

For your convenience, a sign that can be cut out is included in this installation instruction.

European Community (EC) Directive ComplianceIf this product has the CE mark it is approved for installation within the European Community or EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

If this product has the CE mark it is approved for installation within the European Community or EEA regions. It has been designed and tested to meet the following directives.

These products are tested to meet the Council Directive 2014/30/EU by applying the following standards:

• EN 61000-6-4:2007, Electromagnetic Compatibility (EMC) - Part 6-4: Generic Standard for Industrial Environments (Class A)

• EN 61000-6-2:2005, Electromagnetic Compatibility (EMC) - Part 6-2: Generic Standards - Immunity for Industrial Environments

• EN 61326-1:2013 (Industrial), Electrical Equipment For Measurement, Control, and Laboratory Use - Industrial EMC Requirements

41307

Publication 1797-IN015G-EN-P - August 2017

Page 10: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

10 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

European Hazardous Location Approval

The following applies to products marked II (1)2 G

• Are Equipment Group II, Equipment Category (1)2, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive 2014/34/EU. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details.

• The type of protection is “Ex ib[ia] IIC T4” according to EN 60079-11.

• Comply to Standards EN 60079-0:2006, EN 60079-11:2007, and EN 60079-26:2004, reference certificate number DMT 99 ATEX E 011 X.

• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are likely to occur occasionally. Such locations correspond to Zone 1 or 2 classification according to ATEX directive 2014/34/EU.

IEC Hazardous Location Approval

The following applies to products with the IECEx certification:

• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are likely to occur only infrequently and for short periods. Such locations correspond to Zone 1 or 2 classification to IEC 60079-0.

• The type of protection is “Ex ib IIC T4” and “Ex ib[ia] IIC T4” according to IEC 60079-11.

• Comply to Standards IEC 60079-0:2004, IEC 60079-11:2006, reference IECEx certificate number IECEx BVS 09.0021X.

Special Conditions for Safe Use:

The fibre optic adapter type 1797-RPFM* can only be use in combination with the ControlNet adapter type 1797-RPA*.

Publication 1797-IN015G-EN-P - August 2017

Page 11: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 11

A warning sign shall be installed in the direct vicinity of this Fibre Optic Hub: “Warning - Avoid electrostatic charging.”.

UL, C-UL Compliance

If this product has the UL/C-UL mark, it has been designed, evaluated, tested, and certified to meet the following standards:

• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III Division 1, Hazardous (Classified) Locations

• UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations

• UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2 Hazardous (Classified) Locations

• UL 61010, UL Standard for Safety Electrical Equipment For Measurement, Control, and Laboratory Use; Part 1: General Requirements

• CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive Equipment for Use in Hazardous Locations

• CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in Class I Hazardous Locations

• CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres, Part 0: General Requirements

• CSA-E79-11-95, Electrical Apparatus for Explosive Gas Atmospheres, Part 11: Intrinsic Safety “i”

• CSA C22.2 No. 14-95, Industrial Control Equipment

FM Compliance

If this product has the FM mark, it has been designed, evaluated, tested, and certified to meet the following standards:

• FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous (Classified) Locations General Requirements

• FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified) Locations

Publication 1797-IN015G-EN-P - August 2017

Page 12: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

12 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

• FM C1. No.3615:1989, Explosionproof Electrical Equipment General Requirements

• FM C1. No.3810:1989, 1995, Electrical and Electronic Test, Measuring and Process Control Equipment

• ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment

Inputs/OutputsDo not apply any nonintrinsically safe signals to the adapter or fiber modules.

When using as an intrinsically safe electrical apparatus according to EN 60079-11, the European directives and regulations must be followed.

41309

1797-RPA

Power Supply

+V

-V

Channel Network Bus

uCuC

Fiber Hub Bus

41310

1797-RPFM

Channel 1

Channel 2

Receiver

Receiver

Transmitter

Transmitter

Bus

Proc

Fiber Hub Bus

Publication 1797-IN015G-EN-P - August 2017

Page 13: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 13

Wire the Modules

1. Connect the ControlNet Ex tap drop cable to the connector after removing the insulator boot.

2. Connect the fiber media to the fiber module by selecting either the left or right set of receive and transmit ports and attaching the receive and transmit fibers, as appropriate.

IMPORTANT The tap drop BNC must have its insulator ring in position when inserted in the adapter BNC connector.

IMPORTANT Make note of which fiber is receive and which is transmit as they must be interchanged at the opposite end.

41170

ControlNet Ex Coax Tap

Insulator Ring Installed

1

.

.

