2008 - 2009 nc state university strategic energy & water plan

40
STRATEGIC ENERGY AND WATER PLAN UPDATE Fiscal Year 2008-09 Promoting campus sustainability through the managed use of energy!

Upload: university-sustainability-office

Post on 24-Mar-2016

217 views

Category:

Documents


1 download

DESCRIPTION

The annual Strategic Energy and Water Plan for North Carolina State University is produced by that school's Energy Management office. The report includes goals, trends, data and more for the fiscal year July 1 - June 30.

TRANSCRIPT

Page 1: 2008 - 2009 NC State University Strategic Energy & Water Plan

STRATEGIC ENERGY AND WATER PLAN UPDATE

Fiscal Year 2008-09

Promoting campus sustainability through the managed use of energy!

Page 2: 2008 - 2009 NC State University Strategic Energy & Water Plan
Page 3: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 3

Executive Summary 5Introduction 8Accomplishments for 2008-2009 10Charting Utilities 20Looking Ahead to 2009-2010 26The Strategic Energy and Water Plan 32Glossary 34Appendix A - Emergency Procedures for Water 36Declaration Page 37

Table of Contents

Edward Sekmistrz Energy Management Engineer edward [email protected]

(919) 515-2188

Brandon Vann Energy Data Analyst

brandon [email protected] (919) 513-1980

[email protected] www.ncsu.edu/energy

Paul McConocha Energy Program Manager

[email protected](919) 513-7178

Page 4: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Page 5: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 5

Executive Summary

Goals

Focus Areas

The Office of Energy Management at North Carolina State University recognizes that by being good stewards of our energy and water resources, we will maintain a quality environment while reducing consumption and controlling costs. The Office of Energy Management also recognizes that the physical size and population of North Carolina State University is continually growing.

In 2007 the North Carolina State Government passed Session Law 2007-546, which states:

Energy consumption in all existing State buildings will be reduced by 20% by the year 2010, •and 30% by the 2015 relative to fiscal year 2002-03. All new State buildings will be 30% more efficient than ASHRAE standard 90.1-2004.•All State agencies will develop a comprehensive plan to manage and report their utilities each •fiscal year to the State Energy Office and Department of Administration.New water systems shall be designed and constructed to use a minimum of 20% less potable •water than indoor water use baseline calculated for the building after meeting the fixture performance requirements by the 2006 North Carolina Plumbing Code.

StatusIn fiscal year 2008-09, NC State University has:

Increased energy consumption in BTUs •per gross square foot by 2.2%, with an overall increase of 3.1% since FY 2002-03.Rebounded 26.6% to near pre-drought •water consumption, while still maintaining 29.4% percent reduction from the FY 2001-02 levels.Grown in gross square footage by 0.5%, •with a total expansion of 23% compared to FY 2002-03.Developed an additional 2.6% in student •enrollment, with a total increase of 7.5% over FY 2002-03.

The Office of Energy Management uses the Strategic Energy and Water Plan to guide our activities in five focus areas:

Energy Data Management•Energy Supply Management•Energy Use in Facilities•Equipment Efficiencies•Campus Integration•

More details regarding these goals, trends and focus areas are provided in this report.

Page 6: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Util

ity C

ost p

er G

SF

Ene

rgy

Cos

t per

Th

ousa

nd G

SF p

er

DD

Ene

rgy

(BTU

) C

onsu

mpt

ion

per

GSF

Ene

rgy

(BTU

) C

onsu

mpt

ion

per

GSF

per

DD

Wat

er C

ost p

er G

SF

Wat

er C

onsu

mpt

ion

(CC

F) p

er G

SF

Hea

ting

and

Coo

ling

Deg

ree

Day

s (D

D)

Cam

pus A

rea,

Gro

ss

Squa

re F

eet (

GSF

)

Spo

nsor

ed A

war

d A

ctiv

ity (M

illio

n $)

Util

ity C

ost p

er

Stud

ent (

$/FT

E)

2008-09 $ 2.66 $ 0.51 177,274 35.8 $ 0.16 0.047 4945 12,190,764 $206.2 $ 1,075

% Change from

2007-08-1.6% -3.4% 2.2% 1.3% 17.5% 26.6% 0.9% 0.5% -4% -3.5%

% Change from

Baseline134.1% 41.5% 3.1% 9.4% 32.4% -29.4% -5.8% 23.0% 22% 53.4%

Note 1: Baseline year for Water Cost per GSF and Water Consumption per GSF is 2001-02 because of Governor Easley’s Executive Order Number 26. For all other KPI, the Baseline Year is 2002-03.

Executive Summary

Key Performance Indicators

Page 7: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 7

Executive Summary

Highlights of TrendsTotal amount spent on utilities in FY 2008-•09 was approximately $33 million. This represents an increase of utility spending of $241,955 from FY 2007-08.

The cost per therm of natural gas decreased •by 15% from FY 2007-08.

The local water utility increased rates by 15% •at the beginning of FY 2008-09.

This year’s cost per kWh of electricity has •increased 3.4%.

The energy consumption in BTU per gross •square foot increased for the year by 2.2%, with an overall increase of 3.1% since FY 2002-03.

NC State University is currently maintaining •and exceeding the goal for water consumption per gross square foot, down 29.4% from baseline year GY 2001-02. Since baseline year, we have avoided over 980 million gallons of water consumption.

Due to the effects of the economic downturn, •total energy costs decreased slightly by $0.04 per gross square foot on the year with a total increase of 34.1% since FY 2002-03.

The NC State campus has grown by more than •23% since FY 2002-03. Student enrollment during this same period has increased by 7.5% since FY 2002-03. The utility cost per Fall Term Student has increased by 53.4% since FY 2002-03.

