2008 product catalogue
TRANSCRIPT
2008 Product Catalogue
Telephone: 01707 282880Post Sales Technical Support / Spares and Warranty: 0870 3000 300
email: [email protected]
web: www.mitsubishielectric.co.uk/aircon
UNITED KINGDOM Mitsubishi Electric Europe Air Conditioning Systems DivisionTravellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. General enquiries Telephone: 01707 282880 Fax: 01707 278674
IRELAND Mitsubishi Electric Europe Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531)
Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2008. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.
Printed in April 2008
SAP No. 214760
www.greengatewayinitiative.co.uk
Designed by Square Bear Ltd 01604 899099. Square Bear Ltd are committed to using FSC certified paper and printers, wherever possible.
The laminate used on this brochure is environmentally friendly, recyclable and biodegradable
Features Key
2008 Product CatalogueA comprehensive range of Air Conditioning Systems from Mitsubishi Electric
Mitsubishi Electric Partner ProgrammeOpen to all contractors - large or small - the Mitsubishi Electric Par tner Programme offers contractors atotally new and unique set of benefits. There are two categories within the programme - Accredited Installerand Business Solutions Partner - these levels being a straight-forward reflection of the Partner’sstage of growth, with all customers signing up to the programmes standards and committing to continued training and professional development.
For more information please contact your local sales office
Mitsubishi Electric Training OptionsMitsubishi Electric has four state-of-the-ar t training suites based at different locations around the countr y for your convenience.Providing training for all levels of exper tise, our courses are taught by experienced engineers, with a wealth of knowledge and are all CPD accredited.
For bookings please telephone 01707 278797
Systems marked with the ECA logo have an energy label of A or B, are registered on theEnergy Technology List and hence qualify for 100% first year enhanced capital allowances(whole system cost and ‘reasonable’ cost of installation). For further information please go to www.eca.gov.uk
Nominal conditions cooling: indoor 27˚C DB, 19˚C WB; outdoor 35˚C DB, 24˚C WB.Nominal conditions heating: indoor 20˚C DB; outdoor 7˚C DB, 6˚C WB.UK Conditions: Summer; indoor 21˚C DB, 15˚C WB; outdoor 27˚C DB. Winter; indoor 21˚C DB; outdoor -1˚C WB.
Notes: Recommended fuse ratings given throughout this price list are based on British Standard (BS88).
the name Mitsubishi is synonymous with excellenceKnown the world over, Mitsubishi is a trusted global leaderassociated with a variety of products and services. Founded in1907, the company known today as Mitsubishi Electric, quicklyrose to the forefront of the air conditioning industry - a position we still enjoy today.
Unsurpassed air conditioning from Mitsubishi ElectricAir conditioning is an ideal way of controlling the air quality inside any building, large or small.Not only does it cool in the summer months but air conditioning can also heat, replacing traditionalheating systems. More and more people today are experiencing the benefits of comfortable working,living and leisure environments made possible with air conditioning. As market leaders, we prideourselves in providing high performance, competitive systems with low running costs.
Protecting the environmentMitsubishi Electric boasts an explicit commitment to sustainable business practices such as energy and resource efficiency, minimising ecological impacts of our products and reducing greenhouse gas emissions. We are the only manufacturer in the industry recognised by Portfolio 21 as one of the top five companies in the world for our sustainable environmental policy. All of our factories are also ISO 14001 registered, the international standard that specifies a process for controlling and improving a company's environmental performance and with the advent of our Green Gateway Initiative, we strive to constantly promote best practice.
The Forest Stewardship Council (FSC) is an international network promoting responsible management of the world's forest. The paper this catalogue is printed on supports the development of responsible forest management worldwide. The wood comes from FSC certified, well managed forests, company controlled sources and/or recycled material.
Page 13-52
Bigger, better and easier to use: the new2008 Mitsubishi Electric Air ConditioningProduct CatalogueThis revised catalogue offers you more information than ever before. The first thing you’llnotice is that the 2008 catalogue is bigger than before. That’s because the MitsubishiElectric air conditioning range contains many new models, plus a fully comprehensiveselection of control options to choose from.
In addition to increasing the range, we’ve also tried to help you find what you need morequickly and efficiently. We hope you will find it an interesting and informative read.
If there is anything not covered in the catalogue and you want to know more, simplycontact your Mitsubishi Electric supplier who will be delighted to help you. Alternatively, youcan log onto our website at www.mitsubishielectric.co.uk/aircon for further information.
Page 53-116
Page 117-197
Page 199-217
Page 219-254
Contents
Page 1
M Series / Mr SlimSplit-System Air Conditioning
Mitsubishi ElectricSplit-Systems
M Series and Mr SlimFor the last couple of years Mitsubishi Electric’s M Series and Mr Slim range of split-systemshave gradually moved closer together, in terms of features and benefits, capacity and now mostimportantly in terms of control. While both ranges maintain their individual brand identity, allof our models have benefited from massive investment by Mitsubishi Electric, the overall resultbeing a vastly improved and more flexible collection of split-systems.
One of the most important features of the inverter range is the adoption of a new version of A Control, allowing the standardisation of the M Series and Mr Slim ranges, as well as strengthening the remote controller functionality. As a result of this it is now also possible to connect Mr Slim indoorunits to MXZ Multi-Split outdoor units, allowing for complete design flexibility. The Mr Slim StandardInverter models have further increased the range, offering a lower cost option, whilst still incorporatingMitsubishi Electric’s energy saving inverter technology. Also new to the Split-Systems range are the newhigh COP, MSZ-FD M Series models, our most efficient wall mounted units to date.
A Control is Mitsubishi Electric’s control mechanism for providing standard remote controller functionsalongside system diagnostics, fault code monitoring and the ability to interface with the MELANS(Mitsubishi Electric Air Conditioning Network Solution) equipment such as the G50 CentralisedController, TG2000, Modbus, Trend, LonWorks® & BACnet® etc. A Control has now been furtherimproved by Mitsubishi Electric, providing increased flexibility alongside greater functionality.
Page 4
Inverter technology saves energy for two main reasons:1. The compressor varies its speed to match the cooling or heating load and therefore consumes only the power necessary
to match the exact requirement of the room.
2. When an inverter driven air conditioner is operating at partial load, the energy efficiency of the system is significantly higher than at full load. In a typical application, partial load conditions prevail for more than 90% of operation time. A fixed speed system can only operate at 100% capacity and cannot match the annual efficiencies of an inverter system.
The entire R410A M Series and Mr Slim ranges areavailable as an inverter option
The adoption of this technology as standard by Mitsubishi Electric, shows our commitment to both increasing your savings as well as protecting the global environment.
Energy Saving: Reduced power consumption
increased efficiency
Page 5
Energy SavingTechnology
Application of new technologies in Mitsubishi Electric inver ter systems significantly enhance the generic benefits of inverter driven systems.
Reduced power consumptionincreased efficiency
Reluctance DC Rotary Compressors
The centralised winding DC motor uses less copper wiring than a conventional versionand features a new high density, centralised winding method that raises motor windingefficiency to 96%. Units incorporating this motor also benefit from a low starting current aswell as a stable set point.
Highly Efficient Scroll CompressorsThe scroll compressor is equipped with a ‘Frame Compliance Mechanism’ that allows movement in the axial direction of the frame supporting the moving scroll. This construction realises up to a 27%improvement in compressor efficiency by reducing both leakage and friction losses.
DC Fan MotorA high-efficiency DC motor drives the fan of the outdoor units. It offers up to 60% greater efficiency than an equivalent AC motor.
Simple Par tial Switching Method PAM ControlCompared to the conventional active filter method, the simplepartial method PAM (Pulse Amplitude Modulation) control found on the new models helps to reduce energy losses. When combined with the Vector-Wave Eco Inver ter, PAMcontrol also allows for greater power and efficiency.
Normal Inverter vs. PAM
PAM adjusts the form of the current wave so that it is close to that of the supply voltage wave. High harmonics are reduced and 98% of the electricity is utilised.
Time
SupplyVoltage
Current
SupplyVoltage
Time
Current
Page 6
Total Energy Conservation
Power Receiver and Twin LEV ControlMitsubishi Electric has developed a power receiver and twin LEVs(linear expansion valves) that optimise the performance of thecompressor. By ensuring optimum control in response to theoperating waveform and outdoor temperature, this technology is tailored to the characteristics of the new refrigerant to enhance operating efficiency.
Vector-Wave Eco InverterThis technology uses a specially designed microprocessor to produce the most efficient waveform in response tovarying compressor motor rpm. By improving operatingefficiency from low to high speeds, annual electricity costs are reduced.
Page 7
* 1Assuming existing pipework is suitable for R410A operational pressures * 2Not available on the MXZ-8A140VA Multi-Split outdoor unit or Classic Inverter (MSZ-HC)
Re-use of existing pipe work
In general the upgrading of existing R22 systems to modern efficient R410A systems has been a difficult or expensive option.This is because the existing pipe work would either have to be replaced,or cleaned with dedicated specialist equipment. These actions werenecessar y as the chlorine residue from R22 system pipe work caused chemical reactions with the lubricating oils used in HFCcompressors, the result being poor performance and system failure.
Mitsubishi Electric’s
Replace Technology
Upgrading existing R22/R407c systems to efficient inver ter models* 1
The M Series Inverter*2 & Mr Slim PowerInver ter ranges incorporate ‘ReplaceTechnology’ to allow the upgrading of systemsusing existing pipe work without the need toapply any special cleaning machines. Sizes 25to 71 utilise the Mitsubishi Electric patentedHard Alkyl Benzene (HAB) oil, a unique oilthat is more tolerant of contamination. Bycombining this oil with developments in oilseparator technology it is possible for thismodel to use existing pipe work without anyspecial operations.
Sizes 100 to 250 continue to use the morefamiliar Ester Oils that are sensitive tochemical contamination. To allow these modelsto utilise existing pipe work a unique ‘ReplaceFilter’ containing activated charcoal has beenincluded in the refrigerant circuit. During
commissioning the system is operated in‘Replace Mode’, this operation removing allthe chlorine contamination from the existingpipe work allowing trouble free operation.
Replacement filter (Sectional photo)
Activated carbon (absorbs chlorine and other chemicals)
Filter
RefrigerantRefrigerant
OutletInlet
Page 8
Reduces installation time & costs
AdvantagesFor tenants / owner � Reduces installation time causing less disruption of business� Saves on installation costs
For installer� Installation time is reduced significantly� It is not necessary to purchase new piping for R410A refrigerant� Time-consuming pipe cleaning is not necessary when employing Replace Technology
Page 9
Model / Size
MSZ-GA/GB/GC-VA
MSZ-FD-VA
PKA-RP-GAL/FAL(2)
MFZ-KA-VA
SEZ-KD-VA
PEAD-RP-EA(2)
PEA-RP-GA
SLZ-KA-VA
PLA-RP-BA(2)
PCA-RP-GA(2)
PCA-RP-HA
PSA-RP-GA
Split-System Product Range OverviewOutdoor Units
M Series Inverter
(Multi-Split)
M Series Inverter
MXZ-4A80VAMXZ-5A100VA
M Series Inverter
Multi-Split
22(2.2kW)
Multi-Split only
25(2.5kW)
35(3.5kW)
50(5.0kW)
60(6.0kW)
71(7.1kW)
0.9kW Cooling Capacity
Indoor Units
MXZ-3A54VAMXZ-4A71VA
M Series Inverter
Multi-Split
MUZ-GC35/FD25-35VA(H)SUZ-KA25/35VA
MXZ-2A52VA
MUZ-GB50/GA60-71VASUZ-KA50-71VA
Page 10
MXZ-8A140VA
M Series Power Multi
M Series Inverter
MUZ-GC25VA
44kW Cooling Capacity
100(10.0kW)
125(12.5kW)
140(14.0kW)
200(19.0kW)
250(22.0kW)
400(38.0kW)
500(44.0kW)
Mr Slim Power Inverter
PUHZ-RP60/71VHA3
Mr Slim Power Inverter
PUHZ-P100VHA2
Mr Slim Standard Inverter
PUHZ-P125-140VHA2PUHZ-P200/250YHA
Mr Slim Standard Inverter
PUHZ-RP35/50VHA3PUH-P125-140YHA
Mr Slim
Page 11
PUHZ-RP100V/YHA3PUHZ-RP125/140V/YHA2PUHZ-RP200/250YHA2
Mr Slim Power Inverter
PUH-P100YHA
Mr Slim
Available in a variety of options, our Split-System
range fits in wherever it’s needed. Indoor units
can be four way blow cassettes, ducted, wall,
floor or ceiling mounted. Up to eight indoor units
can then be connected to a single outdoor unit
providing the ideal air conditioning solution.
Designed to fit anywhere
The adaptable Split-System range
Simple technologyat its best
Systems marked with the ECA logo have an energy label of A or B, are registered on theEnergy Technology List and hence qualify for 100% first year enhanced capital allowances(whole system cost and ‘reasonable’ cost of installation). For further information please go to www.eca.gov.uk
Nominal conditions cooling: indoor 27˚C DB, 19˚C WB; outdoor 35˚C DB, 24˚C WB.Nominal conditions heating: indoor 20˚C DB; outdoor 7˚C DB, 6˚C WB.UK Conditions: Summer; indoor 21˚C DB, 15˚C WB; outdoor 27˚C DB. Winter; indoor 21˚C DB; outdoor -1˚C WB.
Page 12
M SeriesRoom Air Conditioning
Surprisingly affordable, the efficiency of the M Series range presents substantial savings inheating mode, when compared with more conventional heating systems. Additional features such as ‘Econo-Cool’ allow airflow to beprecisely directed towards users, allowing settemperatures to be raised by 2ºC with no loss incomfort and a 20% gain in energy efficiency.
Flexible enough to suit a range of applications, the M Series includes models that will run up toeight indoor units per outdoor unit. With vastlyincreased pipe length and height differences overits R407c predecessors, the M Series is extremelyversatile, helping to make system application easier.This diagram shows how a typical multi-splitsystem could be installed into a medium sizedoffice for example.
Highly efficientwhilst ozone friendly too
The entire M Series range is now available using Inverter technology. By matching the compressor speed to the cooling or heating load of the room, up to a 30% reduction in power consumption can be achieved.
Increasingly aware of the importance of protecting the environment, the M Series rangeuses the (ozone friendly) refrigerant with zeroODP (Ozone Depletion Potential) - R410A.Many models also make use of a new air filtering system containing the compoundCatechin, which helps to improve air quality andprevent the spread of bacteria and viruses.
M Series offers the end user some of the highestenergy efficiency ratings available, alongsidegreater application flexibility. Lower runningcosts and increased comfor t forconsumers are vir tually guaranteedand Mitsubishi Electric has made M Series the natural choice fortoday’s small to medium sizedapplication market.
The M Series range
Designed to heat or cool small to medium sized applications, the M Series range provides a versatile, yet affordable air conditioning solution. Quick to install and also one of the quietest units on the market (as low as 20dBA* 1), this newly designed, attractive range offers the perfect way to ensure a comfortableenvironment with the minimum of disruption.
* 1MSZ-FD25VA
Perfect for small to medium sized applications
Page 14
Designed to f it
anywhere
Clean, ComfortableEnvironmentCatechin Filter
Catechin is a bioflavonoid that is found in green tea. Bioflavonoids are a group of chemical substancespresent in many plants, that have both antiviral and antioxidant qualities. In addition to these benefits,Catechin also offers excellent deodorising characteristics; which is why Mitsubishi Electric uses thiscompound in its air conditioning filters to not only improve air quality, but to also prevent the spreadof bacteria and viruses within a room. The filter can be easily removed and when washed regularly,deodorising effectiveness should last for more than 10 years. MSZ-G and MSZ-HC wall mountedand MFZ floor mounted systems are supplied with or have the option of the Catechin filter.
“Anti-Allergy Enzyme Filter” mechanism
� Artificial enzyme catalyst on the filament catches the allergens.
� The artificial enzyme catalyst helps the chemical reaction with Oxygen and severs the S-S bonds.*1
� Proteins with severed S-S bonds are no longer allergen proteins.
*1 Mites and other allergen protein consist of sulfur atoms (S) that have bonded together.
Silent Operation
Unlike conventional models with a grilled air intake, wall mounted models feature a smoothly contoured,flat panel finish with a top air intake that not only improves aesthetics, but also helps to reduce noise as the heat exchanger area is fully covered. In fact, noise level during normal operation is only 20dBA for the MSZ-FD25VA, making it one of the quietest indoor units on the market. This is as a result of the multi-angled heat exchanger having a modified fin shape that reduces air resistance, producing a smoother, quieter flow of air.
Alongside this, the wide diameter of the fan produces greater airflow at lower fan speeds and the uneven pitch between each fan blade helps to eliminate unwanted noise.
Technological improvements reducing operating sound levels
Only 20dBA
Page 16
Operating StatusMonitoringMonitor lamps located on the right of the indoor unit provideat-a-glance recognition of the air conditioner operating status.When the difference between the set temperature and roomtemperature is more than 2°C, both monitor lamps will turnon. If it is less than 2°C, only the upper lamp will light.
The vane on the MSZ-GC22-35/GB50VA and MSZ-FD25/35VAwall mounted models easily detaches, allowing access to the louvres.These can then be opened outwards (without any special tools) forquick cleaning of the heat exchanger, fan and air vents. Regularcleaning will increase both operating efficiency and energy-savings.
Quick Clean
Design can
reduce your
electricity bill by
approximately 30%
*1Electricity bill comparison of operation under a fixed temperature with 8g of soil on the fan and also without.
Quick Clean Design
Electricity bill increases
by 5%*1
Electricity bill increases
by 25%*1
Heat Exchanger Fan Air Vent
Page 17
Powerful Heating CapacityThe VAH outdoor unit is engineered for use in cold regions and is equipped with a powerful compressor, enabling an improvement inheating capacity. The heating power is raised by about 30% over the standard model and keeps the room comfortable even on cold days.
Field Test Result: Size 35. Sweden, 23rd January 2008
Page 18
The New MSZ-FD SeriesThe new FD Series line-up is engineered for high energy efficiency and low sound levels. The I-See Sensor,Plasma-Duo filter system and other superb new functions raise the comfort level to even greater heights.
High Energy EfficiencyWith the latest inverter technology, energy efficiency is improved by about 20%.Specifically, more than 5.0 is attained for both the COP and EER for a size 25.
Quiet RunningA larger line flow fan is included in the FD model. This allows stable capacity with fewer rotations, reducing operating noise.
Page 19
The "I-See Sensor" automatically moves from side to side, searching floor temperature over a wide area of 150°.
Conventional air conditioners control indoor temperature by using only thetemperature of the intake air at the top of the room. As a result, the floorlevel temperature, which exerts such a crucial impact on the temperaturethat people feel, tends to be overlooked. The I-See Sensor detects the floor temperatures to ensure constant comfort in the living areas.
Cold air tends to sink to floor level, which is often the cause of over cooling. The I-See Sensor tracks this floor level temperature and adjusts the air outlet temperature accordingly.
Warm air tends to rise up from the floor level, which often prevents that zone from warming up. The I-See Sensor tracks this floor level temperature and adjusts the air outlet flow accordingly.
Besides a pre-filter, the MSZ-FD is also fitted with two plasma air-purifyingfunctions. These functions are engineered to change air dirt particles frommicron to nano-size in scale.
Plasma DeodorisationThe “Platinum catalyst deodorising filter” captures small foul-smelling substances in the air, then breaksdown the source of the odours with the power of the ozone generated in the plasma electrode unit and the platinum catalyst contained in the filter.
Plasma Electrode UnitA plasma electrode unit is mounted inside the airconditioner. Electro-discharge is used to generateozone & plasma. The collaboration betweenozone & plasma and two special filters creates a dynamic plasma air cleaning function.
Plasma Air PurificationThe “Anti-allergen electric enzyme filter” usesthe power of the static electricity charged inthe filter, as well as plasma generated in theplasma electrode unit to capture the bacteria,pollen and other allergens in the air, which arethen neutralised by the enzyme in the filter.
Mould Fighter mechanismStep 1After cooling operation the Plasma Electrode unit fills the inside of the indoor unit with ozone (O3).
Step 2The heat exchangeris dried for about40mins by the fanmode operation.
The MSZ-FD is equipped with a “Mould Fighter” function designed to suppress the growth ofspores of mould. The ozone generated in the plasma electrode unit attacks the mould spores,reducing mould growth by about 20%.
MXZ Multi-Split Systems
� 14kW Inverter Multi System, based on Mr Slim Power Inverter technology
� Ability to connect up to eight indoor units across the M Series and Mr Slim product range within a capacity index of 18.5kW
� Total Pipe Length of 115m / Height Difference of 30m
� ‘A’ rated energy label - High COP (3.91) & EER (3.52)
� Single phase power supply
� Connection of indoor units is through either a 3-way (PAC-AK30BC)or 5-way (PAC-AK50BC) branch box, either singularly or with two in combination
� Individual control of each indoor unit is now possible (ON/OFF and Setpoint)
� Low starting and running currents
� Connection to M-NET system via MAC-399IF-E interface (one per indoor unit needed)
� New Centralised Simple ON/OFF remote controller MAC-821SC-E available for use on all MXZ Multi-Split units. Up to eight indoor units can be controlled from one remote controller (Interface MAC-397IF-E is needed, one per indoor unit)
The MXZ-8A140VA Power Multi Inver ter Heat Pump Multi-Split Outdoor Unit
Ideal for apartments or small commercial buildings
Page 20
Outdoor Unit
Branch Box
Branch Box
Example of Power Multi System using eight indoor units
All Mitsubishi Electric MXZ Multi-Splitmodels have an energy label of ‘A’
Page 21
Available in wall and floor mounted, the M Series
range is quiet, economic to
run and easy to install. The outdoor units
can run up to eight indoor units, all
controlled with a simple remote controller.
Whatever your requirements
may be, Mitsubishi Electric
offers the perfect air conditioning
solution for any situation.
ExcellentFeatures
Systems marked with the ECA logo have an energy label of A or B, are registered on theEnergy Technology List and hence qualify for 100% first year enhanced capital allowances(whole system cost and ‘reasonable’ cost of installation). For further information please go to www.eca.gov.uk
Nominal conditions cooling: indoor 27˚C DB, 19˚C WB; outdoor 35˚C DB, 24˚C WB.Nominal conditions heating: indoor 20˚C DB; outdoor 7˚C DB, 6˚C WB.UK Conditions: Summer; indoor 21˚C DB, 15˚C WB; outdoor 27˚C DB. Winter; indoor 21˚C DB; outdoor -1˚C WB.
S imple technologyat its best
Page 22
MSZ-HC-VA(B) Inverter Heat Pump, Wall Mounted System
MSH-GA-VB Heat Pump, Wall Mounted System
MSZ-GA/GB/GC-VA Inverter Heat Pump, Wall Mounted System
MSZ-FD-VA Inverter Heat Pump, Wall Mounted System
MFZ-KA-VA Inverter Heat Pump, Floor Mounted System
MXZ-A-VA Multi-Split Inverter Heat Pump
MXZ-8A140VA Power Multi Inverter Heat Pump
Outdoor Units
M Series Accessories / Optional Extras
24
26
28
30
32
34
36
50
52
Contents
Page 23
MSZ-HC-VA(B) Inverter Heat Pump
Mitsubishi Electric’s new range of high specification, flat panel wall mountedmodels make use of inverter technology, whilst providing extremely goodvalue for money, costing approximately 20% less than the MSZ-G equivalent.
These units have extremely quiet sound levels, whilst also deliveringeconomical air conditioning, with improved COP/EER figures and in many cases corresponding ‘A’ rated energy labels.
* Catechin filter is optional * Air cleaning filter is optional
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Heating/Cooling - Lo-Mi-Hi-SupHi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Heating/Cooling - Lo-Mi-Hi-SupHi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A)
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
MSZ-HC-VA(B) - INDOOR UNITSMSZ-HC25VA
3.2 (0.9-4.4)
2.5 (0.9-3.0)
2.65 (0.75-3.65)
2.5 (0.9-3.0)
0.79
3.64 / 3.25
A / A
5.1-6.5-7.8-9.1 / 5.3-7.0-8.7-10.5
9.52(3/8”)
6.35(1/4”)
26-32-38-43 / 26-32-38-43
788
225
295
9
Fed by Outdoor Unit
Single
0.22
6
4
MSZ-HC35VAB
3.6 (0.9-4.8)
3.4 (1.0-3.7)
3.0 (0.75-4.0)
3.35 (1.0-3.65)
0.76
3.62 / 3.01
A / B
4.9-6.7-8.0-9.2 / 5.2-6.8-8.4-10.2
9.52(3/8”)
6.35(1/4”)
26-32-38-43 / 26-32-38-43
788
225
295
9
Fed by Outdoor Unit
Single
0.22
6
4
MODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. CORES
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 7m
MUZ-HC-VA(B) - OUTDOOR UNITSMUZ-HC25VA
47 / 46
25
684
255
540
220-240v, 50Hz
Single
0.88 / 0.77
0.801 / 0.616
4.2
4.2 / 3.7 [5.5]
16
3
10
5
0.73
MUZ-HC35VAB
48 / 47
25
684
255
540
220-240v, 50Hz
Single
0.995 / 1.13
0.905 / 0.904
5.3
4.8 / 5.3 [6.5]
16
3
10
5
0.75
Technical Information
Page 24
Classic Wall Mounted System
MSZ
-HC
-VA
(B)
Inve
rter
Hea
t Pu
mp
INDOOR UNIT MSZ-HC25/35VA(B)
Upper View >
Front View > Side View >
M S
erie
sR
ange
200
8Dimensions
Page 25
MSH-GA-VB Heat Pump
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Heating/Cooling - Lo-Mi-Hi-SupHi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Heating/Cooling - Lo-Mi-Hi-SupHi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A)
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
MSH-GA-VB - INDOOR UNITSMSH-GA50VB
5.2
5.0
4.3
4.95
0.65
3.23 / 2.81
C / C
8.8-10.7-12.8 / 8.8-10.7-12.8
12.7(1/2”)
6.35(1/4”)
34-38-42 / 34-38-42
1100
258
325
16
220-240v, 50Hz
Single
0.30
6
2 Core 12v
MSH-GA60VB
7.2
6.3
6.0
6.25
0.64
2.90 / 2.61
D / D
8.8-10.7-12.8 / 9.8-11.2-12.8
15.88(5/8”)
6.35(1/4”)
34-40-45 / 37-41-45
1100
258
325
16
220-240v, 50Hz
Single
0.30
6
2 Core 12v
MODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. CORES
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 7m
MUH-GA-VB - OUTDOOR UNITSMUH-GA50VB
52 / 52
47
850
290
605
220-240v, 50Hz
Single
1.61 / 1.78
1.465 / 1.424
37
7.23 / 7.93 [12.9]
16
3
25
10
1.80
MUH-GA60VB
53 / 53
74
840
330
850
220-240v, 50Hz
Single
2.48 / 2.41
2.257 / 1.928
74
10.70 / 10.39 [16.5]
25
3
25
10
2.35
Notes: MSH-GA50/60VB indoor units require a 240v, 50hz single phase supply and the outdoor units require the same, separate supply. Between the indoor and outdoor unit is a 2 Core, low voltage interconnecting cable.
Technical Information
Page 26
Mitsubishi Electric’s range of high specification, flat panel wallmounted models make use of traditional fixed speed technology,whilst providing extremely good value for money, costingapproximately 30% less than the inverter equivalent.
These units have extremely quiet sound levels, whilst also deliveringeconomical air conditioning. Ideal for use in any size room, both units come equipped with a wide-angle airflow system, as well as an automatic swing vane, allowing airflow to be extended to every corner of a room.
* Air cleaning filter is optional
Classic Wall Mounted System
MSH
-GA
-VB
Hea
t Pu
mp
INDOOR UNIT MSH-GA50/60VB
Upper View >
Side View >
Front View >
M S
erie
sR
ange
200
8Dimensions
Page 27
MSZ-GA/GB/GC-VA - INDOOR UNITS
MSZ-GA/GB/GC-VA Inverter Heat Pump
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Heating/Cooling - Lo-Mi-Hi-SupHi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Heating/Cooling - Lo-Mi-Hi-SupHi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) – HRC (A)
INTERCONNECTING CABLE No. CORES
MUZ-GA/GB/GC-VA - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling - Lo-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. CORES
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 7m
MSZ-GA60VA6.8 (0.9-8.1)
6.0 (0.9-6.7)
5.65 (0.75-6.75)
5.95 (0.9-6.65)
0.79
3.51 / 3.11
B / B
8.7-13.1-17.2 / 8.7-12.8-17.2
15.88 (5/8”)
6.35 (1/4”)
32-40-54
1100
258
325
16
Fed by Outdoor Unit
Single
6
4
MSZ-GA71VA8.1 (0.9-9.6)
7.1 (0.9-8.3)
6.75 (0.75-8.0)
7.05 (0.9-8.25)
0.71
3.31 / 2.93
C / C
9.4-13.6-17.2 / 9.4-13.3-17.2
15.88 (5/8”)
9.52 (3/8”)
33-40-54
1100
258
325
16
Fed by Outdoor Unit
Single
6
4
MSZ-GB50VA5.8 (0.9-7.8)
5.0 (0.9-5.8)
4.8 (0.75-6.5)
4.95 (0.9-5.75)
0.69
3.41 / 3.03
B / B
6.9-7.4-10.9 / 6.9-7.4-10.9
12.7 (1/2”)
6.35 (1/4”)
30-36-42-48 / 32-38-44-48
780
210
298
9
Fed by Outdoor Unit
Single
6
4
MSZ-GC22VA3.3
2.2
2.75
2.2
-
-
-
4.6-6.3-8.0-10.0 / 4.1-5.9-7.7-9.6
9.52 (3/8”)
6.35 (1/4”)
21-29-36-43
788
234
295
9
Fed by Outdoor Unit
Single
6
4
MSZ-GC25VA3.2 (0.9-4.5)
2.5 (0.9-3.0)
2.65 (0.75-3.75)
2.5 (0.9-3.0)
0.79
3.83 / 3.76
A / A
4.6-6.3-8.0-10.0 / 4.1-5.9-7.7-9.6
9.52 (3/8”)
6.35 (1/4”)
21-29-36-43
788
234
295
9
Fed by Outdoor Unit
Single
6
4
MSZ-GC35VA4.0 (0.9-5.0)
3.5 (1.0-3.9)
3.3 (0.75-4.15)
3.45 (1.0-3.85)
0.76
3.79 / 3.26
A / A
4.1-5.6-7.7-9.5 / 3.9-5.5-7.4-9.2
9.52 (3/8”)
6.35 (1/4”)
22-29-36-43
788
234
295
9
Fed by Outdoor Unit
Single
6
4
MUZ-GA60VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
1.94 / 1.93
1.77 / 1.54
8.93
8.93 / 8.83 [16]
25
3
30
15
1.8
MUZ-GA71VA
53-55 / 51-53
58
840
330
850
220-240v, 50Hz
2.45 / 2.42
2.23 / 1.94
11.2
11.2 / 11.0 [16]
25
3
30
15
2.0
MUZ-GB50VA
53-55 / 51-52
53
840
330
850
220-240v, 50Hz
1.70 / 1.65
1.55 / 1.32
7.46
7.78 / 7.58 [16]
25
3
30
15
1.5
N/A Multi-Split Only
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
MUZ-GC25VA
47 / 46
26
684
255
540
220-240v, 50Hz
0.835 / 0.665
0.76 / 0.532
4.2
4.2 / 3.6 [5.8]
16
3
20
12
0.75
MUZ-GC35VA
48 / 47
31
800
285
550
220-240v, 50Hz
1.055 / 1.075
0.96 / 0.86
5.0
4.9 / 5.0 [6.5]
16
3
20
12
0.85
Technical Information
Page 28
The MSZ series has been completely redesignedand features the new Catechin filter system.
These models also offer industry leading noise levels and have a distinctively styled front panel that not only looks appealing but also helpsto make cleaning of the unit easier.
Wall Mounted System
* Wide swing & long airflow mode available for MSZ-GA60/71VA * The anti-allergy enzyme filter is optional* Quick clean design available for MSZ-GC22-35/GB50VA
MSZ
-GA
/GB/
GC
-VA
Inve
rter
Hea
t Pu
mp
INDOOR UNIT MSZ-GC22-35VA
INDOOR UNIT MSZ-GB50VA
INDOOR UNIT MSZ-GA60/71VA
Front View >Side View >
Upper View >
Front View >
Side View >
Upper View >
Front View >
Side View >
Upper View >
M S
erie
sR
ange
200
8Dimensions
Page 29
MSZ-FD-VA - INDOOR UNITS
MSZ-FD-VA Inverter Heat Pump
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Heating/Cooling - Lo-Mi-Hi-SupHi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Heating/Cooling - Lo-Mi-Hi-SupHi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) – HRC (A)
INTERCONNECTING CABLE No. CORES
MUZ-FD-VAH - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. CORES
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 7m
MSZ-FD25VA3.2 (1.5-6.3)
2.5 (1.1-3.5)
2.65 (1.25-5.25)
2.5 (1.1-3.45)
0.85
5.25 / 5.15
A / A
4.5-6.7-9.2-12.1 / 4.6-6.3-8.6-11.2
9.52 (3/8”)
6.35 (1/4”)
20-29-36-43 / 20-29-36-42
798
257
295
12
Fed by Outdoor Unit
Single
6
4
MSZ-FD35VA4.0 (1.3-7.7)
3.5 (0.8-4.0)
3.3 (1.1-6.4)
3.45 (0.8-3.95)
0.85
4.71 / 4.19
A / A
4.7-6.7-9.2-12.5 / 4.6-6.3-8.6-11.2
9.52 (3/8”)
6.35 (1/4”)
21-29-36-44 / 21-29-36-43
798
257
295
12
Fed by Outdoor Unit
Single
6
4
MUZ-FD25VAH
46 / 46
36
800
285
550
220-240v, 50Hz
0.61 / 0.485
0.555 / 0.388
2.9
2.9 / 2.4 [9.2]
16
3
20
12
1.15
MUZ-FD35VAH
50 / 47
36
800
285
550
220-240v, 50Hz
0.85 / 0.835
0.774 / 0.668
3.9
3.9 / 3.8 [10.5]
16
3
20
12
1.15
Technical Information
Page 30
The MSZ-FD series is our most energy efficient M Series wall mounted unit to date. These high COP models feature the new Plasma Duo filter system. These models also offerindustry leading noise levels and have a distinctively styled front panel that not only looks appealing but also helps to make cleaning of the unit easier.
Also incorporated is an ‘I-See Sensor’, providing even temperaturedistribution and further reducing energy consumption.
Wall Mounted System
MSZ
-FD
-VA
Inve
rter
Hea
t Pu
mp
INDOOR UNIT MSZ-FD25/35VA
Front View > Side View >
Upper View >
M S
erie
sR
ange
200
8Dimensions
Page 31
MFZ-KA-VA - INDOOR UNITS
MFZ-KA-VA Inverter Heat Pump
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Heating/Cooling - Lo-Mi-Hi-SupHi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Heating/Cooling - Lo-Mi-Hi-SupHi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) – HRC (A)
INTERCONNECTING CABLE No. CORES
SUZ-KA-VA - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. CORES
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 7m
MFZ-KA25VA
3.4 (0.9-5.1)
2.5 (0.9-3.4)
2.85 (0.75-4.25)
2.5 (0.9-3.35)
0.66
4.07 / 4.31
A / A
5.0-6.2-7.6-9.1 / 4.8-5.8-7.1-8.7
9.52 (3/8”)
6.35 (1/4”)
22-27-32-37 / 22-27-32-37
700
200
600
14
Fed by Outdoor Unit
Single
6
4
MFZ-KA35VA
4.0 (0.9-6.2)
3.5 (0.9-3.9)
3.3 (0.75-5.15)
3.45 (0.9-3.85)
0.65
3.64 / 3.21
A / A
5.2-6.2-7.8-9.5 / 5.0-6.1-7.4-9.1
9.52 (3/8”)
6.35 (1/4”)
25-28-33-38 / 23-28-33-38
700
200
600
14
Fed by Outdoor Unit
Single
6
4
MFZ-KA50VA
6.0 (0.9-7.9)
4.8 (0.9-5.4)
5.0 (0.75-6.55)
4.75 (0.9-5.35)
0.63
3.23 / 3.10
C / B
7.4-8.8-9.8-11.8 / 7.1-7.9-9.2-10.7
12.7 (1/2”)
6.35 (1/4”)
32-35-39-44 / 32-35-39-43
700
200
600
14
Fed by Outdoor Unit
Single
6
4
SUZ-KA25VA
46 / 46
33
800
285
550
220-240v, 50Hz
0.835 / 0.58
0.76 / 0.46
3.8
4.0 / 2.8 [9.2]
16
3
20
12
0.9
SUZ-KA35VA
48 / 47
37
800
285
550
220-240v, 50Hz
1.10 / 1.09
1.00 / 0.87
4.8
5.0 / 5.0 [10.3]
16
3
20
12
1.05
SUZ-KA50VA
55 / 53
53
840
330
850
220-240v, 50Hz
1.86 / 1.55
1.69 / 1.24
8.3
8.5 / 7.0 [17.8]
25
3
30
15
1.6
Technical Information
Page 32
The MFZ-KA-VA series is extremely versatile and isdesigned for wall attached installation at floor level.The auto swing vane provides a more natural andcomfortable airflow throughout the room and the lightweight, compact design makes installation easy.
Floor Mounted System
MFZ
-KA
-VA
Inve
rter
Hea
t Pu
mp
INDOOR UNIT MFZ-KA25-50VA
Front View >
Upper View >
Side View >M
Ser
ies
Ran
ge 2
008Dimensions
Page 33
MXZ-A-VA - OUTDOOR UNITS
MXZ-A-VA Inverter Heat Pump (5.2 - 10.0kW)
MODEL REFERENCE
NUMBER OF CONNECTABLE INDOOR UNITS
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
MAX AIRFLOW (m3/min) Heating/Cooling
NOISE (dBA) Heating/Cooling - Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
RUNNING CURRENT (A) [MAX] Heating/Cooling
INTERCONNECTING CABLE No. CORES
TOTAL PIPE LENGTH (m)
MAX PIPE LENGTH PER INDOOR UNIT (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 40m (20m for MXZ-2A52VA)
FUSE RATING (BS88) – HRC (A)
MXZ-3A54VA
2 - 3
6.8 (2.6-9.0)
5.4 (2.9-6.8)
5.65 (2.15-7.5)
5.35 (2.9-6.75)
4.67 / 4.17
A / A
41.2 / 42.1
47-48 / 44-46
840
330
710
57
220-240v, 50Hz
1.455 / 1.295
1.32 / 1.04
6.39
6.39 / 5.69 [16.4]
4 Core
50
25
15 (10 if Outdoor higher than Indoor)
2.7
25
MXZ-4A71VA
2 - 4
8.6 (3.4-9.0)
7.1 (3.7-8.8)
7.15 (2.85-7.5)
7.05 (3.65-8.75)
4.41 / 3.68
A / A
46.5 / 42.1
48-50 / 45-48
840
330
710
58
220-240v, 50Hz
1.95 / 1.93
1.77 / 1.54
8.56
8.56 / 8.48 [16.4]
4 Core
60
25
15 (10 if Outdoor higher than Indoor)
2.7
25
MXZ-5A100VA
2 - 5
12.0 (3.4-14.0)
10.0 (3.7-11.0)
9.95 (2.85-11.65)
9.9 (3.65-10.9)
4.23 / 3.41
A / A
59.3 / 56.6
46-54 / 45-51
900
320
900
68
220-240v, 50Hz
2.835 / 2.935
2.58 / 2.35
12.88
12.45 / 12.88 [19.4]
4 Core
80
25
15 (10 if Outdoor higher than Indoor)
4.0
25
MXZ-2A52VA
2
6.4 (1.0-7.2)
5.2 (1.1-6.0)
5.3 (0.85-6.0)
5.15 (1.1-5.95)
3.75 / 3.46
A / A
31 / 31
48-50 / 45-49
800
285
550
40
220-240v, 50Hz
1.705 / 1.505
1.55 / 1.2
7.64
7.64 / 6.75 [10.2]
4 Core
30
20
15 (10 if Outdoor higher than Indoor)
1.3
16
MXZ-4A80VA
2 - 4
9.4 (3.4-11.6)
8.0 (3.7-9.2)
7.8 (2.85-9.65)
7.95 (3.65-9.15)
4.87 / 3.65
A / A
43.8 / 42.2
46-48 / 44-46
900
320
900
67
220-240v, 50Hz
1.93 / 2.19
1.76 / 1.75
9.62
8.48 / 9.62 [17.4]
4 Core
70
25
15 (10 if Outdoor higher than Indoor)
3.5
25
MULTI-SPLIT - INDOOR UNITSMODEL REFERENCE
MSZ-GC22/25/35VAMSZ-GB50VA
MSZ-FD25/35VAMFZ-KA25/35/50VA
SEZ-KD25/35/50VAPEAD-RP50EA
SLZ-KA25/35/50VAPLA-RP50BA
PCA-RP50GA2MXZ-3A54VA
MSZ-GC22/25/35VAMSZ-FD25/35VA
MFZ-KA25/35VA SEZ-KD25/35VA SLZ-KA25/35VAMXZ-2A52VA
MSZ-GC22/25/35VAMSZ-GB50VAMSZ-GA60VA
MSZ-FD25/35VA
MFZ-KA25/35/50VASEZ-KD25/35/50/60VA
PEAD-RP50EASLZ-KA25/35/50VA
PLA-RP50/60BAPCA-RP50/60GA(2)MXZ-4A71VA
MSZ-GC22/25/35VAMSZ-GB50VA
MSZ-GA60/71VAMSZ-FD25/35VA
MFZ-KA25/35/50VASEZ-KD25/35/50/60/71VA
PEAD-RP50EASLZ-KA25/35/50VAPLA-RP50/60/71BA
PCA-RP50/60/71GA(2)MXZ-4A80VA
MSZ-GC22/25/35VAMSZ-GB50VA
MSZ-GA60/71VAMSZ-FD25/35VA
MFZ-KA25/35/50VASEZ-KD25/35/50/60/71VA
PEAD-RP50EASLZ-KA25/35/50VAPLA-RP50/60/71BA
PCA-RP50/60/71GA(2)MXZ-5A100VA
WALL MOUNTED FLOOR MOUNTED DUCTED CEILING CASSETTE CEILING SUSPENDED
� Up to five indoor units may be connected to a single outdoor unit
� Energy saving inverter controlled outdoor unit adjusts compressor performance to economically match the demand for heating and cooling
� Units may be added within the capacity of the system as requirements change
� Single outdoor unit for minimal noise and space impact
� Capacities of indoor units may be mixed to suit individual rooms
Technical Information
Page 34
The multi-split system allows up to five M Series or Mr Slim wall mounted,cassette, ducted, floor or ceiling mounted indoor unit heat-pumps of differentcapacities to be operated from a single outdoor unit. This makes it an economicanswer in multi-room applications, whilst also offering space saving benefits.
Multi-Split Units
MX
Z-A
-VA
M
ulti-
Split
Inve
rter
Hea
t Pu
mp
(5.2
-10.
0kW
)
OUTDOOR UNIT MXZ-2A52VA
Front View > Side View >Upper View >
OUTDOOR UNIT MXZ-3A54VA / MXZ-4A71VA
Front View > Side View >Upper View >
D connection for MXZ-4A71VA
OUTDOOR UNIT MXZ-4A80VA / MXZ-5A100VA
Front View > Side View >Upper View >
E connection for MXZ-5A100VA
M S
erie
sR
ange
200
8Dimensions
Page 35
MXZ-8A140VA - OUTDOOR UNIT
MXZ-8A140VA Power Multi (14kW)
MODEL REFERENCE
NUMBER OF CONNECTABLE INDOOR UNITS
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
MAX AIRFLOW (m3/min)
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
RUNNING CURRENT (A) [MAX] Heating/Cooling
INTERCONNECTING CABLE No. CORES
TOTAL PIPE LENGTH (m)
MAX PIPE LENGTH PER INDOOR UNIT (m)
FURTHEST PIPE LENGTH - Outdoor to Indoor (m)
MAX HEIGHT DIFFERENCE - Outdoor to Indoor (m)
MAX HEIGHT DIFFERENCE - Indoor to Indoor (m)
CHARGE R410A (kg) - 40m
FUSE RATING (BS88) – HRC (A)
MXZ-8A140VA
2 - 8
16.0
14.0
13.3
13.9
4.10 / 3.69
A / A
100
52 / 50
950
330 (+30)
1350
128
220-240v, 50Hz
3.90 / 3.79
3.55 / 3.03
14
16.33 / 15.86 [29.5]
4 Core
115
15 (from Branch Box)
70
30 (20 if Outdoor lower than Indoor)
12
8.5
40
PAC-AK30BC
1 - 3
From Outdoor Unit
From Branch Box
15.88(5/8”)
9.52(3/8”)
55
60
30
15
450
280
198
PAC-AK30BC - BRANCH BOXMODEL REFERENCE
NUMBER OF CONNECTABLE INDOOR UNITS
POWER SUPPLY TO BRANCH BOX
POWER SUPPLY TO INDOOR UNITS
PIPE SIZE mm(in) Main Outdoor Side - Gas
PIPE SIZE mm(in) Main Outdoor Side - Liquid
MAX PIPE LENGTH - Outdoor Unit to Branch Box (m)
TOTAL PIPE LENGTH - Branch Boxes to Indoor Unit (m)
MAX HEIGHT DIFFERENCE - Outdoor Unit to Branch Box (m)
MAX HEIGHT DIFFERENCE - Branch Box to Indoor Unit (m)
DIMENSIONS (mm) Width
Depth
Height
PAC-AK50BC
1 - 5
From Outdoor Unit
From Branch Box
15.88(5/8”)
9.52(3/8”)
55
60
30
15
450
280
198
PAC-AK50BC - BRANCH BOXMODEL REFERENCE
NUMBER OF CONNECTABLE INDOOR UNITS
POWER SUPPLY TO BRANCH BOX
POWER SUPPLY TO INDOOR UNITS
PIPE SIZE mm(in) Main Outdoor Side - Gas
PIPE SIZE mm(in) Main Outdoor Side - Liquid
MAX PIPE LENGTH - Outdoor Unit to Branch Box (m)
TOTAL PIPE LENGTH - Branch Boxes to Indoor Unit (m)
MAX HEIGHT DIFFERENCE - Outdoor Unit to Branch Box (m)
MAX HEIGHT DIFFERENCE - Branch Box to Indoor Unit (m)
DIMENSIONS (mm) Width
Depth
Height
MULTI-SPLIT - INDOOR UNITSMODEL REFERENCE
MSZ-GC22/25/35VA
MSZ-GB50VA
MSZ-GA60/71VA
MSZ-FD25/35VA
MFZ-KA25/35/50VASEZ-KD25/35/50/60/71VA
PEAD-RP50/60/71EA
SLZ-KA25/35/50VA
PLA-RP35/50/60/71BA(2)MXZ-8A140VA
WALL MOUNTED FLOOR MOUNTED DUCTED CEILING CASSETTE
� 14kW Inverter Multi System, based on Mr Slim Power Inverter technology
� Total Pipe length of 115m / Height difference of 30m
� Individual control of each indoor unit is now possible (ON/OFF & Setpoint)
� Low starting and running currents
� Connection to M-NET system via MAC-399IF interface (one per indoor unit)
� New Centralised Simple ON/OFF remote controller MAC-821SC-E available to control up to 8 indoor units (interface MAC-397IF is needed, one per indoor unit)
Technical Information
Page 36
The Power Multi system allows up to eight M Series or Mr Slim cassette, ducted,floor, ceiling or wall mounted indoor units of different capacities to be operatedfrom a single outdoor unit, making use of two types of branch box to achievethis. This makes it an economic answer in multi-room applications and ideal forapartments or small commercial buildings.
