Distance Protection EV S V1Bl. 1 of 26
SIPROTEC 4
Distance Protection
7SA6
Distance Protection EV S V1Bl. 2 of 26
What is SIPROTEC 4?
SIPROTEC 4
is the family of numerical
Protection, Control and Substation Automation devices
by
SIEMENS
Distance Protection EV S V1Bl. 3 of 26
The protection functions are not new!
They were therefor largely taken over from existing devices.
What is SIPROTEC 4?
Distance Protection EV S V1Bl. 4 of 26
The optional integrated local and remote control
SIPROTEC 4 What makes these devices so attractive ?
Distance Protection EV S V1Bl. 5 of 26
Additional functions
Interlocking Processing of
measured values
Log. IN 1
Log. IN 2
Log.IN3
Logic inputs to the CFC from the Matrix
Logic outputs to the matrix
F1
F2
>1
CFC
Log.OUT1
SIPROTEC 4 What makes these devices so attractive ?
The ability to integrate
bay level interlocking
Distance Protection EV S V1Bl. 6 of 26
The comprehensive measured
value processing
I1 :400.9A f:50.0HzU1:12.22kVP :+8.03MW cosQ :+2.64MVar
L1 402.1A Max450.1A L2 401.2A Max421.2AL3 401.0A Max431.4AE 00.0A
% IL UL-E UL-LL1 100.0 100.4 100.1L2 100.4 100.3 100.0L3 100.1 100.1 100.4
SIPROTEC 4 What makes these devices so attractive ?
Distance Protection EV S V1Bl. 7 of 26
The connection of switchgear
without interposing
devices
SIPROTEC 4 What makes these devices so attractive ?
Distance Protection EV S V1Bl. 8 of 26
The robust terminals
SIPROTEC 4 What makes these devices so attractive ?
Distance Protection EV S V1Bl. 9 of 26
The flexible communication interfaces
as Fibre Optic
or electrical
exchange retrofit
SIPROTEC 4 What makes these devices so attractive ?
Distance Protection EV S V1Bl. 10 of 26
SIPROTEC 4 What makes these devices so attractive ?
The user friendly
operation with DIGSI 4
Distance Protection EV S V1Bl. 11 of 26
Distance protection: Presence and Future
7SA6
Experience
7SA510
7SA5117SA513
Requi
rem
ents
SIPROTEC 4
7SA522 7SJ63Syste
m
SIPROTEC 4Hardware Modules
Variability
Distance Protection EV S V1Bl. 12 of 26
SIPROTEC 4 Distance protection 7SA6
7SA6 Distance protection for
all voltage levels
Distance Protection EV S V1Bl. 13 of 26
SIPROTEC 4 Distance protection 7SA6
Protection and automation
4-line display
Full functionality in all housing options!
Distance Protection EV S V1Bl. 14 of 26
SIPROTEC 4 Distance protection 7SA6
Protection, automation and
local control
Integrated graphic display
Full functionality in all housing options!
Distance Protection EV S V1Bl. 15 of 26
SIPROTEC 4 Distance protection 7SA6
Protection, automation local control
detached HMI
Full functionality in all housing options!
Distance Protection EV S V1Bl. 16 of 26
Fault locator20mA, BCD
SIPROTEC 4Distance protection 7SA6
Non-switched distance protection
Earth fault detection (isolated/compensated
systems)
Automaticreclosure
Breaker Fail protection
2-stageSynchro check
Voltage protection
Earth fault (short circuit) protection
Distance Protection EV S V1Bl. 17 of 26
SIPROTEC 4Distance protection 7SA6 - functions
52Local/Tele Ctrl.
Commands
CB Indications
74TC
Trip Circuit
supervision
86
Lockout
21
Distance
21N
6868T
Power
Swing
FL
Fault
Locator
50N51N
Gnd
O/C
67N
Directional
Ground
5051
Over-
current
50N-251N-2
85-21
Pilot
Dist.
85-67N
Pilot
Gnd
50HS
Switch
onto-
Flt. O/C
50STUB
STUB
O/C
Weak
infeed
27WI 25
Synchro-
check
79Auto-
reclosure
59
Over-
voltage
50BF
Bkr.
fail.