1 2 43

+V -V +V -V

Q UALITY

B-AAllen-Bradley

1797 - RPA

ControlNet ExREPEATER ADAPTERComm

StatusModuleStatus

PWR

.

Recv Xmit Recv Xmit

Chan 2Chan 1

1797 - RPFM Q UALI TY

B-AAllen-Bradley

ControlNet ExFIBER MODULE

MEDIUM RANGE

.

1

.

.

1 2 43

+V -V +V -V

Q UALITY

B-AAllen-Bradley

1797 - RPA

ControlNet ExREPEATER ADAPTERComm

StatusModuleStatus

PWR

.

Recv Xmit Recv Xmit

Chan 2Chan 1

1797 - RPFM Q UALI TY

B-AAllen-Bradley

ControlNet ExFIBER MODULEMEDIUM RANGE

.

ReceiveTransmit

TransmitReceive

41311

Publication 1797-IN015G-EN-P - August 2017

Page 14: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

14 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

3. Apply +V and -V power to the adapter through a removable terminal block from the Ex power supply.

Screw terminals and spring terminals are provided.

4. Strip the +V and -V wires to a length so no bare conductor shows after inserting the wires into position.

5. If you are using the spring terminals of the plug, insert a screwdriver into the slot and carefully pry until the spring clamp opens to accept the wire.

WARNING Do not use any unused terminals on this adapter. Using these terminals as supporting terminals can result in damage to the module and unintended operation of your system.

Make certain that you power this adapter with an intrinsically safe power supply. Do not exceed the values listed in the specifications for this adapter.

Do not remove or replace a module when power is applied. Interruption of the bus can result in unintended operation or machine motion.

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

+V -V +V -V

+V -V +V -V

41297

Publication 1797-IN015G-EN-P - August 2017

Page 15: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 15

Describing the ControlNet Ex System DiagramA maximum of 48 ControlNet Ex nodes may be connected together by 250 m (820 ft) of coax cable and 48 taps. The distance to increases to 1000 m (3280 ft) when you use only 2 taps. See the table below for more information.

The fiber media of the 1797-RPFM can be installed in a hazardous location (Zone 0, 1 or 2; Class I, Zones 0, 1, and 2; Class I, Division 1 and 2; Class II, Division 1 and 2; Class III, Division 1 and 2) to connect two 1797-RPFM modules or they can be installed through different locations into the nonhazardous location to connect the 1797-RPFM with any approved associated apparatus.

All cables and fiber media that are not light blue must be marked as IS using the 1797-EXMK marking kit or other locally approved IS identification or segregation method.

During the installation of the ControlNet Ex system, all metallic parts must be isolated to prevent an earth connection (high voltage withstanding of isolating material must be > 500V ac).

IMPORTANT Make sure all fiber modules are attached and secured prior to applying intrinsically safe power to the adapter. Failure to do so may cause damage to the adapter and modules.

Publication 1797-IN015G-EN-P - August 2017

Page 16: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

16 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

System Diagram Name

Catalog Number

Catalog Name Description

1797-RPA 1797-RPA ControlNet Ex Modular Repeater Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx

1797-RPFM 1797-RPFM ControlNet Ex Fiber Repeater Module, Medium Distance

Allows connection of a maximum of two devices per 1797-RPA and is powered directly by 1797-RPA

1797-ACNR15/B 1797-ACNR15/B Redundant Media ControlNet Ex Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx -each one with two redundant output channels that are connected to different ControlNet Ex networks (coax cables and 1797-TPx)

CNet Ex Tap Trm 1797-TCAP ControlNet Ex Tap (Dummy) Terminator

Represents one ControlNet Ex node and is a simple capacitor (56 pF) with a coax connector

ControlNet Ex Tap

1797-TPx ControlNet Ex Coax Tap

Four types of connections available: S (straight t-tap), R (right angle t-tap), YS (straight y-tap), and YR (right angle y-tap) - a maximum of 48 taps can be connected together by coax trunk cable

CNet Ex Trk Trm 1797-XT ControlNet Ex Trunk Terminator

Simple resistor (75 Ω) with coax connector that must be on each end of the ControlNet Ex coax trunk for termination

Coax Trunk Cable 1786-RG6 Quad-Shield, RG-6 75 Ω Coax Trunk Cable

Maximum (functional) length between 2 1797-TPx is 1000 m (3280 ft) - each 1797-TPx reduces the (functional) coax cable length by 16.3 m (53.4 ft)

None None Standard Coax Trunk Cable BNC Couplers

Different standard cable couplers, such as 90o, 180o.

Publication 1797-IN015G-EN-P - August 2017

Page 17: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 17

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system

diagram.

