Page 1: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 1 of 26

SIPROTEC 4

Distance Protection

7SA6

Page 2: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 2 of 26

What is SIPROTEC 4?

SIPROTEC 4

is the family of numerical

Protection, Control and Substation Automation devices

by

SIEMENS

Page 3: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 3 of 26

The protection functions are not new!

They were therefor largely taken over from existing devices.

What is SIPROTEC 4?

Page 4: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 4 of 26

The optional integrated local and remote control

SIPROTEC 4 What makes these devices so attractive ?

Page 5: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 5 of 26

Additional functions

Interlocking Processing of

measured values

Log. IN 1

Log. IN 2

Log.IN3

Logic inputs to the CFC from the Matrix

Logic outputs to the matrix

F1

F2

>1

CFC

Log.OUT1

SIPROTEC 4 What makes these devices so attractive ?

The ability to integrate

bay level interlocking

Page 6: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 6 of 26

The comprehensive measured

value processing

I1 :400.9A f:50.0HzU1:12.22kVP :+8.03MW cosQ :+2.64MVar

L1 402.1A Max450.1A L2 401.2A Max421.2AL3 401.0A Max431.4AE 00.0A

% IL UL-E UL-LL1 100.0 100.4 100.1L2 100.4 100.3 100.0L3 100.1 100.1 100.4

SIPROTEC 4 What makes these devices so attractive ?

Page 7: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 7 of 26

The connection of switchgear

without interposing

devices

SIPROTEC 4 What makes these devices so attractive ?

Page 8: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 8 of 26

The robust terminals

SIPROTEC 4 What makes these devices so attractive ?

Page 9: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 9 of 26

The flexible communication interfaces

as Fibre Optic

or electrical

exchange retrofit

SIPROTEC 4 What makes these devices so attractive ?

Page 10: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 10 of 26

SIPROTEC 4 What makes these devices so attractive ?

The user friendly

operation with DIGSI 4

Page 11: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 11 of 26

Distance protection: Presence and Future

7SA6

Experience

7SA510

7SA5117SA513

Requi

rem

ents

SIPROTEC 4

7SA522 7SJ63Syste

m

SIPROTEC 4Hardware Modules

Variability

Page 12: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 12 of 26

SIPROTEC 4 Distance protection 7SA6

7SA6 Distance protection for

all voltage levels

Page 13: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 13 of 26

SIPROTEC 4 Distance protection 7SA6

Protection and automation

4-line display

Full functionality in all housing options!

Page 14: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 14 of 26

SIPROTEC 4 Distance protection 7SA6

Protection, automation and

local control

Integrated graphic display

Full functionality in all housing options!

Page 15: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 15 of 26

SIPROTEC 4 Distance protection 7SA6

Protection, automation local control

detached HMI

Full functionality in all housing options!

Page 16: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 16 of 26

Fault locator20mA, BCD

SIPROTEC 4Distance protection 7SA6

Non-switched distance protection

Earth fault detection (isolated/compensated

systems)

Automaticreclosure

Breaker Fail protection

2-stageSynchro check

Voltage protection

Earth fault (short circuit) protection

Page 17: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 17 of 26

SIPROTEC 4Distance protection 7SA6 - functions

52Local/Tele Ctrl.

Commands

CB Indications

74TC

Trip Circuit

supervision

86

Lockout

21

Distance

21N

6868T

Power

Swing

FL

Fault

Locator

50N51N

Gnd

O/C

67N

Directional

Ground

5051

Over-

current

50N-251N-2

85-21

Pilot

Dist.

85-67N

Pilot

Gnd

50HS

Switch

onto-

Flt. O/C

50STUB

STUB

O/C

Weak

infeed

27WI 25

Synchro-

check

79Auto-

reclosure

59

Over-

voltage

50BF

Bkr.

fail.

