201001221723430.63030586_g115installationmanual0304.pdf

Upload: rikumohan

Post on 14-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    1/56

    Please read these instructions carefully.

    6303 0586 03/2004 US/CA For installers

    Boiler Installation and

    Maintenance Manual

    Oil and Gas fired Cast Iron BoilerLogano G115 US

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    2/562

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Inhaltsverzeichnis

    1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    1.1 Regarding this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    1.2 Suitable Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    1.3 Guideline of Notices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    1.4 Observe the following Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.4.1 In Case of Smoke . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    1.4.2 Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.4.3 Boiler Room Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    1.5 Tools, Materials and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    1.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    2 PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    3 TECHNICAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    3.1 Technical Data less Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    3.2 Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83.2.1 General Operating Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    3.2.2 Requirements for Boiler Room and Surroundings . . . . . . . . . . . . . . . . . . . . . . . . 9

    3.2.3 Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    3.2.4 Fuel Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    3.2.5 Requirements for Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    3.2.6 Conditions Pertaining to Piping and Water Quality. . . . . . . . . . . . . . . . . . . . . . . 11

    4 Packaging and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    5 Moving the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    5.1 Reducing Boiler Weight for Transport. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    5.2 Lifting and Carrying the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    5.3 Moving the Boiler with Boiler Cart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    6 Placing the Boiler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    6.1 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    6.2 Reversing the Burner Door Swing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    6.3 Installation of Boiler Feet (Components of B-Kit) . . . . . . . . . . . . . . . . . . . . . . . . . 17

    6.4 Placement of the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    7 Boiler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    7.1 Installation of Venting System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    7.1.1 For Oil-Fired, Direct Vent Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    7.1.2 For Chimney Venting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    7.2 Installation of Water Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    7.2.1 B-Kit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    7.2.2 Installation of Boiler Drain (B-Kit Component) . . . . . . . . . . . . . . . . . . . . . . . . . 21

    7.2.3 Installation of System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    7.3 Filling and Checking for Water Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    7.4 Burner Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    7.5 Installation of Oil Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    7.6 Aquastat Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    7.7 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247.7.1 Control System Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    7.7.2 Installation of Temperature Sensor and Burner Cable . . . . . . . . . . . . . . . . . . . . . 26

    7.7.3 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    7.7.4 Strain Relief Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    7.8 Jacket Panel Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    3/563

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Inhaltsverzeichnis

    8 Placing the Boiler in Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    8.1 Setting the Initial System Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    8.2 Checking Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    8.3 Check Position of Flue Baffle Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    8.4 Get System Ready for Proper Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    8.5 Start-up of Control and Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    8.6 Guidelines Regarding Burner Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308.7 Adjusting Stack Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    8.7.1 Adjusting Flue Baffles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    8.7.2 Removing Flue Baffles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    8.7.3 Removing Blocking Plates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    8.8 Testing of the Manual Reset High Limit (STB) of Logamatic controls. . . . . . . . . . . . . . . 32

    8.9 Install Front Jacket Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    8.10 Detailed Start-up Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    9 Taking the Boiler out of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    9.1 Normal Boiler Shut-down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    9.2 Emergency Shut-down. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    10 Boiler Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    10.1 Why do Maintenance? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    10.2 Prepare Boiler for Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    10.3 Boiler Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3610.3.1 Cleaning the Boiler with Brushes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    10.3.2 Wet Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    10.4 Testing System Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    10.5 Testing Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    10.6 Inspection and Maintenance Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    11 Restoring Sytem Lock-outs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    12 Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    13 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    14 SP30D and Burner Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    15 Table of Key Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    4/564

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Safety Considerations1

    1 Safety Considerations

    1.1 Regarding this Manual

    This document contains important information regardingsafe and proper installation, operation and maintenanceof the boiler.

    The G115 is designated as a hot water heating boiler.

    The Installation and Maintenance Instructions aredirected to the installing contractor who has professionalknowledge regarding boiler installation andmaintenance.

    1.2 Suitable Applications

    The boiler can only be used for hot water space heatingapplications for single and multi family homes.

    Use the rating plate information to size the boiler( Chapter 3, page 7) for the application.

    1.3 Guideline of Notices

    Two levels of danger are identified by the followingwarning labels:

    Cross notice

    Designated by means of a narrow , referral to a noticein another document .

    1.4 Observe the following Symbols

    The local and state codes and regulations must beobserved during the installation of the boiler:

    The local building code requirements regardingplacement, combustion air and venting and chimneysystem must be followed.

    Follow applicable electrical code requirements.

    Follow the regulations of the local gas utility if theboiler is to be operated with a gas burner.

    Follow the local code and standards regarding safeboiler operation.

    1.4.1 In Case of Smoke

    1.4.2 Installation Guidelines

    WARNING!

    DANGER

    Denotes a possible severely dangerous

    situation where, without proper caution,bodily injury or loss of life may result.

    CAUTION!

    DANGER OF INJURY/SYSTEM DAMAGE

    Denotes a possible dangerous situationthat can lead to mild to moderate bodilyinjury or physical damage.

    APPLICATION NOTICE

    Application comment for optimum use ofequipment and adjustment as well asuseful information.

    NOTICE

    Use only original Buderus spare parts forreplacement purposes. Buderus can not

    be held liable for damage caused by nonBuderus parts.

    WARNING!

    DANGER

    due to explosion of flammable gases!

    z No open fire! Do not smoke!

    z Avoid formation of sparks! Do nottouch any electric switch, phone,electric plug or bell!

    z Shut off main gas supply.

    z Open windows and doors!

    z Notify all occupants!

    z Leave the building!

    z Immediately call your gas supplier,heating contractor or fire departmentfrom a phone outside the building!

    WARNING!

    DANGER

    due to explosion of flammable gases.

    z Work only on gas components whenyou have a license to do so.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    5/56

    Safety Considerations 1

    5

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    1.4.3 Boiler Room Guidelines

    1.5 Tools, Materials and Accessories

    For the installation and maintenance of the boiler youwill need typical tools used in the trade. In addition, thefollowing components are useful:

    Boiler cart with rope or Buderus boiler cart.

    Wood blocking. Cleaning brushes and/or chemical cleaning agents

    for a wet cleaning.

    1.6 Disposal

    z Please dispose of any trash in an environmental

    friendly fashion.

    z Please discard properly of any heating systemrelated components.

    DANGER!

    DANGER

    due to electricity.

    z One is only allowed to work onelectrical components, if one is certifiedfor such work.

    zPrior to opening the control: shut downthe power supply and pad lock againstaccidental reactivation.

    z Observe all applicable installationguidelines.

    WARNING!

    DANGER

    due to poisoning.Insufficient combustion air can result indangerous operation if all combustion air is

    taken from indoors.

    z Please observe that combustion airopenings are not reduced in size orclosed.

    z If this problem has not been corrected,one can not operate the boiler.

    z Make the end-user aware of theseguidelines and their potential danger.

    WARNING!

    FIRE DANGER

    due to flammable or liquid materialsz Make sure that flammable and liquid

    materials are not in the close vicinity ofthe boiler.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    6/566

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    PRODUCT DESCRIPTION2

    2 PRODUCT DESCRIPTION

    The G115 boiler is a low temperature boiler for oil or gasfiring for outdoor reset operation or as a cold start boiler.

    The boiler consists of:

    optional Logamatic control boiler jacket

    boiler block with insulation

    customized burner

    The optional Logamatic control manages most controlfunctions in a heating system.

    As an alternative, a Honeywell aquastat can be used forboiler control.

    The boiler jacket serves to reduce energy loss and as a

    noise reducing agent.The boiler block transfers the heat generated by theburner to the boiler water. The insulation reduces thestand-by losses.

    Customized burner

    The boiler must be equipped with a customized burnerfor operation. Please observe the technical data of theboiler when selecting a burner ( Chapter 3.1, page 7).

    Fig. 1 Boiler less burner

    1 Control panel

    2 Boiler jacket

    3 Boiler block with insulation

    4 Burner door cover

    1

    2

    3

    4

    CAUTION!

