1vap420001-tg instrument transformer reference guide · primary current type product bulletin page...

45
Instrument Transformer Reference Meter and Relay Applications for the Electrical Industry

Upload: others

Post on 19-Jun-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Instrument TransformerReferenceMeter and Relay Applications for theElectrical Industry

Page 2: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

5 kV-36 kV VOLTAGE TRANSFORMERS

Class Type Product Bulletin Page No.

Primary Voltage Type Product Bulletin Page No.

1

Note: For Current and Voltage Transformer Pricing Information refer to: 600 V -PL 42-8005 kV-36 kV -PL 42-900

The transformers listed in this guide represent those mostcommonly built for the electric utility industry but are a smallsample of what we actually offer. For special designs or unitsnot listed, please contact your local ABB representative.

VT Voltage Designations

14400/24940YThis unit is rated for 14400 operating Volts. It can be connected at14400 Volts line-to-ground on a 24940 Volt system (line-to-line Voltsare 24940 V) OR it can be connected line-to-line on a system with14400 V line-to-line. This unit is not suitable for operation at 24940Volts. The "Y" indicates it has two fully insulated bushings, suitable forline-to-line connection.

14400/24940GYThis unit is rated for 14400 operating Volts. It can be connected at14400 Volts line-to-ground on a 24940 Volt system (line-to-line Voltsare 24940 V). It CANNOT be connected line-to-line. The "GY"indicates it only has one fully insulated bushing, making it suitable forline-to-ground connection only.

14400/14400YThis unit is rated for 14400 operating Volts. It can be connected at14400 Volts line-to-line.

14400/14400GYThis unit is rated for 14400 operating Volts. However, it can only beconnected line-to-ground on a 14400 V system. Therefore, the actualoperating voltage of the unit would be 14400/1.73. The accuracy andthermal ratings of this unit are based on 14400 V. This is typicalwhere there is a relay connected to the unit which should operatewhen there is a single line-to-ground fault. In this condition, the line-to-ground voltage becomes equal to the line-to-line voltage. Thisunit is not suitable for line-to-line connection as indicated by the "GY".

CT Rating Factors: Rating factors given in this brochure are standard at 30ºC. See thethermal loading guide on page 74-75 for derating for higher averageambient temperatures.

Transformers in this booklet conform to the following standards where applicable:

1) IEEE Standard Requirements for Instrument Transformers,C57.13–1993.

2) ANSI Standard for Instrument Transformers for MeteringPurposes, 15 kV and less, C12.11–1987.

50 thru 1000 IMC 1VAP428101-DB 2-3100 thru 800 CBT/1 1VAP428111-DB 2-3100 thru 800 CBT-H 1VAP428111-DB 4-5200 thru 600 CSF 1VAP428131-DB 4-5200 thru 800 CSH 1VAP428141-DB 6-7200 thru 300 CMS 1VAP428151-DB 6-750 thru 1200 CMF 1VAP428181-DB 8-9100 thru 4000 CMV 1VAP428201-DB 10-11200 thru 4000 CMV-Hi Temp 1VAP428201-DB 10-11600 thru 4000 CLC 1VAP428241-DB 12-151000 thru 6000 CLE 1VAP428261-DB 16-17600 thru 4000 RLC 1VAP428281-DB 18-19Multi-Ratio AUXILIARY 42-850 20-21Multi-Ratio A-AUTO 42-852 20-21600 thru 3000 OBCT 42-858 22-23

Primary Current Type Product Bulletin Page No.

600 VOLT CURRENT TRANSFORMERS

GGEENNEERRAALL IINNDDEEXX GGUUIIDDEE

600 VOLT VOLTAGE TRANSFORMERS

240 thru 600 PPW 1VAP428711-DB 24-25120 thru 600 PPM 1VAP428731-DB 24-2560 thru 480 PPX 1VAP428731-DB 24-25

5 kV-36 kV CURRENT TRANSFORMERS

5, 8.7 kV Indoor KIR-60,75 1VAP429141-DB 26-2715 kV Indoor KIR-11 1VAP429141-DB 28-295, 8.7 kV Outdoor KOR-60,75 42-920 30-3115 kV Outdoor KOR-11 42-922 32-3315 kV Outdoor KON-11 42-924 34-3525 kV Outdoor KOR-15C 42-927 36-3736 kV Outdoor KOR-20 42-928A 38-395-25 kV Outdoor KOT 42-930 40-4315-36 kV Outdoor KOTD 42-940 44-47

Class Type Product Bulletin Page No.

5 kV Indoor VIY-60 1VAP429511-DB 48-498.7, 15 kV Indoor VIZ-75, 11 1VAP429551-DB 50-5125 kV Indoor VIZ-12, 12G 1VAP429762-DB 52-5334.5 kV Indoor VIZ-15, 15G 1VAP429761-DB 54-5525 kV Indoor VIZZ-15, 15G 1VAP429591-DB 56-5734.5 kV Indoor VIZ-20, 20G 1VAP429601-DB 58-595 kV Outdoor VOY-60 42-961 60-618.7, 15 kV Outdoor VOZ-75, 11 42-963 60-6115 kV Outdoor VOZ-11M 62-6315 kV Outdoor VOY-11 42-964 62-6315 kV Outdoor VOG-11 42-965 62-6325 kV Outdoor VOY-12 42-966 64-6525 kV Outdoor VOG-12 42-967 64-6525 kV Outdoor VOY-15, 15G 42-970 66-6725 kV Outdoor VOZ-15 42-971 66-6725 kV Outdoor VOZZ-15, 15G 68-6936 kV Outdoor VOY-20, 20G 42-974 68-6936 kV Outdoor VOHD-200, 200G 42-977 70-7136 kV Outdoor VOZZ-20, 20G 42-979 70-71

Application Data 72-75Accuracy Standards 76-77IT Type Designations 78-79Cross-Reference 78-79

Page 3: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

TYPE CBT/1Optional accessory: Mounting Feet (set of 2) Style 9628A05G01

TYPE IMC

32

600 V CURRENT TRANSFORMERS

600 VoltsIndoor10 kV BIL25-400 Hertz

TYPE CCBBTT//11 1VAP428111-DB

No Base

Flat Base

High Base

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz

UL Recognized Component

TYPE IIMMCC 1VAP428101-DB

PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5

50 7524A98G11 2.4 - -100 7524A98G01 1.2 - -150 7524A98G02 1.2 1.2 -200 7524A98G03 0.6 1.2 2.4250 7524A98G04 0.6 1.2 2.4300 7524A98G05 0.6 0.6 0.6400 7524A98G06 0.6 0.6 0.6500 7524A98G07 0.3 0.3 0.6600 7524A98G08 0.3 0.3 0.6800 7524A98G09 0.3 0.3 0.31000 7524A98G10 0.3 0.3 0.3

2.5 2.0 1.5 5.47 4.72 2.00 3.52.5 2.0 1.5 5.47 4.72 2.00 3.52.5 2.0 1.5 5.47 4.72 2.00 3.52.5 2.0 1.5 5.47 4.72 2.00 3.52.5 2.0 1.5 5.47 4.72 2.00 3.52.5 2.0 1.5 5.47 4.72 2.00 3.52.5 2.0 1.5 5.47 4.72 2.00 3.52.5 2.0 1.5 5.47 4.72 2.00 3.52.5 1.5 1.2 5.47 4.72 2.00 3.52.5 1.33 1.0 5.47 4.72 2.00 3.52.5 1.0 0.75 5.47 4.72 2.00 3.5

100 7882A77G01 0.3 - -200 7882A77G04 0.3 0.3 -300 7882A77G07 0.3 0.3 -400 7882A77G10 0.3 0.3 -500 7882A77G13 0.3 0.3 -600 7882A77G16 0.3 0.3 -800 7882A77G19 0.3 0.3 -

4.0 3.0 4.51 3.31 11.87 2.82.0 1.5 4.51 3.31 11.87 2.82.0 1.5 4.51 3.31 11.87 3.12.0 1.5 4.51 3.31 11.87 3.12.0 1.5 4.51 3.31 12.12 3.82.0 1.5 4.51 3.31 12.12 4.01.5 1.2 4.51 3.31 12.12 4.0

100 7882A77G02 0.3 - -200 7882A77G05 0.3 0.3 -300 7882A77G08 0.3 0.3 -400 7882A77G11 0.3 0.3 -500 7882A77G14 0.3 0.3 -600 7882A77G17 0.3 0.3 -800 7882A77G20 0.3 0.3 -

4.0 3.0 4.60 3.37 11.87 2.82.0 1.5 4.60 3.37 11.87 2.82.0 1.5 4.60 3.37 11.87 3.12.0 1.5 4.60 3.37 11.87 3.12.0 1.5 4.60 3.37 12.12 3.82.0 1.5 4.60 3.37 12.12 4.01.5 1.2 4.60 3.37 12.12 4.0

100 7882A77G03 0.3 - -200 7882A77G06 0.3 0.3 -300 7882A77G09 0.3 0.3 -400 7882A77G12 0.3 0.3 -500 7882A77G15 0.3 0.3 -600 7882A77G18 0.3 0.3 -800 7882A77G21 0.3 0.3 -

4.0 3.0 6.50 5.25 11.87 3.02.0 1.5 6.50 5.25 11.87 3.02.0 1.5 6.50 5.25 11.87 3.32.0 1.5 6.50 5.25 11.87 3.32.0 1.5 6.50 5.25 12.12 4.02.0 1.5 6.50 5.25 12.12 4.21.5 1.2 6.50 5.25 12.12 4.2

WindowDiam.(in.)

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

Page 4: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

� Optional Accessory: Primary Bars for 1.50" Window Style 9628A05G09,for 2.00" Window Style 9628A05G10

* Stated accuracies are applicable for 60 Hz.

TYPE CBT-H

TYPE CSF �

54

600 V CURRENT TRANSFORMERS

TYPE CCBBTT--HH 1VAP428111-DB TYPE CCSSFF 1VAP428131-DB

No Base

Flat Base

High Base

No Base

Flat Base

High Base

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz*

600 VoltsIndoor/Outdoor10 kV BIL60 Hertz

PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5

100 7882A78G22 0.3 0.3 -200 7882A78G04 0.3 0.3 0.3300 7882A78G07 0.3 0.3 0.3400 7882A78G10 0.3 0.3 0.3500 7882A78G13 0.3 0.3 0.3600 7882A78G16 0.3 0.3 0.3800 7882A78G19 0.3 0.3 0.3

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

4.0 3.0 4.62 3.37 11.87 4.22.0 1.5 4.62 3.37 11.87 4.22.0 1.5 4.62 3.37 11.87 3.42.0 1.5 4.62 3.37 11.87 3.42.0 1.5 4.62 3.37 12.12 4.32.0 1.5 4.62 3.37 12.12 4.41.5 1.2 4.62 3.37 12.12 4.4

100 7882A78G23 0.3 0.3 -200 7882A78G05 0.3 0.3 0.3300 7882A78G08 0.3 0.3 0.3400 7882A78G11 0.3 0.3 0.3500 7882A78G14 0.3 0.3 0.3600 7882A78G17 0.3 0.3 0.3800 7882A78G20 0.3 0.3 0.3

4.0 3.0 4.62 3.37 11.87 4.22.0 1.5 4.62 3.37 11.87 4.22.0 1.5 4.62 3.37 11.87 3.42.0 1.5 4.62 3.37 11.87 3.42.0 1.5 4.62 3.37 12.12 4.32.0 1.5 4.62 3.37 12.12 4.41.5 1.2 4.62 3.37 12.12 4.4

100 7882A78G24 0.3 0.3 -200 7882A78G06 0.3 0.3 0.3300 7882A78G09 0.3 0.3 0.3400 7882A78G12 0.3 0.3 0.3500 7882A78G15 0.3 0.3 0.3600 7882A78G18 0.3 0.3 0.3800 7882A78G21 0.3 0.3 0.3

4.0 3.0 4.62 3.37 11.87 4.22.0 1.5 6.63 5.25 11.87 4.32.0 1.5 6.63 5.25 11.87 3.52.0 1.5 6.63 5.25 11.87 3.52.0 1.5 6.63 5.25 12.12 4.42.0 1.5 6.63 5.25 12.12 4.51.5 1.2 6.63 5.25 12.12 4.5

PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5

WindowDiam.(in.)

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

200 7524A85G01 0.3 0.3 -300 7524A85G02 0.3 0.3 -400 7524A83G02 0.3 0.3 -600 7524A83G03 0.3 0.3 -

1.5 3.0 2.0 4.85 3.5 3.32 3.751.5 2.0 1.5 4.85 3.5 3.32 3.752.0 2.0 1.5 4.85 3.5 3.32 2.252.0 1.5 1.2 4.85 3.5 3.32 2.25

200 7524A85G03 0.3 0.3 -300 7524A85G04 0.3 0.3 -400 7524A83G05 0.3 0.3 -600 7524A83G06 0.3 0.3 -

1.5 3.0 2.0 4.94 3.5 5.25 4.01.5 2.0 1.5 4.94 3.5 5.25 4.02.0 2.0 1.5 4.94 3.5 5.25 2.52.0 1.5 1.2 4.94 3.5 5.25 2.5

200 7524A85G05 0.3 0.3 -300 7524A85G06 0.3 0.3 -400 7524A83G08 0.3 0.3 -600 7524A83G09 0.3 0.3 -

1.5 3.0 2.0 6.54 5.25 4.50 4.01.5 2.0 1.5 6.54 5.25 4.50 4.02.0 2.0 1.5 6.54 5.25 4.50 2.52.0 1.5 1.2 6.54 5.25 4.50 2.5

Page 5: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

TYPE CSH

76

600 V CURRENT TRANSFORMERS

TYPE CCSSHH 1VAP428141-DB TYPE CCMMSS 1VAP428151-DB

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz

* Stated accuracies are applicable for 60 Hz.

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz

No Base

Flat Base

High Base

No Base

Flat Base

High Base

PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5

WindowDiam.(in.)

Relay*Accuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

200 7526A90G01 0.3 0.3 0.3300 7526A90G02 0.3 0.3 0.3400 7526A90G03 0.3 0.3 0.3500 7526A90G04 0.3 0.3 0.3600 7526A90G05 0.3 0.3 0.3800 7526A90G06 0.3 0.3 0.3

1.5 C20 3.0 2.20 5.41 4.00 3.87 7.251.5 C30 2.0 1.50 5.41 4.00 3.87 7.252.0 C30 2.0 1.50 5.41 4.00 3.87 6.02.0 C30 2.0 1.50 5.41 4.00 3.87 5.52.0 C10 2.0 1.50 5.41 4.00 3.87 5.22.0 C10 1.5 1.20 5.41 4.00 3.87 5.0

200 7526A90G11 0.3 0.3 0.3300 7526A90G12 0.3 0.3 0.3400 7526A90G13 0.3 0.3 0.3500 7526A90G14 0.3 0.3 0.3600 7526A90G15 0.3 0.3 0.3800 7526A90G16 0.3 0.3 0.3

1.5 C20 3.0 2.20 5.53 5.62 3.87 7.501.5 C30 2.0 1.50 5.53 5.62 3.87 7.502.0 C30 2.0 1.50 5.53 5.62 3.87 6.252.0 C30 2.0 1.50 5.53 5.62 3.87 5.752.0 C10 2.0 1.50 5.53 5.62 3.87 5.452.0 C10 1.5 1.20 5.53 5.62 3.87 5.25

200 7526A90G21 0.3 0.3 0.3300 7526A90G22 0.3 0.3 0.3400 7526A90G23 0.3 0.3 0.3500 7526A90G24 0.3 0.3 0.3600 7526A90G25 0.3 0.3 0.3800 7526A90G26 0.3 0.3 0.3

1.5 C20 3.0 2.20 7.09 5.25 4.50 7.501.5 C30 2.0 1.50 7.09 5.25 4.50 7.502.0 C30 2.0 1.50 7.09 5.25 4.50 6.252.0 C30 2.0 1.50 7.09 5.25 4.50 5.752.0 C10 2.0 1.50 7.09 5.25 4.50 5.452.0 C10 1.5 1.20 7.09 5.25 4.50 5.25

TYPE CMS PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5

WindowDiam.(in.)

RelayAccuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

200 7524A79G01 0.3 0.3 -300 7524A79G02 0.3 0.3 0.3

2.0 C10 3.0 2.00 5.50 4.00 3.87 5.502.0 C10 2.0 1.50 5.50 4.00 3.87 5.50

200 7524A79G03 0.3 0.3 -300 7524A79G04 0.3 0.3 0.3

2.0 C10 3.0 2.00 5.59 5.25 3.87 5.752.0 C10 2.0 1.50 5.59 5.25 3.87 5.75

200 7524A79G05 0.3 0.3 -300 7524A79G06 0.3 0.3 0.3

2.0 C10 3.0 2.00 7.09 5.25 4.50 5.752.0 C10 2.0 1.50 7.09 5.25 4.50 5.75

Page 6: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

98

600 V CURRENT TRANSFORMERS

TYPE CCMMFF 1VAP428181-DB

*Stated accuracies are applicable for 60 Hz.