Operat.

values

Super-

visionPilot schemes can use

one channel or two

redundant channels to

the remote end

Serial Communication

Interfaces

CFC Logic

Note: Pilot schemes = Teleprotection

Page 18: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 18 of 26

SIPROTEC 4Distance protection 7SA6 - Highlights

7SA6 = Distance protection range for MV, HV and EHV

7SA6 includes all the functions of 7SA511/510 and 7SA513 Distance protection always with 6 measuring systems, fault detection selectable as

either I>, Z<, U/I and U/I/ Can be applied in systems with compensated, isolated or solid earthing Scope of functions and measurements increased in comparison with 7SA51

Housing and input/output version for each application

All protection functions are available in all housing versions

SIPROTEC 4 = Programmable logic, control, interlocking local control is optional

SIPROTEC 4 = Communication interfaces Various tele-control protocols and physical connections options are available Via serial interface, tele-prot. can be implemented with standard comms. networks

(G703, V11/X21) or async. direct connection (not available at product launch)

Page 19: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 19 of 26

SIPROTEC 4Cost optimised protection schemes

Fully redundant 2 communication channels Direct coupling (G703,V11/X24)(in preparation)

7SD52

7SA6

7SD52

7SA6

Channel1

Channel2

DIF

DIS

7SD52

7SA

7SD52

7SA

Channel

Contacts Contacts1 Communication channel Distance protection coupling to 7SD52

with signal transfer via contacts

DIF

DIS

Page 20: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 22 of 26

7SA6Some enhancements

Distance protection always with 6 measuring systems, fault detection I>, Z<, U/I or U/I/

very fast tripping timesvery good selectivity and system stability

Automatic reclosure with additional functions DLC (closing only when there is no voltage on the line) ADT (closing only when reclosure at remote end is successful) RDT (shortened dead time following TRIP by overreaching zone)Saves plant and avoids unnecessary dead times

Operational measured values comprehensive selection of measurands, tolerance <1%Measurement transducers are no longer required

Page 21: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 23 of 26

Coupling to conventional Tele-control 20mA interface for analogue measured value and fault location output BCD-Measured value and fault location output 7SA6 is perfectly suited for integration in existing substations

Breaker failure protection, 2-stage

Back-up earth fault protection for earthed systems 4-stage, sensitivity 0,5% IN high sensitivity and selectivity, also in the event of high resistance faults

Voltage protection U> and U< ULE, ULL, U0, U1, U2

Non-conventional Instrument transformer inputs* and Process bus connection *

security of investment * Funktionalität ist in Vorbereitung

7SA6 Some enhancements

Page 22: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 24 of 26

7SA62Housing 1/1

7SA61Housing 1/2

7SA610Housing 1/3

7SA6 SIPROTEC 4 with Distance protection

7SA61 Protection 4-line display MV, HV and EHV

7SA6127SA6117SA610

7SA63 Protection + local control integrated graphic display mainly MV

7SA6327SA631

7SA64 Protection + local control detached control panel mainly MV

7SA6427SA641All functions are available in all the housing versions

Page 23: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 25 of 26

Automatic reclosure (AR)

CLOSE

TRIP2 nd

Dead Timet1st

TRIP1-pole3-pole

1stDead Time

CLOSE

*CLOSE

t2nd

TRIP

tgrading

ADT = Close if 1st reclose at remote end is successfulDLC = Close if there is no voltage on the lineRDT = shortened dead time after non-selective TRIP

TRIP final

*

SIPROTEC 4Distance protection 7SA6

Page 24: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 26 of 26

newnew

newnewnewnew

newnew

newnew

newnew

newnew

Distance Protection SIPROTEC 4 Auto-Reclosure (1)

Up to 8 independent ARC cycles can be selected

Mode selection ´only 1 pole´ / ´1-3 pole´ / ´only 3 pole´ Operating mode selectable for each cycle

Support of various operating modes: Auto-reclose cycle initiation by fault detection / trip command

DLC: Dead Line Check

ADT: Adaptive Dead Time

RDT: Reduced Dead Time for Z1B-trip with external fault

Integrated monitoring of initiate conditions

Reclose cycles with and without action time supervision

Page 25: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 27 of 26

newnew

newnew

newnew

newnew

newnew

Distance Protection SIPROTEC 4 Auto-Reclosure (2)