    SYSTEM DAMAGE

    due to improper burner.

    z Use only burners recommended byBuderus as is discussed in ourtechnical documents.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    7/56

    TECHNICAL INFORMATION 3

    7

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    3 TECHNICAL INFORMATION

    3.1 Technical Data less Burner

    Select your suitable burner based on this information.

    Fig. 2 Dimensions and connections (measurements in inches)

    4

    3/8"

    57

    /8"

    121/4"

    23 5/8"

    39 5/8"

    30 3/8"

    10 3/8"

    1 3/4"

    20"

    2 7/8"

    25 1/4"

    3 1/4"2 7/8"

    8 7/8"

    8 7/8"5/8" 1"

    1" NPT Rp3/4"

    Rp11/4"

    EL

    5"

    RK

    VK

    LLK

    FL

    Connections (Measurements see following tables):

    VK = Boiler supply

    RK = Boiler return

    EL = Boiler drain (Connection for drain valve)

    Keep plugs in place in remaining 3 top rear tappings.

    Boiler model 115/21 115/28 115/34

    Number of sections 3 4 5

    Heating Capacity (Gross Output) Btu/hr 74,000 98,000 120,000

    Net IBR Btu/hr 64,000 85,000 104,000

    Boiler water content Gal 8.7 10.8 12.9

    Fireside volume cu.ft. 1.20 1.75 2.21

    Oil firing rate GPH .60 .80 1.0

    Fireside pressure drop psi 0.00058 0.00145

    Permissible max. supply temperature1 F 230

    Allowable operating pressure psi 58

    Maximum Reset High Limit for temperature

    sensor and overheat thermostat (STB)

    s 40

    Table. 1 Technical data less burner

    1 High limit (overheat thermostat STB)

    Permissible maximum supply temperature = High limit (STB) 32 Fe.g.: High limit (STB) = 212 F, maximum permissble supply temperature = 21232 = 180 FSelect the your high limit (STB setting) according your local codes and requirements.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    8/568

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    TECHNICAL INFORMATION3

    3.2 Operating Conditions

    By maintaining the operating requirements listed on thefollowing page, one can expect long and trouble freeoperation of the boiler. Proper and timely maintenance

    procedures must be followed.

    Boiler model 115/21 115/28 115/34

    Total boiler length (L) Inch 22 7/8 27 7/8 32 5/8

    Boiler block length (LK) Inch 21 1/8 25 3/4 30 1/2

    Combustion chamber length Inch 16 20 1/2 25 1/4

    Firebox diameter Inch 10 5/8

    Burner door thickness Inch 3 5/8

    Distance between boiler feet (FL) Inch 10 3/8 16 1/8 20 7/8

    Dry weight1 Lbs 330 403 476

    Table. 2 Dimensions, Weight and other Data

    1 Weight incl. packaging material approx. 68 % more.

    CAUTION!

    SYSTEM DAMAGE

    In case one does not follow theseoperating requirements it can lead topremature failures. Major deviations cancause permanent damage to the boiler.

    z Follow the instructions on the ratinglabel and those in the manual.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    9/56

    TECHNICAL INFORMATION 3

    9

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    3.2.1 General Operating Requirements

    3.2.2 Requirements for Boiler Room and Surroundings

    Operating conditions

    Minimum boiler

    temperature

    Boiler Shut-down Mixed temperature Heating

    Circuit w/ mixing valve 1Minimum

    return temperature

    Systems controlled by R2017 controls for outdoor reset operation

    No requirements

    Operating conditions are met

    with R2107 control 2

    Automatic with Logamatic

    R2107

    No requirement, yet beneficial

    with low temperature boiler with130/113 F system design

    Necessary with:

    radiant floor applications

    Systems with large water

    content > 115 gal/100,000

    Btu/hr)

    No requirement, except with

    modulating burner

    Oil firing: 113 F

    Gas firing: 130 F

    Systems controlled by aquastats or R2109

    150 F 3 Possible, provided the boiler

    operates after total shut-down

    for at least 3 hours intermittently

    to avoid condensate build-up.

    Necessary Necessary for

    Systems \with very large

    water content

    >115 gal/100,000 Btu/hr:

    130 F Firing with modulating

    burners: 130 F

    Table. 3 General Operating Requirements

    1 A heating circuit equipped with a motorized mixing valve improves the controllability of that sub-system and is specifically recommended when

    requiring different water temperatures for optimum control.

    2 In case the control system has no in fluence over the flow in a heating circuit (for instance using the Pumplogic feature of the R2107), then one

    should achieve a minimum supply temperature of 122 F within 10 minutes after burner start-up by means of reducing (or interrupting) the water

    flow through the boiler.

    3 Minimum setting on the adjustable high limit or aquastat: During burner operation one should achieve the minimum boiler temperature within 10

    minutes after burner start-up by means of flow reduction and one should maintain this temperature.

    Operating Conditions Comments - Detailed Information

    Boiler room temperature +40 to +104 F

    Relative humidity max. 90 % No condensate or dampness in boiler room.

    Dust No excessive amounts of dust should be present in the boiler room, e. g.:

    no sheet rock or construction dust.

    The available combustion air can not contain dust or other particles/ use of

    an air filter might be needed, e. g.:

    Combustion air from nearby streets with high dust levels.

    Combustion air from nearby production facilities such as chemical plants &

    shops.

    Airborn particulates.

    Hydrohalogen contamination Combustion air must be free of hydro halogen components.

    Eliminate any chemical compound such as paints, lacquers, thinners,cleaning agents. If not possible, provide fresh outside air for combustion.

    Please observe the following:

    Product information of Buderus catalog.

    Also observe guidelines in K3 chapter of Buderus catalog.

    Fans, removing air from boiler

    room.

    Avoid forced air removal by mechanical means during boiler operation.

    bath room exhaust fans

    dryer

    airconditioning equipment

    Table. 4 Boiler room and surroundings

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    10/5610

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    TECHNICAL INFORMATION3

    3.2.3 Combustion Air Requirements

    3.2.4 Fuel Conditions

    Animals The boiler room and specially the air inlet openings for combustion air must be

    kept free from animals entering by means of grills.

    Fire protection Maintain proper clearances to combustible materials as required per local code.

    Maintain a minimum distance of 16". Do not store flammable materials near the

    boiler.

    Flood zone conditions Separate the fuel supply and electrical power supply from the boiler during floodconditions. Replace the boiler components such as insulation, electrical and con-

    trol components afterwards.

    Operating Conditions Comments - Detailed Information

    Table. 4 Boiler room and surroundings

    Operating Conditions Boiler capacity (combine total boiler

    capacity for multiple units)

    Cross area required

    Two air inlet openings from

    outside: one top, one near

    bottom

    < 170,000 Btu/hr At least 43 square inch

    > 170,000 Btu/hr At least 43 square inch and plus 2.5 square inch per

    10,000 Btu/hr,

    if the output is higher than 170,000 Btu/hr.Table. 5 Observe your local codes and requirements to combustion air requirements

    Operating Conditions Comments - Detailed Information

    Permissible fuels w/ customs

    burners

    The G115 boiler can be operated with the following fuels.:

    Please select the proper burner based on desired fuel.When using oil of an extreme poor quality (kinematic viscosity

    > 0.0093 sq in/sec (> 45.5 s Sayboldt) at 68 F), use a shortened mainte-

    nance cycle. Boiler service and cleaning should be performed twice a year

    then.

    Natural gas based on burner specifications.

    Propane based on burners specs.

    Biogas, methane, waste gas subject to the operating conditions below.

    Contaminations All fuels shall be free of contaminants (such as dust, particulates, liquids) that

    could cause damage to the nozzles or oil lines.

    Biogas

    methane

    waste gas

    Following operating conditions must be maintained:

    Constant boiler temperature of at least 167 F.

    No boiler shut-down.

    Minimum return temperature of at least 140 F.

    Regular service and cleaning, for instance a chemical cleaning and follow-up

    surface treatment.

