2012 IRC Wall Bracing Provisions
CONNECTIONS CRIPPLE WALLS FOUNDATION
Module 8
2012 IRC Wall Bracing 2
Objectives
• Upon completion of this module, you will be better able to:
• Describe connection of braced wall panels
• Describe cripple walls
• Identify foundations
2012 IRC Wall Bracing 3
Item Building Element Number and Type
of Fastener
Spacing of
Fasteners
7 Built-up studs-face nail 10d (3" × 0.128") 24" o.c.
8
Abutting studs at
intersecting wall corners,
face nail
16d (3 ½” x 0.135”) 12" o.c.
12 Double studs, face nail 10d (3" × 0.128") 24" o.c.
13 Double top plates, face nail 10d (3" × 0.128") 24" o.c.
2012 IRC Wall Bracing 4
Bracing: Connections BWP sole plates and top plates connections per Table R602.3(1)
Excerpt from Table R602.3(1) Items 7, 8, 12, 13
Item Building Element Number and Type of
Fastener
Spacing of
Fastener
14
Double top plates,
minimum 24-inch offset of
end joints, face nail in
lapped area
8-16d (31/2″ × 0.135″) --
16 Sole plate to joist or
blocking at braced wall
panels
3-16d (31/2″ × 0.135″) 16″ oc
2012 IRC Wall Bracing 5
Bracing: Connections BWP sole plates and top plates connections per Table R602.3(1)
Excerpt from Table R602.3(1) Items 14 and 16
2012 IRC Wall Bracing 6
Bracing: Connections
When braced wall panels are perpendicular to joists above or below, blocking shall be provided in line with the BWPs…
R602.10.8 Item 1, Figure R602.10.8(1)
3.7
BWP BWP BWP
Bracing: Connections
7
BWP Perpendicular to Framing
Figure R602.10.8(1) & Table R602.3(1)
2012 IRC Wall Bracing 7
Bracing: Connections
2012 IRC Wall Bracing 8
Where joists are parallel to BWPs above or below… where a parallel framing member cannot be located… full-depth blocking at 16 inch spacing shall be provided…
BWP Blocking (not parallel)
R602.10.8 Item 2, Figure R602.10.8(2)
Bracing: Connections
9
BWP Parallel to Framing
Figure R602.10.8(2) & Table R602.3(1)
2012 IRC Wall Bracing
SDC
Wind Speed
Distance (bottom
of roof sheathing
to top of plate)
Blocking1
SDC A, B, C
Wind < 100 mph
9.25" or less Not required, attach per R602.3(1)
9.25" to 15.25" Per R602.10.8.2 Item 1 and
Figure R602.10.8.2(1)
SDC D0, D1, D2
Wind > 100 mph 15.25" or less
Per R602.10.8.2 Item 2 and Figure
R602.10.8.2(1)
All SDCs
Wind < 110 mph 15.25" to 48"
Per R602.10.8.2 Item 3 and Figure
R602.10.8.2(2) or R602.10.8.2(3)
Bracing: Connections
2012 IRC Wall Bracing 10
(1) Rafter or truss plate connection per Table R602.3(1)
R602.10.8.2
BWP Connection Requirements to Roof Framing
Bracing: Connections
2012 IRC Wall Bracing 11
Figure R602.10.8.2(1)
BWP Perpendicular to Rafters or Roof Trusses
For SDC A, B and C and wind
speeds less than 100 mph,
where
• 9.25″ < distance < 15.25″ from
top of the rafters to
perpendicular top plates
• The rafters connected to the top
plates of braced wall panels
with blocking in accordance
with Figure R602.10.8.2(1) and
attached using Table R602.3(1).
2012 IRC Wall Bracing 12
Bracing: Connections
BWP Perpendicular to Rafters or Roof Trusses
For all Seismic Design
Categories and wind
speeds, where
• Distance > 15.25″ from top
of rafters or roof trusses to
perpendicular top plates
• Perpendicular rafters or roof
trusses shall be connected
to the top plates of braced
wall panels in accordance
with Figure R602.10.8.2(2) or
Figure R602.10.8.2(3)
Roof Trusses per R802.10
Figure R602.10.8.2(2)
2012 IRC Wall Bracing 13
Bracing: Connections
Figure R602.10.8.2(3)
Roof Trusses per R802.10
Bracing
BWP Perpendicular to Rafters or Roof Trusses
Roof Connections
Section R802.11
2009 IRC - requires roof assemblies with more than 20 psf roof uplift pressure to use connectors having a minimum capacity equal to Table R802.11. Use Table R301.2(2) to determine uplift (-) value
2012 IRC Wall Bracing 14 R802.11
2009 IRC
Component and cladding loads above 20 psf require a connector.
For shallow roofs, that only occurs in regions with winds more than 100 mph
2012 IRC Wall Bracing 15
Roof Connections
Roof Connections
Zones 2 and 3 are at the edges of roofs
2012 IRC Wall Bracing 16
Roof Connections
Section R802.11
2012 IRC - requires roof assemblies with uplift greater than 200 lbs to have rafters or trusses tied to walls with connectors having a minimum capacity equal to Table R802.11
2012 IRC Wall Bracing 17 R802.11
2012 IRC
Use of Table R301.2(2) is not needed
Under 200 lbs, 3 toenails are OK
Above 200 lbs, a manufactured connector is required.
