Page 1: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 2: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 3: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 4: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 5: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 6: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 7: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density

FOR FIBER OPTIC CABLE

TYPE 5 INSTALLATION

THE SPECIFICATIONS.

SHALL COMPLY WITH APPLICABLE PROVISIONS OF

BACKFILLING, RESEEDING OR RESODDING

B

B

FRONT SLOPES GREATER THAN 4:1 - MIN. DIST. 3'

FRONT SLOPES OF 6:1 TO 4:1 - MIN. DIST. 5'

FIBER OPTIC CABLE

TYPE 5 INSTALLATION FOR

HDPE SDR 11, SMOOTHWALL DUCT

ENCASEMENT HDPE SDR 11, SMOOTHWALL

HDPE - HIGH DENSITY POLYETHYLENE

DIST.- DISTANCE

MIN. - MINIMUM

ABBREVIATIONS

BE TO THE SATISFACTION OF THE ENGINEER.

THE CONTRACTOR AT THE CONTRACTOR'S EXPENSE. REPAIR SHALL

ROADWAY PAVEMENT CAUSED BY UPHEAVAL SHALL BE REPAIRED BY

UPHEAVAL IN ROADWAY SHALL NOT BE ALLOWED. DISTURBANCE OF6.

JACKING AND BORING NOT ALLOWED.5.

REQUIREMENTS OF THAT RAILROAD.

ENCASEMENT UNDER RAILROAD TRACKS SHALL CONFORM TO THE4.

NUMBER OF LINES AND SIZE OF ENCASEMENT AS SHOWN ON PLANS.3.

SHOWN ON PLANS.

NUMBER AND SIZE OF CONDUITS AND FIBER OPTIC CABLE AS2.

DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS.

PAY ITEM 756. REFER TO SECTION 756 OF THE CURRENT ALABAMA

ALL CONDUIT INSIDE ENCASEMENT SHALL BE PAID FOR UNDER1.

NOTES:

OF TRANSPORTATIONALABAMA DEPARTMENT

PAVED SHOULDERS

ROADWAY

TONE WIRE, #14 AWG

SECTION B - B:

FIBER OPTIC CABLE

72" MINIMUM DEPTH

I.T.S. - 734 - 001 951

YEAR

REFERENCE FISCAL SHEET

PROJECT NO NO

NOT TO SCALE

TENNESSEE

FLORIDA

GulfofMexico

GEOR

GIA

MISSISSIP

PI

DEPA

RTMENT OF TRANSP

ORTA

TIO

N

ALABAMA

OF TRANSPORTATION REPRESENTATIVE AUTHORIZED TO APPROVE THIS USE. ANYONE MAKING

UNAUTHORIZED USE OF THIS DRAWING MAY BE PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

DESIGN BUREAU SPECIAL DRAWING

1409 COLISEUM BOULEVARD

MONTGOMERY, AL 36130-3050

THIS DRAWING REPRESENTS DESIGNS PREPARED FOR USE BY THE ALABAMA DEPARTMENT OF

ANY ORGANIZATION, WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE ALABAMA DEPARTMENT

TRANSPORTATION AND IS NOT TO BE COPIED, REPRODUCED, ALTERED, OR USED BY ANYONE, OR

REVISIONS

CURRENT ALABAMA DEPARTMENT OF TRANSPORTATION

--SPECIFICATIONS--

DRAWN BY:

DATE DRAWN:

SPECIAL DRAWING NO. INDEX NO.

I.T.S. - 734 - 9

Page 8: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 9: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density
Page 10: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density

SURFACESKID RESISTANT

PULL SLOTS (2)

FIBER OPTIC

W/WASHERS (2)HEX BOLTS3/8" - 16

PULL SLOTS (2)

FIBER OPTIC

TONE WIRE

BONDING PLATE

SURFACESKID RESISTANT

(ALDOT #57)

COARSE GRAVEL

(ALDOT #57)

COARSE GRAVEL

1 - HEAVY DUTY COVER (2 PIECES)

1 - OPEN BOTTOMED BOX1 - OPEN BOTTOMED BOX

1 - HEAVY DUTY COVER (1 PIECE)

GROUND LINE

COMMBOX W/ COVERCABLE RACK

GROUND LINE

FIBER TRUNK CABLE *

CONDUIT

* NOTE: FIBER TRUNK AND DROP CABLE(S) AS REQUIRED ON PLAN LAYOUT

CLOSURE

SPLICE

CONDUIT

FIBER TRUNK CABLE *

FIBER DROP CABLE *

W/WASHERS (2)

HEX BOLTS

3/8" - 16

COMMBOX TYPE F2

GROUND LINEGROUND LINE

COMMBOX TYPE F1

COMMBOX TYPE F1 (NOMINAL: 24" X 36" X 30") COMMBOX TYPE F2 (NOMINAL: 30" X 48" X 36")

NOTES:

COIL)

(MAINTENANCE

SLACK LOOP

DETAIL: CABLE RACK INSTALLATION

1 - CABLE RACK 1 - CABLE RACK

6"

6"

6" 6" 6"

18"

6"

6" 6" 6" 6"

18"

REQUIREMENTS.

ALL SLACK LOOP SHALL MEET MANUFACTURER'S BEND RADIUS6.

RACK USING A NON-METALLIC MATERIAL.

ALL SLACK LOOP SHALL BE LOOSELY STRAPPED TO THE CABLE5.

AND A MINIMUM OF 6 INCHES FROM THE TOP.

CABLE RACK SHALL BE CENTERED ON ONE WALL OF COMMBOX4.