    Table. 6 Fuel

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    11/56

    TECHNICAL INFORMATION 3

    11

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    3.2.5 Requirements for Power Supply

    3.2.6 Conditions Pertaining to Piping and Water Quality

    Operating Conditions Comments - Detailed Information

    Main power supply 110 120 V Observe the acceptable voltage range for the burner.Provide proper ground to

    boiler for equipment and personal protection.

    High amp protection 10 A

    Frequency 60 Hz AC voltage

    Protection Ground all equipment per local code.

    Table. 7 Power supply

    Operating Conditions Comments - Detailed Information

    Operating pressure (over

    pressure)

    15 58 psi Maximum pressure is 30 psi based on furnished relief valve.

    Allowable test pressure 45 75 psi

    Adjustable temperature limit

    TR

    122 194 F Adjustable high limit range under normal operating conditions

    Manual reset high limit 212 248 F Suitable range for manual reset high limit of 212 to 248 F.

    Water quality Initial fill water and make-up water should be potable water type quality. A pH ran-

    ge of 8.2 to 9.5 is desired.

    Table. 8 Piping and water quality

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    12/5612

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Packaging and Components4

    4 Packaging and Components

    z Check the packaging for consealed damage.

    z Check the packaging for completeness. Contactyour wholesaler in case of missing parts.

    1 B-Kit packaging is supplied inside the combustion chamber.

    2 Honeywell aquastat is supplied with customized burner if so

    ordered.

    Component Qty Packaging

    Boiler block 1 1 Pallet

    Boiler jacket, installed on

    boiler

    Burner door and burner door

    cover installed on boiler block

    B-Kit-components:

    Supply manifold

    (11/4" NPT)

    30 psi relief valve

    (") boiler drain

    Pressure/temperature

    gauge (1" NPT R1)

    conversion nipple (parallel

    to NPT)

    90- elbow (1" NPT)

    90- elbow (" NPT)

    Burner mounting studs and

    washers

    Screw in feet

    1 1 Plastic

    packaging with

    boiler1

    Control panel,

    alternative aquastat21 1 cardboard

    box (ordered

    separately)

    Technical documents 1 Plastic

    packaging w/

    boiler

    Table. 9 Packaging and components

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    13/56

    Moving the Boiler 5

    13

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    5 Moving the Boiler

    This chapter describes how to move the boiler.

    5.1 Reducing Boiler Weight for Transport

    One can reduce boiler weight by removing the frontpanel and burner door itself.

    z Remove the screws holding the front panel in place.

    z Lift up the front panel slightly and remove.

    z Open burner door by removing the two burner doorbolts.

    z Lift burner door from hinges.

    CAUTION!

    SYSTEM DAMAGE

    due to bumps.

    z Protect the boiler from bumps andrough treatment.

    NOTICE

    z Protect the boiler connections fromdamage and dirt, when the boiler is notinstalled immediately.

    NOTICE

    Please dispose of the packaging in an

    environmental fashion.

    Fig. 3 Removing the front panel

    Fig. 4 Removal of burner door

    NOTICE

    Protect the burner door and the burnertube from damage and dirt, when burnerdoor is removed from the boiler.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    14/5614

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Moving the Boiler5

    5.2 Lifting and Carrying the Boiler

    The boiler can be picked up at the hand grips locatedalong the lower jacket panels.

    5.3 Moving the Boiler with Boiler CartYou can order a Buderus kuli cart from your localwholesaler.

    z Lift up the boiler from the rear side by using movingequipment (e. g. Buderus kuli cart or other dolly).

    z Secure the boiler to the cart.

    z Move the boiler to the job location.

    Fig. 5 Lifting and carrying the boiler

    NOTICE

    The boiler is secured to the pallet with twobolts.

    z Remove the bolts from pallet beforelifting the boiler.

    DANGER!

    NOTICE BODILY DANGER

    due to carrying of heavy loads.

    z Lift and carry the boiler with at least twopeople at the designated hand grippositions.

    Fig. 6 Moving the boiler with a Buderus kuli cart

    DANGER!

    BODILY DANGER

    if the product is not properly secured to thecart.

    z Use proper moving equipment such asthe Buderus kuli cart or other dolly.

    z Secure the boiler to the cart and movethe boiler to the job location.

    NOTICE

    By tipping the cart, you can install the boilerfeet ( Chapter 6.3, page 17).

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    15/56

    Placing the Boiler 6

    15

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Service Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    6 Placing the Boiler

    This chapter discusses how to place the boiler in theboiler room.

    6.1 Clearances

    Position the boiler while observing the clearances in( Fig. 7). Access to the boiler is reduced whenreducing these clearances.

    The boiler foundation must be level and sufficientlystrong.

    The burner door is factory installed right swinging. Youcan reverse the door swing in the field.

    CAUTION!

    SYSTEM DAMAGE

    due to freezing temperatures.

    z Place the boiler in a frost free room.

    Fig. 7 Clearance dimensions for G115 boilers

    Measure Distance

    A Recommended 51 1/8"

    minimum 39 3/8"

    B Recommended 27 1/2"

    minimum 15 3/4"

    C Recommended 15 3/4"

    minimum 3 7/8"

    LK see Chapter 3 for Technical Data

    Table. 10 Recommended and minimum clearances

    (Measurement in Inches)

    NOTICE

    Smaller clearances must abide with stateand local code. The boiler is approved for6" side clearances. A minimum distance tocombustible materials must be maintainedof 18" per NFPA 31 code requirements.

    NOTICEObserve required distances to othercomponents such as water piping, ventingand other components.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    16/5616

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Service Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Placing the Boiler6

    6.2 Reversing the Burner Door Swing

    The burner door hinges are factory installed on the right

    hand- the burner door swings to the right. You canadjust the hinges so that the burner door swings to theleft in the field.

    Note: the front panel must first be removed.

    (

    Chapter 5.1, page 13).z Remove burner door ( Chapter 5.1, page 13).

    z Remove hex head bolts of burner door hinges andremove hinges.

    z Install the hinges on the left side of the boiler with thehex head bolts.

    z Remove the eyelets from the burner door byremoving the hex head bolts.

    zLocate and secure with hex head bolts these eyeletsto the left side of the burner door.

    z Hang the burner door on the hinges.

    z Check to make sure that the flue baffle plates arehorizontally in the boiler ( Chapter 8.3, page 29).

    z Secure the burner door with the burner door bolts.Make sure to tighten the burner door bolts evenlywith about 7.5 ft-lbs torque.

    Fig. 8 Reversing burner door (on boiler block)

    1 Hex head bolts for hinges

    2 Door hinges

    121 2

    Fig. 9 Reversing burner door (on burner door)

    1 Hex head bolts for door eyelets

    2 Door eylet

    3 Burner door

    4 Door hinges

    5 Flue baffles

    1

    2

    3

    4

    5

    NOTICE

    When reversing the swing of the burner

    door, make sure to remove the burnercable and oil line from the burner first.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    17/56

    Placing the Boiler 6

    17

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Service Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    6.3 Installation of Boiler Feet (Components of B-Kit)

    You can level the boiler using the screw-in boiler feet, so

    that air can not collect in the boiler.

    Requirement: remove front panel from boiler( Chapter 5.1, page 13).

    z Tip the boiler slightly using the boiler cart( Chapter 5.3, page 14) or put a piece of woodunder one side.

    z Screw in the boiler feet 1/4" to 3/8".

    z Level the boiler.

    6.4 Placement of the Boiler

    z Bring the boiler to its final location.

    z Put a level on the boiler and adjust boiler feet to levelthe boiler.

    Fig. 10 Installation of boiler feet

    1Boiler rail

    2 Boiler feet

    12

    NOTICE

    When installing a G115 boiler on top of ahorizontal Buderus DHW indirect tank, donot use the boiler feet on the boiler, butrather use the feet to level the tank.

    Fig. 11 Leveling the boiler

    NOTICE

    Protect the boiler connections from dustand debris, if the boiler will not be

    connected right away.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    18/5618

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Installation7

    7 Boiler Installation

    This chapter describes how the individual componentsmust be installed on the boiler. These components are:

    Flue connection

    Water connections

    Electrical connections Burner installation (field installation)

    Fuel line connection

    7.1 Installation of Venting System

    7.1.1 For Oil-Fired, Direct Vent Applications

    Follow instructions in the G115 Direct Vent Manual,supplied with the direct oil burner options.

