2008 title 24 nonresidential hvac acceptance testing for...

121
2008 Title 24 Nonresidential HVAC Acceptance Testing for Building Officials & Contractors Presented by: name title date California Commissioning Collaborative

Upload: lenhan

Post on 01-Feb-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

2008 Title 24 Nonresidential HVAC Acceptance Testing

for Building Officials & Contractors

Presented by: name title

date

California Commissioning Collaborative

Page 2: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 2

What this talk will cover

•  Description of acceptance testing requirements in 2008 Title 24

•  The motivation behind the requirements

•  How acceptance testing affects design and specification practices

•  How it impacts compliance documentation

•  New responsibilities of the designer and the contractor

•  Impacts on plan review and inspection

Page 3: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 3

Overview

•  Building Efficiency a product of: –  Materials and equipment

–  Installation and set-up

–  Occupant patterns and control

•  Traditional standards –  Specify materials, equipment, controls

–  Law of diminishing returns for more efficient equipment

•  2008 Title 24 standards – Acceptance Tests –  Ensure equipment works as intended

Page 4: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 4

What is acceptance testing?

•  Two components of acceptance testing – Construction inspection

•  Is the specified equipment installed and calibrated?

– Functional performance testing •  Does the equipment work as intended?

•  Tests designed to uncover specification, installation or set-up problems

•  Not replacing commissioning – Commissioning = broader scope

Page 5: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 5

Is acceptance testing needed?

•  PIER Small Commercial HVAC survey* •  Small commercial buildings < 4 yrs old

– 64% of economizers failed •  Cooling energy increased by 37%

– 38% of supply fans cycling during occupancy •  Violation of Title 24

– 30% unoccupied fan operation •  Increase of fan and heating energy

– 8% no outside air – 8% simultaneous heating and cooling

* http://www.energy.ca.gov/reports/2003-11-17_500-03-082.PDF

Page 6: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 6

Who benefits from acceptance tests?

•  The designer –  System installed and controlled according to code design intent –  Reputation based on correct equipment operation

•  The contractor –  Technician’s work is reviewed –  Fewer call-backs

•  The owner –  Equipment works right the first time –  Energy cost savings

•  Society –  Less pollution associated with reduced energy consumption

Page 7: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 7

Acceptance Tests

•  Required self-certification that equipment and systems were tested and work as intended

•  Requires someone with a license to sign off on the testing (architect, engineer or contractor)

•  Only one test (air distribution efficiency) requires 3d party verification – Home Energy Rating Service (HERS)

Page 8: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 8

Resources

•  2008 Standards (Title 24) •  2008 Standards Nonresidential Appendices NA 7

–  Reference – not needed for design or testing

•  2008 Nonresidential Energy Standards Compliance Manual –  Chapter 4 – Mechanical Systems –  Chapter 10 – Acceptance Requirements –  End of Manual – Compliance and Acceptance Forms

•  CEC Resources –  http://www.energy.ca.gov/title24/2008standards/ –  CEC Bldg Standards Hotline 1-800-772-3300

Page 9: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 9

Acceptance Chapter in Nonresidential Manual

•  Overview of compliance process

•  At-A-Glance – 2 page overview of test – Purpose Ø Estimated Time

– Benefits Ø Warnings or Cautions

–  Instrumentation Ø Test conditions

– Acceptance Criteria

•  Detailed test description

Page 10: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 10

Acceptance and Compliance Forms

•  Compliance forms –  Filled out by designer –  MECH-1-C (C for compliance) –  Reviewed by plans checker

•  Acceptance Forms –  Filled out by person conducting test –  Reviewed by person with a license –  Usually contractor, TAB or commissioning agent –  MECH-1-A to MECH (A for acceptance) –  Collected by Inspector prior to CO (Certificate of Occupancy)

•  Forms in Appendix A of the Nonresidential Compliance Manual

Page 11: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 11

Code Enforcement Process: Plans and Specifications

•  Compliance documentation with equipment specification and forms – MECH-1C lists all tests and which

equipment must be tested

– MECH-3C lists design minimum outside air •  Criteria for outside air tests (NJ.3.1 & 3.2)

•  Plan checker reviews and approves or asks for modifications – All AC systems should be listed with

appropraite tests

Page 12: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 12

Code Enforcement Process: Testing and Inspection

•  Installing contractor or other “eligible professional” conducts tests and fills out MECH-#A acceptance forms –  Equipment fixed until it passes all tests