2012 IRC Wall Bracing 18 Table R802.11
Roof Connections
For loads above 200 psf
2012 IRC Wall Bracing 19
CRIPPLE WALLS
2012 IRC Wall Bracing 20
2012 IRC Wall Bracing 21
Main Concepts – Code provisions defined in R602.9.
– Supported on continuous footings.
– There are two methods for determining the required braced panel length for cripple walls (R602.10.11).
Cripple Walls
Cripple Wall
A framed wall
extending from the
top of the foundation
to the underside of
the floor framing of
the first story above
grade plane.
Bracing Length from
Tables R602.10.3(1) or (3)
for Roof only
1.15 x (Roof only Bracing Length)
Cripple Walls
2012 IRC Wall Bracing 22
Cripple Wall Supporting One Story
Bracing Length from
Tables R602.10.3(1) or (3)
for Roof only
Roof + Floor Bracing Length
Redesignated as a Two-story
or
R602.10.11
Seismic Design Categories A-D1
14' BWP edge to edge 20' BWP edge to edge
Bracing Length from
Tables R602.10.3(1) or (3)
for Roof only
1.15 x (Roof + 1 Floor BP Length)
Bracing Length from
Tables R602.10.3(1) or (3)
for Roof + 1 Floor
14' BWP edge to edge
Cripple Wall Supporting Two Stories
Redesignated as a Three Story
20' BWP edge to edge
Bracing Length from
Tables R602.10.3(1) or (3)
for Roof only
BP length for Roof + 2 Floors
Bracing Length from
Tables R602.10.3(1) or (3)
for Roof + 1 Floor
or
Cripple Walls
2012 IRC Wall Bracing 23 R602.10.11
Seismic Design Categories A-D1
2012 IRC Wall Bracing Wind 24
Cripple Walls
Cripple Wall or Story Above Grade? See Chapter 2 Definitions: Story Above Grade Grade Plane
Stacked framing not permitted
Cripple Walls
2012 IRC Wall Bracing 25
FOUNDATION
2012 IRC Wall Bracing 26
Bracing: Foundation
2012 IRC Wall Bracing 27
Soil friction Lateral bearing capacity
Weight of the structure and footing Bearing capacity of soil
Weight of soil
Sliding Resisted by soil friction and lateral bearing capacity of soil.
Overturning Resisted by weight of structure and footing, weight of soil on footing, and bearing capacity of soil.
Bracing: Foundation
2012 IRC Wall Bracing 28
7"
1' 0"
6"
1' 0"
6" 7"
W W
T
P
3-1/2"
R403.1.1
Slab on Grade Raised Floor
Bracing: Foundation
2012 IRC Wall Bracing 29
6' Max.
7 bolt dia. min. to 12" max.
1/2" bolt with 7" min. embedment in concrete or masonry
End of Plate
R403.1.6
Bracing: Foundation
2012 IRC Wall Bracing 30
Footings: Anchor bolt length
• Bolts embedded 7 inches • Total length = 7" + plate(s) depth + threaded end
Footing depth • Minimum 12 inches (R403.1.4) • Frost depth controls in many areas
Footing width, W • Table R403.1 lists minimum footing widths
Bracing: Foundation
2012 IRC Wall Bracing 31
Code Section Provision SDC
A-C
High Seismic Regions
SDC D0-D2
R602.10.6, Figures
R602.10.6.1 and
R602.10.6.2
Alternate wall
bracing (ABW,
PFH)
Methods ABW and PFH
required 1-#4 horizontal top
and bottom of footing
Methods ABW and PFH
required 1-#4 horizontal at
top and bottom of footing
R602.10.9,
Figure R602.10.9
Short concrete
or masonry
walls below
BWPs
Rebar required complying
with Figure R602.10.9 if wall
length, height, and
thickness are
L ≤ 48" AND H > 12" AND T < 6"
Rebar required complying
with Figure R602.10.9 if wall
length, height, and
thickness are
L ≤ 48" AND H > 12" AND T < 6
Wall Bracing – Foundation Requirements (R602.10)
Bracing: Foundation
2012 IRC Wall Bracing 32
3"
#4 bars at top & bottom
For footings supporting an ABW or PFH panel
R403.1.3.2
Wall Bracing Section Requirements
Bracing: Foundation
2012 IRC Wall Bracing 33
Narrow Masonry Wall Requirements Only required for walls less
than 48" long.
Bracing: Foundation - Wood
2012 IRC Wall Bracing 34
Summary
This module covered: • Connection of braced wall panels
– Table R602.3(1) contains a number of requirements for the fastening of wall elements.
– When braced wall panels are parallel to joists above or below and the joists are not aligned with the braced wall panels, blocking at 16 inches on center is required between the joists.
• Cripple Walls – situated at the bottom of the first story – main code provisions for cripple walls are in Section R602.9.
• Foundations – In the case of the RCO, foundations are focused on footings – OBC Sections R403 and R602.10 do not directly reference the
foundation and basement wall section of Chapter 4.