    7.1.2 For Chimney Venting

    Connect boiler with 5 vent pipe to vertical chimney anduse vent material approved by local codes for oil-firedboilers. If codes net present, refer to:

    NFPA 31, Installation of Oil-Burning Equipment.

    NFPA 211, Standard for Chimneys, Fireplaces,Vents and Solid Fuel Burning Appliances.

    In Canada, refer to CSA B139, Installation Code forOil-Burning Equipment.

    NFPA 211 requires chimney to be lined prior toconnecting boiler.

    Instecting and cleaning existing chimney

    z Inspect existing chimney prior to installing new boiler.

    z Clean and remove any blockage from chimney.

    z Repair or replace defect pipes or liner.

    z Repair chimney with mortar and joints if necessary.

    Down Drafts

    NOTICE

    z To avoid down drafts, extend chimneyat least 3 feet above location of roof

    penetration and at least 2 feet aboveany roof portion within 10 feet.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    19/56

    Boiler Installation 7

    19

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Minimum clearances to combustibles for vent pipe

    Minimum recommended chimney size

    Minimum recommended chimney size: 8" x 8" (6 " x 6" inside liner) or 6" round with 15 ft minimum height.Use 5" chimney liner when relining existing chimney.

    Vent pipe installation

    z Slide 5" vent pipe on flue connection and secure with2 screws using pre-drilled holes in boiler breeching.

    z Slope vent pipe at least " per foot up towardschimney.

    z Connect breeching above the bottom of chimney toavoid blockage. Avoid extending breeching too farinto chimney.

    z Install thimble or slip joint at connection point to allowremoval for cleaning.

    After burner start-up, set breeching draft to -.01 to -.02inches WC using draft guage. (Over fire pressure can beslightly positive). When necessary, install barometriccontrol in breeching, to relieve excessive draft or tocomply with applicable codes. Always positionbarometric control blade vertically. Set proper openingusing draft gauge.

    Vent Pipe TypMinimum

    clearances

    Double-wall L 6"

    Single-wall L 18"

    Table. 11 Minimum clearances to combustibles for vent pipe

    Fig. 12 Securing the flue connection

    1 Flue connector2 Boiler vent collar

    12

    NOTICE

    Avoid long horizontal runs, excessivenumber of elbows and tees.

    WARNING!

    DANGER

    Do not use barometric control and seal allvent joints if:

    z excessive resistance to flow ofcombustion gases can be expected.

    z actual chimney diameter and/or heightis less than recommended. Installationof a CO detector is recommended inthis case. Positive over fire pressureoperation of boiler will establish draft inventing system.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    20/5620

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Installation7

    7.2 Installation of Water Connections

    7.2.1 B-Kit Installation

    Use the B-kit components located in the boiler fire box tofinalize the boiler supply connection.

    z Use the 1-1/4" BSP x NPT conversion nipple at thesupply connection. Identify the section with thelonger thread length is threaded BSP (straightthread). The threads on this side also have no taper.(NPT side has taper).

    z Using high quality Teflon and/or pipe dope, insert thelonger threaded end into the boiler supply connection

    (VK).

    z Install 90 degree elbow 1" NPT on conversionnipple. Orient in desired direction.

    z Install supply manifold into 90 degree elbow. Youcan orient this manifold in three different directions(Fig. 14).

    z Install pressure/temperature gauge.

    CAUTION!

    SYSTEM DAMAGE

    due to leaking connections.

    z Install the piping connections to theboiler without having undue stress onthe near boiler piping.

    Fig. 13 Measuring thread length on 1-1/4" conversion nipple

    R

    1"(Europe)

    1

    "NPT(USA)

    1"1"

    VK

    1"

    Fig. 14 B-Kit Installation

    1 90 degree 1" NPT elbow

    2 Supply manifold

    3 Pressure/temperature gauge4 Relief valve

    5 90 degree " NPT street elbow

    1

    2

    3

    4

    5

    NOTICEThe pressure relief valve can only beinstalled after the hydrostatic test( Chapter 7.3, page 21).

    Use the supplied " street 90 to ensurethat the relief valve discharge is installedhorizontally.

    NOTICE

    We recommend, specially in older, largevolume systems, to install a dirt filter in thereturn connection to the boiler to reducewaterside debris build-up.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    21/56

    Boiler Installation 7

    21

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    7.2.2 Installation of Boiler Drain (B-Kit Component)

    z Install the " boiler drain (B-kit component) into theEL tapping.

    7.2.3 Installation of System Components

    Use the adjacent diagram as an aid during theinstallation of near boiler components.

    Additional installation samples are found in Chapter 12, page 43.

    7.3 Filling and Checking for Water Leaks

    The boiler must be tested hydrostatically for leaks.Check the entire system for leaks prior to placing thesystem in operation to prevent leaks during operation.

    Perform the hydrostatic at 1.5 times the expectedoperating pressure and in accordance with local coderequirements:

    Fig. 15 Boiler drain installation

    ELRK

    NOTICE

    Install a fill connection in the supply pipingto the boiler.

    Fig. 16 Installation diagram

    12

    3 4 5 6 3

    3

    8

    7

    9

    3

    Return

    Boiler drain

    VK

    RK

    10 Supply

    Fill valve

    Legend for Fig. 161 Relief valve

    2 Pressure/temperature gauge

    3 Ball valve

    4 Air eliminator

    5 System pump

    6 Back flow preventer

    7 Expansion tank

    8 Automatic feet valve

    9 Flow check

    10 Purge station

    Fig. 17 Pressure and temperature gauge

    CAUTION!

    SYSTEM DAMAGE

    Be careful not to expose the system to

    excessive test pressures during thehydrostatic test as it can damagepressure, control and safety components.

    z Make sure that all pressure, controland safety components are NOTinstalled during the hydrostatic test.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    22/5622

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Installation7

    z Plug relief valve connection ( Fig. 14, page 20)and all boiler openings with plugs. (Not supplied).

    z Close the ball valve to the expansion tank.

    z Open automatic feed valve.

    z Fill the boiler slowly with the feed valve.

    z Open the automatic air eliminator to allow air toescape.

    z Slowly fill the heating system. Monitor the pressuregauge.

    z Check all water connections for leaks.

    z Vent the heating system by opening and bleedingradiators. Open purge valve slowly and allow air toescape.

    z When water pressure drops during the fill, open upthe fill valve more.

    z When no leaks are found, remove plug, drain waterand install relief valve (Fig. 14, page 20).

    Maximum

    operating pressure

    Maximum

    test pressure

    30 psi (based on supplied

    relief valve)

    45 psi

    58 psi (based on 50 psi relief

    valve)

    75 psi

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    23/56

    Boiler Installation 7

    23

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    7.4 Burner Mounting

    Install only burners that have been tested and approved

    by Buderus Hydronic Systems, Inc. for use on a G115boiler. ( Chapter 3, page 7).

    z Burner mounting studs and washers are includedwith the G115 B-kit. Install the studs into the burnerdoor.

    z Install the correct burner into the G115 boiler. Checkpump pressure, air setting, turbulator setting andflange position. Refer to burner specificationsincluded with KP burner package.

    z Put the washers on the studs and secure burner toboiler using furnished nuts.

    z Follow burner manufacturers recommendationregarding installation, fine tuning and maintenanceprocedures.

    7.5 Installation of Oil Line

    Install the fuel line in accordance with local code. Werecommend the use of an oil filter near the burner in

    addition to an oil filter near the oil tank.

    z Visually inspect the fuel line for leaks, replace whennecessary.

    z Install a shut-off in the oil line.

    z Connect the oil line without undue strain.

    z Check the fuel supply line for leaks and correct.

    CAUTION!

    SYSTEM DAMAGE

    due to incorrect burner.

    z Use only burners approved for use withBuderus G115 boilers.