•  Completed forms handed to inspector along with other documentation –  Inspector makes sure documentation is filled out

correctly –  Incomplete documentation is returned to contractor

•  Certificate of Occupancy granted when building is in full compliance

Page 13: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 13

Designer has a big impact on ease and cost of acceptance tests

•  Designer clearly identifies tests – Problem if covered equipment not specified

on MECH-1C form and later needs testing

•  Designer specifies equipment – Pre-calibrated equipment is cheaper

•  Designer builds in test capabilities – Test ports and pre-installed gauges

– Valves for isolating equipment

Page 14: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 14

Key Statements in MECH-1C

•  The plans meet code

•  I am qualified to sign these forms

•  List of all mechanical acceptance tests with blanks for: – Equipment to be tested

– Checkboxes to indicate which tests apply to the equipment listed

Page 15: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 15

HVAC Acceptance Tests

•  Defined in Standards’ Mandatory Section 125

•  Detailed in the Appendix NA7

•  Nonresidential Compliance Manual – Test Descriptions in Chapter 10

– Forms in Appendix A

Page 16: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 16

Acceptance Requirements (1 of 2)

ACM Section and Test Standard Section

Additional Standard Section

Certificate of Acceptance

NA 7.5.1.1 Variable Air Volume Systems Outdoor Air 125(a)1 121 MECH-2A

NA 7.5.1.2 Constant Volume Systems Outdoor Air NA 7.5.2 Constant Volume Packaged HVAC Systems 125(a)2 122 MECH-3A

NA 7.5.3 Air Distribution 125(a)3 124, 144(k) or 149(b)1D MECH-4A

NA 7.5.4 (Air-Side) Economizer 125(a)4 144(e) MECH-5A

NA 7.5.5 Demand Control Ventilation 125(a)5 121(c)3&4 MECH-6A

NA 7.5.6 Supply Fan Variable Flow Controls 125(a)6 144(c)2 MECH-7A

NA 7.5.7 Valve Leakage Test 125(a)7 & 8 144(j)2 or 3 MECH-8A

NA 7.5.8 Supply Water Temperature Reset Controls 125(a)9 144(j)4 MECH-9A

NA 7.5.9 Hydronic System Variable Flow Controls 125(a)7 144(j)6 MECH-10A

NA 7.5.10 Automatic Demand Shed Controls 125(a)10 122(h) MECH-11A

Updated for 2008

Page 17: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 17

New Acceptance Requirements (2 of 2) for Compliance Credit Measures

ACM Section and Test Standard Section

Additional Standard Section

Certificate of Acceptance

NA 7.5.1.11 FDD for Packaged DX Systems 125(a)11 MECH-12A

NA 7.5.1.12 FDD for AHUS and Zone Terminal Units 125(a)12 MECH-13A

NA 7.5.1.13 Distributed Energy Storage DX AC Systems 125(a)13 MECH-14A

NA 7.5.1.14 Thermal Energy Storage Systems 125(a)14 MECH-15A

Page 18: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 18

Acceptance Tests Always Applied to Single Zone Rooftop Units

•  MECH-2A - Outdoor Air for CAV – Measured outside air within 10% of the values

listed on MECH-3C

•  MECH-3A - Constant Volume & Single-Zone Unitary – Verifies that sequence of operation is correct

•  Setup and setback works •  Fan turns off – unoccupied period •  When fan off – O/A damper closed •  No simultaneous heating and cooling

Page 19: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 19

Acceptance Tests - Single Zone Rooftop Units – sometimes in order of likelihood •  MECH-5A - Economizer Controls

–  Only if the unit has an economizer •  MECH-6A - Demand Control Ventilation

–  Required for high density applications •  Retail (first floor) •  Auditoriums •  Schools are specifically exempt

•  MECH-4A - Air Distribution Ducts –  Duct leakage test –  Only if > 25% of duct surface area outdoors or in

ventilated attic (not plenum) –  Change-outs ducts not inc conditioned space

Page 20: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 20

Acceptance Tests Always Applied to Variable Air Volume Systems

•  MECH-2A - Outdoor Air for VAV – Measured outside air within 10% of the values

listed on MECH-3C at high and low flowrate

•  MECH-7A Supply Fan VAV – Fan slows down at lower loads – For DDC to zone, duct pressure drops

•  MECH-5A - Economizer Controls – Systems over > 75,000 Btu/h required to have

an economizer

Page 21: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 21

Direct Digital Control to the Zone

•  System has a central automated control that receives feedback from all zones – Allows pressure reset of variable flow fans or

pumps •  Pressure dropped until most open damper or coil

valve is almost full open. Thus all zones have enough pressure.