With Windowand Flat Base

With Windowand High Base

With Primary Barand Flat Base

With Primary Barand High Base

600 Volts Indoor/Outdoor 10 kV BIL25-60 Hertz

PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5 B-1.8

50 4460A30G25 1.2 - - -100 4460A30G23 0.3 - - -200 4460A30G01 0.3 0.3 0.3 -400 4460A30G03 0.3 0.3 0.3 -500 4460A30G05 0.3 0.3 0.3 -600 4460A30G07 0.3 0.3 0.3 -800 4460A30G09 0.3 0.3 0.3 -1000 4460A30G21 0.3 0.3 0.3 -1200 4460A30G19 0.3 0.3 0.3 0.3200/400 4460A30G11 0.3/0.3 0.3/0.3 0.3/0.3 -300/600 4460A30G13 0.3/0.3 0.3/0.3 0.3/0.3 -400/800 4460A30G15 0.3/0.3 0.3/0.3 0.3/0.3 -

WindowDiam.(in.)

Relay*Accuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

2.50 - 4.0 3.0 7.12 5.62 4.50 12.32.50 C10 4.0 3.0 7.12 5.62 4.50 12.32.50 C30 4.0 3. 7.12 5.62 4.50 12.33.06 C30 4.0 3.0 7.12 5.62 4.50 8.53.06 C30 3.0 2.2 7.12 5.62 4.50 8.53.06 C30 2.0 1.5 7.12 5.62 4.50 8.53.06 C20 2.0 1.5 7.12 5.62 4.50 8.33.06 C30 2.0 1.5 7.12 5.62 4.50 8.33.06 C30 1.5 1.2 7.12 5.62 4.50 8.32.50 C30/C50 4.0/2.0 3.0/1.5 7.12 5.62 4.50 12.43.06 C20/C50 4.0/2.0 2.2/1.5 7.12 5.62 4.50 9.73.06 C20/C50 2.0/2.0 1.5/1.5 7.12 5.62 4.50 8.7

50 4460A30G26 1.2 - - -100 4460A30G24 0.3 - - -200 4460A30G02 0.3 0.3 0.3 -400 4460A30G18 0.3 0.3 0.3 -500 4460A30G04 0.3 0.3 0.3 -600 4460A30G06 0.3 0.3 0.3 -800 4460A30G08 0.3 0.3 0.3 -1000 4460A30G10 0.3 0.3 0.3 -1200 4460A30G20 0.3 0.3 0.3 0.3200/400 4460A30G12 0.3/0.3 0.3/0.3 0.3/0.3 -300/600 4460A30G14 0.3/0.3 0.3/0.3 0.3/0.3 -400/800 4460A30G16 0.3/0.3 0.3/0.3 0.3/0.3 -

2.50 - 4.0 3.0 7.91 5.25 4.50 12.32.50 C10 4.0 3.0 7.91 5.25 4.50 12.32.50 C30 4.0 3.0 7.91 5.25 4.50 12.33.06 C30 4.0 3.0 7.91 5.25 4.50 8.53.06 C30 3.0 2.2 7.91 5.25 4.50 8.53.06 C30 2.0 1.5 7.91 5.25 4.50 8.53.06 C20 2.0 1.5 7.91 5.25 4.50 8.33.06 C30 2.0 1.5 7.91 5.25 4.50 8.33.06 C30 1.5 1.2 7.91 5.25 4.50 8.32.50 C30/C50 4.0/2.0 3.0/1.5 7.91 5.25 4.50 12.43.06 C20/C50 4.0/2.0 2.2/1.5 7.91 5.25 4.50 9.73.06 C20/C50 2.0/2.0 1.5/1.5 7.91 5.25 4.50 8.7

100 7525A01G25 0.3 - - -200 7525A01G01 0.3 0.3 0.3 -400 7525A01G03 0.3 0.3 0.3 -500 7525A01G05 0.3 0.3 0.3 -600 7525A01G07 0.3 0.3 0.3 -800 7525A01G09 0.3 0.3 0.3 -1000 7525A01G23 0.3 0.3 0.3 -1200 7525A01G19 0.3 0.3 0.3 0.3200/400 7525A01G11 0.3/0.3 0.3/0.3 0.3/0.3 -300/600 7525A01G13 0.3/0.3 0.3/0.3 0.3/0.3 -400/800 7525A01G15 0.3/0.3 0.3/0.3 0.3/0.3 -

2.50 C10 4.0 3.0 7.12 5.62 11.88 14.32.50 C30 4.0 3.0 7.12 5.62 11.88 14.33.06 C30 4.0 3.0 7.12 5.62 11.88 12.53.06 C30 3.0 2.2 7.12 5.62 11.88 12.53.06 C30 2.0 1.5 7.12 5.62 11.88 12.53.06 C20 2.0 1.5 7.12 5.62 11.88 12.33.06 C30 2.0 1.5 7.12 5.62 11.88 12.33.06 C30 1.5 1.2 7.12 5.62 11.88 12.32.50 C30/C50 4.0/2.0 3.0/1.5 7.12 5.62 11.88 14.43.06 C20/C50 3.0/2.0 2.2/1.5 7.12 5.62 11.88 13.73.06 C20/C50 2.0/2.0 1.5/1.5 7.12 5.62 11.88 12.7

100 7525A01G26 0.3 - - -200 7525A01G02 0.3 0.3 0.3 -400 7525A01G04 0.3 0.3 0.3 -500 7525A01G06 0.3 0.3 0.3 -600 7525A01G08 0.3 0.3 0.3 -800 7525A01G10 0.3 0.3 0.3 -1000 7525A01G24 0.3 0.3 0.3 -1200 7525A01G20 0.3 0.3 0.3 0.3200/400 7525A01G12 0.3/0.3 0.3/0.3 0.3/0.3 -300/600 7525A01G14 0.3/0.3 0.3/0.3 0.3/0.3 -400/800 7525A01G16 0.3/0.3 0.3/0.3 0.3/0.3 -

2.50 C10 4.0 3.0 7.91 5.25 11.88 14.32.50 C30 4.0 3.0 7.91 5.25 11.88 14.33.06 C30 4.0 3.0 7.91 5.25 11.88 12.53.06 C30 3.0 2.2 7.91 5.25 11.88 12.53.06 C30 2.0 1.5 7.91 5.25 11.88 12.53.06 C20 2.0 1.5 7.91 5.25 11.88 12.33.06 C30 2.0 1.5 7.91 5.25 11.88 12.33.06 C30 1.5 1.2 7.91 5.25 11.88 12.32.50 C30/C50 4.0/2.0 3.0/1.5 7.91 5.25 11.88 14.43.06 C20/C50 3.0/2.0 2.2/1.5 7.91 5.25 11.88 13.73.06 C20/C50 2.0/2.0 1.5/1.5 7.91 5.25 11.88 12.7

Page 7: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Optional Accessories for Wide Bottom style:Mounting feet (kit of 4) 9628A05G15One-piece base 9628A05G16

TYPE CMV

1110

600 V CURRENT TRANSFORMERS

TYPE CCMMVV 1VAP428201-DB 1VAP428201-DB

* Stated accuracies are applicable for 60 Hz.

Tapered Bottom

Wide Bottom

Bus bar adapter fits thefollowing bus bar sizes:1/4" 3/8"+ 1/2"+

+with modification

600 Volts, Indoor/Outdoor, 10 kV BIL25-60 Hertz

PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5 B-0.9 B-1.8

WindowDiam.(in.)

Relay*Accuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

100 7524A75G17 1.2 - - - -200 7524A75G01 0.3 - - - -300 7524A75G02 0.3 0.3 - - -400 7524A75G03 0.3 0.3 - - -500 7524A75G12 0.3 0.3 0.3 - -600 7524A75G04 0.3 0.3 0.3 - -800 7524A75G05 0.3 0.3 0.3 - -1000 7524A75G06 0.3 0.3 0.3 - -1200 7524A75G07 0.3 0.3 0.3 0.3 -1500 7524A75G08 0.3 0.3 0.3 0.3 -2000 7524A75G09 0.3 0.3 0.3 0.3 0.33000 7524A75G10 0.3 0.3 0.3 0.3 0.34000 7524A75G11 0.3 0.3 0.3 0.3 0.3

3.5 x 4.5 - 4.0 3.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 4.0 3.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 4.0 3.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 4.0 3.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 3.0 2.2 9.17 6.00 2.19 6.03.5 x 4.5 C20 3.0 2.2 9.17 6.00 2.19 6.03.5 x 4.5 C20 3.0 2.2 9.17 6.00 2.19 6.03.5 x 4.5 C30 2.0 1.5 9.17 6.00 2.19 6.03.5 x 4.5 C40 2.0 1.5 9.17 6.00 2.19 6.03.5 x 4.5 C50 2.0 1.5 9.17 6.00 2.19 6.03.5 x 4.5 C50 1.5 1.2 9.17 6.00 2.19 6.03.5 x 4.5 C30 1.33 1.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 1.0 0.75 9.17 6.00 2.19 6.0

100 7524A73G17 1.2 - - - -200 7524A73G01 0.3 - - - -300 7524A73G02 0.3 0.3 - - -400 7524A73G03 0.3 0.3 - - -500 7524A73G12 0.3 0.3 0.3 - -600 7524A73G04 0.3 0.3 0.3 - -800 7524A73G05 0.3 0.3 0.3 - -1000 7524A73G06 0.3 0.3 0.3 - -1200 7524A73G07 0.3 0.3 0.3 0.3 -1500 7524A73G08 0.3 0.3 0.3 0.3 -2000 7524A73G09 0.3 0.3 0.3 0.3 0.33000 7524A73G10 0.3 0.3 0.3 0.3 0.34000 7524A73G11 0.3 0.3 0.3 0.3 0.3

3.5 x 4.5 - 4.0 3.0 8.75 6.00 2.19 6.53.5 x 4.5 C20 4.0 3.0 8.75 6.00 2.19 6.53.5 x 4.5 C20 4.0 3.0 8.75 6.00 2.19 6.53.5 x 4.5 C20 4.0 3.0 8.75 6.00 2.19 6.53.5 x 4.5 C20 3.0 2.2 8.75 6.00 2.19 6.53.5 x 4.5 C20 3.0 2.2 8.75 6.00 2.19 6.53.5 x 4.5 C20 3.0 2.2 8.75 6.00 2.19 6.53.5 x 4.5 C30 2.0 1.5 8.75 6.00 2.19 6.53.5 x 4.5 C40 2.0 1.5 8.75 6.00 2.19 6.53.5 x 4.5 C50 2.0 1.5 8.75 6.00 2.19 6.53.5 x 4.5 C50 1.5 1.2 8.75 6.00 2.19 6.53.5 x 4.5 C30 1.33 1.0 8.75 6.00 2.19 6.53.5 x 4.5 C20 1.0 0.75 8.75 6.00 2.19 6.5

200 923A231G01 0.3 - - - -300 923A231G02 0.3 0.3 - - -400 923A231G03 0.3 0.3 - - -600 923A231G04 0.3 0.3 0.3 - -800 923A231G05 0.3 0.3 0.3 - -1000 923A231G06 0.3 0.3 0.3 - -1200 923A231G07 0.3 0.3 0.3 0.3 -1500 923A231G08 0.3 0.3 0.3 0.3 -2000 923A231G09 0.3 0.3 0.3 0.3 0.33000 923A231G10 0.3 0.3 0.3 0.3 0.34000 923A231G11 0.3 0.3 0.3 0.3 0.3

3.5 x 4.5 C20 4.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 4.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 4.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 3.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 3.0 9.17 6.00 2.19 6.03.5 x 4.5 C30 2.0 9.17 6.00 2.19 6.03.5 x 4.5 C40 2.0 9.17 6.00 2.19 6.03.5 x 4.5 C50 2.0 9.17 6.00 2.19 6.03.5 x 4.5 C20 1.5 9.17 6.00 2.19 6.03.5 x 4.5 C30 1.33 9.17 6.00 2.19 6.03.5 x 4.5 C20 1.0 9.17 6.00 2.19 6.0

WindowDiam.(in.)

Relay*Accuracy

RatingFactor@ 85°C

Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)

PrimaryAmps Style Number

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5 B-0.9 B-1.8

This CT is designed for hightemperature environments. Refer to Product Bulletin for details.

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz

TYPE CCMMVV--HHii TTeemmpp

Optional Accessories for Tapered Bottom styles (CMV & CMV-Hi Temp):Bus Bar Adapter 9628A05G17 (Supplied with style 7524A75GXX; to order without, use style 7524A76GXX)

TYPECMV Hi-Temp

Page 8: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

13

1VAP428241-DB

Optional Accessories:Mounting Feet-set of 4 with hardware 9628A05G20One-piece base 9628A05G21Window plate (one required) 9628A05G22

Primary Bar Assemblies:800-1500 Amps 1 Bar 9628A05G232000 Amps 2 Bars 9628A05G243000 Amps 3 Bars 9628A05G254000 Amps 4 Bars 9628A05G26

12

600 V CURRENT TRANSFORMERS

TYPE CCLLCC

� Tap Connection X2-X3* Stated accuracies are applicable for 60 Hz.

WithoutHardware

With Mounting Feet 4-Piece

CLC continued on next page

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz

600 7524A58G16 0.3 0.3 0.3 - -800 7524A58G01 0.3 0.3 0.3 - -1000 7524A58G02 0.3 0.3 0.3 - -1200 7524A58G03 0.3 0.3 0.3 0.3 -1500 7524A58G04 0.3 0.3 0.3 0.3 -2000 7524A58G05 0.3 0.3 0.3 0.3 0.33000 7524A58G06 0.3 0.3 0.3 0.3 0.34000 7524A58G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A58G08 0.3 0.3 - - - �0.3 0.3 0.3 0.3 -

800/1600 7524A58G09 0.3 0.3 - - - �0.3 0.3 0.3 0.3 0.3

1000/2000 7524A58G10 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

1500/3000 7524A58G11 0.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

2000/4000 7524A58G12 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

PrimaryAmps

StyleNumber

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5 B-0.9 B-1.8

WindowDiam.(in.)

Relay*Accuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

5.50 C30 3.0 2.2 9.75 8.25 2.62 11.05.50 C30 2.0 1.5 9.75 8.25 2.62 11.05.50 C50 2.0 1.5 9.75 8.25 2.62 11.05.50 C30 2.0 1.5 9.75 8.25 2.62 11.05.50 C30 3.0 2.2 9.75 8.25 2.62 11.05.50 C50 2.0 1.5 9.75 8.25 2.62 11.05.50 C10 1.5 1.2 9.75 8.25 2.62 11.05.50 - 1.33 1.0 9.75 8.25 2.62 11.0

5.50 C10 3.0 2.2 9.75 8.25 2.62 11.0C30 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 2.62 11.0C60 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 2.62 11.0C50 2.0 1.5

5.50 - 2.0 1.5 9.75 8.25 2.62 11.0C10 1.5 1.2

5.50 - 2.0 1.5 9.75 8.25 2.62 11.0- 1.33 1.0

600 7524A59G16 0.3 0.3 0.3 - -800 7524A59G01 0.3 0.3 0.3 - -1000 7524A59G02 0.3 0.3 0.3 - -1200 7524A59G03 0.3 0.3 0.3 0.3 -1500 7524A59G04 0.3 0.3 0.3 0.3 -2000 7524A59G05 0.3 0.3 0.3 0.3 0.33000 7524A59G06 0.3 0.3 0.3 0.3 0.34000 7524A59G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A59G08 0.3 0.3 - - - �0.3 0.3 0.3 0.3 -

800/1600 7524A59G09 0.3 0.3 - - - �0.3 0.3 0.3 0.3 0.3

1000/2000 7524A59G10 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

1500/3000 7524A59G11 0.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

2000/4000 7524A59G12 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

5.50 C30 3.0 2.2 9.75 8.25 6.37 11.55.50 C30 2.0 1.5 9.75 8.25 6.37 11.55.50 C50 2.0 1.5 9.75 8.25 6.37 11.55.50 C30 2.0 1.5 9.75 8.25 6.37 11.55.50 C30 3.0 2.2 9.75 8.25 6.37 11.55.50 C50 2.0 1.5 9.75 8.25 6.37 11.55.50 C10 1.5 1.2 9.75 8.25 6.37 11.55.50 - 1.33 1.0 9.75 8.25 6.37 11.5

5.50 C10 3.0 2.2 9.75 8.25 6.37 11.5C30 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 6.37 11.5C60 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 6.37 11.5C50 2.0 1.5

5.50 - 2.0 1.5 9.75 8.25 6.37 11.5C10 1.5 1.2

5.50 - 2.0 1.5 9.75 8.25 6.37 11.5- 1.33 1.0

UL Recognized Component

Page 9: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Bars used are .250" thick by 4" wide. On multi-bar assemblies,there is .250" spacing between bars. Assembly can be mountedwith bars horizontal or vertical.