    Fig. 18 Burner stud mounting locations on G115 burner door

    4 3/8"

    5 7/8"

    NOTICE

    The burner KP kit, supplied by BuderusHydronic Systems, Inc. contains acustomized, pre-set oil burner, a Taco 007

    or Grundfos circulator and pump flanges, aHoneywell L8148A aquastat and a flexibleoil line.

    NOTICE

    Observe for fine tuning of the burner boththe draft conditions of the chimney and burner manufacturers documentation.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    24/5624

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Installation7

    7.6 Aquastat Installation

    A Honeywell aquastat controls the boiler supply

    temperature when not using a Buderus Logamaticcontrol.

    z Install the Honeywell aquastat into the brass boilerwell. Make sure the capillary is fully inserted in the

    well. Do not kink capillary tubing.Refer to Chapter 8, page 28 regarding placing theboiler in operation.

    7.7 Electrical Connections

    This section only applies to G115 boilers equipped with

    a Buderus Logamatic control.

    z Remove rear top cover. Remove first rear sheetmetal screws.

    z Remove top cover plate. The electrical wiring will runthrough this race way.

    Fig. 19 Installation of aquastat

    1 Capillary

    1

    WARNING!

    DANGER

    due to electrical currents.

    z All electrical work must be performedby a qualified electrician.

    z Before opening the control: Shut offelectrical supply and prevent fromaccidental reactivation.

    z Observe all installation instructions.

    Fig. 20 Removal of top rear cover and top cover plate

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    25/56

    Boiler Installation 7

    25

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    7.7.1 Control System Installation

    z Slide plastic front tabs of control panel in the ovalshaped openings.

    z Slide the control panel forward.

    z Push forward on plastic snap tabs in rear of control toengage them into the top panels square knock-outs.

    z Remove top cover of control panel. Remove coverscrews.

    z Secure control to top cover using small sheet metalscrews.

    Fig. 21 Installation of control

    1 Plastic snap tabs

    2 Plastic front tabs

    3 Oval knock-outs

    4 Square knock-outs

    1

    3

    4

    2

    Fig. 22 Removal of top cover

    1 Top cover screws

    2 Sheet metal screws

    1

    2

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    26/5626

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Installation7

    7.7.2 Installation of Temperature Sensor and Burner Cable

    z Route the capillary tubing carefully and avoid kinking.Route capillaries and sensor wiring to the immersionwell.

    z Strap excess tubing and wiring together and place ontop of insulation.

    z Burner wiring can be routed down towards the frontof the boiler. If burner is supplied with a wiringharness, route harnesss between jacket panels and

    boiler insulation.z Install burner wiring per wiring instructions included

    with Logamatic control or refer to diagrams locatedon pages 51 to 53.

    z Bring the sensor bundle to the installed chrome welland slide bundle into the well. The plastic holding clipwill slide back.

    z Insert all sensing elements fully into the well andsecure tubing with furnished metal holding clip.

    7.7.3 Electrical Connections

    Install a power supply point near the boiler inaccordance with local and state code.

    Fig. 23 Routing and connecting of capillary, sensor and

    electrical wiring

    1 Cable raceway opening in top front cover

    2 Capillary tubing and sensor wiring.

    3 Well location.

    4 Burner cable/wiring

    1

    3

    2

    4

    CAUTION!

    SYSTEM DAMAGE

    Be careful not to kink or have the capillarytubes come in contact with sharpsurfaces.

    z Route the capillary tubing carefully and

    avoid kinking. Route capillaries andsensor wiring to the immersion well.

    Fig. 24 Installation of sensor bundle

    1 Chrome immersion well

    2 Plastic holding clip

    3 Tension clip

    4 Metal holding clip

    1

    1

    2

    3

    4

    NOTICE

    Every G115 boiler has a factory installedimmersion well for use with a Honeywellaquastat.

    z When installing a Logamatic control,you must replace the installed brass

    well with the chrome well supplied withthe Logamatic control.

    NOTICE

    Make sure all sensing elements are allfully inserted into the well and make good

    contact with well inner surface. Make sureto use the tension clip in the middle ofsensing elements.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    27/56

    Boiler Installation 7

    27

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    z Route all electrical wiring through the top cover raceway and install wiring per electrical schematics inLogamatic manuals.

    7.7.4 Strain Relief Installation

    Secure all electrical wiring near the Logamatic using thefurnished plastic cable ties.

    z Install cable ties with the tab facing up into the rear ofthe Logamatic (step 1).

    z Slide cable ties down and lock them in (step 2).

    z Push cable ties in (step 3).z Push hinging tab down to secure cable (step 4).

    7.8 Jacket Panel Installation

    z Put control top cover back and secure.

    z Install rear top panel on boiler.

    WARNING!

    FIRE HAZARD

    Electrical wiring can be damaged by hot

    boiler parts.

    z Make sure that all tubing and wiringcomponents are all placed on top ofthe boiler insulation.

    Fig. 25 Secure wiring with cable ties

    Fig. 26 Installation of rear top cover

    1 Control top cover

    2 Rear top panel

    2

    1

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    28/5628

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Placing the Boiler in Operation8

    8 Placing the Boiler in Operation

    This chapter describes the initial start-up procedure forthe G115 boiler irrespective of the employed controlsystem.

    z Please fill out the start-up protocol during thisprocess ( Chapter 8.10, page 33).

    Further information regarding boiler room lay-out andclearances, combustion air requirements and ventingsystem as well as boiler operational requirements referback to Chapter 3.2, page 8.

    8.1 Setting the Initial System PressureSet the system for regular operation during the initialstart-up procedure.

    z

    Add additional make-up water until the desiredpressure is achieved; at least 12 - 15 psi, but no morethan 30 psi. (Actual settings are dependent on thepressure rating of the relief valve).

    z Vent the system during the initial fill.

    8.2 Checking Relief Valve

    z Make sure nobody is near the discharge of the reliefvalve.

    z Lift up on the relief valve.

    The relief valve has to open and relief water andpressure. Replace the relief valve immediately if it doesnot discharge. A defective relief valve can causedamage to the system.

    CAUTION!

    Boiler DAMAGE

    due to excessive dust and aircontamination.

    z Do not operate the boiler under highdust conditions, such as sheet rockdust and construction dust. Make sure

    to provide clean combustion air if theboiler needs to operate under suchconditions,

    z Install an airfilter, or other means toensure clean combustion air. Dust canoriginate from within duringconstruction, but also from outsidewhen the installation is in close vicinityof chemical plants, shop or dustyoutside conditions.

    Fig. 27 Pressure and temperature gauge

    CAUTION!

    SYSTEM DAMAGE

    due to material stresses as a result oftemperature differences.

    z Use cold water for the initial fill. Limit

    the fill water temperature to 100 Fmaximum.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    29/56

    Placing the Boiler in Operation 8

    29

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    8.3 Check Position of Flue Baffle Plates

    Check to make sure that the flue baffle plates are in

    horizontal position before the initial start-up process.

    z Open the burner door by removing the two burnerdoor bolts.

    z Pull the baffle plates slightly out of the boiler.

    z Bring the baffles in a fully horizontal position andpush back into the boiler.

    z Close the burner door and torque door bolts evenlywith 90 lbs-inch torque using hex-head bolts.

    8.4 Get System Ready for ProperOperation

    z Open fuel shut-off valve.

    z Turn on main system disconnect switch.

    8.5 Start-up of Control and Burner

    Follow the burner start-up procedure per burnermanufacturer' recommendations. Follow the

    instructions furnished with the burner.

    Turn on the main switch of the Logamatic control toactivate the heating system. The burner comes on whenthe control is switched to manual mode. Follow theinstructions in the Service Manual of the control.

    z Select "manual" operation.

    z Set the desired adjustable limit temperature on the

    control.z Turn control on (Position I).

    Fig. 28 Opening of the burner door

    1 Flue baffles in secondary passages

    1

    Fig. 29 Switching control panel (Logamatic 2000 series

    controls)

    1 Adjustable high limit dial

    2 Main control switch

    I 0

    2

    1

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    30/5630

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Placing the Boiler in Operation8

    8.6 Guidelines Regarding Burner Start-up

    Allow the burner to operate for 15 to 20 minutes prior to

    performing combustion test.