The energy consumption in BTU per gross •square foot adjusted for weather has increased overall by 9.4% from FY 2002-03, and by 1.3% from FY 2007-08.

Electrical account rate schedule changes •have avoided over $25,234 this year with an overall avoidance of $712,705 since FY 2002-03.

Natural gas account rate schedule changes •have avoided $1,789,249 during FY 2008-09. A total of just over $2.4 million in avoided costs have been achieved since FY 2002-03 by adjusting rate schedules.

Page 8: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Introduction

North Carolina State University, located in Raleigh, North Carolina, is a land grant University with approximately 35,000 students, faculty and staff. NCSU is a leader in the areas of teaching, research and public service. Facilities Operations through the Office of Energy Management has been charged with the responsibility to manage the energy and water resources purchased and consumed by NCSU in the most cost efficient manner and to promote energy and water conservation and awareness throughout the campus community. Our activities must support a superior academic environment and continued growth while simultaneously accomplishing our primary conservation responsibilities.

Our Mission

Our Staff

Our Vision

The Office of Energy Management recognizes that by being good stewards of our energy and water resources we will maintain a quality environment while reducing consumption and controlling costs. This will be accomplished by creating a culture that is dedicated to achieving environmental sustainability by supporting conservation objectives and recognizing and eliminating waste.

The vision of the Office of Energy Management is to sustain a long-term reduction of energy that is purchased by NCSU. We have established the goal of tracking and recording the Aggregate Annual Energy Consumption per Gross Square Foot, adjusted for weather. Additionally, we will reduce the Annual Water Consumption per Gross Square Foot over 2001-02. We will promote campus sustainability through the managed use of energy and water.

Fiscal year 2003-2004 was the inaugural year for the Office of Energy Management at NC State University. There are now seven full-time employees including an Energy Program Manager, Energy Management Engineer, Energy Data Analyst, three Electronic Technicians, and a dedicated Meter Reader.

Page 9: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 9

Our Implementation StrategyEnergy management in a complex ever-changing environment is as much a journey as a destination. Growth, new technologies, environmental concerns, availability of fuels and new regulations and codes are a few of the challenges we must navigate. The Energy Management Plan is the roadmap we use to establish our objectives and guide our activities. A matrix, based on our Energy Management Plan, was created to track the progress of our activities (see page 32). The plan has five focus areas:

Energy Data ManagementEnergy Supply Management Energy and Water Use in FacilitiesEquipment EfficiencyCampus Integration

Each of these focus areas is being implemented in a five-step dynamic approach:

Information Gathering – The first step in the execution of any project or activity is to identify the sources of information available, gather that information, and present it in a meaningful and understandable form.

Plan – Based on the information gathered an action plan should be developed. This will include procedures for execution of the project, the goals for the project and the indicators that will be used to measure the success of the project.

Act – The actual execution of the plan.

Measure – Monitor and report on the key indicators as outlined in the plan.

Assess – Review and evaluate the findings and continue with the plan or revise as required.

Introduction

In August 2007, North Carolina General Assembly passed Session Law 2007-546 to make leading strides toward energy and water conservation. This law states that all current state buildings must be 20% more energy efficient by the year 2010, and 30% more efficient by the year 2015. It also states that all new state buildings will be 30% more energy efficient. All schools within the UNC School System and North Carolina Community College System must adhere to this law. It is also the intent of the General Assembly that priority be given to North Carolina-based resources to provide economic growth to North Carolina.

Page 10: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Accomplishments for 2008-2009

Energy Data Management HighlightsThe addition of sixteen• “state of the art” Nexus electrical meters this fiscal year, is providing real-time monitoring of electrical demand and continuous tracking of energy use. The Nexus metering also supplies advanced tools for evaluation of building loads, and contributing elements tied to building circuitry. As part of the ongoing mission, additional real-time metering is being added to the campus infrastructure whenever opportunites arise.

The implementation of Crystal Reports software •is streamlining the data gathering process by allowing access to data from the EBS billing software database and other sources. Previously, this data was difficult to obtain. This is resulting in better customer service by enabling quicker response times for unique data requests.

In an effort to better serve internal utility •customers, the web portal for the EBS billing software is in operational status. This allows internal customers to proactively track and better understand monthly consumption and billing. This further allows building and budget managers the opportunity to better control costs and forecast expenditures dealing with utilities. At present, there are thirty-three users for the EBS Web Portal with eleven users added since last year.

Energy Star was created in 1992 as a joint program between the U.S. Environmental Protection Agency and the U.S. Department of Energy. Over 70% of Americans recognize the Energy Star label. Over the past decade, ENERGY STAR has been a driving force behind the more widespread use of such technological innovations as efficient fluorescent lighting, power management systems for office equipment, and low standby energy use.

By becoming an Energy Star Partner, NC State University has committed to improving their energy usage campus-wide. This partnership provides technical resources and tools for energy solu-tions and better management of practices.

Page 11: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 11

Accomplishments for 2008-2009

Past 12 months

ActivitiesMeasurement

Expected ActualAnnual Savings

Expected Actual Cost Jobs Assigned toFunding Source

Monthly Bill-ing using EBS (Completion of Payable section).

Streamline billing

TBD TBD N/E N/E

Office of Energy Mgmt Salary

Install advanced chilled water meters at Thermal Plants.

Improveaccuracy TBD TBD $300,000 N/E

Capital Project Management COP

Backfill data into the EBS historian.

Streamline billing TBD TBD N/E N/E

Office of Energy Mgmt Salary

Finalize & test 16 new Nexus electri-cal meters.

DataAccuracy

In process TBD TBD N/E N/E

CampusControl Shop Salary

Finalize & test 10 new chilled water meters at buildings.