– Allows resetting of zone temperature in response to a utility signal (demand response)

– Allows adjusting outside air in response to CO2 level in zones

Page 22: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 22

Acceptance Tests Frequently Applied to VAV Systems with DDC to the Zone •  MECH-11A Automatic

Demand Shed Control –  Setup in response to utility

signal

•  MECH-6A Demand Control Ventilation –  Required for high density

applications •  Retail (first floor) •  Auditoriums •  Exempted: Schools, healthcare,

social service

Page 23: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 23

Acceptance Tests Usually Applied to Hydronic Systems •  MECH-8A - Valve Leakage Test

–  Check isolation valves on boilers and chillers

–  Test all valves on rest of system •  MECH-10A - Hydronic System

Variable Flow Control –  Under low coil load, fan speed

drops –  Under low coil load, system that

is DDC to zone, pressure drops •  MECH-9A - Supply Water

Temp. Reset –  Reset required only for systems

> 500,000 Btu/h. –  If system has controls, test

required

Page 24: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 24

Compliance forms end in “–C”

Page 25: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 25

5

VAV AHU 1 & 2 2 CHW System 1

CV RTU 1 to 5

Checks in red indicate tests that would always be done for these system types

Page 26: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 26

What is an acceptable package of acceptance tests

•  All Acceptance Tests listed on MECH-1C are completed

•  All signature blocks legible and signed

•  All values filled in & specific to equipment –  Identical values for all tests indicate tests not

being conducted

•  All tests should be “Passed”

Page 27: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 27

Changes in 2008

•  Revisions to MECH-1C Certificate of Compliance

•  New Field Inspection Checklist

•  New Installation Certificate (10-103(a)3A)

•  Reorganized Acceptance Test Forms (Certificates of Acceptance)

T24 2008 HVAC Forms

Page 28: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 28

The not so fine print

•  Systems Acceptance. Before occupancy permit is granted …

•  … all control devices shall be certified as meeting the Acceptance Requirements

•  Systems Acceptance. Before occupancy permit is granted. All newly installed HVAC equipment must be tested using the Acceptance Requirements.

•  The MECH-1C form is not completed and is not to be accepted by the building department unless the correct boxes are checked.

•  The building inspector must receive the properly filled out and signed forms before the building can receive final occupancy.

•  Do you see a pattern??

Page 29: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 29

New Field Inspection Checklist •  Filled out by designer or Title

24 documentation author (or automatically by compliance software)

•  Used by field inspector to help identify critical components

Title 24 2008

Page 30: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 30

Installation Certificate

•  Completed by licensed person responsible for building construction or installation of the mechanical system

•  Certifies that installed system meets code requirements

Title 24 2008

There is no longer a MECH 1A Form!

Page 31: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 31

Project information (typical)

Technician block (typical)

Reviewer block (typical)

Acceptance forms end in “-#A”

Page 32: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 32

People Qualified to Certify Tests “Responsible Person”

•  California licensed engineer, or architect –  Eligible under Division 3 of the Business &

Professions Code ... to take responsibility for the scope of work

–  Mechanical and civil engineers

•  California licensed contractor

Page 33: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 33

California Contractors typically eligible to take responsibility for acceptance tests •  A General Engineering Contractor •  B General Building Contractor •  C-4 Boiler, Hot Water Heating System Fitting Contractor •  C-20 Warm-air Heating, Ventilation & Air Conditioning Contractor •  C-36 Plumbing Contractor •  C-38 Refrigeration Contractor •  C-43 Sheet Metal Contractor •  D-62 Air and Water Balancing •  C-10 Electrical Contractor (controls) •  C-7 Low Voltage Systems Contractor (controls)

•  Other contractors with related classifications

Page 34: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 34

Construction inspection (typical)

Functional Testing block (typical)

Page 35: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 35

Test summary (Typical)

Page 36: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 36

Completed acceptance tests are a condition of the Certificate of Occupancy

•  Late installation of a given piece of equipment is no excuse

•  All other equipment can be tested and a conditional permit granted for the late piece of equipment

Page 37: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 37

Simple Spot Tests – Summer Economizer

•  Have contractor place all AC in cooling mode in early morning – All economizers should be open

•  Have contractor place in heating mode – All economizers should be closed

•  Have contractor place systems back in cooling mode – All economizers should close when it is hot

out

Page 38: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 38

Simple spot tests VAV system – summer

•  Have contractor set cooling setpoint low – Fan speed should increase – listen or look at

VFD output

•  Have contractor set cooling setpoint high – Fan speed should decrease

Page 39: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 39

Minimum Outdoor Ventilation Air Acceptance MECH-2A Appendix NA 7.5.1

Page 40: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 40

Why is minimum outside air important

•  Too little O/A – sick building syndrome – Often too little O/A at low flow for VAV

systems

•  Too much O/A – huge energy penalty – Hot summer day - 3 tons extra cooling for

each 1,000 cfm excess outside air.