15

1VAP428241-DB

14

600 V CURRENT TRANSFORMERS

TYPE CCLLCC CONT’D.

� Tap Connection X2-X3* Stated accuracies are applicable for 60 Hz.

With OnePiece Base

With WindowPlate

4.00

1.75

4.25

11.75

14.50

1.75

.250 THICK BARØ.563 HOLES8-TOTAL

Ø.281 HOLES4-TOTAL

PrimaryAmps

StyleNumber

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5 B-0.9 B-1.8

WindowDiam.(in.)

Relay*Accuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30° C 55° C

600 7524A60G16 0.3 0.3 0.3 - -800 7524A60G01 0.3 0.3 0.3 - -1000 7524A60G02 0.3 0.3 0.3 - -1200 7524A60G03 0.3 0.3 0.3 0.3 -1500 7524A60G04 0.3 0.3 0.3 0.3 -2000 7524A60G05 0.3 0.3 0.3 0.3 0.33000 7524A60G06 0.3 0.3 0.3 0.3 0.34000 7524A60G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A60G08 0.3 0.3 - - - �0.3 0.3 0.3 0.3 -

800/1600 7524A60G09 0.3 0.3 - - - �0.3 0.3 0.3 0.3 0.3

1000/2000 7524A60G10 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

1500/3000 7524A60G110.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

2000/4000 7524A60G12 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

5.50 C30 3.0 2.2 9.75 8.25 2.62 11.05.50 C30 2.0 1.5 9.75 8.25 2.62 11.05.50 C50 2.0 1.5 9.75 8.25 2.62 11.05.50 C30 2.0 1.5 9.75 8.25 2.62 11.05.50 C30 3.0 2.2 9.75 8.25 2.62 11.05.50 C50 2.0 1.5 9.75 8.25 2.62 11.05.50 C10 1.5 1.2 9.75 8.25 2.62 11.05.50 - 1.33 1.0 9.75 8.25 2.62 11.0

5.50 C10 3.0 2.2 9.75 8.25 2.62 11.0C30 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 2.62 11.0C60 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 2.62 11.0C50 2.0 1.5

5.50 - 2.0 1.5 9.75 8.25 2.62 11.0C10 1.5 1.2

5.50 - 2.0 1.5 9.75 8.25 2.62 11.0- 1.33 1.0

600 7524A61G16 0.3 0.3 0.3 - -800 7524A61G01 0.3 0.3 0.3 - -1000 7524A61G02 0.3 0.3 0.3 - -1200 7524A61G03 0.3 0.3 0.3 0.3 -1500 7524A61G04 0.3 0.3 0.3 0.3 -2000 7524A61G05 0.3 0.3 0.3 0.3 0.33000 7524A61G06 0.3 0.3 0.3 0.3 0.34000 7524A61G07 0.3 0.3 0.3 0.3 0.3

600/1200 7524A61G08 0.3 0.3 - - - �0.3 0.3 0.3 0.3 -

800/1600 7524A61G09 0.3 0.3 - - - �0.3 0.3 0.3 0.3 0.3

1000/2000 7524A61G10 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

1500/3000 7524A61G11 0.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

2000/4000 7524A61G12 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

5.50 C30 3.0 2.2 9.75 8.25 6.37 11.55.50 C30 2.0 1.5 9.75 8.25 6.37 11.55.50 C50 2.0 1.5 9.75 8.25 6.37 11.55.50 C30 2.0 1.5 9.75 8.25 6.37 11.55.50 C30 3.0 2.2 9.75 8.25 6.37 11.55.50 C50 2.0 1.5 9.75 8.25 6.37 11.55.50 C10 1.5 1.2 9.75 8.25 6.37 11.55.50 - 1.33 1.0 9.75 8.25 6.37 11.5

5.50 C10 3.0 2.2 9.75 8.25 6.37 11.5C30 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 6.37 11.5C60 2.0 1.5

5.50 C30 3.0 2.2 9.75 8.25 6.37 11.5C50 2.0 1.5

5.50 - 2.0 1.5 9.75 8.25 6.37 11.5C10 1.5 1.2

5.50 - 2.0 1.5 9.75 8.25 6.37 11.5- 1.33 1.0

Bar Assemblies

Page 10: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

1716

1VAP428261-DB

600 V CURRENT TRANSFORMERS

TYPE CCLLEE

� Tap Connection X2-X3* Stated accuracies are applicable for 60 Hz.

Without Mounting Feet

WithMounting Feet

2-Piece

Optional Accessories:Mounting Feet (set of 2 w/hdwr.) 9628A05G27Window Plates (set of 2 w/hdwr.) 9628A05G28

600 VoltsIndoor/Outdoor10 kV BIL25-400 Hertz

UL Recognized Component

PrimaryAmps

StyleNumber

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5 B-0.9 B-1.8

WindowDiam.(in.)

Relay*Accuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

2000 7524A63G01 0.3 0.3 0.3 0.3 -3000 7524A63G02 0.3 0.3 0.3 0.3 0.34000 7524A63G03 0.3 0.3 0.3 0.3 0.35000 7524A63G04 0.3 0.3 0.3 0.3 0.36000 7524A63G05 0.3 0.3 0.3 0.3 0.3

1000/2000 7524A63G06 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 -

1500/3000 7524A63G07 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

2000/4000 7524A63G08 0.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

2500/5000 7524A63G09 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

3000/6000 7524A63G10 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

8.25 C50 2.0 1.5 12.87 11.37 2.62 16.08.25 C100 2.0 1.5 12.87 11.37 2.62 16.08.25 C100 1.5 1.2 12.87 11.37 2.62 16.08.25 C100 1.33 1.0 12.87 11.37 2.62 16.08.25 - 1.0 0.75 12.87 11.37 2.62 16.0

8.25 C30 3.0 2.2 12.87 11.37 2.62 16.0C50 2.0 1.5

8.25 C50 3.0 2.2 12.87 11.37 2.62 16.0C100 2.0 1.5

8.25 C50 2.0 1.5 12.87 11.37 2.62 16.0C100 1.5 1.2

8.25 C100 2.0 1.5 12.87 11.37 2.62 16.0C200 1.33 1.0

8.25 - 1.33 1.0 12.87 11.37 2.62 16.0- 1.0 0.75

2000 7524A64G01 0.3 0.3 0.3 0.3 -3000 7524A64G02 0.3 0.3 0.3 0.3 0.34000 7524A64G03 0.3 0.3 0.3 0.3 0.35000 7524A64G04 0.3 0.3 0.3 0.3 0.36000 7524A64G05 0.3 0.3 0.3 0.3 0.3

1000/2000 7524A64G06 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 -

1500/3000 7524A64G07 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

2000/4000 7524A64G08 0.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

2500/5000 7524A64G09 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

3000/6000 7524A64G10 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

8.25 C50 2.0 1.5 12.87 11.37 6.37 17.08.25 C100 2.0 1.5 12.87 11.37 6.37 17.08.25 C100 1.5 1.2 12.87 11.37 6.37 17.08.25 C100 1.33 1.0 12.87 11.37 6.37 17.08.25 - 1.0 0.75 12.87 11.37 6.37 17.0

8.25 C30 3.0 2.2 12.87 11.37 6.37 17.0C50 2.0 1.5

8.25 C50 3.0 2.2 12.87 11.37 6.37 17.0C100 2.0 1.5

8.25 C50 2.0 1.5 12.87 11.37 6.37 17.0C100 1.5 1.2

8.25 C100 2.0 1.5 12.87 11.37 6.37 17.0C200 1.33 1.0

8.25 - 1.33 1.0 12.87 11.37 6.37 17.0- 1.0 0.75

Page 11: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Standard

1918

1VAP428281-DB

600 V CURRENT TRANSFORMERS

TYPE RRLLCC

� Tap Connection X2-X3* Stated accuracies are applicable for 60 Hz.

Hi RelayAccuracy

4.50

4.88

10.50

1.00

4.13

Ø.313 HOLE

4-TOTAL

.375 x 1.250 SLOT

W .750 HOLE

2-TOTAL

600 VoltsIndoor/Outdoor10 kV BIL25-60 Hertz

UL Recognized Component

PrimaryAmps

StyleNumber

IEEE Metering AccuracyB-0.1 B-0.2 B-0.5 B-0.9 B-1.8

WindowDiam.(in.)

Relay*Accuracy

Rating Factor Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)30°C 55°C

750 7524A52G01 0.3 0.3 0.3 - -800 7524A52G02 0.3 0.3 0.3 0.3 -900 7524A52G03 0.3 0.3 0.3 0.3 -1000 7524A52G04 0.3 0.3 0.3 0.3 -1200 7524A52G05 0.3 0.3 0.3 0.3 0.31500 7524A52G06 0.3 0.3 0.3 0.3 0.32000 7524A52G07 0.3 0.3 0.3 0.3 0.33000 7524A52G08 0.3 0.3 0.3 0.3 0.34000 7524A52G09 0.3 0.3 0.3 0.3 0.3

600/1200 7524A52G10 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

800/1600 7524A52G11 0.3 0.3 0.3 - - �0.3 0.3 0.3 0.3 0.3

1000/2000 7524A52G12 0.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

1500/3000 7524A52G13 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

2000/4000 7524A52G14 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

5.5 C100 2.0 1.5 11.25 10.50 4.12 21.05.5 C100 2.0 1.5 11.25 10.50 4.12 21.05.5 C100 2.0 1.5 11.25 10.50 4.12 21.05.5 C100 2.0 1.5 11.25 10.50 4.12 21.05.5 C200 2.0 1.5 11.25 10.50 4.12 21.05.5 C200 2.0 1.5 11.25 10.50 4.12 21.05.5 C200 1.5 1.2 11.25 10.50 4.12 21.05.5 C200 1.33 1.0 11.25 10.50 4.12 21.05.5 C200 1.33 1.0 11.25 10.50 4.12 21.0

5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0C200 2.0 1.5

5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0C200 1.5 1.2

5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0C200 1.5 1.2

5.5 C100 1.5 1.2 11.25 10.50 4.12 21.0C200 1.33 1.0

5.5 C100 1.5 1.2 11.25 10.50 4.12 21.0C200 1.33 1.0

1000 9625A21G01 0.3 0.3 0.3 0.3 0.32000 9625A21G02 0.3 0.3 0.3 0.3 0.33000 9625A21G03 0.3 0.3 0.3 0.3 0.34000 9625A21G04 0.3 0.3 0.3 0.3 0.3

1000/2000 9625A21G05 0.3 0.3 0.3 0.3 - �0.3 0.3 0.3 0.3 0.3

1500/3000 9625A21G06 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

2000/4000 9625A21G07 0.3 0.3 0.3 0.3 0.3 �0.3 0.3 0.3 0.3 0.3

5.5 C200 2.0 1.5 11.25 10.50 4.12 29.05.5 C400 1.5 1.2 11.25 10.50 4.12 29.05.5 C400 1.5 1.2 11.25 10.50 4.12 29.05.5 C400 1.5 1.2 11.25 10.50 4.12 29.0

5.5 C200 2.0 1.5 11.25 10.50 4.12 29.0C400 1.5 1.2

5.5 C200 1.5 1.2 11.25 10.50 4.12 29.0C400 1.33 1.0

5.5 C200 1.5 1.2 11.25 10.50 4.12 29.0C400 1.33 1.0

Page 12: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

1 2 6 87

1 2 3 10 1611

9 15 1614

40turns

70 taps @10 turn steps

taps @1 turn steps

95turns

taps @10 turn steps

28 27 taps @ 1 turn steps

4 4

- to -

- to - - to -

Main Winding Buck-Boost Winding

13380

x 1600133

Auxiliary CTs offer a wide selection of turns ratios for use inchanging the overall ratio of main CTs. Available ratios can bedetermined from the winding (wdg.) turns tabulation. The maximumcontinuous current rating of multi-ratio transformers can becalculated as follows:

Full wdg. Imax = 1600/Full winding turns

Tap conn. Imax =

Example: 7881A02G03• Wdg. 1-4 = 133 turns, Imax = 1600/133 = 12 amps.

• 2-part wdg. (series) = 160 turns, Imax = 1600/160 = 10 amps.

• 2-part wdg. (/ /) = 80 turns, Imax = 1600/80 = 20 amps.

• Tap conn. 1-2 = 80 turns, Imax = = 15.5 amps.

Single ratio auxiliary CTs have a nominal output of 5 amperes and acontinuous current rating factor of 1.33.

IndoorTest Voltage: 2500 Volts25 Through 60 Hertz

Multi-Ratio Winding Developmenttapped winding

2 part wdg.

Full wdg. turns

Tap turnsx

1600

Full wdg. turns�2 part wdg.

fully utilized

H1 X2X1H2

2120

PB 42-850

1 2 3 4

5 6 7 8

Typical accuracy values at 800 ampere turns are:

6.50

1.25

2.255.006.75

TYPE A CCUURRRREENNTT BBAALLAANNCCIINNGG AAUUTTOO PB 42-852

Indoor Test Voltage: 2500 Volts25-60 Hertz Type A transformers provide a largenumber of fine ratio adjustment tapsfor establishing an exact current ratiobalance between the CTs on theinput and output sides of powertransformers.

600 V CURRENT TRANSFORMERS

AAUUXXIILLIIAARRYY

5.007.75

4.25

5.50

1.66

Dimensions & Weights50 VA 100 VA

Height 7.00 7.00Width 6.50 6.50Length 6.75 7.75Weight 20.0 24.0

Dimensions & WeightsMulti-Ratio Single-Ratio

Height 7.00 6.37Width 5.50 5.75Length 8.50 7.75Weight 23.00 23.00

Single

Winding Development

Mounting Base Dimensions

Mounting Base Dimensions

Style Winding TurnsRatio Number 1-2 2-3 3-4 5-6 7-8

Multi 7881A02G01 160 40 67 800 800Multi 7881A02G02 160 40 67 200 200Multi 7881A02G03 80 20 33 80 80Multi 7881A02G04 80 20 33 800 800Multi 7881A02G05 80 20 33 400 400Multi 7881A02G06 80 20 33 100 100Multi 7881A02G07 195 7 32 117 117Multi 7881A03G01 125 25 50 25 25Multi 7881A03G02 160 40 67 40 40Multi 7881A03G03 160 40 67 80 80Multi 7881A03G04 160 40 67 400 400

5:5 7881A01G01 140 14010:5 7881A01G02 70 14015:5 7881A01G03 47 141

Relay MeterMulti-Ratio T50 0.3 thru B-0.5, 0.6 thru B-1.8Single Ratio T50 0.3 thru B-0.5, 0.6 thru B-1.8

Volt-AmpereRating

StyleNumber

50 7881A17G01

100 7881A17G02

Ratio Adjustment Range

from 10.8:5 to 5:5 Amps

from 10.8:5 to 5:5 Amps

Page 13: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

IEEE Bushing Flange CharacteristicsBolt Bolt Bolt

Circle Bolt Circle Bolt Circle BoltDiam. No. of Size Diam. No. of Size Diam. No. of Size(in.) Bolts (in.) (in.) Bolts (in.) (in.) Bolts (in.)71/4 4 11/16 81/4 4 11/16 91/4 6 7/8

Note: When stacking two bushing current transformers on a common bushing, bracket 589B864G07 should also be ordered.

12 589B864G01 589B864G01 589B864G0218 - - 589B864G0422 - - -32 - - -

InsideDiameter

(in.)

2322

PB 42-858

600 V CURRENT TRANSFORMERS

TYPE OOBBCCTT

� Applies to Normal Ratio Only (Full Winding)

X1 X2 X3 X4 X5

40

TURNS

20

TURNS

100

TURNS

80

TURNS

Multi-Ratio, Externally Mounted Test Voltage: 2500 Volts 25-60 Hertz

Mounting Brackets, includes mounting hardware

X1 X2 X3 X4 X5

20

TURNS

10

TURNS

50

TURNS

40

TURNS

X1 X2 X3 X4 X5

80

TURNS

160

TURNS

60

TURNS

100

TURNS

X1 X2 X3 X4 X5

200

TURNS

240

TURNS

60

TURNS

100

TURNS

Primary Style IEEE Metering Accuracy �

Amps Number B-0.1 B-0.2 B-0.5 B-1.8

600 7881A86G01 0.3 0.3 0.3 1.2600 7881A86G02 0.6 0.6 0.6 1.2600 7881A86G03 0.6 0.6 0.6 1.2600 7881A86G04 0.6 0.6 1.2 -

Relay�

AccuracyRatingFactor

Case ID(in.)

Case OD(in.)