Operat.
values
Super-
visionPilot schemes can use
one channel or two
redundant channels to
the remote end
Serial Communication
Interfaces
CFC Logic
Note: Pilot schemes = Teleprotection
Distance Protection EV S V1Bl. 18 of 26
SIPROTEC 4Distance protection 7SA6 - Highlights
7SA6 = Distance protection range for MV, HV and EHV
7SA6 includes all the functions of 7SA511/510 and 7SA513 Distance protection always with 6 measuring systems, fault detection selectable as
either I>, Z<, U/I and U/I/ Can be applied in systems with compensated, isolated or solid earthing Scope of functions and measurements increased in comparison with 7SA51
Housing and input/output version for each application
All protection functions are available in all housing versions
SIPROTEC 4 = Programmable logic, control, interlocking local control is optional
SIPROTEC 4 = Communication interfaces Various tele-control protocols and physical connections options are available Via serial interface, tele-prot. can be implemented with standard comms. networks
(G703, V11/X21) or async. direct connection (not available at product launch)
Distance Protection EV S V1Bl. 19 of 26
SIPROTEC 4Cost optimised protection schemes
Fully redundant 2 communication channels Direct coupling (G703,V11/X24)(in preparation)
7SD52
7SA6
7SD52
7SA6
Channel1
Channel2
DIF
DIS
7SD52
7SA
7SD52
7SA
Channel
Contacts Contacts1 Communication channel Distance protection coupling to 7SD52
with signal transfer via contacts
DIF
DIS
Distance Protection EV S V1Bl. 22 of 26
7SA6Some enhancements
Distance protection always with 6 measuring systems, fault detection I>, Z<, U/I or U/I/
very fast tripping timesvery good selectivity and system stability
Automatic reclosure with additional functions DLC (closing only when there is no voltage on the line) ADT (closing only when reclosure at remote end is successful) RDT (shortened dead time following TRIP by overreaching zone)Saves plant and avoids unnecessary dead times
Operational measured values comprehensive selection of measurands, tolerance <1%Measurement transducers are no longer required
Distance Protection EV S V1Bl. 23 of 26
Coupling to conventional Tele-control 20mA interface for analogue measured value and fault location output BCD-Measured value and fault location output 7SA6 is perfectly suited for integration in existing substations
Breaker failure protection, 2-stage
Back-up earth fault protection for earthed systems 4-stage, sensitivity 0,5% IN high sensitivity and selectivity, also in the event of high resistance faults
Voltage protection U> and U< ULE, ULL, U0, U1, U2
Non-conventional Instrument transformer inputs* and Process bus connection *
security of investment * Funktionalität ist in Vorbereitung
7SA6 Some enhancements
Distance Protection EV S V1Bl. 24 of 26
7SA62Housing 1/1
7SA61Housing 1/2
7SA610Housing 1/3
7SA6 SIPROTEC 4 with Distance protection
7SA61 Protection 4-line display MV, HV and EHV
7SA6127SA6117SA610
7SA63 Protection + local control integrated graphic display mainly MV
7SA6327SA631
7SA64 Protection + local control detached control panel mainly MV
7SA6427SA641All functions are available in all the housing versions
Distance Protection EV S V1Bl. 25 of 26
Automatic reclosure (AR)
CLOSE
TRIP2 nd
Dead Timet1st
TRIP1-pole3-pole
1stDead Time
CLOSE
*CLOSE
t2nd
TRIP
tgrading
ADT = Close if 1st reclose at remote end is successfulDLC = Close if there is no voltage on the lineRDT = shortened dead time after non-selective TRIP
TRIP final
*
SIPROTEC 4Distance protection 7SA6
Distance Protection EV S V1Bl. 26 of 26
newnew
newnewnewnew
newnew
newnew
newnew
newnew
Distance Protection SIPROTEC 4 Auto-Reclosure (1)
Up to 8 independent ARC cycles can be selected
Mode selection ´only 1 pole´ / ´1-3 pole´ / ´only 3 pole´ Operating mode selectable for each cycle
Support of various operating modes: Auto-reclose cycle initiation by fault detection / trip command