Certification Specific ControlNet Ex System DiagramsThe following pages include certification specific ControlNet Ex system diagrams and notes pertaining to these diagrams. Select either CENELEC, UL, C-UL, or FM and follow the requirements of that diagram as you configure and install your system.

System Diagram Name Catalog Number Source

1797-RPA 1797-RPA Allen-Bradley

1797-RPFM 1797-RPFM Allen-Bradley

1797-ACNR15 1797-ACNR15 Allen-Bradley

Coax Trunk Cable(1) 1786-RG6 Allen-Bradley

3092A(2) Belden Wire & Cable Co.

3092A with blue jacket Belden Wire & Cable Co.

ControlNet Ex Tap 1797-TPx Allen-Bradley

CNet Ex Trk Trm 1797-XT Allen-Bradley

CNet Ex Tap Trm 1797-TCAP Allen-Bradley

1 In addition to these cable types, the following specification can be followed to allow additional types: Cable Impedance = 75 Ω + 3 Ω Cable Capacitance = <5.94 nF per 100 m Cable Resistance = >9.08 Ω per 100 m Cable Attenuation 0.2 MHz > 0.93 dB/100 m 5 MHz > 1.39 dB/100 m (-20…70 °C) 0.5 MHz > 0.95 dB/100 m 10 MHz > 1.86 dB/100 m

1 MHz > 1.07 dB/100 m 20 MHz > 2.73 dB/100 m 2 MHz > 1.16 dB/100 m 50 MHz > 4.33 dB/100 m

2 Belden Wire & Cable 1189A may be used, but with functional loss of communication distance, nodes, or both.

Publication 1797-IN015G-EN-P - August 2017

Page 18: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

18 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

CENELEC Installation LabelA label with this system marking must be attached near the main components of the system. If the system is installed in a cabinet, this label must be fixed inside the cabinet.

CENELEC 1797-RPA, -RPFM I/O Entity Parameters

Terminals Uo (V) Io (mA) Groups Co (μF) Lo (μH)

Male Bus Connector

5.4 400 IIB/IIC 65 10

0102

ControlNet Ex System

Allen-Bradley

Attention!Avoid electrostatic charging!

-200C <= Ambient Temperature <= +700C

1 Allen-Bradley Dr.Mayfield Hts., OH USA

DMT 99 ATEX E 065 XII (1)2G Ex ia ib IIC

Publication 1797-IN015G-EN-P - August 2017

Page 19: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 19

CENELEC ControlNet Ex System Diagram

1

.

..

..

CNet

Ex

trk tr

m

3067

0CE

Cont

rolN

et E

xta

p

Safe

Are

a

Haz

ardo

us A

rea

Zone

0

Nod

e 1

Cont

rolN

et E

xta

pCo

ntro

lNet

Ex

tap

Cont

rolN

et E

x tap

CNet

Ex

tap

trm

Ci< 6

8 pF

Li

neg

l.

ChB

Uo=5

.4V,

Io

=160

mA,

F -

3>50

0 kH

z

Flex

bus

Uo=5

.4V,

Io=4

00 m

A,Po

=2.1

6 W

,Co

=65

μF,

Lo=1

0 μH

Ch0

fiber

The

Coax

Trun

k Cab

le is

per

mitt

ed to

hav

e a

min

imum

leng

th o

f 1,0

00m

with

onl

y 2 co

nnec

ted

Cont

rolN

et E

x Ta

ps d

ropp

ing

to o

nly

250m

with

the

max

imum

allo

wed

con

nect

ed C

ontro

lNet

Ex T

aps o

f 48.

Nod

e 4

... 4

8N

ode

3

The

Cont

rolN

et E

x Sys

tem

is a

n in

trins

ical

ly sa

fe sy

stem

acc

ordi

ng to

EN

5003

9. W

hen

inst

allin

g th

e sy

stem

, the

ce

rtific

ate

of c

onfo

rmity

and

the

natio

nal i

nsta

llatio

n re

gula

tions

mus

t be

heed

ed. T

he c

ompo

nent

s of t

he

Cont

rolN

et E

x sys

tem

and

the

inte

rcon

nect

ions

are

sho

wn

on th

e in

stal

latio

n dr

awin

g (P

ub. 1

797-

RM00

1).

For t

he tr

ansm

ittal

bet

wee

n th

e sa

fe a

rea

and

the

haza

rdou

s ar

ea o

nly o

ptic

al g

lass

-fibe

rs a

re p

erm

itted

. The

di

amet

er o

f a s

ingl

e gl

ass-

fiber

mus

t be

>6um

. The

pow

er d

ensi

ty o

f the

tran

smitt

er d

iode

mus

t be

<5m

W/m

m2 .