Height(in.)

Weight(in.)

C400 1.33 12.0 24.1 6.37 240C400 1.33 18.0 30.4 6.37 330C400 1.33 22.0 34.5 6.37 400C400 1.33 32.0 44.6 6.37 550

1200 7881A86G05 0.3 0.3 0.3 0.31200 7881A86G06 0.3 0.3 0.3 0.61200 7881A86G07 0.3 0.3 0.3 0.61200 7881A86G08 0.3 0.3 0.6 0.6

C800 1.33 12.0 24.1 6.37 240C800 1.33 18.0 30.4 6.37 330C800 1.33 22.0 34.5 6.37 400C800 1.33 32.0 44.6 6.37 550

2000 7881A86G09 0.3 0.3 0.3 0.32000 7881A86G10 0.3 0.3 0.3 0.32000 7881A86G11 0.3 0.3 0.3 0.32000 7881A86G12 0.3 0.3 0.3 0.6

C800 1.33 12.0 23.5 4.94 155C800 1.33 18.0 29.7 4.94 210C800 1.33 22.0 33.7 4.94 245C800 1.33 32.0 43.8 4.94 340

3000 7881A86G51 0.3 0.3 0.3 0.33000 7881A86G52 0.3 0.3 0.3 0.33000 7881A86G53 0.3 0.3 0.3 0.33000 7881A86G54 0.3 0.3 0.3 0.3

C800 1.33 12.0 22.6 4.75 125C800 1.33 18.0 28.4 4.56 160C800 1.33 22.0 32.6 4.56 190C800 1.33 32.0 42.7 4.56 260

- - - -- - - -

589B864G03 589B864G04 589B864G05 -- - - 589B864G06

IEEE Bushing Flange CharacteristicsBolt Bolt Bolt Bolt

Circle Bolt Circle Bolt Circle Bolt Circle BoltDiam. No. of Size Diam. No. of Size Diam. No. of Size Diam. No. of Size(in.) Bolts (in.) (in.) Bolts (in.) (in.) Bolts (in.) (in.) Bolts (in.)131/4 6 11/4 141/4 6 11/4 153/4 8 11/4 21 12 11/4

Page 14: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

TYPE PPX

2524

600 V VOLTAGE TRANSFORMERS

TYPE PPPPMM aanndd PPPPXX 1VAP428731-DB

� 50/60 Hertz � 70 V Secondary* 240 V Secondary

PPW Thermal Rating:150 VA at 30º C ambient100 VA at 55º C ambient

600 Volts, Indoor and Outdoor10 kV BIL, 60 Hertz

PPM Thermal Rating:500 VA at 30º C ambient350 VA at 55º C ambientPPX Thermal Rating:500 VA at 30º C ambient350 VA at 55º C ambient

UL Recognized Component UL Recognized Component

Primary StyleVoltage Ratio Number

240/416Y 2:1 7526A04G01288/500Y 2.4:1 7526A04G02300/520Y 2.5:1 7526A04G03480/480Y 4:1 7526A04G04600/600Y 5:1 7526A04G05

TYPE PPW

TYPE PPM

IEEE Metering Height Width Length WeightAccuracy (in.) (in.) (in.) (lbs.)

0.3 Classfor W0.6 Classfor X Burdens

4.56 4.50 5.00 9.04.56 4.50 5.00 9.04.56 4.50 5.00 9.04.56 4.50 5.00 9.04.56 4.50 5.00 9.0

240/416Y 2:1 7526A10G01288/500Y 2.4:1 7526A10G02300/520Y 2.5:1 7526A10G03480/480Y 4:1 7526A10G04600/600Y 5:1 7526A10G05120/208Y 1:1 7526A10G06480/480Y 2:1 9628A88G07 *

0.3 ClassforW, X, M, & YBurdens

5.97 5.87 6.12 19.05.97 5.87 6.12 19.05.97 5.87 6.12 19.05.97 5.87 6.12 19.05.97 5.87 6.12 19.05.97 5.87 6.12 19.05.97 5.87 6.12 19.0

120/208Y 1:1 7525A16G01�

69.3/120Y 0.578:1 7525A16G03400/400Y 3.33:1 7525A16G04�

120/208Y* 1.7143:1 7525A16G05�*�

207.8/360Y 1.7317:1 7525A16G0960/104Y 0.5:1 7525A16G10�

0.6W-Y 5.97 5.87 6.12 19.00.3W, 0.6X-Y 5.97 5.87 6.12 19.00.3W, 0.6X-Y 5.97 5.87 6.12 19.00.3W, 0.6X-Y 5.97 5.87 6.12 19.00.3W-Y 5.97 5.87 6.12 19.00.6W-Y 5.97 5.87 6.12 19.0

600 Volts, Indoor and Outdoor10 kV BIL, 60 Hertz

TYPE PPPPWW 1VAP428711-DB

Page 15: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

2726

5 kV-8.7 kV INDOORCURRENT TRANSFORMERS

TYPE KKIIRR--6600 AANNDD KKIIRR--7755 PB 1VAP429141-DB

7.13

8.63

.75

4.75

.38

5.50

1.66

5.00 1.81

4.25

*Accuracy 20% less at 50 Hertz.

Mechanical Rating:5 thru 600 Amps, 150 x normal

800 Amps, 110 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second

800 Amps, 75 x normal for 1 second

Indoor 60 & 75 kV BIL50/60 Hertz*

NSV 5.0 kV60 kV BIL

NSV 8.7 kV75 kV BIL

PrimaryAmps

StyleNumber

IEEE MeteringAccuracy

5 7524A01G01

All Ratings0.3-B0.1

through B1.8

10 7524A01G0215 7524A01G0320 7524A01G0425 7524A01G0530 7524A01G0640 7524A01G0750 7524A01G0875 7524A01G09100 7524A01G10150 7524A01G11200 7524A01G12300 7524A01G13400 7524A01G14600 7524A01G15800 7524A01G161000 7524A01G211200 7524A01G20

Relay*Accuracy

RatingFactor

Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)

T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 35T100 1.5 8.06 6.13 15.0 38T100 1.5 8.06 6.13 15.0 38T100 1.5 8.06 6.13 15.0 38T100 1.5 8.06 6.13 15.0 38T100 1.33 8.06 6.13 15.0 38T100 1.33 8.06 6.13 15.0 38T100 1.0 8.06 6.13 15.0 39

5 7524A02G01

All Ratings0.3-B0.1

through B1.8

10 7524A02G0215 7524A02G0320 7524A02G0425 7524A02G0530 7524A02G0640 7524A02G0750 7524A02G0875 7524A02G09100 7524A02G10150 7524A02G11200 7524A02G12300 7524A02G13400 7524A02G14600 7524A02G15800 7524A02G16

T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 36T100 1.5 10.3 6.13 16.0 39T100 1.5 10.3 6.13 16.0 39T100 1.5 10.3 6.13 16.0 39

Mounting Base Dimensions (in.)

Page 16: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

5 7524A03G01 T200 1.5 9.87 6.75 23 5610 7524A03G02 T200 1.5 9.87 6.75 23 5615 7524A03G03 T200 1.5 9.87 6.75 23 5620 7524A03G04 T200 1.5 9.87 6.75 23 5625 7524A03G05 T200 1.5 9.87 6.75 23 5630 7524A03G06 T200 1.5 9.87 6.75 23 5640 7524A03G07 0.3 B0.1 T200 1.5 9.87 6.75 23 5650 7524A03G08 through T200 1.5 9.87 6.75 23 5675 7524A03G09 B1.8 T200 1.5 9.87 6.75 23 56100 7524A03G10 All Ratings T200 1.5 9.87 6.75 23 56150 7524A03G11 T200 1.5 9.87 6.75 23 56200 7524A03G12 T200 1.5 9.87 6.75 23 56300 7524A03G13 T200 1.5 9.87 6.75 23 61400 7524A03G14 T200 1.5 9.87 6.75 23 61600 7524A03G16 T200 1.5 9.87 6.75 23 61800 7524A03G17 T200 1.33 9.87 6.75 23 611000 7524A03G21 T200 1.33 9.87 6.75 23 611200 7524A03G18 T200 1.0 9.87 6.75 23 62

5/10 7524A04G01 T90/T200 2.0/1.5 9.87 6.75 23 5610/20 7524A04G02 T90/T200 2.0/1.5 9.87 6.75 23 5620/40 7524A04G03 T90/T200 2.0/1.5 9.87 6.75 23 5625/50 7524A04G04 0.3 T90/T200 2.0/1.5 9.87 6.75 23 5650/100 7524A04G05 B0.1 T90/T200 2.0/1.5 9.87 6.75 23 5675/150 7524A04G06 through T90/T200 2.0/1.5 9.87 6.75 23 56100/200 7524A04G07 B1.8 Full T90/T200 2.0/1.5 9.87 6.75 23 56150/300 7524A04G08 B0.9 Tap T90/T200 2.0/1.5 9.87 6.75 23 61200/400 7524A04G09 All Ratings T90/T200 2.0/1.5 9.87 6.75 23 61300/600 7524A04G10 T90/T200 2.0/1.5 9.87 6.75 23 61400/800 7524A04G11 T100/T200 2.0/1.33 9.87 6.75 23 61600/1200 7524A04G14 T90/T200 2.0/1.0 9.87 6.75 23 62

2928

15 kV INDOORCURRENT TRANSFORMERS

TYPE KKIIRR--1111 PB 1VAP429141-DB

9.63 .44

10.50

5.13

.44

2.75

1.66

5.00

.87

4.25

6.00

4.25

*Accuracy 20% less at 50 Hertz.

Mechanical Rating:5 thru 600 Amps, 150 x normal

800 Amps, 110 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second

800 Amps, 75 x normal for 1 second

Indoor 110 kV BIL50/60 Hertz*

NSV 15.0 kV110 kV BILSingle Ratio

NSV 15.0 kV110 kV BIL

Double Ratio

Mounting Base Dimensions (in.)

Page 17: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

5 7524A10G01 T100 1.5 12.3 9.37 11.00 4110 7524A10G02 T100 1.5 12.3 9.37 11.00 4115 7524A10G03 T100 1.5 12.3 9.37 11.00 4120 7524A10G04 T100 1.5 12.3 9.37 11.00 4125 7524A10G05 T100 1.5 12.3 9.37 11.00 4130 7524A10G06 0.3 B0.1 T100 1.5 12.3 9.37 11.00 4140 7524A10G07 through T100 1.5 12.3 9.37 11.00 4150 7524A10G08 B1.8 T100 1.5 12.3 9.37 11.00 4175 7524A10G09 All Ratings T100 1.5 12.3 9.37 11.00 41100 7524A10G10 T100 1.5 12.3 9.37 11.00 41150 7524A10G11 T100 1.5 12.3 9.37 11.00 41200 7524A10G12 T100 1.5 12.3 9.37 11.00 45300 7524A10G13 T100 1.5 12.3 9.37 11.00 45400 7524A10G14 T100 1.5 12.3 9.37 11.00 45600 7524A10G15 T100 1.5 12.3 9.37 11.00 45800 7524A10G16 T100 1.33 12.3 9.37 11.00 451000 7524A10G17 T70 1.33 12.3 9.37 11.00 45

5 7524A11G01 T100 1.5 12.3 9.37 11.00 4110 7524A11G02 T100 1.5 12.3 9.37 11.00 4115 7524A11G03 T100 1.5 12.3 9.37 11.00 4120 7524A11G04 T100 1.5 12.3 9.37 11.00 4125 7524A11G05 T100 1.5 12.3 9.37 11.00 4130 7524A11G06 0.3 B0.1 T100 1.5 12.3 9.37 11.00 4140 7524A11G07 through T100 1.5 12.3 9.37 11.00 4150 7524A11G08 B1.8 T100 1.5 12.3 9.37 11.00 4175 7524A11G09 All Ratings T100 1.5 12.3 9.37 11.00 41100 7524A11G10 T100 1.5 12.3 9.37 11.00 41150 7524A11G11 T100 1.5 12.3 9.37 11.00 41200 7524A11G12 T100 1.5 12.3 9.37 11.00 45300 7524A11G13 T100 1.5 12.3 9.37 11.00 45400 7524A11G14 T100 1.5 12.3 9.37 11.00 45600 7524A11G15 T100 1.5 12.3 9.37 11.00 45800 7524A11G16 T100 1.33 12.3 9.37 11.00 451000 7524A11G17 T70 1.33 12.3 9.37 11.00 45

3130

5 kV-8.7 kV CURRENT TRANSFORMERS

TYPE KKOORR--6600 aanndd KKOORR--7755 PB 42-920

8.50

6.25

.75

9.38

7.88

*Accuracy 20% less at 50 Hertz.

Outdoor60 kV and 75 kV BIL50/60 Hertz*

Mechanical Rating:5 thru 400 Amps, 150 x normal600-1000 Amps, 110 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second1000 Amps, 50 x normal for 1 second

NSV 5.0 kV 60 kV BIL

NSV 8.7 kV 75 kV BIL

Mounting Base Dimensions (in.)

Page 18: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

5 7524A12G01 T200 1.5 15.7 10.8 12.5 7010 7524A12G02 T200 1.5 15.7 10.8 12.5 7015 7524A12G03 T200 1.5 15.7 10.8 12.5 7020 7524A12G04 T200 1.5 15.7 10.8 12.5 7025 7524A12G05 T200 1.5 15.7 10.8 12.5 7030 7524A12G06 0.3 B0.1 T200 1.5 15.7 10.8 12.5 7040 7524A12G07 through T200 1.5 15.7 10.8 12.5 7050 7524A12G08 B1.8 T200 1.5 15.7 10.8 12.5 7075 7524A12G09 All Ratings T200 1.5 15.7 10.8 12.5 70100 7524A12G10 T200 1.5 15.7 10.8 12.5 70150 7524A12G11 T200 1.5 15.7 10.8 12.5 70200 7524A12G12 T200 1.5 15.7 10.8 12.5 73300 7524A12G13 T200 1.5 15.7 10.8 12.5 73400 7524A12G14 T200 1.5 15.7 10.8 12.5 73600 7524A12G15 T200 1.5 15.7 10.8 12.5 73800 7524A12G16 T200 1.33 15.7 10.8 12.5 731000 7524A12G18 T150 1.5 15.7 10.8 12.5 731200 7524A12G17 T200 1.5 15.7 10.8 12.5 73

5/10 7524A13G01 T90/T200 2.0/1.5 15.7 10.8 12.5 7010/20 7524A13G02 T90/T200 2.0/1.5 15.7 10.8 12.5 7020/40 7524A13G03 T90/T200 2.0/1.5 15.7 10.8 12.5 7025/50 7524A13G04 0.3 B0.1 T90/T200 2.0/1.5 15.7 10.8 12.5 7050/100 7524A13G05 through T90/T200 2.0/1.5 15.7 10.8 12.5 7075/150 7524A13G06 B1.8 Full T90/T200 2.0/1.5 15.7 10.8 12.5 70100/200 7524A13G07 B0.9 Tap T90/T200 2.0/1.5 15.7 10.8 12.5 73150/300 7524A13G08 All Ratings T90/T200 2.0/1.5 15.7 10.8 12.5 73200/400 7524A13G09 T90/T200 2.0/1.5 15.7 10.8 12.5 73300/600 7524A13G10 T90/T200 2.0/1.5 15.7 10.8 12.5 73400/800 7524A13G11 T100/T200 2.0/1.33 15.7 10.8 12.5 73600/1200 7524A13G12 T90/T200 2.0/1.5 15.7 10.8 12.5 73

3332

15 kV CURRENT TRANSFORMERS

TYPE KKOORR--1111 PB 42-922

10.88

8.62

10.00

9.50

*Accuracy 20% less at 50 Hertz.

Outdoor110 kV BIL50/60 Hertz*

Mechanical Rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

NSV 15.0 kV110 kV BIL

Double Ratio

NSV 15.0 kV110 kV BILSingle Ratio

Mounting Base Dimensions (in.)

Page 19: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

3534

15 kV CURRENT TRANSFORMERS

TYPE KKOONN--1111 PB 42-924

10.88

8.63

10.00

9.50

*Accuracy 20% less at 50 Hertz.