    Earlier combustion tests can lead to erroneous readingsdue to burning off of the sealing rope. We recommendto check the burner after a few weeks of operation.

    Necessary instruments:

    CO2 measuring equipment

    Draft measuring equipment

    Oil pressure gauge

    Stack thermometer

    Smoke tester

    z Measure the over fire pressure at the measuring porton the burner door.

    z Measure the breeching draft in the vent connectortwo vent pipe diameters away from the ventconnections. (Only on chimney vent models: refer toDirect Vent Manual for proper test location).

    8.7 Adjusting Stack Temperatures

    Refer to ( Chapter 3, page 7) for approximate stacktemperatures.

    When you determine that the stack temperature is toolow, and condensate formation might take place in thechimney, the stack temperature can be increased by thefollowing steps:

    Adjust the flue baffles

    Remove the flue baffles

    Remove flue blocking plates

    z Shut-off the boiler ( Chapter 9.1, page 34).

    NOTICE

    Improper burner adjustments can lead toimproper combustion and sooting of theboiler. Burner lock-outs can also occur asa result.

    z Always check the combustion with thefollowing instruments.

    z Never check and/or adjust burneroperation by eye sight.

    Fig. 30 Pressure test port on burner door

    1 Pressure test port

    1

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    31/56

    Placing the Boiler in Operation 8

    31

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    8.7.1 Adjusting Flue Baffles

    Adjust or remove the flue baffles always in pairs.

    z Open burner door by removing the two hex headbolts.

    z Pull the flue baffles slightly out of the flue passages.

    z Rotate flue baffles inward and slide back into the fluepassages.

    z Close burner door and secure with burner door bolts(ca. 90 Lbs/inch). Tighten bolts evenly.

    z Measure the stack temperature again.

    8.7.2 Removing Flue Baffles

    To further increase the stack temperature, remove bothflue baffles.

    z Open burner door by removing the two hex headbolts.

    z Remove flue baffles from the front.

    z Close burner door and secure with burner door bolts(ca. 90 Lbs/inch). Tighten bolts evenly.

    z Measure the stack temperature again.

    WARNING!

    EXPOSION DANGER

    due to leaking gases.

    z Shut-off main valve when, in order toopen the burner door, the gas line mustbe disconnected from the burner. Allowthe remaining gas to disperse into the

    air. Do not smoke or generate a spark.

    CAUTION!

    Combustion Hazard

    due to contact with hot boiler surfaces.

    z Wear thermal protection gloves or use aset of pliers.

    Fig. 31 Adjusting flue baffles

    Fig. 32 Removing flue baffles

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    32/5632

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Placing the Boiler in Operation8

    8.7.3 Removing Blocking Plates

    When the stack temperature after removal of flue bafflesis still too low, you can also remove the front sectionblocking plates to increase the stack temperature.

    z Open burner door by removing the two hex headbolts.

    zRemove blocking plates by removing set screw fromthe front section.

    z Measure the stack temperature again.

    8.8 Testing of the Manual Reset High Limit (STB) of Logamatic controls

    The manual reset high limit will permanently interruptburner operation once its limit (230 F) is exceeded. To

    restore operation, it is required to reset this control andlower the water temperature well below its fixed setting.

    z Refer to Logamatic Service Manual to checkoperation of manual reset high limit.

    8.9 Install Front Jacket Parts

    z Hang boiler front panel into slots of boiler sidepanels.

    z Secure front panel with the two screws into the sidepanels.

    Fig. 33 Removing blocking plates

    Fig. 34 Installation of boiler front panel

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    33/56

    Placing the Boiler in Operation 8

    33

    We reserve the right to make any changes due to techincal modification!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    8.10 Detailed Start-up Procedure

    z Check off performed start-up steps, sign and date.

    Start-up Procedure Page Value Measured Comments

    1. Filling of system and check for leaks 21

    __________ psi

    2. Set operating pressure

    vent heating system

    check operation of relief valve

    pre-set expansion tank pressure ( see expansion tank manufacturer'

    instructions)

    28

    __________ psi

    3. Check combustion air and venting system

    4. Check position of flue baffles 29

    5. Turn on control ( Refer to control Service Manual) 29

    6. Turn on burner ( Refer to burner manual) 29

    7. Measure stack temperature (Adjust if needed) 30

    __________ F

    8. Check manual reset high limit (STB) 32

    9. Adjust control settings based on requirements ( Refer to control Service

    Manual))

    10. Inform end user and hand over instructions

    Confirm start-up procedure

    Company stamp/signature/date

    NOTICEz Always inform your customer

    regarding proper fuel source andrecord in Operating Manual.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    34/5634

    We reserve the right to make any changes due to techincal modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Taking the Boiler out of Operation9

    9 Taking the Boiler out of Operation

    9.1 Normal Boiler Shut-down

    z With Buderus Logamatic controls: Turn the mainswitch to "0" position. This shuts off power tocomponents wired directly to the control panel.

    z With Honeywell aquastat control: Shut off mainheating system switch. (Position "OFF") This shutsoff power to all components wired through thisswitch.

    z Further shut-down procedure: refer to aquastatdocumentation.

    z Shut off fuel supply by closing main valve.

    9.2 Emergency Shut-down

    Please explain suitable system operation duringemergency conditions, such as fire:

    z Shut off fuel supply by closing main valve.

    z Shut down the heating system electrically eitherusing the main emergency switch or the suitableelectrical breaker.

    Abb. 35 Shutting down heating system (Logamatic 2000)

    1 ON/OFF switch

    I 0

    1

    Fig. 36 Heating system shut-down (with aquastat)

    CAUTION!

    SYSTEM DAMAGE

    due to freezing.

    When the system is shut off, the systemcould potentially freeze up.

    z Keep the system operational as longas possible.

    z Protect the system against freeze-upby draining the entire system at itslowest point.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    35/56

    Boiler Maintenance 10

    35

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    10 Boiler Maintenance

    10.1 Why do Maintenance?

    Regular maintenance is required for the followingreasons:

    To maintain high efficiency operation and minimizefuel usage.

    To sustain reliable operation.

    To maintain clean combustion and reduce pollutantemissions.

    Please offer your customer an annual service andmaintenance plan. You can review the service andmaintenance protocol regarding precise description ofsuitable services ( Chapter 10.6, page 39).

    10.2 Prepare Boiler for Cleaning

    z Shut down the heating system ( Chapter 9.1,page 34).

    z Remove boiler front panel and possibly burner cover( Chapter 5.1, page 13).

    z Disconnect electrical supply to burner.

    NOTICE

    Spare parts can be ordered by contacting

    your Buderus wholesaler.

    WARNING!

    DANGER

    due to electricity.

    z Prior to opening control panel: Shutdown electricity supply and padlock

    shut to protect against accidentaloperation.

    WARNING!

    DANGER

    due to explosion of flammable fumes.

    z Perform service work on gascomponents only, when one has thenecessary certification.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    36/5636

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Maintenance10

    10.3 Boiler Cleaning

    The boiler can be cleaned using boiler brushes and/or

    with a wet cleaning. Boiler brushes are available fromyour Buderus wholesaler.

    z Open burner door by removing the two hex headbolts.

    10.3.1 Cleaning the Boiler with Brushes

    z Record the position of the flue baffles so they can beplaced back in their original position.

    z Remove blue baffles from passages.

    z Clean flue fire baffles using a hard bristled brush.

    z Brush out flue passages by rotating the round brush.

    z Clean the combustion chamber with a flat brush.

    Remove the loosened debris from combustionchamber, flue passages and breaching connectionareas.

    z Insert the flue baffles into the boiler in their originalposition.

    z Check burner door sealing rope. Replace damagedor hardened sealing rope.

    z Close burner door by tightening the burner door bolts(Torque to 90 Lbs-in ). Torque burner door evenly forproper door closure.

    CAUTION!

    COMBUSTION DANGER

    Due to contact with hot boiler parts.

    z Wear thermal protection gloves or usea set of pliers.