Prot

ect t

he sy

stem

aga

inst

ele

ctro

stat

ic ch

arge

. Pos

t a si

gn n

ear t

he m

ain

com

pone

nts o

f the

syst

em: A

ttent

ion!

Av

oid

elec

trost

atic

cha

rge.

1797

-ACN

R15/

* or

RS

D-GW

-Ex2

.CN

1797

-ACN

R15/

* or

RS

D-GW

-Ex2

.CN

Flex

bus

Uo=5

.4V,

Io=4

00 m

A,Po

=2.1

6 W

,Co

=65

μF,

Lo=1

0 μH

Pow

er S

uppl

yUi

=9.5

V,Ii=

1 A,

Ci=<

120

nF,

Li=n

eglig

ible

ChA

Uo=5

.4V,

Io

=160

mA,

F -

3>50

0 kH

z

Pow

er S

uppl

yUi

=9.5

V,Ii=

1 A,

Ci=<

120

nF,

Li=n

eglig

ible

ChB

Uo=5

.4V,

Io

=160

mA,

F -

3>50

0kHz

ChA

Uo=5

.4V,

Io

=160

mA,

F -

3>50

0 kH

z

75 O

hm

1W

Ci n

egl.

Li n

egl.

The

ambi

ent t

empe

ratu

re ra

nge

of th

e Co

ntro

lNet

Ex

syst

em is

-20

to +

70 o C.

Near

the

mai

n co

mpo

nent

s of

the

syst

em a

pla

te w

ith th

e sy

stem

mar

king

mus

t be

atta

ched

. If

the

syst

em is

inst

alle

d in

a c

abin

et th

e pl

ate

mus

t be

fixed

on

the

insi

de o

f the

cab

inet

doo

r.

*RG6

-CNe

t is

defin

ed a

s:Ca

ble

Impe

danc

e=75

Ohm

+ o

r -3

Ohm

Ca

ble

Capa

cita

nce<

6nF

per 1

00 m

Ca

ble

Resi

stan

ce>9

.08

Ohm

per

100

m

Cabl

e At

tenu

atio

n (-2

0to+

70 o C)

0.2

MHz

> 0

.93

dB/1

00 m

5 M

Hz >

1.3

9 dB

/100

m

0.5

MHz

> 0

.95

dB/1

00 m

10 M

Hz >

1.86

dB/

100

m

1 M

Hz >

1.0

7 dB

/100

m20

MHz

> 2

.73

dB/1

00 m

coax

trun

k ca

ble

coax

trun

k ca

ble

Cabl

e ty

pe 1

189A

, 30

92A,

or 3

092A

Blu

e fro

m m

anuf

actu

rer

Beld

en W

ire o

r typ

e RG

6-CN

et*

CNet

Ex

trk tr

m

75 O

hm

1W

Ci n

egl.

Li n

egl.

Ci <

60

pF

Li <

560

nH

Li <

110

0 uH

Li <

110

0 uH

Nod

e 2

1797

-RPA

/* or

RS

D-CF

A-Ex

.CN

1797

-RPF

M/*

or

RSD-

FC-E

x2.C

N 3k

m17

97-R

PFM

/* o

r RS

D-FC

-Ex2

.CN

3 km

Ch0

fiber

Ch1

fiber

Ch1

fiber

Pow

er S

uppl

yUi

=9.5

V,Ii=

1 A,

Ci=<

120

nF,

Li=ne

glig

ible

Uo=5

.4V,

Io

=201

mA,

F -

3>50

0 kH

z

Haz

ardo

us A

rea

Zone

0

Publication 1797-IN015G-EN-P - August 2017

Page 20: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

20 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

UL, C-UL ControlNet Ex System Diagram

1

. .