Outdoor110 kV BIL50/60 Hertz*

Mechanical Rating:All Ratings 270 x normal

Thermal Rating:All Ratings 190 x normal, 1 second

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

5 7524A25G16 C40 3.0 13.5 10.8 12.4 3710 7524A25G01 C40 3.0 13.5 10.8 12.4 3715 7524A25G02 C40 3.0 13.5 10.8 12.4 3720 7524A25G03 C40 3.0 13.5 10.8 12.4 3725 7524A25G04 C40 3.0 13.5 10.8 12.4 3730 7524A25G05 C40 3.0 13.5 10.8 12.4 3740 7524A25G06 C40 3.0 13.5 10.8 12.4 3750 7524A25G07 0.3 B0.1, C40 3.0 13.5 10.8 12.4 3775 7524A25G08 B0.2, B0.5 C40 3.0 13.5 10.8 12.4 37100 7524A25G09 All Ratings C40 3.0 13.5 10.8 12.4 37150 7524A25G10 C40 3.0 13.5 10.8 12.4 41200 7524A25G11 C40 3.0 13.5 10.8 12.4 41300 7524A25G12 C40 3.0 13.5 10.8 12.4 41400 7524A25G13 C40 3.0 13.5 10.8 12.4 41600 7524A25G14 C40 2.0 13.5 10.8 12.4 41800 7524A25G15 C40 1.5 13.5 10.8 12.4 411000 7524A25G18 C40 1.2 13.5 10.8 12.4 411200 7524A25G19 C40 1.0 13.5 10.8 12.4 41

NSV 15.0 kV110 kV BIL

Mounting Base Dimensions (in.)

Page 20: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

25 kV CURRENT TRANSFORMERS

TYPE KKOORR--1155CC

9.06

10.50

.72

.44

.6310.00

11.25

37

Outdoor150 kV BIL50/60 Hertz*

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

5 923A185G01 3.0 17.9 10.9 13.9 11010 923A185G02 3.0 17.9 10.9 13.9 11015 923A185G03 3.0 17.9 10.9 13.9 11020 923A185G04 3.0 17.9 10.9 13.9 11025 923A185G05 0.3 B0.1, C100 3.0 17.9 10.9 13.9 11030 923A185G06 through All Ratings 3.0 17.9 10.9 13.9 11040 923A185G07 B0.9 3.0 17.9 10.9 13.9 11050 923A185G08 All Ratings 3.0 17.9 10.9 13.9 11075 923A185G09 3.0 17.9 10.9 13.9 110100 923A185G10 3.0 17.9 10.9 13.9 110150 923A185G11 3.0 17.9 10.9 13.9 110200 923A185G12 3.0 17.9 10.9 13.9 110300 923A185G13 3.0 17.9 10.9 13.9 110400 923A185G14 3.0 17.9 10.9 13.9 110500 923A185G15 2.0 17.9 10.9 13.9 110600 923A185G16 2.0 17.9 10.9 13.9 110800 923A185G17 1.5 17.9 10.9 13.9 1101200 923A185G18 1.0 17.9 10.9 13.9 110

5/10 923A186G01 3.0/1.5 17.9 10.9 13.9 11010/20 923A186G02 3.0/1.5 17.9 10.9 13.9 11020/40 923A186G03 0.3 B0.1 thru C100 Tap 3.0/1.5 17.9 10.9 13.9 11025/50 923A186G04 B0.9 Tap C200 Full 3.0/1.5 17.9 10.9 13.9 11050/100 923A186G05 B1.8 Full All Ratings 3.0/1.5 17.9 10.9 13.9 11075/150 923A186G06 All Ratings 3.0/1.5 17.9 10.9 13.9 110100/200 923A186G07 3.0/1.5 17.9 10.9 13.9 110150/300 923A186G08 3.0/1.5 17.9 10.9 13.9 110200/400 923A186G09 3.0/1.5 17.9 10.9 13.9 110300/600 923A186G10 3.0/1.5 17.9 10.9 13.9 110400/800 923A186G11 3.0/1.5 17.9 10.9 13.9 110600/1200 923A186G12 2.0/1.0 17.9 10.9 13.9 110

36 *Accuracy 20% less at 50 Hertz.

Single Ratio

Double Ratio

Mechanical Rating:All styles single ratio:

290 x normal All styles double ratio:

290 TAP145 FULL

Thermal Rating:All styles 100 x normal, 1 second

PB 42-927(THIS REPLACES KOR-15AND KOR-15B)

Mounting Base Dimensions (in.)

Page 21: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

10 7524A22G01 3.0 20.9 11.2 13.9 11215 7524A22G02 3.0 20.9 11.2 13.9 11220 7524A22G03 3.0 20.9 11.2 13.9 11225 7524A22G04 3.0 20.9 11.2 13.9 11230 7524A22G05 3.0 20.9 11.2 13.9 11240 7524A22G06 0.3 B0.1, C100 3.0 20.9 11.2 13.9 11250 7524A22G07 B0.2, B0.5, All Ratings 3.0 20.9 11.2 13.9 11275 7524A22G08 B0.9 3.0 20.9 11.2 13.9 112100 7524A22G09 All Ratings 3.0 20.9 11.2 13.9 112150 7524A22G10 3.0 20.9 11.2 13.9 112200 7524A22G11 3.0 20.9 11.2 13.9 120300 7524A22G12 3.0 20.9 11.2 13.9 120400 7524A22G13 3.0 20.9 11.2 13.9 120500 7524A22G14 2.0 20.9 11.2 13.9 120600 7524A22G15 2.0 20.9 11.2 13.9 120800 7524A22G16 1.5 20.9 11.2 13.9 1201200 7524A22G17 1.0 20.9 11.2 13.9 120

5/10 7524A21G01 3.0 Tap 20.9 11.2 13.9 11210/20 7524A21G02 1.5 Full 20.9 11.2 13.9 11220/40 7524A21G03 0.3 B0.1 thru C100 Tap 20.9 11.2 13.9 11225/50 7524A21G04 B0.9 Tap C200 Full 20.9 11.2 13.9 11250/100 7524A21G05 B1.8 Full All Ratings 20.9 11.2 13.9 11275/150 7524A21G06 All Ratings 20.9 11.2 13.9 112100/200 7524A21G07 20.9 11.2 13.9 120150/300 7524A21G08 20.9 11.2 13.9 120200/400 7524A21G09 20.9 11.2 13.9 120300/600 7524A21G10 20.9 11.2 13.9 120400/800 7524A21G11 20.9 11.2 13.9 120600/1200 7524A21G12 2.0/1.0 20.9 11.2 13.9 120

3938 *Accuracy 20% less at 50 Hertz.

36 kV CURRENT TRANSFORMERS

TYPE KKOORR--2200 PB 42-928A

NSV 36 kV 200 kV BILSingle Ratio

NSV 36 kV200 kV BILDouble Ratio

Outdoor200 kV BIL50/60 Hertz*

9.06

10.50

.72

.44

.6310.00

11.25

Mounting Base Dimensions (in.)

Mechanical Rating:All styles single ratio:

290 x normal All styles double ratio:

290 TAP145 FULL

Thermal Rating:All styles 100 x normal, 1 second

Page 22: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Tube Type3.25" ID

4140 *Accuracy 20% less at 50 Hertz. KOT Continued on Next Page

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

800 7524A32G01 0.3B0.9 C100 2.0 17.25 10.50 10.25 401200 7524A32G02 0.3B1.8 C200 2.0 17.25 10.50 10.25 401500 7524A32G03 0.3B1.8 C200 2.0 17.25 10.50 10.25 402000 7524A32G04 0.3B1.8 C200 2.0 17.25 10.50 10.25 403000 7524A32G05 0.3B1.8 C200 1.5 17.25 10.50 10.25 404000 7524A32G06 0.3B1.8 C200 1.5 17.25 10.50 10.25 40600/1200 7524A32G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 10.25 40

B1.8 Full1000/2000 7524A32G08 0.3B0.9 Tap C100/C200 3.0/2.0 17.25 10.50 10.25 40

B1.8 Full2000/4000 7524A32G09 0.3B1.8 Tap C100/C200 2.0/1.5 17.25 10.50 10.25 40

B1.8 Full

800 7524A33G01 0.3B0.9 C100 2.0 17.25 10.50 13.25 431200 7524A33G02 0.3B1.8 C200 2.0 17.25 10.50 13.25 431500 7524A33G03 0.3B1.8 C200 2.0 17.25 10.50 13.25 432000 7524A33G04 0.3B1.8 C200 2.0 17.25 10.50 13.25 433000 7524A33G05 0.3B1.8 C200 1.5 17.25 10.50 13.25 434000 7524A33G06 0.3B1.8 C200 1.5 17.25 10.50 13.25 43600/1200 7524A33G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 13.25 43

B1.8 Full1000/2000 7524A33G08 0.3B0.9 Tap C100/C200 3.0/2.0 17.25 10.50 13.25 43

B1.8 Full2000/4000 7524A33G09 0.3B1.8 Tap C100/C200 2.0/1.5 17.25 10.50 13.25 43

B1.8 Full

800 7524A34G01 0.3B0.9 C100 2.0 17.25 10.50 17.75 471200 7524A34G02 0.3B1.8 C200 2.0 17.25 10.50 17.75 471500 7524A34G03 0.3B1.8 C200 2.0 17.25 10.50 17.75 472000 7524A34G04 0.3B1.8 C200 2.0 17.25 10.50 17.75 473000 7524A34G05 0.3B1.8 C200 1.5 17.25 10.50 17.75 474000 7524A34G06 0.3B1.8 C200 1.5 17.25 10.50 17.75 47600/1200 7524A34G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 17.75 47

B1.8 Full1000/2000 7524A34G08 0.3B0.9 Tap C100/C200 3.0/2.0 17.25 10.50 17.75 47

B1.8 Full2000/4000 7524A34G09 0.3B1.8 Tap C100/C200 2.0/1.5 17.25 10.50 17.75 47

B1.8 Full

800 7524A35G01 0.3B0.9 C100 2.0 17.25 10.50 26.75 521200 7524A35G02 0.3B1.8 C200 2.0 17.25 10.50 26.75 521500 7524A35G03 0.3B1.8 C200 2.0 17.25 10.50 26.75 522000 7524A35G04 0.3B1.8 C200 2.0 17.25 10.50 26.75 523000 7524A35G05 0.3B1.8 C200 1.5 17.25 10.50 26.75 524000 7524A35G06 0.3B1.8 C200 1.5 17.25 10.50 26.75 52600/1200 7524A35G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 26.75 52

B1.8 Full1000/2000 7524A35G08 0.3B0.9 Tap C100/C200 3.0/2.0 17.25 10.50 26.75 52

B1.8 Full2000/4000 7524A35G09 0.3B1.8 Tap C100/C200 2.0/1.5 17.25 10.50 26.75 52

B1.8 Full

5 kV-25 kV CURRENT TRANSFORMERS

TYPE KKOOTT PB 42-930

Outdoor60, 75, 110, 150 kV BIL50/60 Hertz*

Mechanical Rating:All units: effectively unlimited

Thermal Rating:800 and 1200 Amp: 80 x normal, 1 second1500 Amp and above: 100 x normal, 1 second

5.75

7.00

7.00

8.25

KOT-60Tube TypeNSV 5.0 kV 60 kV BIL

KOT-75Tube TypeNSV 8.7 kV 75 kV BIL

KOT-11Tube TypeNSV 15.0 kV110 kV BIL

KOT-15Tube TypeNSV 25 kV150 kV BIL

Mounting Base Dimensions

Page 23: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

1.75

1.75

2.50

2.50

.501.75

.25

.25

1.75.50

.88

.883.00

.25.25

.25

4342 *Accuracy 20% less at 50 Hertz.

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

800 923A271G01 0.3B0.9 C100 2.00 17.25 10.50 19.62 621200 923A271G02 0.3B1.8 C200 2.00 17.25 10.50 19.62 621500 923A271G03 0.3B1.8 C200 2.00 17.25 10.50 19.62 622000 923A271G04 0.3B1.8 C200 1.50 17.25 10.50 19.62 623000 923A271G05 0.3B1.8 C200 1.33 17.25 10.50 19.62 734000 923A271G06 0.3B1.8 C200 1.00 17.25 10.50 19.62 73600/1200 923A271G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 19.62 62

B1.8 Full1000/2000 923A271G08 0.3B0.9 Tap C100/C200 2.0/1.5 17.25 10.50 19.62 62

B1.8 Full2000/4000 923A271G09 0.3B1.8 Tap C100/C200 1.5/1.0 17.25 10.50 19.62 73

B1.8 Full

800 923A273G01 0.3B0.9 C100 2.00 17.25 10.50 22.62 671200 923A273G02 0.3B1.8 C200 2.00 17.25 10.50 22.62 671500 923A273G03 0.3B1.8 C200 2.00 17.25 10.50 22.62 672000 923A273G04 0.3B1.8 C200 1.50 17.25 10.50 22.62 673000 923A273G05 0.3B1.8 C200 1.33 17.25 10.50 22.62 794000 923A273G06 0.3B1.8 C200 1.00 17.25 10.50 22.62 79600/1200 923A273G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 22.62 67

B1.8 Full1000/2000 923A273G08 0.3B0.9 Tap C100/C200 2.0/1.5 17.25 10.50 22.62 67

B1.8 Full2000/4000 923A273G09 0.3B1.8 Tap C100/C200 1.5/1.0 17.25 10.50 22.62 79

B1.8 Full

800 923A275G01 0.3B0.9 C100 2.00 17.25 10.50 27.12 751200 923A275G02 0.3B1.8 C200 2.00 17.25 10.50 27.12 751500 923A275G03 0.3B1.8 C200 2.00 17.25 10.50 27.12 752000 923A275G04 0.3B1.8 C200 1.50 17.25 10.50 27.12 753000 923A275G05 0.3B1.8 C200 1.33 17.25 10.50 27.12 894000 923A275G06 0.3B1.8 C200 1.00 17.25 10.50 27.12 89600/1200 923A275G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 27.12 75

B1.8 Full1000/2000 923A275G08 0.3B0.9 Tap C100/C200 2.0/1.5 17.25 10.50 27.12 75

B1.8 Full2000/4000 923A275G09 0.3B1.8 Tap C100/C200 1.5/1.0 17.25 10.50 27.12 89

B1.8 Full

800 923A270G01 0.3B0.9 C100 2.00 17.25 10.50 36.12 901200 923A270G02 0.3B1.8 C200 2.00 17.25 10.50 36.12 901500 923A270G03 0.3B1.8 C200 2.00 17.25 10.50 36.12 902000 923A270G04 0.3B1.8 C200 1.50 17.25 10.50 36.12 903000 923A270G05 0.3B1.8 C200 1.33 17.25 10.50 36.12 1074000 923A270G06 0.3B1.8 C200 1.00 17.25 10.50 36.12 107600/1200 923A270G07 0.3B0.5 Tap C100/C200 3.0/2.0 17.25 10.50 36.12 90

B1.8 Full1000/2000 923A270G08 0.3B0.9 Tap C100/C200 2.0/1.5 17.25 10.50 36.12 90

B1.8 Full2000/4000 923A270G09 0.3B1.8 Tap C100/C200 1.5/1.0 17.25 10.50 36.12 107

B1.8 Full

5 kV-25 kV CURRENT TRANSFORMERS

TYPE KKOOTT CONT’D. PB 42-930

Outdoor60, 75, 110, 150 kV BIL50/60 Hertz*

Bar Type

Base details on previous page

KOT-60Bar TypeNSV 5.0 kV 60 kV BIL

KOT-75Bar TypeNSV 8.7 kV 75 kV BIL

KOT-11Bar Type

NSV 15.0 kV 110 kV BIL

KOT-15Bar TypeNSV 25 kV 150 kV BIL

Primary Terminals2000 Amperes and Below

Primary Terminals3000 Amperes and Above

Page 24: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

4544 *Accuracy 20% less at 50 Hertz. KOTD Continued on Next Page

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

200/400 923A142G01 0.3B0.5 C100/200 2.0/2.0 20.0 14.7 17.0 220300/600 923A142G02 0.3B0.9 C100/200 2.0/2.0 20.0 14.7 17.0 220400/800 923A142G03 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 17.0 220500/1000 923A142G04 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 17.0 220600/1200 923A142G05 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 17.0 220800/1600 923A142G06 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 17.0 2201000/2000 923A142G07 0.3B1.8 C400/800 2.0/2.0 20.0 14.7 17.0 2201500/3000 923A142G08 0.3B1.8 C400/800 2.0/1.5 20.0 14.7 17.0 2202000/4000 923A142G09 0.3B1.8 C400/800 2.0/1.25 20.0 14.7 17.0 2202500/5000 923A142G10 0.3B1.8 C400/800 2.0/1.0 20.0 14.7 17.0 220

200/400 923A156G01 0.3B0.5 C100/200 2.0/2.0 22.5 14.7 17.0 245300/600 923A156G02 0.3B0.9 C100/200 2.0/2.0 22.5 14.7 17.0 245400/800 923A156G03 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 17.0 245500/1000 923A156G04 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 17.0 245600/1200 923A156G05 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 17.0 245800/1600 923A156G06 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 17.0 2451000/2000 923A156G07 0.3B1.8 C400/800 2.0/2.0 22.5 14.7 17.0 2451500/3000 923A156G08 0.3B1.8 C400/800 2.0/1.5 22.5 14.7 17.0 2452000/4000 923A156G09 0.3B1.8 C400/800 2.0/1.25 22.5 14.7 17.0 2452500/5000 923A156G10 0.3B1.8 C400/800 2.0/1.0 22.5 14.7 17.0 245