•  Without adjusted O/A – easily 100% excess outside air

Page 41: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 41

Outside air dampers

•  When in heating mode or in cooling mode where bringing outside air would increase load on building…

•  ….outside air dampers are set or controlled to allow the minimum outside air needed to protect health and dispel normal odors.

Page 42: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 42

Purpose of Outdoor Air Acc. Test

•  Verification of minimum OutSide Air (OSA) as scheduled on plans

•  Verification that minimum OSA is provided throughout the range of operation in a VAV system and at design for CV systems

•  Measured CFM of minimum outside air at min flow and full flow must be within 10% of design CFM on MECH-3C

Page 43: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 43

Design Minimum Outside Air MECH-3C VAV-O = office space, VAV-A = assembly space, Min O/A in Column I

VAV-O 1,000 0.15 150 5 75 150 160 350 400 400 300 N/A

VAV-A 1,000 0.15 150 34 510 510 510 1,200 400 1,200 550 N/A

Totals 39 660 670 0 Min O/A for MECH-2A

67 x 0.5 = 34

Page 44: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 44

Fixed Minimum OA Damper Position only allowed for constant volume systems

Outdoor Air Intake

Return Air

Minimum Signal Pot.

Signal from SAT Controller

For VAV systems does NOT WORK since mixed air plenum pressure varies!! Outdoor

air flow will vary proportional to supply air flow

Page 45: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 45

Test Procedure CV System

1.  Disable economizer (if applicable) 2.  Disable DCV (if applicable) 3.  Measure and record OSA 4.  Restore boxes, economizer and DCV

controls

Setup

Test

Clean up

Page 46: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 46

How to Disable an Economizer

•  Drop high-limit control setpoint below current OA temperature or enthalpy (all controls), or

•  Raise OA temperature or enthalpy reading above high limit control setpoint (DDC controls), or

•  Disable economizer control block (DDC controls)

Page 47: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 47

How to Disable and Engage DCV Controls

•  Disable DCV – Raise CO2 setpoint significantly above current

CO2 reading (all controls)

•  Engage DCV – Lower CO2 setpoint to lowest possible

setpoint (all controls)

Page 48: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 48

How to Measure OSA

•  AFMS (air flow monitoring station) –  If part of the system

•  Calibrated damper (if part of the system)

•  Traverse of OSA louver/duct

•  Traverse of SA and RA ducts (differential)

•  For each test OSA must be +/-10% of design

•  Note: on small packaged units you might have to provide a temporary sheet metal hood on the OSA intake to get a good reading

Page 49: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 49

Construction Inspection

•  Calibration of AFMS or calibrated damper (if part of the system)

•  Verify that there is a provision for dynamic control of OSA (if VAV)

•  Verify that there is a provision for minimum OSA (if CV)

Page 50: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 50

VAV Acceptable O/A Control Dual Minimum

•  Minimum damper position is set proportionally based on fan speed between setpoints determined when the fan is at full speed and minimum speed

•  Low cost

•  Affected by wind, stack effect, filter loading

Page 51: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 51

Example Method of Dynamic OSA Control: Injection Fan

Signal from SAT Controller

Outdoor Air Intake

Return Air

Injection Fan w/ Discharge Damper

Page 52: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 52

Outdoor Air Intake

Return Air

Signal from SAT Controller

Example Method of Dynamic OSA Control: Fixed Damper with DP control

∆P correlated to flow for fixed orifice Can be 1 section or

entire OA damper

Page 53: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 53

Test Procedure VAV System

1.  Disable economizer (if applicable) 2.  Disable DCV (if applicable) 3.  Drive all boxes to minimum airflow 4.  Measure and record OSA 5.  Drive all boxes to design airflow 6.  Measure and record OSA 7.  Restore boxes, economizer and DCV controls 8.  System passes if measured OSA in steps 4 & 6

are within 10% of design OSA Combine tests to save time and $$

–  MECH-2A full airflow test with DCV disabled –  MECH-6A. full airflow test with DCV enabled

Setup

Test 1

Test 2

Clean up

Page 54: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 54

How to Drive VAV Boxes Open

•  Set zone cooling temperature setpoint below the current zone temperature (all controls)

•  Override the VAV box airflow setpoint (DDC controls)

•  With DDC controls you might want to specify preset functions to drive all boxes to design airflow and minimum airflow to speed up the tests

•  Note: if you override the VAV box damper you may provide more than the design maximum airflow