1

Haz

ardo

us (C

lass

ified

) Loc

atio

nCl

ass

I, Zo

nes

1 an

d 2,

Gro

ups

IIC, I

IB, I

IACl

ass

I Div

isio

n 1

and

2, G

roup

s A,

B, C

, DCl

ass

II, D

ivis

ion

1 an

d 2,

Gro

ups

E, F,

GCl

ass

III, D

ivis

ion

1 an

d 2CN

et E

x trk

trm

3067

0

Cont

rolN

et E

xta

p

CNet

Ex

trk tr

m

Non

-Haz

ardo

usLo

catio

n17

86-R

PFM

oran

y as

soci

ated

appa

ratu

s w

here

the

light

emitt

ing

diod

e ou

tput

is

<5m

W/m

m2

Haz

ardo

us (C

lass

ified

)Lo

catio

nZo

ne 0

, 1 o

r 2, I

ICCl

ass

I, Zo

nes

0, 1

and

2,

Grou

ps II

C, II

B, II

ACl

ass

I Div

isio

n 1

and

2,

Grou

ps A

, B, C

, DCl

ass

II, D

ivis

ion

1 an

d 2,

Gr

oups

E, F

, GCl

ass

III, D

ivis

ion

1 an

d 2

Haz

ardo

us (C

lass

ified

) Loc

atio

nZo

ne 1

or 2

, IIC

Clas

s I,

Zone

s 1

and

2, G

roup

s IIC

, IIB

, IIA

Clas

s I D

ivis

ion

1 an

d 2,

Gro

ups

A, B

, C, D

fiber

opt

ic ca

ble

any I

S de

vice

with

en

tity

conc

ept

para

met

ers V

max

, Im

ax

C i, L

i) ap

prop

riate

for

conn

ectio

n to

asso

ciat

ed a

ppar

atus

w

ith e

ntity

con

cept

pa

ram

eter

s lis

ted

in

Tabl

e 1.

M

axim

um d

evic

es=8

.

Nod

e 1

Cont

rolN

et E

xta

pCo

ntro

lNet

Ex

tap

Cont

rolN

et E

xta

p

CNet

Ex

tap

trm

coax

trun

k ca

ble

ChB

ChA

1

ChA

ChB

any

IS d

evice

with

ent

ity

conc

ept p

aram

eter

s V m

ax,

I max

Ci,

L i) a

ppro

pria

te fo

r co

nnec

tion

to a

ssoc

iate

d ap

para

tus

with

ent

ity

conc

ept p

aram

eter

s

lis

ted

in Ta

ble

1.

Max

imum

dev

ices=

8.

To a

ny a

ppro

ved

devi

ce o

r as

soci

ated

app

arat

us w

ith

Entit

y Con

cept

pa

ram

eter

s of

Voc

=9.5

V an

d I sc

=1 A

Pow

er S

uppl

y

Vmax

=9.5

V,

Imax

=1 A

, Ci

<120

nF,

Li=

0

coax

trun

k ca

ble

Ch1

Ch1

The

ambi

ent t

empe

ratu

re ra

nge

of th

e Co

ntro

lNet

Ex

syst

em is

-20

to +

70o C.

3

Nod

e 4

... 4

8 17

97-A

CNR1

5N

ode

317

97-A

CNR1

5

Nod

e 2

1797

-RPA

1797

-RPF

M17

97-R

PFM

12

2

15

4

2

2

To a

ny a

ppro

ved

devi

ce o

r as

soci

ated

app

arat

us w

ith

Entit

y Co

ncep

t pa

ram

eter

s of

Voc

=9.5

V an

d I sc

=1A

1

Pow

er S

uppl

y Vm

ax=9

.5V,

Im

ax=1

A,

Ci<1

20 n

F,

Li=0

Ch0

Ch0

Pow

er S

uppl

y

Vmax

=9.5

V, I

max

=1 A

, Ci

<120

nF,

Li=

0To

any

appr

oved

dev

ice

or a

ssoc

iate

d ap

para

tus

with

Ent

ity

Conc

ept

para

met

ers o

f Voc

<9.5

V an

d I sc

<1 A

1

2

Publication 1797-IN015G-EN-P - August 2017

Page 21: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 21

UL, C-UL ControlNet Ex System Requirements

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

WARNING: Substitution of components may impair intrinsic safety. AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the nonhazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the nonhazardous location.

The glass fiber must have a minimum diameter of 6 μm.

UL, C-UL, FM 1797-RPA, -RPFM I/O Entity Parameters

Terminals Vt (V) It (mA) Groups Ca (μF) La (μH)

Male Bus Connector

5.8 400 A to G 3.0 3.0

Publication 1797-IN015G-EN-P - August 2017

Page 22: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

22 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

FM ControlNet Ex System Diagram

1

. .