200/400 923A170G01 0.3B0.5 C100/200 2.0/2.0 25.0 14.7 17.0 260300/600 923A170G02 0.3B0.9 C100/200 2.0/2.0 25.0 14.7 17.0 260400/800 923A170G03 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 17.0 260500/1000 923A170G04 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 17.0 260600/1200 923A170G05 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 17.0 260800/1600 923A170G06 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 17.0 2601000/2000 923A170G07 0.3B1.8 C400/800 2.0/2.0 25.0 14.7 17.0 2601500/3000 923A170G08 0.3B1.8 C400/800 2.0/1.5 25.0 14.7 17.0 2602000/4000 923A170G09 0.3B1.8 C400/800 2.0/1.25 25.0 14.7 17.0 2602500/5000 923A170G10 0.3B1.8 C400/800 2.0/1.0 25.0 14.7 17.0 260

15 kV-36 kV CURRENT TRANSFORMERS

TYPE KKOOTTDD PB 42-940

Outdoor110, 150, 200 kV BIL50/60 Hertz*

Tube Type5" ID

7.50

.75

9.00

13.50 .75

15.00

KOTD-110Tube TypeNSV 15 kV110 kV BIL

KOTD-150Tube TypeNSV 25 kV150 kV BIL

KOTD-200Tube TypeNSV 36 kV200 kV BIL

Mounting Base Dimensions

Page 25: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

4746

15 kV-36 kV CURRENT TRANSFORMERS

TYPE KKOOTTDD CONT’D. PB 42-940

25.00

4.00

1.12

1.75

1.75

23.88

.56

Ø.56 8-TOTAL

Outdoor110, 150, 200 kV BIL50/60 Hertz*

Bar Type

Base detail on previous page

Primary Style IEEE Meter IEEE Relay* RatingAmps Number Accuracy Accuracy Factor Height Width Length Weight

200/400 923A148G01 0.3B0.5 C100/200 2.0/2.0 20.0 14.7 25.0 235300/600 923A148G02 0.3B0.9 C100/200 2.0/2.0 20.0 14.7 25.0 235400/800 923A148G03 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 25.0 235500/1000 923A148G04 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 25.0 235600/1200 923A148G05 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 25.0 235800/1600 923A148G06 0.3B1.8 C200/400 2.0/2.0 20.0 14.7 25.0 2351000/2000 923A148G07 0.3B1.8 C400/800 2.0/2.0 20.0 14.7 25.0 2351500/3000 923A148G08 0.3B1.8 C400/800 2.0/1.5 20.0 14.7 25.0 2352000/4000 923A148G09 0.3B1.8 C400/800 2.0/1.25 20.0 14.7 25.0 2352500/5000 923A148G10 0.3B1.8 C400/800 2.0/1.0 20.0 14.7 25.0 235

200/400 923A162G01 0.3B0.5 C100/200 2.0/2.0 22.5 14.7 25.0 260300/600 923A162G02 0.3B0.9 C100/200 2.0/2.0 22.5 14.7 25.0 260400/800 923A162G03 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 25.0 260500/1000 923A162G04 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 25.0 260600/1200 923A162G05 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 25.0 260800/1600 923A162G06 0.3B1.8 C200/400 2.0/2.0 22.5 14.7 25.0 2601000/2000 923A162G07 0.3B1.8 C400/800 2.0/2.0 22.5 14.7 25.0 2601500/3000 923A162G08 0.3B1.8 C400/800 2.0/1.5 22.5 14.7 25.0 2602000/4000 923A162G09 0.3B1.8 C400/800 2.0/1.25 22.5 14.7 25.0 2602500/5000 923A162G10 0.3B1.8 C400/800 2.0/1.0 22.5 14.7 25.0 260

200/400 923A176G01 0.3B0.5 C100/200 2.0/2.0 25.0 14.7 25.0 275300/600 923A176G02 0.3B0.9 C100/200 2.0/2.0 25.0 14.7 25.0 275400/800 923A176G03 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 25.0 275500/1000 923A176G04 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 25.0 275600/1200 923A176G05 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 25.0 275800/1600 923A176G06 0.3B1.8 C200/400 2.0/2.0 25.0 14.7 25.0 2751000/2000 923A176G07 0.3B1.8 C400/800 2.0/2.0 25.0 14.7 25.0 2751500/3000 923A176G08 0.3B1.8 C400/800 2.0/1.5 25.0 14.7 25.0 2752000/4000 923A176G09 0.3B1.8 C400/800 2.0/1.25 25.0 14.7 25.0 2752500/5000 923A176G10 0.3B1.8 C400/800 2.0/1.0 25.0 14.7 25.0 275

KOTD-110Bar TypeNSV 15 kV110 kV BIL

KOTD-150Bar TypeNSV 25 kV150 kV BIL

KOTD-200Bar TypeNSV 36 kV200 kV BIL

*Accuracy 20% less at 50 Hertz.

Bar Dimensions

Page 26: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

4948� Thermal and Accuracy ratings are at 120 V secondary voltage. � Fluxed for line-to-line voltage; when connected line-to-ground,

normal secondary voltage is 69.3 volts.

5 kV INDOORVOLTAGE TRANSFORMERS

TYPE VVIIYY--6600 PB 1VAP429511-DB

9.31

5.50

7.38

8.44

6.38

Indoor60 kV BIL60 Hertz

Primary Style IEEE MeterVoltage Ratio Number Accuracy � Height Width Length Weight

2400/4160Y 20:1 7525A50G01 0.3W, X, M, Y 6.90 6.37 9.31 324200/4200Y 35:1 7525A50G02 0.3W, X, M, Y 6.90 6.37 9.31 324800/4800Y 40:1 7525A50G03 0.3W, X, M, Y 6.90 6.37 9.31 32

2400/4160Y 20:1 7525A51G01 0.3W, X, M, Y 8.25 6.75 10.00 364200/4200Y 35:1 7525A51G02 0.3W, X, M, Y 8.25 6.75 10.00 364800/4800Y 40:1 7525A51G03 0.3W, X, M, Y 8.25 6.75 10.00 36

2400/4160GY 20:1 7525A52G01 0.3W, X, M, Y 8.56 6.37 10.00 344200/4200GY � 35:1 7525A52G02 0.3W, X, M, Y 8.56 6.37 10.00 344800/4800GY � 40:1 7525A52G03 0.3W, X, M, Y 8.56 6.37 10.00 34

Unfused

2 Fuses

1 Fuse

Thermal Rating:�1000 VA at 30ºC700 VA at 55ºC

Unfused

One Fuse

Two Fuses

Mounting Base Dimensions (in.)

UL Recognized Component Fuses are Type CLE-PT, Style number 677C452G06

Page 27: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

8.7 kV and 15 kV INDOORVOLTAGE TRANSFORMERS

TYPE VVIIZZ--7755 AANNDD VVIIZZ--1111 PB 1VAP429551-DB

5150

13.13

8.00

12.25

10.25

9.00

Indoor75 kV and 110 kV BIL60 Hertz

Primary Style IEEE MeterVoltage Ratio Number Accuracy� Height Width Length Weight

2400/4160Y 20:1 7525A66G01 0.3W, X, M, Y, Z 9.00 9.25 13.12 694200/7280Y 35:1 7525A66G02 0.3W, X, M, Y, Z 9.00 9.25 13.12 694800/8320Y 40:1 7525A66G03 0.3W, X, M, Y, Z 9.00 9.25 13.12 697200/7200Y 60:1 7525A66G04 0.3W, X, M, Y, Z 9.00 9.25 13.12 69

7200/12470Y 60:1 7525A66G05 0.3W, X, M, Y, Z 9.00 9.25 13.12 698400/14560Y 70:1 7525A66G07 0.3W, X, M, Y, Z 9.00 9.25 13.12 6912000/12000Y 100:1 7525A66G08 0.3W, X, M, Y, Z 9.00 9.25 13.12 6914400/14400Y 120:1 7525A66G10 0.3W, X, M, Y, Z 9.00 9.25 13.12 69

2400/4160Y 20:1 7525A67G01 0.3W, X, M, Y, Z 11.25 9.25 15.50 734200/7280Y 35:1 7525A67G02 0.3W, X, M, Y, Z 11.25 9.25 15.50 734800/8320Y 40:1 7525A67G03 0.3W, X, M, Y, Z 11.25 9.25 15.50 737200/7200Y 60:1 7525A67G04

7200/12470Y 60:1 7525A67G05 0.3W, X, M, Y, Z 11.25 9.25 15.50 738400/14560Y 70:1 7525A67G07 0.3W, X, M, Y, Z 11.25 9.25 15.50 7312000/12000Y 100:1 7525A67G08 0.3W, X, M, Y, Z 11.25 9.25 15.50 7314400/14400Y 120:1 7525A67G10 0.3W, X, M, Y, Z 11.25 9.25 15.50 73

2400/4160GY 20:1 7525A68G01 0.3W, X, M, Y, Z 12.18 9.25 15.50 714200/7280GY 35:1 7525A68G02 0.3W, X, M, Y, Z 12.18 9.25 15.50 714800/8320GY 40:1 7525A68G03 0.3W, X, M, Y, Z 12.18 9.25 15.50 717200/7200GY� 60:1 7525A68G04

7200/12470GY 60:1 7525A68G05 0.3W, X, M, Y, Z 12.18 9.25 15.50 718400/14560GY 70:1 7525A68G07 0.3W, X, M, Y, Z 12.18 9.25 15.50 7112000/12000GY� 100:1 7525A68G08 0.3W, X, M, Y, Z 12.18 9.25 15.50 7114400/14400GY� 120:1 7525A68G10 0.3W, X, M, Y, Z 12.18 9.25 15.50 71

VIZ-7575 kV BILUnfused

VIZ-11110 kV BILUnfused

VIZ-7575 kV BIL2 Fuses

VIZ-11110 kV BIL

2 Fuses

VIZ-7575 kV BIL

1 Fuse

VIZ-11110 kV BIL

1 Fuse

Thermal Ratings:�

1500 VA at 30ºC1000 VA at 55ºC

� Thermal and Accuracy ratings are at 120 V secondary voltage.� Fluxed for line-to-line voltage; when connected line-to-ground,

normal secondary voltage is 69.3 Volts.

One Fuse

Two Fuses

Mounting Base Dimensions (in.)

UL Recognized Component

Fuses are Type CLE-PT: Style number 677C452G03 (0.5E)Style number 677C452G08 (1.0 E Option)

Page 28: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

5352

25 kV INDOORVOLTAGE TRANSFORMERS

TYPE VVIIZZ--1122 PB 1VAP429762-DB

PrimaryVoltage

WindingRatio

StyleNumber

18000/18000Y 150:1 9628A33G0121000/21000Y 175:1 9628A33G0224000/24000Y 200:1 9628A33G0327600/27600Y 240:1 9628A34G01

RatedVoltage Factor

Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)

1.1 10.50 10.25 13.0 1101.1 10.50 10.25 13.0 1101.1 10.50 10.25 13.0 1101.1 12.38 10.25 13.0 120

TYPE VVIIZZ--1122GG PB 1VAP429762-DB

PrimaryVoltage

WindingRatio

StyleNumber

RatedVoltage Factor

Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)

VIZ-12GUnfused

VIZ-12GFused

13.00

12.00

8.00

10.25

8.75

.44 X 1.94SLOT4-TOTAL

.44 X 1.19SLOT4-TOTAL

16.00

7.87

15.00

5.62

.44 X 1.19SLOT4-TOTAL

Mounting Base Dimensions (in.)

Mounting Base Dimensions (in.)

12000/20780GY 100:1 7881A72G0114400/24940GY 120:1 7881A72G0216000/27600GY 133.33:1 7881A72G0318000/18000GY 150:1 7881A72G0414400/24940GY 120:1 7881A72G05

12000/20780GY 100:1 7881A64G0114400/24940GY 120:1 7881A64G02

1.25 12.13 8.0 16.0 1021.25 12.13 8.0 16.0 1021.25 12.13 8.0 16.0 1021.1 12.13 8.0 16.0 1021.25 12.13 8.0 16.0 102

1.25 14.88 8.0 19.0 1051.25 14.88 8.0 19.0 105

Indoor125 kV BIL60 Hertz

Thermal Rating:2000 VA @ 30°C ambient1500 VA @ 55°C ambient

IEEE Metering Accuracy:0.3W, X, M, Y, Z & 1.2 ZZ

Indoor125 kV BIL60 Hertz

Thermal Rating:1500 VA @ 30°C Ambient750 VA @ 55°C Ambient

IEEE Metering Accuracy:0.3 W, X, M, Y, & Z

Fuse kit, style 9628A05G72 (for remote mounting)

Fuse kit to convert unfused VIZ-12G to fused style: 9628A05G68

VIZ-12Unfused

Page 29: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

34.5 kV INDOORVOLTAGE TRANSFORMERS

TYPE VVIIZZ--1155 PB 1VAP429761-DB

Indoor150 kV BIL50 & 60 Hertz

Thermal Rating:2000 VA @ 30°C Ambient1500 VA @ 55°C Ambient

IEEE Metering Accuracy:0.3W, X, M, Y, Z & 1.2 ZZ

PrimaryVoltage

WindingRatio

StyleNumber

RatedVoltage Factor

Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)

27600/27600Y 240:1 9628A34G0134500/34500Y 300:1 9628A34G0224940/24940Y 207.83:1 9628A34G0312000/12000Y 100:1 9628A34G0424000/24000Y 200:1 9628A34G0526400/26400Y 220:1 9628A34G06

1.1 12.10 10.25 13.0 1201.1 12.10 10.25 13.0 1201.1 12.10 10.25 13.0 1201.1 12.10 10.25 13.0 1201.1 12.10 10.25 13.0 1201.1 12.10 10.25 13.0 120

PrimaryVoltage

WindingRatio

StyleNumber

RatedVoltage Factor

Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)

TYPE VVIIZZ--1155GG PB 1VAP429761-DB

12000/20780GY 100:1 9629A81G0114400/24940GY 120:1 9629A81G0219920/34500GY 166:1 9629A81G0324000/24000GY 200:1 9629A81G04

1.1 12.10 10.25 13.57 1201.1 12.10 10.25 13.57 1201.1 12.10 10.25 13.57 1201.1 12.10 10.25 13.57 120

Indoor150 kV BIL50 & 60 Hertz

Thermal Rating:2000 VA @ 30°C Ambient1500 VA @ 55°C Ambient

IEEE Metering Accuracy:0.3W, X, M, Y, and Z

VIZ-15GUnfused

VIZ-15GFused

12000/20780GY 100:1 9629A82G0114400/24940GY 120:1 9629A82G0216100/27900GY 140:1 9629A82G0324000/24000GY 200:1 9629A82G04

1.25 14.82 10.25 17.9 1221.25 14.82 10.25 17.9 1221.25 14.82 10.25 17.9 1221.25 14.82 10.25 17.9 122

13.00

12.00

8.00

10.25

8.75

.44 X 1.94SLOT4-TOTAL

.44 X 1.19SLOT4-TOTAL

13.00

12.00

8.00

10.25

8.75

.44 X 1.94SLOT4-TOTAL

.44 X 1.19SLOT4-TOTAL

Mounting Base Dimensions (in.)

Mounting Base Dimensions (in.)

Fuse kit, style 9628A05G86 (for remote mounting)

Fuse kit to convert unfused VIZ-15G to fused style: 9628A05G89

VIZ-15Unfused

5554

Page 30: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

.75 .75

1.75

1.25 1.25

1.25

1.25

1.25 1.25

1.38

.50

.75 1.13

.44

14.50

.44

15.00

.438 x 1.688 SLOTWITH .219 RADIUS6-TOTAL

Ø.438 HOLE6-TOTAL

.438 x .938 SLOTWITH .219 RADIUS4-TOTAL

.50

25 kV VOLTAGE TRANSFORMERS

TYPE VVIIZZZZ--1155 AANNDD VVIIZZZZ--1155GG PB 1VAP429591-DB

Indoor150 kV BIL60 Hertz

Available at other ratiosand single tappedsecondary or doublesecondary.

Thermal Ratings:3000 VA at 30ºC Ambient

Primary Style IEEE MeterVoltage Ratio Number� Accuracy Height Width Length Weight

12000/20800Y 100:1 7525A82G01 0.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 20514400/24940Y 120:1 7525A82G02 0.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 20518000/18000Y 150:1 7525A82G03 0.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 20524000/24000Y 200:1 7525A82G04 0.3W, X, M, Y, Z, ZZ 22.3 16.0 18.6 205

12000/20800GY 100:1 7525A84G01 0.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 20514400/24940GY 120:1 7525A84G02 0.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 20520000/20000GY 166.67:1 7525A84G03 0.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 20524000/24000GY 200:1 7525A84G04 0.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 20518000/18000GY 150:1 7525A84G05 0.3W, X, M, Y, Z, ZZ 22.3 15.6 18.6 205

VIZZ-15150 kV BIL

*VIZZ-15G 150 kV BIL

*Single bushing

� Style with Clamp Type Primary Terminal. Stud Type available.