Inverter Heat Pump Multi-Split Unit
MX
Z-8
A14
0VA
Pow
er M
ulti
Inve
rter
Hea
t Pu
mp
(14k
W)
OUTDOOR UNIT MXZ-8A140VA
Front View > Side View >
Front View > Side View >
Upper View >
Upper View >
Front View > Side View > Upper View >
BRANCH BOX PAC-AK30BC
BRANCH BOX PAC-AK50BC
M S
erie
sR
ange
200
8Dimensions
Page 37
MSZ-GA/GB/GC-VA Series
MFZ-KA-VA Series SEZ-KD-VA Series
MXZ-3A54/4A71VAInverter Multi units
MXZ-4A80/5A100VA Inverter Multi units
6Outdoor Units
30Indoor Units
MXZ-8A140VA Power Multi unit
PLA-RP-BA(2) Series
PCA-RP-GA(2) Series
SLZ-KA-VA Series
PEAD-RP-EA Series
Inverter Multi-Split Systems
MXZ-2A52VA Inverter Multi unit
MSZ-FD-VA Series
Page 38
Multi-Split systems allow up to eight M Series or Mr Slim cassette, ducted, floor, ceiling or wall mounted indoor units of different capacities to be operated from a single outdoor unit
1 ROOM22
25
35
2 ROOMS22 + 22
22 + 25
22 + 35
25 + 25
25 + 35
35 + 35
Indoor unitcombination Cooling / Heating Capacity (kW)
Unit A
2.20 / 3.30
2.50 / 3.60
3.50 / 4.00
2.20 / 3.05
2.20 / 2.90
1.93 / 2.43
2.50 / 3.15
2.13 / 2.63
2.60 / 3.20
Unit B
2.20 / 3.05
2.50 / 3.30
3.07 / 3.87
2.50 / 3.15
2.97 / 3.67
2.60 / 3.20
Unit C
MXZ-2A52VA1Outdoor Unit 2 Indoor Units
MXZ-4A71VA1Outdoor Unit Up to 4 Indoor Units
1 ROOM22
25
35
50
60
2 ROOMS22 + 22
22 + 25
22 + 35
22 + 50
22 + 60
25 + 25
25 + 35
25 + 50
25 + 60
35 + 35
35 + 50
35 + 60
50 + 50
50 + 60
60 + 60
3 ROOMS22 + 22 + 22
22 + 22 + 25
22 + 22 + 35
22 + 22 + 50
22 + 22 + 60
22 + 25 + 25
22 + 25 + 35
22 + 25 + 50
22 + 25 + 60
22 + 35 + 35
22 + 35 + 50
22 + 35 + 60
22 + 50 + 50
25 + 25 + 25
25 + 25 + 35
25 + 25 + 50
25 + 25 + 60
25 + 35 + 35
25 + 35 + 50
25 + 35 + 60
25 + 50 + 50
35 + 35 + 35
35 + 35 + 50
Unit A
2.20 / 3.30
2.50 / 3.60
3.50 / 4.00
5.00 / 7.20
6.00 / 7.90
2.20 / 3.30
2.20 / 3.23
2.20 / 2.82
2.08 / 2.63
1.82 / 2.31
2.50 / 3.60
2.50 / 3.17
2.27 / 2.87
2.00 / 2.53
3.40 / 4.30
2.80 / 3.54
2.51 / 3.17
3.40 / 4.30
3.09 / 3.91
3.40 / 4.30
2.20 / 2.87
2.20 / 2.74
1.98 / 2.39
1.66 / 2.01
1.50 / 1.82
2.16 / 2.62
1.91 / 2.31
1.61 / 1.95
1.46 / 1.77
1.70 / 2.06
1.46 / 1.77
1.34 / 1.62
1.28 / 1.56
2.36 / 2.86
2.09 / 2.53
1.78 / 2.15
1.61 / 1.95
1.86 / 2.26
1.61 / 1.95
1.48 / 1.79
1.42 / 1.72
2.36 / 2.86
2.07 / 2.51
Unit B
2.20 / 3.30
2.50 / 3.67
3.50 / 4.48
4.72 / 5.97
4.98 / 6.29
2.50 / 3.60
3.50 / 4.43
4.53 / 5.73
4.80 / 6.07
3.40 / 4.30
4.00 / 5.06
4.29 / 5.43
3.40 / 4.30
3.71 / 4.69
3.40 / 4.30
2.20 / 2.87
2.20 / 2.74
1.98 / 2.39
1.66 / 2.01
1.50 / 1.82
2.47 / 2.99
2.16 / 2.62
1.83 / 2.22
1.66 / 2.01
2.70 / 3.27
2.32 / 2.81
2.12 / 2.57
2.91 / 3.52
2.36 / 2.86
2.09 / 2.53
1.78 / 2.15
1.61 / 1.95
2.62 / 3.17
2.26 / 2.74
2.07 / 2.51
2.84 / 3.44
2.36 / 2.86
2.07 / 2.51
Unit C
2.20 / 2.87
2.50 / 3.12
3.14 / 3.82
3.78 / 4.58
4.10 / 4.96
2.47 / 2.99
3.03 / 3.67
3.66 / 4.43
3.98 / 4.82
2.70 / 3.27
3.32 / 4.02
3.64 / 4.41
2.91 / 3.52
2.36 / 2.86
2.92 / 3.54
3.54 / 4.30
3.88 / 4.68
2.62 / 3.17
3.23 / 3.91
3.55 / 4.30
2.84 / 3.44
2.36 / 2.86
2.96 / 3.58
Unit D
Indoor unitcombination
Cooling / Heating Capacity (kW)
Inverter Multi-Split System Combinations
1 ROOM22
25
35
50
2 ROOMS22 + 22
22 + 25
22 + 35
22 + 50
25 + 25
25 + 35
25 + 50
35 + 35
35 + 50
50 + 50
3 ROOMS22 + 22 + 22
22 + 22 + 25
22 + 22 + 35
22 + 22 + 50
22 + 25 + 25
22 + 25 + 35
22 + 25 + 50
22 + 35 + 35
25 + 25 + 25
25 + 25 + 35
25 + 25 + 50
25 + 35 + 35
Indoor unitcombination
Cooling / Heating Capacity (kW)
Unit A
2.20 / 3.30
2.50 / 3.60
3.50 / 4.00
5.00 / 6.80
2.20 / 3.30
2.20 / 3.18
2.08 / 2.62
1.65 / 2.08
2.50 / 3.40
2.25 / 2.83
1.80 / 2.27
2.70 / 3.40
2.22 / 2.80
2.70 / 3.40
1.80 / 2.27
1.72 / 2.17
1.50 / 1.89
1.26 / 1.59
1.64 / 2.08
1.45 / 1.83
1.23 / 1.54
1.30 / 1.62
1.80 / 2.27
1.59 / 2.00
1.35 / 1.70
1.42 / 1.78
Unit B
2.20 / 3.30
2.50 / 3.62
3.32 / 4.18
3.75 / 4.72
2.50 / 3.40
3.15 / 3.97
3.60 / 4.53
2.70 / 3.40
3.18 / 4.00
2.70 / 3.40
1.80 / 2.27
1.72 / 2.17
1.50 / 1.89
1.26 / 1.59
1.88 / 2.36
1.65 / 2.07
1.39 / 1.75
2.05 / 2.59
1.80 / 2.27
1.59 / 2.00
1.35 / 1.70
1.99 / 2.51
Unit C
1.80 / 2.27
1.96 / 2.46
2.40 / 3.02
2.88 / 3.62
1.88 / 2.36
2.30 / 2.90
2.78 / 3.51
2.05 / 2.59
1.80 / 2.27
2.22 / 2.80
2.70 / 3.40
1.99 / 2.51
MXZ-3A54VA1Outdoor Unit Up to 3 Indoor Units
Page 40
1 ROOM22
25
35
50
60
71
2 ROOMS22 + 22
22 + 25
22 + 35
22 + 50
22 + 60
22 + 71
25 + 25
25 + 35
25 + 50
25 + 60
25 + 71
35 + 35
35 + 50
Unit A
2.20 / 3.30
2.50 / 3.60
3.50 / 4.00
5.00 / 7.20
6.00 / 7.90
7.10 / 8.60
2.20 / 3.30
2.20 / 3.23
2.20 / 2.82
2.20 / 2.72
1.75 / 2.52
1.66 / 2.22
2.50 / 3.60
2.50 / 3.17
2.50 / 3.00
2.11 / 2.76
2.01 / 2.42
3.50 / 4.00
3.10 / 3.87
Unit B
2.20 / 3.30
2.50 / 3.67
3.50 / 4.48
5.00 / 6.20
6.00 / 6.88
6.19 / 7.18
2.50 / 3.60
3.50 / 4.43
5.00 / 6.00
5.64 / 6.64
5.84 / 6.98
3.50 / 4.00
4.65 / 5.53
Unit C Unit D
Indoor unitcombination
Cooling / Heating Capacity (kW)
MXZ-4A80VA1Outdoor Unit Up to 4 Indoor Units
35 + 60
35 + 71
50 + 50
50 + 60
50 + 71
60 + 60
60 + 71
3 ROOMS
22 + 22 + 22
22 + 22 + 25
22 + 22 + 35
22 + 22 + 50
22 + 22 + 60
22 + 22 + 71
22 + 25 + 25
22 + 25 + 35
22 + 25 + 50
22 + 25 + 60
22 + 25 + 71
22 + 35 + 35
22 + 35 + 50
22 + 35 + 60
22 + 35 + 71
22 + 50 + 50
22 + 50 + 60
22 + 50 + 71
25 + 25 + 25
25 + 25 + 35
25 + 25 + 50
25 + 25 + 60
25 + 25 + 71
25 + 35 + 35
25 + 35 + 50
25 + 35 + 60
25 + 35 + 71
25 + 50 + 50
25 + 50 + 60
35 + 35 + 35
35 + 35 + 50
35 + 35 + 60
35 + 35 + 71
35 + 50 + 50
35 + 50 + 60
Unit A
2.61 / 3.46
2.51 / 3.10
3.95 / 4.70
3.42 / 4.27
3.27 / 3.88
4.00 / 4.70
3.84 / 4.31
2.20 / 2.90
2.20 / 2.84
2.14 / 2.62
1.72 / 2.20
1.46 / 1.99
1.40 / 1.80
2.20 / 2.72
2.08 / 2.52
1.79 / 2.13
1.64 / 1.93
1.49 / 1.75
1.87 / 2.25
1.63 / 1.93
1.50 / 1.77
1.38 / 1.62
1.44 / 1.70
1.33 / 1.57
1.23 / 1.45
2.50 / 3.00
2.28 / 2.76
1.98 / 2.35
1.82 / 2.14
1.65 / 1.94
2.07 / 2.48
1.82 / 2.14
1.67 / 1.96
1.53 / 1.79
1.60 / 1.88
1.48 / 1.74
2.65 / 3.13
2.33 / 2.74
2.15 / 2.53
1.99 / 2.33
2.08 / 2.44
1.93 / 2.27
Unit B
5.24 / 5.94
5.44 / 6.30
3.95 / 4.70
4.57 / 5.13
4.72 / 5.52
4.00 / 4.70
4.16 / 5.09
2.20 / 2.90
2.20 / 2.81
2.14 / 2.62
1.72 / 2.20
1.46 / 1.99
1.40 / 1.80
2.50 / 3.09
2.36 / 2.87
2.04 / 2.42
1.87 / 2.20
1.69 / 1.99
2.99 / 3.58
2.58 / 3.07
2.40 / 2.81
2.18 / 2.57
3.28 / 3.85
3.03 / 3.56
2.80 / 3.29
2.50 / 3.00
2.28 / 2.76
1.98 / 2.35
1.82 / 2.14
1.65 / 1.94
2.89 / 3.46
2.54 / 2.99
2.33 / 2.74
2.14 / 2.51
3.20 / 3.76
2.96 / 3.48
2.65 / 3.13
2.33 / 2.74
2.15 / 2.53
1.99 / 2.33
2.96 / 3.48
2.76 / 3.24
Unit C
2.20 / 2.90
2.50 / 3.19
3.42 / 4.16
4.41 / 5.00
5.03 / 5.42
5.20 / 5.80
2.50 / 3.09
3.31 / 4.01
4.07 / 4.85
4.49 / 5.27
4.82 / 5.66
2.99 / 3.58
3.69 / 4.39
4.1 / 4.82
4.44 / 5.21
3.28 / 3.85
3.64 / 4.27
3.97 / 4.67
2.50 / 3.00
3.19 / 3.87
3.94 / 4.70
4.36 / 5.13
4.70 / 5.52
2.89 / 3.46
3.64 / 4.27
4.00 / 4.70
4.33 / 5.09
3.20 / 3.76
3.56 / 4.18
2.65 / 3.13
3.34 / 3.92
3.70 / 4.34
4.02 / 4.74
2.96 / 3.48
3.31 / 3.89
Unit D
Indoor unitcombination
Cooling / Heating Capacity (kW)
4 ROOMS22 + 22 + 22 + 22
22 + 22 + 22 + 25
22 + 22 + 22 + 35
22 + 22 + 22 + 50
22 + 22 + 25 + 25
22 + 22 + 25 + 35
22 + 22 + 25 + 50
22 + 22 + 35 + 35
22 + 25 + 25 + 25
22 + 25 + 25 + 35
22 + 25 + 25 + 50
22 + 25 + 35 + 35
25 + 25 + 25 + 25
25 + 25 + 25 + 35
25 + 25 + 25 + 50
25 + 25 + 35 + 35
Unit A
1.77 / 2.15
1.72 / 2.08
1.55 / 1.87
1.35 / 1.63
1.66 / 2.01
1.50 / 1.82
1.31 / 1.59
1.37 / 1.66
1.61 / 1.94
1.46 / 1.77
1.29 / 1.56
1.34 / 1.62
1.77 / 2.15
1.61 / 1.95
1.42 / 1.72
1.48 / 1.79
Unit B
1.77 / 2.15
1.72 / 2.08
1.55 / 1.87
1.35 / 1.63
1.66 / 2.01
1.50 / 1.82
1.31 / 1.59
1.37 / 1.66
1.83 / 2.22
1.66 / 2.01
1.45 / 1.76
1.52 / 1.84
1.77 / 2.15
1.61 / 1.95
1.42 / 1.72
1.48 / 1.79
Unit C
1.77 / 2.15
1.72 / 2.08
1.55 / 1.87
1.35 / 1.63
1.89 / 2.29
1.71 / 2.07
1.50 / 1.81
2.18 / 2.64
1.83 / 2.22
1.66 / 2.01
1.45 / 1.76
2.12 / 2.57
1.77 / 2.15
1.61 / 1.95
1.42 / 1.72
2.07 / 2.51
Unit D
1.77 / 2.15
1.94 / 2.36
2.45 / 2.98
3.05 / 3.71
1.89 / 2.29
2.39 / 2.89
2.98 / 3.61
2.18 / 2.64
1.83 / 2.22
2.32 / 2.81
2.91 / 3.52
2.12 / 2.57
1.77 / 2.15
2.27 / 2.75
2.84 / 3.44
2.07 / 2.51
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 41
4 ROOMS22 + 22 + 22 + 22
22 + 22 + 22 + 25
22 + 22 + 22 + 35
22 + 22 + 22 + 50
22 + 22 + 22 + 60
22 + 22 + 22 + 71
22 + 22 + 25 + 25
22 + 22 + 25 + 35
22 + 22 + 25 + 50
22 + 22 + 25 + 60
22 + 22 + 25 + 71
22 + 22 + 35 + 35
22 + 22 + 35 + 50
22 + 22 + 35 + 60
22 + 22 + 50 + 50
22 + 25 + 25 + 25
22 + 25 + 25 + 35
22 + 25 + 25 + 50
22 + 25 + 25 + 60
22 + 25 + 35 + 35
22 + 25 + 35 + 50
22 + 25 + 35 + 60
22 + 35 + 35 + 35
22 + 35 + 35 + 50
25 + 25 + 25 + 25
25 + 25 + 25 + 35
25 + 25 + 25 + 50
25 + 25 + 25 + 60
25 + 25 + 35 + 35
25 + 25 + 35 + 50
25 + 35 + 35 + 35
35 + 35 + 35 + 35
Unit A
1.95 / 2.35
1.90 / 2.27
1.73 / 2.05
1.52 / 1.78
1.40 / 1.64
1.28 / 1.51
1.87 / 2.20
1.68 / 1.99
1.48 / 1.74
1.36 / 1.60
1.26 / 1.48
1.54 / 1.81
1.36 / 1.60
1.12 / 1.49
1.22 / 1.44
1.78 / 2.14
1.63 / 1.93
1.44 / 1.70
1.33 / 1.57
1.51 / 1.77
1.33 / 1.57
1.24 / 1.46
1.40 / 1.63
1.24 / 1.45
1.98 / 2.35
1.82 / 2.14
1.60 / 1.88
1.48 / 1.74
1.67 / 1.96
1.48 / 1.74
1.55 / 1.81
2.00 / 2.35
Unit B
1.95 / 2.35
1.90 / 2.27
1.73 / 2.05
1.52 / 1.78
1.40 / 1.64
1.28 / 1.51
1.87 / 2.20
1.68 / 1.99
1.48 / 1.74
1.36 / 1.60
1.26 / 1.48
1.54 / 1.81
1.36 / 1.60
1.12 / 1.49
1.22 / 1.44
2.04 / 2.42
1.86 / 2.20
1.64 / 1.93
1.52 / 1.78
1.71 / 2.01
1.52 / 1.78
1.41 / 1.65
2.20 / 2.59
1.97 / 2.32
1.98 / 2.35
1.82 / 2.14
1.60 / 1.88
1.48 / 1.74
1.67 / 1.96
1.48 / 1.74
2.15 / 2.53
2.00 / 2.35
Unit C
1.95 / 2.35
1.90 / 2.27
1.73 / 2.05
1.52 / 1.78
1.40 / 1.64
1.28 / 1.51
2.13 / 2.50
1.91 / 2.26
1.68 / 1.97
1.55 / 1.83
1.43 / 1.68
2.46 / 2.89
2.18 / 2.55
1.92 / 2.37
2.78 / 3.26
2.04 / 2.42
1.86 / 2.20
1.64 / 1.93
1.52 / 1.78
2.39 / 2.81
2.12 / 2.49
1.97 / 2.32
2.20 / 2.59
1.97 / 2.32
1.98 / 2.35
1.82 / 2.14
1.60 / 1.88
1.48 / 1.74
2.33 / 2.74
2.08 / 2.44
2.15 / 2.53
2.00 / 2.35
Unit D
1.95 / 2.35
2.15 / 2.59
2.76 / 3.25
3.44 / 4.06
3.81 / 4.48
4.16 / 4.87
2.13 / 2.50
1.91 / 3.16
3.36 / 3.95
3.73 / 4.37
4.05 / 4.76
2.46 / 2.89
3.10 / 3.65
3.84 / 4.05
2.78 / 3.26
2.04 / 2.42
2.60 / 3.07
3.28 / 3.85
3.64 / 4.27
2.39 / 2.81
3.03 / 3.56
3.38 / 3.97
2.20 / 2.59
2.82 / 3.31
1.98 / 2.35
2.54 / 2.98
3.20 / 3.76
3.56 / 4.18
2.33 / 2.74
2.96 / 3.48
2.15 / 2.53
2.00 / 2.35
Indoor unitcombination
Cooling / Heating Capacity (kW)
1 ROOM22
25
35
50
60
71
Unit A
2.20 / 3.30
2.50 / 3.60
3.50 / 4.00
5.00 / 7.20
6.00 / 7.90
7.10 / 8.60
Unit B Unit C Unit D
Indoor unitcombination Cooling / Heating Capacity (kW)
MXZ-5A100VA1Outdoor Unit Up to 5 Indoor Units
2 ROOMS22 + 22
22 + 25
22 + 35
22 + 50
22 + 60
22 + 71
25 + 25
25 + 35
25 + 50
25 + 60
25 + 71
35 + 35
35 + 50
35 + 60
35 + 71
50 + 50
50 + 60
50 + 71
60 + 60
60 + 71
71 + 71
3 ROOMS
22 + 22 + 22
22 + 22 + 25
22 + 22 + 35
22 + 22 + 50
22 + 22 + 60
22 + 22 + 71
22 + 25 + 25
22 + 25 + 35
22 + 25 + 50
22 + 25 + 60
22 + 25 + 71
22 + 35 + 35
22 + 35 + 50
22 + 35 + 60
22 + 35 + 71
22 + 50 + 50
22 + 50 + 60
22 + 50 + 71
22 + 60 + 60
22 + 60 + 71
Unit A
2.20 / 3.30
2.20 / 3.23
2.20 / 2.82
2.20 / 2.72
2.08 / 2.52
1.86 / 2.22
2.50 / 3.60
2.50 / 3.17
2.50 / 3.00
2.28 / 2.94
2.04 / 2.60
3.50 / 4.00
3.19 / 4.12
2.89 / 3.68
2.62 / 3.30
3.95 / 5.00
3.64 / 4.55
3.43 / 4.13
4.15 / 5.00
3.89 / 4.58
4.40 / 5.00
2.20 / 2.90
2.20 / 2.80
2.14 / 2.78
1.84 / 2.57
1.68 / 2.33
1.53 / 2.10
2.20 / 2.72
2.08 / 2.68
1.79 / 2.49
1.64 / 2.26
1.49 / 2.05
1.87 / 2.40
1.63 / 2.26
1.50 / 2.07
1.46 / 1.89
1.50 / 1.98
1.42 / 1.83
1.38 / 1.69
1.40 / 1.70
1.29 / 1.58
Unit B
2.20 / 3.30
2.50 / 3.67
3.50 / 4.48
5.00 / 6.18
5.67 / 6.88
5.99 / 7.18
2.50 / 3.60
3.50 / 4.43
5.00 / 6.00
5.47 / 7.06
5.81 / 7.40
3.50 / 4.00
4.56 / 5.88
4.96 / 6.32
5.33 / 6.70
3.95 / 5.00
4.36 / 5.45
4.87 / 5.87
4.15 / 5.00
4.61 / 5.42
4.40 / 5.00
2.20 / 2.90
2.20 / 2.81
2.14 / 2.78
1.84 / 2.57
1.68 / 2.33
1.53 / 2.10
2.50 / 3.09
2.36 / 3.05
2.04 / 2.84
1.87 / 2.57
1.69 / 2.33
2.99 / 3.80
2.58 / 3.60
2.40 / 3.29
2.32 / 3.01
3.40 / 4.51
3.22 / 4.17
3.15 / 3.85
3.80 / 4.65
3.53 / 4.31
Unit C
2.20 / 2.90
2.50 / 3.19
3.42 / 4.44
4.17 / 5.86
4.59 / 6.35
4.94 / 6.80
2.50 / 3.09
3.31 / 4.27
4.07 / 5.67
4.49 / 6.17
4.82 / 6.62
2.99 / 3.80
3.69 / 5.14
4.1 / 5.64
4.72 / 6.10
3.40 / 4.51
3.86 / 5.00
4.47 / 5.46
3.80 / 4.65
4.18 / 5.11
Unit D
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 42
22 + 22 + 35 + 71
22 + 22 + 50 + 50
22 + 22 + 50 + 60
22 + 22 + 50 + 71
22 + 25 + 25 + 25
22 + 25 + 25 + 35
22 + 25 + 25 + 50
22 + 25 + 25 + 60
22 + 25 + 25 + 71
22 + 25 + 35 + 35
22 + 25 + 35 + 50
22 + 25 + 35 + 60
22 + 25 + 35 + 71
22 + 25 + 50 + 50
22 + 25 + 50 + 60
22 + 25 + 50 + 71
22 + 35 + 35 + 35
22 + 35 + 35 + 50
22 + 35 + 35 + 60
22 + 35 + 35 + 71
22 + 35 + 50 + 50
25 + 25 + 25 + 25
25 + 25 + 25 + 35
25 + 25 + 25 + 50
25 + 25 + 25 + 60
25 + 25 + 25 + 71
25 + 25 + 35 + 35
25 + 25 + 35 + 50
25 + 25 + 35 + 60
25 + 25 + 35 + 71
25 + 25 + 50 + 50
25 + 25 + 50 + 60
25 + 25 + 50 + 71
25 + 35 + 35 + 35
25 + 35 + 35 + 50
25 + 35 + 35 + 60
25 + 35 + 35 + 71
35 + 35 + 35 + 35
35 + 35 + 35 + 50
35 + 35 + 35 + 60
Unit A
1.32 / 1.61
1.37 / 1.68
1.29 / 1.57
1.24 / 1.47
1.78 / 2.26
1.63 / 2.05
1.50 / 1.98
1.42 / 1.83
1.38 / 1.69
1.57 / 2.07
1.42 / 1.83
1.40 / 1.70
1.29 / 1.58
1.35 / 1.65
1.26 / 1.54
1.22 / 1.44
1.48 / 1.91
1.39 / 1.70
1.30 / 1.59
1.25 / 1.48
1.31 / 1.54
1.98 / 2.50
1.82 / 2.27
1.70 / 2.20
1.59 / 2.04
1.54 / 1.88
1.73 / 2.29
1.67 / 2.04
1.55 / 1.90
1.47 / 1.76
1.50 / 1.83
1.45 / 1.72
1.39 / 1.61
1.63 / 2.12
1.55 / 1.89
1.48 / 1.77
1.40 / 1.66
2.25 / 2.75
2.08 / 2.48
1.97 / 2.33
Unit B
1.32 / 1.61
1.37 / 1.68
1.29 / 1.57
1.24 / 1.47
2.04 / 2.58
1.86 / 2.34
1.70 / 2.25
1.61 / 2.08
1.57 / 1.92
1.77 / 2.35
1.61 / 2.08
1.58 / 1.94
1.47 / 1.80
1.53 / 1.87
1.43 / 1.75
1.38 / 1.64
2.34 / 3.03
2.22 / 2.71
2.07 / 2.53
2.00 / 2.36
2.07 / 2.45
1.98 / 2.50
1.82 / 2.27
1.70 / 2.20
1.59 / 2.04
1.54 / 1.88
1.73 / 2.29
1.67 / 2.04
1.55 / 1.90
1.47 / 1.76
1.50 / 1.83
1.45 / 1.72
1.39 / 1.61
2.29 / 2.96
2.17 / 2.66
2.08 / 2.48
1.96 / 2.32
2.25 / 2.75
2.08 / 2.48
1.97 / 2.33
Unit C
2.10 / 2.57
3.13 / 3.82
2.92 / 3.57
2.82 / 3.33
2.04 / 2.58
1.86 / 2.34
1.70 / 2.25
1.61 / 2.08
1.57 / 1.92
2.48 / 3.29
2.25 / 2.92
2.22 / 2.71
2.06 / 2.52
3.06 / 3.74
2.87 / 3.50
2.77 / 3.27
2.34 / 3.03
2.22 / 2.71
2.07 / 2.53
2.00 / 2.36
2.96 / 3.50
1.98 / 2.50
1.82 / 2.27
1.70 / 2.20
1.59 / 2.04
1.54 / 1.88
2.42 / 3.21
2.33 / 2.85
2.17 / 2.66
2.06 / 2.47
3.00 / 3.67
2.91 / 3.44
2.78 / 3.22
2.29 / 2.96
2.17 / 2.66
2.08 / 2.48
1.96 / 2.32
2.25 / 2.75
2.08 / 2.48
1.97 / 2.33
Unit D
4.26 / 5.21
3.13 / 3.82
3.50 / 4.29
4.00 / 4.73
2.04 / 2.58
2.60 / 3.27
3.40 / 4.52
3.86 / 5.01
4.48 / 5.47
2.48 / 3.29
3.22 / 4.17
3.80 / 4.65
4.18 / 5.10
3.06 / 3.74
3.44 / 4.21
3.93 / 4.65
2.34 / 3.03
3.17 / 3.88
3.56 / 4.35
4.05 / 4.80
2.96 / 3.51
1.98 / 2.50
2.54 / 3.19
3.40 / 4.40
3.83 / 4.88
4.38 / 5.36
2.42 / 3.21
3.33 / 4.07
3.73 / 4.54
4.20 / 5.01
3.00 / 3.67
3.49 / 4.12
3.94 / 4.56
2.29 / 2.96
3.11 / 3.79
3.11 / 4.27
3.98 / 4.70
2.25 / 2.75
2.96 / 3.56
3.39 / 4.01
Indoor unitcombination
Cooling / Heating Capacity (kW)
25 + 25 + 25
25 + 25 + 35
25 + 25 + 50
25 + 25 + 60
25 + 25 + 71
25 + 35 + 35
25 + 35 + 50
25 + 35 + 60
25 + 35 + 71
25 + 50 + 50
25 + 50 + 60
25 + 50 + 71
25 + 60 + 60
25 + 60 + 71
35 + 35 + 35
35 + 35 + 50
35 + 35 + 60
35 + 35 + 71
35 + 50 + 50
35 + 50 + 60
35 + 50 + 71
35 + 60 + 60
35 + 60 + 71
50 + 50 + 50
50 + 50 + 60
50 + 50 + 71
4 ROOMS
22 + 22 + 22 + 22
22 + 22 + 22 + 25
22 + 22 + 22 + 35
22 + 22 + 22 + 50
22 + 22 + 22 + 60
22 + 22 + 22 + 71
22 + 22 + 25 + 25
22 + 22 + 25 + 35
22 + 22 + 25 + 50
22 + 22 + 25 + 60
22 + 22 + 25 + 71
22 + 22 + 35 + 35
22 + 22 + 35 + 50
22 + 22 + 35 + 60
Unit A
2.50 / 3.00
2.28 / 2.82
1.98 / 2.75
1.82 / 2.50
1.71 / 2.27
2.07 / 2.64
1.82 / 2.50
1.73 / 2.29
1.62 / 2.10
1.70 / 2.20
1.57 / 2.04
1.54 / 1.88
1.56 / 1.90
1.47 / 1.76
2.65 / 3.33
2.42 / 3.21
2.29 / 2.96
2.16 / 2.73
2.22 / 2.86
2.17 / 2.66
2.06 / 2.46
2.08 / 2.48
1.96 / 2.32
3.06 / 3.66
2.91 / 3.43
2.78 / 3.22
1.95 / 2.50
1.90 / 2.42
1.73 / 2.18
1.52 / 2.09
1.48 / 1.92
1.40 / 1.77
1.83 / 2.34
1.68 / 2.12
1.52 / 2.03
1.45 / 1.88
1.37 / 1.73
1.54 / 1.93
1.45 / 1.88
1.38 / 1.74
Unit B
2.50 / 3.00
2.28 / 2.82
1.98 / 2.75
1.82 / 2.50
1.71/ 2.27
2.89 / 3.68
2.54 / 3.50
2.42 / 3.21
2.27 / 2.94
3.40 / 4.40
3.15 / 4.07
3.08 / 3.77
3.72 / 4.55
3.54 / 4.23
2.65 / 3.33
2.42 / 3.21
2.29 / 2.96
2.16 / 2.73
3.19 / 4.07
3.10 / 3.79
2.95 / 3.53
3.56 / 4.26
3.36 / 3.98
3.07 / 3.67
2.91 / 3.44
2.78 / 3.22
1.95 / 2.50
1.90 / 2.42
1.73 / 2.18
1.52 / 2.09
1.48 / 1.92
1.40 / 1.77
1.84 / 2.34
1.68 / 2.12
1.52 / 2.03
1.45 / 1.88
1.37 / 1.73
1.54 / 1.93
1.45 / 1.88
1.38 / 1.74
Unit C
2.50 / 3.00
3.19 / 3.96
3.94 / 5.50
4.36 / 6.00
4.88 / 6.46
2.89 / 3.68
3.64 / 5.00
4.15 / 5.50
4.61 / 5.96
3.40 / 4.40
3.78 / 4.89
4.38 / 5.35
3.72 / 4.55
4.19 / 5.01
2.65 / 3.33
3.46 / 4.58
3.92 / 5.08
4.38 / 5.54
3.19 / 4.07
3.73 / 4.55
4.19 / 5.01
3.56 / 4.26
3.98 / 4.70
3.07 / 3.67
3.48 / 4.13
3.94 / 4.56
1.95 / 2.50
1.90 / 2.42
1.73 / 2.18
1.52 / 2.09
1.48 / 1.92
1.40 / 1.77
2.09 / 2.66
1.91 / 2.40
1.72 / 2.31
1.65 / 2.13
1.55 / 1.96
2.46 / 3.07
2.31 / 2.98
2.19 / 2.77
Unit D
1.95 / 2.50
2.15 / 2.74
2.76 / 3.46
3.44 / 4.73
4.06 / 5.24
4.50 / 5.69
2.09 / 2.66
2.68 / 3.36
3.44 / 4.63
3.95 / 5.11
4.41 / 5.58
2.46 / 3.07
3.29 / 4.26
3.75 / 4.75
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 43
5 ROOMS22 + 22 + 22 + 22 + 22
22 + 22 + 22 + 22 + 25
22 + 22 + 22 + 22 + 35
22 + 22 + 22 + 22 + 50
22 + 22 + 22 + 22 + 60
22 + 22 + 22 + 22 + 71
22 + 22 + 22 + 25 + 25
22 + 22 + 22 + 25 + 35
22 + 22 + 22 + 25 + 50
22 + 22 + 22 + 25 + 60
22 + 22 + 22 + 25 + 71
22 + 22 + 22 + 35 + 35
22 + 22 + 22 + 35 + 50
22 + 22 + 22 + 35 + 60
22 + 22 + 22 + 35 + 71
22 + 22 + 25 + 25 + 25
22 + 22 + 25 + 25 + 35
22 + 22 + 25 + 25 + 50
22 + 22 + 25 + 25 + 60
22 + 22 + 25 + 25 + 71
22 + 22 + 25 + 35 + 35
22 + 22 + 25 + 35 + 50
22 + 22 + 35 + 35 + 35
22 + 25 + 25 + 25 + 25
22 + 25 + 25 + 25 + 35
22 + 25 + 25 + 25 + 50
22 + 25 + 25 + 25 + 60
22 + 25 + 25 + 25 + 71
22 + 25 + 25 + 35 + 35
22 + 25 + 25 + 35 + 50
22 + 25 + 25 + 35 + 60
22 + 25 + 35 + 35 + 35
25 + 25 + 25 + 25 + 25
25 + 25 + 25 + 25 + 35
25 + 25 + 25 + 25 + 50
25 + 25 + 25 + 25 + 60
25 + 25 + 25 + 25 + 71
25 + 25 + 25 + 35 + 35
25 + 25 + 35 + 35 + 35
25 + 25 + 35 + 35 + 50
Unit A
2.00 / 2.40
1.95 / 2.34
1.79 / 2.15
1.59 / 1.91
1.49 / 1.78
1.38 / 1.66
1.90 / 2.28
1.75 / 2.10
1.56 / 1.87
1.46 / 1.75
1.36 / 1.63
1.62 / 1.94
1.46 / 1.75
1.37 / 1.64
1.28 / 1.53
1.85 / 2.22
1.71 / 2.04
1.53 / 1.83
1.43 / 1.71
1.33 / 1.60
1.58 / 1.90
1.43 / 1.71
1.47 / 1.77
1.80 / 2.16
1.67 / 2.00
1.50 / 1.80
1.40 / 1.68
1.30 / 1.57
1.56 / 1.86
1.40 / 1.68
1.31 / 1.58
1.46 / 1.75
2.00 / 2.40
1.85 / 2.22
1.67 / 2.00
1.56 / 1.88
1.46 / 1.75
1.72 / 2.07
1.61 / 1.94
1.47 / 1.76
Unit B
2.00 / 2.40
1.95 / 2.34
1.79 / 2.15
1.59 / 1.91
1.49 / 1.78
1.38 / 1.66
1.90 / 2.28
1.75 / 2.10
1.56 / 1.87
1.46 / 1.75
1.36 / 1.63
1.62 / 1.94
1.46 / 1.75
1.37 / 1.64
1.28 / 1.53
1.85 / 2.22
1.71 / 2.04
1.53 / 1.83
1.43 / 1.71
1.33 / 1.60
1.58 / 1.90
1.43 / 1.71
1.48 / 1.77
2.05 / 2.46
1.89 / 2.27
1.70 / 2.04
1.59 / 1.91
1.49 / 1.79
1.76 / 2.11
1.59 / 1.91
1.50 / 1.80
1.64 / 1.97
2.00 / 2.40
1.85 / 2.22
1.67 / 2.00
1.56 / 1.88
1.46 / 1.75
1.72 / 2.07
1.61 / 1.94
1.47 / 1.76
Unit C
2.00 / 2.40
1.95 / 2.34
1.79 / 2.15
1.59 / 1.91
1.49 / 1.78
1.38 / 1.66
1.90 / 2.28
1.75 / 2.10
1.56 / 1.87
1.46 / 1.75
1.36 / 1.63
1.62 / 1.94
1.46 / 1.75
1.37 / 1.64
1.28 / 1.53
2.10 / 2.52
1.94 / 2.33
1.74 / 2.08
1.62 / 1.95
1.52 / 1.82
1.80 / 2.16
1.62 / 1.95
2.35 / 2.82
2.05 / 2.46
1.89 / 2.27
1.70 / 2.04
1.59 / 1.91
1.49 / 1.79
1.76 / 2.11
1.59 / 1.91
1.50 / 1.80
2.30 / 2.76
2.00 / 2.40
1.85 / 2.22
1.67 / 2.00
1.56 / 1.88
1.46 / 1.75
1.72 / 2.07
2.26 / 2.71
2.06 / 2.47
Unit D
2.00 / 2.40
1.95 / 2.34
1.79 / 2.15
1.59 / 1.91
1.49 / 1.78
1.38 / 1.66
2.15 / 2.58
1.97 / 2.38
1.77 / 2.13
1.66 / 1.99
1.54 / 1.85
2.57 / 3.09
2.32 / 2.78
2.17 / 2.61
2.03 / 2.44
2.10 / 2.52
1.94 / 2.33
1.74 / 2.08
1.62 / 1.95
1.52 / 1.82
2.52 / 3.02
2.27 / 2.73
2.35 / 2.82
2.05 / 2.46
1.89 / 2.27
1.70 / 2.04
1.59 / 1.91
1.49 / 1.79
2.46 / 2.96
2.23 / 2.68
2.10 / 2.51
2.30 / 2.76
2.00 / 2.40
1.85 / 2.22
1.67 / 2.00
1.56 / 1.88
1.46 / 1.75
2.42 / 2.90
2.26 / 2.71
2.06 / 2.47
Unit E
2.00 / 2.40
2.20 / 2.65
2.84 / 3.40
3.64 / 4.36
4.04 / 4.88
4.48 / 5.36
2.15 / 2.58
2.78 / 3.32
3.55 / 4.26
3.96 / 4.76
4.38 / 5.26
2.57 / 3.09
3.30 / 3.97
3.72 / 4.47
4.13 / 4.95
2.10 / 2.52
2.70 / 3.26
3.46 / 4.18
3.90 / 4.68
4.30 / 5.16
2.52 / 3.02
3.25 / 3.90
2.35 / 2.82
2.05 / 2.46
2.66 / 3.19
3.40 / 4.08
3.83 / 4.59
4.23 / 5.07
2.46 / 2.96
3.19 / 3.82
3.59 / 4.31
2.30 / 2.76
2.00 / 2.40
2.60 / 3.12
3.32 / 4.00
3.76 / 4.50
4.16 / 4.98
2.42 / 2.90
2.26 / 2.71
2.94 / 3.54
Unit F Unit G Unit H
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 44
1 ROOM22
25
35
50
60
71
2 ROOMS22 + 22
22 + 25
22 + 35
22 + 50
22 + 60
22 + 71
25 + 25
25 + 35
25 + 50
25 + 60
25 + 71
35 + 35
35 + 50
35 + 60
35 + 71
50 + 50
50 + 60
50 + 71
60 + 60
60 + 71
71 + 71
3 ROOMS22 + 22 + 22
22 + 22 + 25
22 + 22 + 35
22 + 22 + 50
22 + 22 + 60
22 + 22 + 71
22 + 25 + 25
22 + 25 + 35
Unit A
2.20 / 3.30
2.50 / 3.60
3.50 / 4.00
5.00 / 7.20
6.00 / 7.90
7.10 / 8.60
2.20 / 2.50
2.20 / 2.53
2.20 / 2.51
2.20 / 2.51
2.20 / 2.52
2.20 / 2.51
2.50 / 2.85
2.50 / 2.88
2.50 / 2.87
2.50 / 2.85
2.50 / 2.86
3.50 / 4.00
3.50 / 3.99
3.50 / 4.02
3.50 / 4.00
5.00 / 5.70
5.00 / 5.73
5.00 / 5.70
6.00 / 6.85
6.00 / 6.87
7.00 / 8.00
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.50
2.20 / 2.52
Unit B
2.20 / 2.50
2.50 / 2.87
3.50 / 3.99
5.00 / 5.69
6.00 / 6.88
7.10 / 8.09
2.50 / 2.85
3.50 / 4.02
5.00 / 5.73
6.00 / 6.85
7.10 / 8.14
3.50 / 4.00
5.00 / 5.71
6.00 / 6.88
7.10 / 8.10
5.00 / 5.70
6.00 / 6.87
7.10 / 8.10
6.00 / 6.85
7.10 / 8.13
7.00 / 8.00
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.50 / 2.85
2.50 / 2.87
Unit C
2.20 / 2.50
2.50 / 2.86
3.50 / 3.98
5.00 / 5.69
6.00 / 6.86
7.10 / 8.09
2.50 / 2.85
3.50 / 4.01
Unit D
Indoor unitcombination
Cooling / Heating Capacity (kW)
MXZ-8A140VA1Outdoor Unit Up to 8 Indoor Units
22 + 25 + 50
22 + 25 + 60
22 + 25 + 71
22 + 35 + 35
22 + 35 + 50
22 + 35 + 60
22 + 35 + 71
22 + 50 + 50
22 + 50 + 60
22 + 50 + 71
22 + 60 + 60
22 + 60 + 71
22 + 71 + 71
25 + 25 + 25
25 + 25 + 35
25 + 25 + 50
25 + 25 + 60
25 + 25 + 71
25 + 35 + 35
25 + 35 + 50
25 + 35 + 60
25 + 35 + 71
25 + 50 + 50
25 + 50 + 60
25 + 50 + 71
25 + 60 + 60
25 + 60 + 71
25 + 71 + 71
35 + 35 + 35
35 + 35 + 50
35 + 35 + 60
35 + 35 + 71
35 + 50 + 50
35 + 50 + 60
35 + 50 + 71
35 + 60 + 60
35 + 60 + 71
35 + 71 + 71
50 + 50 + 50
50 + 50 + 60
50 + 50 + 71
50 + 60 + 60
50 + 60 + 71
60 + 60 + 60
Unit A
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.20 / 2.51
2.20 / 2.51
2.20 / 2.52
2.20 / 2.51
2.20 / 2.50
2.20 / 2.52
2.15 / 2.46
2.17 / 2.48
2.01 / 2.30
1.88 / 2.14
2.50 / 2.86
2.50 / 2.85
2.50 / 2.85
2.50 / 2.86
2.50 / 2.85
2.50 / 2.86
2.50 / 2.86
2.50 / 2.85
2.50 / 2.86
2.50 / 2.86
2.50 / 2.85
2.40 / 2.74
2.41 / 2.76
2.24 / 2.56
2.10 / 2.40
3.50 / 4.00
3.50 / 4.00
3.50 / 4.01
3.48 / 3.97
3.50 / 3.99
3.38 / 3.86
3.14 / 3.59
3.16 / 3.61
2.95 / 3.37
2.77 / 3.16
4.67 / 5.33
4.38 / 5.00
4.09 / 4.68
4.12 / 4.70
3.87 / 4.42
4.67 / 5.33
Unit B
2.50 / 2.86
2.50 / 2.85
2.50 / 2.86
3.50 / 3.99
3.50 / 3.99
3.50 / 4.01
3.50 / 3.99
5.00 / 5.70
5.00 / 5.72
4.90 / 5.59
5.92 / 6.76
5.49 / 6.27
6.06 / 6.93
2.50 / 2.86
2.50 / 2.85
2.50 / 2.85
2.50 / 2.86
2.50 / 2.85
3.50 / 4.02
3.50 / 4.01
3.50 / 4.00
3.50 / 4.01
5.00 / 5.72
5.00 / 5.70
4.79 / 5.48
5.79 / 6.62
5.38 / 6.15
5.95 / 6.80
3.50 / 4.00
3.50 / 4.00
3.50 / 4.01
3.48 / 3.97
5.00 / 5.70
4.83 / 5.52
4.49 / 5.13
5.42 / 6.19
5.06 / 5.78
5.62 / 6.42
4.67 / 5.33
4.38 / 5.00
4.09 / 4.68
4.94 / 5.65
4.64 / 5.30
4.67 / 5.33
Unit C
5.00 / 5.72
6.00 / 6.84
7.10 / 8.12
3.50 / 3.99
5.00 / 5.70
6.00 / 6.87
7.10 / 8.10
5.00 / 5.70
6.00 / 6.86
6.95 / 7.94
5.92 / 6.76
6.50 / 7.42
6.06 / 6.93
2.50 / 2.86
3.50 / 3.99
5.00 / 5.70
6.00 / 6.87
7.10 / 8.10
3.50 / 4.02
5.00 / 5.73
6.00 / 6.85
7.10 / 8.13
5.00 / 5.72
6.00 / 6.84
6.81 / 7.78
5.79 / 6.62
6.37 / 7.28
5.95 / 6.80
3.50 / 4.00
5.00 / 5.70
6.00 / 6.88
7.05 / 8.06
5.00 / 5.70
5.79 / 6.62
6.37 / 7.28
5.42 / 6.19
5.99 / 6.84
5.62 / 6.42
4.67 / 5.33
5.25 / 6.00
5.81 / 6.64
4.94 / 5.65
5.49 / 6.28
4.67 / 5.33
Unit D
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 45
4 ROOMS22 + 22 + 22 + 22
22 + 22 + 22 + 25
22 + 22 + 22 + 35
22 + 22 + 22 + 50
22 + 22 + 22 + 60
22 + 22 + 22 + 71
22 + 22 + 25 + 25
22 + 22 + 25 + 35
22 + 22 + 25 + 50
22 + 22 + 25 + 60
22 + 22 + 25 + 71
22 + 22 + 35 + 35
22 + 22 + 35 + 50
22 + 22 + 35 + 60
22 + 22 + 35 + 71
22 + 22 + 50 + 50
22 + 22 + 50 + 60
22 + 22 + 50 + 71
22 + 22 + 60 + 60
22 + 22 + 60 + 71
22 + 25 + 25 + 25
22 + 25 + 25 + 35
22 + 25 + 25 + 50
22 + 25 + 25 + 60
22 + 25 + 25 + 71
22 + 25 + 35 + 35
22 + 25 + 35 + 50
22 + 25 + 35 + 60
22 + 25 + 35 + 71
22 + 25 + 50 + 50
22 + 25 + 50 + 60
22 + 25 + 50 + 71
22 + 25 + 60 + 60
22 + 25 + 60 + 71
22 + 35 + 35 + 35
22 + 35 + 35 + 50
Unit A
2.20 / 2.52
2.20 / 2.51
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.51
2.20 / 2.51
2.20 / 2.51
2.20 / 2.51
2.20 / 2.52
2.05 / 2.35
2.14 / 2.44
2.00 / 2.29
1.87 / 2.13
1.88 / 2.15
1.76 / 2.01
2.20 / 2.52
2.20 / 2.51
2.20 / 2.51
2.20 / 2.52
2.15 / 2.46
2.20 / 2.52
2.20 / 2.52
2.17 / 2.48
2.01 / 2.30
2.10 / 2.39
1.96 / 2.24
1.83 / 2.10
1.84 / 2.10
1.73 / 1.98
2.20 / 2.50
2.17 / 2.48
Unit B
2.20 / 2.52
2.20 / 2.51
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.51
2.20 / 2.51
2.20 / 2.51
2.20 / 2.51
2.20 / 2.52
2.05 / 2.35
2.14 / 2.44
2.00 / 2.29
1.87 / 2.13
1.88 / 2.15
1.76 / 2.01
2.50 / 2.86
2.50 / 2.85
2.50 / 2.85
2.50 / 2.86
2.45 / 2.80
2.50 / 2.86
2.50 / 2.86
2.46 / 2.82
2.29 / 2.61
2.38 / 2.72
2.23 / 2.55
2.08 / 2.38
2.10 / 2.40
1.97 / 2.25
3.50 / 4.00
3.45 / 3.94
Unit C
2.20 / 2.52
2.20 / 2.51
2.20 / 2.50
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.50 / 2.85
2.50 / 2.86
2.50 / 2.86
2.50 / 2.85
2.50 / 2.86
3.50 / 3.99
3.50 / 3.99
3.50 / 4.00
3.27 / 3.73
4.86 / 5.56
4.55 / 5.19
4.24 / 4.85
5.12 / 5.85
4.80 / 5.49
2.50 / 2.86
2.50 / 2.85
2.50 / 2.85
2.50 / 2.86
2.45 / 2.80
3.50 / 4.01
3.50 / 4.00
3.45 / 3.94
3.20 / 3.66
4.76 / 5.44
4.46 / 5.10
4.17 / 4.76
5.03 / 5.75
4.72 / 5.39
3.50 / 4.00
3.45 / 3.94
Unit D
2.20 / 2.52
2.50 / 2.86
3.50 / 3.99
5.00 / 5.73
6.00 / 6.86
7.10 / 8.14
2.50 / 2.85
3.50 / 4.00
5.00 / 5.71
6.00 / 6.83
7.10 / 8.11
3.50 / 3.99
5.00 / 5.69
6.00 / 6.86
6.63 / 7.57
4.86 / 5.56
5.45 / 6.23
6.02 / 6.88
5.12 / 5.85
5.68 / 6.49
2.50 / 2.86
3.50 / 3.99
5.00 / 5.69
6.00 / 6.86
6.95 / 7.94
3.50 / 4.01
5.00 / 5.72
5.92 / 6.76
6.50 / 7.42
4.76 / 5.44
5.35 / 6.11
5.92 / 6.76
5.03 / 5.75
5.58 / 6.38
3.50 / 4.00
4.93 / 5.63
Indoor unitcombination
Cooling / Heating Capacity (kW)
22 + 35 + 35 + 60
22 + 35 + 35 + 71
22 + 35 + 50 + 50
22 + 35 + 50 + 60
22 + 35 + 50 + 71
22 + 35 + 60 + 60
22 + 50 + 50 + 50
22 + 50 + 50 + 60
25 + 25 + 25 + 25
25 + 25 + 25 + 35
25 + 25 + 25 + 50
25 + 25 + 25 + 60
25 + 25 + 25 + 71
25 + 25 + 35 + 35
25 + 25 + 35 + 50
25 + 25 + 35 + 60
25 + 25 + 35 + 71
25 + 25 + 50 + 50
25 + 25 + 50 + 60
25 + 25 + 50 + 71
25 + 25 + 60 + 60
25 + 25 + 60 + 71
25 + 35 + 35 + 35
25 + 35 + 35 + 50
25 + 35 + 35 + 60
25 + 35 + 35 + 71
25 + 35 + 50 + 50
25 + 35 + 50 + 60
25 + 35 + 50 + 71
25 + 35 + 60 + 60
25 + 50 + 50 + 50
25 + 50 + 50 + 60
35 + 35 + 35 + 35
35 + 35 + 35 + 50
35 + 35 + 35 + 60
35 + 35 + 35 + 71
35 + 35 + 50 + 50
35 + 35 + 50 + 60
35 + 50 + 50 + 50
Unit A
2.03 / 2.32
1.89 / 2.16
1.96 / 2.23
1.84 / 2.11
1.73 / 1.98
1.73 / 1.99
1.79 / 2.05
1.69 / 1.93
2.50 / 2.85
2.50 / 2.86
2.50 / 2.86
2.50 / 2.85
2.40 / 2.74
2.50 / 2.85
2.50 / 2.85
2.41 / 2.76
2.24 / 2.56
2.33 / 2.67
2.19 / 2.50
2.05 / 2.34
2.06 / 2.35
1.93 / 2.21
2.50 / 2.87
2.41 / 2.76
2.26 / 2.58
2.11 / 2.41
2.18 / 2.50
2.06 / 2.35
1.93 / 2.21
1.94 / 2.22
2.00 / 2.29
1.89 / 2.16
3.50 / 4.00
3.16 / 3.61
2.97 / 3.39
2.78 / 3.18
2.88 / 3.29
2.72 / 3.11
2.65 / 3.03
Unit B
3.22 / 3.68
3.01 / 3.44
3.12 / 3.57
2.93 / 3.35
2.75 / 3.15
2.77 / 3.16
4.07 / 4.65
3.85 / 4.40
2.50 / 2.85
2.50 / 2.86
2.50 / 2.86
2.50 / 2.85
2.40 / 2.74
2.50 / 2.85
2.50 / 2.85
2.41 / 2.76
2.24 / 2.56
2.33 / 2.67
2.19 / 2.50
2.05 / 2.34
2.06 / 2.35
1.93 / 2.21
3.50 / 4.01
3.38 / 3.86
3.16 / 3.61
2.95 / 3.37
3.06 / 3.50
2.88 / 3.29
2.71 / 3.09
2.72 / 3.11
4.00 / 4.57
3.78 / 4.32
3.50 / 4.00
3.16 / 3.61
2.97 / 3.39
2.78 / 3.18
2.88 / 3.29
2.72 / 3.11
3.78 / 4.32
Unit C
3.22 / 3.68
3.01 / 3.44
4.46 / 5.10
4.19 / 4.79
3.93 / 4.49
4.75 / 5.42
4.07 / 4.65
3.85 / 4.40
2.50 / 2.85
2.50 / 2.86
2.50 / 2.86
2.50 / 2.85
2.40 / 2.74
3.50 / 4.00
3.50 / 3.99
3.38 / 3.86
3.14 / 3.59
4.67 / 5.33
4.38 / 5.00
4.09 / 4.68
4.94 / 5.65
4.64 / 5.30
3.50 / 4.01
3.38 / 3.86
3.16 / 3.61
2.95 / 3.37
4.38 / 5.00
4.12 / 4.71
3.87 / 4.42
4.67 / 5.33
4.00 / 4.57
3.78 / 4.32
3.50 / 4.00
3.16 / 3.61
2.97 / 3.39
2.78 / 3.18
4.12 / 4.71
3.89 / 4.44
3.78 / 4.32
Unit D
5.53 / 6.32
6.09 / 6.96
4.46 / 5.10
5.03 / 5.75
5.58 / 6.38
4.75 / 5.42
4.07 / 4.65
4.61 / 5.27
2.50 / 2.85
3.50 / 4.01
5.00 / 5.72
6.00 / 6.84
6.80 / 7.78
3.50 / 4.00
5.00 / 5.70
5.79 / 6.62
6.37 / 7.28
4.67 / 5.33
5.24 / 6.00
5.81 / 6.64
4.94 / 5.65
5.49 / 6.28
3.50 / 4.01
4.83 / 5.52
5.42 / 6.19
5.99 / 6.84
4.38 / 5.00
4.94 / 5.65
5.49 / 6.28
4.67 / 5.33
4.00 / 4.57
4.54 / 5.19
3.50 / 4.00
4.52 / 5.16
5.09 / 5.82
5.65 / 6.45
4.12 / 4.71
4.67 / 5.33
3.78 / 4.32
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 46
5 ROOMS22 + 22 + 22 + 22 + 22
22 + 22 + 22 + 22 + 25
22 + 22 + 22 + 22 + 35
22 + 22 + 22 + 22 + 50
22 + 22 + 22 + 22 + 60
22 + 22 + 22 + 22 + 71
22 + 22 + 22 + 25 + 25
22 + 22 + 22 + 25 + 35
22 + 22 + 22 + 25 + 50
22 + 22 + 22 + 25 + 60
22 + 22 + 22 + 25 + 71
22 + 22 + 22 + 35 + 35
22 + 22 + 22 + 35 + 50
22 + 22 + 22 + 35 + 60
22 + 22 + 22 + 35 + 71
22 + 22 + 22 + 50 + 50
22 + 22 + 22 + 50 + 60
22 + 22 + 25 + 25 + 25
22 + 22 + 25 + 25 + 35
22 + 22 + 25 + 25 + 50
22 + 22 + 25 + 25 + 60
22 + 22 + 25 + 25 + 71
22 + 22 + 25 + 35 + 35
22 + 22 + 25 + 35 + 50
22 + 22 + 25 + 35 + 60
22 + 22 + 25 + 35 + 71
22 + 22 + 25 + 50 + 50
22 + 22 + 25 + 50 + 60
22 + 22 + 35 + 35 + 35
22 + 22 + 35 + 35 + 50
22 + 22 + 35 + 35 + 60
22 + 22 + 35 + 35 + 71
22 + 22 + 35 + 50 + 50
22 + 25 + 25 + 25 + 25
22 + 25 + 25 + 25 + 35
22 + 25 + 25 + 25 + 50
22 + 25 + 25 + 25 + 60
22 + 25 + 25 + 25 + 71
22 + 25 + 25 + 35 + 35
22 + 25 + 25 + 35 + 50
22 + 25 + 25 + 35 + 60
22 + 25 + 25 + 35 + 71
22 + 25 + 25 + 50 + 50
22 + 25 + 25 + 50 + 60
22 + 25 + 35 + 35 + 35
22 + 25 + 35 + 35 + 50
22 + 25 + 35 + 35 + 60
22 + 25 + 35 + 50 + 50
22 + 35 + 35 + 35 + 35
22 + 35 + 35 + 35 + 50
Unit A
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.20 / 2.52
2.08 / 2.38
1.94 / 2.21
2.20 / 2.52
2.20 / 2.51
2.18 / 2.50
2.04 / 2.33
1.90 / 2.17
2.20 / 2.51
2.04 / 2.33
1.91 / 2.19
1.79 / 2.05
1.86 / 2.12
1.75 / 2.00
2.20 / 2.51
2.20 / 2.51
2.14 / 2.44
2.00 / 2.29
1.87 / 2.13
2.20 / 2.52
2.00 / 2.29
1.88 / 2.15
1.76 / 2.01
1.82 / 2.08
1.72 / 1.97
2.06 / 2.36
1.88 / 2.15
1.77 / 2.02
1.66 / 1.90
1.72 / 1.97
2.20 / 2.50
2.20 / 2.52
2.10 / 2.39
1.96 / 2.24
1.83 / 2.10
2.17 / 2.48
1.96 / 2.24
1.84 / 2.11
1.73 / 1.98
1.79 / 2.04
1.69 / 1.93
2.03 / 2.32
1.84 / 2.11
1.74 / 1.99
1.69 / 1.92
1.90 / 2.16
1.74 / 1.99
Unit B
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.20 / 2.52
2.08 / 2.38
1.94 / 2.21
2.20 / 2.52
2.20 / 2.51
2.18 / 2.50
2.04 / 2.33
1.90 / 2.17
2.20 / 2.51
2.04 / 2.33
1.91 / 2.19
1.79 / 2.05
1.86 / 2.12
1.75 / 2.00
2.20 / 2.51
2.20 / 2.51
2.14 / 2.44
2.00 / 2.29
1.87 / 2.13
2.20 / 2.52
2.00 / 2.29
1.88 / 2.15
1.76 / 2.01
1.82 / 2.08
1.72 / 1.97
2.06 / 2.36
1.88 / 2.15
1.77 / 2.02
1.66 / 1.90
1.72 / 1.97
2.50 / 2.85
2.50 / 2.86
2.38 / 2.72
2.23 / 2.55
2.08 / 2.38
2.46 / 2.82
2.23 / 2.55
2.10 / 2.40
1.97 / 2.25
2.03 / 2.33
1.92 / 2.20
2.30 / 2.63
2.10 / 2.40
1.98 / 2.26
1.92 / 2.20
3.02 / 3.46
2.77 / 3.16
Unit C
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.20 / 2.52
2.08 / 2.38
1.94 / 2.21
2.20 / 2.52
2.20 / 2.51
2.18 / 2.50
2.04 / 2.33
1.90 / 2.17
2.20 / 2.51
2.04 / 2.33
1.91 / 2.19
1.79 / 2.05
1.86 / 2.12
1.75 / 2.00
2.50 / 2.86
2.50 / 2.85
2.43 / 2.78
2.27 / 2.60
2.12 / 2.42
2.50 / 2.86
2.27 / 2.60
2.13 / 2.44
2.00 / 2.29
2.07 / 2.37
1.96 / 2.23
3.29 / 3.76
2.99 / 3.41
2.82 / 3.22
2.65 / 3.03
2.74 / 3.12
2.50 / 2.85
2.50 / 2.86
2.38 / 2.72
2.23 / 2.55
2.08 / 2.38
2.46 / 2.82
2.23 / 2.55
2.10 / 2.40
1.97 / 2.25
2.03 / 2.33
1.92 / 2.20
3.22 / 3.68
2.93 / 3.35
2.77 / 3.16
2.69 / 3.08
3.02 / 3.46
2.77 / 3.16
Unit D
2.20 / 2.52
2.20 / 2.51
2.20 / 2.52
2.20 / 2.52
2.08 / 2.38
1.94 / 2.21
2.50 / 2.87
2.50 / 2.86
2.48 / 2.84
2.32 / 2.65
2.16 / 2.47
3.50 / 3.98
3.25 / 3.71
3.04 / 3.48
2.85 / 3.26
4.21 / 4.82
3.98 / 4.55
2.50 / 2.86
2.50 / 2.85
2.43 / 2.78
2.27 / 2.60
2.12 / 2.42
3.50 / 4.00
3.18 / 3.64
2.99 / 3.41
2.80 / 3.20
4.14 / 4.73
3.91 / 4.47
3.29 / 3.76
2.99 / 3.41
2.82 / 3.22
2.65 / 3.03
3.91 / 4.47
2.50 / 2.85
2.50 / 2.86
2.38 / 2.72
2.23 / 2.55
2.08 / 2.38
3.45 / 3.94
3.12 / 3.57
2.93 / 3.35
2.75 / 3.15
4.07 / 4.65
3.85 / 4.40
3.22 / 3.68
2.93 / 3.35
2.77 / 3.16
3.85 / 4.40
3.02 / 3.46
2.77 / 3.16
Unit E
2.20 / 2.52
2.50 / 2.85
3.50 / 4.01
5.00 / 5.72
5.68 / 6.48
6.24 / 7.14
2.50 / 2.87
3.50 / 4.00
4.96 / 5.66
5.56 / 6.36
6.14 / 7.01
3.50 / 3.98
4.63 / 5.30
5.22 / 5.95
5.78 / 6.59
4.21 / 4.82
4.77 / 5.45
2.50 / 2.86
3.50 / 3.98
4.86 / 5.56
5.45 / 6.22
6.02 / 6.88
3.50 / 4.00
4.55 / 5.18
5.12 / 5.85
5.68 / 6.49
4.14 / 4.73
4.69 / 5.36
3.29 / 3.76
4.26 / 4.88
4.82 / 5.52
5.37 / 6.14
3.91 / 4.47
2.50 / 2.85
3.50 / 4.00
4.76 / 5.44
5.35 / 6.11
5.92 / 6.76
3.45 / 3.94
4.46 / 5.09
5.03 / 5.74
5.58 / 6.37
4.07 / 4.65
4.62 / 5.27
3.22 / 3.68
4.19 / 4.79