1

Haz

ardo

us (C

lass

ified

) Loc

atio

nCl

ass

I, Zo

nes

1, G

roup

s IIC

Clas

s I D

ivis

ion

1, G

roup

s A,

B, C

, DCl

ass

II, D

ivis

ion

1, G

roup

s E,

F, G

Clas

s III

, Div

isio

n 1

Non

-Haz

ardo

us L

ocat

ion

CNet

Ex

trk tr

m

3067

0

Cont

rolN

et E

xta

p

Haz

ardo

us (C

lass

ified

)Lo

catio

nCl

ass

I, Zo

ne 0

Gr

oup

IICCl

ass

I Div

isio

n 1,

Gr

oups

A, B

, C, D

Clas

s II,

Div

isio

n 1,

Gr

oups

E, F

, GCl

ass

III, D

ivis

ion

1

Haz

ardo

us (C

lass

ified

) Loc

atio

nCl

ass

I, Zo

ne 1

, Gro

up II

CCl

ass

I Div

isio

n 1,

Gro

ups

A, B

, C, D

fiber

opt

ic ca

ble

Nod

e 1

Cont

rolN

et E

xta

p

coax

trun

k ca

ble

ChB

ChA

ChA

ChB

Vmax

=9.5

V,

Imax

=1 A

, Ci

<=12

0 nF

, Li=

0

coax

trun

k cab

le

Ch1

Ch1

The

ambi

ent t

empe

ratu

re ra

nge

of th

e Co

ntro

lNet

Ex

syst

em is

-20

to +

70o C.

3

Nod

e 4

... 4

8 17

97-A

CNR1

5N

ode

317

97-A

CNR1

5

Nod

e 2

1797

-RPA

1797

-RPF

M17

97-R

PFM

1

2

2

54

2

2

Ch0

Ch0

2

For c

onne

ctio

n to

oth

er I/

O m

odul

es, r

efer

to G

ener

al F

M

Certi

ficat

ion

Info

rmat

ion

in

Publ

icat

ion

1797

-RM

001.

For c

onne

ctio

n to

oth

er I/

O m

odul

es, r

efer

to G

ener

al

FM C

ertif

icat

ion

Info

rmat

ion

in P

ublic

atio

n 17

97-R

M00

1.

From

FM a

ppro

ved

1797

-PS2

N

From

FM a

ppro

ved

1797

-PS2

NVmax

=9.5

V,

Imax

=1 A

, Ci

<=12

0 nF

, Li=

0

Any

asso

ciat

ed a

ppar

atus

w

here

the

light

em

ittin

g di

ode

outp

ut is

<5m

W/m

m2 o

r tot

al

<1m

W.

Vmax

=9.5

V,

Imax

=1 A

, Ci

<=12

0 nF,

Li

=0

From

FM a

ppro

ved

1797

-PS2

N

Cont

rolN

et E

xta

p

Co

ntro

lNet

Ex

tap

CN

et E

x ta

p trm

CNet

Ex

trk tr

m

Any

asso

ciat

ed a

ppar

atus

w

here

the

light

em

ittin

g di

ode

outp

ut is

<5

mW

/mm

2 or t

otal

<1

mW

.

1786

-RPF

Mor

Any a

ssoc

iate

d ap

para

tus

whe

re th

e lig

ht e

mitt

ing

diod

e ou

tput

is <

5 m

W/m

m2 o

r tot

al

<1 m

W.

11

Publication 1797-IN015G-EN-P - August 2017

Page 23: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 23

FM ControlNet Ex Requirements

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

WARNING: Substitution of components may impair intrinsic safety.

If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the nonhazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the nonhazardous location.

The glass fiber must have a minimum diameter of 6 μm.

The ControlNet Ex tap must be connected directly to the module (no additional cable may be connected).

Must be FM approved.

Total coax trunk cable length is limited to 1000 m (3280 ft) with up to 2 ControlNet Ex taps connected and to 250 m (820 ft) with the maximum allowed ControlNet Ex taps of 48. For ControlNet Ex taps between 2 and 48 use: 1000 m (3280 ft) - 16.3 m (53.4 ft) x (number of taps - 2) to find the maximum allowed cable length.

Publication 1797-IN015G-EN-P - August 2017

Page 24: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

24 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

Module IndicatorsThe following explains the indications seen on the 1797-RPA and 1797-RPFM modules.

1797-RPA Indicators

The figure below identifies indicators on the repeater adapter.

Power Indicator

Comm and Module Status Indicators for the 1797-RPA Module

If This IndicatesSteady Green Power is applied.Off No power is applied.

If Both Are This IndicatesAlternately Red/Green

The adapter is being powered-up or reset. The LEDs alternately flash red and green for about 5 s.

Steady Green Normal operation.Off The unit is not powered. Check the module power status.Red There is an adapter fault.

If the fault indication is caused by a jabber condition, the fault indication will automatically be cleared when the jabber condition is removed from the coax or fiber port.If a jabber condition is not causing the fault, replace the repeater adapter.

1 32 4

+V +V-V -V

1797-RPA

PWR

REPEATERADAPTER

COMMSTATUS

MODULESTATUS

41174

Module Power StatusComm Status

Module Status

1797-RPA

Publication 1797-IN015G-EN-P - August 2017

Page 25: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 25

1797-RPFM Indicators

The figure below identifies indicators on the fiber module.