Page 55: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 55

How to Drive System to Minimum Airflow

•  Set zone cooling temperature setpoint above the current zone temperature (all controls)

•  Override the VAV box control airflow setpoint (DDC controls, could be preset)

•  Manually slow down fan until airflow is ~30% of design airflow (all controls, requires AFMS or duct traverse)

Page 56: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 56

Project information

(typical)

Technician block

(typical)

Reviewer block

(typical)

Page 57: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 57

Title 24 2008

Construction inspection

(typical)

Testing block (typical)

1,910 2,000

3.2 mins

92.5

95.5

1,850 2,000

3 mins

AH 1 2nd Floor Offices

Project XYC, Somewhere, California

Page 58: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 58

Test summary (Typical)

AH 1 2nd Floor Offices

Project XYC, Somewhere, California

Page 59: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 59

Reasons to Reject the MECH-2A

•  Signatures or names are missing for technician or reviewer

•  Ratio of measured flowrate to design outside air flow rate (Percent OSA) – >110%

– <90%

•  Suspicious if all tests: – Measured airflow equal to design airflow rate

Page 60: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 60

Packaged HVAC Controls MECH-3A

Page 61: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 61

Purpose

•  Check thermostat, setpoints and scheduling controls

•  Verify that heating, economizer and cooling are properly sequenced

•  Verify operation in occupied and unoccupied modes

Page 62: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 62

Page 63: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 63

MECH-3A Functional Tests

•  Simulate various operating modes –  Heating load occupied, no-load occupied, heating

load unoccupied, no load unoccupied, etc. –  Each condition is a column on the table

•  Check for various HVAC unit responses –  Different responses represented by each row –  Areas grayed out are incorrect responses –  Areas with check boxes are correct responses

•  Test and fix until under each operating mode only responses are those indicated by check box

Page 64: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 64

Page 65: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 65

Occupied Mode Test Procedure

1.  Heating –  Supply fan operates continuously –  OSA is provided –  No cooling occurs –  Verify that all heating stages work

2.  Dead Band –  Supply fan operates continuously –  OSA is provided –  No heating or cooling occurs

3.  Cooling –  Supply fan operates continuously –  OSA is provided –  No heating occurs –  Verify that all cooling stages work

Note the cooling test is repeated under economizer acceptance

Page 66: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 66

How to drive the unit into heating, cooling or deadband •  Cooling

–  Move thermostat cooling setpoint below the current room temperature

•  Dead Band –  Move the thermostat cooling setpoint above the

current room temperature, and –  Move the thermostat heating setpoint below the

current room temperature •  Heating

–  Move the thermostat heating setpoint above the current room temperature

Page 67: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 67

Unoccupied Mode Test Procedure

4.  Heating –  Supply fan cycles on with call for heating (and off when satisfied) –  OSA is closed or cycles with supply fan –  No cooling occurs

5.  Dead Band –  Supply fan is off –  OSA damper is closed –  No heating or cooling occurs

6.  Cooling –  Supply fan cycles on with call for heating (and off when satisfied) –  OSA is closed or cycles with supply fan –  No heating occurs

Again, the cooling test is repeated under economizer acceptance

Page 68: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 68

How to move the unit into “unoccupied” mode

•  Adjust the schedule so that the unit is scheduled off at the current time, or

•  Reset the current time so that it is outside of the scheduled occupied period

Page 69: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 69

Override Mode Test Procedure

7. Enable after hours override –  System goes to “occupied” mode

–  System returns to “unoccupied” mode after timed delay

8. Return system to normal operation –  Reset all setpoints

–  Remove any jumpers

Page 70: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 70

How to activate the after-hours override

•  Put the unit into “unoccupied” mode (see previous slide)

•  Push the after-hours button on the thermostat

Page 71: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 71

Air-Side Economizer MECH-5A

Page 72: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 72

Purpose

•  Check economizer installation and provision for exhaust or relief

•  Test economizer operation

•  When a call for cooling and it is cool outside the economizer brings in outside air

•  Other times min O/A

Page 73: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 73

Overview

•  References –  Standard Sections §144(e) and §125(a)4

–  Form MECH-5A

–  Non-Residential Appendix NA 7.5.4

–  Nonresidential Compliance Manual 10.6.10

•  Scope –  All new systems with air-side economizers

–  No functional testing required if economizer is factory installed and certified operational

•  None certified currently

Page 74: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 74

Page 75: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 75

High Limit Switch

Page 76: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 76

Economizer Functional Testing

Step 1: Disable demand control ventilation (DCV) systems (if applicable) Step 2: Enable the economizer and simulate a cooling demand

–  Economizer damper is 100 percent open and return air damper is 100 percent closed.