DataAccuracy TBD TBD

$400,000 N/E

Capital Project Management R & R

Test/Imple-ment Supervi-sory Control and Data Acquisition (SCADA).

Improvevisibility

In process TBD TBD

$300,000 N/E

CapitalProjectsManagement COP

Provided 10 new users with access to the EBS Web Portal.

Process Improvement TBD TBD N/E N/E

Office of En-ergy Mgmt Salary

Performed software up-grades to the EBS billing system. #

Improve capability

Inprocess TBD TBD N/E N/E

Office of En-ergy Mgmt Salary

# cost for software upgrades included in the annual maintenance fee by Instep, Chicago, Illinois

Energy Data Management Activities

Page 12: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Energy Supply Management Highlights

The purchase of tariff, transport and strip natural gas versus fuel oil was evaluated monthly. •Purchase of transport and strip natural gas was continued to take advantage of historical trends indicating potential cost-avoidance for the University.

The cost effectiveness of rate schedules for electric accounts was and continues to be monitored. •The savings of using Time of Use rates versus standard rates was tracked on thirty-eight accounts.

The demand profiles for the Sullivan sub-station were identified allowing the building automation •group to attempt to alter building settings on the load side to shift the supply side demand peak to a later time.

Fine-tuning the ability to shift loads to non-peak periods will allow a significant opportunity o for cost avoidance for the supply side rates.

Accomplishments for 2008-2009

Page 13: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 13

Accomplishments for 2008-2009

Energy Supply Management Activities

Past 12 months Activities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

Evaluate/reconcile the purchase of strip & transport type gas volumes monthly.

Lower costs

$1.8million

Lower costs

$1.8million N/E N/E

Office of Energy Mgmt Salary

Reconcile savings on electrical accounts from standard service to Time of Use.

Lower costs $25,234

Lower costs $25,234 N/E N/E

Office of Energy Mgmt Salary

Develop program for the purchase of strip natural gas.

Lower costs N/E

Lowercosts TBD N/E N/E

Office of Energy Mgmt Salary

Update the natural gas, electricity, and water rates in the EBS billing system.

Streamlineprocess On going N/E TBD N/E N/E

Office of Energy Mgmt Salary

Page 14: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Energy and Water Use Management Highlights

Accomplishments for 2008-2009

Facilities Operations coordinated building •temperature setbacks during the holiday break with estimated savings of $190,814 compared to the base year of 2004.

Park Shops, SAS, EBIII and Thompson Hall •were connected to the campus chilled water loops. This provided reliability and efficiency of cooling these buildings.

Metering (electricity, chilled water, steam, city •water) was upgraded, and installed.

Eight additional chilled water meters o were installed at the thermal plants.

Twenty meters were placed into o service due to building renovations, replacements, and new building infrastructure.

Recommendations were submitted to the Standards Committee for using energy efficient ballasts •and fluorescent lamps.

Practice of eliminating trays in the Dining Halls was continued providing for water savings.•

Practice of using rain or condensate to supplement cooling tower makeup water was continued at •Yarbrough, Jordan, Fox Labs and the Monteith Research Center.

Page 15: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 15

Accomplishments for 2008-2009

Past 12 monthsActivities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

Winter break setback. Lower costs Lower costs $190,814 N/E N/EOffice of Energy Mgmt Salary

Dining Hall tray elimination. Conservation N/E N/E TBD N/E N/E Dining Salary

Recommend use of energy efficient ballasts & lamps.

Loweroperating costs In process

Lower operating costs TBD N/E N/E

Office of Energy Mgmt Salary

Use of rain or condensate to supplement makeup of cooling tower water. Lower costs On going Lower costs

TBD N/E N/E

BM & OUtilities & Engineering Services Salary

Energy and Water Use Management Activities

Page 16: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Equipment Efficiency Management Highlights

Accomplishments for 2008-2009

Lighting efficiency upgrades were installed in Mann Hall, Bragaw Hall, Bldg 301, and the •Dan Allen parking deck. The use of the following technologies was implemented:

25 watt T8 lamps replaced T12 fluorescent lamps in Mann Hall.o

Low wattage T8 ballasts were installed in Mann Hall.o

277 Volt 27 watt CFL replaced 150 watt metal halide lamps in Bldg 301.o

LED lighting replaced fluorescent lighting in Bragaw Hall.o

LED lighting replaced metal halide lighting in the Dan Allen parking deck.o

Boiler Efficiency Improvements were completed.•

Replacement of inefficient boiler at the West Dunn building.o

Boiler blow-down heat recovery system became operational at Centennial Thermal o Plant.

Dan Allen Parking Deck Lighting Upgrade

Before After

Page 17: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 17

Accomplishments for 2008-2009

Past 12 monthsActivities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to Funding Source

Bldg 301: Upgrade pendent style metal halide lighting to 277 volt CFL. Lower costs $8,000 $8,000

$4,000

N/E

Office of Energy Mgmt

R & ROperating

Mann Hall: Upgrade from T12 to T8 lighting using low wattage ballasts and 25 watt lamps and delamp. Lower costs $ 7,000 $ 7,000 $ 25,000 N/E

Office of Energy Mgmt R & R

Centennial Utility Plant: Install boiler blow down heat recovery. Lower costs N/E TBD $25,000 N/E

Utilities & Engineering R & R

Performance Contracting (13 building): Select ESCO firm.

ConservationEquipmentupgrades

TBD TBD TBD N/E

Capital Project Mgmt

Performance Contract

West Dunn Bldg:Replace inefficient boiler. Lower costs

Lower costs

TBD

$30,000 N/E BM & O

State Energy Reserve Fund

Lighting Upgrade of the Dan Allen Parking Deck using LED technology. Lower costs

Lower costs TBD

$500,000 N/E

Capital Project Mgmt

Operating

Lighting Upgrade of the of the Bragaw Hall using LEDtechnology. Lower costs

Lower costs

TBD

$500,000 N/E

Capital Project Mgmt Operating

Retro Commission Schaub and Partners III.