1797-RPFM Comm and Status Indicators

If Either Is The Respective Segment (1 or 2) isFlashing Green/Off Experiencing temporary network errors.

The situation will normally correct itself. If the situation persists, troubleshoot your nodes and cable system. When troubleshooting your cable system, make sure:

• all BNC connector pins are properly sealed.• all taps are A-B taps.• all terminators are 75 Ω and are installed at both ends

of all segments.Flashing Red/Off Experiencing a high level of network errors.

This may indicate a broken cable, broken tap, or missing segment terminator.Important: The indicators will flash red/off when a system has no network activity. This would be normal for a system that has no ControlNet nodes installed or enabled.

If Both Are This IndicatesOff There is no power or the module is faulted.Green The channel is operational.Flashing Green/Off There is no data activity on the associated channel.

1797-RPFM

Recv XmitRecv Xmit

Chan 1 Chan 2

41312Channel 2 Status

1797-RPFM

Channel 1 Status

Publication 1797-IN015G-EN-P - August 2017

Page 26: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

26 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

About the Mounting KitUse the optional 1794-NM1 mounting kit to mount your system on a panel or wall without a DIN rail.

RepairThe adapter and fiber module are not field-repairable. Any attempt to open this adapter or fiber module will void the warranty and the IS certification. If

repair is necessary, return the modules to the manufacturer.

IMPORTANT For detailed certification information, refer to the FLEX Ex System Certification Reference Manual, publication 1797-RM001.

1794-NM1 Mounting Kit with 18 screws (2 screws for the adapter and 2 screws for each module).

30238

Publication 1797-IN015G-EN-P - August 2017

Page 27: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 27

Specifications - 1797-RPAI/O Capacity 2 fiber modulesIS Media Type Ex ib IIB/IIC T4,

AEx ib IIC T4, Class I, Division 1 Groups A to G T4

IS Module Type Ex ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A to D T4

Communication Rate 5 MbpsControlNet Ex BNC Oscillation powered by:

Uo < 5.4V dc Io < 201 mA ac coupled with high-pass filter f > 500 kHz

Indicators Comm - green/red Module - green/red Power - green

Output (Intrinsically Safe) (30 Pin Male TTL Bus Connector)

Manufacturer specific bus Uo < 5.4V Io < 201 mA Po < 1.09 W Lo < 0.45 mH Co < 71 μF

Isolation Path Bus to Power Supply Adapter to Adapter ControlNet Ex Node to Other

Nodes ControlNet to Power Supply

Galvanic to DIN EN 60079-11 Galvanic functional Galvanic functional Galvanic to DIN EN 60079-11

Power Supply (-V, +V Intrinsically Safe)

Ui < 9.5V dc Ii < 1 A Pi < 9.5 W Li = negligible Ci < 120 nF

Power Consumption 8.5 WPower Dissipation 8.5 WThermal Dissipation 29 BTU/hrConductors Wire Size 4 mm2 (12 gauge) stranded max

1.2 mm (3/64 in.) insulation maxDimensions Metric

Imperial94 mm x 94 mm x 91 mm (3.7 in. x 3.7 in. x 3.58 in.)

Publication 1797-IN015G-EN-P - August 2017

Page 28: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

28 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

Weight Approximately 200 gEnvironmental ConditionsOperational Temperature -20…70 oC (-4…158 oF)Storage Temperature -40…85 oC (-40…185 oF)Relative Humidity 5…95% noncondensingShock Operating Tested 15 g peak acceleration, 11 (±1) ms pulse width

Nonoperating Tested 15 g peak acceleration, 11 (±1) ms pulse widthVibration Tested 2 g @ 10…500 Hz per IEC 68-2-6

Agency CertificationCENELEC II (1) 2G ib[ia] IIC T4UL, C-UL Class I Division 1 Groups A to D T4

Class I Zone 1 AEx ib IIC T4 FM Class I Division 1 Groups A to D T4

Class I Zone 1 AEx ib IIC T4INMETRO BR-Ex ia/ib IIB/IIC T4

IECEx Ex ib IIC T4 and Ex ib[ia] IIC T4Certificates

CENELEC DMT 99 ATEX E011 X

UL, C-UL UL File Number E197983

FM FM Certificate Number 3009806

INMETRO 05/UL-BRAE-0011X

IECEx IECEx BVS 09.0021X

Class I Division 1 Hazardous

FM

Publication 1797-IN015G-EN-P - August 2017

Page 29: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 29

Specifications - 1797-RPFM IS Media Type Ex ia IIB/IIC T4,

AEx ia IIC T4, Class I, Division 1 Groups A to G T4

IS Module Type Ex ib IIB/IIC T4, AEx ib IIC T4, Class I Division 1 Groups A to D T4