4.74 / 5.42
3.85 / 4.40
3.02 / 3.46
3.95 / 4.52
Unit F Unit G Unit H
Indoor unitcombination Cooling / Heating Capacity (kW)
Page 47
25 + 25 + 25 + 25 + 25
25 + 25 + 25 + 25 + 35
25 + 25 + 25 + 25 + 50
25 + 25 + 25 + 25 + 60
25 + 25 + 25 + 25 + 71
25 + 25 + 25 + 35 + 35
25 + 25 + 25 + 35 + 50
25 + 25 + 25 + 35 + 60
25 + 25 + 25 + 35 + 71
25 + 25 + 25 + 50 + 50
25 + 25 + 25 + 50 + 60
25 + 25 + 35 + 35 + 35
25 + 25 + 35 + 35 + 50
25 + 25 + 35 + 35 + 60
25 + 25 + 35 + 50 + 50
25 + 35 + 35 + 35 + 35
25 + 35 + 35 + 35 + 50
35 + 35 + 35 + 35 + 35
6 ROOMS22 + 22 + 22 + 22 + 22 + 22
22 + 22 + 22 + 22 + 22 + 25
22 + 22 + 22 + 22 + 22 + 35
22 + 22 + 22 + 22 + 22 + 50
22 + 22 + 22 + 22 + 22 + 60
22 + 22 + 22 + 22 + 22 + 71
22 + 22 + 22 + 22 + 25 + 25
22 + 22 + 22 + 22 + 25 + 35
22 + 22 + 22 + 22 + 25 + 50
22 + 22 + 22 + 22 + 25 + 60
22 + 22 + 22 + 22 + 25 + 71
22 + 22 + 22 + 22 + 35 + 35
22 + 22 + 22 + 22 + 35 + 50
22 + 22 + 22 + 22 + 35 + 60
22 + 22 + 22 + 25 + 25 + 25
22 + 22 + 22 + 25 + 25 + 35
22 + 22 + 22 + 25 + 25 + 50
22 + 22 + 22 + 25 + 25 + 60
22 + 22 + 22 + 25 + 35 + 35
22 + 22 + 22 + 25 + 35 + 50
22 + 22 + 22 + 35 + 35 + 35
22 + 22 + 25 + 25 + 25 + 25
22 + 22 + 25 + 25 + 25 + 35
22 + 22 + 25 + 25 + 25 + 50
22 + 22 + 25 + 25 + 25 + 60
22 + 22 + 25 + 25 + 35 + 35
22 + 22 + 25 + 25 + 35 + 50
22 + 22 + 25 + 35 + 35 + 35
22 + 22 + 35 + 35 + 35 + 35
22 + 25 + 25 + 25 + 25 + 25
Unit A
2.50 / 2.86
2.50 / 2.85
2.33 / 2.67
2.19 / 2.50
2.05 / 2.34
2.41 / 2.76
2.19 / 2.50
2.06 / 2.35
1.93 / 2.21
2.00 / 2.29
1.89 / 2.16
2.26 / 2.58
2.06 / 2.35
1.94 / 2.22
1.89 / 2.16
2.12 / 2.42
1.94 / 2.22
2.80 / 3.20
2.20 / 2.51
2.20 / 2.51
2.12 / 2.43
1.92 / 2.20
1.81 / 2.07
1.70 / 1.94
2.20 / 2.52
2.08 / 2.38
1.89 / 2.16
1.78 / 2.03
1.67 / 1.91
1.95 / 2.23
1.78 / 2.03
1.68 / 1.92
2.18 / 2.50
2.04 / 2.33
1.86 / 2.12
1.75 / 2.00
1.91 / 2.19
1.75 / 2.00
1.80 / 2.06
2.14 / 2.44
2.00 / 2.28
1.82 / 2.08
1.72 / 1.97
1.88 / 2.15
1.72 / 1.97
1.70 / 2.02
1.67 / 1.91
2.10 / 2.39
Unit B
2.50 / 2.86
2.50 / 2.85
2.33 / 2.67
2.19 / 2.50
2.05 / 2.34
2.41 / 2.76
2.19 / 2.50
2.06 / 2.35
1.93 / 2.21
2.00 / 2.29
1.89 / 2.16
2.26 / 2.58
2.06 / 2.35
1.94 / 2.22
1.89 / 2.16
2.97 / 3.39
2.72 / 3.11
2.80 / 3.20
2.20 / 2.51
2.20 / 2.51
2.12 / 2.43
1.92 / 2.20
1.81 / 2.07
1.70 / 1.94
2.20 / 2.52
2.08 / 2.38
1.89 / 2.16
1.78 / 2.03
1.67 / 1.91
1.95 / 2.23
1.78 / 2.03
1.68 / 1.92
2.18 / 2.50
2.04 / 2.33
1.86 / 2.12
1.75 / 2.00
1.91 / 2.19
1.75 / 2.00
1.80 / 2.06
2.14 / 2.44
2.00 / 2.28
1.82 / 2.08
1.72 / 1.97
1.88 / 2.15
1.72 / 1.97
1.70 / 2.02
1.67 / 1.91
2.38 / 2.72
Unit C
2.50 / 2.86
2.50 / 2.85
2.33 / 2.67
2.19 / 2.50
2.05 / 2.34
2.41 / 2.76
2.19 / 2.50
2.06 / 2.35
1.93 / 2.21
2.00 / 2.29
1.89 / 2.16
3.16 / 3.61
2.88 / 3.29
2.72 / 3.11
2.65 / 3.03
2.97 / 3.39
2.72 / 3.11
2.80 / 3.20
2.20 / 2.51
2.20 / 2.51
2.12 / 2.43
1.92 / 2.20
1.81 / 2.07
1.70 / 1.94
2.20 / 2.52
2.08 / 2.38
1.89 / 2.16
1.78 / 2.03
1.67 / 1.91
1.95 / 2.23
1.78 / 2.03
1.68 / 1.92
2.18 / 2.50
2.04 / 2.33
1.86 / 2.12
1.75 / 2.00
1.91 / 2.19
1.75 / 2.00
1.80 / 2.06
2.43 / 2.78
2.27 / 2.60
2.07 / 2.37
1.96 / 2.23
2.13 / 2.44
1.96 / 2.23
2.00 / 2.30
2.66 / 3.04
2.38 / 2.72
Unit D
2.50 / 2.86
2.50 / 2.85
2.33 / 2.67
2.19 / 2.50
2.05 / 2.34
3.38 / 3.86
3.06 / 3.50
2.88 / 3.29
2.71 / 3.09
4.00 / 4.56
3.78 / 4.32
3.16 / 3.61
2.88 / 3.29
2.72 / 3.11
3.78 / 4.32
2.97 / 3.39
2.72 / 3.11
2.80 / 3.20
2.20 / 2.51
2.20 / 2.51
2.12 / 2.43
1.92 / 2.20
1.81 / 2.07
1.70 / 1.94
2.20 / 2.52
2.08 / 2.38
1.89 / 2.16
1.78 / 2.03
1.67 / 1.91
1.95 / 2.23
1.78 / 2.03
1.68 / 1.92
2.48 / 2.83
2.32 / 2.65
2.10 / 2.41
1.99 / 2.27
2.17 / 2.47
1.99 / 2.27
2.86 / 3.27
2.43 / 2.78
2.27 / 2.60
2.07 / 2.37
1.96 / 2.23
2.13 / 2.44
1.96 / 2.23
2.82 / 3.22
2.66 / 3.04
2.38 / 2.72
Unit E
2.50 / 2.86
3.50 / 3.99
4.67 / 5.32
5.24 / 6.00
5.80 / 6.64
3.38 / 3.86
4.37 / 5.00
4.94 / 5.65
5.49 / 6.28
4.00 / 4.56
4.54 / 5.19
3.16 / 3.61
4.12 / 4.71
4.67 / 5.33
3.78 / 4.32
2.97 / 3.39
3.89 / 4.44
2.80 / 3.20
2.20 / 2.51
2.20 / 2.51
2.12 / 2.43
1.92 / 2.20
1.81 / 2.07
1.70 / 1.94
2.50 / 2.86
2.36 / 2.70
2.15 / 2.45
2.02 / 2.31
1.90 / 2.17
3.10 / 3.54
2.83 / 3.24
2.68 / 3.06
2.48 / 2.83
2.32 / 2.65
2.10 / 2.41
1.99 / 2.27
3.04 / 3.48
2.78 / 3.18
2.86 / 3.27
2.43 / 2.78
2.27 / 2.60
2.07 / 2.37
1.96 / 2.23
2.99 / 3.41
2.74 / 3.13
2.82 / 3.22
2.66 / 3.04
2.38 / 2.72
Unit F
2.20 / 2.51
2.50 / 2.85
3.38 / 3.85
4.38 / 5.00
4.94 / 5.65
5.49 / 6.28
2.50 / 2.86
3.31 / 3.78
4.29 / 4.91
4.86 / 5.55
5.40 / 6.17
3.10 / 3.54
4.05 / 4.62
4.59 / 5.25
2.48 / 2.83
3.24 / 3.71
4.22 / 4.82
4.77 / 5.45
3.04 / 3.48
3.98 / 4.55
2.86 / 3.27
2.43 / 2.78
3.18 / 3.64
4.14 / 4.73
4.68 / 5.36
2.99 / 3.41
3.90 / 4.47
2.82 / 3.22
2.66 / 3.04
2.38 / 2.72
Unit G Unit H
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 48
22 + 25 + 25 + 25 + 25 + 35
22 + 25 + 25 + 25 + 25 + 50
22 + 25 + 25 + 25 + 25 + 60
22 + 25 + 25 + 25 + 35 + 35
22 + 25 + 25 + 25 + 35 + 50
22 + 25 + 25 + 35 + 35 + 35
25 + 25 + 25 + 25 + 25 + 25
25 + 25 + 25 + 25 + 25 + 35
25 + 25 + 25 + 25 + 25 + 50
25 + 25 + 25 + 25 + 25 + 60
25 + 25 + 25 + 25 + 35 + 35
25 + 25 + 25 + 25 + 35 + 50
25 + 25 + 25 + 35 + 35 + 35
7 ROOMS22 + 22 + 22 + 22 + 22 + 22 + 22
22 + 22 + 22 + 22 + 22 + 22 + 25
22 + 22 + 22 + 22 + 22 + 22 + 35
22 + 22 + 22 + 22 + 22 + 22 + 50
22 + 22 + 22 + 22 + 22 + 25 + 25
22 + 22 + 22 + 22 + 22 + 25 + 35
22 + 22 + 22 + 22 + 22 + 25 + 50
22 + 22 + 22 + 22 + 22 + 35 + 35
22 + 22 + 22 + 22 + 25 + 25 + 25
22 + 22 + 22 + 22 + 25 + 25 + 35
22 + 22 + 22 + 22 + 25 + 35 + 35
22 + 22 + 22 + 25 + 25 + 25 + 25
22 + 22 + 22 + 25 + 25 + 25 + 35
22 + 22 + 25 + 25 + 25 + 25 + 25
22 + 22 + 25 + 25 + 25 + 25 + 35
22 + 25 + 25 + 25 + 25 + 25 + 25
22 + 25 + 25 + 25 + 25 + 25 + 35
25 + 25 + 25 + 25 + 25 + 25 + 25
25 + 25 + 25 + 25 + 25 + 25 + 35
8 ROOMS22 + 22 + 22 + 22 + 22 + 22 + 22 + 22
22 + 22 + 22 + 22 + 22 + 22 + 22 + 25
22 + 22 + 22 + 22 + 22 + 22 + 25 + 25
22 + 22 + 22 + 22 + 22 + 25 + 25 + 25
Unit A
1.96 / 2.24
1.79 / 2.04
1.69 / 1.93
1.84 / 2.10
1.69 / 1.93
1.73 / 1.99
2.33 / 2.66
2.19 / 2.50
2.00 / 2.28
1.89 / 2.16
2.06 / 2.35
1.89 / 2.16
1.94 / 2.22
2.00 / 2.28
1.96 / 2.24
1.84 / 2.11
1.69 / 1.93
1.92 / 2.20
1.81 / 2.07
1.66 / 1.90
1.71 / 1.96
1.89 / 2.16
1.78 / 2.03
1.68 / 1.92
1.85 / 2.12
1.75 / 2.00
1.82 / 2.07
1.71 / 1.97
1.79 / 2.05
1.69 / 1.93
2.00 / 2.28
1.89 / 2.16
1.75 / 2.00
1.72 / 1.96
1.69 / 1.93
1.66 / 1.90
Unit B
2.23 / 2.55
2.03 / 2.33
1.92 / 2.20
2.10 / 2.40
1.92 / 2.20
1.98 / 2.26
2.33 / 2.66
2.19 / 2.50
2.00 / 2.28
1.89 / 2.16
2.06 / 2.35
1.89 / 2.16
1.94 / 2.22
2.00 / 2.28
1.96 / 2.24
1.84 / 2.11
1.69 / 1.93
1.92 / 2.20
1.81 / 2.07
1.66 / 1.90
1.71 / 1.96
1.89 / 2.16
1.78 / 2.03
1.68 / 1.92
1.85 / 2.12
1.75 / 2.00
1.82 / 2.07
1.71 / 1.97
2.03 / 2.32
1.92 / 2.20
2.00 / 2.28
1.89 / 2.16
1.75 / 2.00
1.72 / 1.96
1.69 / 1.93
1.66 / 1.90
Unit C
2.23 / 2.55
2.03 / 2.33
1.92 / 2.20
2.10 / 2.40
1.92 / 2.20
1.98 / 2.26
2.33 / 2.66
2.19 / 2.50
2.00 / 2.28
1.89 / 2.16
2.06 / 2.35
1.89 / 2.16
1.94 / 2.22
2.00 / 2.28
1.96 / 2.24
1.84 / 2.11
1.69 / 1.93
1.92 / 2.20
1.81 / 2.07
1.66 / 1.90
1.71 / 1.96
1.89 / 2.16
1.78 / 2.03
1.68 / 1.92
1.85 / 2.12
1.75 / 2.00
2.07 / 2.37
1.96 / 2.23
2.03 / 2.32
1.92 / 2.20
2.00 / 2.28
1.89 / 2.16
1.75 / 2.00
1.72 / 1.96
1.69 / 1.93
1.66 / 1.90
Unit D
2.23 / 2.55
2.03 / 2.33
1.92 / 2.20
2.10 / 2.40
1.92 / 2.20
2.77 / 3.16
2.33 / 2.66
2.19 / 2.50
2.00 / 2.28
1.89 / 2.16
2.06 / 2.35
1.89 / 2.16
2.72 / 3.11
2.00 / 2.28
1.96 / 2.24
1.84 / 2.11
1.69 / 1.93
1.92 / 2.20
1.81 / 2.07
1.66 / 1.90
1.71 / 1.96
1.89 / 2.16
1.78 / 2.03
1.68 / 1.92
2.11 / 2.41
1.99 / 2.27
2.07 / 2.37
1.96 / 2.23
2.03 / 2.32
1.92 / 2.20
2.00 / 2.28
1.89 / 2.16
1.75 / 2.00
1.72 / 1.96
1.69 / 1.93
1.66 / 1.90
Unit E
2.23 / 2.55
2.03 / 2.33
1.92 / 2.20
2.93 / 3.35
2.69 / 3.08
2.77 / 3.16
2.33 / 2.66
2.19 / 2.50
2.00 / 2.28
1.89 / 2.16
2.88 / 3.29
2.65 / 3.03
2.72 / 3.11
2.00 / 2.28
1.96 / 2.24
1.84 / 2.11
1.69 / 1.93
1.92 / 2.20
1.81 / 2.07
1.66 / 1.90
1.71 / 1.96
2.14 / 2.45
2.02 / 2.31
1.91 / 2.19
2.11 / 2.41
1.99 / 2.27
2.07 / 2.37
1.96 / 2.23
2.03 / 2.32
1.92 / 2.20
2.00 / 2.28
1.89 / 2.16
1.75 / 2.00
1.72 / 1.96
1.69 / 1.93
1.66 / 1.90
Unit F
3.12 / 3.56
4.07 / 4.64
4.62 / 5.27
2.93 / 3.35
3.85 / 4.39
2.77 / 3.16
2.33 / 2.66
3.05 / 3.50
4.00 / 4.57
4.54 / 5.19
2.88 / 3.29
3.78 / 4.32
2.72 / 3.11
2.00 / 2.28
1.96 / 2.24
1.84 / 2.11
1.69 / 1.93
2.19 / 2.50
2.06 / 2.35
1.89 / 2.16
2.72 / 3.10
2.14 / 2.45
2.02 / 2.31
2.68 / 3.06
2.11 / 2.41
1.99 / 2.27
2.07 / 2.37
1.96 / 2.23
2.03 / 2.32
1.92 / 2.20
2.00 / 2.28
1.89 / 2.16
1.75 / 2.00
1.72 / 1.96
1.69 / 1.93
1.89 / 2.16
Unit G
2.00 / 2.28
2.23 / 2.55
2.93 / 3.34
3.85 / 4.40
2.19 / 2.50
2.88 / 3.29
3.78 / 4.32
2.72 / 3.10
2.14 / 2.45
2.83 / 3.24
2.68 / 3.06
2.11 / 2.41
2.78 / 3.18
2.07 / 2.37
2.74 / 3.13
2.03 / 2.32
2.69 / 3.07
2.00 / 2.28
2.65 / 3.03
1.75 / 2.00
1.72 / 1.96
1.92 / 2.20
1.89 / 2.16
Unit H
1.75 / 2.00
1.96 / 2.23
1.92 / 2.20
1.89 / 2.16
Indoor unitcombination
Cooling / Heating Capacity (kW)
Page 49
Outdoor Units
Side View >
MUZ-GC35VA / MUZ-FD25/35VAH / SUZ-KA25/35VA
MUZ-HC25/35VA(B) / MUZ-GC25VA
Upper View >
Front View >
Side View >
Upper View >
Front View >
Dimensions
Page 50
M S
erie
sR
ange
200
8O
utdo
or U
nit
Dim
ensi
ons
MUH-GA60VB / MUZ-GB50VA / MUZ-GA60/71VA / SUZ-KA50VA
Side View >Front View >
Upper View >
MUH-GA50VB
Side View >Front View >
Upper View >
Dimensions
Page 51
M S
erie
sR
ange
200
8A
cces
sori
es /
Opt
iona
l Ext
ras
Accessories / Optional ExtrasM Series
Air Cleaning Filter MAC-1700FT - for MSH-GA50/60VB (10 pack)
Catechin Filter MAC-3003CF - for MSZ-HC25/35VA(B) (10 pack)
Anti-Allergy Enzyme Filter MAC-408FT-E - for MSZ-GC22-35VA (10 pack)MAC-415FT-E - for MSZ-GB50VA (10 pack)MAC-2300FT - for MSZ-GA60-71VA (10 pack)
Wired Remote controller PAR-21MAA - for MSZ-GC22-35VA, MSZ-GB50VA, MSZ-GA60/71VA, MSZ-FD25/35VA & MFZ-KA25-50VAMAC-821SC-E - Centralised Simple ON/OFF Remote Controller for MXZ Multi-Splits
Interfaces MAC-399IF - for connection to M-NET system
MAC-397IF - for Contact Terminal, PAR-21MAA Wired Remote Controller and MAC-821SC-E Centralised ON/OFF Remote Controller
Air Outlet Guide PAC-SG59SG-E - for MXZ-8A140VA
Page 52
Mr SlimPackaged Split-System Air Conditioning
The Mr Slim rangeCompact and versatile, the
The 2008 Mr Slim range has been updated with new features, as well as the alreadyimpressive efficiency levels being improved. New to the range are the 19 & 22kW outdoormodels, available in both Power Inverter and Standard Inverter options. The smalleroutdoor models have also undergone improvements, in line with Mitsubishi Electricsforward looking approach.
New indoor units include the SEZ-KD ducted models and four new large capacity ductedmodels (PEA-RP-GA) available in up to 44kW cooling capacity. A new range of 4-wayblow cassettes (PLA-RP-BA2) are now available with improved COP's and EER's, furtherincreasing Mitsubsihi Electrics energy efficient portfolio. Finally a range of Heat Pump Air Curtains have been developed with Thermoscreens, for use with our Power Invertermodels, an ideal application for a retail establishment.
Mr Slim units are more than just physically compact and discreet. They’re also amongst the quietest operating units available, which means that apart from enjoying a comfortable,controllable environment, users hardly know Mr Slim is there at all.
Suitable to heat or cool a huge variety of applications, the Mr Slim range is oneof Britain’s best selling air conditioning split-systems. Combine the efficiency with the complete versatility that this range has to offer and the possibilities are virtually infinite.
Page 54
options are endless
Easy to f it wherever you need
An installers favourite, the excellent design of the Mr Slim range ensures quick and simple installation with the minimum of disruption. With extensive pipe runs of up to 120m, this versatile range makes it easier to select a layout to install the unit.
The issue of using existing R22/R407c pipe work has been resolvedusing Mitsubishi Electric’s unique ‘Replace Technology’, offering the opportunity to upgrade older, less efficient systems with the minimum of cost and installation disruption.
* 1 Based on the following operating conditions - Place-Office in Tokyo, Japan / Operating time-8am to 8pm, 6 days/week / Operating period-Cooling: April 16 - November 8Heating: December 14 - March 23 / Set temperature-Cooling: 27°C, Heating: 20˚C. Non-inverter model installed eight years ago is a PLH-3GKHB / PUH-3YKA. Power Inverter model is a PLA-RP71BA2 / PUHZ-RP71VHA3.
The Mr Slim Power Inverter range is now stronger than ever. The technological developments applied to this new range of equipmentoffer the end user some of the highest energy efficiency ratings available,alongside greater application flexibility.
This range is available in single and 3-phase options, the latter having runningcurrents that are more than half that of the single phase option, offering a clear benefit to business premises that already have 3-phase supply installed. All models have low starting currents of 5 amps.
Power Inverter
Improved COP / EER Ratings - COP and EER ratings have increased across the board with many models within our range now having energy labels of ‘A’ in both heating and cooling.
Reducing Power Consumption by 70% - The Mr Slim Power Inverter canreduce power consumption by up to 70% compared to a previously installed non-invertermodel*1, making the energy cost savings associated with this range truly remarkable. A highpower function also delivers increased capacity at times of high demand, allowing the roomtarget temperature to be reached as rapidly as possible from start up.
Page 56
New 19 & 22kW models now available -
The unit size of these models has now beensignificantly reduced as displayed here.
Silent OperationOperation has been made near-silent (67% quieter than corresponding R22 outdoor unit*1) as a result of improvement in the design of the fan blades and the new grille shape. The Power Inverter is even quieter at night when outsidetemperatures drop, as it can be set to low-noise mode (cooling only) reducing operating noise by 3dBA (50% quieter thannormal day mode). A low-noise priority function is also available by connecting a separate commercially available timer orselector switch. When a signal is received from the timer or switch, the unit automatically runs in low-noise mode.
Duty Standby Operation3 new functions are available with Mr Slim systems*2:
*1 When comparing the Power Inverter (PUHZ-RP71VHA3) with R22 (PUH3-VKA) in cooling.*2 Not available when using SUZ outdoor units. Must be used in conjunction with a PAR-21MAA controller.
Page 57
Rotation2 outdoor units (master & sub) operate alternately,switching every 1, 3, 5, 7, 14, 28 days (selectable).
Back UpWhen master outdoor unit fails, sub unit begins operation.
Join InWhen master outdoor unit fails to reach settemperature, sub unit operates in conjunction (available in cooling mode only).
Rotate
Back Up
Join In
Improved COP / EER Figures - COP / EER figures have been improvedwhen compared to the previous R407c range.
The Standard Inverter models provide an inverter solution at a lowercapital cost than the Power Inverter range. These outdoor models continueto offer high efficiency as standard, with some systems qualifying forEnhanced Capital Allowance. Models are available in 10, 12.5 & 14kW singlephase and now 19 & 22kW three phase.
Standard Inverter
2.61 2.69 3.01 3.41EER COP
D E B B
COPImprovedby 27%
R407c Fixed speed unitPUH-P100VGAA
Standard InverterPUHZ-P100VHA2
EER
COP
Low noise mode can be set at night time to reduce noise levels by approximately 50%.
The example here is using a PUHZ-P100VHA2.
1350
mm
943m
m
330mm 330mm
407mm
950mm 950mm
Power Inverter
121kg Standard Inverter
75kg
Compared to Power Inverter
Height reduced by 407mm
Weight reduced by 46kg
Day 50dBAOutdoor Temperature 35ºC
Night 47dBAOutdoor Temperature 25ºC
1/2 the audible sound(compared to
daytime)
3dBALess
Example:
Silent Outdoor Unit - Low Noise Mode
10.0kW model now has acompact single fan design andweighs less, when compared to its Power Inverter equivalent,making installation easier.
Page 58
Inverter solutionsat a lower price
SUZ outdoor units are able to be connected to selected Mr Slim indoor units, creating a new range of low cost inverter driven systems.
Pump down switch
Pump down switch
Pushing a switch starts / stops refrigerant recovery operation automatically. This work will then be completed by closing a valve.
Smooth refrigerant recovery can be assured by pushing the pump down switch at unit movement / renewal.
Design with Environmental Consideration
Page 59
The PLA-RP-BA(2) (PLFY-P-VBM-E for City Multi)
4-Way Blow Cassette, offers a range of new features, as well as a new design and pure white colour.
New 4-Way Blow Cassette
Wide AirflowThe new wide shape vane (capable of wide angle air supply) provides comfort at the corners of a room, regardless of cooling or heating operation.A reduction in the air speed by 20% (compared to the previous product)eliminates the uncomfortable draft sensation often experienced.
Reduced Draft Air DistributionReduced draft air distribution allows the vanes to supply airflow horizontally, thus preventing discomfort due to excessive cooling or from direct exposure of occupants to the air blow.
Independent Vane ControlIf the airflow direction needs to be changed as a result of an altered room layout or due to the mode selected (i.e. cooling or heating), the air direction of each vane can be set independently using the PAR-21MAA wired remote controller.
Automatic Airflow Adjustment ModeThe automatic airflow adjustment mode is provided in addition to the 4 normal airflow stages and allowsautomatic adjustment of the airflow in accordance with the difference between the set temperature and the room temperature.
For example: The automatic airflow adjustment modeallows quick cooling of a room using high mode, thenwhen the room temperature has stabilised, the low mode will be applied to maximise comfort.
Grille with Automatic Filter LoweringFunction (Optional)This grille can be operated by both the wired remote controller and theexclusive infra-red remote controller.It can be lowered in 8 steps down to 4m in accordance with the ceiling height, enabling you to easily clean the air filter. Regular cleaning of the filter is an important factor in saving energy.
� Previous product � New product
Reduced Draft Air
Distribution
HighLow Automatic airflowadjustmentMedium 2 Medium 1
PAR-21MAA Wired Remote Controller
Elevation Grille Remote Controller
(comes with the grille)
PAR-21MAA
Down blow
Horizontal blow
Adjustable Fixed
Automaticlowering
to4m
Page 60
360°The "I-See Sensor" rotates to measure the floor temperature
“Sensible Temperature Control” to Prevent Excessive Cooling and Heating
The (optional corner panel) Provides EvenTemperature Distribution and Reduces Energy Consumption
By measuring the inlet temperature and floor temperature, a temperature felt by the human body (sensible temperature) will be calculated and maintained, suppressing excessive cooling and heating.
The “I-See Sensor” uses new temperature sensing technology developed by Mitsubishi Electric. In order to create a comfortable environment in shops and offices, it is essential to control the temperature near the floor where occupants and visitors gather. The “I-See Sensor” measures the infra-red rays generated from the surrounding wall and floor surfaces and converts these into temperature values. In addition, floor temperatures are also measured at distant spots, allowing optimum airflow to reach these areas.
� “I-See Sensor” operation: The “I-See Sensor”rotates slowly in intervals of 5 seconds, correctly measuring the temperature of the entire floor space.
5 seconds 5 seconds 5 seconds 5 seconds
In the past... only the inlet temperature near the ceiling was measured, tending to overlook the uneven temperature distribution near the floor.
Conventional air conditioning in shops and offices onlymeasured the temperature near to the ceiling, therefore the uneven temperature distribution between the ceiling and the floor remained unchecked.
As a result, the set temperature tended to be higher in orderto obtain comfort at floor level.
Inlet temperature sensor
Area measured by cassette model without "I-See Sensor"
37ºC
25ºC
13ºC
Without “I-See Sensor”.Set temperature is23ºC (in Heating)
e.g. To achieve a sensible temperature of 20ºC, the set temperature must be as high as 23ºC
Inlet temperature sensor
2.7m
Area measured by the cassette model equipped with "I-See Sensor"360°
sensing
37ºC
25ºC
13ºC
With the “I-See Sensor” plus automatic airflowadjustment mode.Set temperature is 20ºC (in Heating)
e.g. With the set temperature at 20ºC, a sensible temperature of 20ºC at floor level can be obtained.
With “I-See Sensor”... both the floor temperature and inlet temperature are measured.
The New 4-Way Blow Ceiling Cassette with the “I-See Sensor” simultaneously measures the floor and inlet temperatures, providing improved comfort to occupants and increased energy savings.
Page 61
The adaptable Mr Slim range
Available in a variety of options, the Mr Slim range
fits in wherever it’s needed. Indoor units can be
four way blow cassettes, ducted,
wall or ceiling mounted. Up to four indoor
units can then be connected to a single outdoor unit
providing the ideal air conditioning solution.
Designed to f it anywhere
Simple technologyat its best
Systems marked with the ECA logo have an energy label of A or B, are registered on theEnergy Technology List and hence qualify for 100% first year enhanced capital allowances(whole system cost and ‘reasonable’ cost of installation). For further information please go to www.eca.gov.uk
Nominal conditions cooling: indoor 27˚C DB, 19˚C WB; outdoor 35˚C DB, 24˚C WB.Nominal conditions heating: indoor 20˚C DB; outdoor 7˚C DB, 6˚C WB.UK Conditions: Summer; indoor 21˚C DB, 15˚C WB; outdoor 27˚C DB. Winter; indoor 21˚C DB; outdoor -1˚C WB.
Page 62
Contents
PKA-RP Power Inverter Heat Pump, Wall Mounted System
PKA-RP Standard Inverter Heat Pump, Wall Mounted System
PKA-RP Heat Pump, Wall Mounted System
SEZ-KD-VA Inverter Heat Pump, Ceiling Concealed Ducted System
PEAD-RP Power Inverter Heat Pump, Ceiling Concealed Ducted System
PEAD-RP Standard Inverter Heat Pump, Ceiling Concealed Ducted System
PEAD-RP Heat Pump, Ceiling Concealed Ducted System
PEA-RP-GA Power Inverter Heat Pump, Large Capacity Ceiling Concealed Ducted System
PEA-RP-GA Standard Inverter Heat Pump, Large Capacity Ceiling Concealed Ducted System
SLZ-KA-VA Inverter Heat Pump, 600x600 4-Way Blow Ceiling Cassette System
PLA-RP Power Inverter Heat Pump, 4-Way Blow Ceiling Cassette System
PLA-RP Standard Inverter Heat Pump, 4-Way Blow Ceiling Cassette System
PLA-RP Heat Pump, 4-Way Blow Ceiling Cassette System
PCA-RP Power Inverter Heat Pump, Ceiling Suspended System
PCA-RP Standard Inverter Heat Pump, Ceiling Suspended System
PCA-RP Heat Pump, Ceiling Suspended System
PCA-RP-HA Power Inverter Heat Pump, Stainless Steel Ceiling Suspended System
PCA-RP-HA Standard Inverter Heat Pump, Stainless Steel Ceiling Suspended System
PCA-RP-HA Heat Pump, Stainless Steel Ceiling Suspended System
PSA-RP Power Inverter Heat Pump, Floor Standing System
PSA-RP Standard Inverter Heat Pump, Floor Standing System
PSA-RP Heat Pump, Floor Standing System
PHV DXE Heat Pump, Air Curtain
Mr Slim Multi-Split Systems Heat Pump
Outdoor Units
Air Handling Unit Controller
Mr Slim Accessories / Optional Extras
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
115
116
Page 63
PKA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) – HRC (A)
INTERCONNECTING CABLE No. CORES
PKA-RP35GAL
3.6 (1.6-5.2)
3.6 (1.6-4.5)
3.05 (1.35-4.4)
3.25 (1.45-4.05)
0.87
3.41 / 3.50
B / A
9-10-11-12
12.7 (1/2”)
6.35 (1/4”)
36-38-41-43
990
235
340
16
Fed by Outdoor Unit
Single
6
4
PKA-RP50FAL2
6.0 (2.5-7.3)
5.0 (2.3-5.6)
5.1 (2.15-6.2)
4.5 (2.05-5.05)
0.86
3.41 / 3.01
B / B
15-20
12.7 (1/2”)
6.35 (1/4”)
39-45
1400
235
340
24
Fed by Outdoor Unit
Single
6
4
PKA-RP60FAL
7.0 (2.8-8.2)
6.0 (2.7-6.7)
5.95 (2.4-6.95)
5.4 (2.45-6.05)
0.83
3.48 / 3.87
B / A
15-20
15.88 (5/8”)
9.52 (3/8”)
39-45
1400
235
340
24
Fed by Outdoor Unit
Single
6
4
PKA-RP71FAL
7.6 (3.5-10.2)
7.1 (3.3-8.1)
6.45 (3.0-8.65)
6.4 (2.95-7.3)
0.77
3.41 / 3.59
B / A
15-20
15.88 (5/8”)
9.52 (3/8”)
39-45
1400
235
340
24
Fed by Outdoor Unit
Single
6
4
PKA-RP100FAL
11.2 (4.5-14.0)
10.0 (4.9-11.4)
9.5 (3.85-11.9)
9.0 (4.4-10.25)
0.77
3.45 / 3.41
B / A
22-28
15.88 (5/8”)
9.52 (3/8”)
41-46
1680
235
340
28
Fed by Outdoor Unit
Single
6
4
PUHZ-RP - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) Single Phase
Heating/Cooling [MAX] 3 Phase
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
PUHZ-RP35VHA3
46 / 44
42
800
300 + 23
600
220-240v, 50Hz
Single
1.06 / 1.03
0.94 / 0.86
5
4.56 / 4.34 [13]
-
16
3
50
30
2.5
PUHZ-RP50VHA3
46 / 44
42
800
300 + 23
600
220-240v, 50Hz
Single
1.76 / 1.66
1.57 / 1.41
5
6.9 / 6.59 [13]
-
16
3
50
30
2.5
PUHZ-RP60VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
2.01 / 1.55
1.79 / 1.32
5
7.93 / 7.04 [19]
-
25
3
50
30
3.5
PUHZ-RP71VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
2.23 / 1.98
2.00 / 1.68
5
10.17 / 8.47 [19]
-
25
3
50
30
3.5
PUHZ-RP100VHA3/YHA3
51 / 49
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
3.25 / 2.93
2.89 / 2.49
5
12.91 / 13.05 [28]
4.55 / 4.60 [13]
32 / 16
3 / 5
75
30
5.0
Wall Mounted System� Adjustable louvres for uniform air distribution
� Internal pipe connection to wall mounted unit for easy and neat installation
PKA-RP Power Inverter Heat Pump
Technical Information
Page 64
INDOOR UNIT PKA-RP35GAL
INDOOR UNIT PKA-RP50-71FAL(2)
INDOOR UNIT PKA-RP100FAL
Mr
Slim
Ran
ge 2
008
Lower Side View >
Left Side View > Front View > < Right Side View
Lower Side View >
Left Side View > Front View > < Right Side View
Front View >
Lower Side View >
Left Side View > Right Side View >
PKA
-RP
Pow
er In
vert
er H
eat
Pum
p
Dimensions
Page 65
PKA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PKA-RP100FAL
11.2 (4.5-12.5)
9.4 (4.9-11.2)
9.5 (3.85-10.65)
8.45 (4.4-10.1)
0.79
3.21 / 3.01
C / B
22-28
15.88 (5/8”)
9.52 (3/8”)
41-46
1680
235
340
28
Fed by Outdoor Unit
Single
6
4
PUHZ-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 20m
PUHZ-P100VHA2
54 / 50
75
950
330 + 30
943
220-240v, 50Hz
Single
3.49 / 3.12
3.11 / 2.65
4
13.14 / 12.78 [28]
32
3
50
30
2.7
Wall Mounted System
� Adjustable louvres for uniform air distribution
� Internal pipe connection to wall mounted unit for easy and neat installation
PKA-RP Standard Inverter Heat Pump
The Standard Inverter range provides inverter solutions for customers who want all the benefits that inverters offer, but do not have the budget available for the more expensive Power Inverter range.
Technical Information
Page 66
INDOOR UNIT PKA-RP100FAL
Lower Side View >
Left Side View > Front View > < Right Side View
Mr
Slim
Ran
ge 2
008
PKA
-RP
Stan
dard
Inve
rter
Hea
t Pu
mp
Dimensions
Page 67
PKA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PKA-RP100FAL
11.5
9.8
9.8
8.8
0.77
22-28
15.88 (5/8”)
9.52 (3/8”)
41-46
1680
235
340
28
Fed by Outdoor Unit
Single
6
4
Wall Mounted System
PKA-RP Heat Pump
PUH-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
PUH-P100YHA
52 / 50
94
950
330 + 30
943
380-415v, 50Hz
3
3.47 / 3.50
3.09 / 2.98
45
5.7 / 5.91 [11.8]
20
5
50
50
4.4
Technical Information
� Adjustable louvres for uniform air distribution
� Internal pipe connection to wall mounted unit for easy and neat installation
The Heat Pump system provides a low cost alternative to three phase Power Inverter systems.
Page 68
INDOOR UNIT PKA-RP100FAL
Lower Side View >
Left Side View > Front View > < Right Side View
Mr
Slim
Ran
ge 2
008
PKA
-RP
Hea
t Pu
mp
Dimensions
Page 69
SEZ-KD-VA - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Mi-Hi
EXTERNAL STATIC PRESSURE Pa Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
SUZ-KA-VA - OUTDOOR UNITS
MODEL REFERENCE
NOISE (dBA) (Lo-Hi) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. CORES
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 7m
SEZ-KD25VA
3.0 (0.9-4.5)
2.5 (0.9-3.2)
2.5 (0.75-3.75)
2.5 (0.9-3.15)
0.80
3.61 / 3.21
A / A
5.5-7.0-9.0
5-15-35-50
9.52 (3/8”)
6.35 (1/4”)
23-26-30
790
700
200
18
Fed by Outdoor Unit
Single
6
4
SEZ-KD35VA
4.0 (0.9-5.0)
3.5 (1.0-3.9)
3.3 (0.75-4.15)
3.45 (1.0-3.85)
0.78
3.61 / 3.21
A / A
7-9-11
5-15-35-50
9.52 (3/8”)
6.35 (1/4”)
23-28-33
990
700
200
21
Fed by Outdoor Unit
Single
6
4
SEZ-KD50VA
6.0 (1.1-7.2)
5.0 (1.1-5.6)
5.0 (0.9-6.0)
4.95 (1.1-5.55)
0.76
3.21 / 2.81
C / C
10-12.5-15
5-15-35-50
12.7 (1/2”)
6.35 (1/4”)
30-34-37
990
700
200
23
Fed by Outdoor Unit
Single
6
4
SEZ-KD60VA
7.0 (0.9-8.0)
5.5 (1.1-6.3)
5.8 (0.75-6.65)
5.45 (1.1-6.25)
0.79
3.41 / 2.91
B / C
12-15-18
5-15-35-50
15.88 (5/8”)
6.35 (1/4”)
30-34-38
1190
700
200
27
Fed by Outdoor Unit
Single
6
4
SEZ-KD71VA
8.1 (0.9-10.4)
7.1 (0.9-8.3)
6.75 (0.75-8.65)
7.05 (0.9-8.25)
0.74
3.42 / 2.81
B / C
12-16-20
5-15-35-50
15.88 (5/8”)
9.52 (3/8”)
30-35-40
1190
700
200
27
Fed by Outdoor Unit
Single
6
4
SUZ-KA25VA
46 / 46
33
800
285
550
220-240v, 50Hz
0.83 / 0.778
0.76 / 0.62
3.65
4.04 / 3.44 [8.16]
16
3
20
12
0.9
SUZ-KA35VA
48 / 47
37
800
285
550
220-240v, 50Hz
1.108 / 1.09
1.01 / 0.87
4.75
5.21 / 5.01 [9.18]
16
3
20
12
1.05
SUZ-KA50VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
1.87 / 1.78
1.70 / 1.42
6.75
6.98 / 7.38 [16]
25
3
30
30
1.6
SUZ-KA60VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
2.05 / 1.89
1.87 / 1.51
9.75
10.38 / 8.98 [16]
25
3
30
30
1.8
SUZ-KA71VA
53-55 / 51-53
58
840
330
850
220-240v, 50Hz
2.37 / 2.53
2.15 / 2.02
10.3
10.74 / 11.14 [16]
25
3
30
30
2.0
Ceiling Concealed Ducted System
SEZ-KD-VA Inverter Heat Pump
Designed for homes, offices, restaurants or shops, the SEZ-KD-VA series operates at low noise levels. Its new improved low unit height and lightweight design also help to make installation easier and more convenient.
Technical Information
Note: Optional interfaces for M-NET connectivity (MAC-399IF) and group control, fault/run (MAC-397IF) are available. Please see accessories / optional extras section.
Page 70
Upper View >
INDOOR UNIT SEZ-KD25-71VA
Front View >
Mr
Slim
Ran
ge 2
008
SEZ
-KD
-VA
Inve
rter
Hea
t Pu
mp
Dimensions
Models A B C D E F
Size 25 700 752 798 660 7 600
Size 35-50 900 952 998 860 9 800
Size 60-71 1100 1152 1198 1060 11 1000
Page 71
Side View >
PEAD-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
EXTERNAL STATIC PRESSURE (Pa) Lo-Hi
NOISE (dBA) Lo-Hi (*4)
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PEAD-RP140EA
16.0 (5.0-18.0)
14.0 (5.5-15.3)
13.6 (4.25-15.3)
12.6 (4.95-13.75)
0.83
3.41 / 3.01
B / B
36.5-46
15.88 (5/8”)
9.52 (3/8”)
70-130*3
46-51 (47-53)
1715
740
325
70
Fed by Outdoor Unit
Single
6
4
PEAD-RP125EA
14.0 (5.0-16.0)
12.5 (5.5-14.0)
11.9 (4.25-13.6)
11.25 (4.95-12.6)
0.82
3.61 / 3.21
A / A
33.5-42
15.88 (5/8”)
9.52 (3/8”)
70-130*3
44-50 (46-52)
1415
740
325
65
Fed by Outdoor Unit
Single
6
4
PEAD-RP100EA2
11.2 (4.5-14.0)
10.0 (4.9-11.4)
9.5 (3.85-11.9)
9.0 (4.4-10.25)
0.86
3.51 / 3.27
B / A
33.5-42
15.88 (5/8”)
9.52 (3/8”)
70-130*2
44-50 (46-52)
1415
740
325
65
Fed by Outdoor Unit
Single
6
4
PEAD-RP71EA
8.0 (3.5-10.2)
7.1 (3.3-8.1)
6.8 (3.0-8.65)
6.4 (2.95-7.3)
0.83
3.42 / 3.30
B / A
20-25
15.88 (5/8”)
9.52 (3/8”)
70-130*1
37-41 (40-45)
1175
740
325
44
Fed by Outdoor Unit
Single
6
4
PEAD-RP60EA
7.0 (2.8-8.2)
6.0 (2.7-6.7)
5.95 (2.4-6.95)
5.4 (2.45-6.05)
0.79
3.68 / 3.23
A / A
17-21
15.88 (5/8”)
9.52 (3/8”)
30-70
37-41 (39-46)
1175
700
295
42
Fed by Outdoor Unit
Single
6
4
PEAD-RP50EA
6.0 (2.5-7.3)
4.9 (2.3-5.6)
5.1 (2.15-6.2)
4.4 (2.05-5.05)
0.82
3.64 / 3.22
A / A
13.5-17
12.7 (1/2”)
6.35 (1/4”)
30-70
36-40 (38-44)
935
700
295
35
Fed by Outdoor Unit
Single
6
4
PEAD-RP35EA2
4.1 (1.6-5.2)
3.6 (1.6-4.5)
3.5 (1.35-4.4)
3.25 (1.45-4.05)
0.89
3.41 / 3.21
B / A
13.5-17
12.7 (1/2”)
6.35 (1/4”)
30-70
36-40 (38-44)
935
700
295
33
Fed by Outdoor Unit
Single
6
4
PUHZ-RP35VHA3
46 / 44
42
800
300 + 23
600
220-240v, 50Hz
Single
1.20 / 1.12
1.05 / 0.95
5
4.84 / 4.62 [13]
-
16
3
50
30
2.5
PUHZ-RP50VHA3
46 / 44
42
800
300 + 23
600
220-240v, 50Hz
Single
1.65 / 1.52
1.47 / 1.29
5
7.08 / 6.77 [13]
-
16
3
50
30
2.5
PUHZ-RP60VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
1.90 / 1.86
1.69 / 1.58
5
8.2 / 7.31 [19]
-
25
3
50
30
3.5
PUHZ-RP71VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
2.34 / 2.15
2.08 / 1.83
5
11.29 / 9.59 [19]
-
25
3
50
30
3.5
PUHZ-RP100VHA3/YHA3
51 / 49
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
3.19 / 3.06
2.84 / 2.60
5
15.01 / 15.15 [28]
6.65 / 6.70 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP125VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
3.88 / 3.89
3.45 / 3.31
5
18.6 / 18.15 [28]
7.82 / 7.66 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP140VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
4.69 / 4.65
4.17 / 3.95
5
22.61 / 22.34 [29.5]
9.15 / 9.06 [13]
40 / 16
3 / 5
75
30
5.0
PUHZ-RP - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) Single Phase
Heating/Cooling [MAX] 3 Phase
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Ceiling Concealed Ducted System
PEAD-RP Power Inverter Heat Pump
Notes: External static pressure - (35-60: 30 + 70Pa connections as standard) / (71-140: 130Pa optional fan motor - *1 PAC-SK005MT-F, *2 PAC-SK004MT-F, *3 PAC-SK003MT-F).*4 70Pa (35-60) / 130Pa optional fan motor (71-140).