Mounting Base Dimensions (in.)

5756

Page 31: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

34.5 kV INDOORVOLTAGE TRANSFORMERS

TYPES VVIIZZ--2200 && VVIIZZ--2200GG PB

1VAP429601-DB

PrimaryVoltage

WindingRatio

StyleNumber

RatedVoltage Factor

Height(in.)

Width(in.)

Length(in.)

Weight(lbs.)

20125/34500Y 175:1 7883A60G0327600/27600Y 240:1 7883A60G0234500/34500Y 300:1 7883A60G01

VIZ-20Unfused

1.1 16.5 16.26 19.13 1611.1 16.5 16.26 19.13 1611.1 16.5 16.26 19.13 161

VIZ-20Fused

20125/34500Y 175:1 7883A40G0327600/27600Y 240:1 7883A40G0234500/34500Y 300:1 7883A40G01

1.1 16.5 16.26 19.13 1651.1 16.5 16.26 19.13 1651.1 16.5 16.26 19.13 165

VIZ-20GUnfused

20125/34500GY 175:1 7883A61G0134500/34500GY 300:1 7883A61G0219942/34500GY 289:1 7883A61G0416100/27900GY 240:1 7883A61G05

1.4 16.5 10.0 19.13 1481.1 16.5 10.0 19.13 1481.1 16.5 10.0 19.13 1481.4 16.5 10.0 19.13 148

VIZ-20GFused

20125/34500GY 175:1 7883A41G0134500/34500GY 300:1 7883A41G0224000/24000GY 200:1 7883A41G0525000/25000GY 208.33:1 7883A41G0626400/26400GY 220:1 7883A41G0724900/24900GY 207.5:1 7883A41G0828800/28800GY 240:1 7883A41G0927600/27600GY 240:1 7883A41G10

1.4 16.5 10.0 19.13 1501.1 16.5 10.0 19.13 1501.4 16.5 10.0 19.13 1501.1 16.5 10.0 19.13 1501.1 16.5 10.0 19.13 1501.1 16.5 10.0 19.13 1501.1 16.5 10.0 19.13 1501.1 16.5 10.0 19.13 150

10.00

19.13

8.75

12.81

NAMEPLATE

Ø.55

4-TOTAL

Mounting Base Dimensions (in.)Indoor200 kV BIL50 & 60 Hertz

Thermal Rating:1000 VA @ 30°C Ambient750 VA @ 55°C Ambient

IEEE Metering Accuracy:0.3W, X, M, Y, and Z

Fuse kit to convert unfused VIZ-20 to fused style: 9628A05G90Fuse kit to convert unfused VIZ-20G to fused style: 9628A05G83

5958

Page 32: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

6160

5 kV, 8.7 kV and 15 kVVOLTAGE TRANSFORMERS

TYPE VVOOYY--6600 PB 42-961

9.37

7.62

8.49.50

6.74

TYPE VVOOZZ--7755 aanndd VVOOZZ--1111 PB 42-963

12.12

10.75

10.00

1.25

7.37

Outdoor60 kV BIL60 Hertz

Thermal Rating:1000 VA at 30ºC ambient

Outdoor75 kV and 110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30ºC ambient

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

2400/4160Y 20:1 7525A85G01 0.3W, X, M, Y 11.69 9.62 10.75 424200/4200Y 35:1 7525A85G02 0.3W, X, M, Y 11.69 9.62 10.75 424800/4800Y 40:1 7525A85G03 0.3W, X, M, Y 11.69 9.62 10.75 42

2400/4160Y 20:1 7525A89G01 0.3W, X, M, Y, Z 15.81 11.67 13.94 744200/7280Y 35:1 7525A89G02 0.3W, X, M, Y, Z 15.81 11.67 13.94 744800/8320Y 40:1 7525A89G03 0.3W, X, M, Y, Z 15.81 11.67 13.94 747200/7200Y 60:1 7525A89G04 0.3W, X, M, Y, Z 15.81 11.67 13.94 74

7200/12470Y 60:1 7525A89G05 0.3W, X, M, Y, Z 15.81 11.67 13.94 747620/13200Y 63.5:1 7525A89G06 0.3W, X, M, Y, Z 15.81 11.67 13.94 748400/14560Y 70:1 7525A89G07 0.3W, X, M, Y, Z 15.81 11.67 13.94 7412000/12000Y 100:1 7525A89G08 0.3W, X, M, Y, Z 15.81 11.67 13.94 7413200/13200Y 110:1 7525A89G09 0.3W, X, M, Y, Z 15.81 11.67 13.94 7414400/14400Y 120:1 7525A89G10 0.3W, X, M, Y, Z 15.81 11.67 13.94 74

Mounting Base Dimensions (in.)

VOY-6060 kV BIL

VOZ-7575 kV BIL

VOZ-11110 kV BIL

Mounting Base Dimensions (in.)

Page 33: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Mounting Base Dimensions (in.)

6362

15 kV VOLTAGE TRANSFORMERS

TYPE VVOOZZ--1111MM

9.37

7.62

8.49.50

6.74

TYPE VVOOYY--1111 PB 42-964

12.12

10.75

10.00

1.25

7.37

Outdoor110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30ºC ambient

Outdoor110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30ºC ambient

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

7200/12470GY 60:1 7525A91G05 0.3W, X, M, Y, Z 15.81 12.13 13.94 747620/13200GY 63.5:1 7525A91G06 0.3W, X, M, Y, Z 15.81 12.13 13.94 748400/14560GY 70:1 7525A91G07 0.3W, X, M, Y, Z 15.81 12.13 13.94 74

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

7200/12470Y 60:1 7525A23G05 0.3W, X, M, Y 15.81 12.13 13.94 747620/13200Y 63.5:1 7525A23G06 0.3W, X, M, Y 15.81 12.13 13.94 748400/14560Y 70:1 7525A23G07 0.3W, X, M, Y 15.81 12.13 13.94 7412000/12000Y 100:1 7525A23G08 0.3W, X, M, Y 15.81 12.13 13.94 7413200/13200Y 110:1 7525A23G09 0.3W, X, M, Y 15.81 12.13 13.94 7414400/14400Y 120:1 7525A23G10 0.3W, X, M, Y 15.81 12.13 13.94 74

TYPE VVOOGG--1111 PB 42-965

10.88

7.37 1.25

10.00

9.87

Outdoor110 kV BIL60 Hertz

Thermal Rating:1000 VA at 30ºC ambient

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

7200/12470GY 60:1 7525A95G01 0.3W, X, M, Y 15.81 10.88 13.94 467620/13200GY 63.5:1 7525A95G02 0.3W, X, M, Y 15.81 10.88 13.94 468400/14560GY 70:1 7525A95G03 0.3W, X, M, Y 15.81 10.88 13.94 46

VOZ-11M110 kV BIL

Mounting Base Dimensions (in.)

Mounting Base Dimensions (in.)

VOY-11110 kV BIL

VOG-11110 kV BIL

Page 34: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

6564

25 kV VOLTAGE TRANSFORMERS

TYPE VVOOYY--1122 PB 42-966

12.12

10.75

10.00

1.25

7.37

TYPE VVOOGG--1122 PB 42-967

Outdoor125 kV BIL60 Hertz

Thermal Ratings:1000 VA at 30ºC ambient

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

12000/20780Y 100:1 7525A87G01 0.3W, X, M, Y 15.81 12.13 13.94 7414400/24940Y 120:1 7525A87G02 0.3W, X, M, Y 15.81 12.13 13.94 7418000/18000Y 150:1 7525A87G03 0.3W, X, M, Y 15.81 12.13 13.94 7424000/24000Y 200:1 7525A87G04 0.3W, X, M, Y 15.81 12.13 13.94 74

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

12000/20780GY 100:1 7525A97G01 0.3W, X, M, Y 15.81 10.88 13.94 4614400/24940GY 120:1 7525A97G02 0.3W, X, M, Y 15.81 10.88 13.94 46

VOY-12125 kV BIL

Outdoor125 kV BIL60 Hertz

Thermal Ratings:750 VA at 30ºC ambient

10.88

7.37 1.25

10.00

9.87

Mounting Base Dimensions (in.)

Mounting Base Dimensions (in.)

VOG-12125 kV BIL

Page 35: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

6766

25 kV VOLTAGE TRANSFORMERS

TYPE VVOOYY--1155 aanndd VVOOYY--1155GG PB 42-970

13.38

10.00

12.00

1.25

1.25

6.12

1.25

1.25

13.38

10.00

12.00

1.25

1.25

6.12

1.25

1.25

TYPE VVOOZZ--1155 PB 42-971

Outdoor150 kV BIL60 Hertz

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

12000/20780Y 100:1 7526A62G01 0.3W, X, M, Y 19.00 15.87 16.94 14814400/24940Y 120:1 7526A62G02 0.3W, X, M, Y 19.00 15.87 16.94 14818000/18000Y 150:1 7526A62G03 0.3W, X, M, Y 19.00 15.87 16.94 14820000/20000Y 166.7:1 7526A62G04 0.3W, X, M, Y 19.00 15.87 16.94 14824000/24000Y 200:1 7526A62G05 0.3W, X, M, Y 19.00 15.87 16.94 148

12000/20780GY 100:1 7526A63G01 0.3W, X, M, Y 19.00 13.81 16.94 14214400/24940GY 120:1 7526A63G02 0.3W, X, M, Y 19.00 13.81 16.94 142

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

12000/20780Y 100:1 7525A90G01 0.3W, X, M, Y, Z 19.00 15.87 16.94 14814400/24940Y 120:1 7525A90G02 0.3W, X, M, Y, Z 19.00 15.87 16.94 14818000/18000Y 150:1 7525A90G03 0.3W, X, M, Y, Z 19.00 15.87 16.94 14824000/24000Y 200:1 7525A90G04 0.3W, X, M, Y, Z 19.00 15.87 16.94 148

Thermal Ratings:1000 VA at 30ºC ambient

Outdoor150 kV BIL60 Hertz

Thermal Ratings:2000 VA at 30ºC ambient

VOY-15150 kV BIL

VOY-15G150 kV BIL

Mounting Base Dimensions (in.)

VOZ-15150 kV BIL

Mounting Base Dimensions (in.)

Page 36: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Primary Style IEEE MeterVoltage Ratio Number Accuracy Height Width Length Weight

27600/27600Y 240:1 7881A82G03 0.3W, X, M, Y 19.00 15.87 16.94 148

34500/34500Y 275:1 7881A82G04 0.3W, X, M, Y 19.00 15.87 16.94 148

20125/34500GY 175/300:1 7526A55G01 0.3W, X, M, Y 19.00 13.81 16.94 142

Single and Double Secondaries Available.

6968

25 kV AND 36 kVVOLTAGE TRANSFORMERS

TYPE VVOOZZZZ--1155 aanndd VVOOZZZZ--1155GG

.75 .75

1.75

1.25 1.25

1.25

1.25

1.25 1.25

1.38

.50

.75 1.13

.44

14.50

.44

15.00

.438 x 1.688 SLOTWITH .219 RADIUS6-TOTAL

Ø.438 HOLE6-TOTAL

.438 x .938 SLOTWITH .219 RADIUS4-TOTAL

.50

Outdoor150 kV BIL60 Hertz

Primary Style IEEE MeterVoltage Ratio Number � Accuracy Height Width Length Weight

12000/20800Y 100:1 7525A93G01 0.3W, X, M, Y, Z,ZZ 23.0 16.1 17.6 205

14400/24940Y 120:1 7525A93G02 0.3W, X, M, Y, Z,ZZ 23.0 16.1 17.6 205

18000/18000Y 150:1 7525A93G03 0.3W, X, M, Y, Z,ZZ 23.0 16.1 17.6 205

24000/24000Y 200:1 7525A93G04 0.3W, X, M, Y, Z,ZZ 23.0 16.1 17.6 205

12000/20800GY 100:1 7525A98G01 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

14400/24940GY 120:1 7525A98G02 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

Thermal Ratings:3000 VA at 30ºC Ambient

VOZZ-15150 kV BIL

VOZZ-15G 150 kV BIL

Single Bushing

Available with double secondaries andtapped double secondaries.

� Style includes clamp type primary terminals. Stud type available for spade terminals.

Outdoor200 kV BIL60 Hertz

VOY-20G200 kV BIL

13.38

10.00

12.00

1.25

1.25

6.12

1.25

1.25

Mounting Base Dimensions

TYPE VVOOYY--2200 aanndd VVOOYY--2200GG PB 42-974

Mounting Base Dimensions (in.)

Thermal Ratings:1000 VA at 30ºC Ambient

VOY-20200 kV BIL

Page 37: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

Mounting Base Dimensions

Primary Style IEEE MeterVoltage Ratio Number� Accuracy Height Width Length Weight

27600/27600Y 240 & 240:1 9629A96G02 0.3W, X, M, Y, 26.0 18.1 24.3 380Z, ZZ

34500/34500Y 300 & 300:1 9629A96G01 0.3W, X, M, Y, 26.0 18.1 24.3 380Z, ZZ

20125/34500GY 175/300:1 9629A97G01 0.3W, X, M, Y, 26.7 17.0 24.3 380& 175/300:1 Z, ZZ

20125/34500GY 175/300:1 7882A42G01 0.3W, X, M, Y, 26.7 17.0 24.3 380Z, ZZTapped and Single Secondaries Available

7170

15.50

17.87

8.25

16.50

20.50

Outdoor200 kV BIL60 Hertz

Thermal Ratings:3000 VA at 30ºC Ambient

� Style includes clamp type primary terminals. Stud type available for spade terminals.

TYPE VVOOZZZZ--2200 aanndd VVOOZZZZ--2200GG PB 42-979

7.37

14.74

5.12

4.79

12.75

16.75

17.50

Outdoor200 kV BIL60 Hertz

Primary Style IEEE MeterVoltage Ratio Number� Accuracy Height Width Length Weight

20125/34500Y 175/300:1 7882A31G01 0.3W, X, M, Y 22.6 18.9 20.0 255Full and Tap

27600/27600Y 240/400:1 7882A31G02 0.3W, X, M, Y 22.6 18.9 20.0 255Full and Tap

34500/34500Y 300/500:1 7882A31G03 0.3W, X, M, Y 22.6 18.9 20.0 255Full and Tap

20125/34500GY 175/300:1 9629A95G01 0.3W, X, M, Y 23.3 16.1 20.0 245Full and Tap

Thermal Ratings:1000 VA at 30ºC Ambient

36 kV VOLTAGE TRANSFORMERS

TYPE VVOOHHDD--220000 AANNDD VVOOHHDD--220000GG PB 42-977

Mounting Base Dimensions

VOZZ-20200 kV BIL

VOZZ-20G200 kV BIL

VOHD-200200 kV BIL

VOHD-200G200 kV BIL

Page 38: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

7372

AAPPPPLLIICCAATTIIOONN DDAATTAA

Continued on Next Page

Lin

e

Vo

lta

ge

Prim

ary

Se

co

nd

ary

Vo

lta

ge

Tra

nsfo

rme

r

Prim

ary

Se

co

nd

ary

R

R

Vo

ltm

ete

r

Vo

lta

ge

Re

lay

Wa

tt-H

ou

r M

ete

r

Cu

rre

nt

Re

lay A

mm

ete

r

Po

larity

Ma

rk

Lo

ad

Cu

rre

nt

Cu

rre

nt

Tra

nsfo

rme

r

To

Lo

ad

INS

TRU

ME

NT

TRA

NS

FOR

ME

RS

isol

ate

met

ers

or

othe

r in

stru

men

ts

from

hi

gh

volta

ges

and

curr

ents

and

tra

nsfo

rms

them

(i.e

., st

ep-d

own)

to

va

lues

w

here

th

ey

can

be

mea

sure

d by

stan

dard

met

ers.

All

inst

rum

ent

trans

form

ers

are

clas

sifie

d as

eith

er

curr

ent

trans

form

ers

or

volta

getra

nsfo

rmer

s.

They

ar

e us

ed

for

reve

nue

met

erin

g an

d al

so w

ith r

elay

s an

d in

dica

ting

inst

rum

ents

.

Cur

rent

Tra

nsfo

rmer

s (C

T)Th

e pr

imar

y w

indi

ngs

of c

urre

nt tr

ansf

orm

ers

are

conn

ecte

d in

se

ries

with

th

e lin

e an

d th

eir

seco

ndar

ies

conn

ecte

d to

the

cur

rent

coi

ls o

rel

emen

ts o

f m

eter

s, r

elay

s or

ins

trum

ents

. A

llst

anda

rd c

urre

nt t

rans

form

ers

have

a 5

Am

pere

rate

d se

cond

ary

rega

rdle

ss

of

thei

r pr

imar

ycu

rren

t.

