EGRESS WIDTH PER OCCUPANT CALCULATIONS (FULLY SPRINKLERED)
FULL FLOOR TENANT Based Upon the 2012 IBC Code
Sections 1005.3.1 and 1005.3.2
STAIR DOOR WIDTH STAIR WIDTH
INCHES / RATIO INCHES / RATIO
EXIT #1: 34 0.15 227 STAIR #1: 44 0.2 220
EXIT #2: 34 0.15 227 STAIR #2: 44 0.2 220
TOTAL ALLOWED = 453 TOTAL ALLOWED = 440
OCCUPANCY LOAD CALCULATIONS:
Based upon the 2012 IBC Table 1004.1.2
Floor Area of Tenant Space: Square Footage
Total Floor Area: 22965 GSF
Vertical Penetration: 1122 USF
Mechanical/ Electrical: 337 USF
Total Usable Tenant Space: 20475 USF
Occupant Load
USF / RATIO = TOTAL OCCUPANCY
BUSINESS AREAS: 18128 100 182
CONFERENCE/ ASSEMBLY AREAS: 1729 15 116
STORAGE: 618 300 3
LIBRARY/Exercise: 0 50 0
CLASSROOM: 0 20 0
TOTAL TENANT OCCUPANCY = 301
1ST FLOOR MINIMUM NUMBER OF PLUMBING FACILITIES - Table 2902.1
TYPE OF
OCCUPANCY
OCCUPANT LOAD
(PER
MALE/FEMALE)
WATER CLOSETS
LAVATORIES
DRINKING
FOUNTAINS
(URINAL SEE SECTION
419.2)
MALE FEMALE MALE FEMALE
BUSINESS 91 2.820 2.820 2.138 2.138 0.056
1 PER 25 FOR THE FIRST 50;
1 PER 50 THEREAFTER
1 PER 40 FOR
FIRST 80; 1 PER 80
THEREAFTER
1 PER 100
STORAGE 2 0.020 0.020 0.020 0.020 0.004
1 PER 100 1 PER 100
1 PER 1000
ASSEMBLY 58 0.464 0.892 0.290 0.290 0.232
1 PER 125 1 PER 65 1 PER 200
1 PER 500
MECHANICAL 2 0.020 0.020 0.020 0.020 0.004
1 PER 100 1 PER 100
1 PER 1000
TOTAL
REQUIRED
306 3.3240 3.7523 2.4675 2.4675 0.2964
TOTAL
PROVIDED
4 4 3 4 2
*Note: Male WC count reduced/modified by Urinal Count (replacing no more than
1
2
of required WC)
215'-4"
/ 3 = 7
2'-0"
38'-3" / 3 = 13'-0" 26'-3
"
58'-5"
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
-
DOOR TYPE D3 DOOR TYPE D4
DOOR TYPE D5
DOOR TYPE D6
DOOR TYPE D7
MODERNFOLD OPERABLE PARTITIONS AT LARGE CONFERENCE - SEE SHEET A0.3 AND A0.4 FOR MORE INFORMATION
DOOR TYPE D1
DOOR TYPE D2
ALUMINUM FRAME @ JAMB
3" = 1'-0"
J1
ALUMINUM FRAME @ JAMB
3" = 1'-0"
J2
CARPET TO LINOLEUM
3" = 1'-0"
T3
CARPET TO CARPET
3" = 1'-0"
T1
CARPET TO WOOD
3" = 1'-0"
T2
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
J3
EZYJAMB FRAME @ JAMB
3" = 1'-0"
POCKET DOOR @ HEAD
3" = 1'-0"
H4
POCKET DOOR @ JAMB
3" = 1'-0"
J4
-
THERMOSTAT
LIGHT SWITCH AND PUSH BUTTON
STROBE AND SECURITY OUTLET BOXES
(MEASURE TO BOTTOM OF FIXTURE)
ALIGN
ELECTRICAL OUTLET
TELEPHONE / DATA OUTLET
CO2 SENSORS
CARD READER
COAT HOOK
A DORMA Group Company
WARNING!!!
#17G SWITCH REQUIRED!
STANDARD #17 SWITCH
WILL NOT WORK!
PLEASE CHECK SWITCH TYPE.
362SR-D
RS
PANEL LAYOUT
OP-01
LARGE CONF. ROOM
A DORMA Group Company
362SR-D
RS
PANEL LAYOUT
OP-01
LARGE CONF. ROOM
WARNING!!!
#17G SWITCH REQUIRED!
STANDARD #17 SWITCH
WILL NOT WORK!
PLEASE CHECK SWITCH TYPE.
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
G1
BUTT GLAZING JOINT
6" = 1'-0"
G2
GLAZING JAMB
6" = 1'-0"
G3
GLAZING AT HEAD
3" = 1'-0"
G4
FULL HEIGHT GLAZING AT BASE
3" = 1'-0"
NOTES:
STROBES, LIGHT SWITCHES, AND ETC. DEVICES TO ALIGN AS SHOWN.
ALL ADJACENT DEVICES TO BE GANGED UNDER THE SAME COVERPLATE WHENEVER
FEASIBLE.
GENERAL CONTRACTOR SHALL BE REQUIRED TO RELOCATE ITEMS AT NO ADDITIONAL COST
TO TENANT, ARCHITECT OR BUILDING OWNER.
ALL DEVICES AND COVERPLATES TO BE WHITE UNLESS NOTED OTHERWISE. COVERPLATES
FOR ALL DEVICES MOUNTED IN MILLWORK, TILE, OR OTHER SPECIALTY FINISHES TO BE
STAINLESS OR ALUMINUM. SEE ARCHITECTURAL AND MEP PLANS FOR FURTHER
INFORMATION.