Technical Information
Page 72
Models A B C D E
Size 35-50 772 305 - 830 804
Size 60 1012 280 290 1070 1044
INDOOR UNIT PEAD-RP35-60EA(2)
INDOOR UNIT PEAD-RP71-140EA(2)
Models A B C D E
Size 71 1012 280 290 1070 1044
Size 100-125 1252 360 370 1310 1284
Size 140 1552 460 470 1610 1584
Side View >
Upper View >
Front View >
Upper View > Front View >
Side View >
Mr
Slim
Ran
ge 2
008
PEA
D-R
PPo
wer
Inve
rter
Hea
t Pu
mp
Dimensions
Page 73
PEAD-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
EXTERNAL STATIC PRESSURE (Pa) Lo-Hi
NOISE (dBA) Lo-Hi (*4)
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PEAD-RP140EA
16.0 (5.0-18.0)
13.6 (5.5-15.0)
13.6 (4.25-15.3)
12.25 (4.95-13.5)
0.84
3.21 / 2.61
C / D
36.5-46
15.88 (5/8”)
9.52 (3/8”)
70-130*3
46-51 (47-53)
1715
740
325
70
Fed by Outdoor Unit
Single
6
4
PEAD-RP125EA
14.0 (5.0-16.0)
12.3 (5.5-14.0)
11.9 (4.25-13.6)
11.05 (4.95-12.6)
0.83
3.41 / 2.81
B / C
33.5-42
15.88 (5/8”)
9.52 (3/8”)
70-130*3
44-50 (46-52)
1415
740
325
65
Fed by Outdoor Unit
Single
6
4
PEAD-RP100EA2
11.2 (4.5-12.5)
9.4 (4.9-11.2)
9.5 (3.85-10.65)
8.45 (4.4-10.1)
0.86
3.41 / 3.01
B / B
33.5-42
15.88 (5/8”)
9.52 (3/8”)
70-130*2
44-50 (46-52)
1415
740
325
65
Fed by Outdoor Unit
Single
6
4
PEAD-RP71EA
8.0 (0.9-10.2)
7.1 (0.9-8.1)
6.65 (0.75-8.5)
7.05 (0.9-8.05)
0.81
3.21 / 2.81
C / C
20-25
15.88 (5/8”)
9.52 (3/8”)
70-130*1
37-41 (40-45)
1175
740
325
44
Fed by Outdoor Unit
Single
6
4
PEAD-RP60EA
7.0 (0.9-8.0)
6.0 (1.1-6.3)
5.8 (0.75-6.65)
5.95 (1.1-6.25)
0.80
3.38 / 2.93
C / C
17-21
15.88 (5/8”)
6.35 (1/4”)
30-70
37-41 (39-46)
1175
700
295
42
Fed by Outdoor Unit
Single
6
4
PEAD-RP50EA
5.9 (0.9-7.2)
4.9 (1.1-5.6)
4.9 (0.75-6.0)
4.85 (1.1-5.55)
0.79
3.49 / 2.82
B / C
13.5-17
12.7 (1/2”)
6.35 (1/4”)
30-70
36-40 (38-44)
935
700
295
35
Fed by Outdoor Unit
Single
6
4
PEAD-RP35EA2
4.1 (0.9-5.0)
3.6 (1.0-3.9)
3.4 (0.75-4.15)
3.55 (1.0-3.85)
0.90
3.63 / 3.21
A / A
13.5-17
9.52 (3/8”)
6.35 (1/4”)
30-70
36-40 (38-44)
935
700
295
33
Fed by Outdoor Unit
Single
6
4
SUZ-KA35VA
48 / 47
37
800
285
550
220-240v, 50Hz
Single
1.13 / 1.12
1.03 / 0.90
4.75
5.36 / 5.16 [9.18]
16
3
20
12
1.05
SUZ-KA50VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
Single
1.69 / 1.74
1.54 / 1.39
6.75
6.96 / 7.36 [16]
25
3
30
30
1.6
SUZ-KA60VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
Single
2.07 / 2.05
1.88 / 1.64
9.75
10.45 / 9.05 [16]
25
3
30
30
1.8
SUZ-KA71VA
53-55 / 51-53
58
840
330
850
220-240v, 50Hz
Single
2.49 / 2.53
2.27 / 2.02
10.3
11.45 / 11.85 [16]
25
3
30
30
2.0
PUHZ-P100VHA2
54 / 50
75
950
330 + 30
943
220-240v, 50Hz
Single
3.28 / 3.12
2.92 / 2.65
4
15.24 / 14.88 [28]
32
3
50
30
2.7
PUHZ-P125VHA2
55 / 51
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.11 / 4.38
3.66 / 3.72
14
19.36 / 19.99 [28]
32
3
50
30
4.5
PUHZ-P140VHA2
56 / 52
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.98 / 5.21
4.43 / 4.43
14
24.00 / 25.17 [29.5]
40
3
50
30
4.5
SUZ-KA / PUHZ-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) (Lo-Hi) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg)
Ceiling Concealed Ducted System
PEAD-RP Standard Inverter Heat Pump
Notes: External static pressure - (35-60: 30 + 70Pa connections as standard) / (71-140: 130Pa optional fan motor - *1 PAC-SK005MT-F, *2 PAC-SK004MT-F, *3 PAC-SK003MT-F).*4 70Pa (35-60) / 130Pa optional fan motor (71-140).
The Standard Inverter range provides inverter solutions for customers who want all the benefits that inverters offer, but do not have the budget available for the more expensive Power Inverter range.
Notes: All units charged to 7m (35-71), 20m (100) and 30m (125-140) pipe length.
Technical Information
Page 74
Models A B C D E
Size 35-50 772 305 - 830 804
Size 60 1012 280 290 1070 1044
INDOOR UNIT PEAD-RP35-60EA(2)
INDOOR UNIT PEAD-RP71-140EA(2)
Models A B C D E
Size 71 1012 280 290 1070 1044
Size 100-125 1252 360 370 1310 1284
Size 140 1552 460 470 1610 1584
Side View >
Upper View >
Front View >
Upper View > Front View >
Side View >
Mr
Slim
Ran
ge 2
008
PEA
D-R
PSt
anda
rd In
vert
er H
eat
Pum
p
Dimensions
Page 75
PEAD-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
EXTERNAL STATIC PRESSURE (Pa) Lo-Hi
NOISE (dBA) Lo-Hi (*3)
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PEAD-RP100EA2
11.5
10.0
9.8
9.0
0.86
33.5-42
15.88 (5/8”)
9.52 (3/8”)
70-130*1
44-50 (46-52)
1415
740
325
65
Fed by Outdoor Unit
Single
6
4
PEAD-RP125EA
14.3
12.3
12.2
11.05
0.82
33.5-42
15.88 (5/8”)
9.52 (3/8”)
70-130*2
44-50 (46-52)
1415
740
325
65
Fed by Outdoor Unit
Single
6
4
PEAD-RP140EA
16.7
14.2
14.2
12.8
0.83
36.5-46
15.88 (5/8”)
9.52 (3/8”)
70-130*2
46-51 (47-53)
1715
740
325
70
Fed by Outdoor Unit
Single
6
4
Ceiling Concealed Ducted System
PEAD-RP Heat Pump
PUH-P100YHA
52 / 50
94
950
330 + 30
943
380-415v, 50Hz
3
3.42 / 3.69
3.04 / 3.14
45
7.8 / 8.01 [13.9]
20
5
50
50
4.4
PUH-P125YHA
52 / 50
131
950
330 + 30
1350
380-415v, 50Hz
3
4.32 / 4.41
3.85 / 3.75
70
9.19 / 9.41 [17.8]
20
5
50
50
5.0
PUH-P140YHA
53 / 51
131
950
330 + 30
1350
380-415v, 50Hz
3
5.28 / 5.63
4.70 / 4.79
85
11.14 / 11.24 [21.5]
25
5
50
50
5.0
PUH-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Notes: External static pressure - (100-140: 130Pa optional fan motor - *1 PAC-SK004MT-F, *2 PAC-SK003MT-F). *3 130Pa optional fan motor (100-140).
Technical Information
The Heat Pump system provides a low cost alternative to three phase Power Inverter systems.
Page 76
INDOOR UNIT PEAD-RP100-140EA(2)
Models A B C D E
Size 100-125 1252 360 370 1310 1284
Size 140 1552 460 470 1610 1584
Upper View >
Front View >
Side View >
Mr
Slim
Ran
ge 2
008
PEA
D-R
P H
eat
Pum
p
Dimensions
Page 77
PEA-RP-GA - INDOOR UNITSMODEL REFERENCECAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
EXTERNAL STATIC PRESSURE (Pa)
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
POWER INPUT (kW) (nominal)
(UK)
STARTING CURRENT (A)
RUNNING CURRENT (A) [Max]
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
INTERCONNECTING CABLE No. CORES
PUHZ-RP-YHA2 - OUTDOOR UNITSMODEL REFERENCENOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
RUNNING CURRENT (A) [Max] Heating/Cooling
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
PEA-RP200GA
22.4 (9.5-25.0)
19.0 (9.0-22.4)
19.05 (8.1-21.25)
17.1 (8.3-21.15)
0.81
3.45 / 2.84
B / C
52-65
28.58 (1 1/8”)
9.52 (3/8”)
150
48-51
1400
634
400
70
380-415v, 50Hz
3
1.00
0.89
5.62.0 [2.4]
6
5
3
PEA-RP250GA
27.0 (12.5-31.5)
22.0 (11.2-28.0)
22.95 (10.65-26.8)
19.8 (10.3-25.2)
0.86
3.29 / 2.64
C / D
64-80
28.58 (1 1/8”)
12.7 (1/2”)
150
49-52
1600
634
400
77
380-415v, 50Hz
3
1.18
1.05
5.6
2.3 [2.8]
6
5
3
PUHZ-RP200YHA2
59 / 58
135
950
330+30
1350
380-415v, 50Hz
3
5.5 / 5.7
4.9 / 4.85
5
8.9 / 7.7 [19]
32
5
120
30
6.5
PUHZ-RP250YHA2
59 / 58
136
950
330+30
1350
330-415v, 50Hz
3
7.02 / 7.16
6.25 / 6.09
5
11.1 / 9.5 [21]
32
5
120
30
7.1
PEA-RP400GA
44.8 (18.0-50.0)
38.0 (18.0-44.8)
38.1 (15.3-42.5)
34.95 (16.55-41.2)
0.75
3.56 / 2.93
B / C
120
28.58 (1 1/8”) x2
9.52 (3/8”) x2
150
52
1947
764
595
130
380-415v, 50Hz
3
1.55
1.38
8.7
3.8 [4.6]
10
5
3
PEA-RP500GA
54.0 (25.0-63.0)
44.0 (22.4-56.0)
45.9 (21.25-53.55)
40.5 (20.6-51.5)
0.77
3.20 / 2.56
D / E
160
28.58 (1 1/8”) x2
12.7 (1/2”) x2
150
53
1947
764
595
133
380-415v, 50Hz
3
2.84
2.53
10
5.4 [6.5]
10
5
3
PUHZ-RP200YHA2 x2
59 / 58
135
950
330+30
1350
380-415v, 50Hz
3
5.5 / 5.7
4.9 / 4.85
5
8.9 / 7.7 [19]
32
5
120 per outdoor
30
6.5
PUHZ-RP250YHA2 x2
59 / 58
136
950
330+30
1350
330-415v, 50Hz
3
7.02 / 7.16
6.25 / 6.09
5
11.1 / 9.5 [21]
32
5
120 per outdoor
30
7.1
Large Capacity Ceiling Concealed Ducted System
PEA-RP-GA Power Inverter Heat Pump
� Twin, triple or quadruple configurations on one outdoor unit, utilising Mr Slim indoor units
� Static pressure of up to 150Pa
� Outdoor unit size reduced by approx 33%, with height being reduced by 66% (compared to previous model)
Technical Information
Page 78
INDOOR UNIT PEA-RP200GA
Upper View >
Front View >
Side View >
INDOOR UNIT PEA-RP250GA
INDOOR UNIT PEA-RP400-500GA
Upper View >
Front View >
Side View >
Upper View >
Front View >
Side View >
Mr
Slim
Ran
ge 2
008
PEA
-RP-
GA
Pow
er In
vert
er H
eat
Pum
p
Dimensions
Page 79
PEA-RP-GA - INDOOR UNITSMODEL REFERENCECAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
EXTERNAL STATIC PRESSURE (Pa)
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
POWER INPUT (kW) (nominal)
(UK)
STARTING CURRENT (A)
RUNNING CURRENT (A) [Max]
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
INTERCONNECTING CABLE No. CORES
PEA-RP200GA
22.4 (9.5-25.0)
19.0 (9.0-22.4)
19.05 (8.1-21.25)
17.1 (8.3-21.15)
0.81
3.04 / 2.64
D / D
52-65
28.58 (1 1/8”)
9.52 (3/8”)
150
48-51
1400
634
400
70
380-415v, 50Hz
3
1.00
0.89
5.6
2.0 [2.4]
6
5
3
PEA-RP250GA
27.0 (12.5-31.5)
22.0 (11.2-28.0)
22.95 (10.65-26.8)
19.8 (10.3-25.2)
0.86
3.19 / 2.61
D / D
64-80
28.58 (1 1/8”)
12.7 (1/2”)
150
49-52
1600
634
400
77
380-415v, 50Hz
3
1.18
1.05
5.6
2.3 [2.8]
6
5
3
PUHZ-P200YHA
59 / 59
126
950
330+30
1350
380-415v, 50Hz
3
6.36 / 6.21
5.66 / 5.28
5
9.88 / 9.47 [19]
32
5
70
30
5.8
PUHZ-P250YHA
59 / 59
133
950
330+30
1350
330-415v, 50Hz
3
7.29 / 7.26
6.49 / 6.17
5
12.0 / 11.0 [21]
32
5
70
30
7.1
PEA-RP400GA
44.8 (19.0-50.0)
38.0 (18.0-44.8)
38.1 (16.15-42.5)
34.95 (16.55-41.2)
0.75
3.14 / 2.72
D / D
120
28.58 (1 1/8”) x2
9.52 (3/8”) x2
150
52
1947
764
595
130
380-415v, 50Hz
3
1.55
1.38
8.7
3.8 [4.6]
10
5
3
PEA-RP500GA
54.0 (25.0-63.0)
44.0 (22.4-56.0)
45.9 (21.25-53.55)
40.5 (20.6-51.5)
0.77
3.10 / 2.53
D / E
160
28.58 (1 1/8”) x2
12.7 (1/2”) x2
150
53
1947
764
595
133
380-415v, 50Hz
3
2.84
2.53
10
5.4 [ 6.5]
10
5
3
PUHZ-P200YHA x2
59 / 59
126
950
330+30
1350
380-415v, 50Hz
3
6.36 / 6.21
5.66 / 5.28
5
9.88 / 9.47 [19]
32
5
70 per outdoor
30
5.8
PUHZ-P250YHA x2
59 / 59
133
950
330+30
1350
330-415v, 50Hz
3
7.29 / 7.26
6.49 / 6.17
5
12.0 / 11.0 [21]
32
5
70 per outdoor
30
7.1
PUHZ-P-YHA - OUTDOOR UNITSMODEL REFERENCENOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
RUNNING CURRENT (A) [Max] Heating/Cooling
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Large Capacity Ceiling Concealed Ducted System
PEA-RP-GA Standard Inverter Heat Pump
� Twin, triple or quadruple configurations on one outdoor unit, utilising Mr Slim indoor units
� Static pressure of up to 150Pa
Technical Information
Page 80
The Standard Inverter range provides inverter solutions for customers who want all the benefits that inverters offer, but do not have the budget available for the more expensive Power Inverter range.
INDOOR UNIT PEA-RP200GA
Upper View >
Front View >
Side View >
INDOOR UNIT PEA-RP250GA
INDOOR UNIT PEA-RP400-500GA
Upper View >
Front View >
Side View >
Upper View >
Front View >
Side View >
Mr
Slim
Ran
ge 2
008
PEA
-RP-
GA
Stan
dard
Inve
rter
Hea
t Pu
mp
Dimensions
Page 81
600x600 4-Way Blow Ceiling Cassette System
SLZ-KA-VA - INDOOR UNITS
SLZ-KA-VA Inverter Heat Pump
The SLZ-KA-VA series is perfect for both residential andsmall business applications, as it offers inverter technologyalongside quiet operation. The compact size of this unit is ideal for 600 by 600mm ceilings and with a depth of208mm, this lightweight unit makes installation a breeze.This unit also comes complete with a long life filter that will last for approximately 2,500 hours.
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Mi-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi-Hi
DIMENSIONS (mm) (grille) Width
Depth
Height
WEIGHT (kg) Unit
Grille
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
SUZ-KA-VA - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) (Lo-Hi) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. CORES
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 7m
SLZ-KA25VA
3.0 (0.9-4.5)
2.5 (0.9-3.2)
2.5 (0.75-3.75)
2.5 (0.9-3.15)
0.86
3.61 / 3.62
A / A
8-9-10
9.52 (3/8”)
6.35 (1/4”)
28-31-37
570 (650)
570 (650)
208 (20)
16.5
3
Fed by Outdoor Unit
Single
6
4
SLZ-KA35VA
4.0 (0.9-5.0)
3.5 (1.0-3.9)
3.3 (0.75-4.15)
3.45 (1.0-3.85)
0.77
3.64 / 3.30
A / A
8-9-11
9.52 (3/8”)
6.35 (1/4”)
29-33-38
570 (650)
570 (650)
208 (20)
16.5
3
Fed by Outdoor Unit
Single
6
4
SLZ-KA50VA
5.0 (0.9-6.5)
4.6 (1.1-5.2)
4.15 (0.75-5.4)
4.55 (1.1-5.15)
0.68
3.23 / 2.82
C / C
8-9-11
12.7 (1/2”)
6.35 (1/4”)
30-34-39
570 (650)
570 (650)
208 (20)
16.5
3
Fed by Outdoor Unit
Single
6
4
SUZ-KA25VA
46 / 46
33
800
285
550
220-240v, 50Hz
0.83 / 0.69
0.76 / 0.55
3.65
4.0 / 3.4 [8.16]
16
3
20
12
0.9
SUZ-KA35VA
48 / 47
37
800
285
550
220-240v, 50Hz
1.10 / 1.06
1.00 / 0.85
4.75
5.15 / 4.95 [9.18]
16
3
20
12
1.05
SUZ-KA50VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
1.55 / 1.63
1.41 / 1.30
6.75
7.0 / 7.4 [16]
25
3
30
30
1.6
Technical InformationNote: Optional interfaces for M-NET connectivity (MAC-399IF) and group control, fault/run (MAC-397IF) are available. Please see accessories / optional extras section.
Page 82
Lower View >
INDOOR UNIT SLZ-KA25-50VA
Side View >
Mr
Slim
Ran
ge 2
008
SLZ
-KA
-VA
Inve
rter
Hea
t Pu
mp
Dimensions
Page 83
� Airflow controllable for ceiling heights up to 4.2m, with automatic adjustment of fan speed� Reduced draft air distribution, with independent vane control� Filter lowering operation down to 4m (optional PLP-6BAJ grille required)� Optional ‘I See Sensor' for energy saving and smooth temperature
control throughout the room
PLA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal) [3 Phase]
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
(Grille) Depth
Height
WEIGHT (kg) Unit
Panel
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
GRILLE REFERENCE
WIRED REMOTE CONTROLLER REFERENCE
PLA-RP140BA
16.0 (5.0-18.0)
14.0 (5.5-15.3)
13.6 (4.25-15.3)
12.6 (4.95-13.75)
0.71
3.61 / 3.01
A / B
24-26-29-32
15.88 (5/8”)
9.52 (3/8”)
36-39-42-44
840 (950)
840 (950)
298 (35)
27
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP125BA2
14.0 (5.0-16.0)
12.5 (5.5-14.0)
11.9 (4.25-13.6)
11.25 (4.95-12.6)
0.81
3.99/3.35 [3.92/3.30]
A / A
22-25-28-31
15.88 (5/8”)
9.52 (3/8”)
34-36-39-41
840 (950)
840 (950)
298 (35)
27
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP100BA2
11.2 (4.5-14.0)
10.0 (4.9-11.4)
9.5 (3.85-11.9)
9.0 (4.4-10.25)
0.79
4.41/4.10 [4.31/4.00]
A / A
20-23-26-30
15.88 (5/8”)
9.52 (3/8”)
32-34-37-40
840 (950)
840 (950)
298 (35)
27
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP71BA2
8.0 (3.5-10.2)
7.1 (3.3-8.1)
6.8 (3.0-8.65)
6.4 (2.95-7.3)
0.81
4.21 / 3.66
A / A
14-16-18-21
15.88 (5/8”)
9.52 (3/8”)
28-30-32-34
840 (950)
840 (950)
258 (35)
23
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP60BA
7.0 (2.8-8.2)
6.0 (2.7-6.7)
5.95 (2.4-6.95)
5.4 (2.45-6.05)
0.76
3.78 / 3.64
A / A
12-14-16-18
15.88 (5/8”)
9.52 (3/8”)
28-29-31-32
840 (950)
840 (950)
258 (35)
23
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP50BA
6.0 (2.5-7.3)
5.0 (2.3-5.6)
5.1 (2.15-6.2)
4.5 (2.05-5.05)
0.81
3.61 / 3.23
A / A
12-14-16-18
12.7 (1/2”)
6.35 (1/4”)
28-29-31-32
840 (950)
840 (950)
258 (35)
22
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP35BA
4.1 (1.6-5.2)
3.6 (1.6-4.5)
3.5 (1.35-4.4)
3.25 (1.45-4.05)
0.84
3.66 / 3.36
A / A
11-12-13-15
12.7 (1/2”)
6.35 (1/4”)
27-28-29-31
840 (950)
840 (950)
258 (35)
22
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PUHZ-RP35VHA3
46 / 44
42
800
300 + 23
600
220-240v, 50Hz
Single
1.12 / 1.07
1.00 / 0.91
5
4.37 / 4.23 [13]
-
16
3
50
30
2.5
PUHZ-RP50VHA3
46 / 44
42
800
300 + 23
600
220-240v, 50Hz
Single
1.66 / 1.55
1.48 / 1.32
5
6.76 / 6.52 [13]
-
16
3
50
30
2.5
PUHZ-RP60VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
1.85 / 1.65
1.65 / 1.40
5
7.79 / 6.97 [19]
-
25
3
50
30
3.5
PUHZ-RP71VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
1.90 / 1.94
1.69 / 1.65
5
10.17 / 8.55 [19]
-
25
3
50
30
3.5
PUHZ-RP100VHA3/YHA3
51 / 49
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
2.54/2.44 [2.60/2.50]
2.26/2.07 [2.31/2.13]
5
13.26 / 13.47 [28]
4.90 / 5.02 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP125VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
3.51/3.73[3.57/3.79]
3.12/3.17 [3.18/3.22]
5
16.92 / 16.53 [28]
6.14 / 6.04 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP140VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
4.43 / 4.65
3.94 / 3.95
5
20.92 / 20.72 [29.5]
7.37 / 7.53 [13]
40 / 16
3 / 5
75
30
5.0
PUHZ-RP - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
[3 Phase] Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) Single Phase
Heating/Cooling [MAX] 3 Phase
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
4-Way Blow Ceiling Cassette System
PLA-RP Power Inverter Heat Pump
Technical Information
Page 84
INDOOR UNIT PLA-RP35-140BA(2)
Models A B
Size 35-71 241 258
Size 100-140 281 298
Upper View >
Lower View >
Side View >
Mr
Slim
Ran
ge 2
008
PLA
-RP
Pow
er In
vert
er H
eat
Pum
p
Dimensions
Page 85
SUZ-KA35VA
48 / 47
37
800
285
550
220-240v, 50Hz
Single
1.11 / 1.09
1.01 / 0.87
4.75
4.89 / 4.77 [9.18]
16
3
20
12
1.05
SUZ-KA50VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
Single
1.82 / 1.78
1.62 / 1.42
6.75
6.64 / 7.11 [16]
25
3
30
30
1.6
SUZ-KA60VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
Single
2.11 / 1.94
1.92 / 1.55
9.75
10.04 / 8.71 [16]
25
3
30
30
1.8
SUZ-KA71VA
53-55 / 51-53
58
840
330
850
220-240v, 50Hz
Single
2.49 / 2.53
2.27 / 2.02
10.3
10.33 / 10.81 [16]
25
3
30
30
2.0
PUHZ-P100VHA2
54 / 50
75
950
330 + 30
943
220-240v, 50Hz
Single
3.28 / 3.12
2.92 / 2.65
4
13.49 / 13.20 [28]
32
3
50
30
2.7
PUHZ-P125VHA2
55 / 51
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.11 / 4.09
3.66 / 3.48
14
17.68 / 18.37 [28]
32
3
50
30
4.5
PUHZ-P140VHA2
56 / 52
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.98 / 5.21
4.43 / 4.43
14
22.31 / 23.55 [29.5]
40
3
50
30
4.5
SUZ-KA / PUHZ-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) (Lo-Hi) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg)
Notes: All units charged to 7m (35-71), 20m (100) and 30m (125-140) pipe length.
PLA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
(Grille) Depth
Height
WEIGHT (kg) Unit
Panel
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
GRILLE REFERENCE
WIRED REMOTE CONTROLLER REFERENCE
PLA-RP140BA
16.0 (5.0-18.0)
13.6 (5.5-15.0)
13.6 (4.25-15.3)
12.25 (4.95-13.5)
0.71
3.21 / 2.61
C / D
24-26-29-32
15.88 (5/8”)
9.52 (3/8”)
36-39-42-44
840 (950)
840 (950)
298 (35)
27
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP125BA
14.0 (5.0-16.0)
12.3 (5.5-14.0)
11.9 (4.25-13.6)
11.05 (4.95-12.6)
0.71
3.41 / 3.01
B / B
22-25-28-31
15.88 (5/8”)
9.52 (3/8”)
34-36-39-41
840 (950)
840 (950)
298 (35)
25
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP100BA
11.2 (4.5-12.5)
9.4 (4.9-11.2)
9.5 (3.85-10.65)
8.45 (4.4-10.1)
0.74
3.41 / 3.01
B / B
20-23-26-30
15.88 (5/8”)
9.52 (3/8”)
32-34-37-40
840 (950)
840 (950)
298 (35)
25
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP71BA
8.0 (0.9-10.2)
7.1 (0.9-8.1)
6.65 (0.75-8.5)
7.05 (0.9-8.05)
0.73
3.21 / 2.81
C / C
14-16-18-21
15.88 (5/8”)
9.52 (3/8”)
28-30-32-34
840 (950)
840 (950)
258 (35)
23
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP60BA
6.9 (0.9-8.0)
5.7 (1.1-6.3)
5.75 (0.75-6.65)
5.65 (1.1-6.25)
0.76
3.27 / 2.94
C / C
12-14-16-18
15.88 (5/8”)
6.35 (1/4”)
28-29-31-32
840 (950)
840 (950)
258 (35)
23
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP50BA
6.0 (0.9-7.2)
5.0 (1.1-5.6)
5.0 (0.75-6.0)
4.95 (1.1-5.55)
0.81
3.30 / 2.81
C / C
12-14-16-18
12.7 (1/2”)
6.35 (1/4”)
28-29-31-32
840 (950)
840 (950)
258 (35)
22
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP35BA
4.1 (0.9-5.0)
3.5 (1.0-3.9)
3.4 (0.75-4.15)
3.45 (1.0-3.85)
0.84
3.69 / 3.21
A / A
11-12-13-15
9.52 (3/8”)
6.35 (1/4”)
27-28-29-31
840 (950)
840 (950)
258 (35)
22
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
4-Way Blow Ceiling Cassette System
PLA-RP Standard Inverter Heat Pump
The new Standard Inverter range provides inverter solutions for customers who want all the benefits that inverters offer, but do not have the budget available for the more expensive Power Inverter range.
� Airflow controllable for ceiling heights up to 4.2m, with automatic adjustment of fan speed
� Reduced draft air distribution, with independent vane control
� Filter lowering operation down to 4m(optional PLP-6BAJ grille required)
� Optional ‘I See Sensor’ for energy saving andsmooth temperature control throughout the room
Technical Information
Page 86
INDOOR UNIT PLA-RP35-140BA
Models A B
Size 35-71 241 258
Size 100-140 281 298
Upper View >
Lower View >
Side View >
Mr
Slim
Ran
ge 2
008
PLA
-RP
Stan
dard
Inve
rter
Hea
t Pu
mp
Dimensions
Page 87
PLA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) (grille) Width
Depth
Height
WEIGHT (kg) Unit
Panel
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
GRILLE REFERENCE
WIRED REMOTE CONTROLLER REFERENCE
PLA-RP100BA
11.5
10.0
9.8
9.0
0.74
20-23-26-30
15.88 (5/8”)
9.52 (3/8”)
32-34-37-40
840 (950)
840 (950)
298 (35)
25
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP125BA
14.3
12.3
12.15
11.05
0.71
22-25-28-31
15.88 (5/8”)
9.52 (3/8”)
34-36-39-41
840 (950)
840 (950)
298 (35)
25
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
PLA-RP140BA
17.0
14.2
14.45
12.8
0.71
24-26-29-32
15.88 (5/8”)
9.52 (3/8”)
36-39-42-44
840 (950)
840 (950)
298 (35)
27
6
Fed by Outdoor Unit
Single
6
4
PLP-6BA
PAR-21MAA
4-Way Blow Ceiling Cassette System
PLA-RP Heat Pump
PUH-P100YHA
52 / 50
94
950
330 + 30
943
380-415,50Hz
3
3.40 / 3.53
3.03 / 3.00
45
6.05 / 6.33 [12.2]
20
5
50
50
4.4
PUH-P125YHA
52 / 50
131
950
330 + 30
1350
380-415v, 50Hz
3
4.23 / 4.36
3.76 / 3.71
70
7.51 / 7.79 [16.1]
20
5
50
50
5.0
PUH-P140YHA
53 / 51
131
950
330 + 30
1350
380-415v, 50Hz
3
5.35 / 5.41
4.76 / 4.60
85
9.45 / 9.62 [19.8]
25
5
50
50
5.0
PUH-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Notes: Optional infra-red grille and remote controller available.
Technical Information
� Airflow controllable for ceiling heights up to 4.2m, with automatic adjustment of fan speed
� Reduced draft air distribution, with independent vane control
� Filter lowering operation down to 4m (optional PLP-6BAJ grille required)
� Optional ‘I See Sensor' for energy saving and smooth temperature control throughout the room
The Heat Pump system provides a low cost alternative to three phase Power Inverter systems.
Page 88
INDOOR UNIT PLA-RP100-140BA
Models A B
Size 35-71 241 258
Size 100-140 281 298
Upper View >
Lower View >
Side View >
Mr
Slim
Ran
ge 2
008
PLA
-RP
Hea
t Pu
mp
Dimensions
Page 89
PCA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PCA-RP140GA
16.0 (5.0-18.0)
14.0 (5.5-15.3)
13.6 (4.25-15.3)
12.6 (4.95-13.75)
0.75
3.48 / 3.01
B / B
27-30-32-34
15.88 (5/8”)
9.52 (3/8”)
42-44-46-48
1620
680
270
45
Fed by Outdoor Unit
Single
6
4
PCA-RP125GA
14.0 (5.0-16.0)
12.5 (5.5-14.0)
11.9 (4.25-13.6)
11.25 (4.95-12.6)
0.77
3.41 / 3.22
B / A
27-30-32-34
15.88 (5/8”)
9.52 (3/8”)
41-43-45-46
1620
680
270
43
Fed by Outdoor Unit
Single
6
4
PCA-RP100GA
11.2 (4.5-14.0)
10.0 (4.9-11.4)
9.5 (3.85-11.9)
9.0 (4.4-10.25)
0.75
3.44 / 3.42
B / A
20-21-23-25
15.88 (5/8”)
9.52 (3/8”)
40-41-43-45
1310
680
270
37
Fed by Outdoor Unit
Single
6
4
PCA-RP71GA
7.6 (3.5-10.2)
7.1 (3.3-8.1)
6.45 (3.0-8.65)
6.4 (2.95-7.3)
0.74
3.41 / 3.32
B / A
14-15-16-18
15.88 (5/8”)
9.52 (3/8”)
37-39-41-43
1310
680
210
34
Fed by Outdoor Unit
Single
6
4
PCA-RP60GA
7.0 (2.8-8.2)
6.0 (2.7-6.7)
5.95 (2.4-6.95)
5.4 (2.45-6.05)
0.86
3.45 / 3.68
B / A
14-15-16-18
15.88 (5/8”)
9.52 (3/8”)
37-39-41-43
1310
680
210
34
Fed by Outdoor Unit
Single
6
4
PCA-RP50GA2
6.0 (2.5-7.3)
5.0 (2.3-5.6)
5.1 (2.15-6.2)
4.5 (2.05-5.05)
0.88
3.41 / 3.01
B / B
14-15-16-18
12.7 (1/2”)
6.35 (1/4”)
37-39-41-43
1310
680
210
34
Fed by Outdoor Unit
Single
6
4
Ceiling Suspended System
PCA-RP Power Inverter Heat Pump
� Indoor unit designed for direct ceiling suspension
� Flush to wall installation for concealmentof service connections
� Electronic control includes learning defrost, fault finding diagnostics, low ambient fan speed control and anti-phase/ single phase protection
PUHZ-RP50VHA3
46 / 44
42
800
300 + 23
600
220-240v, 50Hz
Single
1.76 / 1.66
1.57 / 1.41
5
7.0 / 6.69 [13]
-
16
3
50
30
2.5
PUHZ-RP60VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
2.03 / 1.63
1.81 / 1.39
5
8.03 / 7.14 [19]
-
25
3
50
30
3.5
PUHZ-RP71VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
2.23 / 2.14
1.98 / 1.82
5
10.27 / 8.57 [19]
-
25
3
50
30
3.5
PUHZ-RP100VHA3/YHA3
51 / 49
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
3.26 / 2.92
2.90 / 2.48
5
13.08 / 13.22 [28]
4.72 / 4.77 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP125VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
4.11 / 3.88
3.66 / 3.30
5
16.99 / 16.54 [28]
6.21 / 6.05 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP140VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415,50Hz
Single / 3
4.60 / 4.65
4.09 / 3.95
5
20.93 / 20.66 [29.5]
7.47 / 7.38 [13]
40 / 16
3 / 5
75
30
5.0
PUHZ-RP - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) Single Phase
Heating/Cooling [MAX] 3 Phase
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Technical Information
Page 90
INDOOR UNIT PCA-RP50-71GA(2)
INDOOR UNIT PCA-RP100GA
INDOOR UNIT PCA-RP125-140GA
Side View >Front View >Lower View >
Side View >Front View >Lower View >
Side View >Front View >Lower View >
Mr
Slim
Ran
ge 2
008
PCA
-RP
Pow
er In
vert
er H
eat
Pum
p
Dimensions
Page 91
SUZ-KA50VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
Single
1.76 / 1.78
1.60 / 1.42
6.75
6.88 / 7.28 [16]
25
3
30
30
1.6
SUZ-KA60VA
53-55 / 51-53
53
840
330
850
220-240v, 50Hz
Single
2.05 / 1.92
1.87 / 1.54
9.75
10.28 / 8.88 [16]
25
3
30
30
1.8
SUZ-KA71VA
53-55 / 51-53
58
840
330
850
220-240v, 50Hz
Single
2.49 / 2.53
2.27 / 2.02
10.3
10.43 / 10.83 [16]
25
3
30
30
2.0
PUHZ-P100VHA2
54 / 50
75
950
330 + 30
943
220-240v, 50Hz
Single
3.49 / 3.35
3.11 / 2.85
4
13.31 / 12.95 [28]
32
3
50
30
2.7
PUHZ-P125VHA2
55 / 51
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.98 / 4.38
4.43 / 3.72
14
17.75 / 18.38 [28]
32
3
50
30
4.5
PUHZ-P140VHA2
56 / 52
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.98 / 5.21
4.43 / 4.43
14
22.32 / 23.49 [29.5]
40
3
50
30
4.5
SUZ-KA / PUHZ-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) (Lo-Hi) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg)
Notes: All units charged to 7m (50-71), 20m (100) and 30m (125-140) pipe length.
PCA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PCA-RP140GA
16.0 (5.0-18.0)
13.6 (5.5-15.0)
13.6 (4.25-15.3)
12.25 (4.95-13.5)
0.76
3.21 / 2.61
C / D
27-30-32-34
15.88 (5/8”)
9.52 (3/8”)
42-44-46-48
1620
680
270
45
Fed by Outdoor Unit
Single
6
4
PCA-RP125GA
14.0 (5.0-16.0)
12.3 (5.5-14.0)
11.9 (4.25-13.6)
11.05 (4.95-12.6)
0.78
2.81 / 2.81
D / C
27-30-32-34
15.88 (5/8”)
9.52 (3/8”)
41-43-45-46
1620
680
270
43
Fed by Outdoor Unit
Single
6
4
PCA-RP100GA
11.2 (4.5-12.5)
9.4 (4.9-11.2)
9.5 (3.85-10.65)
8.45 (4.4-10.1)
0.77
3.21 / 2.81
C / C
20-21-23-25
15.88 (5/8”)
9.52 (3/8”)
40-41-43-45
1310
680
270
37
Fed by Outdoor Unit
Single
6
4
PCA-RP71GA
8.0 (0.9-10.2)
7.1 (0.9-8.1)
6.65 (0.75-8.5)
7.05 (0.9-8.05)
0.71
3.21 / 2.81
C / C
14-15-16-18
15.88 (5/8”)
9.52 (3/8”)
37-39-41-43
1310
680
210
34
Fed by Outdoor Unit
Single
6
4
PCA-RP60GA
6.9 (0.9-8.0)
5.5 (1.1-6.3)
5.75 (0.75-6.65)
5.45 (1.1-6.25)
0.79
3.37 / 2.86
C / C
14-15-16-18
15.88 (5/8”)
6.35 (1/4”)
37-39-41-43
1310
680
210
34
Fed by Outdoor Unit
Single
6
4
PCA-RP50GA2
6.0 (0.9-7.2)
5.0 (1.1-5.6)
5.0 (0.75-6.0)
4.95 (1.1-5.55)
0.81
3.41 / 2.81
B / C
14-15-16-18
12.7 (1/2”)
6.35 (1/4”)
37-39-41-43
1310
680
210
34
Fed by Outdoor Unit
Single
6
4
Ceiling Suspended System
PCA-RP Standard Inverter Heat Pump
The new Standard Inverter range provides inverter solutions for customers who want all the benefits thatinverters offer, but do not have the budget available for the more expensive Power Inverter range.
Technical Information
� Indoor unit designed for direct ceiling suspension
� Flush to wall installation for concealmentof service connections
� Electronic control includes learning defrost, fault finding diagnostics, low ambient fan speed control and anti-phase / single phase protection
Page 92
INDOOR UNIT PCA-RP50-71GA(2)
INDOOR UNIT PCA-RP100GA
INDOOR UNIT PCA-RP125-140GA
Side View >Front View >Lower View >
Side View >Front View >Lower View >
Side View >Front View >Lower View >
Mr
Slim
Ran
ge 2
008
PCA
-RP
Stan
dard
Inve
rter
Hea
t Pu
mp
Dimensions
Page 93
PCA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Mi1-Mi2-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PCA-RP100GA
11.5
9.8
9.8
8.8
0.75
20-21-23-25
15.88 (5/8”)
9.52 (3/8”)
40-41-43-45
1310
680
270
37
Fed by Outdoor Unit
Single
6
4
PCA-RP125GA
14.3
12.3
12.15
11.05
0.77
27-30-32-34
15.88 (5/8”)
9.52 (3/8”)
41-43-45-46
1620
680
270
43
Fed by Outdoor Unit
Single
6
4
PCA-RP140GA
17.0
14.2
14.45
12.8
0.75
27-30-32-34
15.88 (5/8”)
9.52 (3/8”)
42-44-46-48
1620
680
270
45
Fed by Outdoor Unit
Single
6
4
Ceiling Suspended System
PCA-RP Heat Pump
PUH-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (kW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
PUH-P100YHA
52 / 50
94
950
330 + 30
943
380-415v, 50Hz
3
3.45 / 3.55
3.07 / 3.02
45
5.87 / 6.08 [12.0]
20
5
50
50
4.4
PUH-P125YHA
52 / 50
131
950
330 + 30
1350
380-415v, 50Hz
3
4.72 / 4.52
4.20 / 3.84
70
7.58 / 7.8 [16.2]
20
5
50
50
5.0
PUH-P140YHA
53 / 51
131
950
330 + 30
1350
380-415v, 50Hz
3
5.22 / 5.44
4.65 / 4.62
85
9.46 / 9.56 [19.8]
25
5
50
50
5.0
Technical Information
� Indoor unit designed for direct ceiling suspension
� Flush to wall installation for concealment of service connections
� Electronic control includes learning defrost, fault finding diagnostics, low ambient fan speed control and anti-phase / single phase protection
The Heat Pump system provides a low cost alternative to three phase Power Inverter systems.
Page 94
INDOOR UNIT PCA-RP100GA
INDOOR UNIT PCA-RP125-140GA
Side View >Front View >
Lower View >
Side View >Front View >
Lower View >
Mr
Slim
Ran
ge 2
008
PCA
-RP
Hea
t Pu
mp
Dimensions
Page 95
PCA-RP71HA
7.6 (3.5-10.2)
7.1 (3.3-8.1)
6.45 (3.0-8.65)
6.4 (2.95-7.3)
0.74
3.41 / 3.21
B / A
17-19
15.88 (5/8”)
9.52 (3/8”)
34-38
1136
650
280
41
Fed by Outdoor Unit
Single
6
4
PCA-RP125HA
13.8 (5.0-16.0)
12.5 (5.5-14.0)
11.75 (4.25-13.6)
11.25 (4.95-12.6)
0.77
3.41 / 3.22
B / A
30-38
15.88 (5/8”)
9.52 (3/8”)
44-50
1520
650
280
56
Fed by Outdoor Unit
Single
6
4
PCA-RP-HA - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
Stainless Steel Ceiling Suspended System
PCA-RP-HA Power Inverter Heat Pump
PUHZ-RP71VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
2.23 / 2.21
1.98 / 1.88
5
10.17 / 8.47 [19]
-
25
3
50
30
3.5
PUHZ-RP125VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415v, 50Hz
Single / 3
4.05 / 3.88
3.60 / 3.30
5
17.17 / 16.72 [28]
6.39 / 6.23 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (KW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) Single Phase
Heating/Cooling [MAX] 3 Phase
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
The PCA-RP-HA series is a ceiling suspended unit ideal for use in kitchen environments. The external casing is made of durable stainless steel that is resistant to oil and smoke, ensuring that the unit can be easily cleaned at all times.
� High performance oil mist filter
� Easy maintenance - fan casing can be separated into different sections allowing easy cleaning. The drain pan can also be cleaned easily on-site as the pipe connector can be quickly removed
� Optional decoration covers
Technical Information
Page 96
INDOOR UNIT PCA-RP71HA
INDOOR UNIT PCA-RP125HA
Front View >
Side View >
Lower View >
12241180
9861136
110
102
75
1136
650
258
650
280
1608
13701520
110
102
75
1564
1520
650
258
650
280
Side View >
Front View >
Lower View >
Mr
Slim
Ran
ge 2
008
PCA
-RP-
HA
Pow
er In
vert
er H
eat
Pum
p
Dimensions
Page 97
PCA-RP125HA
13.8 (5.0-16.0)
12.3 (5.5-14.0)
11.75 (4.25-13.6)
11.05 (4.95-12.6)
0.78
3.21 / 2.81
C / C
30-38
15.88 (5/8”)
9.52 (3/8”)
44-50
1520
650
280
56
Fed by Outdoor Unit
Single
6
4
PCA-RP-HA - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
Stainless Steel Ceiling Suspended System
PCA-RP-HA Standard Inverter Heat Pump
PUHZ-P125VHA2
55 / 51
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.30 / 4.38
3.83 / 3.72
14
17.93 / 18.56 [28]
32
3
50
30
4.5
PUHZ-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (KW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
The new Standard Inverter range provides inverter solutions for customers who want all the benefits that inverters offer, but do not have the budget available for the more expensive Power Inverter range.
� High performance oil mist filter
� Easy maintenance - fan casing can be separated into different sections allowing easy cleaning. The drain pan can also be cleaned easily on-site as the pipe connector can be quickly removed
� Optional decoration covers
Technical Information
Page 98
INDOOR UNIT PCA-RP125HA
1608
13701520
110
102
75
1564
1520
650
258
650
280
Side View >
Front View >
Lower View >
Mr
Slim
Ran
ge 2
008
PCA
-RP-
HA
Stan
dard
Inve
rter
Hea
t Pu
mp
Dimensions
Page 99
PCA-RP125HA
14.3
12.3
12.2
11.05
0.77
30-38
15.88 (5/8”)
9.52 (3/8”)
44-50
1520
650
280
56
Fed by Outdoor Unit
Single
6
4
PCA-RP-HA - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
Stainless Steel Ceiling Suspended System
PCA-RP-HA Heat Pump
PUH-P125YHA
52 / 50
131
950
330 + 30
1350
380-415v, 50Hz
3
5.01 / 4.55
4.46 / 3.87
70
7.76 / 7.98 [16.3]
20
5
50
50
5.0
PUH-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (KW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
The PCA-RP-HA series is a ceiling suspended unit ideal for use in kitchen environments. The external casing is made of durable stainless steel that is resistant to oil and smoke, ensuring that the unit can be easily cleaned at all times.
� High performance oil mist filter
� Easy maintenance - fan casing can be separated into different sections allowing easy cleaning. The drain pan can also be cleaned easily on-site as the pipe connector can be quickly removed
� Optional decoration covers
Technical Information
The Heat Pump system provides a low cost alternative to three phase Power Inverter systems.
Page 100
INDOOR UNIT PCA-RP125HA
1608
13701520
110
102
75
1564
1520
650
258
650
280
Side View >
Front View >
Lower View > Mr
Slim
Ran
ge 2
008
PCA
-RP-
HA
Hea
t Pu
mp
Dimensions
Page 101
PSA-RP71GA
7.6 (3.5-10.2)
7.1 (3.3-8.1)
6.45 (3.0-8.65)
6.4 (2.95-7.3)
0.73
3.41 / 3.23
B / A
15-18
15.88 (5/8”)
9.52 (3/8”)
40-45
600
270
1900
43
Fed by Outdoor Unit
Single
6
4
PSA-RP125GA
14.0 (5.0-16.0)
12.4 (5.5-14.0)
11.9 (4.25-13.6)
11.15 (4.95-12.6)
0.75
3.41 / 3.01
B / B
26-33
15.88 (5/8”)
9.52 (3/8”)
46-51
600
350
1900
51
Fed by Outdoor Unit
Single
6
4
PSA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
Floor Standing System
PSA-RP Power Inverter Heat Pump
PUHZ-RP71VHA3
48 / 47
68
950
330 + 30
943
220-240v, 50Hz
Single
2.23 / 2.20
1.98 / 1.87
5
10.4 / 8.7 [19]
-
25
3
50
30
3.5
PUHZ-RP125VHA2/YHA2
52 / 50
116 / 130
950
330 + 30
1350
220-240v, 50Hz / 380-415v, 50Hz
Single / 3
4.11 / 4.12
3.66 / 3.50
5
17.21 / 16.76 [28]
6.43 / 6.27 [13]
32 / 16
3 / 5
75
30
5.0
PUHZ-RP - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (KW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) Single Phase
Heating/Cooling [MAX] 3 Phase
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Technical InformationNote: When used with a Mr Slim Multi-Split system. PSA-RP cannot be connected with indoor units of different type.
The PSA-RP Floor Standing System compliments the MitsubishiElectric range of indoor units. The sleek, modern design of this unitis ideal for numerous applications including bars and restaurants.
� Built in controller
Page 102
INDOOR UNIT PSA-RP71GA
INDOOR UNIT PSA-RP125GA
Front View > Side View > Upper View >
Front View > Side View > Upper View >
Mr
Slim
Ran
ge 2
008
PSA
-RP
Pow
er In
vert
er H
eat
Pum
p
Dimensions
Page 103
PSA-RP125GA
14.0 (5.0-16.0)
12.3 (5.5-14.0)
11.9 (4.25-13.6)
11.05 (4.95-12.6)
0.76
2.81 / 2.81
D / C
26-33
15.88 (5/8”)
9.52 (3/8”)
46-51
600
350
1900
51
Fed by Outdoor Unit
Single
6
4
PSA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
COP / EER (nominal)
ENERGY LABEL Heating/Cooling
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PSA-RP Standard Inverter Heat Pump
PUHZ-P125VHA2
55 / 51
99
950
330 + 30
1350
220-240v, 50Hz
Single
4.98 / 4.38
4.43 / 3.72
14
17.97 / 18.6 [28]
32
3
50
30
4.5
PUHZ-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (KW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Floor Standing System
Technical Information
The Standard Inverter range provides inverter solutions for customerswho want all the benefits that inverters offer, but do not have the budgetavailable for the more expensive Power Inverter range.
The PSA-RP Floor Standing System compliments the Mitsubishi Electricrange of indoor units. The sleek, modern design of this unit is ideal for numerous applications including bars and restaurants.
� Built in controller
Note: When used with a Mr Slim Multi-Split system. PSA-RP cannot be connected with indoor units of different type.
Page 104
INDOOR UNIT PSA-RP125GA
Front View > Side View > Upper View >
Mr
Slim
Ran
ge 2
008
PSA
-RP
Stan
dard
Inve
rter
Hea
t Pu
mp
Dimensions
Page 105
PSA-RP125GA
14.3
12.3
12.2
11.05
0.75
26-33
15.88 (5/8”)
9.52 (3/8”)
46-51
600
350
1900
51
Fed by Outdoor Unit
Single
6
4
PSA-RP - INDOOR UNITSMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF (nominal)
AIRFLOW (m3/min) Lo-Hi
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Lo-Hi
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
ELECTRICAL SUPPLY
PHASE
FUSE RATING (BS88) - HRC (A)
INTERCONNECTING CABLE No. CORES
PSA-RP Heat Pump
PUH-P125YHA
52 / 50
131
950
330 + 30
1350
380-415v, 50Hz
3
4.41 / 4.54
3.92 / 3.86
70
7.8 / 8.02 [16.4]
20
5
50
50
5.0
PUH-P - OUTDOOR UNITSMODEL REFERENCE
NOISE (dBA) Heating/cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
SYSTEM POWER INPUT (KW) Heating/Cooling (nominal)
Heating/Cooling (UK)
STARTING CURRENT (A)
SYSTEM RUNNING CURRENT (A) [MAX] Heating/Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
MAX PIPE LENGTH (m)
MAX HEIGHT DIFFERENCE (m)
CHARGE R410A (kg) - 30m
Floor Standing System
Technical Information
The Heat Pump system provides a low cost alternative to three phase Power Inverter systems.
The PSA-RP Floor Standing System compliments the Mitsubishi Electric range of indoor units. The sleek, modern design of this unit is ideal for numerous applications including bars and restaurants.
� Built in controller
Note: When used with a Mr Slim Multi-Split system. PSA-RP cannot be connected with indoor units of different type.
Page 106
INDOOR UNIT PSA-RP125GA
Front View > Side View > Upper View >
Mr
Slim
Ran
ge 2
008Dimensions
PSA
-RP
Hea
t Pu
mp
Page 107
PHV DXE Heat Pump Air CurtainHeat Pump Air Curtain System
In collaboration with Thermoscreens, Mitsubishi Electric have developed a range of air cur tains that are able tobe connected to our Power Inver ter heat pumps, as opposed to the more traditional direct electric methodassociated with air cur tains.
� Reduced CO2 emissions (up to 67%)
� Reduced Running Costs (up to 67%)
� 2.5 year payback period against equivalent Electric system
� Inverter technology (does not waste energy)
� Range of different sizes to suit every application
� Allows open door policy in retail outletswhilst being energy efficient
� Clean environment - protection from dust, fumes etc
� Comfortable climate for customers
� Easy to install and maintain
Page 108
PHV DXE - RECESSEDMODEL REFERENCE
DIMENSIONS (mm) (WxDxH)
SUPPLY (50Hz)
HEAT OUTPUT (kW) 100% / 50%
COP 100% / 50%
LOADING (amps)
VELOCITY (m/s)
AIR VOLUME (m3/h)
WEIGHT (kg)
dB(A) @ 3m 100% / 50%
MAX. MOUNTING HEIGHT (m)
OUTDOOR UNIT MODEL
PHV1500R DXE HO
1650x436x296
415V*1
14.4 / 8.3
2.5 / 3.7
12.7*1
9
2600
67
60 / 58
3.5
PUHZ-RP140VHA2/YHA2
PHV2000R DXE LO
2240x436x296
415V*2
14.1 / 7.9
2.9 / 3.7
15.7*2
9.5
3300
85
61 / 59
3.5
PUHZ-RP100VHA3/YHA3
PHV2000R DXE HO
2240x436x296
415V*2
21.3 / 11.2
2.4 / 3.2
15.7*2
9
3130
88
61 / 59
3.5
PUHZ-RP200YHA2
Technical Information
Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load *2 for units with electric heaters disabled, 240v power supply 2.7 amp load.
PHV DXE - FREE STANDINGMODEL REFERENCE
DIMENSIONS (mm) (WxDxH)
SUPPLY (50Hz)
HEAT OUTPUT (kW) 100% / 50%
COP 100% / 50%
LOADING (amps)
VELOCITY (m/s)
AIR VOLUME (m3/h)
WEIGHT (kg)
dB(A) @ 3m 100% / 50%
MAX. MOUNTING HEIGHT (m)
OUTDOOR UNIT MODEL
PHV1500 DXE HO
1746x377x255
415V*1
14.4 / 8.3
2.5 / 3.7
12.7*1
9
2600
60
60 / 58
3.75
PUHZ-RP140VHA2/YHA2
PHV2000 DXE LO
2296x377x255
415V*2
14.1 / 7.9
2.9 / 3.7
15.7*2
9.5
3300
78
61 / 59
3.75
PUHZ-RP100VHA3/YHA3
PHV2000 DXE HO
2296x377x255
415V*2
21.3 / 11.2
2.4 / 3.2
15.7*2
9.5
3130
80
61 / 59
3.75
PUHZ-RP200YHA2
Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load *2 for units with electric heaters disabled, 240v power supply 2.7 amp load.
