Commercial Service Sizing

Commercial Service Sizing

Calculations

Page 2: 2008 Commercial Service Sizing 2008

Commercial Service Sizing

Copyright 1999-2007 Dan Dudley

Standard Commercial CalculationsStandard Commercial Calculations

• Six loads are considered:– Lighting Loads– Receptacle Loads– Special Appliance Loads– Heating or A/C Loads– Motor Loads– Largest Motor Load

Page 3: 2008 Commercial Service Sizing 2008

Commercial Service Sizing

Copyright 1999-2007 Dan Dudley

• Lighting Loads considered:– General Lighting Loads– Show Window Loads– Lighting Track Loads– Outside Lighting Loads– Sign Lighting Loads

Standard Commercial CalculationsStandard Commercial Calculations

Page 4: 2008 Commercial Service Sizing 2008

Copyright 1999-2006 Dan Dudley

Commercial Service Sizing

Given:

50’ X 60’ Store (3000 Sq Ft)

30’ Show window lighting

Total of 80 duplex receptacles

240/120 V, 1 phase, 3 wire service

Actual connected load of 8500 VA

Commercial Service SizingCommercial Service Sizing

Page 5: 2008 Commercial Service Sizing 2008

Copyright 1999-2006 Dan Dudley

Commercial Service Sizing

Solution: Calculation Code Citation

Continuos Loads:

3000 Sq Ft X 3 VA X 125% 11,250 VA T220.12 / 215.2(a)(1)

Sign Lighting 1200 va X 125% 1,500 VA 600.5

Show Window 30’ X 200 VA X 125% 7,500 VA 220.14(G)(2)

20,250 VA

Other Lighting Loads

Non-Continuos Loads:

Receptacles 80 X 180 VA 14,400 VA 220.14(j)

first 10,000 Va @ 100% 10,000 VA T220.44

Remaining 4,400 Va @ 50% 2,200 VA

Existing load 8,500 VA

TOTAL VA 40,950 VA

220.14(G)(1) and 210.62 state that the PER RECEPTACLES LOAD is calculated at 180VA per receptacle and there must be at least one (1) per 12 linear feet.

Page 6: 2008 Commercial Service Sizing 2008

Copyright 1999-2006 Dan Dudley

Commercial Service Sizing

TOTAL DEMAND 40,950 VA

Line = 40,950 VA / 240 V = 170.625 Amps

Neutral = 170.625 Amps = 170.625 Amps

Service Feeder = # 2/0 THW, THHN T310.16

Service Neutral = # 2/0 THW, THHN T310.16

Grounding Electrode Conductor = # 6 T250.66

Equipment Grounding Conductor = # 6 T250.122

NOTE** Article 110.14(c) 1 & 2 still applies and you select the conductor size according to the AMPACITY. (75°C rating)

Neutral note* 220.621(B)(2) Allows 70% neutral after first 200AMPS is taken at 100%.

Page 7: 2008 Commercial Service Sizing 2008

Copyright 1999-2006 Dan Dudley

Commercial Service Sizing

Receptacle Load unknown

T.220.12 note b