Lower costs

Lower costs

TBD $185,000 N/E

Capital Project Mgmt

State Energy ReserveFund

COT & MRC; replace boiler burners.

Lower costs

Lower costs

TBD $115,000 N/E BM & O Operating

Equipment Efficiency Management Activities

Page 18: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Accomplishments for 2008-2009

Campus Integration Management HighlightsLabels were placed in strategic entrances and exits to campus buildings promoting “Just Switch •It OFF.” As new and renovated buildings came online, new labels were placed. Additionally, mousepads have been placed in available student computing lab locations.

Daily advertisements were run in the student newspaper, “the Technician.” These advertisements •often held tips and tricks to help students conserve water and energy in their normal daily routines. Additionally, large full-color advertisements were placed in special editions of the Technician, such as the Student Orientation Guide and the Fall Football Preview.

The Office of Energy Management facilitated the Conservation Action Team, and actively •participated in the Campus Environmental Sustainability Team (CEST). This involvement allowed for collaborative work with campus entities to increase education and organize efforts for overall campus sustainability.

The Million Dollar Challenge was promoted during New Student Orientations, Earth Day activities, •at residence halls, and during other events such as Energy Awareness Week.

Conservation awareness was highlighted on Earth Day with the introduction of the HPG, Human •Power Generator. The display helped participants better understand the physical energy required to power both incandescent and compact flourescent bulbs.

Earth Day 2009

Page 19: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 19

Campus Integration Management Activities

Accomplishments for 2008-2009

Past 12 monthsActivities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

Labeled buildings “Just Switch it Off” ; SAS, Park-shops, Riddick. Conservation N/E TBD N/E N/E Office of Energy Mgmt Salary

Designed and updated advertisements in Technician, WolfBytes. Conservation N/E TBD $5,000 N/E Office of Energy Mgmt Salary

Coordinated regular Conservation Action Team meetings; educated in accord with Session Law 2007-546. N/E On going N/E TBD N/E N/E Office of Energy Mgmt Salary

Monitored and provided response to the email site Save Energy @NCSU.edu. N/E On going N/E TBD N/E N/E Office of Energy Mgmt SalaryDesigned, printed, and distributed brochures on energy and waterconservation. N/E N/E TBD $1,000 N/E Office of Energy Mgmt Salary

Produced and printed annual energy and water report. N/E N/E TBD $1,000 N/E Office of Energy Mgmt SalaryOrganized and attended Energy Awareness events (Energy Week, Earth Day, etc.). N/E N/E TBD $750 N/E Office of Energy Mgmt Salary

Purchased educationalbulletin board in Carmichael. N/E On going N/E TBD $500 N/E Office of Energy Mgmt Salary

Updated the Energy Management website. N/E On going N/E TBD N/E N/E Office of Energy Mgmt Salary

Met with students dealing with display of real time energy information. N/E On going N/E TBD N/E N/E Office of Energy Mgmt Salary

Page 20: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Charting Utilities 2008-2009

The Office of Energy Management is currently responsible for managing purchased utility for most buildings on main campus and several research facilities. It reports on utilities purchased from vendors (such as Progress Energy and PSNC Energy) as well as utilities provided to individual campus facilities (from substations and thermal plants):

Purchased Utility Accounts: 130 electric, 105 natural gas, 104 domestic water/irrigation•

Demand Utility Meters: 230 electric, 79 steam/condensate, 189 cold water, 30 domestic and heating •hot water, and 61 chilled water.

Total meters: 586•

The purchased utilities are paid through the PeopleSoft financial system using the EBS interface.

The demand utility meters are read each month with a hand-held device and entered into EBS, utility billing software system. Historical information on demand and purchased utilities is now tracked through the Oracle database implemented for the EBS system. Currently, the demand data is used primarily to monitor consumption by receipt-funded entities such as University Housing and University Dining. We are also using this information to benchmark utility consumption for different building types (ie. classroom, office, and laboratory) where metering information is available.

The data presented is based mainly from supply side, or “purchased utilities,” by NC State. Data from sub-metering on the demand side is presented when available.

Tracking Campus Utility Consumption and Distribution

Page 21: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 21

Charting Utilities 2008-2009

Utility Consumption Units Consumption Units Cost

Electricity 284,885,005 kWh 972,313 Million BTU $ 20,250,338

Natural Gas 11,785,006 therms 1,178,501 Million BTU $ 10,079,218

Fuel Oil #6 57,186 Gal 8,578 Million BTU $ 684,583

Fuel Oil #2 12,280 Gal 1,719 Million BTU $ 37,107

Total Energy 2,161,110 Million BTU $ 31,051,245

Water 424,974,686 Gal 568,110 CCF $ 1,795,424

Stormwater $ 122,807 Total Energy and Wa-ter (excluding Storm-water) $ 32,846,669

Total Energy and Water Consumption

Avoided Costs: Rate Negotiations

Utility Used For Cost Avoidance Avoided Costs up to Fiscal 07-08

Fiscal 08-09 Avoided Costs

Avoided Costs to Date

Progress Energy – 38 accounts oper-ated on Time Of Use Rate.