HEAT PUMP OUTDOOR UNITSMODEL REFERENCE
DIMENSIONS (mm) (WxDxH)
SUPPLY (50Hz)
MAX. CURRENT (A)
FUSE SIZE HRC (BS88)
MAX. PIPE RUN Length (m)
Height (m)
PIPE SIZES Gas mm(in)
Liquid mm(in)
INTERCONNECTING CABLE
PUHZ-RP100VHA3/YHA3
950x330+30x1350
230V / 415V
28 / 13
32 / 16
50
30
15.88 (5/8)
9.52 (3/8)
2 core
PUHZ-RP140VHA2/YHA2
950x330+30x1350
230V / 415V
29.5 / 13
40 / 16
50
30
15.88 (5/8)
9.52 (3/8)
2 core
PUHZ-RP200YHA2
950x330+30x1350
415V
19
25
100
30
28.58 (1 1/8)
9.52 (3/8)
2 core
AIR CURTAIN PHV1500/2000R DXE
Mr
Slim
Ran
ge 2
008Dimensions
PHV
DX
EA
ir C
urta
in
AIR CURTAIN PHV1500/2000 DXE
Rear View >
Upper View >
Side View > Rear View >
Page 109
Side View >
Upper View >
Heat Pump
Mr Slim Multi-Split Systems
IndoorUnits
Indoor Units
Outdoor UnitsOutdoor Units
Multi distributorPipes
Multi distributorPipes
BB
C
CD
h h
HH
Indoor Units
OutdoorUnits
Multi distributorPipes
CD
E
B
A
h
H
AA
QUADRUPLETRIPLETWIN
≥
PIPE RUN PARAMETERS
Outdoor Model Pipe Runs Max. Pipe Run (m)
PUH-P100-140YHA A+B+C twin 50
PUH-P100-140YHA A+B+C+D triple 50
PUH-P100-140YHA B – C or C – D or B – D 8
PUHZ-P100-140VHA2 A+B+C twin 50
PUHZ-P200/250YHA A+B+C twin 70
PUHZ-RP71VHA3 A+B+C twin 50
PUHZ-RP100-140V/YHA2/3 A+B+C twin 75
PUHZ-RP200/250YHA2 A+B+C twin 80 (120)
PUHZ-P140VHA2 A+B+C+D triple 50
PUHZ-P200/250YHA A+B+C+D triple 70
PUHZ-RP140V/YHA2 A+B+C+D triple 75
PUHZ-RP200/250YHA2 A+B+C+D triple 80 (120)
PUHZ-P200/250YHA A+B+C+D+E quadruple 70
PUHZ-RP200/250YHA2 A+B+C+D+E quadruple 80 (120)
PUHZ-P100-140VHA2 B – C or C – D or B – D 8
PUHZ-RP71-140V/YHA2/3 B – C or C – D or B – D 8
PUHZ-P200/250YHA B - C or B - D or B - E or C - D or C - E or D - E 8
PUHZ-RP200/250YHA2 B - C or B - D or B - E or C - D or C - E or D - E 8
H = 30m. h = 1m. Note: H for the PUHZ-RP200/250YHA2 = 40m
The multi-split system is an ideal option for open plan spaces in medium sized premises such as offices or shops, where two,three or four units are required. These can be Mr Slim ceiling cassettes (PLA-RP), ceiling suspended (PCA-RP), ducted (PEAD-RP), floor standing (PSA-RP) or wall mounted (PKA-RP) models and can be connected to a single outdoor unit usingtwin, triple or quadruple multi distributor pipes.
� Twin, triple or quadruple indoor heat pump units can be operated inMulti-Split configuration from a single outdoor unit
� Heat pumps must operate in same heating or cooling mode
� Cooling capacity range 3.3 to 28kW
� Heating capacity range 3.5 to 31.5kW
Note: SEZ or SLZ units cannot be used as part of a Mr Slim Multi-Split system. PSA-RP cannot be connected with indoor units of different type. Technical Information
≥
≥≥
≥
Page 110
h
Outdoor Heat Pump
PUHZ-RP71
PUH-P100
PUHZ-P100
PUHZ-RP100
PUH-P125
PUHZ-P125
PUHZ-RP125
PUH-P140
PUHZ-P140
PUHZ-RP140
PUH-P140
PUHZ-P140
PUHZ-RP140
PUHZ-P200
PUHZ-P200
PUHZ-P200
PUHZ-RP200
PUHZ-RP200
PUHZ-RP200
PUHZ-P250
PUHZ-P250
PUHZ-P250
PUHZ-RP250
PUHZ-RP250
PUHZ-RP250
Total Heating Capacity (kW)
3.5 - 10.2
11.5
4.5 - 12.5
4.5 - 14.0
14.3
5.0 - 16.0
5.0 - 16.0
17.0
5.0 - 18.0
5.0 - 18.0
17.0
5.0 - 18.0
5.0 - 18.0
9.5 - 25.0
9.5 - 25.0
9.5 - 25.0
9.5 - 25.0
9.5 - 25.0
9.5 - 25.0
12.5 - 31.5
12.5 - 31.5
12.5 - 31.5
12.5 - 31.5
12.5 - 31.5
12.5 - 31.5
Total Cooling Capacity (kW)
3.3 - 8.1
10.0
4.9 - 11.2
4.9 - 11.4
12.3
5.5 - 14.0
5.5 - 14.0
14.2
5.5 - 15.0
5.5 - 15.3
14.2
5.5 - 15.0
5.5 - 15.3
9.0 - 22.4
9.0 - 22.4
9.0 - 22.4
9.0 - 22.4
9.0 - 22.4
9.0 - 22.4
11.2 - 28.0
11.2 - 28.0
11.2 - 28.0
11.2 - 28.0
11.2 - 28.0
11.2 - 28.0
Pipe Kit Part Number
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDD-50SR-E
MSDT-111R-E
MSDT-111R-E
MSDT-111R-E
MSDD-50WR-E
MSDT-111R-E
MSDF-1111R-E
MSDD-50WR-E
MSDT-111R-E
MSDF-1111R-E
MSDD-50WR-E
MSDT-111R-E
MSDF-1111R-E
MSDD-50WR-E
MSDT-111R-E
MSDF-1111R-E
Multi-Split Systems - Combinations Table
Indoor Unit
Size 35
Size 50
Size 50
Size 50
Size 60
Size 60
Size 60
Size 71
Size 71
Size 71
Size 50
Size 50
Size 50
Size 100
Size 60
Size 50
Size 100
Size 60
Size 50
Size 125
Size 71
Size 60
Size 125
Size 71
Size 60
No. of Indoor Units
2
2
2
2
2
2
2
2
2
2
3
3
3
2
3
4
2
3
4
2
3
4
2
3
4
Technical Information
Mul
ti-Sp
lit S
yste
ms
Mr
Slim
Ran
ge 2
008
Page 111
Outdoor Units
SUZ-KA50/60/71VA
Side View >
SUZ-KA25/35VA
Upper View >
Front View >
Upper View >
Front View > Side View >
Dimensions
Page 112
Upper View >
Left Side View > Front View > Right Side View >Rear View >
PUHZ-RP35/50VHA3
Front View >
Upper View >
PUHZ-RP60/71VHA3 / PUHZ-P100VHA2 / PUH-P100YHA
Right Side View >
Dimensions
Out
door
Uni
t D
imen
sion
sM
r Sl
imR
ange
200
8
Page 113
Upper View >
Left Side View > Front View > Right Side View >Rear View >
Outdoor UnitsPUHZ-RP100VHA3/YHA3 / PUHZ-RP125-250VHA2 / PUHZ-P125/140VHA2PUHZ-P200/250YHA / PUH-P125/140YHA
Dimensions
Page 114
Out
door
Uni
t D
imen
sion
s /
Air
Han
dlin
g U
nit
Con
trol
ler
Mr
Slim
Ran
ge 2
008
Air Handling Unit Controller
PAC-IF011B-E
PAC-IF011B-EMITSUBISHI ELECTRIC OUTDOOOR UNIT
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
AUTO STEP PUHZ-RP
PUHZ-P
SUZ-KA
PUH-P
MANUAL STEP PUHZ-RP
PIPE SIZE (mm) PUHZ-(R)P
SUZ-KA
Gas / Liquid PUH-P
HEAT EXCHANGER Max Capacity
Min Capacity
DIMENSIONS (mm) Width
Depth
Height
WEIGHT (kg)
SIZE 35
4.1
3.5
VHA3
-
VA
-
VHA3
12.7 / 6.35
9.52 / 6.35
-
1050
350
336
69
278
2.5
SIZE 50
6.0
5.0
VHA3
-
VA
-
VHA3
12.7 / 6.35
12.7 / 6.35
-
1500
500
336
69
278
2.5
SIZE 60
7.0
6.0
VHA3
-
VA
-
VHA3
15.88 / 9.52
15.88 / 6.35
-
1800
600
336
69
278
2.5
SIZE 71
7.6
7.1
VHA3
-
VA
-
VHA3
15.88 / 9.52
15.88 / 9.52
-
2130
710
336
69
278
2.5
SIZE 100
11.2
10.0
V/YHA3
VHA2
-
YHA
V/YHA3
15.88 / 9.52
-
15.88 / 9.52
3000
1000
336
69
278
2.5
SIZE 125
14.0
12.5
V/YHA2
VHA2
-
YHA
V/YHA2
15.88 / 9.52
-
15.88 / 9.52
3750
1250
336
69
278
2.5
SIZE 140
16.0
14.0
V/YHA2
VHA2
-
YHA
V/YHA2
15.88 / 9.52
-
15.88 / 9.52
4200
1400
336
69
278
2.5
SIZE 200
22.4
19.0
YHA2
YHA
-
-
YHA2
28.58 / 9.52
-
-
6000
2000
336
69
278
2.5
SIZE 250
27.0
22.0
YHA2
YHA
-
-
YHA2
28.58 / 12.7
-
-
7500
2500
336
69
278
2.5
The Air Handling Unit Controllers are an interface to allow connectionto third party manufacturer equipment.
Mitsubishi Electric Mr Slim outdoor units can be used with this interface box, creating an ideal solution when a unique air handling unit is required.
� No need for expansion device
� Error, operation and defrost output
� Demand control by analogue or digital inputs(0-10Ω, 4-20mA , 1-5V, 0-10V, Step, Auto-Step)
Note: One air handling unit controller is required per air handling unitCooling: Indoor 27ºC DB/19ºC WB, Outdoor 35ºC DB/24ºC WBHeating: Indoor 20ºC DB, Outdoor 7ºC DB/6ºC WB
A Control wiring Thermistor wiring
Piping
Air Handling Unit (field supplied)
Controller (field supplied)
Outdoor Unit (Mitsubishi Electric)
Air Handling Unit Controller (Mitsubishi Electric)
Example:
Technical Information
Page 115
VOLUME (cm3)
Accessories / Optional ExtrasM Series
Wall Mounted Units S70 515 716 - Terminal blockS71 000 028 - CN22 connector
Ceiling Concealed Ducted Units PAC-SK005MT-F - 130Pa fan motor PEAD-RP71EAPAC-SK004MT-F - 130Pa fan motor PEAD-RP100EA2PAC-SK003MT-F - 130Pa fan motor PEAD-RP125/140EAPAC-KE03DM-G - Optional drain lift pump PEAD-RP35-140EA(2)MAC-399IF - Interface for connection to M-NET System SEZ-KD25-71VAMAC-397IF - Interface for group control and run/fault SEZ-KD25-71VA
4-Way Blow Cassette Units PAC-SH53TM-E - Multi function casement PLA-RP35-140BA(2) for fresh air 100mm knockout orto hold the high efficiency filter option
PAC-SH59KF-E - High efficiency filter PLA-RP35-140BA(2)PLP-6BALM - Grille and infra-red controller PLA-RP35-140BA(2)PLP-6BAJ - Grille with filter lowering function PLA-RP35-140BA(2)PAC-SA1ME-E - ‘I-See Sensor’ corner panel PLA-RP35-140BA(2)PAR-SA9FA-E - Infra-red signal receiver PLA-RP35-140BA(2)S70E40714 - Infra-red controller (PAR-SL97A-E) PLA-RP35-140BA(2)MAC-399IF - Interface for connection to M-NET System SLZ-KA25-50VAMAC-397IF - Interface for group control and run/fault SLZ-KA25-50VA
Ceiling Suspended Units PAR-SL99B-E - Wireless remote controller and adaptorPAC-SE85DMA-E - Optional drain lift pump PCA-RP50-71GA(2)PAC-SE86DMA-E - Optional drain lift pump PCA-RP100-140GAPAC-SG38KF-E - Oil mist filter for PCA-RP71/125HA (12 pack)PAC-SF81KC-E - Decoration covers (front cover & suspending bracket) for PCA-RP71HAPAC-SF82KC-E - Decoration covers (front cover & suspending bracket) for PCA-RP125HA
Outdoor Units PAC-SG61DS-E - Drain socket set PUHZ-RP35-250V/YHA2/3 / PUHZ-P100-250VHA2/YHAPAC-SG58SG-E - Air outlet guide PUHZ-RP35-50VHA3PAC-SG59SG-E - Air outlet guide PUHZ-RP60-250V/YHA2/3, 2 sets required for sizes 100-250
System Control Units PAC-SE55RA-E - Remote on/off adaptorPAC-SF40RM-E - Run/fault indicationPAC-YT32PTA-E - Program timerPAC-SE41TS-E - Remote sensorPAC-SF80MA - A/M-NET adaptorPAC-YT51CRA - Simplified remote controllerPAR-21MAA - Wired controllerPAC-SK81SI-E - Sub interface board
Pipe Kits MSDD-50SR-E - Multi distribution pipe twin units - 50:50 - sizes 71/100/125/140MSDD-50WR-E - Multi distribution pipe twin units - 50:50 - sizes 200/250MSDT-111R-E - Multi distribution pipe triple units - 33:33:33 - sizes 140/200/250MSDF-1111R-E - Multi distribution pipe quadruple units - 25:25:25:25 - sizes 200/250
Power Supply Terminal Kits PAC-SH52HR-E - Power supply terminal kit for PLA-RP when using PUHZ-RP200/250YHA2PAC-SG96HR-E - Power supply terminal kit for PKA-RP / PCA-RP / PSA-RP when using PUHZ-RP200/250YHA2PAC-SG97HR-E - Power supply terminal kit for PEAD-RP / PCA-RP-HA when using PUHZ-RP200/250YHA2
Acc
esso
ries
/ O
ptio
nal E
xtra
sM
r Sl
imR
ange
200
8
Page 116
City MultiEnergy Efficient VRF Systems
The City Multi rangeSolutions for more demanding applications
Efficient &
Page 118
The City Multi range is Mitsubishi Electric’s answer to large scale VRF (Variable Refrigerant Flow) applications. The efficiency of City Multiis second to none and offers a substantial increase in energy efficiency, with corresponding EER/COP ratings.
The City Multi Y Series range offers a simple and flexible solution where there is a demand for a changeover capability between heating and cooling, helping to ensure a constant, comfortable indoor climate.
Mitsubishi Electric also has the ability to provide simultaneous heating and cooling through its R2 and WR2systems. The difference here being that this is achieved through only two pipes rather than theconventional three. By using Mitsubishi Electric’s 2-pipe heat recovery technology, substantial savingscan again be made on annual running costs. With a wide range of 76 indoor units, up to 50(depending on the capacity available) can be connected to a YHM outdoor unit.
Broadening the range of potential City Multi applications is Mitsubishi Electric’s 3rd generation watercooled R410A WR2 system. This system not only produces heat recovery from the refrigerant circuitbut also via its water circuit, offering double heat recovery potential.
Sophisticated technology, combined with a high level of control and energy efficiency:
City Multi is perfectly positioned to meet the demands of today’s market.
The Strength of City MultiThe R410A YHM-A series offers some of the highest EER/COP ratings in the market.
f lexible
What is VRF?VRF stands for Variable Refrigerant Flow. A VRF air conditioning system modulates the flow ofrefrigerant depending upon the capacity requirements of the building. A VRF system comprises of acondensing unit sited externally and a series of multiple indoor units to provide cooling and/orheating to the occupied space.
Our answer to VRFMitsubishi Electric sets the boundaries of VRF technology with the City Multi range, which is availableusing R410A refrigerant with zero ODP (Ozone Depletion Potential). The range has been specificallydesigned for today's building requirements and addresses key market issues such as energy efficiency,adaptability and reliability. Mitsubishi Electric manufactures the only 2-pipe heat recoverysimultaneous heating and cooling system in the world and equally unique, a water-cooled version. With user fr iendly control systems utilising Internet technology and integrated cooling and ventilation indoor units, City Multi is the benchmark and market leader in VRF technology.
What is inverter driven technology?Mitsubishi Electric spends more than 5% of its turnover on research and development, with ourengineers always looking at ways in which we can improve and lead in air conditioning efficiency. The use of inverter technology in our City Multi systems is paramount in this process, working byvarying the compressor speed to match the cooling or heating load, thereby consuming only thepower necessary to match the exact requirement of the room. When City Multi is operating atpartial load, the energy efficiency of the system is significantly higher than at full load. In a typicalapplication partial load conditions prevail for more than 90% of operation time. A fixed speed systemcan only operate at 100% capacity and cannot match the annual efficiencies of an inverter system
What is a Heat Pump system?Mitsubishi Electric’s City Multi Y Series, is a heat pump system, which provides either heating orcooling to a building at any given time.
What is a Heat Recovery system?Mitsubishi Electric’s City Multi R2 and WR2 series’ have the ability to provide heating and cooling atthe same time in areas connected to the same outdoor unit.
The Basics
Page 120
The secret of City Multi heat recovery systems lies in the
BC Controller
How does the R2 / WR2 Heat Recovery System operate on 2 Pipe’s?
The BC Controller houses a liquid/gas separator, allowing the outdoor unit to deliver a mixture (2 phase) of hot gas for heating and liquid for cooling, all through the same pipe. Three pipe systemsallocate a pipe to each of these phases. When this mixture arrives at the BC Controller, it is separated and the correct phase delivered to each indoor unit depending on the individual requirement ofeither heating or cooling.
Why R410A?R410A is a more efficient refrigerant as it has a higher specificheat capacity when compared to R407c or R22. This higherenergy carrying capacity allows for smaller pipe sizes, longer piperuns and reduces the volume of refrigerant within a system.
This is a major factor when complying with EN378, aEuropean standard concerning safety and environmentalrequirements in the design, manufacture, installation,operation, maintenance and disposal of refrigerating systems.
Comparison example of piping connection sites
= 2 sites = 3 sites
Why Heat Recovery?Flexibility and efficiency are key factors when selecting a heatrecovery system. For example, while a heat pump system isadequate for a large open plan office, businesses that have amore partitioned structure to an office will require the needto simultaneously heat or cool different sections of the officeaccording to each users individual preferences.
The efficiency of this type of system comes from the ability touse the by-products of cooling and heating to transfer energywhere it is required, thus acting as a balanced heat exchangerachieving up to 20% cost savings over a conventional heatpump system.
The number of connection sites needed for a R2 / WR2system are also significantly lower than those needed for athree pipe version. This helps to reduce installation costs,further increasing the savings associated with City Multi.
Page 121
The technology to makeCity Multi the natural choice
City Multi R410A YHM-A technologyUsing the very latest in IPM (Intelligent Power Module) technology, precise control ofenergy input is achieved allowing City Multi to fur ther improve COPs for R410A systems.IPM uses 1Hz steps of capacity control, matching building requirements through more accuratecontrol of the occupied space with reduced power input.
As in previous versions, IPM technology operates extremely effectively under part load conditions(50-80% of operating capacity), a condition that most systems will be in for their normal working life.Therefore the consideration of efficiency at part load is accounted for as well as when at peak loadconditions, offering high system efficiency all year round.
Energy efficiency has always been the driver for City Multi technologicaldevelopment. Technology that always delivers the quality and reliability neededfor commercial air conditioning environments. Mitsubishi Electric spend morethan 5% of their turnover on research and development, with our engineers alwayslooking at ways in which we can improve and lead in air conditioning efficiency.
Stable and smooth operation - 100% inverter control
All City Multi compressors are inverter-driven - Capable of precisely matching abuilding's cooling and heating demands.
The outdoor unit combinations comprise of one module for 8-18hp systems (for R2 up to16hp), two modules for 20-36hp systems (for R2, 18-32hp) and three modules for 38-50hpsystems (Y series only). Each module carries one inverter compressor making simple and highlyreliable control possible. Not only does it allow low starting currents, the inverter drivencompressor also provides precise indoor comfort and adapts to the air conditioning load, achieving smooth transition across the range of compressor frequencies.
Page 122
Y Series 8-18hp / R2 8-16hp Y Series 20-36hp / R2 18-32hp Y Series 38-50hp
Total Energy Conservation
Total Energy Conservation
Comparison of COP (energy efficiency) of an 8hp YHM-A system.
The difference between YHM-A and previousMitsubishi Electric models
Technology is key when increasedefficiency is demanded. The City MultiYHM-A range is designed to deliver this.
A highly efficient R410A scroll compressordesign results in less friction losses at the motor.A simplified refrigerant circuit (low pressure loss)including new accumulator design also adds afew more points to the efficiency scale.
Enhancements to the heat interchange circuit,inverter driven fan motor and heat exchangerdesign, again add vital increases to overall systemefficiency and COPs.
CITY MULTI REFRIGERANT
CIRCUIT
NORMAL REFRIGERANT
CIRCUIT
Heat Interchange CircuitTo further enhance the class leading efficiency of City Multi, the unique HeatInterchange Circuit provides extra sub cooling. This system allows optimumrefrigerant distribution to multiple indoor units, by allowing more effective use of refrigerant flowing through the electronic expansion valves.
Because of the added efficiency, volumes of refrigerant in systems arecontinuing to reduce.
The importance of COPCOP stands for “Co-efficient of Performance”. It is a measure of theuseful energy a system can deliver compared to the energy that it consumes. It is calculated by dividing the energy output by the energy input of a system. The higher the figure then the moreefficient the system is deemed to be, with commensurate reducedrunning costs.
For Heat Pumps to be included on the Energy Technology Product Listunder the Enhanced Capital Allowance scheme, they must achieve aheating COP of 3.4 and a cooling EER (energy efficiency ratio) of 3.0.Therefore every input of 1kW of energy must deliver an output of 3.4kW for heating and 3.0kW for cooling, achieving an energy label of B.
Page 123
Ground SourceHeat Pumps
A very efficient source of energy for water source heat pump systems is the Earthitself. Ground source heat pumps use the Earth's natural solar collection and heatstorage capabilities as an infinite heat source/heat sink.At between 1.7m and 3m below the ground, the temperature changes from 17ºC in the summer to 10ºC in the winter.Deeper down however, the temperature of the ground is a constant 10ºC all year round. It is these relatively constant,dependable temperatures that can be harnessed using ground source heat pumps.
The constant ground temperatures allow the heat pump to operate at optimum efficiency in both heating and cooling, as the high summer or low winter temperatures do not influence performance. Heat is extracted or rejected into the ground using water which is pumped through a network of plastic pipes.
There are two standard ground source methods available, Open Loop and Closed Loop (Bore Hole or Slinky):
� Open Loop - Large bodies of water can be utilised as a stable source of water at arelatively constant temperature. This can be either surface water or ground water.Surface water would include lakes, reservoirs, rivers and the sea.
� Closed Loop Slinky - A trench is dug to a depth of between 1.7 to 3m and plastic spiral pipe is laid into the bottom. The pipe is covered with sand to provide good ground to pipe contact and then the trench is backfilled with the excavated soil.
� Closed Loop Bore Hole - A series of holes are drilled down into the ground at a depth of 50 to 130m, depending on geothermal conditions. Two water pipes connected via a 'u bend' are fed directly into these holes and then surrounded by a conductive grout.
Ground Source Heat Pump installed insidethe building, typically 1 per floor
Bore Hole absorbs or rejects heat from the ground
Flow and return water loop supplies water to and from the units
Indoor units provide heating or cooling
Example of a Closed Loop Bore Hole Application:
Page 124
A range of Acoustic Kits designed for noise reduction. An industry first, the kits offer a 6dBA noise level reduction from standard.
For supply and / or installation please contact
Ambient Acoustics on 01934 712802
New Acoustic Kits for PUHY and PURY Series units
Highly eff icient &extremely f lexible
Page 125
Features andHigh off coil / High sensible coolingPoor design or application of air conditioning systems can sometimes lead to cold draughts anduneven room temperatures. Low off coil temperatures cause dehumidifying of the air which cancreate dry eyes and sore throats.
Mitsubishi Electric now provides a High Sensible Cooling Function specifically designed to deal withthis. By raising the off coil temperature, a 10% increase in sensible cooling capacity over standardoperation is achievable, the result being greater comfort for occupants. These high SHF’s are availablethroughout the range of indoor units, allowing optimum selection of units tailored to more specificdesign criteria.
Reduced noise levelsNew fan designCity Multi VRF systems led the introduction of larger single fan rotors some ten years ago, achievingsubstantially lower noise levels over multiple designs. Continuing the development in the areas of bladeshape and weight, Mitsubishi Electric have managed to achieve even higher performance and lowernoise levels.
To reduce noise levels further and comply with inner city residential noise regulations, all outdoor unitsinclude Night Set-back mode. This function works by lowering the fan speed and compressorfrequency proportionally with reduction in demand (44dBA for PUHY-P250YHM-A). The compressorcompartment is also now sealed, further reducing noise levels.
Page 126
New fan designReduction of operation noise
New heat exchanger designImprovement of COP
New inverter compressorImprovement of COP
New control box designImprovement of reliability and easy maintenance
Benefits
Fine Control of the Inverter ProvidesBetter Eff iciency and PerformanceAir cooled inverters use the ambient temperature to cool the inverter. For water cooled VRF (whichare installed inside the building) refrigerant cooling is used to maintain accurate control of the Inverter.
Refrigerant volume checking functionThis function runs the system, measuring various temperatures and pressures throughout thesystem, comparing these to the values stored in the units memory from the previous service.If a leakage has occurred the system will indicate so, enabling customers to easily comply withthe F-Gas regulation.
Replace technologyThis unique function allows the re-use of refrigerant piping, controllers, power and controlwiring for all previously installed Mitsubishi Electric R22 and R407c Heat Recovery and Coolingonly systems and partial replace of Heat Pumps (pressure regulations require one pipe fromthe outdoor to the first branch to be replaced). This function offers unprecedented savings oninstallation costs, disruption to business and down time, not to mention the considerablerunning cost and CO2 emission savings - more than halving the running costs compared to a10 year old unit.
Cooling operation set temperature of 14ºCEnvironments such as gyms, laboratories etc often require the ability to cool lower than the standardcomfort cooling setpoint. By selecting a dip switch on the unit, a cooling operation settemperature of 14ºC DB is possible on the floor standing and ducted models only. The indoorunit fan will be fixed at high speed during this operation.
Page 127
YGM-A YHM-A
YGM-A YHM-A
8-12hp systems (Y / R2 Series) 1.43m2
14-18hp systems (Y Series)14-16hp systems (R2 Series)
1.89m2
mm
33kg
Approximately 21% reduction in foot print(PUHY-P250)
The unit can easily be transported, even into inaccessible buildings
The downsized outdoor unit can be transported through an 800mm wide lift door
The narrow space between buildings makes it difficult to use a crane
8-12hp outdoor units Example of lift
Effective use of spaceThe new models have a smaller foot print requirement than previous models. The width and depthhave been reduced by 7% and 13% respectively, with the height being reduced by 130mm.
(PUHY-P250YHM-A compared to previous YGM-A versions).
Weight reductionWeight has been reduced by approximately 33kg
(PUHY-P250YHM-A compared to previous YGM-A versions).
Page 128
Blue Fin treatmentThe anti-corrosion Blue Fin treatment of the heat exchanger is especially effective in urban environments where the traffic pollutions can damage the aluminium fins reducing the capacity and life expectancy of the unit.
All City Multi R410A outdoor units have been treated with Blue Fin
R410A pipe sizingAs R410A has a higher specific heat capacity than R22, the pipework is smaller. This means the pipe itself is cheaper, easier to install and less riser space is required within the building.
10hp model
Water temperature operation range -WR2 / WY Water cooled units
Page 129
Heating operation range -Air cooled unitsAt low ambient temperatures the guaranteed operating range in heating is minus 20ºC
Operating range in cooling is from an outdoor temperature of -5ºC.
Constant & comfortableindoor climates
Outdoor Temperature (ºC) Water Temperature (ºC)
City Multi exceedscurrent demands for Eff iciencyThe need for energy efficiency is paramount and is determined by legislation and regulation.Businesses saw their energy bills rise by up to 15% with the introduction of the Climate ChangeLevy in April 2001. A year later, the newly revised Par t L (Par t J in Scotland) of the buildingregulations placed new standards on design of buildings and plant deployed for heating, cooling andventilating. A revised version to conform with the Energy Performance of Buildings Directive was alsointroduced in 2006; all geared to reducing energy consumption and therefore CO2 emissions.
To encourage efficient use of energy, the UK Government introduced the Enhanced CapitalAllowance Scheme (ECA). Qualifying products on the Energy Technology Product List include heatpumps for space heating. The City Multi range has been designed to ensure businesses qualify forECA and benefit from the utmost efficiency, both financially and environmentally.
Mitsubishi Electric has produced a series of comprehensive CPD approved guides.These include:
Page 130
� The Energy Performance of Buildings Directive (EPBD)
� Mixed Mode Cooling Systems
� Building Energy Management Systems (BEMS)
� Water Cooled VRF Systems
� The European F-Gas Regulation
� The New Part L of the Building Regulations 2006
� The New 10% Renewable Energy Target
� Heat Pump Boilers
� Part F of the Building Regulations
� The Code for Sustainable Homes
� Building Energy Ratings
� Renewable Energy Sources
� Maintenance, Replacement and the WEEE Directive
� Combined Heat and Power
� Carbon Reduction in the Built Environment
� The Application of Heat Pump Boilers
� The Enhanced Capital Allowance Scheme (2008)
� Under the scheme, all businesses liable for UK corporation tax, are able to claim an enhanced capital allowance on any qualifying expenditure (regardless of size and location of business or whether in the industrial or commercial sector)
� Businesses can offset the full cost of specific technologies (such as City Multi) against taxable profits of the period of the investment
� In order to qualify for this scheme, technology has to meet the energy saving criteria as published in the Energy Technology Criteria List. City Multi fully meets this criteria in its drive for energy efficiency
� Only investment in new and unused plant and machinery qualify
For further information go to www.eca.gov.uk and click on Mitsubishi Electric Air Conditioning under the heat pump category.
Enhanced Capital Allowance Scheme (ECA)
The key features of the scheme:
Page 131
A wide choice of models
The model line up
The new YHM-A air sourced outdoor models are modular in design and as such differingcombinations of them can be connected together to create the required outdoor unit size neededfor a particular application.
Both the Y Series and R2 ranges come in standard (-P) and high COP (-EP) versions. In addition, the standard versionsallow for space-saving by virtue of the combination of units having a smaller foot print than the high COP versions.
Y Series Heat Pump - Standard Version
Series
Y
R2
Size
Model Name
PUHY-P YHM-A
PUHY-EP YHM-A
PURY-P YHM-A
PURY-EP YHM-A
200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250
8hp 10hp 12hp 14hp 16hp 18hp 20hp 22hp 24hp 26hp 28hp 30hp 32hp 34hp 36hp 38hp 40hp 42hp 44hp 46hp 48hp 50hp
� � � � � � � � � � � � � � � � � � � � �
� � � � � � � � � � � � �
� � � � � � � � � � �
� � � � � � �
10hp
PUHY-P250YHM-A
12hp
PUHY-P300YHM-A
Y Series (10-12hp) PUHY-P YHM-A
28hp
PUHY-P700YSHM-A
30hp
PUHY-P750YSHM-A
32hp
PUHY-P800YSHM-A
Y Series (28-36hp) PUHY-P YSHM-A
14hp
PUHY-P350YHM-A
16hp
PUHY-P400YHM-A
18hp
PUHY-P450YHM-A
Y Series (14 -18hp) PUHY-P YHM-A
38hp
PUHY-P950YSHM-A
40hp
PUHY-P1000YSHM-A
Y Series (38 -40hp) PUHY-P YSHM-A
20hp
PUHY-P500YSHM-A
22hp
PUHY-P550YSHM-A
24hp
PUHY-P600YSHM-A
26hp
PUHY-P650YSHM-A
Y Series (20 -26hp) PUHY-P YSHM-A
42hp
PUHY-P1050YSHM-A
Y Series (42hp) PUHY-P YSHM-A
44hp
PUHY-P1100YSHM-A
46hp
PUHY-P1150YSHM-A
48hp
PUHY-P1200YSHM-A
50hp
PUHY-P1250YSHM-A
Y Series (44-50hp) PUHY-P YSHM-A
34hp
PUHY-P850YSHM-A
36hp
PUHY-P900YSHM-A
Page 132
Y Series Heat Pump - High COP Version
8hp
PUHY-EP200YHM-A
12hp
PUHY-EP300YHM-A
Y Series - High COP (8 -12hp) PUHY-EP YHM-A
Y Series - High COP (28-30hp) PUHY-EP YSHM-A
16hp
PUHY-EP400YSHM-A
18hp
PUHY-EP450YSHM-A
20hp
PUHY-EP500YSHM-A
Y Series - High COP (16-20hp) PUHY-EP YSHM-A
32hp
PUHY-EP800YSHM-A
34hp
PUHY-EP850YSHM-A
28hp
PUHY-EP700YSHM-A
30hp
PUHY-EP750YSHM-A
Y Series - High COP (32-34hp) PUHY-EP YSHM-A
Y Series - High COP (22-26hp) PUHY-EP YSHM-A
36hp
PUHY-EP900YSHM-A
Y Series - High COP (36hp) PUHY-EP YSHM-A
22hp
PUHY-EP550YSHM-A
24hp
PUHY-EP600YSHM-A
26hp
PUHY-EP650YSHM-A
R2 Series Heat Recovery - Standard Version
10hp
PURY-P250YHM-A
12hp
PURY-P300YHM-A
R2 Series (10 -12hp) PURY-P YHM-A
R2 Series (26 -28hp) PURY-P YSHM-A
R2 Series (14 -16hp) PURY-P YHM-A
30hp
PURY-P750YSHM-A
32hp
PURY-P800YSHM-A
26hp
PURY-P650YSHM-A
28hp
PURY-P700YSHM-A
R2 Series (30 -32hp) PURY-P YSHM-A
R2 Series (18 -24hp) PURY-P YSHM-A
14hp
PURY-P350YHM-A
16hp
PURY-P400YHM-A
20hp
PURY-P500YSHM-A
22hp
PURY-P550YSHM-A
24hp
PURY-P600YSHM-A
R2 Series Heat Recovery - High COP Version
8hp
PURY-EP200YHM-A
12hp
PURY-EP300YHM-A
R2 Series - High COP (8 -12hp) PURY-EP YHM-A R2 Series - High COP (16-18hp) PURY-EP YSHM-A
24hp
PURY-EP600YSHM-A
R2 Series - High COP (24hp) PURY-EP YSHM-A
R2 Series - High COP (20-22hp) PURY-EP YSHM-A
16hp
PURY-EP400YSHM-A
18hp
PURY-EP450YSHM-A
20hp
PURY-EP500YSHM-A
22hp
PURY-EP550YSHM-A
Page 133
City Multi Product Range OverviewOutdoor Units14kW Cooling Capacity
PQ(H/R)Y-P200/250YGM-A
WY / WR2Y Series (4/5/6hp)
Model / Size
PLFY-P-VBM-E
PLFY-P-VCM-E
PLFY-P-VLMD-E
PMFY-P-VBM-E
PEFY-P-VMS1-E
PEFY-P-VMM-E
PEFY-P-VMH-E
PCFY-P-VGM-E
PKFY-P-VBM/VGM/VFM-E
PFFY-P-VLRM-E
PFFY-P-VLRMM-E
PFFY-P-VLEM-E
PFFY-P-VKM-E
GUF-RD3
PQFY-P
15(1.7kW)
20(2.2kW)
25(2.8kW)
32(3.6kW)
40(4.5kW)
Indoor Units
PUMY-P100-140V/YHMA
Page 134
PQ(H/R)Y-P400/500YSGM-A
WY / WR2
63(7.1kW)
80(9.0kW)
100(11.2kW)
125(14.0kW)
140(16.0kW)
250(28.0kW)
140kW Cooling Capacity
PUH/RY-EP200YHM-A
Y / R2 Series High COP
PUH/RY-P350-450YHM-A*1
Y / R2 Series Standard
50(5.6kW)
Page 135
*1 Size 450 only available for Y Series
PUH/RY-P250/300YHM-A
Y / R2 Series Standard
PUH/RY-EP300YHM-A
Y / R2 Series High COP
The energy efficient
City Multi VRF range
Unique 2-pipe technology provides
simultaneous heating and cooling, alongside excellent energy
efficiency and corresponding EER/COP
ratings. Up to 50 indoor units can be connected to a single
outdoor unit, offering the sophistication,
control and energy efficiency
demanded today.
Systems marked with the ECA logo are registered on the Energy Technology List andhence qualify for 100% first year enhanced capital allowances (whole system cost and‘reasonable’ cost of installation). For further information please go to www.eca.gov.uk
Nominal conditions cooling: indoor 27˚C DB, 19˚C WB; outdoor 35˚C DB, 24˚C WB.Nominal conditions heating: indoor 20˚C DB; outdoor 7˚C DB, 6˚C WB.UK Conditions: Summer; indoor 21˚C DB, 15˚C WB; outdoor 27˚C DB. Winter; indoor 21˚C DB; outdoor -1˚C WB.
S imple technologyat its best
Page 136
Y Series (4-6hp) Heat Pump, Outdoor Unit
Y Series Standard (10-18hp) Heat Pump, Outdoor Unit
Y Series Standard (20-36hp) Heat Pump, Outdoor Unit
Y Series Standard (38-50hp) Heat Pump, Outdoor Unit
Y Series High COP (8-26hp) Heat Pump, Outdoor Unit
Y Series High COP (28-36hp) Heat Pump, Outdoor Unit
WY Series (8-20hp) Water Cooled Heat Pump, Outdoor Unit
R2 Series Standard (10-16hp) Heat Recovery, Outdoor Unit
R2 Series Standard (20-32hp) Heat Recovery, Outdoor Unit
R2 Series High COP (8-24hp) Heat Recovery, Outdoor Unit
R2 Series Piping Restrictions
WR2 Series (8-20hp) Water Cooled Heat Recovery, Outdoor Unit
PFD-P-VM-E Heat Pump, Close Control System
PLFY-P-VBM-E 2, 3 and 4-Way Blow Ceiling Cassette Indoor Unit
PLFY-P-VCM-E 600x600 4-Way Blow Ceiling Cassette Indoor Unit
PLFY-P-VLMD-E 2-Way Blow Ceiling Cassette Indoor Unit
PMFY-P-VBM-E 1-Way Blow Ceiling Cassette Indoor Unit
PEFY-P-VMS1-E Ultra Thin Ceiling Concealed Ducted Indoor Unit
PEFY-P-VMM-E Ceiling Concealed Ducted Indoor Unit
PEFY-P-VMH-E High Static Pressure Ceiling Concealed Ducted Indoor Unit
PCFY-P-VGM-E Ceiling Suspended Indoor Unit
PKFY-P-VBM/VGM/VFM-E Wall Mounted Indoor Unit
PFFY-P-VLRM-E Floor Standing Concealed Indoor Unit
PFFY-P-VLRMM-E Floor Standing Concealed Indoor Unit
PFFY-P-VLEM-E Floor Standing Exposed Indoor Unit
PFFY-P-VKM-E Floor Standing Exposed Indoor Unit
GUF-RD3 Lossnay Outdoor Air Processing Unit
PQFY-P VRF Heat Pump Boiler
BC Controllers
Air Handling Unit Controllers
Accessories / Optional Extras
138
140
142
144
146
148
150
152
154
156
158
160
162
164
166
168
170
172
174
176
178
180
182
184
186
188
190
192
194
196
197
Contents
Page 137
Heat Pump Outdoor Unit
Y Series (4-6hp)
Y SERIES OUTDOOR UNIT - 4-6hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP / EER (nominal)
Max no. OF CONNECTABLE INDOOR UNITS
Max CONNECTABLE CAPACITY
AIRFLOW (m3/min)
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA) Heating/Cooling
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
GUARANTEED OPERATING RANGE Cooling
Heating
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PUMY-P100VHMA
12.5
11.2
10.4
10.3
3.66
3.34
3.27
2.84
3.42 / 3.35
6
14.5 (130%)
100
15.88 (5/8”)
9.52 (3/8”)
51 / 49
127
950
330+30
1350
220-240v, 50Hz
Single
5
15.5
14.1
-5ºC ~ 46ºC
-15ºC ~ 15ºC
40
3
PUMY-P125VHMA
16.0
14.0
13.3
12.9
4.33
4.32
3.85
3.66
3.69 / 3.24
8
18.2 (130%)
100
15.88 (5/8”)
9.52 (3/8”)
52 / 50
127
950
330+30
1350
220-240v, 50Hz
Single
5
18.3
18.3
-5ºC ~ 46ºC
-15ºC ~ 15ºC
40
3
PUMY-P140VHMA
18.0
15.5
14.9
14.3
5.58
5.35
4.99
4.53
3.23 / 2.90
8
20.2 (130%)
100
15.88 (5/8”)
9.52 (3/8”)
53 / 51
127
950
330+30
1350
220-240v, 50Hz
Single
5
23.6
22.7
-5ºC ~ 46ºC
-15ºC ~ 15ºC
50
3
PUMY-P100-140VHMA/YHMA Piping RestrictionsTOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
120m max
80m max
30m max
30m max (20m max if outdoor installed below)
12m max
Optional PartsModel Name DescriptionCMY-Y62-G-E Branch Pipe (2 Branch)
PUMY-P100YHMA
12.5
11.2
10.4
10.3
3.63
3.3
3.23
2.81
3.44 / 3.39
6
14.5 (130%)
100
15.88 (5/8”)
9.52 (3/8”)
51 / 49
140
950
330+30
1350
380-415v, 50Hz
3
5
5.32
4.84
-5ºC ~ 46ºC
-15ºC ~ 15ºC
16
4 + earth
PUMY-P125YHMA
16.0
14.0
13.3
12.9
4.29
4.27
3.82
3.63
3.73 / 3.28
8
18.2 (130%)
100
15.88 (5/8”)
9.52 (3/8”)
52 / 50
140
950
330+30
1350
380-415v, 50Hz
3
5
6.29
6.26
-5ºC ~ 46ºC
-15ºC ~ 15ºC
16
4 + earth
PUMY-P140YHMA
18.0
15.5
14.9
14.3
5.32
5.32
4.73
4.52
3.38 / 2.91
8
20.2 (130%)
100
15.88 (5/8”)
9.52 (3/8”)
53 / 51
140
950
330+30
1350
380-415v, 50Hz
3
5
7.8
7.8
-5ºC ~ 46ºC
-15ºC ~ 15ºC
16
4 + earth
Technical Information
The latest in Mitsubishi Electric R410A Y Series technology. The new City Multi models allow up to 8 indoor units to be connected to a single outdoor unit, using the standard branch/header pipework systemproven in the larger models. Utilising the latest Mitsubishi Electric inver ter technology, the system is fu l ly controllable with all City Multi controllers or linked to third party BEMS.
� A two core non-polar transmission line allows for simple installation of up to eight indoor units
� Latest in inverter technology including a highly efficient DC Scroll Compressor, DC fan motor and Demand Control
� The condensing unit is extremely slimline which allows easy location and application of the system
� Single or three phase power supply
� Anti-Corrosion blue and flat fin technology
� Size 15 PEFY-P-VMS1-E now able to connect to PUMY
Page 138
Upper View >
Side View > Front View >
PUMY-P100-140VHMA/YHMA
Cit
y M
ulti
Ran
ge 2
008
Y S
erie
s (4
-6hp
)
Dimensions
Page 139
Heat Pump Outdoor Unit
Y SERIES STANDARD OUTDOOR UNITS 10-18hp
Y Series Standard (10-18hp)
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PUHY-P250YHM-A
31.5
28.0
28.7
26.6
7.83
7.73
7.75
4.79
4.02 / 3.62
21
185
57
200
920
760
1710
380-415v, 50Hz
3
8
12.1
11.9
32
4 + earth
PUHY-P300YHM-A
37.5
33.5
33.0
31.5
9.39
9.07
9.11
6.71
3.99 / 3.69
26
185
59
215
920
760
1710
380-415v, 50Hz
3
8
14.5
14.0
32
4 + earth
PUHY-P350YHM-A
45.0
40.0
39.6
37.6
12.09
11.20
11.73
8.29
3.72 / 3.57
30
225
60
245
1220
760
1710
380-415v, 50Hz
3
8
18.6
17.3
32
4 + earth
PUHY-P400YHM-A
50.0
45.0
44.0
42.3
13.47
13.23
13.07
9.79
3.71 / 3.40
34
225
61
245
1220
760
1710
380-415v, 50Hz
3
8
20.8
20.4
40
4 + earth
PUHY-P450YHM-A
56.0
50.0
48.7
46.0
15.38
16.28
14.00
11.40
3.64 / 3.07
39
225
62
245
1220
760
1710
380-415v, 50Hz
3
8
23.7
25.1
50
4 + earth
PUHY-P250-450YHM-A Piping Restrictions
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
1000m max
165m max
40m max
50m max (40m max if outdoor installed below)
15m max
Improved for even higher efficiency
Technical Information
The City Multi Y series makes use of a two pipe refrigerant circuit throughout, with the choice of either Branch Pipe or Header Pipe feeds to indoor units, with manual changeover from cooling to heating to ensure that a constant indoor climate is maintained.
� New wrap around coil for improved energy efficiency
� Choice of Branch Pipe or Header Pipe feeds to indoor units
� Energy-saving inverter driven outdoor compressor units with very low start currents
� No requirement for plant rooms or bulky service shafts
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m, with a total system pipe length of 1000m
� 100% inverter control
� High Sensible Cooling Function - By raising the off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Page 140
PUHY-P250, 300YHM-A
PUHY-P350, 400, 450YHM-A
Upper View >
Upper View >
Cit
y M
ulti
Ran
ge 2
008
Y S
erie
s St
anda
rd (
10-1
8hp)
Dimensions
Front View >Side View >
Front View >Side View >
Page 141
PUHY-P500-900YSHM-A Piping Restrictions
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
1000m max
165m max
40m max
50m max (40m max if outdoor installed below)
15m max
Heat Pump Outdoor Unit
Y Series Standard (20-36hp)
Improved for even higher efficiency
Technical Information
The City Multi Y series makes use of a two pipe refrigerant circuit throughout, with the choice of either Branch Pipe or Header Pipe feeds to indoor units, with manual changeover from cooling to heating to ensure that a constant indoor climate is maintained.
� New wrap around coil for improved energy efficiency
� Choice of Branch Pipe or Header Pipe feeds to indoor units
� Energy-saving inverter driven outdoor compressor units with very low start currents
� No requirement for plant rooms or bulky service shafts
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m, with a total system pipe length of 1000m
� 100% inverter control
� High Sensible Cooling Function - By raising the off coil temperature,a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Page 142
Y SERIES STANDARD OUTDOOR UNITS 20-36hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PUHY-P500YSHM-A
63.0
56.0
54.8
51.5
16.40
16.47
14.92
11.53
3.84 / 3.40
43
185 / 185
60
200 + 200
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
25.3
25.4
32 / 32
4 + earth
PUHY-P550YSHM-A
69.0
63.0
60.0
58.0
18.06
18.36
16.43
12.85
3.82 / 3.43
47
185 / 185
60.5
215 + 200
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
27.9
28.3
32 / 32
4 + earth
PUHY-P600YSHM-A
76.5
69.0
66.6
63.5
19.92
18.75
18.13
13.13
3.84 / 3.68
50
225 / 185
60.5
245 + 200
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
30.7
28.9
32 / 32
4 + earth
PUHY-P650YSHM-A
81.5
73.0
70.9
67.2
21.90
20.79
19.93
14.55
3.72 / 3.51
50
225 / 185
61
245 + 215
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
33.8
32.1
32 / 32
4 + earth
PUHY-P700YSHM-A
88.0
80.0
75.7
73.6
23.71
22.47
22.05
16.18
3.71 / 3.56
50
225 / 225
61
245 + 245
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
36.6
34.7
32 / 32
4 + earth
PUHY-P750YSHM-A
95.0
85.0
81.7
78.2
25.46
25.07
23.68
18.05
3.73 / 3.39
50
225 / 225
63
245 + 245
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
39.3
38.7
40 / 32
4 + earth
PUHY-P800YSHM-A
100.0
90.0
86.0
82.8
25.70
27.69
23.90
19.94
3.89 / 3.25
50
225 / 225
64
245 + 245
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
39.7
42.8
50 / 32
4 + earth
PUHY-P850YSHM-A
108.0
96.0
95.0
88.3
28.42
30.18
26.15
19.92
3.80 / 3.18
50
225 / 225
64.5
245 + 245
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
43.9
46.6
50 / 40
4 + earth
PUHY-P900YSHM-A
113.0
101.0
99.4
92.9
30.29
33.33
27.87
22.00
3.73 / 3.03
50
225 / 225
64.5
245 + 245
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
46.8
51.5
50 / 50
4 + earth
PUHY-P500, 550YSHM-A
PUHY-P600, 650YSHM-A
Cit
y M
ulti
Ran
ge 2
008
Y S
erie
s St
anda
rd (
20-3
6hp)
Dimensions
Side View > Front View >
Side View > Front View >
Side View > Front View >
PUHY-P700, 750, 800, 850, 900YSHM-A
Page 143
PUHY-P950-1250YSHM-A Piping Restrictions
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
1000m max
165m max
40m max
50m max (40m max if outdoor installed below)
15m max
Heat Pump Outdoor Unit
Y Series Standard (38-50hp)
Improved for even higher efficiency
Technical Information
The City Multi Y series makes use of a two pipe refrigerant circuit throughout, with the choice of either Branch Pipe or Header Pipe feeds to indoor units, with manual changeover from cooling to heating to ensure that a constant indoor climate is maintained.
� New wrap around coil for improved energy efficiency
� Choice of Branch Pipe or Header Pipe feeds to indoor units
� Energy-saving inverter driven outdoor compressor units with very low start currents
� No requirement for plant rooms or bulky service shafts
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m, with a total system pipe length of 1000m
� 100% inverter control
� High Sensible Cooling Function - By raising the off coil temperature,a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Page 144
Y SERIES STANDARD OUTDOOR UNITS 38-50hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PUHY-P950YSHM-A
119.5
108.0
105.2
99.4
30.02
30.68
27.62
20.25
3.98 / 3.52
50
185 / 185 / 185
64
245 + 215 + 200
1220 + 920 + 920
760
1710
380-415v, 50Hz
3
8 / 8 / 8
46.4
47.4
40 / 32 / 32
4 + earth
PUHY-P1000YSHM-A
127.0
113.0
111.8
104.0
33.15
32.47
30.50
21.43
3.83 / 3.48
50
225 / 185 / 185
64
245 + 215 + 215
1220 + 920 + 920
760
1710
380-415v, 50Hz
3
8 / 8 / 8
51.2
50.1
40 / 32 / 32
4 + earth
PUHY-P1050YSHM-A
132.0
118.0
116.2
108.6
35.01
33.90
32.21
22.37
3.77 / 3.48
50
225 / 225 / 185
64
245 + 245 + 200
1220 + 1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8 / 8
54.1
52.4
40 / 32 / 32
4 + earth
PUHY-P1100YSHM-A
140.0
124.0
123.2
114.1
36.93
35.83
33.98
23.65
3.79 / 3.46
50
225 / 225 / 225
64
245 + 245 + 245
1220 + 1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8 / 8
57.0
55.3
40 / 32 / 32
4 + earth
PUHY-P1150YSHM-A
145.0
130.0
127.6
119.6
39.08
39.39
35.95
26.00
3.71 / 3.30
50
225 / 225 / 225
64.5
245 + 245 + 245
1220 + 1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8 / 8
60.4
60.8
50 / 32 / 32
4 + earth
PUHY-P1200YSHM-A
150.0
136.0
132.0
125.1
40.10
41.71
36.89
27.53
3.74 / 3.26
50
225 / 225 / 225
65
245 + 245 + 245
1220 + 1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8 / 8
61.9
64.4
50 / 40 / 32
4 + earth
PUHY-P1250YSHM-A
156.5
140.0
137.7
128.8
42.06
45.01
38.70
29.71
3.72 / 3.11
50
225 / 225 / 225
65.5
245 + 245 + 245
1220 + 1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8 / 8
65.0
69.5
50 / 50 / 32
4 + earth
PUHY-P950, 1000YSHM-A
PUHY-P1050YSHM-A Cit
y M
ulti
Ran
ge 2
008
Y S
erie
s St
anda
rd (
38-5
0hp)
Dimensions
Side View > Front View >
Side View > Front View >
Side View > Front View >
PUHY-P1100, 1150, 1200, 1250YSHM-A
Page 145
Heat Pump Outdoor Unit
Y Series High COP (8-26hp)
PUHY-EP200-650Y(S)HM-A Piping Restrictions
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
1000m max
165m max
40m max
50m max (40m max if outdoor installed below)
15m max
Improved for even higher efficiency
Technical Information
The City Multi Y series makes use of a two pipe refrigerant circuit throughout, with the choice of either Branch Pipe or Header Pipe feeds to indoor units, with manual changeover from cooling to heating to ensure that a constant indoor climate is maintained.