    Fig. 37 Opening of burner door

    1 Flue baffles in secondary flue passages

    1

    Fig. 38 Brushing our of flue passages

    Fig. 39 Brushing out the combustion chamber

    NOTICE

    Burner door sealing rope is availablethrough your local Buderus wholesaler.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    37/56

    Boiler Maintenance 10

    37

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    10.3.2 Wet Cleaning

    Use for the wet cleaning a suitable cleaning agentdesigned to dissolve the internal build-up or clean thesoot.

    Following the wet cleaning, proceed with the brushingsteps outlined in ( Chapter 10.3.1, page 36).

    z Cover control with plastic to prevent water damage.

    z Spray heating surfaces evenly with cleaning agent.

    z Close burner door and turn on heating system.

    z Heat the boiler to a minimum temperature of 160 F.

    z Turn the system off.z Brush out heating surfaces.

    10.4 Testing System Pressure

    The system pressure should be 15 to 30 psi for a closedsystem.

    z Check system pressure.

    z When the pressure gauge shows less than 12 - 15psi, the pressure is too low.

    NOTICE

    Observe and follow recommendations ofthe cleaning agent' manufacturer. Undercertain conditions you may need to deviatefrom the guidelines below.

    Fig. 40 Pressure/temperature gauge to display system

    pressure and supply temperature

    CAREFUL!

    SYSTEM DAMAGE

    due to frequent make-up water.

    When you add frequently make-up waterto the system, this can lead to corrosionand lime build-up in the system.

    z Make sure that the heating system is

    equipped with automatic airelimination.

    z Verify that the system has no leaks and

    check the expansion tank for properoperation.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    38/5638

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Maintenance10

    z Add make-up water through the automatic feedvalve.

    z Vent system.

    z Check system working pressure.

    10.5 Testing Relief Valve

    Check the functioning of the relief valve every 1 to 3years as required per local code.

    z Make sure nobody is near the discharge of the reliefvalve.

    z Lift up on the relief valve.

    The relief valve must open and discharge water. If thevalve does not discharge, replace the valve andrecheck. If the defective valve is not replaced, it canlead to damage to certain system components due toexcessive high pressures.

    CAREFUL!

    SYSTEM DAMAGE

    due to material stresses as a result of

    temperature differences.

    z Add only additional make-up waterwhen the system is cold (Temperaturegauge reading should not exceed

    100 F).

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    39/56

    Boiler Maintenance 10

    39

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    10.6 Inspection and Maintenance Procedure

    z Sign off and date performed service work. This service and maintenance protocol can also becopied for further use.

    Service work Page Date: ______ Date: ______ Date: ______

    1. Check general status of system

    2. Do visual performance test on system

    3. Check fuel and water components for:

    Leaks during operation

    Hydrostatic water test

    Visual corrosion

    Exterior system changes

    4. Check flue passages for soot, shut off system 35

    5. Check burner operation ( See burner manual)

    6. Check combustion air inlets and vent system

    7. Check system pressure, relief valve and expansion tank 37

    8. Check DHW tank anode status ( See DHW tank manual)

    9. Check control settings ( See manual)

    10. Final check, record combustion test results

    Confirm service work

    Sign/date Sign/date Sign/date

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    40/5640

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Maintenance10

    Date: ______ Date: ______ Date: ______ Date: ______ Date: ______ Date: ______ Date: ______

    1.

    2.

    3.

    4.

    5.

    6.

    7.

    8.

    9.

    10.

    Sign/date Sign/date Sign/date Sign/date Sign/date Sign/date Sign/date

    NOTICE

    When you find conditions during theannual service/maintenance work thatrequire attention, please perform thenecessary remedial steps.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    41/56

    Boiler Maintenance 10

    41

    We reserve the right to make any changes due to technical modifications!

    Boiler Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Maintenance Procedure page Date: ______ Date: ______ Date: ______

    1. Take the boiler out off operation 35

    2. Remove blue baffles from passages and clean flue fire baffles 35

    3. Clean flue passages and the combustion chamber,Insert the flue baffles into the boiler in their original position

    35

    4. Check burner door sealing rope. Replace damaged or hardened

    sealing rope. Close burner door by tightening the burner door bolts.

    36

    5. Take the boiler in operation 29

    6. Final check at the system after maintenance and service inspection

    7. Check boiler in operation

    Confirm service and maintenance work

    Sign/date Sign/date Sign/date

    Date: ______ Date: ______ Date: ______ Date: ______ Date: ______ Date: ______ Date: ______

    1.

    2.

    3.

    4.

    5.

    6.

    7.

    Sign/date Sign/date Sign/date Sign/date Sign/date Sign/date Sign/date

    http://../G0000501_03G00043/Kundenunterlagen/FM_bedingt_neu%20aktuell/BKap08_de1.pdfhttp://../G0000501_03G00043/Kundenunterlagen/FM_bedingt_neu%20aktuell/BKap08_de1.pdf
  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    42/5642

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Restoring Sytem Lock-outs11

    11 Restoring Sytem Lock-outs

    One can identify two different types of lock-outs

    burner lock-outs.

    control and system lock-outs.

    A lock-out light will typically be lit on the burner ( seeburner manual) during its lock-out. Press the burnerreset button once to restart the burner. Call your servicecompany immediately if the burner locks out again. DoNOT continue to reset the burner.

    Error conditions on the control or in the system are typi-cally displayed on the control display, if so equipped.Further information can be found in the control

    Service Manual.

    Correct burner lock-outs

    z Remove burner cover, when the burner is so equip-

    ped. Press the burner reset buttom once.Fig. 41 Resetting the burner

    1 Burner

    1

    WARNING

    SYSTEM DAMAGE

    durch Frost.

    When the entire system is shut off, it cancause a freeze-up condition.

    z Have any lock-out condition correctedimmediately and restart the heatingsystem.

    z If this is not possible, protect the sys-

    tem for freeze-up by draining the hea-ting system and domestic hot watersystem at their respective lowestpoints.

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    43/56

    Piping Diagrams 12

    43

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    12 Piping Diagrams

    Explanation of the abbreviations

    KR Flow check SH 3-way motorized valve

    MAG Expansion tank WH Boiler bypass

    PH Heating pump SV Relief valve / Air elimination

    PW DHW charging pump THV Zone valve

    Fig. 42 Zoning with zone valve

    Baseboard

    Baseboard

    Baseboard

    G115

    PHSV

    MAG

    THV

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    44/5644

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Piping Diagrams12

    Fig. 43 Zoning with pumps

    G115

    Baseboard

    Baseboard

    Baseboard

    MAG

    SV

    PH

    KR

    Fig. 44 Zoning with zone valves and built-in bypass for larger water volume systems

    Baseboard

    Baseboard

    Baseboard

    G115 " Boiler Bypas

    PHSV

    MAG

    THV

    WH

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    45/56

    Piping Diagrams 12

    45

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Fig. 45 Multiple zones with DHW, high temperature and low temperature circuits with a motorized 3-way valve

    G115

    R2107

    M

    Baseboard

    1800

    100 0120 0

    160 0180 0

    100 0

    PS

    SV

    MAG

    KR

    SH

    PH

    PH

    KR

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    46/5646

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Spare Parts13

    13 Spare Parts

    The following parts are available through BuderusHydronic Systems. Model specific part numbers arelisted under the various models. In other cases the tableshows the number of components for each model.