–  For systems > 75,000 Btu/h economizer is integrated •  100 % open when the cooling demand can no longer be met by the economizer alone.

–  All applicable fans and dampers operate as intended to maintain building pressure.

–  The unit heating is disabled. Step 3: Disable the economizer and simulate a cooling demand.

–  Economizer damper closes to its minimum position. –  All applicable fans and dampers operate as intended to maintain building

pressure. –  The unit heating is disabled

Step 4: Simulate a heating demand and set the economizer so that it is capable of operating (i.e. actual outdoor air conditions are below lockout setpoint).

–  The economizer is at minimum position Step 5: Restore DCV systems and remove all system overrides

Page 77: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 77

How to Disable an Economizer

•  Drop high-limit control setpoint below current OA temperature or enthalpy (all controls), or

•  Raise OA temperature or enthalpy reading above high limit control setpoint (DDC controls), or

•  Disable economizer control block (DDC controls)

•  Do the opposite to enable economizer

Page 78: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 78

Page 79: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 79

VAV Supply Air Acceptance Test MECH-7A

Drawing courtesy of Steven Taylor

Page 80: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 80

Purpose

•  Check calibration and setpoint of pressure sensor for VAV systems

•  Check stability of control on VAV systems at full and part load

•  Make sure fan speed slows with reduced load, supply air pressure does not rise

•  For DDC to zone system, system air pressure drops at reduced load

Page 81: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 81

Overview

•  References –  Standard Sections §144(c)2B, C & D and §125(a)6

–  Non-Residential Appendix 7.5.6

–  Nonresidential Compliance Manual 10.6.14

•  Scope –  New VAV fans greater than or equal to 10 hp

–  Both prescriptive and performance approach

Page 82: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 82

Construction Inspection - Verify

•  Discharge static pressure sensors are either factory calibrated or field-calibrated.

•  The static pressure location, setpoint, and reset control meets the requirements of §144(c)2C and §144(c)2D.

–  Sensor Location so set point < 1/3 the total design static P (i.e. near the end of the duct)

•  except for DDC to zone systems w/ pressure reset

–  If located below major duct splits, sensors in each major branch, take lowest value for control

–  DDC to Zone, Set Point Reset. •  pressure set point based on the zone w/ most need •  zone damper needing most pressure is nearly wide open.

Page 83: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 83

Construction Inspection

Page 84: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 84

Test Procedure

You may have to disable SA temperature reset during this test to prevent unwanted flow fluctuations

1.  Drive boxes to achieve design airflow (refer to min OSA test for how to do this)

2.  Record measured SP (must be +/- 10% of setpoint)

3.  Note if fan speed stabilizes within 5 minutes

Page 85: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 85

Test Procedure

4.  Drive boxes to achieve minimum airflow (refer to min OSA test for how to do this)

5.  Record measured duct static pressure (must be +/- 10% of setpoint)

6.  For DDC to zone systems, pressure setpoint must be reduced

7.  Note if fan speed stabilizes within 5 minutes

Page 86: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 86

Functional Performance Testing

Page 87: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 87

Demand Control Ventilation (DCV) MECH-6A

Page 88: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 88

Demand Control Ventilation Requirements (§121(c)4)

•  Where DCV is applied, it must meet the following: –  One sensor for each space that meets the criteria of 121(c)3B

–  Sensor must be CO2

–  Sensor must be located in the breathing zone between 3’ and 6’ AFF or at the anticipated level of the occupant’s heads

–  Maintain setpoint of 600ppm + OSA ppm •  400 PPM default or •  dynamically measured

–  No greater than design ventilation @ 15 cfm/person

–  No less than ventilation from Table 121-A (cfm/ft2)

–  Design ventilation for spaces without DCV

Page 89: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 89

Do Return CO2 Sensors Work?

Return is diluted by other Zones and does not track the critical zone

No. Separate sensors are needed in each high density space

Page 90: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 90

Purpose

•  Check DCV calibration and installation

•  Test DCV at: – High CO2 levels

– Low CO2 levels

Page 91: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 91

Related Tests

•  NA 7.5.1 Outdoor Air Acceptance

•  NA 7.5.4 (Air-Side) Economizer Acceptance

This test should be combined with minimum OSA and economizer acceptance tests to reduce time and costs

Page 92: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 92

Page 93: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 93

DCV Test Procedure

•  Disable economizer controls •  Measure CO2 concentration

–  If dynamic control < 600 ppm above ambient concentration –  Default ambient concentration 400 ppm, indoor air < 1,000 ppm

•  Step 1:Simulate a signal at or slightly above the CO2 concentration setpoint required by §121(c)4C. Verify and document the following:

–  For single zone units, outdoor air damper modulates open to satisfy the total ventilation air called for in the Certificate of Compliance.