DLC: Dead Line Check
ADT: Adaptive Dead Time
RDT: Reduced Dead Time for Z1B-trip with external fault
Integrated monitoring of initiate conditions
Reclose cycles with and without action time supervision
Distance Protection EV S V1Bl. 27 of 26
newnew
newnew
newnew
newnew
newnew
Distance Protection SIPROTEC 4 Auto-Reclosure (2)
Remote close command from ARC master to opposite line end
Separate dead times for all ARC cycles
Three pole coupling of trip command for implausibility
Integrated dead time monitoring
Integrated circuit breaker monitoring and plausibility check
Integrated evolving fault recognition and treatment
Automatic blocking of the ARC following manual close or open CB condition
Initiation of ARC by internal or external functions
Support of 1 ½ and double circuit breaker applications
Distance Protection EV S V1Bl. 28 of 26
Slave provides close command when: the remote close command is received from the master (remote station) or healthy voltage (3-phasig) is measured for
a settable time CB-ready state prevails (selectable) Sync-check release was given (selectable)
Distance Protection SIPROTEC 4 Auto-Reclosure with ADT*
SS1 SS2
Slave im ASP-ModusMaster im Normalbetrieb
* Adaptive Dead Time, patent pending
ADT*-Advantages
No repeated closure onto faults (improved system stability)
Reduces stress of CB poles (longer maintenance cycles)
Distance Protection EV S V1Bl. 29 of 26
SIPROTEC 47SA61 - I/O capability
The distance protection range 7SA61 is available with the following I/O versions:
Front interface with 4-line back-lit display, numerical keypad, LED‘s, Function keys and PC-serial interface
7SA
610*
-*A
7SA
610*
-*B
7SA
611*
-*A
7SA
611*
-*B
7SA
612*
-*A
7SA
612*
-*B
7SA
612*
-*C
Housing width (x 19“) 1/31/3 ½ ½ 1/1
1/11/1
Binary inputs 5 7 13 20 21 29 33Live contact 1 1 1 1 1 1 1Binary outputs/trip/alarm relays 8 5 16 8 24 32 11Power relays for direct control of motorised isolators 0 0 0 4 0 0 8LED’s for indication of Event status 7 7 14 14 14 14 14LED’s for indication of device ready status 2 2 2 2 2 2 2Current transformer 4 4 4 4 4 4 4Voltage transformer 4 4 4 4 4 4 4High speed tripping relays 20mA analogue output (ordering option)
Distance Protection EV S V1Bl. 30 of 26
SIPROTEC 47SA63 - Mengengerüst
The distance protection range 7SA63 is available with the following I/O versions:
Front interface with large back-lit graphic display for bay mimic diagram, numerical keypad, LED‘s control keys, key switches, Function keys and PC-serial interface
7S
A6
31
*-*A
7S
A6
31
*-*B
7S
A6
32
*-*A
7S
A6
32
*-*B
7S
A6
32
*-*C
Housing width (x 19“) ½ ½ 1 /11 /1
1 /1Binary inputs 13 20 21 29 33Live contact 1 1 1 1 1Binary outputs/trip/alarm relays 16 8 24 32 11Power relays for direct control of motorised isolators 0 4 0 0 8LED’s for indication of Event status 14 14 14 14 14LED’s for indication of device ready status 2 2 2 2 2Current transformer 4 4 4 4 4Voltage transformer 4 4 4 4 4High speed tripping relays 20mA analogue output (ordering option)
Distance Protection EV S V1Bl. 31 of 26
SIPROTEC 47SA64 - Mengengerüst
The distance protection range 7SA64 is available with the following I/O versions:
Device with detached HMI for Mounting in the back of the control cubicle with large back-lit graphic display for bay mimic diagram, numerical keypad, LED‘s, Control keys, Key switches, Function keys and PC-serial interface
7S
A6
41
*-*A
7S
A6
41
*-*B
7S
A6
42
*-*A
7S
A6
42
*-*B
7S
A6
42
*-*C
Housing width (x 19“) ½ ½1/1
1/1
1/1
Binary inputs 13 20 21 29 33Live contact 1 1 1 1 1Binary outputs/trip/alarm relays 16 8 24 32 11Power relays for direct control of motorised isolators 0 4 0 0 8LED’s for indication of Event status 14 14 14 14 14LED’s for indication of device ready status 2 2 2 2 2Current transformer 4 4 4 4 4Voltage transformer 4 4 4 4 4High speed tripping relays 20mA analogue output (ordering option)