� Highest ever COP’s / EER’s due to new higher efficiency inverter technology and wrap around coil
� Choice of Branch Pipe or Header Pipe feeds to indoor units
� Energy-saving inverter driven outdoor compressor units with very low start currents
� No requirement for plant rooms or bulky service shafts
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m, with a total system pipe length of 1000m
� 100% inverter control
� High Sensible Cooling Function - By raising the off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Y SERIES HIGH COP OUTDOOR UNIT 8-26hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PUHY-EP200YHM-A
25.0
22.4
23.0
21.3
5.77
5.18
5.71
3.21
4.33 / 4.32
17
185
57
200
920
760
1710
380-415v, 50Hz
3
8
8.9
8.0
20
4 + earth
PUHY-EP300YHM-A
37.5
33.5
33.0
31.5
9.28
8.25
9.00
6.11
4.04 / 4.06
26
225
60
245
1220
760
1710
380-415v, 50Hz
3
8
14.3
12.7
32
4 + earth
PUHY-EP400YSHM-A
50.0
45.0
44.0
42.3
11.54
10.41
11.19
7.70
4.33 / 4.32
34
185 / 185
60
200 + 200
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
17.8
16.0
20 / 20
4 + earth
PUHY-EP450YSHM-A
56.0
50.0
48.7
46.0
13.05
13.15
11.88
9.21
4.29 / 3.80
39
185 / 185
60
200 + 200
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
20.1
20.3
32 / 20
4 + earth
PUHY-EP500YSHM-A
63.0
56.0
54.8
51.5
15.14
13.46
13.78
9.42
4.16 / 4.16
43
225 / 185
62
245 + 200
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
23.4
20.8
32 / 20
4 + earth
PUHY-EP550YSHM-A
69.0
63.0
60.0
58.0
17.12
16.32
15.58
11.42
4.03 / 3.86
47
225 / 185
62
245 + 200
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
26.4
25.2
32 / 32
4 + earth
PUHY-EP600YSHM-A
76.5
69.0
66.6
63.5
18.93
16.99
17.23
11.89
4.04 / 4.06
50
225 / 225
63
245 + 245
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
29.2
26.2
32 / 32
4 + earth
PUHY-EP650YSHM-A
81.5
73.0
70.9
67.2
19.13
18.34
17.41
12.84
4.26 / 3.98
50
225 / 225
63
245 + 245
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
29.5
28.3
32 / 32
4 + earth
Page 146
PUHY-EP400, 450YSHM-A
Side View > Front View >
PUHY-EP200, 300YHM-A
PUHY-EP500, 550YSHM-A
Cit
y M
ulti
Ran
ge 2
008
Y S
erie
s H
igh
CO
P (8
-26h
p)
Dimensions
Side View > Front View >
Side View > Front View >PUHY-EP600, 650YSHM-A
PUHY-EP200YHM-A schematic is the same as PUHY-P250, 300YHM-A on page 141PUHY-EP300YHM-A schematic is the same as PUHY-P350, 400, 450YHM-A on page 141
Page 147
Heat Pump Outdoor Unit
Y Series High COP (28-36hp)
PUHY-EP700-900YSHM-A Piping Restrictions
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
1000m max
165m max
40m max
50m max (40m max if outdoor installed below)
15m max
Improved for even higher efficiency
Technical Information
The City Multi Y series makes use of a two pipe refrigerant circuit throughout, with the choice of either Branch Pipe or Header Pipe feeds to indoor units, with manual changeover from cooling to heating to ensure that a constant indoor climate is maintained.
� Highest ever COP’s / EER’s due to new higher efficiency inverter technology and wrap around coil
� Choice of Branch Pipe or Header Pipe feeds to indoor units
� Energy-saving inverter driven outdoor compressor units with very low start currents
� No requirement for plant rooms or bulky service shafts
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m, with a total system pipe length of 1000m
� 100% inverter control
� High Sensible Cooling Function - By raising the off coil temperature,a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Page 148
Y SERIES HIGH COP OUTDOOR UNIT 28-36hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PUHY-EP700YSHM-A
88.0
80.0
75.7
73.6
20.00
20.99
18.60
15.11
4.40 / 3.81
50
225 / 185 / 185
63
245 + 200 + 200
1220 + 920 + 920
760
1710
380-415v, 50Hz
3
8 / 8 / 8
30.9
32.4
32 / 20 / 20
4 + earth
PUHY-EP750YSHM-A
95.0
85.0
81.7
78.2
22.19
21.79
20.64
15.69
4.28 / 3.90
50
225 / 185 / 185
63
245 + 200 + 200
1220 + 920 + 920
760
1710
380-415v, 50Hz
3
8 / 8 / 8
34.3
33.6
32 / 32 / 20
4 + earth
PUHY-EP800YSHM-A
100.0
90.0
86.0
82.8
23.41
22.00
21.77
15.84
4.27 / 4.09
50
225 / 225 / 185
64
245 + 245 + 200
1220 + 1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8 / 8
36.1
34.0
32 / 32 / 20
4 + earth
PUHY-EP850YSHM-A
108.0
96.0
95.0
88.3
25.59
24.67
23.54
16.28
4.22 / 3.89
50
225 / 225 / 185
64
245 + 245 + 200
1220 + 1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8 / 8
39.5
38.1
32 / 32 / 32
4 + earth
PUHY-EP900YSHM-A
113.0
101.0
99.4
92.9
27.90
24.87
25.67
16.41
4.05 / 4.06
50
225 / 225 / 225
65
245 + 245 + 245
1220 +1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8 / 8
43.1
38.4
32 / 32 / 32
4 + earth
Cit
y M
ulti
Ran
ge 2
008
Y S
erie
s H
igh
CO
P (2
8-36
hp)
PUHY-EP700, 750YSHM-A
PUHY-EP800, 850YSHM-A
Dimensions
Side View > Front View >
Side View > Front View >
Side View > Front View >
PUHY-EP900YSHM-A
Page 149
WY SERIES HEAT SOURCE UNIT - 8-20hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PQHY-P200YGM-A
25.0
22.4
4.69
4.79
13
46
272
990
550
1800
380-415v, 50Hz
3
8
7.2
7.4
20
4 + earth
PQHY-P250YGM-A
31.5
28.0
5.80
5.95
16
47
275
990
550
1800
380-415v, 50Hz
3
8
8.9
9.1
25
4 + earth
PQHY-P400YSGM-A
50.0
45.0
11.01
11.35
22
50
208 + 244
1980
550
1800
380-415v, 50Hz
3
8
17.0
17.5
40
4 + earth
PQHY-P500YSGM-A
63.0
56.0
13.60
15.06
24
53
208 + 248
1980
550
1800
380-415v, 50Hz
3
8
21.0
23.3
50
4 + earth
WY Series (8-20hp)Heat Pump, Water Cooled Condensing Unit
PQHY-P200-500Y(S)GM-A Piping Restrictions
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
FURTHEST PIPING LENGTH AFTER 1st BRANCH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
BETWEEN INDOOR AND INDOOR UNITS - HEIGHT
300m max
150m max
40m max
50m max (40m max if outdoor installed below)
15m max
Technical Information
The WY Series has all the benefits of the Y Series using water cooled condensingunits. It is also able to produce heat recovery via the water circuit between heat source units, making for a very economical system.
� High COPs possible thanks to increased efficiency and careful control of the system, allowing the largest operational water circuit temperature band ever
� Combining WY with waste heat energy provides unique application solutions
� Up to 24 indoor units can be connected to each condensing unit
� Condensing units can be situated indoors allowing greater design flexibility and no limitation on building size
� Single inverter compressor up to 20hp
� Improved pipe run of 150m with a total system pipe length of up to 300m
� High Sensible Cooling Function - By raising the off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
� Now able to operate with closed loop ground source water temperatures, bore hole and slinky applications are now possible
Page 150
PQHY-P200, 250YGM-A
PQHY-P400, 500YSGM-A
Upper View >
Front View >
Left Side View >
Upper View >
Front View >
Left Side View >
Cit
y M
ulti
Ran
ge 2
008
WY
Ser
ies
(8-2
0hp)
Dimensions
Page 151
R2 Series Standard (10-16hp)Simultaneous Heating and Cooling with Heat Recovery Outdoor Unit
Improved for even higher efficiencyThroughout the year, many buildings require cooling in some areas and heating in others -even in adjacent rooms. The outstanding City Multi R2 system meets this requirement bydistributing surplus heat from cooling operations (and vice versa) to rooms where it is needed.This efficiency can result in energy savings of up to 30% over conventional systems.
� New higher efficiency inverter technology, with low start currents and wrap around coil for added efficiency
� Up to 40 indoor units connected to each outdoor unit
� Easy to install unique 2-pipe technology means minimal disruption, quicker installation and less connections than a 3 pipe equivalents
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m with a total system pipe length of up to 600m
� 100% inverter control
� High Sensible Cooling Function - By raising the off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Page 152
R2 SERIES STANDARD OUTDOOR UNIT 10-16hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PURY-P250YHM-A
31.5
28.0
28.7
26.6
7.83
7.73
7.75
4.79
4.02 / 3.62
25
185
57
235
920
760
1710
380-415v, 50Hz
3
8
12.1
11.9
32
4 + earth
PURY-P300YHM-A
37.5
33.5
33.0
31.5
9.58
9.25
9.29
6.85
3.91 / 3.62
30
185
59
240
920
760
1710
380-415v, 50Hz
3
8
14.8
14.2
32
4 + earth
PURY-P350YHM-A
45.0
40.0
39.6
37.6
12.47
12.47
12.10
9.23
3.60 / 3.20
35
225
60
265
1220
760
1710
380-415v, 50Hz
3
8
19.2
19.2
32
4 + earth
PURY-P400YHM-A
50.0
45.0
44.0
42.3
13.71
13.74
13.30
10.17
3.64 / 3.27
40
225
61
265
1220
760
1710
380-415v, 50Hz
3
8
21.1
21.2
40
4 + earth
Technical Information
Note: For piping restrictions for PURY-P250-400YHM-A please see page 158
Cit
y M
ulti
Ran
ge 2
008
R2
Seri
es S
tand
ard
(10-
16hp
)
PURY-P250, 300YHM-A
PURY-P350, 400YHM-A
Upper View >
Upper View >
Dimensions
Front View >Side View >
Front View >Side View >
Page 153
R2 Series Standard (20-32hp)Simultaneous Heating and Cooling with Heat Recovery Outdoor Unit
Improved for even higher efficiencyThroughout the year, many buildings require cooling in some areas and heating in others - even in adjacent rooms. The outstanding City Multi R2 system meets this requirement bydistributing surplus heat from cooling operations (and vice versa) to rooms where it is needed.This efficiency can result in energy savings of up to 30% over conventional systems.
� New higher efficiency inverter technology, with low start currents and wrap around coil for added efficiency
� Up to 50 indoor units connected to each outdoor unit
� Easy to install unique 2-pipe technology means minimal disruption, quicker installation and less connections than a 3 pipe equivalents
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m with a total system pipe length of up to 950m
� 100% inverter control
� High Sensible Cooling Function - By raising the off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Page 154
Note: For piping restrictions for PURY-P500-800YSHM-A please see page 158
Technical Information
R2 SERIES STANDARD OUTDOOR UNIT 20-32hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PURY-P500YSHM-A
63.0
56.0
54.8
51.5
16.79
16.75
15.28
11.73
3.75 / 3.34
50
185 / 185
60
235 + 235
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
25.9
25.8
32 / 32
4 + earth
PURY-P550YSHM-A
69.0
63.0
60.0
58.0
18.81
18.68
17.12
13.08
3.66 / 3.37
50
185 / 185
61
240 + 235
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
29.0
28.8
32 / 32
4 + earth
PURY-P600YSHM-A
76.5
69.0
66.6
63.5
20.83
19.64
18.96
13.75
3.67 / 3.51
50
185 / 185
62
240 + 240
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
32.1
30.3
32 / 32
4 + earth
PURY-P650YSHM-A
81.5
73.0
70.9
67.2
22.55
22.80
20.52
15.96
3.61 / 3.20
50
225 / 185
62.5
265 + 240
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
34.8
35.2
32 / 32
4 + earth
PURY-P700YSHM-A
88.0
80.0
75.7
73.6
24.30
24.72
22.60
17.80
3.62 / 3.23
50
225 / 185
63
265 + 240
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
37.5
38.2
40 / 32
4 + earth
PURY-P750YSHM-A
95.0
85.0
81.7
78.2
26.36
27.86
24.51
20.06
3.60 / 3.05
50
225 / 225
63.5
265 + 265
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
40.7
43.0
40 / 32
4 + earth
PURY-P800YSHM-A
100.0
90.0
86.0
82.8
27.64
29.75
25.71
21.42
3.61 / 3.02
50
225 / 225
64
265 + 265
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
42.7
45.9
40 / 40
4 + earth
Cit
y M
ulti
Ran
ge 2
008
R2
Seri
es S
tand
ard
(20-
32hp
)
PURY-P500, 550, 600YSHM-A
PURY-P650, 700YSHM-A
Dimensions
Side View > Front View >
Side View > Front View >
Side View > Front View >
PURY-P750, 800YSHM-A
Page 155
R2 Series High COP (8-24hp)Simultaneous Heating and Cooling with Heat Recovery Outdoor Unit
Improved for even higher efficiencyThroughout the year, many buildings require cooling in some areas and heating inothers - even in adjacent rooms. The outstanding City Multi R2 system meets thisrequirement by distributing surplus heat from cooling operations (and vice versa) to rooms where it is needed. This efficiency can result in energy savings of up to 30% over conventional systems.
� Highest ever COP’s / EER’s due to new high efficiency inverter technology and wrap around coil for added efficiency
� Up to 50 indoor units connected to each outdoor unit
� Easy to install unique 2-pipe technology means minimal disruption, quicker installation and less connections than a 3 pipe equivalents
� Weight and size reduction compared to previous YGM-A models
� Improved pipe run of 165m with a total system pipe length of up to 800m
� 100% inverter control with low start currents
� High Sensible Cooling Function - By raising the off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
Note: For piping restrictions for PURY-EP200-600Y(S)HM-A please see page 158
Technical Information
R2 SERIES HIGH COP OUTDOOR UNIT 8-24hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
COP/EER (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
AIRFLOW (m3/min) High
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
(1650mm without legs) Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (MCB sizes BS EN 60947-2) - (A)
MAINS CABLE No. Cores
PURY-EP200YHM-A
25.0
22.4
23.0
21.3
5.81
5.23
5.75
3.24
4.30 / 4.28
20
185
57
235
920
760
1710
380-415v, 50Hz
3
8
8.9
8.0
20
4 + earth
PURY-EP300YHM-A
37.5
33.5
33.0
31.5
9.37
8.33
9.09
6.16
4.00 / 4.02
30
225
60
265
1220
760
1710
380-415v, 50Hz
3
8
14.4
12.8
32
4 + earth
PURY-EP400YSHM-A
50.0
45.0
44.0
42.3
11.73
10.57
11.38
7.82
4.26 / 4.25
40
185 / 185
60
235 + 235
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
18.1
16.3
20 / 20
4 + earth
PURY-EP450YSHM-A
56.0
50.0
48.7
46.0
13.77
13.09
12.53
9.16
4.06 / 3.81
45
185 / 185
60
235 + 235
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
21.2
20.2
32 / 20
4 + earth
PURY-EP500YSHM-A
63.0
56.0
54.8
51.5
15.33
13.70
13.95
9.59
4.10 / 4.08
50
225 / 185
62
265 + 235
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
23.6
21.1
32 / 20
4 + earth
PURY-EP550YSHM-A
69.0
63.0
60.0
58.0
17.37
16.38
15.81
11.47
3.97 / 3.84
50
225 / 185
62
265 + 235
1220 + 920
760
1710
380-415v, 50Hz
3
8 / 8
26.8
25.3
32 / 32
4 + earth
PURY-EP600YSHM-A
76.5
69.0
66.6
63.5
19.12
17.00
17.40
11.90
4.00 / 4.05
50
225 / 225
63
265 + 265
1220 + 1220
760
1710
380-415v, 50Hz
3
8 / 8
29.5
26.2
32 / 32
4 + earth
Page 156
Side View > Front View >
Side View > Front View >
Side View > Front View >
PURY-EP400, 450YSHM-A
PURY-EP200, 300YHM-A
PURY-EP500, 550YSHM-A
Cit
y M
ulti
Ran
ge 2
008
R2
Seri
es H
igh
CO
P (8
-24h
p)
Dimensions
PURY-EP600YSHM-A
PURY-EP200YHM-A schematic is the same as PURY-P250, 300YHM-A on page 153PURY-EP300YHM-A schematic is the same as PURY-P350, 400YHM-A on page 153
Page 157
OUTDOOR MODEL MAX LENGTHTABLE 1: TOTAL PIPE LENGTHR2 SERIES PIPING RESTRICTIONS
GRAPH 1: TOTAL PIPING LENGTH RESTRICTIONS
P250, P300P350, P400, EP200, EP300P500, P550, EP400, EP450, EP500, EP550P600, P650, EP600P700, P750, P800
550m*1
600m*1
750m*1
800m*1
950m*1
*1 Please refer to Graph 1
1000
PURY-P700,750,800 YSHM-A
PURY-P600,650,800 YSHM-A, PURY-EP600YSHM-A
PURY-P500,550 YSHM-A, PURY-EP400,450,500,550 YSHM-A
PURY-P350,400 YHM-A, PURY-EP200,300 YHM-A
PURY-P250,300YHM-A
900
800
700
600
500
400
300
200
100
0
10 20 30 40 50 60 70 80 90 100 110
Tota
l Ext
ende
d Pi
pe L
engt
h (m
)
Distance Between Outdoor Unit and BC Controller (m)
R2 SERIES PIPING RESTRICTIONS
ITEM PIPE SECTION MAX LENGTH
R2 SERIES PIPING RESTRICTIONS
PIPING LENGTH (1 BC CONTROLLER, NO SUB BC CONTROLLER)
Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IU
A+B+a+b+c+dA+B+d
AB+dHH1
h1h2
(See Table 1)165m
110m*1
60m*2 (40m)50m40m15m15m
*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
R2 Series Piping Restrictions
Page 158
Cit
y M
ulti
Ran
ge 2
008
R2
Seri
es P
ipin
g R
estr
ictio
ns
ITEM PIPE SECTION MAX LENGTH
R2 SERIES PIPING RESTRICTIONS
PIPING LENGTH (>1 BC CONTROLLER FOR 1 OUTDOOR UNIT)
Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IUHeight Between BC (Main or Sub) and BC (Sub)
A+B+C+D+E+a+b+c+d+e+fA+C+E+f
AB+d or C+D+e or C+E+f
HH1
h1h2h3
(See Table 1)165m
110m*1
60m*2 (40m)50m40m15m15m15m
*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
ITEM PIPE SECTION MAX LENGTH
R2 SERIES PIPING RESTRICTIONS
PIPING LENGTH (>1 BC CONTROLLER FOR 2 OUTDOOR UNITS)
Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IUHeight Between BC (Main or Sub) and BC (Sub)Length Between Main OU and Sub OUHeight Between Main OU and Sub OU
F+G+A+B+C+D+E+a+b+c+d+e+fF(G)+A+C+E+f
F(G)+AB+d or C+D+e or C+E+f
HH1
h1h2h3
F+G or Hh4
(See Table 1)165m
110m*1
60m*2 (40m)50m40m15m15m15m5m
0.1m
*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.
Page 159
WR2 SERIES HEAT SOURCE UNIT - 8-20hpMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
MAX No. OF CONNECTABLE INDOOR UNITS
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A)
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PQRY-P200YGM-A
25.0
22.4
4.69
4.79
15
46
263
990
550
1800
380-415v, 50Hz
3
8
7.2
7.4
20
4 + earth
PQRY-P250YGM-A
31.5
28.0
5.80
5.95
19
47
266
990
550
1800
380-415v, 50Hz
3
8
8.9
9.1
25
4 + earth
PQRY-P400YSGM-A
50.0
45.0
11.01
11.35
24
50
208 + 232
1980
550
1800
380-415v, 50Hz
3
8
17.0
17.5
40
4 + earth
PQRY-P500YSGM-A
63.0
56.0
13.60
15.06
24
53
208 + 236
1980
550
1800
380-415v, 50Hz
3
8
21.0
23.3
50
4 + earth
WR2 Series (8-20hp)Water Cooled Condensing UnitSimultaneous Heating and Cooling with Double Heat Recovery
PQRY-P200-500Y(S)GM-A Piping Restrictions
TOTAL PIPING LENGTH
FURTHEST PIPING LENGTH
BETWEEN OUTDOOR AND BC CONTROLLER (MASTER) - LENGTH
BETWEEN INDOOR AND BC CONTROLLER (MASTER/SLAVE) - LENGTH
BETWEEN INDOOR AND OUTDOOR - HEIGHT
BETWEEN INDOOR AND INDOOR - HEIGHT
BETWEEN INDOOR AND BC CONTROLLER (MASTER/SLAVE) - HEIGHT
BETWEEN INDOOR (MASTER) AND INDOOR (SLAVE) - HEIGHT
400m max*3 (300m)
150m max
110m max*4 (70m)
60m max*5 (40m)
50m max (40m)*1
15m max (10m)*2
15m max
15m max (10m)*2
Technical Information
The WR2 system has double heat recovery potential, making this system very economical.Not only does it produce heat recovery from indoor units on the same refrigerant circuit,it also produces heat recovery via the water circuit between heat source units.
� All the benefits of the R2 Series with water cooled condensing units, using a single inverter compressor
� High COPs possible thanks to increased efficiency and careful control of the system, allowing the largest operational water circuit temperature band ever
� Unique 2-pipe refrigerant circuit allows simultaneous heating and cooling plus heat recovery between indoor units as with the R2 system
� Total building heat recovery made possible by exchanging energy in both refrigerant and water circuits
� Combining WR2 with waste heat energy provides unique application solutions
� Condensing units can be situated indoors allowing greater design flexibilityand no limitation on building size
� Single inverter compressor up to 20hp
� Improved pipe run of 150m with a total system pipe length of up to 400m
� High Sensible Cooling Function - By raising the off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the result being greater comfort for occupants
� Now able to operate with closed loop ground source water temperatures, bore hole and slinky applications are now possible
Page 160
*1 When O/U is below indoor *2 In case of P200, P250 indoor unit *3 Distance between outdoor unit and BC Controller is 70m or less *4 Total piping length is 300m or less *5 Height difference between the Master BC Controller and furthest indoor unit is zero
PQRY-P200, 250YGM-A
PQRY-P400, 500YSGM-A
Upper View >
Front View >
Left Side View >
Upper View >
Front View >
Left Side View >
Cit
y M
ulti
Ran
ge 2
008
WR
2 Se
ries
(8-
20hp
)
Dimensions
Page 161
Heat Pump Close Control System
PFD-P-VM-E (10/20hp)
PUHY-P-YHM-A / PQHY-P-YGM-A - OUTDOOR UNITSPFD-P-VM-E - INDOOR UNIT
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
SHF
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
AIRFLOW (m3/min)
EXTERNAL STATIC PRESSURE (Pa)
PIPE SIZE mm(in) Gas
Liquid
NOISE (dBA)
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
STARTING CURRENT (A) Inverter / DOL
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PFD-P250VM-E
31.5
28.0
29.1
26.6
0.93
2.5
2.5
2.15
2.15
160
120
22.2 (7/8”)
9.52 (3/8”)
59
380
1380
780
1950
380-415v, 50Hz
3
47
4.9
4.9
16
4 + earth
PFD-P500VM-E
63.0
56.0
55.4
51.5
0.93
5.0
5.0
4.3
4.3
320
120
28.58 (1 1/8”)
15.88 (5/8”)
63
520
1980
780
1950
380-415v, 50Hz
3
68
8.7
8.7
20
4 + earth
PUHY-P-YHM-A / PQHY-P-YGM-A Piping Restrictions
TOTAL PIPING LENGTH
BETWEEN INDOOR AND OUTDOOR UNITS - HEIGHT
165m max (150m for PQHY)
50m max (40m max if outdoor installed below)
Technical Information
Mitsubishi Electric’s new Close Control System is specifically designed for computer rooms, laboratories etc, where a need for high sensible cooling and close control of temperature and humidity is required. Because of the need forclose control 24 hours a day, 365 days a year, a newly developed inverter driven compressor has been incorporatedinto the outdoor unit, maximising the energy efficiency of the PFD series. It is also able to be connected to a computer network using our G50 controller, in order to monitor and provide remote email alarms.
� High sensible cooling
� Newly developed inverter driven compressor
� Energy efficient with high COP’s
� Close control of temperature, ±1ºC
� Easy to install - no service space needed at the rear of the unit
� Optional third party humidifier available
� Quick recovery following power failure
� Return or discharge air temperature control
Page 162
PUHY-P250YHM-A
31.5
28.0
28.7
26.6
N/A
6.6
6.8
6.55
4.2
185
N/A
22.2 (7/8”)
9.52 (3/8”)
57
200
920
760
1710
380-415v, 50Hz
3
8
10.2
10.5
32
4 + earth
PUHY-P250YHM-A x2
63.0
56.0
54.8
51.5
N/A
6.6 / 6.6
6.8 / 6.8
6.55 / 6.55
4.2 / 4.2
185 / 185
N/A
28.58 (1 1/8”)
15.88 (5/8”)
57 / 57
200 + 200
920 + 920
760
1710
380-415v, 50Hz
3
8 / 8
10.2 / 10.2
10.5 / 10.5
32 / 32
4 + earth
PQHY-P250YGM-A x2
63.0
56.0
N/A
N/A
N/A
5.6 / 5.6
5.9 / 5.9
N/A
N/A
N/A
N/A
28.58 (1 1/8”)
15.88 (5/8”)
47 / 47
275 + 275
990 + 990
550
1800
380-415v, 50Hz
3
8 / 8
8.5 / 8.5
9.0 / 9.0
25 / 25
4 + earth
PQHY-P250YGM-A
31.5
28.0
N/A
N/A
N/A
5.6
5.9
N/A
N/A
N/A
N/A
22.2 (7/8”)
9.52 (3/8”)
47
275
990
550
1800
380-415v, 50Hz
3
8
8.5
9.0
25
4 + earth
PFD-P250VM-E
PFD-P500VM-E
Upper View >
Front View >
Side View >
Upper View >
Front View >
Side View >
Cit
y M
ulti
Ran
ge 2
008
PFD
-P-V
M-E
(10
/20h
p)
Dimensions
Page 163
PLFY-P-VBM-E2, 3 and 4-Way Blow Ceiling Cassette Indoor Unit
PLFY-P-VBM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
NOISE (dBA) Lo-Mi1-Mi2-Hi
WEIGHT (kg) (Grille)
DIMENSIONS (mm) Width (Grille)
Depth (Grille)
Height (Grille)
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
GRILLE MODEL REFERENCE
PLFY-P32VBM-E
4.0
3.6
3.7
3.2
2.6
0.84
0.96
0.02
0.03
11-12-13-14
27-28-29-31
22(6)
840(950)
840(950)
258(35)
220-240v, 50Hz
Single
0.14
0.22
6
3
PLP-6BA
PLFY-P50VBM-E
6.3
5.6
5.8
5.0
4.1
0.76
0.83
0.03
0.04
12-13-14-16
27-28-30-31
22(6)
840(950)
840(950)
258(35)
220-240v, 50Hz
Single
0.22
0.29
6
3
PLP-6BA
PLFY-P80VBM-E
10.0
9.0
9.2
8.0
6.5
0.73
0.78
0.06
0.07
16-18-20-22
30-32-35-37
23(6)
840(950)
840(950)
258(35)
220-240v, 50Hz
Single
0.43
0.51
6
3
PLP-6BA
PLFY-P125VBM-E
16.0
14.0
14.8
12.5
10.2
0.71
0.74
0.15
0.16
22-25-28-30
35-38-41-43
27(6)
840(950)
840(950)
298(35)
220-240v, 50Hz
Single
1.00
1.07
6
3
PLP-6BA
PLFY-P40VBM-E
5.0
4.5
4.6
4.0
3.3
0.83
0.91
0.03
0.04
12-13-14-16
27-28-30-31
22(6)
840(950)
840(950)
258(35)
220-240v, 50Hz
Single
0.22
0.29
6
3
PLP-6BA
PLFY-P63VBM-E
8.0
7.1
7.4
6.3
5.2
0.75
0.79
0.04
0.05
14-15-16-18
28-29-30-32
23(6)
840(950)
840(950)
258(35)
220-240v, 50Hz
Single
0.29
0.36
6
3
PLP-6BA
PLFY-P100VBM-E
12.5
11.2
11.6
10.0
8.1
0.73
0.79
0.14
0.15
21-24-27-29
34-37-39-41
27(6)
840(950)
840(950)
298(35)
220-240v, 50Hz
Single
0.94
1.00
6
3
PLP-6BA
Technical Information
Power cassettes offer 72 different airflow patterns, with the ability to handle a multitude of ceiling applications up to4.2 meters in height. The easy to install, slim unit is ideal for maintaining constant temperatures, thanks to adjustablevanes that allow users to precisely direct air where it’s needed.
The Mitsubishi Electric airflow control mechanism has been improved and uses wider vanes so that the unit reducesdrafts and smudging, whilst a high performance drain pump on the drain lift mechanism allows drain water to be lifted up to 850mm from the ceiling surface.
� Handy corner pocket design simplifies maintenance
� Airflow controllable for ceiling heights up to 4.2m, with automatic adjustment of fan speed
� Reduced draft air distribution, with independent vane control
� Drain pump as standard, 850mm from drain pan
� Filter lowering operation down to 4m (optional PLP-6BAJ grille required)
� Optional ‘I See Sensor’ for energy saving and smooth temperature control throughout the room
� For further information on the features of this cassette, please see page 60
Page 164
PLFY-P32, 40, 50, 63, 80, 100, 125VBM-E
MODELS
PLFY-P32-80VBM-E
PLFY-P100-125VBM-E
A
241
281
B
258
298
Upper View >
Lower View >
Side View >
Cit
y M
ulti
Ran
ge 2
008
PLFY
-P-V
BM-E
Dimensions
Page 165
PLFY-P-VCM-E
The compact size of this unit is ideal for 600x600mm ceilings and with a depth of 208mm, this lightweight unit makes installation a breeze. This unit also comes complete with a long life filter that will last for approximately 2,500 hours.
600x600 4-Way Blow Ceiling Cassette Indoor Unit
PLFY-P-VCM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi-Hi
NOISE (dBA) Lo-Mi-Hi
WEIGHT (kg) (Grille)
DIMENSIONS (mm) Width (Grille)
Depth (Grille)
Height (Grille)
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
GRILLE MODEL REFERENCE
PLFY-P20VCM-E
2.5
2.2
2.3
2.1
1.6
0.86
1.00
0.05
0.05
8-9-10
28-31-35
15.5(3)
570(650)
570(650)
208(20)
220-240v, 50Hz
Single
0.23
0.23
6
3
SLP-2AA
PLFY-P25VCM-E
3.2
2.8
3.0
2.6
2.0
0.81
0.90
0.05
0.05
8-9-10
28-31-37
15.5(3)
570(650)
570(650)
208(20)
220-240v, 50Hz
Single
0.23
0.23
6
3
SLP-2AA
PLFY-P32VCM-E
4.0
3.6
3.7
3.4
2.6
0.76
0.85
0.06
0.06
8-9-11
29-33-38
17(3)
570(650)
570(650)
208(20)
220-240v, 50Hz
Single
0.28
0.28
6
3
SLP-2AA
PLFY-P40VCM-E
5.0
4.5
4.6
4.3
3.3
0.70
0.76
0.06
0.06
8-9-11
30-34-39
17(3)
570(650)
570(650)
208(20)
220-240v, 50Hz
Single
0.28
0.28
6
3
SLP-2AA
Technical Information
� Compact size for handy installation and easy maintenance
� Only 208mm high
� Fresh air duct facility
Page 166
PLFY-P20, 25, 32, 40VCM-E
Lower View >
Side View >
Cit
y M
ulti
Ran
ge 2
008
PLFY
-P-V
CM
-E
Dimensions
Page 167
PLFY-P-VLMD-E2-Way Blow Ceiling Cassette Indoor Unit
PLFY-P-VLMD-E - INDOOR UNIT
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
NOISE (dBA) Lo-Mi1-Mi2-Hi
WEIGHT (kg) (Grille)
DIMENSIONS (mm) Width (Grille)
Depth (Grille)
Height (Grille)
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
GRILLE MODEL REFERENCE
PLFY-P20VLMD-E
2.5
2.2
2.3
2.1
1.6
0.81
0.94
0.065
0.072
6.5-8.0-9.5
27-30-33
23(6.5)
776(1080)
634(710)
290(20)
220-240v,
50Hz
Single
0.30
0.36
6
3
CMP-40VLW-B
PLFY-P25VLMD-E
3.2
2.8
3.0
2.6
2.0
0.77
0.85
0.065
0.072
6.5-8.0-9.5
27-30-33
23(6.5)
776(1080)
634(710)
290(20)
220-240v,
50Hz
Single
0.30
0.36
6
3
CMP-
40VLW-B
PLFY-P32VLMD-E
4.0
3.6
3.7
3.4
2.6
0.74
0.81
0.065
0.072
6.5-8.0-9.5
27-30-33
24(6.5)
776(1080)
634(710)
290(20)
220-240v,
50Hz
Single
0.30
0.36
6
3
CMP-40VLW-B
PLFY-P40VLMD-E
5.0
4.5
4.6
4.3
3.3
0.67
0.73
0.074
0.081
7.0-8.5-10.5
29-33-36
24(6.5)
776(1080)
634(710)
290(20)
220-240v,
50Hz
Single
0.34
0.40
6
3
CMP-40VLW-B
PLFY-P50VLMD-E
6.3
5.6
5.8
5.3
4.1
0.70
0.73
0.075
0.082
9.0-11.0-12.5
31-34-37
27(7.5)
946(1250)
634(710)
290(20)
220-240v,
50Hz
Single
0.35
0.41
6
3
CMP-63VLW-B
PLFY-P63VLMD-E
8.0
7.1
7.4
6.7
5.2
0.72
0.77
0.094
0.101
10.0-13.0-15.5
32-37-39
28(7.5)
946(1250)
634(710)
290(20)
220-240v,
50Hz
Single
0.43
0.49
6
3
CMP-63VLW-B
PLFY-P80VLMD-E
10.0
9.0
9.2
8.5
6.5
0.71
0.77
0.140
0.147
15.5-18.5-22.0
33-36-39
44(12.5)
1446(1750)
634(710)
290(20)
220-240v,
50Hz
Single
0.66
0.72
6
3
CMP-100VLW-B
PLFY-P100VLMD-E
12.5
11.2
11.6
10.6
8.1
0.73
0.79
0.150
0.157
17.5-21.0-25.0
36-39-42
47(12.5)
1446(1750)
634(710)
290(20)
220-240v,
50Hz
Single
0.69
0.75
6
3
CMP-100VLW-B
PLFY-P125VLMD-E
16.0
14.0
14.8
13.2
10.2
0.73
0.80
0.27
0.28
24-27-30-33
40-42-44-46
56(13)
1708(2010)
606(710)
290(20)
220-240v,
50Hz
Single
1.33
1.35
6
3
CMP-125VLW-B
Technical Information
The PLFY-P-VLMD-E cassette unit fits into the space in a suspended ceiling to provideheating or cooling. This new unit has been redesigned with lower unit height and lower noise levels.
� Light unit for ease of installation
� Terminal block on outside of unit for easy wiring
� Drain lift-pump mechanism as standard
� Newly designed decoration panel with air flow switching and swing functions as standard
Page 168
PLFY-P20, 25, 32, 40, 50, 63, 80, 100VLMD-E
PLFY-P125VLMD-E
Front View > Upper View >
Lower View >
Side View > Upper View >
Side View >
Rear View > Lower View >
Cit
y M
ulti
Ran
ge 2
008
PLFY
-P-V
LMD
-E
Dimensions
Page 169
PMFY-P-VBM-E1-Way Blow Ceiling Cassette Indoor Unit
PMFY-P-VBM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
NOISE (dBA) Lo-Mi1-Mi2-Hi
WEIGHT (kg) (Grille)
DIMENSIONS (mm) Width (Grille)
Depth (Grille)
Height (Grille)
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
GRILLE MODEL REFERENCE
PMFY-P20VBM-E
2.5
2.2
2.3
2.1
1.6
0.81
0.94
0.042
0.042
6.5-7.2-8.0-8.7
27-30-33-35
14(3)
812(1000)
395(470)
230(30)
220-240v, 50Hz
Single
0.20
0.20
6
3
PMP-40BM
PMFY-P25VBM-E
3.2
2.8
3.0
2.6
2.0
0.77
0.90
0.044
0.044
7.3-8.0-8.6-9.3
32-34-36-37
14(3)
812(1000)
395(470)
230(30)
220-240v, 50Hz
Single
0.21
0.21
6
3
PMP-40BM
PMFY-P32VBM-E
4.0
3.6
3.7
3.4
2.6
0.71
0.77
0.044
0.044
7.3-8.0-8.6-9.3
32-34-36-37
14(3)
812(1000)
395(470)
230(30)
220-240v, 50Hz
Single
0.21
0.21
6
3
PMP-40BM
PMFY-P40VBM-E
5.0
4.5
4.6
4.3
3.3
0.70
0.76
0.054
0.054
7.7-8.7-9.7-10.7
33-35-37-39
14(3)
812(1000)
395(470)
230(30)
220-240v, 50Hz
Single
0.26
0.26
6
3
PMP-40BM
Technical Information
Utilising a compact and lightweight body, the unit is perfect for applications where ceiling space is limited. A total body weight of 14kg makes it one of the lightest available, latest fan technology also makes it one of the quietest.
� Compact size for handy installation and easy maintenance
� Newly developed airflow control technology reduces noise levels to only 27dBA
� Drain lift pump mechanism allows the drain to be positioned anywhere up to 600mm from the ceiling’s surface
� Only 230mm high
� Fresh air duct facility
Page 170
Lower View >
Side View >
Upper View >
Front View >
PMFY-P20, 25, 32, 40VBM-E
Cit
y M
ulti
Ran
ge 2
008
PMFY
-P-V
BM-E
Dimensions
Page 171
PEFY-P-VMS1-EUltra Thin Ceiling Concealed Ducted Indoor Unit
The ultra thin ceiling concealed ducted indoor unit offers increased flexibility and is particularlysuitable for places where low noise operation is desired from a slimline body.
� Ultra thin body - height of only 200mm & width of only 790mm (P15-32)
� Extremely quiet operation - as low as 22dBA
� Cooling operation set temperature can be set down to 14°C db
� Static pressure of 5-50Pa
� Now available in a size 15, ideal for hotel rooms
PEFY-P-VMS1-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi-Hi
EXTERNAL STATIC PRESSURE (Pa) Lo-Mi1-Mi2-Hi
NOISE (dBA) (5Pa) Lo-Mi-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PEFY-P15VMS1-E
1.9
1.7
1.8
1.5
1.2
0.93
1.00
0.03
0.05
5.0-6.0-7.0
5-15-35-50
22-24-28
19
790
700
200
220-240v, 50Hz
Single
0.31
0.42
6
3
PEFY-P25VMS1-E
3.2
2.8
3.0
2.5
2.0
0.84
0.90
0.04
0.06
5.5-7.0-9.0
5-15-35-50
24-26-30
19
790
700
200
220-240v, 50Hz
Single
0.39
0.50
6
3
PEFY-P40VMS1-E
5.0
4.5
4.6
4.0
3.3
0.75
0.82
0.05
0.07
8.0-9.5-11.0
5-15-35-50
28-30-33
24
990
700
200
220-240v, 50Hz
Single
0.45
0.56
6
3
PEFY-P63VMS1-E
8.0
7.1
7.4
6.3
5.2
0.75
0.79
0.07
0.09
12.0-14.0-16.5
5-15-35-50
30-33-36
28
1190
700
200
220-240v, 50Hz
Single
0.61
0.72
6
3
PEFY-P20VMS1-E
2.5
2.2
2.3
2.0
1.6
0.85
1.00
0.03
0.05
5.5-6.5-8.0
5-15-35-50
23-25-29
19
790
700
200
220-240v, 50Hz
Single
0.36
0.47
6
3
PEFY-P32VMS1-E
4.0
3.6
3.7
3.2
2.6
0.78
0.85
0.05
0.07
6.0-8.0-10.0
5-15-35-50
24-27-32
20
790
700
200
220-240v, 50Hz
Single
0.39
0.50
6
3
PEFY-P50VMS1-E
6.3
5.6
5.8
5.0
4.1
0.74
0.78
0.07
0.09
9.5-11.0-13.0
5-15-35-50
30-32-35
24
990
700
200
220-240v, 50Hz
Single
0.56
0.67
6
3
Technical Information
Page 172
PEFY-P15, 20, 25, 32, 40, 50, 63 VMS1-E
A BPEFY-P15-32VMS1-E 700 752
PEFY-P40-50VMS1-E 900 952
C798
998
D660
860
E7
9
F600
800
PEFY-P63VMS1-E 1100 1152 1198 1060 11 1000
Model
Side View >
Front View >
Upper View >
Cit
y M
ulti
Ran
ge 2
008
PEFY
-P-V
MS1
-E
Dimensions
Page 173
PEFY-P-VMM-ECeiling Concealed Ducted Indoor Unit
PEFY-P-VMM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi-Hi
EXTERNAL STATIC PRESSURE (Pa) - Lo-Mi-Hi
NOISE (dBA) Lo-Mi-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PEFY-P20VMM-E
2.5
2.2
2.3
2.1
1.6
0.86
0.94
0.15
0.15
6.0-7.2-8.5
30-50-100
27-30-32
27
815
700
295
220-240v,
50Hz
Single
0.73
0.73
6
3
PEFY-P25VMM-E
3.2
2.8
3.0
2.6
2.0
0.77
0.85
0.15
0.15
6.0-7.2-8.5
30-50-100
27-30-32
27
815
700
295
220-240v,
50Hz
Single
0.73
0.73
6
3
PEFY-P32VMM-E
4.0
3.6
3.7
3.4
2.6
0.76
0.85
0.17
0.17
7.5-9.0-10.5
30-50-100
28-32-35
27
815
700
295
220-240v,
50Hz
Single
0.81
0.81
6
3
PEFY-P40VMM-E
5.0
4.5
4.6
4.3
3.3
0.77
0.85
0.19
0.19
10-12-14
30-50-100
31-34-37
33
935
700
295
220-240v,
50Hz
Single
0.92
0.92
6
3
PEFY-P50VMM-E
6.3
5.6
5.8
5.3
4.1
0.75
0.83
0.20
0.20
12.0-14.5-17.0
30-50-100
31-35-38
33
935
700
295
220-240v,
50Hz
Single
0.98
0.98
6
3
PEFY-P63VMM-E
8.0
7.1
7.4
6.7
5.2
0.75
0.81
0.22
0.22
13.5-16.2-19.0
30-50-100
31-35-38
42
1175
700
295
220-240v,
50Hz
Single
1.07
1.07
6
3
PEFY-P80VMM-E
10.0
9.0
9.2
8.5
6.5
0.72
0.78
0.25
0.25
14.5-18.0-21.0
30-50-100
32-36-39
42
1175
700
295
220-240v,
50Hz
Single
1.15
1.15
6
3
PEFY-P100VMM-E
12.5
11.2
11.6
10.6
8.1
0.78
0.88
0.29
0.29
23-33
50-130
40-44
62
1415
740
325
220-240v,
50Hz
Single
1.34
1.34
6
3
PEFY-P125VMM-E
16.0
14.0
14.8
13.2
10.2
0.77
0.85
0.40
0.40
28-40
50-130
42-45
65
1415
740
325
220-240v,
50Hz
Single
1.90
1.90
6
3
Technical Information
The PEFY-P-VMM-E ducted indoor unit is concealed within the ceiling space to allow unobtrusive air conditioning. Flexibility of duct layout allows air flow patterns to be arranged to suit any application.
� Reduced noise levels thanks to the use of a newlydesigned centrifugal fan - as low as 27dBA
� Drain lift-pump (option), 550mm of lift
� Complete flexibility in air conditioning design
� Cooling operation set temperature can be set down to 14ºC db
Page 174
PEFY-P20, 25, 32, 40, 50, 63, 80VMM-E
PEFY-P100, 125VMM-E
1252
1252
1252
360
360
360370
370
370
1310
1284
Upper View >
Side View >
Upper View >
Front View >
Side View > Front View >
A BPEFY-P20-32VMM-E 652 245
PEFY-P40-50VMM-E 772 305PEFY-P63-80VMM-E 1012 280
C-
-290
D710
8301070
E684
8041044
Model
Cit
y M
ulti
Ran
ge 2
008
PEFY
-P-V
MM
-E
Dimensions
Page 175
PEFY-P-VMH-EHigh Static Pressure Ceiling Concealed Ducted Indoor Unit
PEFY-P-VMH-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Hi
EXTERNAL STATIC PRESSURE (Pa) - Lo-Mi-Hi
NOISE (dBA) Lo-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PEFY-P80VMH-E
10.0
9.0
9.2
8.5
6.5
0.74
0.83
0.32
0.32
18-25
100-150-200
38-43
50
1000
900
380
220-240v,
50Hz
Single
1.47
1.47
6
3
PEFY-P100VMH-E
12.5
11.2
11.6
10.6
8.1
0.80
0.91
0.48
0.48
26.5-38.0
100-150-200
38-44
70
1200
900
380
220-240v,
50Hz
Single
2.34
2.34
6
3
PEFY-P125VMH-E
16.0
14.0
14.8
13.2
10.2
0.74
0.81
0.48
0.48
26.5-38.0
100-150-200
38-44
70
1200
900
380
220-240v,
50Hz
Single
2.34
2.34
6
3
PEFY-P140VMH-E
18.0
16.0
16.6
15.1
11.6
0.74
0.82
0.48
0.48
28-40
100-150-200
38-44
70
1200
900
380
220-240v,
50Hz
Single
2.35
2.35
6
3
Technical Information
With improved design flexibility as a result of increased external static pressure, the PEFY-P-VMH-Eallows authentic duct air conditioning within the strictest aesthetic confines.
� External static pressure of 200Pa
� Greater flexibility for duct extension, branching air outlet configuration
� Reduced noise levels thanks to the use of newly designed centrifugal fan
� Duct can be connected to intake side
� Drain lift-pump (option) 550mm of lift
� Cooling operation set temperature can be set down to 14ºC db
Page 176
PEFY-P80, 100, 125, 140VMH-E
Side View >
Upper View >
Cit
y M
ulti
Ran
ge 2
008
PEFY
-P-V
MH
-E
Dimensions
Page 177
PCFY-P-VGM-ECeiling Suspended Indoor Unit
PCFY-P-VGM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
NOISE (dBA) Lo-Mi1-Mi2-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PCFY-P40VGM-E
5.0
4.5
4.6
4.3
3.3
0.72
0.79
0.10
0.10
8-10-11-12
29-33-36-38
27
1000
680
210
220-240v, 50Hz
Single
0.46
0.46
6
3
PCFY-P63VGM-E
8.0
7.1
7.4
6.7
5.2
0.72
0.79
0.13
0.13
12-14-16-18
32-34-37-39
34
1310
680
210
220-240v, 50Hz
Single
0.60
0.60
6
3
PCFY-P100VGM-E
12.5
11.2
11.6
10.6
8.1
0.71
0.77
0.16
0.16
18-20-23-25
36-38-41-43
37
1310
680
270
220-240v, 50Hz
Single
0.73
0.73
6
3
PCFY-P125VGM-E
16.0
14.0
14.8
13.2
10.2
0.70
0.76
0.24
0.24
26-28-32-35
37-39-42-44
43
1620
680
270
220-240v, 50Hz
Single
1.10
1.10
6
3
Technical Information
Designed for ultra-quiet operation and easy maintenance, the unit provides comfor table air conditioning for a wide range of applications where floor or wall space cannot be used practically.
� Indoor unit designed for direct ceiling suspension
� Flush to wall installation for concealment of service connections
� Drain piping can be connected from left or right
Page 178
PCFY-P40, 63, 100, 125VGM-E
Lower View >
Upper View >
Front View >
Cit
y M
ulti
Ran
ge 2
008
PCFY
-P-V
GM
-E
Dimensions
Page 179
PKFY-P-VBM-E/VGM-E/VFM-EWall Mounted Indoor Units
PKFY-P-VBM-E / VGM-E / VFM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
NOISE (dBA) Lo-Mi1-Mi2-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PKFY-P20VBM-E
2.5
2.2
2.3
2.1
1.6
0.71
0.75
0.04
0.04
4.9-5.2-5.6-5.9
29-31-34-36
10
815
225
295
220-240v, 50Hz
Single
0.20
0.20
6
3
PKFY-P25VBM-E
3.2
2.8
3.0
2.6
2.0
0.73
0.80
0.04
0.04
4.9-5.2-5.6-5.9
29-31-34-36
10
815
225
295
220-240v, 50Hz
Single
0.20
0.20
6
3
PKFY-P32VGM-E
4.0
3.6
3.7
3.4
2.6
0.79
0.88
0.07
0.07
8.0-9.5-10.5-11.5
33-36-38-41
16
990
235
340
220-240v, 50Hz
Single
0.32
0.32
6
3
PKFY-P40VGM-E
5.0
4.5
4.6
4.3
3.3
0.74
0.82
0.07
0.07
8.0-9.5-10.5-11.5
33-36-38-41
16
990
235
340
220-240v, 50Hz
Single
0.32
0.32
6
3
PKFY-P63VFM-E
8.0
7.1
7.4
6.7
5.2
0.78
0.85
0.12
0.12
15-20
39-45
24
1400
235
340
220-240v, 50Hz
Single
0.55
0.55
6
3
PKFY-P50VGM-E
6.3
5.6
5.8
5.3
4.1
0.72
0.78
0.07
0.07
9-10-11-12
34-37-40-43
16
990
235
340
220-240v, 50Hz
Single
0.32
0.32
6
3
Technical Information
An elegant design combined with compact dimensions and quiet operationmake the PKFY-P an ideal unit choice. Noise levels are significantly reducedthanks to a unique airflow passage design that not only makes the unit one of the quietest in the industry, but also suppresses condensation and prevents mixing with secondary air.
� Compact design - only 815mm wide (VBM-E)
� Front grille opening for easy cleaning
� Front power supply for easy wiring after installation
� 5-way piping provides more flexibility in selection of installation sites
Page 180
PKFY-P20, 25VBM-E
PKFY-P32, 40, 50VGM-E
Right Side View >Front View >
Right Side View >Front View >
PKFY-P63VFM-E
Right Side View >Front View >
Cit
y M
ulti
Ran
ge 2
008
PKFY
-P-V
BM-E
/ PK
FY-P
-VG
M-E
/ PK
FY-P
-VFM
-E
Dimensions
Page 181
PFFY-P-VLRM-EFloor Standing Concealed Indoor Unit
PFFY-P-VLRM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Hi
NOISE (dBA) Lo-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PFFY-P20VLRM-E
2.5
2.2
2.3
2.1
1.7
0.90
1.00
0.04
0.04
5.5-6.5
34-40
18.5
886
220
639
220-240v, 50Hz
Single
0.19
0.19
6
3
PFFY-P25VLRM-E
3.2
2.8
3.0
2.6
2.0
0.81
0.95
0.04
0.04
5.5-6.5
34-40
18.5
886
220
639
220-240v, 50Hz
Single
0.19
0.19
6
3
PFFY-P32VLRM-E
4.0
3.6
3.7
3.4
2.6
0.74
0.81
0.06
0.06
7-9
35-40
20
1006
220
639
220-240v, 50Hz
Single
0.29
0.29
6
3
PFFY-P40VLRM-E
5.0
4.5
4.6
4.3
3.3
0.72
0.79
0.065
0.065
9-11
38-43
21
1006
220
639
220-240v, 50Hz
Single
0.32
0.32
6
3
PFFY-P50VLRM-E
6.3
5.6
5.8
5.3
4.1
0.74
0.80
0.085
0.085
12-14
38-43
25
1246
220
639
220-240v, 50Hz
Single
0.40
0.40
6
3
PFFY-P63VLRM-E
8.0
7.1
7.4
6.7
5.2
0.73
0.79
0.10
0.10
12-15.5
40-46
27
1246
220
639
220-240v, 50Hz
Single
0.46
0.46
6
3
A compact concealed unit providing simple, effective air conditioning in perimeter zones. The unit is easy to install and at only 220mm deep offers an unobtrusive method of delivering highly efficient air-conditioning performance.
� Concealed unit for hidden installation
� Ideal for perimeter refurbishments
� Cooling operation set temperature can be set down to 14ºC db
Technical Information
Page 182
PFFY-P20, 25, 32, 40, 50, 63VLRM-E
Side View >
Upper View >
Front View >
Cit
y M
ulti
Ran
ge 2
008
PFFY
-P-V
LRM
-E
Dimensions
Page 183
PFFY-P-VLRMM-EFloor Standing Concealed Indoor Unit
A compact concealed unit providing simple, effective air conditioning in perimeter zones. The unit is easy to install and at only 220mm deep offers an unobtrusive method of delivering highly efficient air-conditioning performance.