–  For multiple zone units, either outdoor air damper or zone damper modulate open to satisfy the zone ventilation requirements.

•  Not required to have cfm greater than MECH-3C column I (design ventilation air cfm)

•  Step 2: Simulate signal well below the CO2 setpoint. Verify : –  For single zone units, outdoor air damper modulates to the design minimum

value. –  For multiple zone units, either outdoor air damper or zone damper modulate less

open to satisfy the reduced zone ventilation requirements. •  CFM must be at least as much as MECH-3C Column D (Min CFM by Area) for DCV

controlled zone + MECH-3C column I (design ventilation air cfm) for uncontrolled zones

•  Step 3: Restore economizer controls and remove all system overrides initiated during the test.

Page 94: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 94

Overriding CO2 Controls

•  To simulate high demand you need to decrease the sensor setpoint

•  To simulate low demand you need to increase the sensor setpoint

•  Best accuracy results from using calibrated gas

Page 95: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 95

Default is 400 ppm

Page 96: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 96

Duct Sealing Air Distribution Systems

MECH-4A

Page 97: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 97

MECH-4-A Air Distribution §144(k)

•  Small (<5,000 sf) CV systems only

•  When > 25% of duct surface is outdoors or in unconditioned space

•  Place greater than 75% of ducts under insulated roof – test not needed

•  Ducts must be tested for duct leakage …. and verified as sealed by a HERS rater

Page 98: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 98

MECH-4-A Construction Inspection

•  Drawbands –  Stainless steel worm drive or

–  UV resistant nylon duct ties

•  Duct leakage tests performed before access is blocked

•  Duct tape not used unless with drawbands and mastic

•  R-8 insulation

•  Outdoor insulation protected from damage

Page 99: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 99

Page 100: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 100

MECH-4A Calculated supply fan flow

•  Rated flow from capacity –  400 cfm/ton

–  21.7 cfm/kBtuh heating only systems

Page 101: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 101

MECH4-A Leakage Test New Construction

•  Seal all diffusers

•  Pressurize system to 25 Pa (0.1 in WC) with fan with calibrated orifice (duct blaster)

•  Measured leakage no greater than 6% of rated flow

•  Likely conducted by HVAC contractor

•  Verified by HERS rater

Page 102: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 102

MECH-4-A Duct testing

Page 103: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 103

MECH-4A Duct Testing Results New Construction or Alterations

Alterations

New

Page 104: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 104

MECH-4-A Duct Sealing on Retrofits §144(k), 149(b)1D&E Applies to small CV system with ducts outside or in

unconditioned spaces when: –  Ducts replaced –  HVAC system is replaced or major repair (new

compressor, new coil etc.) Existing duct leakage

–  ≤15% of rated supply flow –  >60% reduction of leakage prior to sealing ducts with

all visible leaks sealed –  Can’t get at the ducts and all visible leaks are sealed

as certified by a HERS rater •  Exceptions

–  Asbestos –  Existing ducts that were previously certified

Page 105: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 105

HERS Rater Sampling Test Validation

•  All systems must best tested by person conducting acceptance tests

•  Independent HERS rater verifies results through sampled re-testing of systems: –  Verify the first system tested –  Verify one out of the each group of 7 tested

•  If that unit fails the test, •  test a second unit in the group of 7 •  if that fails test the other 5 in the group of 7

–  Certify ALL of the tests made by the contractor –  Enter all tests into the HERS database

•  New groups of 7 applies to each new construction project (but not for retrofit)

Page 106: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 106

Automatic Demand Shed Controls

Page 107: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 107

Automatic Demand Shed Controls (122(h))

•  For systems with DDC to the zone: –  Ability to reset thermostat setpoint up to 4°F on all “non-critical”

zones through real or virtual DI.

–  System needs an adjustable rate of change for reset

•  Shown by LBNL and Purdue to reduce on-peak demand by over 30%.

•  Supported by ASHRAE Standard 55 (Table 5.2.5.2).

6.0°F 5.0°F 4.0°F 3.0°F 2.0°F Maximum Operative Temperature Change Allowed

4 h 2 h 1 h 1/2 h 1/4 h Time Period

6.0°F 5.0°F 4.0°F 3.0°F 2.0°F Maximum Operative Temperature Change Allowed

4 h 2 h 1 h 1/2 h 1/4 h Time Period

All New!