Communication Rate 5 Mbit/sApproximate Fiber Media Length 3 kmFiber Type 62.5…125 mmFiber Termination Type ST (plastic or ceramic)

Fiber Operating Wavelength 1300 nmOptical Power Budget 13.3 dBFiber Optic Transmitter Ch1 and Ch2

Optical peak output power Poptical < 1 mW

Indicators Channel 1 status - green Channel 2 status - green

Input (Intrinsically Safe) (30 Pin Female TTL Bus Connector)

Ui < 5.4V Ii < 201 mA Pi < 1.1 W Li < 15 μH Ci < 41 μF

Output (Intrinsically Safe) (30 Pin Male TTL Bus Connector)

Uo < 5.4V Io < 201 mA Po < 1.1 W Lo < 0.45 mH Co < 71 μF

Isolation Path Bus to ControlNet

Galvanic to DIN EN 60079-11

Power Consumption Included in 1797-RPAPower Dissipation Included in 1797-RPAThermal Dissipation Included in 1797-RPAWeight Approximately 100 gDimensions Metric

Imperial94 mm x 94 mm x 91 mm (3.7 in. x 3.7 in. x 3.58 in.)

Publication 1797-IN015G-EN-P - August 2017

Page 30: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

30 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module

Environmental ConditionsOperational Temperature -20…70 oC (-4…158 oF)Storage Temperature -40…85 oC (-40…185 oF)Relative Humidity 5…95% noncondensingShock Operating Tested 15 g peak acceleration, 11 (±1) ms pulse width

Nonoperating Tested 15 g peak acceleration, 11 (±1) ms pulse widthVibration Tested 2 g @ 10…500Hz per IEC 68-2-6

Agency CertificationCENELEC II (1) 2G ib[ia] IIC T4UL, C-UL Class I Division 1 Groups A-D T4

Class I Zone 1 AEx ib [ia] IIC T4FM Class I Division 1 Groups A-D T4

Class I Zone 1 AEx ib IIC T4INMETRO BR-Ex ia/ib IIB/IIC T4

IECEx Ex ib IIC T4 and Ex ib[ia] IIC T4Certificates

CENELEC DMT 99 ATEX E011 X

UL, C-UL UL File Number E197983

FM FM Certificate Number 3009806

INMETRO 05/UL-BRAE-0011X

IECEx IECEx BVS 09.0021X

Class I Division 1 Hazardous

FM

Publication 1797-IN015G-EN-P - August 2017

Page 31: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module 31

Mounting Dimensions

.

.

12

43

+V -

V +

V -

V

QUA

LIT

YB- AA

llen-

Bra

dley

179

7 - R

PA

Con

trol

Net

Ex

RE

PE

ATE

R A

DA

PT

ER

Com

mS

tatu

sM

odul

eS

tatu

s

PW

R.

.

Rec

vX

mit

Rec

vX

mit

Ch

an 2

Ch

an 1

1797

- R

PF

M

QU

ALIT

YB-A

Alle

n-B

radl

ey

Con

trol

Net

Ex

FIB

ER

MO

DU

LEM

ED

IUM

RA

NG

E

Re

cvX

mit

Rec

vX

mit

Ch

an 2

Ch

an 1

1797

- R

PF

M

QU

ALI

TYB- A

Alle

n-B

radl

ey

Con

trolN

et E

xF

IBE

R M

OD

UL

EM

ED

IUM

RA

NG

E mm

(in.

)

4142

680 (3.2

)

94 (3.7

)94 (3.7

)94 (3.7

)

50 (2.0

)

87 (3.4

)

Publication 1797-IN015G-EN-P - August 2017

Page 32: 1797-IN015G-EN-P ControlNet Ex Modular Repeater Adapter ......4 ControlNet Ex Modular Repeater Adapter & Fiber Repeater Module Publication 1797-IN015G-EN-P - August 2017 About the

Publication 1797-IN015G-EN-P - August 2017 PN-455768Supersedes Publication 1797-5.15 - June 2010 Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Rockwell Automation SupportRockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation AssistanceIf you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running.

New Product Satisfaction ReturnRockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned.

Allen-Bradley, Rockwell Automation, ControlLogix, RSLinx, TechConnect, and FLEX I/O are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

United States 1.440.646.3434 Monday – Friday, 8am – 5pm EST

Outside United States Please contact your local Rockwell Automation representative for any technical support issues.

United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States Please contact your local Rockwell Automation representative for return procedure.

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.