    Boiler block and burner door(Fig. 46)

    Legend for tables 12 and 13:

    x = no spare part

    (x) = component of a set, only furnished with the set

    0 = no picture available

    Item Description Part number

    G115/21

    3 section

    G115/28

    4 section

    G115/34

    5 section

    10 Boiler block G115 05952285 05952290 05952295

    Front section components:

    21 Plug G1 1/4" right 86055310

    22 Gasket for plug D41,7x55x1,5mm AFM 34,white 86159710

    23 Blocking plate with screw M8x16 63015342

    24 Screw DIN7991 M8x16 Ms (x)

    rear section components:51 Plug DIN2950 291 1" 05317680

    52 Threaded stud M10x65 5.6 05555070

    53 Distance sleeve R3/8"x39 (x)

    54 Hex. head nut ISO4032-M10-8-A3K (x)

    55 Washer DIN125-A10,5-A3K (x)

    60 Immersion well Pmw-3See (4 1/2")"US" 00472887

    70 Tie bar - Set M8x310mm 05127574

    70 Tie bar - Set M8x440mm 05127578

    70 Tie bar - Set M8x555mm 05127580

    80 Flue collector 05354074

    Flue collector components81 Sealing rope 8x1050 GP 63020961

    0 Glue for securing rope (a 310ml) 63014361

    90 Return diffuser 1 1/4-NPT1 compl. G115"US" 63028062 63028062 63028061

    91 Gasket 55x41,7x1,5mm 05752540

    Spare parts which are not furnished with the spare boiler b lock:

    120 Flue baffle 05347085 05347087 05347089

    130 Boiler rail 420mm long 05198102

    130 Boiler rail 540mm long 05198104

    130 Boiler rail 660mm long 67900117

    131 Washer DIN126-9 (x)

    132 Hex. head screw ISO4017-M8x25-8.8 (x)

    133 Hex. head nut DIN6923-M8-8.8-A3K (x)

    140 Door hinge G105/G115 05327033

    141 Scheibe DIN125-A10,5-A3K (x)

    142 Sechskantschraube ISO4017-M10x25-8.8 (x)

    150 Sechskantschraube ISO4014-M10x65-8.8 (x)

    160 Washer DIN125-A10,5-A3K (x)

    180 Boiler feet M10x51mm complete 05236440

    Tab. 12 Boiler block and burner door

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    47/56

    Spare Parts 13

    47

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    190 Gasket for flue collar DN130 complete 05354010

    200Flue silencer DN130 complete, without condensate drain; higher sound

    absorption05074020

    or:

    210Flue silencer D130 with adapter 100mm long, with condensate drain,

    lower sound absorption05074022

    Flue silencer components:

    190 Flue collar DN130 complete 05354010

    220 Flue collar DN130 complete (step cuff) 05354030

    230 Sealing rope10x2000 GP 63020963

    250 Burner door complete 63023858

    Burner door components:

    260 Door hinge 05327020

    270 Washer DIN125 A10,5 A3K (x)

    280 Hex. head screw ISO4017 M10x25 8.8 (x)

    290 Observation port cover complete G115/G125/G135 63023634

    Observation port cover components:

    300 Gesket 30x30x3 63014382

    310 Sight glass Tempax 30x30x3,3mm 05447620

    320 Sight glass cover plate x330 Hex. head screw ISO4017 M6x12 8.8 A3K (x)

    340 Pressure measuring port M6 SW10 V2 63026521

    350 Burner door insulation G115 W607 63002401

    Burner door insulation components:

    360 Insulating plate for burner door 24mm 63004169

    370 Insulating ring for burner door 10mm 63004170

    380 Washer DIN9021 A6,4 A3K (x)

    390 Sheet metal screw DIN7981 C ST6,3x25 A3T (x)

    400 Sealing rope14x1650 GP 63020965

    0 Glue for securing sealing rope to burner door (a 310ml) 63014361

    (x)

    Mounting material for boiler block G115 "US"

    63031288

    Components:

    1 Hex. head screw M8x16 Ms

    2 Distance sleeve R3/8"x39

    2 Hex. head nut ISO4032 M10 8 A3K

    8 Washer DIN125 A10,5 A3K

    4 Washer DIN126 9

    4 Hex. head screw ISO4017 M8x25 8.8

    4 Hex. head nut DIN6923 M8 8.8 A3K

    4 Hex. head screw ISO4017 M10x25 8.8

    2 Hex. head screw DIN6921 M10x65 8.8

    1 Hex. head screw ISO4017 M6x12 8.8A3K

    2 Washer DIN9021 A6,4 A3K

    2 Sheet metal screw DIN7981 C ST6,3x25 A3T

    0

    B-KIT G115"US"

    63029762

    Components:

    1 Supply manifold G115"US"

    1 90 degree 1 1/4 NPT elbow

    1 90 degree 3/4 NPT elbow

    1 Conversion nipple R11/4-11/4NPTx75

    1 Boiler drain valve 3/4

    1Relief valve 3/4Mx3/4F 30PSI

    1 Pressure / Temperature gauge 1/4NPT

    1 Screw-Set B-Kit G115"US"1 Boiler feet set M10x51

    Tab. 12 Boiler block and burner door

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    48/5648

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Spare Parts13

    Fig. 46 Boiler block and burner door

    1023033-00-Kesselblock G115 US

    21

    23

    24

    133

    133

    180

    180

    5253

    22

    21

    370

    380

    390

    280

    270

    260

    250

    350

    300290

    310

    330

    340

    320

    350

    400

    360

    22

    52

    5554

    80

    142

    141

    140

    130

    131

    132

    120

    70

    70

    9190

    10

    8151

    60

    150160

    70

    230220

    200

    210

    190

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    49/56

    Spare Parts 13

    49

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Boiler Jacket Components (Fig. 47)

    Item Description Part number

    G115/21

    3 section

    G115/28

    4 section

    G115/34

    5 section

    The complete boiler jacket for a G115 boiler contains the following components: front panel, name plate, front insulation, top gross bracket, 2 side

    panels, boiler block insulation, holding clips, top front cover, top rear cover, rear panel and mounting material set.

    Boiler jacket components:10 Front panel G115/S105 63029203

    18 Name plate Logano G115 67902824

    20 Front insulation G115 63025265

    40 Hex. head screw ISO4017-M8x12-8.8 (x)

    50 Top groos bracket G115/G115U 63029209

    60 Hex. head nut DIN555 M8 5 (x)

    70 Washer DIN126 9 (x)

    80 Side panel 445mm long 63029945

    80 Side panel 565mm long 63029946

    80 Side panel 685mm long 63029947

    85 Sheet metal screw C ST3,9x13 A3T (x)

    90 Screw 3,9x9,5 A3T (x)

    95 Clip (x)

    100 Boiler block insulation G115 05670040

    100 Boiler block insulation G115 05670045

    100 Boiler block insulation G115 05670046

    110 Holding clips for boiler block insulation 00476378

    120 Top front cover G115/G115U/S105/S105U 63029222

    125 Cover plate 300x160 63021497

    130 Top rear cover complete G115 "US" 05198112 05198114 05198176

    140 Rear panel complete G115 05198084

    150 Cable rail way 07060754

    160 Washer DIN432 10,5 St A3E (x)

    170 Hex. head nut DIN555 M10 5 (x)

    (x)

    Mounting material for boiler jacket G115, GC115, G125, G134

    05180842

    Components:

    17 Screw St3,9x9,5-A3T

    3 Sheet metal screw C-St3,9x13-A3T

    1 Screw DIN7985-M6x16-4.8-A3T

    2 Clip

    4 Hex. head screw ISO4017-M8x12-8.8

    1 Hex. head nut DIN555 M8 5

    4 Washer DIN126 9

    4 Washer DIN432 10,5 St A3E

    4 Hex. head nut DIN555 M10 5

    Tab. 13 Boiler jacket components

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    50/5650

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Spare Parts13

    Fig. 47 Boiler jacket components

    1023034-00-Kesselverkleidung G115 US

    4070

    85

    80

    18

    4070

    80

    4070

    6050

    85

    20

    100

    10

    170160

    90

    130

    120

    90

    90

    12590

    140 150

    170160

    90

    95

    110

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    51/56

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    52/5652

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    SP30D and Burner Wiring14

    Fig. 49 Wiring diagram 2

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    53/56

    SP30D and Burner Wiring 14

    53

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    Fig. 50 Wiring diagram 3

  • 7/27/2019 201001221723430.63030586_G115InstallationManual0304.pdf

    54/56

    54

    We reserve the right to make any changes due to technical modifications!

    Installation and Maintenance Manual Logano G115 US Issue 03/2004

    Buderus Heiztechnik GmbH http://www.heiztechnik.buderus.de

    SP3