Page 108: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 108

Overview

•  References – Standard Sections §122(b)4, §122(h) and

§125(a)10 – Non-Residential Appendix NA 7.5.10 – Nonresidential Compliance Manual 10.6.19

•  Scope – New DDC Zone Controls

Page 109: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 109

Purpose

•  To make sure that the demand shed controls are programmed and work when engaged

•  Demand shed controls gives the owner the opportunity to temporarily turn up t-stats in all non-critical areas 4F a few hours per year. – Utility financial incentives – Less likely to have a black-out

Page 110: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 110

Automatic demand shed controls

•  NA7.5.10.1 Construction Inspection •  Prior to Acceptance Testing, verify and document the

following: –  That the EMCS interface enables activation of the central

demand shed controls.

•  NA7.5.10.2 Functional Testing •  Step 1: Engage the global demand shed system. Verify :

–  Cooling setpoint in non-critical spaces increases by the proper amount.

–  Cooling setpoints in critical spaces do not change.

•  Step 2: Disengage the global demand shed system. Verify : –  Cooling setpoint in non-critical spaces return to their original

values. –  Cooling setpoint in critical spaces do not change.

Page 111: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 111

Page 112: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 112

Page 113: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 113

Beyond Scope for Today

ACM Section and Test Standard Section NA 7.5.1.11 FDD for Packaged DX Systems 125(a)11 NA 7.5.1.12 FDD for AHUS and Zone Terminal Units 125(a)12 NA 7.5.1.13 Distributed Energy Storage DX AC Systems 125(a)13 NA 7.5.1.14 Thermal Energy Storage Systems 125(a)14

These tests are documented in the Non-Residential Appendices and Non-Residential Compliance Manual. They are only required when you seek a compliance credit.

Page 114: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 114

Summary

•  Acceptance tests assure that design intent for energy savings is executed

•  All heating and cooling systems have at least one associated acceptance test

•  The designer identifies which tests get applied to which equipment on the MECH-1-C form

•  Plans examiner reviews MECH-1C form to assure all equipment has applicable tests specified –  Compliance forms are rejected and returned to applicant if all

applicable HVAC systems and tests are not called out •  Fully COMPLETED acceptance test forms with all

systems PASSING must be given to inspector before building receives Certificate of Occupancy. –  Schedule a challenge test if results are suspicious

Page 115: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 115

Sample Questions

•  Which compliance form lists all acceptance tests that must be conducted?

•  Who can be a “responsible person” for the acceptance tests?

•  Are acceptance tests a requirement for a certificate of occupancy?

•  Which acceptance test requires a third party HERS verification?

•  Are any tests valid without 3d party verification? •  What is done if a system does not pass an

acceptance test?

Page 116: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 116

More questions

•  What tests are always required on constant air volume systems?

•  What tests are always required of VAV?

•  What tests are usually required of VAV systems with DDC to the zone?

Page 117: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 117

Outdoor Air Acceptance Test Questions

•  Which compliance form contains the design ventilation air information?

•  Measured ventilation air cfm must be within what percentage of design ventilation air cfm?

a)  5%, b) 10%, c) 30%, d)50%

•  For VAV, variable air volume, systems outside air must be measured at design (full) flow and at what other supply air flowrate?

Page 118: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 118

Packaged A/C Acceptance Test Questions

•  Select all true answers below

When is supply fan on during occupied hrs: a) Heating call, b) Cooling call, c) No call for

either heating or cooling When is supply fan on during unoccupied hrs:

a)  Heating call, b) Cooling call, c) No call for either heating or cooling

•  When is the outside air damper completely closed?

Page 119: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 119

Air-side Economizer Test Questions

•  True or False – Economizer open when call for cooling and

outside air temp is below high limit setpoint – Economizer is open when call for heating and

outside air temp is below high limit setpoint – Economizer closed when call for cooling and

outside air temp is above high limit setpoint – Construction inspection not required for

factory installed economizer w/ CEC certification.

Page 120: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 120

Resources – 2008 Standard

•  Energy Efficiency Hotline – E-mail: [email protected]

– Phone: 916-654-5106 or

– Phone: 1-800-772-3300 (toll free in Calif.)

Page 121: 2008 Title 24 Nonresidential HVAC Acceptance Testing for ...buildingincalifornia.com/wp-content/uploads/2014/01/2008+Title+24... · 2008 Title 24 Nonresidential HVAC Acceptance Testing

Title 24 2008 Acceptance Testing 121

Acknowledgements

•  California Commissioning Collaborative

•  Pacific Gas & Electric Company – Codes & Standards Program

•  California Energy Commission – Tav Commins, Project Manager

•  Mark Hydeman, Taylor Engineering

•  Jon McHugh, McHugh Energy Consultants