Remote close command from ARC master to opposite line end

Separate dead times for all ARC cycles

Three pole coupling of trip command for implausibility

Integrated dead time monitoring

Integrated circuit breaker monitoring and plausibility check

Integrated evolving fault recognition and treatment

Automatic blocking of the ARC following manual close or open CB condition

Initiation of ARC by internal or external functions

Support of 1 ½ and double circuit breaker applications

Page 26: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 28 of 26

Slave provides close command when: the remote close command is received from the master (remote station) or healthy voltage (3-phasig) is measured for

a settable time CB-ready state prevails (selectable) Sync-check release was given (selectable)

Distance Protection SIPROTEC 4 Auto-Reclosure with ADT*

SS1 SS2

Slave im ASP-ModusMaster im Normalbetrieb

* Adaptive Dead Time, patent pending

ADT*-Advantages

No repeated closure onto faults (improved system stability)

Reduces stress of CB poles (longer maintenance cycles)

Page 27: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 29 of 26

SIPROTEC 47SA61 - I/O capability

The distance protection range 7SA61 is available with the following I/O versions:

Front interface with 4-line back-lit display, numerical keypad, LED‘s, Function keys and PC-serial interface

7SA

610*

-*A

7SA

610*

-*B

7SA

611*

-*A

7SA

611*

-*B

7SA

612*

-*A

7SA

612*

-*B

7SA

612*

-*C

Housing width (x 19“) 1/31/3 ½ ½ 1/1

1/11/1

Binary inputs 5 7 13 20 21 29 33Live contact 1 1 1 1 1 1 1Binary outputs/trip/alarm relays 8 5 16 8 24 32 11Power relays for direct control of motorised isolators 0 0 0 4 0 0 8LED’s for indication of Event status 7 7 14 14 14 14 14LED’s for indication of device ready status 2 2 2 2 2 2 2Current transformer 4 4 4 4 4 4 4Voltage transformer 4 4 4 4 4 4 4High speed tripping relays 20mA analogue output (ordering option)

Page 28: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 30 of 26

SIPROTEC 47SA63 - Mengengerüst

The distance protection range 7SA63 is available with the following I/O versions:

Front interface with large back-lit graphic display for bay mimic diagram, numerical keypad, LED‘s control keys, key switches, Function keys and PC-serial interface

7S

A6

31

*-*A

7S

A6

31

*-*B

7S

A6

32

*-*A

7S

A6

32

*-*B

7S

A6

32

*-*C

Housing width (x 19“) ½ ½ 1 /11 /1

1 /1Binary inputs 13 20 21 29 33Live contact 1 1 1 1 1Binary outputs/trip/alarm relays 16 8 24 32 11Power relays for direct control of motorised isolators 0 4 0 0 8LED’s for indication of Event status 14 14 14 14 14LED’s for indication of device ready status 2 2 2 2 2Current transformer 4 4 4 4 4Voltage transformer 4 4 4 4 4High speed tripping relays 20mA analogue output (ordering option)

Page 29: 20 Distance Protection EV S V1 Bl. 1 of 26 SIPROTEC 4 Distance Protection 7SA6

Distance Protection EV S V1Bl. 31 of 26

SIPROTEC 47SA64 - Mengengerüst

The distance protection range 7SA64 is available with the following I/O versions:

Device with detached HMI for Mounting in the back of the control cubicle with large back-lit graphic display for bay mimic diagram, numerical keypad, LED‘s, Control keys, Key switches, Function keys and PC-serial interface

7S

A6

41

*-*A

7S

A6

41

*-*B

7S

A6

42

*-*A

7S

A6

42

*-*B

7S

A6

42

*-*C

Housing width (x 19“) ½ ½1/1

1/1

1/1

Binary inputs 13 20 21 29 33Live contact 1 1 1 1 1Binary outputs/trip/alarm relays 16 8 24 32 11Power relays for direct control of motorised isolators 0 4 0 0 8LED’s for indication of Event status 14 14 14 14 14LED’s for indication of device ready status 2 2 2 2 2Current transformer 4 4 4 4 4Voltage transformer 4 4 4 4 4High speed tripping relays 20mA analogue output (ordering option)