$687,471.25 $25,233.59 $712,704.84 Natural gas negotiations – Transport Vs. PSNC Tariff rate. $610,833.51 $1,789,249.04 $2,400,082.54 Natural gas negotiations – Alternate Fuels (oil/NG) Vs Transport rate. $2,497,354.00 $0.00 $2,497,354.00

Page 22: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Charting Utilities 2008-2009

Key Performance IndicatorsFiscal Year 2001-2002 2002-2003 2003-2004 2004-2005 2005-06

Utility Cost per GSF $1.98 $2.10 $2.18 $2.50

Energy Cost per Thousand GSF per DD $0.357 $ 0.386 $0.438 $0.474

Energy (BTU) Consumption per GSF 171,888 170,406 168,685 163,756

Energy (BTU) Consumption per GSF per DD 32.8 33.6 36.1 32.9

Water Cost per GSF $0.119 $0.106 $0.137 $ 0.135 $0.142

Water Consumption (CCF) per GSF 0.066 0.054 0.058 0.054 0.052

Heating and Cooling Degree Days (DD) 5,248 5,078 4,670 4,978

Campus Area, Gross Square Feet (GSF) 9,796,638 9,910,619 9,986,663 11,056,592 11,723,681

Sponsored Award Activity (Million $) $169.5 $208.6 $199.5 $207.0

Utility Cost per Student ($/FTE) $701 $743 $857 $1,043

Page 23: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 23

Charting Utilities 2008-2009

2006-07 2007-08 2008-09 % Change 1 Year % Change from Base-line 1

$2.39 $2.70 $ 2.66 -2% 34%

$0.474 $0.523 $0.505 -3% 41%

165,265 173,490 177,274 2% 3.1%

34.9 35.4 35.8 1% 9.5%

$0.150 $0.134 $0.157 18% 48%

0.047 0.037 0.047 27% -29.4%

4,733 4,903 4,945 1% -5.8%

11,918,022 12,130,370 12,190,764 0.5% 23%

$192.4 $213.7 $206.2 -4% 22%

$989 $1,115 $1,075 -4% 53%

Page 24: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Charting Utilities 2008-2009

Trends in Energy and Water ConsumptionThe energy use per square foot had experienced a steady decline until 2007-08 (see Figure 1). Overall, based on total million BTUs per square foot, energy usage per square foot has increased by 3.1% over baseline year, 2002-03. This energy use per square foot does not take into account the effect of weather on energy use.

North Carolina State University has committed to the State of North Carolina to reduce its energy consumption per gross square foot, adjusted for weather. This is measured in BTU per square foot per total heating and cooling degree days (BTU/ft2/DD). The trend of energy adjusted for weather has also began to increase as shown in Figure 2. Since 2002-03, North Carolina State University has increased by 9.4% in BTU/ft2/DD overall. FY 2008-09 brought some additional buildings online either through new construction or renovation. In either case, building controls were not optimized until these buildings were brought online and appropriately sealed. The energy demand increased as a result of this variety of conditions.

NC State University’s water consumption was reduced by over 29.4% from the 2001-02 baseline. Water conservation practices were implemented and expanded in response to the severe drought and have been maintained into the first part of 2008-09 . This is all due to improved irrigation control, operation of central chilled water plants, installation of water saving fixtures (ie. showers, faucets, laundry machines, etc.) and changes in awareness and behaviors.

Figure 2

Figure 3

Figure 1

Page 25: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 25

Charting Utilities 2008-2009

Trends in Energy and Water Costs

There has been a significant decrease in fossil fuel prices this year due to the economic downturn. Although the natural gas prices has temporarily dropped, the electric rates have continued the upward climb. The cost of water has also increased. Therefore, while conservation measures are implemented to reduce the overall consumption, the cost per square foot will likely continue to increase. The cost per square foot is now about $2.66, which is a 1.6% decrease over 2007-08. This cost is up by 34.1% over baseline 2002-03.

A separate key performance indicator that NC State University is tracking is the cost per Fall Term Enrolled (FTE) student. The FTE reported only includes on-campus students (not distance education students). While the physical campus has been expanding rapidly due to the 2000 Bonds for Higher Education, there has not yet been a significant increase in student enrollment. The cost per student has increased 53.4% over baseline 2002-03 (see Figure 5).

Figure 4

Figure 5

Page 26: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Looking Ahead to 2009-2010

Energy Data Management Planned Activities

Next 12 months Activities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

Identify the 60 “Opted In” Progress Energy accounts for Energy Savings Initiatives. Lower cost TBD TBD TBD N/E N/E

Office of Energy Mgmt Salary

Evaluate Energy Star capabilities for benchmarking.

Determine usefulness TBD TBD TBD N/E N/E

Office of Energy Mgmt

Salary

Test the custom reportingfeature for the EBS Client/EBS Web Portal to provide custom reports.

Streamline process TBD TBD TBD N/E N/E

Office of Energy Mgmt

Salary

Implement custom reporting and archival of pc specific user files.

Streamline process TBD TBD TBD N/E N/E

Office of Energy Mgmt

Salary

Create custom systemreports to enhance and improve validation for data and billing processes.

Streamline process TBD TBD TBD N/E N/E

Office of Energy Mgmt

Salary

1 yearly renewal costs for maintenance/support

The Office of Energy Management process involves collecting data, identifying opportuni-ties, implementing pilot solutions, quantifying the results,and then identifying larger scale projects. From this, we have developed the basis for guidelines and procedures that will provide the foundation for the conservation measures that will allow us to meet our long-term goals. Our projected activities will continue to implement conservation practices and assess their results as outlined in the forthcoming “planned activities.”

Page 27: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 27

Looking Ahead to 2009-2010

Energy Supply Management Activities

Next 12 monthsActivities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

Evaluate/reconcile the purchase of strip & transport type gas volumes monthly.

Lower costs TBD TBD TBD N/E N/E

Office of Energy Mgmt Salary

Reconcile savings on electrical accounts from standard service to Time of Use.

Lower costs TBD TBD TBD N/E N/E

Office of Energy Mgmt Salary

Update program for the purchase of strip natural gas.