INCHES OUT FROM EACH SIDE OF THE COMMBOX.

SHALL EXTEND 18 INCHES BELOW THE BOTTOM AND SIX (6)

AN AGGREGATE BASE OF COURSE GRAVEL (ALDOT #57)3.

BENDING RADIUS OF THE FIBER OPTIC CABLE.

THE RADIUS OF THE CONDUIT TURNS SHALL NOT EXCEED THE

BE SEALED USING WATER-BLOCKING POLYURETHANE MATERIAL.

THE BOX. ALL ENDS OF THE CONDUIT WITHIN COMMBOX SHALL

THAT IT EXTENDS THREE (3) INCHES ABOVE THE BOTTOM OF

ALL CONDUIT SHALL BE TURNED UP THROUGH GRAVEL BASE, SO 2.

COMMBOX.

BE INSTALLED BY MANUFACTURER PRIOR TO DELIVERY OF

ON TOP OF THE OPEN BOTTOMED BOX. THE CABLE RACK SHALL

THE COMMBOX SHALL FIT TOGETHER SO THAT THE COVER FITS

COVER, (1) OPEN BOTTOMED BOX, AND (1) CABLE RACK.

COMMBOX SHALL BE DEFINED TO INCLUDE (1) HEAVY DUTY 1.

NOTESCABLE RACK

SEE

NOTESCABLE RACK

SEE

FOR FIBER OPTIC CABLE

COMMBOX F1 & F2

I.T.S. - 734 - 005 955

TONE WIRE

YEAR

REFERENCE FISCAL SHEET

PROJECT NO NO

NOT TO SCALE

TENNESSEE

FLORIDA

GulfofMexico

GEOR

GIA

MISSISSIP

PI

DEPA

RTMENT OF TRANSP

ORTA

TIO

N

ALABAMA

OF TRANSPORTATION REPRESENTATIVE AUTHORIZED TO APPROVE THIS USE. ANYONE MAKING

UNAUTHORIZED USE OF THIS DRAWING MAY BE PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

DESIGN BUREAU SPECIAL DRAWING

1409 COLISEUM BOULEVARD

MONTGOMERY, AL 36130-3050

OF TRANSPORTATIONALABAMA DEPARTMENT

THIS DRAWING REPRESENTS DESIGNS PREPARED FOR USE BY THE ALABAMA DEPARTMENT OF

ANY ORGANIZATION, WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE ALABAMA DEPARTMENT

TRANSPORTATION AND IS NOT TO BE COPIED, REPRODUCED, ALTERED, OR USED BY ANYONE, OR

REVISIONS

CURRENT ALABAMA DEPARTMENT OF TRANSPORTATION

--SPECIFICATIONS--

DRAWN BY:

DATE DRAWN:

SPECIAL DRAWING NO. INDEX NO.

I.T.S. - 734 - 9

Page 11: alletting.dot.state.al.usalletting.dot.state.al.us/Docs/Standard_Drawings/2015... · 2014-11-20 · hdpe sdr 11, smoothwall duct encasement hdpe sdr 11, smoothwall hdpe - high density

GROUND LINE

1'

2'

2-FIBER CONDUITS

TUBULAR ANCHOR SYSTEM

DIGGING

CALL BEFORE

TENNESSEE

FLORIDA

GulfofMexico

GEOR

GIA

MISSISSIP

PI

DEPARTMENT OF TRANSPORTATION

BURIED

FIBER

OPTIC

CABLE

XXX - XXX - XXXX

ALABAMA

W

RNI

A

NG

MARKER POST (DOME)

DO

ME

CO

VE

R

3.5" MIN. O.D.

18"

72"

DOME COVER

DIGGING

CALL BEFORE

TENNESSEE

FLORIDA

GulfofMexico

GEOR

GIA

MISSISSIP

PI

DEPARTMENT OF TRANSPORTATION

BURIED

FIBER

OPTIC

CABLE

XXX - XXX - XXXX

ALABAMA

W

RNI

A

NG

Dome cover shall be printed on both sides.2.

recommended tubular anchoring system.

Dome marker post shall be anchored with manufacturer's1.

NOTES:

FOR FIBER OPTIC CABLE

MARKER POST

OF TRANSPORTATIONALABAMA DEPARTMENT

I.T.S. - 734 - 006 956

YEAR

REFERENCE FISCAL SHEET

PROJECT NO NO

NOT TO SCALE

TENNESSEE

FLORIDA

GulfofMexico

GEOR

GIA

MISSISSIP

PI

DEPA

RTMENT OF TRANSP

ORTA

TIO

N

ALABAMA

OF TRANSPORTATION REPRESENTATIVE AUTHORIZED TO APPROVE THIS USE. ANYONE MAKING

UNAUTHORIZED USE OF THIS DRAWING MAY BE PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

DESIGN BUREAU SPECIAL DRAWING

1409 COLISEUM BOULEVARD

MONTGOMERY, AL 36130-3050

THIS DRAWING REPRESENTS DESIGNS PREPARED FOR USE BY THE ALABAMA DEPARTMENT OF

ANY ORGANIZATION, WITHOUT THE EXPRESSED WRITTEN CONSENT OF THE ALABAMA DEPARTMENT

TRANSPORTATION AND IS NOT TO BE COPIED, REPRODUCED, ALTERED, OR USED BY ANYONE, OR

REVISIONS

CURRENT ALABAMA DEPARTMENT OF TRANSPORTATION

--SPECIFICATIONS--

DRAWN BY:

DATE DRAWN:

SPECIAL DRAWING NO. INDEX NO.

I.T.S. - 734 - 9