PFFY-P-VLRMM-E - INDOOR UNIT
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi-Hi
EXTERNAL STATIC PRESSURE (Pa) Lo-Mi1-Hi
NOISE (dBA) (20Pa) Lo-Mi-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PFFY-P20VLRMM-E
2.5
2.2
2.3
2.0
1.6
0.80
0.88
0.04
0.04
4.5-5.5-6.5
20-40-60
31-36-40
18.5
886
220
639
220-240v, 50Hz
Single
0.34
0.34
6
3
PFFY-P32VLRMM-E
4.0
3.6
3.7
3.2
2.6
0.75
0.81
0.04
0.04
6.5-7.5-9
20-40-60
27-32-37
20
1006
220
639
220-240v, 50Hz
Single
0.38
0.38
6
3
PFFY-P50VLRMM-E
6.3
5.6
5.8
5.0
4.1
0.76
0.80
0.05
0.05
10-12-14
20-40-60
32-37-41
25
1246
220
639
220-240v, 50Hz
Single
0.48
0.48
6
3
PFFY-P25VLRMM-E
3.2
2.8
3.0
2.5
2.0
0.76
0.80
0.04
0.04
4.5-5.5-6.5
20-40-60
31-36-40
18.5
886
220
639
220-240v, 50Hz
Single
0.34
0.34
6
3
PFFY-P40VLRMM-E
5.0
4.5
4.6
4.0
3.3
0.75
0.79
0.05
0.05
8-9.5-11
20-40-60
30-36-40
21
1006
220
639
220-240v, 50Hz
Single
0.43
0.43
6
3
PFFY-P63VLRMM-E
8.0
7.1
7.4
6.3
5.2
0.73
0.79
0.07
0.07
11-13-15.5
20-40-60
35-40-44
27
1246
220
639
220-240v, 50Hz
Single
0.59
0.59
6
3
Technical Information
Page 184
� Reduced noise levels compared to the PFFY-P-VLRM-E version
� Cooling operation set temperature can be set down to 14ºC db
� Static pressure. The new unit has 3 static pressure settings- 20/40/60Pa ideal for ducting in the perimeter zone
� Concealed unit for hidden installation. The unit can be hiddenbehind a wardrobe in a hotel, then ducted above and below the wardrobe doors. This offers lower noise, less disruption and a low visual impact
PFFY-P20, 25, 32, 40, 50, 63VLRMM-E
Side View >
Upper View >
Front View >
Cit
y M
ulti
Ran
ge 2
008
PFFY
-P-V
LRM
M-E
Dimensions
Page 185
PFFY-P-VLEM-EFloor Standing Exposed Indoor Unit
PFFY-P-VLEM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Hi
NOISE (dBA) Lo-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PFFY-P20VLEM-E
2.5
2.2
2.3
2.1
1.7
0.90
1.00
0.04
0.04
5.5-6.5
34-40
23
1050
220
630
220-240v, 50Hz
Single
0.19
0.19
6
3
PFFY-P25VLEM-E
3.2
2.8
3.0
2.6
2.0
0.81
0.95
0.04
0.04
5.5-6.5
34-40
23
1050
220
630
220-240v, 50Hz
Single
0.19
0.19
6
3
PFFY-P32VLEM-E
4.0
3.6
3.7
3.4
2.6
0.74
0.81
0.06
0.06
7-9
35-40
25
1170
220
630
220-240v, 50Hz
Single
0.29
0.29
6
3
PFFY-P40VLEM-E
5.0
4.5
4.6
4.3
3.3
0.72
0.79
0.065
0.065
9-11
38-43
26
1170
220
630
220-240v, 50Hz
Single
0.32
0.32
6
3
PFFY-P50VLEM-E
6.3
5.6
5.8
5.3
4.1
0.74
0.80
0.085
0.085
12-14
38-43
30
1410
220
630
220-240v, 50Hz
Single
0.40
0.40
6
3
PFFY-P63VLEM-E
8.0
7.1
7.4
6.7
5.2
0.73
0.79
0.10
0.10
12-15.5
40-46
32
1410
220
630
220-240v, 50Hz
Single
0.46
0.46
6
3
A compact cased unit providing simple, effective air conditioning in perimeter zones. The unit is easy to install, and at only 220mmdeep offers an unobtrusive method of delivering a highly efficient air-conditioning performance.
� Remote controller can be incorporated into the main unit
� Cooling operation set temperature can be set down to 14ºC db
Technical Information
Page 186
PFFY-P20,25,32,40,50,63VLEM-E
Side View >
Upper View >
Front View >
Cit
y M
ulti
Ran
ge 2
008
PFFY
-P-V
LEM
-E
Dimensions
Page 187
PFFY-P-VKM-EFloor Standing Exposed Indoor Unit
PFFY-P-VKM-E - INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
High Sensible Cooling (UK)
SHF (UK)
High Sensible (UK)
POWER INPUT (kW) Heating (nominal)
Cooling (nominal)
AIRFLOW (m3/min) Lo-Mi1-Mi2-Hi
NOISE (dBA) Lo-Mi1-Mi2-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Heating
Cooling
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
PFFY-P20VKM-E
2.5
2.2
2.3
2.1
1.6
0.81
0.88
0.025
0.025
5.9-6.8-7.6-8.7
27-31-34-37
15
700
200
600
220-240v, 50Hz
Single
0.20
0.20
6
3
PFFY-P25VKM-E
3.2
2.8
3.0
2.6
2.0
0.77
0.85
0.025
0.025
6.1-7.0-8.0-9.1
28-32-35-38
15
700
200
600
220-240v, 50Hz
Single
0.20
0.20
6
3
PFFY-P32VKM-E
4.0
3.6
3.7
3.4
2.6
0.71
0.77
0.025
0.025
6.1-7.0-8.0-9.1
28-32-35-38
15
700
200
600
220-240v, 50Hz
Single
0.20
0.20
6
3
PFFY-P40VKM-E
5.0
4.5
4.6
4.3
3.3
0.70
0.76
0.028
0.028
8.0-9.0-9.5-10.7
35-38-42-44
15
700
200
600
220-240v, 50Hz
Single
0.24
0.24
6
3
The PFFY-P-VKM-E series is extremely versatile and is designed for wall attached installation at floor level. The auto swing vane provides a more natural and comfortable airflow throughout the room and the lightweight, compact design makes installation easy.
� Pure white, slimline design
� Upper and lower vanes for optimum, powerful and efficient air distribution
Technical Information
Page 188
PFFY-P20,25,32,40VKM-E
Front View >
Upper View >
Side View >C
ity
Mul
tiR
ange
200
8PF
FY-P
-VK
M-E
Dimensions
Page 189
OUTDOOR AIR PROCESSING INDOOR UNITMODEL REFERENCE
CAPACITY (kW) Heating (nominal)
Cooling (nominal)
Heating (UK)
Cooling (UK)
POWER INPUT (kW)
AIRFLOW (m3/h) Lo-Hi
NOISE (dBA) Lo-Hi
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
RUNNING CURRENT (A) Lo-Hi
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
GUF-50RD3
6.42 (2.25)
5.29 (1.66)
5.93 (2.08)
5.03 (1.58)
0.265
400-500
29.5-34.5
54
1016
1288
317
220-240v, 50Hz
Single
0.70-1.15
6
3
GUF-100RD3
13.00 (4.70)
10.81 (3.49)
12.01 (4.34)
10.27 (3.32)
0.505
800-1000
34-39
92
1231
1580
398
220-240v, 50Hz
Single
1.73-2.20
6
3
GUF-50RD3 & GUF100RD3Lossnay Outdoor Air Processing Indoor Unit
Attention
1. Nominal Condition: Cooling/Heating capacity indicates the value of operation under the following air condition and above air volume.Cooling: Indoor 27ºC DB/19.5ºC WB, Outdoor 35ºC DB/24ºC WB.Heating: Indoor 21ºC DB/14.6ºC WB, Outdoor 7ºC DB/6ºC WB.
2. UK Condition:Summer: Indoor 21ºC, Outdoor 27ºCWinter : Indoor 21ºC, Outdoor -1ºCWB
3. The figures in ( ) indicates the heat recovery at Lossnay core.
4. The current, input and efficiency are based on the above air volume.
5. The air nozzle noise (45º angle 1.5m ahead) is about 6dB greater than the indicated value. (High notch).
6. Specifications may be subject to change without notice.
The GUF-50RD3 and GUF-100RD3 outdoor air processing units can be used with any of the extensive range of City Multi indoor units to provide ventilation, dust removal, humidification and heat recovery.
� A combination of a Lossnay & City Multi indoor in a single unit
� Air temperature in any room can be adjusted to the desired temperature via this unit which is used as an indoor unit of the City Multi air conditioning system
� The ventilating and air conditioning functions are integrated in a single unit, saving space and installation costs
� Heat recovery helps to save energy - a benefit that’s not only good for the environment, but also great for cutting energy costs
� Free cooling is also available should outdoor conditions be suitable
Technical Information
Page 190
GUF-50/100RD3
Side View >
Upper View >
Front View >C
ity
Mul
tiR
ange
200
8G
UF-
50R
D3
and
GU
F100
RD
3
Dimensions
Page 191
PQFY-P
PQFY-P140
MODEL REFERENCE
CAPACITY (kW) Heating (nominal)
PIPE SIZE mm(in) Gas Refrigerant
Liquid Refrigerant
Water
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
MAINS CABLE No. Cores
PQFY-P140
14.0
15.88 (5/8”)
9.52 (3/8”)
22
32
500
410
560
220-240v, 50Hz
Single
3
PQFY-P250
25.0
19.05 (3/4”)
9.52 (3/8”)
28
50
610
510
560
220-240v, 50Hz
Single
3
PQFY-PVRF Heat Pump Boiler
Flow RatePressure Drop
l/s
kPA
0.38
11.72
0.45
15.86
0.53
20.69
0.61
25.51
0.68
30.34
0.76
36.54
0.83
42.75
PQFY-P250
Flow RatePressure Drop
l/s
kPA
0.61
14.48
0.76
20.69
0.91
27.58
1.06
35.16
1.21
44.13
1.36
53.09
1.52
62.06
Note: The water flow rate can be above or below these values, but no pressure drop operating data can be provided.
It is well known in the air conditioning industry that heat pumps are proven to provide highly efficient cooling. However,in line with other forward-thinking countries, such as Sweden and Switzerland, Mitsubishi Electric have now designed aheat pump boiler to provide heating and hot water, suitable for underfloor heating or swimming pools. Heat pumptechnology is largely untapped and offers great potential with incredible design flexibility, excellent use of energy andgreatly reduced CO2 emissions.
The cooling operation of an air conditioning system that effectively extracts heat from a space, will normally be achieved atbetween 3.5 to 4.0 COP. This in itself is an efficient system. However, by recovering that heat and using it to heat up waterthe efficiency of the system increases dramatically to over 6.0 COP. Without the use of a Heat Pump Boiler, these levels ofefficiency are rarely achieved in Spring and Autumn, when different rooms may need heating and cooling from the airconditioning at the same time.
By using the VRF Heat Pump Boiler in a permanent heat recovery application, theseefficiencies are now possible all year round. This provides a reduction in running costs and CO2 emissions, both of which play a crucial role when obtaining planning permission as covered by the new Part L2 Legislation.
There is a further reduction in capital costs as there is very little or no requirement for gas boilers and associated works. Particularly when the small amount of heatingrequired in order to boost domestic hot water from the 45ºC (produced by the heat pump), to the required 60ºC supply temperature, can be provided by means of electric. Thus negating the need for the installation of a gas supply entirely.
Technical Information
An overview of the use of Heat Pump Boilers
Unit Flow Rate & Pressure DropFor calculating the Water Flow Rate please use the following calculation:Capacity (kW) = Flow Rate of Water (l/s) x Specific Heat Capacity of Water x (Outlet Water Temp(ºC) - Inlet Water Temp (ºC))
Specific Heat Capacity of water is normally 4.2Kj/KgK
Page 192
PQFY-P140
PQFY-P250
Upper View >Front View >
Upper View >Front View >
Front control panel not shown
Front control panel not shown
Cit
y M
ulti
Ran
ge 2
008
PQFY
-P
Dimensions
Page 193
BC Controllers
BC CONTROLLERSMODEL REFERENCE
NUMBER OF CONNECTIONS
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (KW)
RUNNING CURRENT (A)
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
CMB-P104V-G
4
24
648
362 + 70
284
220-240v, 50Hz
Single
0.085
0.36
6
3
CMB-P106V-G
6
29
648
362 + 70
284
220-240v, 50Hz
Single
0.123
0.52
6
3
CMB-P105V-G
5
27
648
362 + 70
284
220-240v, 50Hz
Single
0.104
0.44
6
3
Technical Information
At the heart of both the R2 and WR2 Series, the BC controller makes simultaneous heating and cooling possible. It has the inherent ‘intelligence’ to be the system’s decision-maker.
� Transferring energy around the system
� Drawing on energy from the heat source units/outdoor units
� Directing energy as requested by the individual indoor units
� Instructs the heat source unit/outdoor unit on the amount of refrigerant (liquid or gas) that is required to achieve the requested cooling or heating requirements
� Allows unique 2-pipe heat recovery application
� HIC Circuit for improved efficiency
Note: CMB-P-V-G units are for use with PURY-(E)P200-350 YHM-A & PQRY-P200/250YGM-A outdoor units only.
SLAVE BC CONTROLLERSMODEL REFERENCE
NUMBER OF CONNECTIONS
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (KW)
RUNNING CURRENT (A)
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
CMB-P104V-GB
4
22
648
362 + 70
284
220-240v, 50Hz
Single
0.076
0.32
6
3
CMB-P1016V-HB
16
57
1098
362 + 70
284
220-240v, 50Hz
Single
0.301
1.26
6
3
CMB-P108V-GB
8
32
648
362 + 70
284
220-240v, 50Hz
Single
0.151
0.63
6
3
Note: CMB-P1016V-HB can be connected to a CMB-P1016V-HA.
MASTER BC CONTROLLERSMODEL REFERENCE
NUMBER OF CONNECTIONS
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
ELECTRICAL SUPPLY
PHASE
POWER INPUT (KW)
RUNNING CURRENT (A)
FUSE RATING (BS88) – HRC (A)
MAINS CABLE No. Cores
CMB-P108V-GA
8
44
1110
450 + 70
289
220-240v, 50Hz
Single
0.161
0.68
6
3
CMB-P1013V-GA
13
57
1110
450 + 70
289
220-240v, 50Hz
Single
0.255
1.07
6
3
CMB-P1016V-HA
16
73
1110
450 + 70
289
220-240v, 50Hz
Single
0.312
1.30
6
3
CMB-P1010V-GA
10
49
1110
450 + 70
289
220-240v, 50Hz
Single
0.198
0.83
6
3
CMB-P1016V-GA
16
64
1110
450 + 70
289
220-240v, 50Hz
Single
0.312
1.30
6
3
Page 194
Note: CMB-P-V-GA units are for use with PURY-(E)P200-650Y(S)HM-A & PQRY-P200-500YSGM-A outdoor units only. CMB-P1016V-HA unit is for use with PURY-P700-800YSHM-A outdoor units only.
CMB-P104, 105, 106V-G
CMB-P108, 1010, 1013, 1016V-GA/HA
CMB-P104, 108V-GB
Side View >Upper View >
CMB-P1016V-HB
A BCMB-P104V-GBCMB-P108V-GB
33
180420
Cit
y M
ulti
Ran
ge 2
008
BC C
ontr
olle
rs
Dimensions
Side View >Upper View >
Side View >Upper View >
Side View >Upper View >
Page 195
Air Handling Unit Controller
PAC-AH-M-H - HEAT PUMP AHU CONTROLLERMODEL REFERENCE
MITSUBISHI ELECTRIC OUTDOOR UNIT
AIR HANDLING UNIT SIZE
ALLOWED EVAPORATOR CAPACITY (kW) - Heating
ALLOWED EVAPORATOR CAPACITY (kW) - Cooling
ALLOWED EVAPORATOR VOLUME (cm3)
STANDARD EVAPORATOR PATH NUMBER*
DIMENSIONS (mm) Width
( ) = Inc Mountings Depth
Height
WEIGHT (kg)
PAC-AH125M-H
PUHY-(E)P200-1250Y(S)HM-A
P100
10.0 - 12.5
9.0 - 11.2
1500 - 2850
4 - 5
326
117 (132)
410 (430)
7
PAC-AH125M-H
PUHY-(E)P200-1250Y(S)HM-A
P125
12.5 - 16.0
11.2 - 14.0
1900 - 3550
4 - 5
326
117 (132)
410 (430)
7
PAC-AH140M-H
PUHY-(E)P200-1250Y(S)HM-A
P140
16.0 - 18.0
14.0 - 16.0
2150 - 4050
5 - 6
326
117 (132)
410 (430)
7
PAC-AH250M-H
PUHY-(E)P200-1250Y(S)HM-A
P200
18.0 - 25.0
16.0 - 22.4
3000 - 5700
6 - 10
326
117 (132)
410 (430)
7
PAC-AH250M-H
PUHY-(E)P200-1250Y(S)HM-A
P250
25.0 - 31.5
22.4 - 28.0
3750 - 7100
8 - 10
326
117 (132)
410 (430)
7
Note: One air handling unit controller is required per air handling unitSaturated refrigerant temperature at exit of evaporator = 8.5ºC, SH=5K, liquid temperature = 25ºC, air = 27ºCDB/19ºCWB*When the diameter of the heat exchanger tube is ø9.52
M-NET wiring Thermistor wiring
Piping
Air Handling Unit (field supplied)
Controller (field supplied)
Outdoor Unit (Mitsubishi Electric)
Example:
Technical Information
The Air Handling Unit Controllers are an interface to allow connection to third party manufacturer equipment.
Mitsubishi Electric City Multi outdoor units can be used with this interface box, creating an ideal solution when a unique air handling unit is required. The Air Handling Unit Controllers are supplied with LEV expansion device(s).
PAC-AH-M-G - COOLING ONLY AHU CONTROLLERMODEL REFERENCE
MITSUBISHI ELECTRIC OUTDOOR UNIT
AIR HANDLING UNIT SIZE
ALLOWED EVAPORATOR CAPACITY (kW)
ALLOWED EVAPORATOR VOLUME (cm3)
STANDARD EVAPORATOR PATH NUMBER*
DIMENSIONS (mm) Width
( ) = Inc Mountings Depth
Height
WEIGHT (kg)
PAC-AH140M-G
PU(H)(R)Y-(E)P200-1250Y(S)HM-A
P140
11.2 - 16.0
2150 - 4050
5 - 6
326
117 (132)
382 (420)
7
PAC-AH250M-G
PU(H)(R)Y-(E)P200-1250Y(S)HM-A
P200
15.9 - 22.4
3000 - 5700
6 - 10
326
117 (132)
382 (420)
7
PAC-AH250M-G
PU(H)(R)Y-(E)P200-1250Y(S)HM-A
P250
18.7 - 28.0
3750 - 7100
8 - 10
326
117 (132)
382 (420)
7
Page 196
Air Handling Unit Controller (Mitsubishi Electric)
220-240v, 50Hz Power Supply
PAC-AH-M-G/H Heat Pump & Cooling Only
Cit
y M
ulti
Ran
ge 2
008
Air
Han
dlin
g U
nit
Con
trol
lers
/ A
cces
sori
es
Accessories / Optional Extras
CMY-Y102S-G2CMY-Y102L-G2CMY-Y202-G2CMY-Y302-G2CMY-Y62-G-ECMY-Y100VBK2CMY-Y200VBK2CMY-Y300VBK2CMY-R100VBKCMY-R200VBKACH1ACOUSTIC KIT
PLP-6BASLP-2AAPLP-6BALMPLP-6BAJPAC-SA1ME-EPAR-SA9FA-ES70E40714
CMP-P40VLW-BCMP-P63VLW-BCMP-P100VLW-BCMP-P125VLW-BPAC-KH11OF
PMP-40BM
PAC-KE03DM-FPAC-KE04DM-FPAC-KE88LAFPAC-KE89LAFPAC-KE80TB-FPAC-KE140TB-F
CMY-R160-JCMY-Y102S-G
PAC-SE41TS-E
- Branch Pipe (Joint) for size 200 or below - total capacity of indoor units- Branch Pipe (Joint) for size 201-400 - total capacity of indoor units- Branch Pipe (Joint) for size 401-650 - total capacity of indoor units or first branch of P500-P650- Branch Pipe (Joint) for size 651 or above - total capacity of indoor units or first branch of P700-P1250- Branch Pipe for 2 branches (PUMY)- Twinning Kit for PUHY-P500-650YSHM-A / PUHY-EP400-650YSHM-A- Twinning Kit for PUHY-P700-900YSHM-A- Twinning Kit for PUHY-P950-1250YSHM-A / PUHY-EP700-900YSHM-A- Twinning Kit for PURY-P500-650YSHM-A / PURY-EP400-600YSHM-A- Twinning Kit for PURY-P700-800YSHM-A- PQFY Auto-Changeover controller- Acoustic kits for PUHY and PURY units
- Grille for PLFY-P-VBM-E- Grille for PLFY-P-VCM-E- Grille and infra-red controller for PLFY-P-VBM-E- Grille with filter lowering function for PLFY-P-VBM-E- ‘I -See Sensor’ corner panel for PLFY-P-VBM-E- Infra-red signal receiver for PLFY-P-VBM-E- Infra-red Controller (PAR-SL97A-E) for PLFY-P-VBM-E
- Grille for PLFY-P20-40VLMD-E- Grille for PLFY-P50-63VLMD-E- Grille for PLFY-P80-100VLMD-E- Grille for PLFY-P125VLMD-E- OA duct flange for PLFY-P20-100VLMD-E
- Grille for PMFY-P-VBM-E
- Drain lift-up mechanism for PEFY-P-VMM-E- Drain lift-up mechanism for PEFY-P-VMH-E- Long life filter for PEFY-P80VMH-E- Long life filter for PEFY-P100-140VMH-E- Filter box for PEFY-P80VMH-E (necessary when long life filter is used)- Filter box for PEFY-P100-140VMH-E (necessary when long life filter is used)
- Joint pipe- Branch pipe
- Remote sensor
Page 197
Outdoor Units
4-Way Blow Cassette Units
2-Way Blow Cassette Units
1-Way Blow Cassette Units
Ceiling Concealed Ducted Units
BC Controllers
Indoor Units
LossnayTotal Heat Exchangers
Poor air quality can be attributed to many problems arising in the workplace or inthe home. It is believed to contribute to a significant loss in productivity, low moraleand higher rates of sickness amongst many employees. The object of providing goodventilation alongside air conditioning in residential and commercial buildings is toprovide conditions under which people can live and work in comfort and safety.
Developed and refined over the past 30 years, theLossnay system has perfected the recovery of waste energy. The units reduce overall energy costs by extracting stale air and thenrecovering the heating or cooling energy to either warm or cool incoming fresh air.By utilising this energy, the Lossnay systemcan save up to 30% on initial capital costs ofheating and cooling plant.
Simple andExcellent air quality and unbeatable Heat Exchange Efficiency
Fresh air supply to the room
Stale room air extracted
Stale exhaust air
Fresh air from outside
Heat exchange unit(Lossnay core)
Page 200
The Secretof the Lossnay System
The secret of the Lossnay system lies in the cross flow,plate fin structure of the heat exchange unit.
A diaphragm made of specially processed paper fully separates inlet and exhaust air supplies, ensuring that only fresh air is introduced to the indoor environment.
The superior heat-transfer and moisture permeability of the special paper ensures highly efficient total heat exchange (temperature and humidity) when inlet and exhaust air supplies cross in the Lossnay element.
Effective
Page 201
Effective ventilationLossnay’s simultaneous air exhaust/supply provides effective ventilation.Conventional ventilators (i.e. extract propeller fans) do not work effectively within air tight buildings because of the negative air pressures involved.
Good energy recoveryTotal heat (sensible and latent) recovery provides a comfortable air temperaturewithin the room. The energy saved by using Lossnay contributes towards lowering the heating or cooling requirement within the building, therefore reducing the energy requirement and running costs.
Free cooling function (LGH series)When the outdoor temperature is lower than the indoor air conditioned temperature in the summer, Lossnay provides fresh outdoor cool air to reduce the indoor air temperature.
Good sound attenuationAs the Lossnay core is made of paper and the permeable holes are small, the Lossnay core provides outstanding soundproofing properties and is appropriate for sound proof rooms.
Part L2 Building RegulationsWith the introduction of Part L2 (Part J in Scotland), new building design is changing to become more airtight, as well as energy efficient. The need for freshair has remained the same however and thus poses new challenges for moderndesign. Lossnay fully meets these challenges due to its basic principal and its efficient heat recovery. See the Technical Information Section for CIBSE recommended fresh air rates.
Enhanced Capital Allowance (ECA)LGH-RX4 now qualifies for Enhanced Capital Allowances.
Main features of
Lossnay
Page 202
Page 203
Operationin winter
4.6°CStale warm air (exhaust)
0°CFresh cool air (outdoor air)
20°CStale warm air
(indoor air)
15.4°CFresh warm air
(indoor supply air)
Heating unit
Operationin summer
25.6°CStale cool air (exhaust)
27°CFresh hot air (outdoor air)
21°CStale cool air (indoor air)
22.4°CFresh cool air
(indoor supply air)
Coolingunit
Using a Lossnay LGH-100RX4 in the winter example above, 8.9kW of heat is recovered per hour from the extracted air.
Total heat recover y
concept
The graph opposite shows the hourly temperature for 2006 in London between 8.00am - 6.00p.m.The point to note is the amount of free cooling available during these hours, as well as the heatrecovery below (22% of the time) and cooling recovery above (20% of the time). Lossnay is a yearround solution for providing fresh air.
Lossnay working in conjunctionwith air conditioningLossnay units can work either on their own to provide fresh air into a room, or in combination with Mr Slim or City Multi ceiling cassettes and ducted units.
When working together with air conditioning, Lossnay units can provide significant energy savings by automatically utilising free cooling as well as heat recovery. As the Lossnay and the air conditioningunit are connected by a two core communication cable, they can work together to optimise bothcomfort and energy efficiency. This is done by the Lossnay reading the mode and set temperature the air conditioning wants, then utilising the outside temperature to help achieve the requiredtemperature either by free cooling or heat recovery.
When using Lossnay in conjunction with air conditioning the heating and cooling loads can bereduced significantly, reducing the running costs by up to 30% compared with air conditioning systems without heat recovery systems.
Lossnay fan speed button is incorporated within the standard PAR-21MAA and PAR-F27MEA controllers
Above example: One LGH25RX4 serving one PLA-RP71BA.Room size 7m x 7m, 140w/m2 heat load. 7 people per room,10litres/per/person of fresh to meet Part F requirements. Maximum amount of fresh air to be introduced is 30% of the fan coil volume. Ceiling cassettes may require fresh air casements.Free cooling is not available below 8ºC when interlocked with Mr Slim or City Multi units.
Page 204
Page 205
Free cooling provided by Lossnay wasavailable in London over 58% of the time in 2006
Ambient Temperature - London 2006, 8am - 6pm
Over 58% of the time between 8am-6pm, the temperature in Londonwas between 8ºC and 20ºC, allowingfree cooling when the air conditioningsetpoint was 21ºC in cooling mode. If the setpoint is higher, free cooling is increased.
Hyper Lossnay CoreLGH-RX4 Lossnay units feature the newly developed “Hyper Lossnay Core”, which uses non-porous, ultra-thin film toachieve high enthalpy exchange efficiency. With a thickness of only 25µm, these are the thinnest in the world and areapproximately one fifth the thickness of previous Mitsubishi Electric products. Moisture permeability is dramaticallyincreased and enthalpy heat exchange greatly improved.
Consists of a two-layer constructionusing a specially processed materialmade of a preferential permeable film on a porous base material. This provides moisture permeabilityand air barrier properties, but the two-layer construction makes a certain thickness unavoidable.
Consists of a specially processedstructure based on a single-layer, non-porous, ultra-thin film material.Moisture exchange (water vapourtransmission) is promoted by thespecial film, which increases theaffinity for moisture (the thinner the film, the higher the permeability).The non-porous ultra-thin filmmaterial acts as a barrier against air leakage.
Use
Hyper Lossnay Core material
Previous Mitsubishi Electric material
Photocopier paper
Dictionary paper
Thickness
25µm
120µm
100µm
51µm
The thinnest paper used in regular printing is 51µm thick (used in dictionaries) and the material of theHyper Lossnay Core is approximatelyhalf the thickness of this.
Comparison of material used in Hyper Lossnay Core (25µm ultra-thin film) with regular paper
Comparison of new and old Lossnay Core cross-sections
Previous Lossnay Core New Hyper Lossnay Core
Porous partition plate Non-porous film partition plate
120µm 25µm
Ducts can be connected in two different directions to the outdoorvents thanks to collars and aperture plates that can be interchangeablyplaced in two different positions. This flexibility allows for installationsclose to the surface of a wall and helps avoid cases where the staleair exhaust vent would be blocked by an obstruction of some kind.This makes both the planning and installation of Lossnay units thatmuch simpler.
Standard installation Installation with duct direction changed
A space is necessary to prevent the influx of rainwater.
Collar Aper ture Plate Exchangeable
Can beinstalled closeto the surfaceof the wall.
Changing the duct direction
Connect ducts in two different directions (Outdoor vents)
Because an adaptor now comes as standard equipment, networking LGH RX4 systems connected with Mitsubishi Electric’sline of air condi tioners has never been easier. There is no need to purchase any extra parts, creating the possibility of verysimple systems and keeping initial costs as well as construction time and trouble to an affordable minimum.
Interface simply
Page 206
Page 207
Multi-Ventilation ModeEnables the appropriate supply/exhaust balance to be selected to suitusage, environment and location.
All LGH models feature the "Multi-ventilationMode," which allows the air supply/exhaustbalance to be varied dynamically to suit theusage environment and location. Modes canbe selected easily by setting the connectorson the circuit board.
* "High" can be further set to "Extra high" using the dip switch.
Normal Office Small Office or Building Smoking Areas
Providing efficient ventilation whilemaintaining air supply/exhaust balance...
Using Lossnay compensates for usingextractor fans...
Priority on air exhaust...
Power air supply& air exhaust
Most widely-used pattern formingthe basis for traditional ventilationdesign. This allows the most efficientventilation while maintaining the airsupply/exhaust balance. The optimumventilation rate can be maintained byselecting the Power air supply/exhaustmode with both the air supply & air exhaust switched to "High" (or "Extra high") on the main unit. For example in an office, the controlswitches can be set to "High" to runin Power air supply/exhaust modewhen a large number of people are in the office, then switched to "Low"to run in Energy-saving ventilationmode late at night or on holidayswhen there are few people present.
In smaller offices or buildings, theremay be insufficient air supply to themain rooms or offices due to theexcessive exhaust via extractor fanslocated in toilets or kitchen areas.Setting to Power air supply mode with the air supply switch on "High" (or "Extra high") and the air exhaust switch on "Low" on the main unit, allows efficient ventilation while making up for the insufficient air supply.
In locations such as smoking areas,dirty air must be exhausted swiftly.Setting the Power air exhaust modewith the air supply switch on "Low"and the air exhaust switch on "High"(or "Extra high") on the main unitallows efficient extraction of cigarettesmoke and odours. Maintaining thearea at a negative air pressure alsoprevents dirty air from spreading to surrounding areas.
Power air supply Power air exhaust
Power air supply/exhaust mode
Power air supply mode
Power air exhaust mode
Energy-saving ventilation mode
Ventilation Mode
High
High
Low
Low
SupplyAirflow
High
Low
High
Low
Exhaust Airflow
Enhanced Capital Allowance & Part L2 The need for energy efficiency is paramount and is determined by legislation and regulation. To encourage efficient use of energy, the UK Government introduced the Enhanced CapitalAllowance Scheme (ECA). The number of qualifying products on the Energy TechnologyProduct List has recently been expanded and includes ‘air to air energy recovery’.The Lossnay heat recovery units (LGH-RX4) have been designed to ensurebusinesses qualify for ECA and benefit from the utmost efficiency, both financially and environmentally.
How Enhanced Capital Allowances WorkEnhanced Capital Allowances are used to encourage businesses to invest in particular typesof equipment by providing up-front tax relief, as 100% of the allowances can be reclaimed in the first year. So, using the below example of a £1000 investment in equipment that qualifies for ECA’s, the company could reclaim £300 in the first year.
Enhanced Capital AllowanceTax Rate 30%
% of expenditure to which allowance applies 100%
Equipment plus installation costs £1000
Taxable amount reduced by 100% OF £1000 = £1000
FIRST YEAR SAVING 30% of £1000 = £300
Part L2 of the Building Regulations is undergoing a major change. With buildingregulations tightened up from April 2006, new commercial buildings have to bepressure tested to show they are airtight and energy efficient. Proof willalso be needed to show that the new buildings will not overheat and the occupants will be able to work comfor tably. This means that the fresh air requirements are even moreimportant than ever before. Lossnay offers many featuresthat will help the building designer as well as the occupantsand with Lossnay’s high efficiency, unique controllability andits modular design approach, Lossnay will assist greatly in Part L2 compliance.
Part L2
Page 208
Page 209
Enhanced Capital Allowance Scheme (ECA)
� Under the scheme, all businesses liable for UK corporation tax, are able to claim an enhanced capital allowance on anyqualifying expenditure (regardless of size and location of business or whether in the industrial or commercial sector)
� Businesses can offset the full cost of specific technologies (such as Lossnay) against taxable profits of the period of the investment
� In order to qualify for this scheme, technology has to meet the energy saving criteria as published in the Energy Technology Criteria List. Our LGH-RX4 Lossnay systems fully meet this criteria in their drive for energy efficiency
� Only investment in new and unused plant and machinery qualify
For further instructions go to www.eca.gov.uk and click on Mitsubishi Electric Air Conditioning under the air to air energy recovery category.
The key features of the ECA scheme:
Restaurants Schools
The atmosphere of a restaurant is crucial to securing and retaining customers. Cleanliness is the key to an attractive atmosphere and restaurants devote significant effort to ensuringtheir premises are sanitary. Sanitation and cleanliness,however, are not enough. No matter how clean a restaurant may look, if there are bothersomeodours lingering in the air, all those efforts go to waste and the restaurant's clean image is tarnished. For these reasons, Lossnay’s superiorventilation capabilities ensure that every breath isa fresh one and a pleasant environment ismaintained for guests at all times. Lossnay alsokeeps owners happy with its remarkable heatrecovery technology that supplies fresh outdoorair with minimal change to indoor temperature,saving on energy costs.
A restaurant can never be tooclean and its air never too fresh
Creating the best possible environment for our children to succeedChildren deserve all the help we can give them to grow up healthy, happy and prosperous. No matter how good a school's curriculum, no matterhow positive and enthusiastic the teacher, a child whodoes not feel well will have a hard time learning. A constant flow of fresh air is nowhere as important as it is in our schools. In classroomswhere large numbers of students are gathered for long periods of time, carbonic gases have the tendency to accumulate, decreasing the levelsof oxygen that are vital for aler tness and concentration. This is especially true during thewinter months when windows tend to remainclosed. Lossnay ventilates fresh outdoor air intoclassrooms to replenish the supply of oxygen and expels not only carbon dioxide, but also otherpollutants and odours that inevitably sully the air.
Lossnay works to remove stale air and supplyfresh, clean air free of the odours associated
with cooking, cigarettes and the people working and dining.
Change in room temperature is kept to a minimum during ventilation thanks to the
heat-recovery function.
The Lossnay operate very quietly, so those inthe midst of enjoying their meals will not be
bothered by any excess noise.
A large array of Lossnay sizes are available tomatch the layout of just about any restaurant.
The continuous influx of fresh, outdoor air andthe exhaust of stale, indoor air ensure that theindoor oxygen level is maintained at just the
right balance for comfort and health.
Occupants have the luxury of breathing freshair at all times even in highly air-tight buildings.
Lossnay's sound attenuation qualities preventoutside noise from penetrating into the room,helping to maintain a quiet environment for
productive study.
Heat-exchange technology prevents fluctuationsin temperature creating significant energy
savings when either heating or cooling a room.
If it’s Lossnay If it’s Lossnay
%3.25What would you most like to see improved in restaurants?
Others: no response
Promotion of waste prevention: 5.4%
Improvement in atmosphere: 6.5%
Reduction of time required forfood to reach the table: 12.0%
Improvement in employees attitude towards customers: 20.5%
Improvement in overallcleanliness
1996 Foodstuffs Consumption Monitor, Second Periodic Survey ( Ministry of Agriculture, Forestry and Fisheries, Japan) In
crea
sed
resp
irat
ion
and
puls
e
O2 Concentration and Deficiency
21
15
10
5
0 Nor
mal
air
Safe
ty m
inim
um
O2
Con
cent
ratio
n (%
)
Diz
zine
ss, n
ause
a,lo
ss o
f mus
cle
stre
ngth
(pr
ecur
sors
of d
eath
)
Pale
ness
of s
kin,
vom
iting
,U
ncon
scio
usne
ss
Com
atos
is(d
eath
in 8
min
)
Con
vulsi
ons,
resp
iratio
nst
ops,
deat
h
21 %18 %
16 %
12 %10 %
8 %
6 %
Page 210
Page 211
Many office buildings today are heavily insulated, air-tight structures with little or no natural ventilation. The unnaturalenvironment created by air conditioners without added ventilation is a breeding ground for bacteria. Factor this in with the accumulation of pollutants and odours in the form ofcigarette smoke, formaldehyde, pollen, dust, carbon dioxideand the necessity of ventilation becomes ever more apparent.In fact, poorly ventilated buildings can give rise to Sick BuildingSyndrome, a malady that is known to cause headaches, soreeyes, itching and loss of concentration. This results not only in discomfort at best and sickness at worst for the building'soccupants, but also the reduced productivity of the workforce.Fresh air, effectively ventilated throughout the building is therefore essential to the overall quality of working life.
Simultaneous forced-air supply and exhaust introduces fresh, outdoor air into the building,effectively ventilating even fully airtight structures.
Multiple split-type units operate independently of one another, simplifying system set up and
ensuring a layout that optimally matches nearly any office design.
Lossnay operation can be interlocked withair-conditioning system operation.
Heat that is commonly lost due to ventilation is collected and reused thanks to the
Lossnay Core, reducing an air conditioners energy load and cutting operating costs.
OfficesFresh air - improving the overallquality of working life
If it’s Lossnay
Lossnay Selection / Payback Softwareand Quick Reference Guide available to order from your local sales office
The unbeatable
LossnayThe Lossnay al lows the extraction of stale
air and efficient recover y of heating
or cooling energy to treat
incoming fresh air. Whatever
your environment, it ’s simple to improve
it with Lossnay.
Systems marked with the ECA logo are registered on the Energy Technology List andhence qualify for 100% first year enhanced capital allowances (whole system cost and ‘reasonable’ cost of installation). For further information please go to www.eca.gov.uk
Nominal conditions cooling: indoor 27˚C DB, 19˚C WB; outdoor 35˚C DB, 24˚C WB.Nominal conditions heating: indoor 20˚C DB; outdoor 7˚C DB, 6˚C WB.UK Conditions: Summer; indoor 21˚C DB, 15˚C WB; outdoor 27˚C DB. Winter; indoor 21˚C DB; outdoor -1˚C WB.
S imple technologyat its best
Page 212
Page 213
Total Heat Exchangers Residential Model
LGH-RX4 Commercial Series
180
182
214
216
Contents
Residential Model
Total Heat Exchangers
LOSSNAYMODEL REFERENCE
ELECTRICAL POWER SUPPLY
PHASE
POWER CONSUMPTION (W) Low
High
AIRFLOW (m3/h) Low
High
NOISE (dBA) Low
High
Low
High
WEIGHT (kg)
DIMENSIONS (mm) Width
Depth
Height
DUCT SIZE (mm)
FUSE RATING (BS88) - HRC (A)
MAINS CABLE No. Cores
RESIDENTIAL WALL- MOUNTED VL 100U
220 - 240V, 50Hz
Single
23
26
65
105
29.5
39
77
70
6.5
620
168
265
2xØ75
6
3
TEMPERATUREEXCHANGEEFFICIENCY (%)
Technical Information
Particularly suitable for modern homes with high insulation afforded by double glazing and cavity insulation, which require ventilation to remove stale air without major heat loss.
� Effective fresh air ventilation
� Efficient recovery of heating/cooling energy
� Good sound attenuation
� Reduces heating costs
Page 214
VL 100U
Tota
l Hea
t Exc
hang
ers
Resid
entia
l Mod
elLo
ssna
yR
ange
200
8Dimensions
Page 215
LGH-RX4
LOSSNAYMODEL REFERENCE
ELECTRICAL POWER SUPPLYSTARTING CURRENT (A)RUNNING CURRENT (A) Low
HighExtra High
INPUT POWER (W) LowHighExtra High
AIRFLOW (m3/h) LowHigh / Extra High
AIRFLOW (l/s) LowHigh / Extra High
EXTERNAL STATIC LowPRESSURE (PA) High
Extra HighNOISE (dBA) Lossnay Low
HighExtra High
Bypass LowHighExtra High
TEMPERATURE LowEXCHANGE HighEFFICIENCY (%) Extra HighENTHALPY Heating LowEXCHANGE High / Extra HighEFFICIENCY (%) Cooling Low
High / Extra HighWEIGHT (kg)DIMENSIONS (mm) Width
DepthHeight
DUCT SIZE (mm)STANDARD FILTER*1
FUSE RATING (BS88) – HRC (A)MAINS CABLE NO. CORES
COMMERCIALLGH-25RX4
220-240V, 50Hz0.80.250.400.49599611716525046692550802326
27.523
26.528
83.578787770716521735780275150EU3
63
COMMERCIALLGH-35RX4
220-240V, 50Hz1.70.480.710.79110167187230350649725701502430322430
32.58479797770
74.56830874888317150EU3
63
COMMERCIALLGH-50RX4
220-240V, 50Hz1.90.600.900.9514221422535050097139306015024.531.534
25.533
35.5827777
73.567.571.564.533
1016888317200EU3
63
COMMERCIALLGH-80RX4
220-240V, 50Hz3.61.401.601.70315370385670800186222701001403133
34.531.534
35.580.57878
73.571
70.56761
10041164398250EU3
63
COMMERCIALLGH-100RX4
220-240V, 50Hz5.41.702.002.1040047549087010002422788010016032.5353734
36.5388179797471
69.56769
12311164398250EU3103
COMMERCIALLGH-150RX4
220-240V, 50Hz7.22.703.103.30625730770125015003474177010014033.536.537.536.538.540
81.57979
74.572726812410041164800
(SA,RA)250 (OA,EA)270x700EU3163
COMMERCIALLGH-200RX4
220-240V, 50Hz10.83.504.204.30820980101016502000458556659015036384037
39.541
81.579797571716714012311164800
(SA,RA)250 (OA,EA)270x700EU3163
COMMERCIALLGH-15RX4
220-240V, 50Hz0.70.220.310.4551731071101503142356095232527232527817777747070
64.517610780275100EU3
63
Notes: Running Current, Input Power and Recovery Efficiency are based on the above airflow rate, power supply 240v, 50Hz. Extra High mode available via dip switch setting. Noise measured at 1.5m under the centre of panel.*1: Eu7 filter available as optional parts.
Fresh air supply to the room
Stale room air extracted
Stale exhaust air
Fresh air from outside
Heat exchange unit(Lossnay core)
Commercial Series
Technical Information
This commercially orientated system can be utilised virtually anywhere.
� Effective fresh air ventilation
� High heat recovery
� Free cooling function
� Good sound attenuation
� New “Hyper Lossnay Core”. At only 25µm (approx 1/5 the thickness of LGH-RX3) the Lossnay core uses the thinnest paper in the world to achieve high enthalpy exchange efficiency
Page 216
MODEL REFERENCE
LGH-150RX4
LGH-200RX4
A
1004
1231
B
690
920
C
1046
1273
LGH-15RX4 to LGH-200RX4
M-NET Controller
PZ-52SF-E (M-NET)Control 16 Lossnay units from sizes 15 -100 or up to 8, sizes 150 - 200
70
48
8 33
120
70
48
8 33
120
Lossnay Controller
PZ-41SLB-EControl 15 Lossnay units from sizes 15 -100 or up to 7, sizes 150 - 200
MODEL REFERENCE
LGH-15RX4
LGH-25RX4
LGH-35RX4
LGH-50RX4
LGH-80RX4
LGH-100RX4
A
780
780
888
888
1164
1164
B
610
735
874
1016
1004
1231
C
275
275
317
317
398
398
D
700
700
790
790
1030
1030
E
641
765
906
1048
1036
1263
ø100
ø150
ø150
ø200
ø250
ø250
DIMENSIONS NOMINALDIAMETER
CEILING SUSPENSION FIXTURE PITCH
LGH-15-100RX4 > LGH-150-200RX4 >
LGH
RX
4 C
omm
erci
al S
erie
sLo
ssna
yR
ange
200
8Dimensions
Page 217
ControlsA comprehensive range of control options
The importance ofThe need for control is paramountin order to optimise the performanceof any air conditioning system and minimise its running costs.Mitsubishi Electric offer a widerange of control options designedto do just this.
Operating an air conditioning system without
the right control can prove costly. It’s therefore
important to ensure that every system is
correctly specified to the degree of control it
requires. Mitsubishi Electric have a wide range
of controls available ‘off-the-shelf ’ and where
needed, individual control systems can be
specifically designed to suit.
Good controls will benefit any application, large
or small. Air conditioning products need to
react to a variety of factors: different room
sizes, usage and staff levels; changes in the
climate; electronic equipment and lighting ... the
list goes on. So whatever the application,
optimum control of air conditioning systems
is essential and will result in a constant,
comfortable environment, which in turn is both
energy and cost efficient.
A degree of
differenceWhen an air conditioning system is not properly
controlled, it will not run as efficiently as it should.
For every degree that the system deviates from
the required temperature, energy costs can rise
by up to 5%. Specify one of the many control
options from Mitsubishi Electric to ensure
air conditioning works as intended, whilst giving
the optimum amount of control.
The simpler
the betterWith the array of comprehensive control
systems available from Mitsubishi Electric,
it becomes simple to design and install air
conditioning systems. From a simple hand held
controller to a G50 system - you are in control.
Page 220
Controlled
performanceIn accordance with the requirements of part L2 in the Building Regulations, our control systems
provide the optimum control available, combined with the most efficient use of energy.
Control
A wide range of
Controls options
The need for control is paramount in order
to optimise the performance of any air conditioning
system and minimise its running costs.
Mitsubishi Electric offer a wide range of
control options designed to do just this.
S imple technologyat its best
Page 222
Remote Controllers
Programmable Timer
System Controller
Interfaces
G50 Controller, Centralised Controller
AG150 Controller, Centralised Controller
GB50 Controller, Centralised Controller
G50/GB50/AG150 Controller, Web Screenshots
G50/GB50/AG150 Desktop Remote Controller
G50/GB50/AG150 Third Party Equipment Interfaces
G50/GB50/AG150 Programmable Logic Controller (PLC)
TG2000 Software, PC Based Software Package
TG2000 Software with Energy Monitoring
TG2000 Software with Third Party Equipment
TG2000 WAN Software (Wide Area Network)
TG2000, Screenshots
BEMS BACnet® Interface (BAC-IP/50)
BEMS BACnet® Mr Slim Interface (BAC-A/50)
BEMS LonWorks® Interface (LMAP)
BEMS Modbus Interfaces (IP-32/50/100M)
BEMS Modbus Mr Slim Interface (A32M)
BEMS Modbus Splits Interface (A1M)
BEMS KNX-EIB Interfaces (KNX-EIB-IP-15/100)
BEMS KNX-EIB Splits Interface (KNX-EIB-A-1)
M2M - Machine 2 Machine Interface (Maxi M2M-IP/50)
M2M - Machine 2 Machine Splits Interface (Mini M2M-A/16)
M2M - Machine 2 Machine Web Screenshots
G50 Control Panels
Run / Standby Control Panels
Energy Monitoring Control Panels
Split-System A2M Interfaces
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
Contents
Page 223
Remote Controllers
Remote Controllers
PAR-FL32MAPAR-21MAA PAR-F27MEAPAC-YT51CRA PAC-SE51CRA BS-51COV PC-51COV PB-51COV
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
FAN SPEED SETTING
SETPOINT LIMIT
AIRFLOW DIRECTION
INDEPENDENT VANECONTROL
TIMER OPERATION
PERMIT / PROHIBITFUNCTION
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
TEST RUN FUNCTION
VENTILATION INTERLOCK
OPTIONAL COVER
CONTACT NUMBERUNDER FAULT CONDITIONS
MULTIPLE LANGUAGES
CLOCK DISPLAY
BUTTON LOCK
EASY MAINTENANCEWITH MR SLIM
RUN / STANDBY WITHMR SLIM
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
FUNCTION
Run and Stop operation for a single group
Switches between Cool/Dry/Auto/Fan/Heat.Operation mode will vary depending on theindoor unit. Auto mode is available with only R2 and WR2 systems
Sets the groups temperature control. Cool/Dry: 19-30°C Heat: 17-28°C Auto: 19-28°C
4 speed - Lo-Mi1-Mi2-Hi 2 speed - Lo-Hi
Limit the setpoint range
Air Flow angles:100º-80º-60º-40ºand auto swing
Only available with PLA-RP-BA, PLFY-P-VBM-E and PLFY-P-VCM-E
ON/OFF time can be set.
Run/Stop, Temperature Setting, Mode Selectionand Filter Reset functions can be prohibited via a higher level system controller
Measures the intake temperature of the master unit within the group
Displays a 4 digit code and the affected unit address
Allows each unit within the group to operate in test mode
Allows the group to be interlocked with a heat recovery Lossnay unit
Brushed Stainless Steel
Polished Chrome
Polished Brass
Displays under fault condition, the fault code of the unit with its address and the contact number to call
English, Italian, Spanish, French, German, Russian, Chinese and Japanese
Displays time
Able to lock all controller buttons, or all controller buttons except On/Off
Able to monitor information about thecompressor (running current, running time,On/Off time). Also able to monitor sensors: h-exh, outdoor outlet, outdoor temp, indoor inlet,indoor h-exh and filter use number of hours
Able to switch over two systems every week. If one fails, the other system starts. If thetemperature is too high, the two systems start.
Compatible with:
DESCRIPTION PAC-YT51CRA PAC-SE51CRA PAR-21MAA PAR-F27MEA PAR-FL32MA
Weekly Weekly Daily Daily Daily Daily
Our air conditioning systems are supported by a multitude of remote controllers. Each remote controller type,whilst being able to support the general control and monitoring functions for a group of indoor units, can also offer other unique operational features.
Mr Slim or M Series (via MAC-397IF) City Multi
Mr Slim or M Series (via MAC-397IF)
City MultiCity Multi, Mr Slim or
M Series (via MAC-397IF)
120x41x70 120x41x70 130x19x120 130x19x120 157x18x57
Operation Display Operation Display Operation Display Operation Display Operation Display
� � � � � � � � � �
� � � � � � � � � �
� �
� �
� � � �
� � � �
� �
� �
� �
� �
� �
� �
� �
� � � � � � � �
� � � � �
� �
� � � �
�
�
�
�
� �
�
� �
� �
�
�
�
�
�
�
� � � � � � � �
Technical Information
Page 224
� �
Programmable Timer
PAC-YT34STA
Programmable Timer
Mitsubishi Electric controllers are complimented by a weekly programmable timer, being ableto control up to fifty indoor units. The PAC-YT34STA also has hardwired connection available (On/Off input, fire alarm input, run output, fault output).
PAC-YT34STA PAC-SC50KUA
Con
trol
sR
ange
200
8R
emot
e C
ontr
olle
rs /
Pro
gram
mab
le T
imer
Technical Information
UNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
CURRENT TIME
ERROR INDICATION
EXTERNAL INPUT
EXTERNAL OUTPUT
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
FUNCTION
Max No. of Indoor Units
Run and Stop operation
Switches between Cool / Heat
Sets the groups temperature control. Cool/Dry: 19-30°C Heat: 17-28°C Auto: 19-28°C
Set the time
Displays a 4 digit code and the affected unit address
Hardwired connections available
Hardwired connections available
Compatible with:
50 units/50 groups 50 units/50 groups
DESCRIPTION PAC-YT34STA
� �
� �
� �
� �
�
� �
City Multi or Mr Slim via PAC-SF80MA or M Series via MAC-399IF
130x19x120
Operation Display
On/Off or Fire Alarm
Run/Faults
NOTE: Units can only be controlled from the scheduling options. When the remote On/Off hardwired input is used, the On/Off remote controller buttons will be deactivated (centrally controlled).