Lower costs TBD TBD TBD N/E N/E

Office of Energy Mgmt Salary

Update the natural gas,electricity, and water rates in EBS billing system.

Streamline process TBD TBD TBD N/E N/E

Office of Energy Mgmt Salary

Page 28: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Next 12 months Activities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to Funding Source

Winter break setback. Conservation TBD TBD TBD N/E N/EOffice of Energy Mgmt Salary

Dining Hall tray elimination. Conservation TBD TBD TBD N/E N/E Dining Salary

Recommend energy and water best practices to the Standards Committee. Conservation TBD TBD TBD N/E N/E

Office of Energy Mgmt Salary

Evaluate other applications where rain or condensate water use would be appropriate. Conservation TBD TBD TBD N/E N/E

BM & OUtilities & Engineering Services Salary

Energy and Water Use Management Activities

Looking Ahead to 2009-2010

In June 2008, in the wake of an extreme multi-year drought, the decision was made to install a rainwater collection tank in Yarbrough Drive Thermal Plant. The water collected in this 1,000 gallon tank is used for cooling tower make-up. Cooling towers require huge amounts of water in order to do their job, much of which is lost into the atmosphere as condensate. Instead of purchas-ing additional potable water, rainwater is collect-ed in this tank from the roof of the plant and then pumped back into the cooling towers. In the month since its installation, this system has collected and made up, and thus avoided the purchase of thou-sands of gallons of water.

Page 29: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 29

Looking Ahead to 2009-2010

Equipment Efficiency Management Activities

Next 12 months Activities

Measure-ment

Expected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

DH Hill upgrade lighting to T8- 25 watt & install occupancy sensors. Lower costs TBD TBD $455,000 N/E

Office of Energy Management

Pending ARRA*2009

Retro Commission Robertson Hall and Student Health Center. Lower costs TBD TBD $45,000 N/E BM & O Operating

Carmichael: Evaluate solar heating (water) viability as part of the performance contract. Lower costs TBD TBD $200,000 N/E

Capital Project Mgmt

Performance Contract

Jordan Hall: upgrade lighting to T8 25 watt & install occupancy sensors. Lower cost TBD TBD $165,000 N/E

Office of Energy Management

Pending ARRA*2009

Butler Bldg: Upgrade lighting & install occupancy sensors. Lower cost TBD TBD $55,000 N/E

Office of Energy Management

Pending ARRA*2009

Session Law 2007-546: LED exit, CFL lamps, occupancy sensors, etc. Compliance TBD TBD $50,000 N/E

BM & OHousingOffice of Energy Mgmt

Pending ARRA*2009

Brooks Hall Air Handler; condensate recovery. Lower costs TBD TBD $3,000 N/E BM & O Operating

Method Road #2; boiler replacement. Lower costs TBD TBD $119,000 N/E BM & O Operating

CBC Large Animal; upgrade lighting. Lower costs TBD TBD $24,000 N/E BM & O Operating

Execute performance contract for energy upgrades for 13 buildings. Lower costs

$1.5 million TBD

$15/20million N/E

Capital Project Mgmt

Performance Contract

Carmichael & CBC; replace plumbing fixtures. Lower costs TBD TBD $55,000 N/E BM & O Operating

* American Recovery & Reinvestment Act

Page 30: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Looking Ahead to 2009-2010

Next 12 monthsActivities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

Label buildings “Just Switch it Off” after renovation, etc. Conservation TBD TBD TBD N/E N/E

Office of EnergyMgmt Salary

Advertisements; Design and update advertise-ments for Technician, WolfBytes. Conservation On going TBD TBD $5,000 N/E

Office of EnergyMgmt Salary

Coordinate regular Conservation Action Team meetings; educate in accord with Session Law 2007-546. Conservation On going TBD TBD N/E N/E

Office of EnergyMgmt Salary

Monitor and provide response to the email site Save Energy @NCSU.edu. N/E On going N/E TBD N/E N/E

Office of EnergyMgmt Salary

Design, print, and distribute brochures on energy and water conservation. N/E On going N/E TBD $2,000 N/E

Office of EnergyMgmt Salary

Produce and print annual energy and water report. N/E In process N/E TBD $1,000 N/E

Office of EnergyMgmt Salary

Campus Integration Management Activities

Page 31: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 31

Looking Ahead to 2009-2010

Campus Integration Management Activities

Next 12 monthsActivities

MeasurementExpected Actual

Annual Savings Expected Actual Cost Jobs Assigned to

Funding Source

Organize and attend Energy Awareness events (Energy Week, Earth Day, etc.).

EnergyAwareness Conservation N/E N/E TBD $750 N/E

Office of EnergyMgmt Salary

Maintain educational bulletin board inCarmichael.

EnergyAwareness Conservation N/E N/E TBD $500 N/E

Office of EnergyMgmt Salary

Update the Energy Management website.

EnergyAwareness Conservation N/E N/E TBD

N/E N/E

Office of EnergyMgmt Salary

Evaluate cost for design and implementation of energy/waterdashboards on website for selected buildings.

EnergyAwareness Conservation N/E N/E TBD

N/E N/E

Office of EnergyMgmt Salary

Evaluate viability of capturing gym energy.

EnergyAwareness Conservation N/E N/E TBD

N/E N/E

Office of EnergyMgmt , BM & OSustainability Office Salary

The Million Dollar Challenge is a marketing campaign encouraging all campus populations to conserve. We

stress that a little saved by each of us can provide a level of savings that will help maintain or even reduce the

operating expense at NC State University. By each person on campus saving $.15 per day in energy and water

consumption, we have the potential to save over $1,000,000. For example, if a student keeps the light

off in their dorm room for 16 hours each day, they will save $.10. They can make up the remaining $.05 by

turning off the water when they brush their teeth and shave.