Eac

h cu

rren

t tra

nsfo

rmer

ha

s sp

ecifi

catio

nsba

sed

on c

ontin

uous

cur

rent

, sho

rt tim

e cu

rren

t,an

d m

echa

nica

l stre

ss.

Ther

e ar

e tw

o ac

cura

cy

clas

sific

atio

ns:

one

for

met

erin

g an

d on

e fo

rre

layi

ng.

The

met

erin

g ac

cura

cy c

lass

ifica

tion

tells

wha

t err

or in

tran

sfor

mat

ion

can

be e

xpec

ted

at

norm

al

curr

ents

. Th

e re

layi

ng

accu

racy

clas

sific

atio

n te

lls w

hat p

erce

nt a

ccur

acy

can

beex

pect

ed w

hen

the

seco

ndar

y is

cal

led

upon

to

indu

ce a

cer

tain

vol

tage

.

The

seco

ndar

y of

the

curr

ent t

rans

form

er s

houl

dal

way

s be

con

nect

ed to

a lo

ad (

burd

en)

or s

hort

circ

uite

d. I

f th

e se

cond

ary

is o

pen

circ

uite

d, t

hetra

nsfo

rmer

may

dev

elop

a d

ange

rous

ly h

igh

seco

ndar

y vo

ltage

.

Rat

ing

Fact

or: T

he fa

ctor

by

whi

ch th

e na

mep

late

prim

ary

curr

ent

of a

CT

is m

ultip

lied

to o

btai

nm

axim

um p

rimar

y cu

rren

t th

at c

an b

e ca

rrie

dco

ntin

uous

ly

with

out

exce

edin

g th

e lim

iting

tem

pera

ture

rise

. The

acc

urac

y cl

ass

at th

e ra

ting

fact

or p

oint

sho

uld

be th

e sa

me

as a

t nam

epla

tera

ting.

Volta

ge T

rans

form

ers

(VT)

The

prim

ary

win

ding

s of

vol

tage

tran

sfor

mer

s ar

e

conn

ecte

d ac

ross

the

line

. Th

ey s

tep

dow

n th

elin

e vo

ltage

to

a

valu

e su

itabl

e fo

r st

anda

rdm

eter

s, n

orm

ally

115

Vol

ts o

r 120

Vol

ts.

In b

asic

con

stru

ctio

n, v

olta

ge t

rans

form

ers

are

muc

h lik

e di

strib

utio

n tra

nsfo

rmer

s ex

cept

tha

tth

e cu

rren

t an

d th

e kV

Aca

paci

ty a

re v

ery

low

.Th

ey a

re d

esig

ned

to g

ive

an a

ccur

ate

volta

getra

nsfo

rmat

ion.

Sele

ctio

nA

num

ber

of

cons

ider

atio

ns

are

invo

lved

in

sele

ctin

g pr

oper

in

stru

men

t tra

nsfo

rmer

sin

clud

ing:

sy

stem

vo

ltage

, B

IL,

load

cu

rren

t,ra

ting

fact

or a

nd a

ccur

acy

clas

s at

spe

cifie

dbu

rden

s. P

hysi

cal r

equi

rem

ents

suc

h as

indo

or o

rou

tdoo

r ins

talla

tion,

win

dow

or b

ar ty

pe (f

or 6

00 V

CTs

), an

d w

indo

w d

iam

eter

are

als

o im

porta

nt.

Man

y of

th

e tra

nsfo

rmer

ty

pes

liste

d in

th

isca

talo

g ha

ve

som

e ch

arac

teris

tics

that

ar

edu

plic

ated

in o

ther

type

s lis

ted,

but

eac

h ty

pe h

asits

ow

n un

ique

com

bina

tion

of fe

atur

es th

at b

est

mee

t the

app

licat

ion

for w

hich

it w

as d

esig

ned.

Pola

rity:

Des

igna

tion

of th

e re

lativ

e in

stan

tane

ous

dire

ctio

ns o

f the

cur

rent

s en

terin

g th

e pr

imar

y le

ads

and

leav

ing

the

seco

ndar

y le

ads.

Whe

n cu

rren

t is

flow

ing

tow

ard

the

mar

ked

prim

ary

lead

, it i

s flo

win

g aw

ayfr

omth

e tra

nsfo

rmer

in th

e m

arke

d se

cond

ary

lead

.

Page 39: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

0 10 20 30 40 50 600

50

100

150

200

250

300

350

400

450

500

1.0

1.33

1.5

2.0

3.0

4.0

Pe

rce

nt

of

rate

d p

rim

ary

cu

rre

nt

Curve designations arecontinuous thermal current rating factorsat 30°C ambient air temperature.

Average Ambient Cooling air temperature for 24

hour period, degrees C

(Maximum ambient air temperature shall not exceed

average by more than 10°C.)

Typical burden value (per stator) ELSTER Type

AB Polyphase MetersClass 20 Transformer

Rated

Potential coil (per stator) at the rated Voltage.

4.2 VA at 0.18 x PF lagging

Current coil (per stator)1.1 VA at 0.22 x PF lagging

Resistance of coppersecondary wire in ohms

per 1000 feet at 68°F(20°C).

Wire Size Ohms

14 2.525012 1.588010 0.99898 0.6282

7574

AAPPPPLLIICCAATTIIOONN DDAATTAA

AMPERE CAPACITYOF INSULATED CONDUCTORS

Single Conductor In Free Air At 30° C (86° F)

COMMON ELECTRICAL TERMS

Ampere (I) = Unit of current or rate of flow of electricityVolt (E) = Unit of electromotive forceOhm (R) = Unit of resistanceOhm's Law E = IRVolt Amperes (VA) = Unit of apparent power

= El (single phase)= E x I x 1.73 ( 3 phase)

Kilovolt Amperes (kVA) = 1000 Volt-AmperesWatt W = Unit of true power

= VA x p-f= .00134 hp

Kilowatt (kW) = 1000 wattsPower Factor (p-f) = ratio of true to apparent power

W kW= orVA kVA

Watthour (WHR) = unit of electrical work= one watt for one hour= 3.413 Btu= 2.655 ft. lbs.

Kilowatthour (kWHR) = 1000 watthoursHorsepower (hp) = Measure of time rate of doing work

= Equivalent of raising 33,000 lbs. one ft.in one minute

= 746 wattsDemand Factor = Ratio of maximum demand to the total

connected loadDiversity Factor = Ratio of the sum of individual maximum

demands of the various subdivisions ofa system to the maximum demand of thewhole system

Load Factor = Ratio of the average load over adesignated period of time to the peak loadoccurring in that period

Types RUW Types RHSize T RHWAWG Approximate TW RUH

or Diameter THWMCM (inches) Cu AI Cu AI

6 .397 80 60 95 754 .452 105 80 125 1003 .481 120 95 145 1152 .513 140 110 170 1351 .588 165 130 195 155

0 .629 195 150 230 18000 .675 225 175 265 210

000 .727 260 200 310 2400000 .785 300 230 360 280

250 .868 340 265 405 315300 .933 375 290 445 350350 .985 420 330 505 395400 1.032 455 355 545 425500 1.119 515 405 620 485

600 1.233 575 455 690 545700 1.304 630 500 755 595750 1.339 655 515 785 620800 1.372 680 535 815 645900 1.435 700 580 870 700

1000 1.494 780 625 935 7501250 1.676 890 710 1065 8551500 1.801 980 795 1175 9501750 1.916 1070 875 1280 10502000 2.021 1155 960 1385 1150

CALCULATION OF LINE AMPERESON POLYPHASE CIRCUITS

Amps = Load kVA x 1000

1.732 x Line-to-Line Voltage

Applicable to both 3-phase, 3-wire delta and3-phase, 4-wire wye.

REQUIRED DIAMETER OF CT WINDOWFOR MULTIPLE CONDUCTOR

Number ofPrimary MinimumConductors Window Diameter

2 2.00 x Conductor O.D.3 2.16 x Conductor O.D.4 2.42 x Conductor O.D.5 2.70 x Conductor O.D.

Page 40: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

7776

AACCCCUURRAACCYY SSTTAANNDDAARRDDSSCurrent Transformers

The accuracy classification of current transformers for metering service includes acorrelation between ratio correction factor and phase angle so as to show the overalleffect on watthour meter registration. The classification is based on the requirement thatthe transformer correction factor (the correction for overall error due to both ratio errorand phase angle) be within the limits specified. For any particular accuracy class the ratiocorrection factor and phase angle must fall within the parallelograms for 100% and 10%current respectively.

For example, the overall correction will never exceed .3% at 100% rated current fora transformer in the 0.3 accuracy class. If the ratio correction factor is 1.003 themaximum allowable phase angle is +15.6 minutes. The transformer correction factor is:

The corresponding ratio correction factor and phase angle for any point inside the 0.3class parallelogram for 100% rated current will always give a transformer correctionfactor between .997 and 1.003.

Standard Burden Characteristics 60 Hz and 5 Ampere secondary

Burden Resistance Inductance Impedance Volt- PowerDesignation Ohms Millihenrys Ohms Amperes Factor

Metering Burdens

B-0.1 0.09 0.116 0.1 2.5 0.9B-0.2 0.18 0.232 0.2 5.0 0.9B-0.5 0.45 0.580 0.5 12.5 0.9B-0.9 0.81 1.040 0.9 22.5 0.9B-1.8 1.62 2.080 1.8 45.0 0.9

Relaying Burdens

B-1 0.5 2.3 1.0 25 0.5B-2 1.0 4.6 2.0 50 0.5B-4 2.0 9.2 4.0 100 0.5B-8 4.0 18.5 8.0 200 0.5

*Based on .6 Power Factor (lagging) of metered load.

Standard Burdens

Burden Designation Secondary Volt-Amperes Burden Power Factor

W 12.5 0.10X 25.0 0.70M 35.0 0.20Y 75.0 O.85Z 200.0 O.85ZZ 400.0 0.85

Limits of Transformer Correction Factor (TCF)

Limits of PowerAccuracy Minimum Maximum Factor of Metered

Class Load-Lagging

minimum maximum

1.2 0.988 1.012 0.6 1.00.6 0.994 1.006 0.6 1.00.3 0.997 1.003 0.6 1.0

*TCF =

=

=

RCF - β

2600

1.003 -2600

15.6

.997

0.3 class-10%rated current

0.3 class-100%rated current

0.6 class-100%rated current

to meet 0.3 accuracy class, the ratio and phase angle at the given burden must fallwithin this parallelogramat 100% rated current

and within this parallelogram at 10% rated current

ratio correction factor (RCF)

phase angleminutes-lagging

phase angleminutes-leading

+10

1.00

+20 +30-10-20-30

.997

0

1.003

1.006

.994

Voltage TransformersThe accuracy classification of voltage transformers for metering service includes a

correlation between ratio correction factor and phase angle so as to show the overalleffect on watthour meter registration. The classification is based on the requirement thatthe transformer correction factor (the correction for overall error due to both ratio errorand phase angle) be within the limits specified. For any particular accuracy class the ratiocorrection factor and phase angle must fall within the parallelogram. These limits applyover the voltage range of ± 10% of the rated voltage at rated frequency.

For example, the overall correction will never exceed .3% for a transformer in the 0.3accuracy class. If the ratio correction factor is 1.003 the maximum allowable phase angleis - 15.6 minutes. The transformer correction factor is:

The corresponding ratio correction factor and phase angle for any point inside the 0.3class parallelogram will always give a transformer correction factor between .997 and1.003.

*TCF =

=

=

RCF + γ

2600

1.003 +2600

-15.6

.997

Equivalent Parallelogram

phase angleminutes-lagging

phase angleminutes-leading

0.6 accuracy classparallelogram

0.3 accuracy classparallelogram

ratio correction factor (RCF)

.994

1.006

1.003

0

.997

-30 -20 -10 +30+20+10

Equivalent Parallelogram

Page 41: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

7978

IITT TTYYPPEE DDEESSIIGGNNAATTIIOONNSSKEY TO TYPE DESIGNATIONS

600 V IMC ECI C = CT, 600 V, meteringCTs CBT-1 RTM accuracy

CBT-H None I = CT, 600 V, IndicatingCMV CRA R = CT, 600 V, RelayingCMF CTR (burden capabilityCSF CSB exceeds normalCSH None metering requirements.)CMS CSB (Lg.)CLC CLA (51/2")CLE CLA (81/4")RLC EMC

600 V PPW PPI/EMP P=VT, 600 VVTs PPM PXA (+)

5 kV-25 kV

CTs KIR 60-11 CTM 5-15KIT 60-11 UP 5-15KOR 60-11 CTOM 5-15KON 11 CTOM 110KOR 15 CCO 150KOT 60-11 EMC 5-15

VTs VIY 60 PC 60 V=VT, > 600 VVOY 60 PCO 60VIZ 75, 11 PTM 75, 100VOZ 75, 11 PTOM 75, 110VOG 11 NoneVOZ 15 PTOM 150VIZZ 15 PT 25

2nd PPosition 33rd PPosition

Window Size Letters SCALE give a closer approximationof window diameter in inches.S C A L E

S = Small 1"-2" 1 11/4 11/2 13/4 2M=Medium 2"-5" 2 21/2 31/4 4 5

L= Large 5"-81/4" 5 51/2 61/2 71/2 8 1/4

G= Gt. > 81/4" F = Family of window sizes i.e., CMF withB=Bar 21/2" & 31/16" windows

V = OvalT = Thru typeH = 0.5 (Half) Ohm Burden

P = Performance I = IndicatingM = .3 accuracy@ 35 VA

4th & 5th Position

I = Indoor N = 0.3B0.5 Perf. 60 = 60 kV BIL0 = Outdoor P = 0.3B0.9 Perf. 75 = 75 kV BIL

R = 0.3B1.8 Perf. 11 = 110 kV BILT = Thru Type 15 = 150 kV BIL

20 = 200 kV BIL

I = Indoor Y = .3 accuracy Same as above0 = Outdoor @ 75 VA

Z = .3 accuracy@ 200 VAG = Single bushingfor line to groundconnection

GEC KulhmanABB Type Durham G.E.Type Schlumberger ABB Type G.E. Type TypeIMC - JCH-0C -CBT/1 TCB JGT-0C R6BA KIR-60,75, 11 JKM-3, 4, 5 -CBT-H TAB JCM-0C R6B KOR-60,75, 11 JKW-3, 4, 5 BB-15-971

600 V CSF TCW JCR-0C R6SA 5-36 kV KON-11 JCK-5 BB-15-972Current CSH TFW JCW-0C R6S Current KON-12 - -Transformers CMF AB JAK-0C R6M Transformer KOR-12 - -

CMV AP JAB-0C R6P KOR-15 JKW-6 BB-25-973CLC AD JAD-0C R6L KOT-60,75, 11 JCD-3, 4, 5 -CLE ACL JCD-0C - KIT-60,75, 11 JCM-3, 4, 5 -RLC AD JCP-0C - KOR-20 JKW-7 BB-34-975/6

KOTD-150,200 JKW-150, 200 -

VIY-60 JVM-3 -VIZ-75, 11 JVM-4, 5 -VOY-60 JVW-3 -VOY-11 JVW-110 PTT-110-977VOZ-75, 11 JVW-4, 5 PTT-110-978

600 V PPW DF None T5R 5-36 kV VOG-11 JVW-110 PTT-110-977GVoltage PPM DA JVA-0 (0.3M only) T6R Voltage VOZ-11M JVW-5 (1 bushing) PTT-110-978GTransformers PPX - None - Transformers VOY, VOG-12 JVW-6 -

VOY-15, 15G JVW-7 (2 bushings) PTT-150-979/GVOZ-15 - -VOHD 200, 200G JVW-7 (1 bushing) PTT-200-9710/GVOZZ-15, 20 JVT 150, 200 -VOZZ-15G, 20G JVS 150, 200 -

CCRROOSSSS RREEFFEERREENNCCEE of Most Commonly Used Types

Page 42: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

NOTES: NOTES:

Page 43: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

NOTES: NOTES:

Page 44: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

NOTES:

Page 45: 1VAP420001-TG Instrument Transformer Reference Guide · Primary Current Type Product Bulletin Page No. 600 VOLT CURRENT TRANSFORMERS GENERAL INDEX GUIDE 600 VOLT VOLTAGE TRANSFORMERS

1VAP

4200

01-T

G Re

v. E

March

200

5 (re

place

s SA1

1081

F fil

e No

. 42-

000)

ABB Inc.3022 NC 43 NorthPinetops, NC 27864 USAFor sales and marketing, contact your localrepresentative or:Tel: +1-252-827-3212Fax: +1-252-827-4286www.abb.com/mediumvoltage