Page 225
PAC-SC50KUAPAC-SF44SRA PAC-SF44SRA
System Controller
UNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
FAN SPEED SETTINGS
AIR FLOW DIRECTION
PERMIT/PROHIBITFUNCTION
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
VENTILATIONINTERLOCK
EXTERNAL INPUT
EXTERNAL OUTPUT
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
FUNCTION
Max No. of Indoor Units
Run and Stop operation
Switches between Cool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on theindoor unit. Auto mode is available with only R2 and WR2 systems
Sets the groups temperature control. Cool/Dry: 19-30°C Heat: 17-28°C Auto: 19-28°C
4 speed - Lo-Mi1-Mi2-Hi 2 speed - Lo-Hi
Air Flow angles: 100º-80º-60º-40º and auto swing
Run/Stop, Temperature Setting, Mode Selectionand Filter Reset functions can be prohibited
Measures the intake temperature of the master unit within the group
Displays a 4 digit code and the affected unit address
Allows the group to be interlocked with a heat recovery Lossnay unit
Hardwired connections available
Hardwired connections available
Compatible with:
50 units/50 groups 50 units/50 groups
DESCRIPTION PAC-SF44SRA
� � �
� �
� �
� �
� �
� �
� �
�
�
� �
Operation Display
On/Off or Fire Alarm
Run/Faults
City Multi or Mr Slim via PAC-SF80MA or M Series via MAC-399IF
130x19x120
System ControllerOne system controller is available for use when you need to control up to fifty indoor units from one location. The PAC-SF44SRA also has hardwired connection available (On/Off input, fire alarm input, run output, fault output).
Technical Information
Page 226
NOTE: When the remote On/Off hardwired input is used, the On/Off remote controller buttons will be deactivated (centrally controlled).
InterfacesA range of newly created interfaces are now available for use when connecting to third party controllers.
DIDOTCB1
DIDOTCB1
Interfaces
ON/OFF BUT CENTRALLYCONTROLLED
ON/OFF BUTNOT CENTRALLYCONTROLLED
TEMPERATURESETTINGS
ERROR INDICATION
HEATINGINTERLOCKING
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
FUNCTION
ON/OFF control. Remote controller ON/OFF button deactivated
ON/OFF control. Remote controller ON/OFF button activated
Sets the groups temperature control. Cool/Dry: 19-30°C Heat: 17-28°C Auto: 19-28°C
A supplied remote sensor is installedon the wet system radiator to prevent the air conditioning running while heating
Interface compatible with:
DESCRIPTION TCB1 DIDO MS-FRT-TCB-TEMP
Con
trol
sR
ange
200
8
Technical Information
Control Monitor Control Monitor Control Monitor
80x45x80 130x19x120 130x19x120
Mr Slim
City Multi
Mr Slim
City MultiMr Slim
� � � �
�
(analogue 0 to 10VDC)
� �
Syst
em C
ontr
olle
r /
Inte
rfac
es� � � � � �
Page 227
Centralised Controller with WebServer Capabilities
G50 Controller
The G50 centralised controller was the first of its kind in the industry to utilise Ethernet Technology. By using InternetExplorer as its local or remote software, the G50 gives you instant access to all your control functions from the comfort ofyour own PC. The G50 can control up to 50 indoor units and can take the place of local remote controllers, offeringthe same level of monitoring and control. The G50 has many functions as standard but can also have further featuresactivated via Pin Codes.
G50 - Web MonitorG50 - EmailG50 - ASG50 - EC
Control and Monitor the G50 via Internet ExplorerEnable E-mail activation on fault conditionsWeekly / Annual Scheduling and Night Set BackEnergy Charge
G50 Software Options - Pin Code ActivationG50 - ESG50 - PCG50 - VRC
G50 Controller
OPERATION PLATFORM
MAX No. OF INDOOR UNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
FAN SPEED SETTING
AIR FLOW DIRECTION
TIMER OPERATION
PERMIT/PROHIBIT FUNCTION
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
TEST RUN FUNCTION
VENTILATION INTERLOCK
WEB SETPOINT LIMIT
WEB AUTO CHANGEOVER
WEB INITIAL SETTING
WEB LOGIN
EXTERNAL INPUT/OUTPUT
POWER SUPPLY PACK
COMPATIBILITY
DIMENSIONS - mm (WxDxH)
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional 2000service pack 4 or Windows Professional XP service pack 2 or Windows Vista
Up to 50 indoor units can be connected
Run and Stop operation for a single group
Switches between Cool/Dry/Auto/Fan/Heat. Operation Mode will vary depending on the indoor unit.Auto mode is available with only R2 and WR2 systems
Sets the groups temperature control. Cool/Dry: 19-30°C, Heat:17-28°C, Auto: 19-28°C
4 speed: Lo-Mi1-Mi2-Hi, 2 speed: Lo-Hi
Air Flow angles:100º-80º-60º-40º and auto swing
Weekly. Maximum of 3 time sequences with 3 Start/Stop times per day for all groups can be allocated
Individual prohibit operations for each remote controller function (Run/Stop,Temperature Setting, Mode Selection and Filter Reset) can be activated
Displays the measured intake temperature from each group
Displays a 4 digit code and the affected unit address. An error log is held showing the last 64 date stamped alarms
Allows each unit within the group to operate in test mode
Allows the group to be interlocked with a heat recovery Lossnay unit
Reduce the setpoint band of each individual unit (e.g. 23ºC to 25ºC)
Automatically switch heat pump outdoor unit to cooling or heating mode depending on the requirements
Commission the G50 from the web pages
Administrator able to allow specific function access to guest
Hardwired connections are available for : Inputs: Level Signal-Batch Start/Stop, Batch Emergency StopOutputs: Start/Stop Status, Error/Normal Status
PAC-SC50KUA
City Multi or Mr Slim via PAC-SF80MA or M Series via MAC-399IF
300x79x120
DESCRIPTION
Technical Information
Energy Saving CapabilityPeak Cut Control Virtual Remote Controllers
ETHERNET
G50
Viewed using Microsoft® Internet Explorer
M-NET
PAC-SC50KUA
Page 228
Touch Screen Centralised Controller with WebServer Capabilities
AG150 Controller
The new AG150 Mitsubishi Electric centralised controller offers a large 9 inch touch screen display with easy controlof up to 50 indoor units. The AG150 can calculate the energy used for each system, zone or indoor unit. The refrigerant status check function can be activated regularly (in conjuction with the new YHM-A City Multi range) and an Internet connection with SSL security is also available to monitor and control the AG150 remotely andreceive Email under fault conditions.
AG150 - BasicAG150 - EnergyAG150 - VRC
Web monitoring, Email, Annual schedulingEnergy monitoring, energy saving, load sheddingVirtual remote controllers
AG150 Software Options - Pin Code Activation
AG150 Controller
OPERATION PLATFORM
MAX No. OF INDOOR UNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
FAN SPEED SETTING
AIR FLOW DIRECTION
TIMER OPERATION
PERMIT/PROHIBIT FUNCTION
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
TEST RUN FUNCTION
VENTILATION INTERLOCK
WEB SETPOINT LIMIT
WEB AUTO CHANGEOVER
WEB INITIAL SETTING
WEB LOGIN
WEB REFRIGERANT STATUS CHECK
ENERGY CHARGING
ENERGY SAVE CONTROL
LOAD SHEDDING
EXTERNAL INPUT/OUTPUT
POWER SUPPLY PACK
COMPATIBILITY
DIMENSIONS - mm (WxDxH)
TOUCH SCREEN
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional 2000 service pack 4 or Windows Professional XP service pack 2 or Windows Vista
Up to 50 indoor units can be connected
Run and Stop operation for a single group
Switches between Cool/Dry/Auto/Fan/Heat. Operation Mode will vary depending on the indoor unit.Auto mode is available with only R2 and WR2 systems
Sets the groups temperature control. Cool/Dry: 19-30°C, Heat:17-28°C, Auto: 19-28°C
4 speed: Lo-Mi1-Mi2-Hi, 2 speed: Lo-Hi
Air Flow angles:100º-80º-60º-40º and auto swing
Annual or weekly. Night set back option available allowing the setpoint to be set to 12ºC
Individual prohibit operations for each remote controller function (Run/Stop,Temperature Setting, Mode Selection and Filter Reset) can be activated
Displays the measured intake temperature from each group
Displays a 4 digit code and the affected unit address. An error log is held showing the last 64 date stamped alarms
Allows each unit within the group to operate in test mode
Allows the group to be interlocked with a heat recovery Lossnay unit
Reduce the setpoint band of each individual unit (e.g. 23ºC to 25ºC)
Automatically switch heat pump outdoor unit to cooling or heating mode depending on the requirements
Commission the G50 from the web pages
Administrator able to allow specific function access to guest
Activate refrigerant volume checking function on Modular City Multi systems
Able to create bills for individual indoor units, groups of indoor units or a complete system (Optional) via the PAC-YG60MCA
Individual indoor unit, group of indoor units or a complete system can be controlled. There are various energy saving options available (Optional)
Activate energy saving mode when energy consumption is too high
Hardwired connections are available for : Inputs: Level Signal-Batch Start/Stop, Batch Emergency StopOutputs: Start/Stop Status, Error/Normal Status
PAC-SC51KUA
City Multi or Mr Slim via PAC-SF80MA or M Series via MAC-399IF
300x62x175
Wide high resolution 9” touch screen
DESCRIPTION
Technical Information
ETHERNET
AG150
Viewed using Microsoft® Internet Explorer
M-NET
PAC-SC51KUA
Page 229
NEW in September 2008
Con
trol
sR
ange
200
8G
50 C
ontr
olle
r / A
G15
0 C
ontr
olle
r
Centralised Controller with WebServer Capabilities
GB50 Controller
G50 - ECG50 - ESG50 - PCG50 - VRC
Energy ChargeEnergy Saving CapabilityPeak Cut Control Virtual Remote Controllers
GB50 Software Options - Pin Code Activation
ETHERNET
GB50
The GB50 has been developed to access all your control functions from the comfort of your own PC, without the need for a controller keypad or LCD display and at a very competitive price.
GB50 Controller
OPERATION PLATFORM
MAX No. OF INDOOR UNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
FAN SPEED SETTING
AIR FLOW DIRECTION
TIMER OPERATION
PERMIT/PROHIBIT FUNCTION
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
TEST RUN FUNCTION
VENTILATION INTERLOCK
WEB SETPOINT LIMIT
WEB AUTO CHANGEOVER
WEB INITIAL SETTING
WEB LOGIN
EXTERNAL INPUT/OUTPUT
POWER SUPPLY PACK
COMPATIBILITY
DIMENSIONS - mm (WxDxH)
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional 2000 service pack 4 or Windows Professional XP service pack 2 or Windows Vista
Up to 50 indoor units can be connected
Run and Stop operation for a single group
Switches between Cool/Dry/Auto/Fan/Heat. Operation Mode will vary depending on the indoor unit. Auto mode is available with only R2 and WR2 systems
Sets the groups temperature control. Cool/Dry: 19-30°C, Heat:17-28°C, Auto: 19-28°C
4 speed: Lo-Mi1-Mi2-Hi, 2 speed: Lo-Hi
Air Flow angles:100º-80º-60º-40º and auto swing
Annual or weekly. Night set back option available allowing the setpoint to be set down to 12ºC
Individual prohibit operations for each remote controller function (Run/Stop,Temperature Setting, Mode Selection and Filter Reset) can be activated
Displays the measured intake temperature from each group
Displays a 4 digit code and the affected unit address. An error log is held showing the last 64 date stamped alarms
Allows each unit within the group to operate in test mode
Allows the group to be interlocked with a heat recovery Lossnay unit
Reduce the setpoint band of each individual unit (e.g. 23ºC to 25ºC)
Automatically switch heat pump outdoor unit to cooling or heating mode depending on the requirements
Commission the GB50 from the web pages
Administrator able to allow specific function access to guest
Hardwired connections are available for : Inputs: Level Signal-Batch Start/Stop, Batch Emergency StopOutputs: Start/Stop Status, Error/Normal Status
PAC-SC50KUA
City Multi or Mr Slim via PAC-SF80MA or M Series via MAC-399IF
250x38x130
DESCRIPTION
Technical Information
M-NET
PAC-SC50KUA
Viewed using Microsoft® Internet Explorer
Page 230
G50/AG150/GB50 Controller Web Screenshots
Login
Access to the web pages is secured using a customisedusername and password.
Monitor Air Conditioning - Overview
The first screen allows you to monitor all the units connected to theG50/AG150/GB50. Each icon displays On/Off, Faults and timer On/Off.
Monitor Air Conditioning - Block view
Each area of the building can be displayed with informationabout On/Off, Setpoint , Mode and Temperature.
Remote Controller Settings
Click on any icons in the Monitor View page to access theremote controller. Lossnay units can also be controlled. Buttons on the local controllers may be locked (On/Off, Mode, Setpoint, Filter Reset).
Daily, Weekly and Annual Scheduling (AS PIN code)
Scheduling may be set from the web pages. A night set back operation is available (Heat, 12ºC).Optional on the G50, standard on the AG150/GB50.
Monitor Fault Codes
Faults with the unit address can be displayed under fault conditions. Email status can also be shown.
Multiple Users (VRC PIN code)
If the G50/AG150/GB50 is connected to an office LAN, the staff will then be able to access the web pages. With VRC eachmember of staff will have their own username and password.
Multiple Users (VRC PIN code)
Installation costs will be reduced as no wall remotecontrollers will need to be purchased and installed.
New icons now available to suit model type installed
Page 231
Con
trol
sR
ange
200
8G
B50
Con
trol
ler
/ G
50/A
G15
0/G
B50
Web
Scr
eens
hots
G50/AG150/GB50 Desktop Remote Controller
More and more customers are using the G50/GB50 controller directly from their computers, so Mitsubishi Electric haslaunched a new, even simpler alternative which presents the customer with what looks like a standard remote controllerinterface - on their PC desktop. Called the PAR-21PC, the new application can also be minimised in the Desktop Toolbar,just like other Windows applications, so that the customer can have immediate control with just one click of the mouse.
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUA
ETHERNET
PAR-21PC Desktop Remote Controller
OPERATION PLATFORM
MAX No. OF INDOOR UNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
FAN SPEED SETTING
AIR FLOW DIRECTION
CLOCK DISPLAY
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
TIMER OPERATION
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional 2000 service pack 4or Windows Professional XP service pack 2 or Windows Vista
Up to 16 indoor units within a group
Run and Stop operation for a single group
Switches between Cool/Dry/Auto/Fan/Heat. Operation Mode will vary depending on the indoor unit. Auto mode is available with only R2 and WR2 systems
Sets the groups temperature control. Cool/Dry: 19-30°C, Heat:17-28°C, Auto: 19-28°C
4 speed: Lo-Mi1-Mi2-Hi, 2 speed: Lo-Hi
Air Flow angles:100º-80º-60º-40º and auto swing
Displays the time on the desktop controller
Displays the measured intake temperature from each group
Displays a 4 digit code and the affected unit address.
Weekly. Maximum of 3 time sequences with 3 Start/Stop times per day for all groups can be allocated
DESCRIPTION
Technical Information
M-NET
PAC-SC50KUA
*NOTE 1
Page 232
The new third party equipment interfaces allow the user to monitor and control third party equipment from the G50/GB50 web pages.
G50/AG150/GB50 Third Party Equipment Interfaces
*NOTE 1
FUNCTION
MAX No. OF INPUTS
MAX No. OF OUTPUTS
MAX No. OF EQUIPMENT
POWER SUPPLY
MONITOR
CONTROL
SIGNAL
DIMENSIONS - mm (WxDxH)
DESCRIPTION PAC-YG66DCA PAC-YG63MCA
Power supply required
Third Party Interfaces
From G50/GB50 web pages or TG2000
From G50/GB50 web pages or TG2000
Signal required to monitor and control equipment
2 x Digital
2 x Digital
2
-
-
-
-
-
-
24VDC
Run / Faults
On/Off
Volt free contact
200x45x120
2 x Analogue
24VDC
Temperature / Humidity
-
Temperature 4-20mA / 1-5V / 0-10V / Pt100Humidity 4-20mA / 1-5V / 0-10V
200x45x120
Technical Information
PAC-YG66DCA PAC-YG63MCA
General Equipment
Third party equipment can be monitored and controlledfrom the web pages.
Temperature / Humidity
Temperature and humidity can be monitored.
Trend Logging
Temperature and humidity can be recorded and displayed.
Temperature / Humidity Limit
Limit (high and low) can be set to trigger alarms via email.
ETHERNET
EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
Page 233
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUANOTE 2: Temperature Sensors and Humidity Sensors not supplied by MEUK G
50/A
G15
0/G
B50
Des
ktop
Rem
ote
Con
trol
ler
/G
50/A
G15
0/G
B50
Third
Par
ty E
quip
men
t In
terf
aces
Con
trol
sR
ange
200
8
ETHERNET
PLC
Ving Card Ving Card Ving Card
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUANOTE 2: It may take up to 3 minutes to switch ON the indoor unit (this time depends on how many indoor units are connected to the PLC).
PLC-QSERIES-LSPD
MAX No. OF INDOOR UNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
PERMIT/PROHIBIT SETTING
OCCUPIED ROOM SETTING
UNOCCUPIED ROOM SETTING
COMPATIBILITY
DIMENSIONS - mm (WxDxH)
FUNCTION
Up to 200 indoor units
Run and Stop operation for a single group
Switches between Cool/Dry/Auto/Fan/Heat. Operation Mode will vary depending on the indoor unit. Auto mode is available with only R2 and WR2 systems
Sets the groups temperature control. Cool/Dry: 19-30°C, Heat:17-28°C, Auto: 19-28°C
Individual prohibit operations for each remote controller function (Run/Stop,Temperature Setting, Mode Selection and Filter Reset) can be activated
ON, AUTO, 21ºC (Factory setting)
City Multi only
198x44x98
DESCRIPTION
Technical Information
M-NET
PAC-SC50KUA
*NOTE 1
If the temperature is below 16ºCthe PLC restarts the unit to ON,HEAT, 19ºC and stops the unit when the temperature has reached18ºC (Factory setting)
If the temperature is above 26ºCthe PLC restarts the unit to ON,COOL, 21ºC and stops the unit when the temperature has reached24ºC (Factory setting)
Page 234
G50/AG150/GB50 Programmable Logic Controller
The PLC controller allows a hotel (for example) to have more accurate control over its air conditioning. The PLC works in conjunction with the key card system installed in each bedroom in many hotels. When the room is occupied, the PLC will switch ON the unit and reset the air conditioning to predetermined settings (for instance AUTO, 21ºC). When the room is unoccupied, the PLC will monitor the temperature in the room. If the temperature is too low or too high, the PLC will restart the unit.
TG2000 Software
M-NET
ETHERNET
PC Based Software PackageThe TG2000 centralised PC based graphical software package allows the operator to control and monitor up to a maximum of 2000 indoor units. This software has been designed to connect directly to an air conditioning system via the G50/GB50 controller, allowing the operator the required functionality to control and monitor the complete air conditioning system from a central location.
Technical Information
PAC-SC50KUA
*NOTE 1
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUA
TG2000 PC Based software that works in conjunction with G50/GB50 Controller
OPERATING PLATFORM
MAX No. OF INDOOR UNITS
OPERATIONAL SECTIONS
ON/OFF
OPERATION MODE
SET TEMPERATURE
AIR SPEED
REMOTE CONTROLLERPROHIBIT/PERMIT
ABNORMALITY (FAULT) MONITORING
ROOM TEMPERATURE MONITORING
SCHEDULED ON/OFF
ENERGY SAVE CONTROL
TREND LOGGING
GRAPHICAL SCREENS
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional 2000 service pack 4 or Windows Professional XP service pack 2 or Windows Vista
2000 Indoor units, 50 indoor units per G50/AG150/GB50
The software package is split into two distinctive areas, System and Controls setting. System Setting: Password protected, System Configuration and group/block organisation, printer setting. Controls Setting: Normal Operation, monitoring and control functions as described below. The software allows individual indoor units to be allocated to logical groups, represented within user definable graphics screens, allocated during the system configuration
Indicates the On/Off status of each group within the selected graphical screen or entire building
Indicates the operational mode (Cool, Heat, Fan, Dry, Auto) for each group on the selected graphical screen
Displays the set temperature for each group on the selected graphical screen. Also able to limit the set point range in both heating and cooling mode
Displays the current fan speed setting for each group on the selected graphical screen
Displays the current prohibit/permit status for each groups remote controller on the selected graphical screen
Individual indoor unit fault monitoring is recorded within the fault log for both viewing and printing. Fault monitoring can also be viewed via the fault log for all units associated with a particular graphical screen or the entire building. Faults can also be tracked and printed using date of failure, date of recovery and error code
Displays the return air temperature of the master indoor unit within a group
On/Off schedules can be set for each group, each graphical screen or the entire building
Individual indoor unit, group of indoor units or a complete system can be controlled. There are various energy saving options available (Optional)
Able to log: Return air temperature, setpoint, mode, On/Off, power consumption by group or by indoor unit, watt-hour meter and then email to customer
The complete system configurations can be allocated between multiple screens. Each screen can display a bitmap image representing the area of the building or floor where the units or groups are physically located
The following information may be sent regularly and automatically via email: energy monitoring data, energy saving data, trend logging data (temperatures etc) and fault code history
DESCRIPTION
Page 235
Con
trol
sR
ange
200
8G
50/A
G15
0/G
B50
Prog
ram
mab
le L
ogic
Con
trol
ler
/T
G20
00 S
oftw
are
TG2000 Software with Energy Monitoring
M-NET
ETHERNET
PC Based Software PackageThe TG2000 centralised PC based graphical software package allows the operator to control and monitor up to amaximum of 2000 indoor units. This software has been designed to connect directly to an air conditioning system viaG50/GB50 controller, allowing the operator all the required functionality to control and monitor the complete airconditioning system from a central location. In addition to providing a centralised control facility, the TG2000 allowscomplete energy consumption data to be logged with user definable billing groups and electrical tariffs for billing purposes.
Technical Information
PAC-SC50KUA
*NOTE 1
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUANOTE 2: Energy Meters not supplied by MEUK
TG2000 Software with Energy Monitoring
OPERATING PLATFORM
MAX No. OF INDOOR UNITS
OPERATIONAL SECTIONS
ON/OFF
OPERATION MODE
SET TEMPERATURE
AIR SPEED
REMOTE CONTROLLERPROHIBIT/PERMIT
ABNORMALITY (FAULT) MONITORING
ROOM TEMPERATURE MONITORING
SCHEDULED ON/OFF
ENERGY CHARGING
WEB REFRIGERANT STATUS CHECK
ENERGY CHARGING
ENERGY SAVE CONTROL
LOAD SHEDDING
TREND LOGGING
GRAPHICAL SCREENS
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional 2000 service pack 4or Windows Professional XP service pack 2 or Windows Vista
2000 Indoor units, 50 indoor units per G50/AG150/GB50
The software package is split into two distinctive areas, System and Controls setting. System Setting: Password protected, System Configuration and group/block organisation, printer setting. Controls Setting: Normal Operation,monitoring and control functions as described below. The software allows individual indoor units to be allocated to logical groups, represented within user definable graphics screens, allocated during the system configuration
Indicates the On/Off status of each group within the selected graphical screen or entire building
Indicates the operational mode (Cool, Heat, Fan, Dry, Auto) for each group on the selected graphical screen
Displays the set temperature for each group on the selected graphical screen. Also able to limit the set point range in both heating and cooling mode
Displays the current fan speed setting for each group on the selected graphical screen
Displays the current prohibit/permit status for each groups remote controller on the selected graphical screen
Individual indoor unit fault monitoring is recorded within the fault log for both viewing and printing. Fault monitoring can also be viewed via the fault log for all units associated with a particular graphical screen or the entire building. Faults can also be tracked and printed using date of failure, date of recovery and error code
Displays the return air temperature of the master indoor unit within a group
On/Off schedules can be set for each group, each graphical screen or the entire building
Able to create or email bills for individual indoor units, groups of indoor units or a complete system (Optional) via the PAC-YG60MCA
Activate refrigerant volume checking function on Modular City Multi systems
Able to create bills for individual indoor units, groups of indoor units or a complete system (Optional)via the PAC-YG60MCA
Individual indoor unit, group of indoor units or a complete system can be controlled. There are various energy saving options available (Optional)
Activate energy saving mode when energy consumption is too high
Able to log: Return air temperature, setpoint, mode, On/Off, power consumption by group or by indoor unit, watt-hour meter and then email to customer
The complete system configurations can be allocated between multiple screens. Each screen can display a bitmap image representing the area of the building or floor where the units or groups are physically located
The following information may be sent regularly and automatically via email: energy monitoring data, energy saving data, trend logging data (temperatures etc) and fault code history
DESCRIPTION
METER 1 METER 2 METER 3 METER 4
PAC-YG60MCA
Page 236
M-NET
ETHERNET
PC Based Software PackageThe TG2000 centralised PC based graphical software package allows the operator to control and monitor up to a maximum of 2000 indoor units. This software has been designed to connect directly to an air conditioning system via G50/GB50 controller, allowing the operator all the required functionality to control and monitor the complete air conditioning system from a central location. In addition to providing a centralised control facility, the TG2000 allows you to monitor and control third party equipment.
Technical Information
PAC-SC50KUA
*NOTE 1
PAC-YG66DCA PAC-YG63MCA
EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
TG2000 Software with Third Party Equipment
OPERATING PLATFORM
MAX No. OF INDOOR UNITS
OPERATIONAL SECTIONS
ON/OFF
OPERATION MODE
SET TEMPERATURE
AIR SPEED
REMOTE CONTROLLERPROHIBIT/PERMIT
ABNORMALITY (FAULT) MONITORING
ROOM TEMPERATURE MONITORING
SCHEDULED ON/OFF
ENERGY SAVE CONTROL
TREND LOGGING
GRAPHICAL SCREENS
THIRD PARTY EQUIPMENT MONITOR
THIRD PARTY EQUIPMENT CONTROL
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional 2000 service pack 4or Windows Professional XP service pack 2 or Windows Vista
2000 Indoor units, 50 indoor units per G50/AG150/GB50
The software package is split into two distinctive areas, System and Controls setting. System Setting: Password protected, System Configuration and group/block organisation, printer setting. Controls Setting: Normal Operation, monitoring and control functions as described below. The software allows individual indoor units to be allocated to logical groups, represented within user definable graphics screens, allocated during the system configuration
Indicates the On/Off status of each group within the selected graphical screen or entire building
Indicates the operational mode (Cool, Heat, Fan, Dry, Auto) for each group on the selected graphical screen
Displays the set temperature for each group on the selected graphical screen. Also able to limit the set point range in both heating and cooling mode
Displays the current fan speed setting for each group on the selected graphical screen
Displays the current prohibit/permit status for each groups remote controller on the selected graphical screen
Individual indoor unit fault monitoring is recorded within the fault log for both viewing and printing. Fault monitoring can also be viewed via the fault log for all units associated with a particular graphical screen or the entire building. Faults can also be tracked and printed using date of failure, date of recovery and error code
Displays the return air temperature of the master indoor unit within a group
On/Off schedules can be set for each group, each graphical screen or the entire building
Individual indoor unit, group of indoor units or a complete system can be controlled. There are various energy saving options available (Optional)
Able to log: Return air temperature, setpoint, mode, On/Off, power consumption by group or by indoor unit, watt-hour meter and then email to customer
The complete system configurations can be allocated between multiple screens. Each screen can display a bitmap image representing the area of the building or floor where the units or groups are physically located
Monitor general equipment Run and Faults via the PAC-YG66DCA interface and Temperature and Humidity via the PAC-YG63MCA
Control general equipment On/Off via the PAC-YG66DCA
The following information may be sent regularly and automatically via email: energy monitoring data, energy saving data, trend logging data (temperatures etc) and fault code history
DESCRIPTION
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUANOTE 2: Temperature and Humidity Sensors not supplied by MEUK
Page 237
TG2000 Software with Third Party Equipment
TG
2000
Sof
twar
e w
ith E
nerg
y M
onito
ring
/T
G20
00 S
oftw
are
with
Thi
rd P
arty
Equ
ipm
ent
Con
trol
sR
ange
200
8
PC Based Software Package used to monitor and control multiple sitesThe TG2000 WAN centralised PC based graphical software package allows the operator to control and monitor upto a maximum of 1000 sites. Utilising the companies Wide Area Network, the complete (geographically distributed) air conditioning asset base can be controlled and monitored from a centralised location.
SITE 1(i.e. MANCHESTER)*NOTE 1
SITE 999(i.e. BIRMINGHAM)*NOTE 1
TG2000WAN (Wide Area Network) Software
OPERATING PLATFORM
MAX No. OF SITES
MAX No. OF INDOOR UNITS PER SITE
OPERATIONAL SECTIONS
ON/OFF
OPERATION MODE
SET TEMPERATURE
AIR SPEED
REMOTE CONTROLLERPROHIBIT/PERMIT
ABNORMALITY (FAULT) MONITORING
ROOM TEMPERATURE MONITORING
SCHEDULED ON/OFF
GRAPHICAL SCREENS
THIRD PARTY EQUIPMENT MONITORING
THIRD PARTY EQUIPMENT CONTROL
FUNCTION
Pentium III, CPU 1000 Mhz, 256 MB RAM, 6GB or more. Internal LAN 10/100 MBps running Windows Professional2000 service pack 4 or Windows Professional XP service pack 2 or Windows Vista
1000
2000 Indoor units, 50 indoor units per G50/AG150/GB50 (per site)
The software package is split into two distinctive areas, System and Controls setting. System Setting: Password protected, System Configuration and group/block organisation, printer setting. Controls Setting: Normal Operation,monitoring and control functions as described below. The software allows individual indoor units to be allocated to logical groups, represented within user definable graphics screens, allocated during the system configuration
Indicates the On/Off status of each group within the selected graphical screen or entire building
Indicates the operational mode (Cool, Heat, Fan, Dry, Auto) for each group on the selected graphical screen
Displays the set temperature for each group on the selected graphical screen. Also able to limit the set point range in both heating and cooling mode
Displays the current fan speed setting for each group on the selected graphical screen
Displays the current prohibit/permit status for each groups remote controller on the selected graphical screen
Individual indoor unit fault monitoring is recorded within the fault log for both viewing and printing. Fault monitoring can also be viewed via the fault log for all units associated with a particular graphical screen or the entire building. Faults can also be tracked and printed using date of failure, date of recovery and error code
Displays the return air temperature of the master indoor unit within a group
On/Off schedules can be set for each group, each graphical screen or the entire building
The complete system configurations can be allocated between multiple screens. Each screen can display a bitmap image representing the area of the building or floor where the units or groups are physically located
Monitor general equipment Run and Faults via the PAC-YG66DCA interface and Temperature and Humidity via the PAC-YG63MCA
Control general equipment On/Off via the PAC-YG66DCA
The following information may be sent regularly and automatically via email: energy monitoring data, energy saving data, trend logging data (temperatures etc) and fault code history
DESCRIPTION
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUANOTE 2: The TG2000 WAN cannot be utilised if the following site functions are required: energy charging, energy saving and trend logging.NOTE 3: Temperature and Humidity Sensors not supplied by MEUK
Technical Information
PAC-YG66DCA PAC-YG63MCA
EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
PAC-YG66DCA PAC-YG63MCA
EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
WAN
Page 238
TG2000 WAN (Wide Area Network) Software
TG2000 ScreenshotsDisplay Whole
The 2000 indoor units status may be shown on one screen.
Display Block
Block may be set for each area. Settings may bechanged by one click of the mouse for each area.
Display Floor
AutoCAD drawing may be imported to TG2000 to display floor screens.
Remote Controller Settings
Click on any icons in the floor view to access the remote controller settings. Buttons on the local controllers may be locked (On/Off, Mode, Setpoint, Filter reset).
Daily, Weekly and Annual Scheduling (AS PIN code)
Scheduling may be set from the TG2000. A night set back operation is available (HEAT, 12ºC). Optional on the G50, standard with the GB50.
Monitor Fault Codes
Faults with the unit address can be displayed underfault conditions.
Energy Monitoring (EC PIN code)
TG2000 in conjunction with energy meters can monitor the energy consumption for each outdoor unit, indoor unit or area. The indoor unit run hours can also be displayed.
Energy Saving (ES PIN code)
TG2000 offers different energy saving options including load shedding.
New icons now available to suit model type installed
TG
2000
WA
N /
TG
2000
Scr
eens
hots
Page 239
Con
trol
sR
ange
200
8
BACnet® INTERFACEFUNCTION NETWORK VARIABLE NOTES
ControlOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Airflow Direction
Filter Sign
MonitorOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Airflow Direction
Fault Code
Filter Sign
Room Temperature
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint
Horizontal - 60,80,100º swing
Normal/Reset
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint
Horizontal - 60,80,100º swing
4 Character code - Indicates all unit alarms
-
-
ProconTM BAC-IP/50
BEMS BACnet® Interface
To further enhance our complete open system network offering, we offer a BACnet® gateway solution. Utilising the ASHRAE BACnet® standard, complete control and monitoring integration can be achieved with up to 50 air conditioning units.
BACnet® INTERFACEFUNCTION BAC-IP/50 COMPATIBLE WITH
MAX No. OFINDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
50
City MultiMr Slim via PAC-SF80MAM Series via MAC-399IF
144x34x104
Andover Controls
York BMS
Siemens
Priva Building Intelligence
Delta Controls
Technical Information
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUA
BAC-IP/50
ETHERNET PAC-SC50KUA
M-NET
*NOTE 1
Page 240
ProconTM BAC-A/50
BEMS BACnet® Mr Slim Interface
A new BACnet® Interface has been specially developed for the Mr Slim systems. The BAC-A/50 cancontrol up to 50 individual systems.
Technical Information
BACnet® MR SLIM INTERFACEFUNCTION NETWORK VARIABLE NOTES
ControlOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Airflow Direction
Filter Sign
MonitorOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Airflow Direction
Fault Code
Filter Sign
Room Temperature
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint
Horizontal - 60,80,100º swing
Normal/Reset
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint
Horizontal - 60,80,100º swing
4 Character code - Indicates all unit alarms
-
-
BACnet® MR SLIM INTERFACEFUNCTION BAC-A/50 COMPATIBLE WITH
MAX No. OFOUTDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
50
Mr Slim via PAC-SK81SI
270x75x210
Andover Controls
York BMS
Siemens
Priva Building Intelligence
Delta Controls
PAC-SK81SI
BAC-A/50
Con
trol
sR
ange
200
8
Page 241
BEM
S B
AC
net®
Inte
rfac
e /
BEM
S B
AC
net®
Mr
Slim
Inte
rfac
e
BEMS LonWorks® Interface
The Mitsubishi Electric LMAP continues to strengthen the ability of our products to interface with other third partybuilding control systems using the globally recognised and accepted open network protocol Echelon LonWorks®.LonWorks® was introduced into the building services industry a number of years ago with the aim of establishingitself as the defacto communications standard. Many hundreds of products now exist that utilise the LonWorks®
protocol from complete systems like BEMS, lighting, power monitoring and security down to simple sensors and relay switches.
To ensure that our products can connect directly and easily with other LonWorks® products, the L-MAP02 was designed utilising Echelon MIPS technology and was the first to provide data in the LonWorks®
SNVT (Standard Network Variable Type) format.
LMAP
Technical Information
LMAP LonWorks® INTERFACEFUNCTION NETWORK VARIABLE NOTES
ControlOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Filter Sign
MonitorOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Fault Code
Filter Sign
Room Temperature
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint (only available when using PAC-YT51CRA or PAR-21MAA)
Normal/Reset
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint (only available when using PAC-YT51CRA or PAR-21MAA)
4 Character code - Indicates all unit alarms
-
-
LMAP LonWorks® INTERFACEFUNCTION LMAP COMPATIBLE WITH
MAX No. OFINDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
50(G50/AG150/GB50 optional)
City MultiMr Slim via PAC-SF80MAM Series via MAC-399IF
340x60x360
Honeywell
Johnson Controls
Realtime Control Systems (LTX51/LTX21 via VCI)
Smart Controls
LMAP
M-NET
Page 242
Technical Information
BEMS Modbus Interfaces
To further compliment the existing control and interface product ranges being offered by Mitsubishi Electricto support their air conditioning systems, the Modbus range has been developed to accommodate the typical end-user needs as experienced within the UK market.
IP-32MIP-50MIP-100M
ProconTM IP-32M / IP-50M / IP-100M
ETHERNET PAC-SC50KUA
M-NET
MODBUS INTERFACE UNITS - OPERATIONAL INFORMATION
FUNCTION NETWORK VARIABLE MODBUS
ControlOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
MonitorOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
Fault Code 4 Character code – Indicates all unit alarms
Room Temperature -
MODBUS INTERFACESIP-50M IP-100M COMPATIBLE WITH
MAX No. OFINDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
32
City MultiMr Slim via PAC-SF80MAM Series via MAC-399IF
270x75x210
50
City MultiMr Slim via PAC-SF80MAM Series via MAC-399IF
270x75x210
100
City MultiMr Slim via PAC-SF80MAM Series via MAC-399IF
270x75x210
Trend via Synapsys SXNC200CylonSatchwellCrestron (Home automation)InvensysInteractive HomesNorth BTAndoverSiemens
*NOTE 1
Modbus
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUA
Page 243
Con
trol
sR
ange
200
8BE
MS
LonW
orks
®In
terf
ace
/BE
MS
Mod
bus
Inte
rfac
es
FUNCTION IP-32M
BEMS Modbus Mr Slim Interface
To further compliment the existing control and interface product ranges being offered by Mitsubishi Electric to support their air conditioning systems, the Modbus range has been developed to accommodate the typical end-user needs as experienced within the UK market.
ProconTM A32M
Technical Information
MODBUS MR SLIM INTERFACE - OPERATIONAL INFORMATION
FUNCTION NETWORK VARIABLE MODBUS
ControlOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
MonitorOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
Fault Code 4 Character code – Indicates all unit alarms
Room Temperature -
MODBUS MR SLIM INTERFACEFUNCTION A32M COMPATIBLE WITH
MAX No. OFOUTDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
32
Mr Slim via PAC-SK81SI
270x75x210
Trend via Synapsys SXNC200CylonSatchwellCrestron (Home automation)InvensysInteractive HomesNorth BTAndoverSiemens
PAC-SK81SI
A32M
Modbus
Page 244
NOTE: Not available on SEZ / SLZ
BEMS Modbus Splits Interface
To further compliment the existing control and interface product ranges being offered by Mitsubishi Electric to support their air conditioning systems, the Modbus range has been developed to accommodate the typical end-user needs as experienced within the UK market.
ProconTM A1M
Technical Information
MODBUS SPLITS INTERFACE - OPERATIONAL INFORMATION
FUNCTION NETWORK VARIABLE MODBUS
ControlOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
MonitorOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
Fault Code 4 Character code – Indicates all unit alarms
Room Temperature -
MODBUS SPLITS INTERFACEFUNCTION A1M COMPATIBLE WITH
MAX No. OFINDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
1
M SeriesMr Slim
72x27x50
Trend via Synapsys SXNC200CylonSatchwellCrestron (Home automation)InvensysInteractive HomesNorth BTAndoverSiemens
A1M
Modbus
Page 245
Con
trol
sR
ange
200
8BE
MS
Mod
bus
Mr
Slim
Inte
rfac
e /
BEM
S M
odbu
s Sp
lits
Inte
rfac
e
BEMS KNX-EIB Interfaces
To further compliment the existing control and interface product ranges being offered by Mitsubishi Electricto support their air conditioning systems, the KNX-EIB range has been developed to accommodate the typical end-user needs as experienced within the UK market.
KNX-EIB-IP-15KNX-EIB-IP-100
ProconTM KNX-EIB-IP-15/100
ETHERNET PAC-SC50KUA
M-NET
KNX-EIB CITY MULTI INTERFACE UNITS - OPERATIONAL INFORMATION
FUNCTION NETWORK VARIABLE MODBUS
ControlOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
MonitorOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
Fault Code 4 Character code – Indicates all unit alarms
Room Temperature -
KNX-EIB CITY MULTI INTERFACESFUNCTION KNX-EIB-IP-15 KNX-EIB-IP-100 COMPATIBLE WITH
MAX No. OFINDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
15
City MultiMr Slim via PAC-SF80MAM Series via MAC-399IF
107x58x105
100
City MultiMr Slim via PAC-SF80MAM Series via MAC-399IF
107x58x105
ABBIntelligent BuildingsNova Controls LtdSiemens
*NOTE 1
KNX-EIB
*NOTE 1: Applicable with G50 / PAC-SC50KUA or AG150 / PAC-SC51KUA or GB50 / PAC-SC50KUA
Page 246
Technical Information
BEMS KNX-EIB Splits Interface
To further compliment the existing control and interface product ranges being offered by Mitsubishi Electric to support their air conditioning systems, the KNX-EIB range has been developed to accommodate the typical end-user needs as experienced within the UK market.
ProconTM KNX-EIB-A-1
Technical Information
KNX-EIB SPLITS INTERFACE - OPERATIONAL INFORMATION
FUNCTION NETWORK VARIABLE MODBUS
ControlOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
MonitorOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
Fault Code 4 Character code – Indicates all unit alarms
Room Temperature -
KNX-EIB SPLITS INTERFACEFUNCTION KNX-EIB-A-1 COMPATIBLE WITH
MAX No. OFINDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm(WxDxH)
1
M SeriesMr Slim
60x25x48
ABBIntelligent BuildingsNova Controls LtdSiemens
Page 247
KNX-EIB-A-1
KNX-EIB Con
trol
sR
ange
200
8BE
MS
KN
X-E
IB In
terf
aces
/
BEM
S K
NX
-EIB
Spl
its In
terf
ace
M2M - OSM2M - ES
Optimised Start for Air ConditioningEnergy Saving Capability
M2M Software Options - Pin Code Activation
M2M INTERFACE - OPERATIONAL INFORMATION
FUNCTION NETWORK VARIABLE
ControlOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Airflow Direction
Filter Sign
MonitorOn/Off
Mode Operation
Setpoint Adjustment
Fan Speed Control
Permit / Prohibit
Airflow Direction
Fault Code
Filter Sign
Room Temperature
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint
Horizontal - 60,80,100º swing
Normal/Reset
Run/Stop
Cool / Dry / Heat / Auto / Fan
Cooling 19-30ºC, Heating 17-28ºC, Auto 19-28ºC
Lo-Mi1-Mi2-Hi
On/Off, Mode, Setpoint
Horizontal - 60,80,100º swing
4 Character code - Indicates all unit alarms
-
-
NOTESUP TO 25 GROUPS UP TO 50 GROUPS
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
M2M - Machine 2 Machine Interface
To offer remote management of its air conditioning units to companies with large numbers of dispersed offices, Mitsubishi Electric has adopted the M2M platform. The machine-to-machine (M2M) technology platform allows customers to integrate multiple sites into one network. The air conditioning units as well as third party equipmentwill be wirelessly connected to the M2M server and use the GPRS network to communicate.
MEUK
M2M SERVER
Technical Information
M2M INTERFACEFUNCTION DESCRIPTION
MAX No. OF INPUTS
MAX No. OF OUTPUTS
MAX No. OF INDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm (WxDxH)
22 (4 to 20mA, 0 to 10VDC, 10kΩ resistor, digital)
4 (volt free contact)4 (pulse with modulation)
50
City Multi, Mr Slim and M Series
300x70x350
ProconTM Maxi M2M-IP/50
Page 248
GPRS
Maxi M2M-IP/50 GB50
DEMONSTRATIONVisit m2m.mitsubishielectric.co.uk/demo to use the live demonstration space (login: demo / password: demo)
METER 1 METER 2 METER 3 METER 4 EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
Maxi M2M-IP/50 GB50
METER 1 METER 2 METER 3 METER 4 EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
M2M - OSM2M - ES
Optimised Start for Air ConditioningEnergy Saving Capability
M2M Software Options - Pin Code Activation DEMONSTRATIONVisit m2m.mitsubishielectric.co.uk/demo to use the live demonstration space (login: demo / password: demo)
To offer remote management of its air conditioning units to companies with large numbers of dispersed offices,Mitsubishi Electric has adopted the M2M platform. The machine-to-machine (M2M) technology platform allowscustomers to integrate multiple sites into one network. The air conditioning units as well as third party equipment will be wirelessly connected to the M2M server and use the GPRS network to communicate.
Con
trol
sR
ange
200
8
Page 249
M2M SPLITS INTERFACE - OPERATIONAL INFORMATION
FUNCTION NETWORK VARIABLE NOTES
ControlOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
Time Zone Weekly scheduling available
MonitorOn/Off Run/Stop
Mode Operation Cool / Dry / Heat / Auto / Fan
Setpoint Adjustment Cooling 19-30˚C
Heating 17-28˚C
Auto 19-28˚C
Fan Speed Control Lo-Mi1-Mi2-Hi
Fault Code 4 Character code – Indicates all unit alarms
Room Temperature -
Time Zone Weekly scheduling available
M2M SPLITS INTERFACEFUNCTION DESCRIPTION
MAX No. OF INPUTS
MAX No. OF OUTPUTS
MAX No. OF INDOOR UNITS
COMPATIBILITY
DIMENSIONS - mm (WxDxH)
8 (4 to 20mA, 0 to 10VDC, 10kΩ resistor, digital)
4 (pulse with modulation)
16
Mr Slim and M Series via Procon A1M
255x60x180
Technical Information
M2M
Inte
rfac
e /
M2M
Spl
its In
terf
ace
MEUK
M2M SERVER
GPRS
A1MMini M2M-A/16
METER 1 METER 2 METER 3 METER 4 EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
Mini M2M-A/16
METER 1 METER 2 METER 3 METER 4 EQUIPMENT 1 EQUIPMENT 2 SENSOR 1 SENSOR 2
ProconTM Mini M2M-A/16
M2M - Machine 2 Machine Splits Interface
A1M
A1M A1M
M2M-Machine 2 Machine Web Screenshots
MEUK Website
M2M is accessible using MEUK website.
Login
A username and password is required to monitorand control sites.
Monitor Active Alarms and Sites
All sites are listed with active alarm sites.
Status
A site can be selected to monitor each system.
Set Parameters
Indoor unit and third party equipment can becontrolled from the Website.
Reports
Reports can be generated for analysis.
Dashboard
G50/AG150/GB50 web pages are available forthe air conditioning units
Administration
Using the administration level, the phone numbers and email of each duty engineer may be set and activated.
Technical Information
Page 250
G50 Control PanelsMitsubishi Electric can supply G50 control panels (surface or internally mounted). This allows easy installation.
M-NET
G50 Control Panel
G50 CONTROL PANELSMODEL No. OF G50 No. OF INDOOR UNITS ROUTER MOUNTED DIMENSIONS (WxDxH)
GP50PS1
GP50PS2
GP50PS3
GP50PS4
GP50PI1
GP50PI2
GP50PI3
GP50PI4
GP50PSR1
GP50PSR2
GP50PSR3
GP50PSR4
GP50PIR1
GP50PIR2
GP50PIR3
GP50PIR4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
50
100
150
200
50
100
150
200
50
100
150
200
50
100
150
200
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
Surface
Surface
Surface
Surface
Internally
Internally
Internally
Internally
Surface
Surface
Surface
Surface
Internally
Internally
Internally
Internally
600x200x600
600x200x600
800x250x600
800x250x600
600x200x600
600x200x600
800x250x600
800x250x600
600x200x600
600x200x600
800x250x600
800x250x600
600x200x600
600x200x600
800x250x600
800x250x600
Technical Information
Page 251
Con
trol
sR
ange
200
8M
2M W
eb S
cree
nsho
ts /
G50
Con
trol
Pan
els
Run / Standby Control PanelsThe run/standby panel allows one system to run one week and the other one to run the other week. If one system fails, the run/standby panel will start the other one. If the temperature is too high, the panel will also start the 2 systems and enable an audible alarm.
Run / StandbyControl Panel
Technical Information
RUN / STANDBY CONTROL PANELSMODEL No. OF SYSTEMS RUN STANDBY HIGH TEMP
PANEL_RS1
PANEL_RS2
PANEL_RS3
2
3
4
1
2
3
1
1
1
YES
YES
YES
ALARM
YES
YES
YES
DIMENSIONS (WxDxH)
400x210x600
500x210x700
500x210x700
Page 252
Energy Monitoring Control PanelsEnergy monitoring is key to the compliance with Part L2. To perform energy monitoring; a lot of differentproducts are required. To optimise the time of installation, Mitsubishi Electric can now supply an energymonitoring panel with energy meter, current transformers, breakers and the interface to the Mitsubishi Electric communication network.
M-NET
Energy Monitoring Control Panel
FUNCTION
PANEL_EM100A
PANEL_EM200A
No. OF SYSTEMS
ENERGY MONITORING CONTROL PANELS
1
2
MAX RUNNING CURRENT (A)
100
200
DIMENSIONS (WxDxH)
600x210x800
600x210x800
Technical Information
Power Supply
Page 253
Con
trol
sR
ange
200
8R
un/S
tand
by C
ontr
ol P
anel
s /
Ener
gy M
onito
ring
Con
trol
Pan
els
Split-System A2M InterfacesThe City Multi systems use advanced communication protocol called M-NET. The Split-Systems can be interfaced to M-NET, allowing compatibility with the main centralised controller (G50, AG150, GB50, TG2000). An A2M adapter would be required per outdoor unit for Mr Slim and per indoor unit for Mr Slim S Series or M Series indoor units.
FUNCTION
COMPATIBILITY
CONNECTION TO
MNET SETTINGS
DIMENSIONS - mm (WxDxH)
Mr Slim S Series / M Series Indoor Unit
Indoor Unit
Dip Switches
160x55x70
PAC-SF80MA
SPLIT-SYSTEM A2M INTERFACES
Mr Slim Outdoor Unit
Outdoor Unit
Rotary Switches
130x15x90
MAC-399IF
Technical Information
PAC-SF80MA
Con
trol
sR
ange
200
8Sp
lit-S
yste
m A
2M In
terf
aces
Page 254
Mitsubishi Electric Partner ProgrammeOpen to all contractors - large or small - the Mitsubishi Electric Par tner Programme offers contractors atotally new and unique set of benefits. There are two categories within the programme - Accredited Installerand Business Solutions Partner - these levels being a straight-forward reflection of the Partner’sstage of growth, with all customers signing up to the programmes standards and committing to continued training and professional development.
For more information please contact your local sales office
Mitsubishi Electric Training OptionsMitsubishi Electric has four state-of-the-ar t training suites based at different locations around the countr y for your convenience.Providing training for all levels of exper tise, our courses are taught by experienced engineers, with a wealth of knowledge and are all CPD accredited.
For bookings please telephone 01707 278797
Systems marked with the ECA logo have an energy label of A or B, are registered on theEnergy Technology List and hence qualify for 100% first year enhanced capital allowances(whole system cost and ‘reasonable’ cost of installation). For further information please go to www.eca.gov.uk
Nominal conditions cooling: indoor 27˚C DB, 19˚C WB; outdoor 35˚C DB, 24˚C WB.Nominal conditions heating: indoor 20˚C DB; outdoor 7˚C DB, 6˚C WB.UK Conditions: Summer; indoor 21˚C DB, 15˚C WB; outdoor 27˚C DB. Winter; indoor 21˚C DB; outdoor -1˚C WB.
Notes: Recommended fuse ratings given throughout this price list are based on British Standard (BS88).
the name Mitsubishi is synonymous with excellenceKnown the world over, Mitsubishi is a trusted global leaderassociated with a variety of products and services. Founded in1907, the company known today as Mitsubishi Electric, quicklyrose to the forefront of the air conditioning industry - a position we still enjoy today.
Unsurpassed air conditioning from Mitsubishi ElectricAir conditioning is an ideal way of controlling the air quality inside any building, large or small.Not only does it cool in the summer months but air conditioning can also heat, replacing traditionalheating systems. More and more people today are experiencing the benefits of comfortable working,living and leisure environments made possible with air conditioning. As market leaders, we prideourselves in providing high performance, competitive systems with low running costs.
Protecting the environmentMitsubishi Electric boasts an explicit commitment to sustainable business practices such as energy and resource efficiency, minimising ecological impacts of our products and reducing greenhouse gas emissions. We are the only manufacturer in the industry recognised by Portfolio 21 as one of the top five companies in the world for our sustainable environmental policy. All of our factories are also ISO 14001 registered, the international standard that specifies a process for controlling and improving a company's environmental performance and with the advent of our Green Gateway Initiative, we strive to constantly promote best practice.
The Forest Stewardship Council (FSC) is an international network promoting responsible management of the world's forest. The paper this catalogue is printed on supports the development of responsible forest management worldwide. The wood comes from FSC certified, well managed forests, company controlled sources and/or recycled material.
2008 Product Catalogue
Telephone: 01707 282880Post Sales Technical Support / Spares and Warranty: 0870 3000 300
email: [email protected]
web: www.mitsubishielectric.co.uk/aircon
UNITED KINGDOM Mitsubishi Electric Europe Air Conditioning Systems DivisionTravellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. General enquiries Telephone: 01707 282880 Fax: 01707 278674
IRELAND Mitsubishi Electric Europe Westgate Business Park, Ballymount, Dublin 24, Ireland. Telephone: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531)
Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2008. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described, or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.
Printed in April 2008
SAP No. 214760
www.greengatewayinitiative.co.uk
Designed by Square Bear Ltd 01604 899099. Square Bear Ltd are committed to using FSC certified paper and printers, wherever possible.
The laminate used on this brochure is environmentally friendly, recyclable and biodegradable
Features Key
2008 Product CatalogueA comprehensive range of Air Conditioning Systems from Mitsubishi Electric