$milliondollarCHALLENGE

$.15 per day

200 days on campus

35,000 faculty, staff, and students $1,050,000.00xx =

Page 32: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

The Strategic Energy and Water Plan

LEGENDMajor Development of TaskExtension of TaskImplementation

# Denotes Work Complete

The Office of Energy Management worked with the State Energy Office in North Carolina to develop a strategic plan to achieve the goal of reducing long-term reduction of 20% in unit consumption of energy that is purchased by NCSU. The Strategic Plan Matrix allows us to track the details of our activities in each of the five focus areas.

NCSU Energy Management Strategic Plan Matrix

Focus Area Phase I

Phase II

Phase III

Phase IV

Phase V

Phase VI

Phase VII

Phase VIII

ENERGY DATA MANAGEMENTSupply Side Utility-Owned Meters

Determine information available/required Create systems to capture/accumulate data Establish Key Performance Indicators #Annual report for SEO #Initiate reporting

Monthly report for detailed account analysis #Develop procedures for account maintenance #

Demand Side NCSU-Owned MetersCreate systems to capture existing data Determine information available/requiredDetermine meter type & location requirementsMeter additions & repairsLocate & map all existing meters

Make Energy Data Accessible to All UsersSelect & purchase utility accounting software #Transfer supply and demand accountsInitiate reporting; format & content

Establish benchmarks / building rankings Establish load profilesENERGY SUPPLY MANAGEMENT

Price negotiations for deregulated utilitiesImplement monthly transport NG purchasesImplement monthly PSNC rate 160 NG purchases

Central Thermal PlantsReview data for utility accounts

Rate schedule optimizationAccount & meter consolidation

Method to verify LGS & LGS-TOU rates #

Page 33: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 33

The Strategic Energy and Water Plan

NCSU Energy Management Strategic Plan Matrix

Focus Area Phase I

Phase II

Phase III

Phase IV

Phase V

Phase VI

Phase VII

Phase VIII

ENERGY USE IN FACILITIESSystem condition assessments

Audits by Energy Management DepartmentUpgrade equipment & building control systemsMaintenance preventive & remedialRepair/replace decisions

Establish operating procedures/guidelines Lighting efficiency guidelinesMotor efficiencies replacement guidelinesBuilding operation guidelines (automation systems)Optimize settings on Building Automation SystemsAudits and tune-ups through SEOBoiler study

Performance Contracting StudyEvaluate alternative/renewable fuels for boilers

EQUIPMENT EFFICIENCYPilot lighting programs Test effectiveness of occupancy sensors #Reduced flow shower heads and sink aeratorsCarmicahel Gym squash court lighting #Occupancy sensors in buildingsLED Exit lights in buildings Lighting upgrades at building levelReplace inefficent motors campus wideEvaluate pilot solar hot water project Evaluate energy savings opprotunites in laboratories

CAMPUS INTEGRATION“Just Switch It” sticker campaignWeb sitePresentationsCampus publicationsLiaisonsStudent GroupsLogo #Controls systems, meters, eDNA trainingEnergy Management Diploma program SEO workshops

Page 34: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Glossary

Building Maintenance and Operations

Abbreviations in Activities Tables

COP

N/A

N/E

NCDOA

Operating

R&R

Certificate of Participation funds

Not applicable, direct savings from these tasks is not quantifiable

Not estimated, direct savings from these tasks is quantifiable but not estimated due to insufficient supporting data

North Carolina Department of Administration helped fund through the State Energy Office

Operating funds from department responsible for task

Repair and renovation funds, may be either CI (Capital Improvement) or Recurring

BM & O

TBD To be determined

Page 35: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 35

DefinitionsBuilding Automation System

Measure of Energy, British Thermal Units, 3,413 BTU= 1kWh

Measure of Volume, 100 cubic feet, 1CCF = 748.05 gallons

Degree Days; a unit of measure equal to a difference of one degree between the mean outdoor temperature on a certain day and a reference temperature (65° F). This term is used to estimate the energy for heating and cooling a building. Source: Raleigh RDU Airport Data from Weather Underground.

Direct Digital Controls

Energy Service Company; a business that develops, installs, and finances projects designed to improve the energy efficiency for facilities over a set time period

Fall Term Enrolled Students; On-campus Total Headcount Enrollment: includes all on-cam-pus students enrolled for one or more course in regular fall term with each person counted only once - excludes audit only and extension student. Source: http://www2.acs.ncsu.edu/UPA/fastfacts/quick.htm. Official Source: Student Data File as submitted to UNC-General Administration.

Measure of volume, gallon(s)

Gross Square Feet; total building square footage that we provide utilities, includes parking desk. Source Facilities Operations Budget Office.

Heating Hot Water

Measure of energy, usually in reference to electricity, 1 kWh = 3,413 BTU

Measure of energy, 1,000,000 BTU = 1 MMBTU = 106 BTU

Amount of Grant Proposals awarded, total dollar amount of grants awarded for organized research, extension, public service, and instruction activities funded through sources external to the University. Source: http://www.ncsu.edu/sparcs/sor/search.php. (Research Administration Data And Reporting System - R.A.D.A.R)

Measure of energy, usually in reference to natural gas, 1 Therm = 105 BTU

Variable Frequency Drive

BAS

BTU

CCF

DD

DDC

ESCO

FTE

Gal

GSF

HHW

kWh

Sponsored Award Activities

MMBTU

Therm

VFD

Glossary

Page 36: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Appendix A - Emergency Procedures for Water

ACTION City Of Raleigh Stage 1 - Effective August 28, 2007 Fines 1st Violation - $200

2nd Violation - $1,000 3rd Violation – Interruption of Service

GroundsManagement

• Reduce watering schedule from three days a week to one day (Wednesday) for turf and ornamental irrigation (except drip irrigation). • Hand held hose watering can be done Wednesdays from 6 AM – 10 AM. • Vehicles washed only at Facilities Operations approved water reuse facility (80% water is reused). ** Athletic fields (safety reasons), preventative maintenance on water systems, and city-permitted watering are exempt from Stage IRestrictions per City of Raleigh. **

BuildingMaintenance&

Operations

• All Leaks Code 1 and should be repaired within 24 hrs. • Vehicles washed only at Facilities Operations approved water reuse facility. • Write work requests to check conductivity controllers and water control valves on cooling towers.

University Dining • Water served only upon request. • Review water uses, install recycle systems where feasible. • Create and distribute a water conservation awareness flyer targeting all building users within the Dining area of operation.

UniversityHousing

• All Leaks Code 1 and should be repaired within 24 hrs. • Create and distribute a water conservation awareness flyer targeting all building users within the Housing area of operation.

Housekeeping • Cease washing of areas such as sidewalks, driveways, patios prohibited, except for sanitary reasons. • No window or power washing.

Athletics • Reduce watering schedule from three days a week to one day (Wednesday) for turf and ornamental irrigation (except drip irrigation). • Reduce watering of playing fields to every other day, except for safety reasons. • No water added to decorative fountains. • Adjust control valves in the urinals to conserve water.

Talley Center • No water added to decorative fountains. • Create and distribute a water conservation awareness flyer targeting all building users within the Talley Student Center area of operation.

Utilities & Engineering

Services

• Write work requests to check conductivity controllers and water control valves on cooling towers. • Suspend fire hydrant flushing. • Convene NCSU Conservation Awareness Team (CAT) to update conservation strategies and educational outreach with the City of Raleigh for Stage I Restrictions. • Coordinate and disseminate the NCSU water conservation plan throughout campus in response to the City of Raleigh and the Governor’s mandates on water conservation. • Monitor consumption levels to measure progress.

All Others • Follow all rules above and those from City of Raleigh. • Examine the water being used in your area, and actively seek out ways to conserve water.

NCSU Response to Raleigh’s Water Restrictions By PhaseUpdated September 11, 2007

STAGE II Plan Will Be Distributed As Necessary

Page 37: 2008 - 2009 NC State University Strategic Energy & Water Plan

Declaration Page

37

Strategic Energy and Water Plan Commitment for North Carolina State University

We recognize energy and water as controllable expenses wherein savings result in reducing overall operating cost. Energy and water management is a responsibility of the staff, faculty and students at each facility, guided and supported by the Energy Manager.

North Carolina State University will develop a Strategic Energy and Water Plan. The Director for Utilities Services is responsible for the success •of the Program at the campus facilities.The Energy Program Manager is responsible for implementation of North Carolina State University’s Strategic Energy and Water Plan. •The Assistant Vice Chancellor for Facilities Operations• will review progress and results quarterly.

Strategic Energy and Water Plan Commitment- GoalsRecognizing that North Carolina State University is experiencing significant growth in facilities and utilization rates, we will establish a goal to reduce the Aggregate Annual Energy Consumption per Gross Square Foot, adjusted for weather, by a minimum of 4% over a 10 year period based on the Key Performance Indicators listed below, using Fiscal Year 2002/2003 as a baseline. We will reduce Annual Water Consumption Per Gross Square Foot by a minimum of 10% over the baseline year 2001-2002.

Strategic Energy and Water Plan Commitment- MeasuresOur tracking measures will be the following State Key Performance Indicators (KPI)

Total Utilities Cost per Gross Square Feet •Total Energy Cost per Thousand Gross Square Feet per•Degree DayTotal Energy Consumption in BTU’s per Gross Square Feet •Total Energy Consumption in BTU’s per Gross Square Feet per Degree Day•Total Water Cost per Gross Square Foot•Water Consumption in Hundred Cubic Feet (CCF) per Gross Square Foot• Total heating and cooling Degree Days•Campus Area (GSF)•Growth in Research Programs($)•Utility Cost per Student ($/FTE)•

Strategic Energy and Water Plan - CommitmentImplemented this 31st day of July, 2009.

Page 38: 2008 - 2009 NC State University Strategic Energy & Water Plan

NORTH CAROLINA STATE UNIVERSITY

Energy is defined as “the ability to do work.” The following is an example of the transformation of

different types of energy into heat and power...

Page 39: 2008 - 2009 NC State University Strategic Energy & Water Plan

2008-09 OFFICE OF ENERGY MANAGEMENT ANNUAL REPORT 39

Page 40: 2008 - 2009 NC State University Strategic Energy & Water Plan

ELECTRONIC AVAILABILITY This document is available online at www.ncsu.edu/energy. We printed minimal copies of this report to support and maintain our University’s sustainable principles. Please think twice before printing it.

PRINT AVAILABILITY 100 copies of this public document were printed at a reasonable cost per copy. The printer used vegetable-based ink on 100% post-consumer recycled paper. Printed copies are for distribution to University officials and the State Energy Office. Remain-ing copies are dispersed through campus to increase student, faculty and staff awareness.

FEEDBACK We encourage readers of this report to provide us with their own insight into how we are progressing and possible future endeavors. Please provide your insight to the Energy Management Office at [email protected]

EQUAL OPPORTUNITY STATEMENT NC State Univeristy is dedicated to equality of opportunity. The University does not condone dis-crimination against students, employees or applicants in any form. NC State commits itself to positive action to secure equal opportunity regardless of race, color, creed, national origin, religion, sex, age or disability. In addition, NC State welcomes all persons without regard to sexual orientation.