MOUNT COAT HOOK ON WALL WHERE GLASS LITES IN DOORS PROHIBIT INSTALLATION OF
COAT HOOKS ON DOOR. LOCATE COAT HOOK IN FIELD WITH ARCHITECT.
-
A DORMA Group Company
PANEL PLAN
A DORMA Group Company
A DORMA Group Company
A DORMA Group Company
PLAN VIEW
ELEVATION
NOTES:
NOTES:
BRACKETS IN STACK:
BRACKETS IN RUN:
BRACKET REQUIREMENTS (EXCEPT AS NOTED):
HEAVY DUTY
HEAVY DUTY
HINGED JAMB HINGED JAMBHINGED CENTER PANEL
TYPE III
POCKET DOOR
OP-02
SMALL CONF ROOMS
PANEL ELEVATION - SIDE "L"
ACO
USTI-SEAL EN
CO
RE - PAIRED
PAN
EL
PANEL ELEVATION
OP-02
SMALL CONF ROOMS
SOSS HINGE PANEL JOINT JAMB
EXPANDABLE PANEL W/ JAMB
VERTICAL SECTION
ACO
USTI-SEAL EN
CO
RE - PAIRED
PAN
EL
DETAIL SHEET
OP-02
SMALL CONF ROOMS
ARCHITECT / GENERAL CONTRACTOR NOTES
ACO
USTI-SEAL EN
CO
RE - PAIRED
PAN
EL
PANEL LAYOUT
OP-02
SMALL CONF ROOMS
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
-
(REFER TO SHEET A0.2 FOR PARTITION TYPES)
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
1 DEMOLITION PLAN1/8" = 1'-0"
-
(REFER TO SHEET A0.0 FOR PROJECT SYMBOLS, ABBREVIATIONS, AND BUILDING INFORMATION)
(REFER TO SHEET A0.3 FOR PARTITION TYPES)
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
1 CONSTRUCTION PLAN1/8" = 1'-0"
-
AV
AV
BF BFBF
BF
BF BF
BF BF
BFBF
BF BF
BF
BF
BF BF
BF
AVAV
BF BF
BF BF
BF BF BF BF BF BF BF
BF
AVAV
AV
AV
AV
AV
AV
AV
AV
CR
J
CR
AV
BF
BF
APPLIANCE, EQUIP, AND PLUMBING FIXTURE SCHEDULE
SYMBOL DESCRIPTION MANUFACTURER FINISH CATALOG NUMBER REMARKS
REFRIGERATOR- FREEZER
FRIGIDAIRE
GALLERY
STAINLESS STEEL FGHF2366PF
23 CU. FT.
COUNTER DEPTH
UNDER-COUNTER REFRIGERATOR
SUMMIT
APPLIANCE
STAINLESS STEEL FF433ESSSADA ENERGY STAR
MICROWAVE GE STAINLESS STEEL PEB2060SMSS
DISHWASHER ASKO STAINLESS STEEL D5624XXLS ENERGY STAR
3/4 HP GARBAGE DISPOSAL LG
SINK ELKAY STAINLESS STEEL ELUHAD2115
FAUCET KOHLER CHROME K-6331
COFFEE MAKER -- -- PROVIDED BY TENANT
GC TO PROVIDE
WATER LIINE
ICE MAKER HOSHIZAKI STAINLESS STEEL C-101BAH-AD ENERGY STAR
WATER FILTRATION -- PROVIDED BY TENANT
GC TO PROVIDE
WATER LIINE
COPIER --
WALL MOUNTED TV -- PROVIDED BY VENDOR
AV RACK -- PROVIDED BY VENDOR
DESKTOP PRINTER -- PROVIDED BY TENANT
SECURITY CAMERA -- PROVIDED BY VENDOR
MOTORIZED PROJECTOR SCREEN -- PROVIDED BY VENDOR
CEILING MOUNTED PROJECTOR -- PROVIDED BY VENDOR
MOTORIZED MECHA-SHADE BLINDS -- PROVIDED BY VENDOR
CAMERA -- PROVIDED BY VENDOR
REMARKS/ NOTES:
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
1 POWER AND SIGNAL PLAN1/8" = 1'-0"
-
TYPE DESCRIPTION LAMP MANUFACTURER FIXTURE NAME CATALOG # NOTES
A 2X2 RECESSED LENSED T8 FOCAL POINT LUNA 2X2 FLU-22-B-2-BX40-E-120-G-PS-WH
ALL DAYLIGHTHARVESTING
FIXTURES 15'-0"FROM THE
PERIMETER TO BEDIMMABLE
B 8' LINEAR TECHZONE FOCAL POINT SEEM 4 FSM4L-FL-375LF-35K-LD1-WH-8'
C 16' LINEAR TECHZONE FOCAL POINT SEEM 4 FSM4L-FL-375LF-35K-LD1-WH-4'
D 4" ROUND DOWNLIGHT FOCAL POINT 4.5" APERTURE id FL4D-15LED-L35-RO-T-L4-RO-CDDIMMABLE ATRECEPTION
E 10' LINEAR LIGHT FOCAL POINT SEEM 4 FSM4L-FL-375LF-35K-LD1-WH-10'
F 12' LINEAR LIGHT FOCAL POINT SEEM 4 FSM4L-FL-375LF-35K-LD1-WH-6'
G UNDERCABINET LIGHT LUMENSPULSE UDERCABINETTASK LIGHTLUCRO-24V-PERPLAN-30K
-FR-WH
H PENDANT USA LUMINATION NANOLED NXTPENDANTLNRP3-9020-M2-10-10-35K
S-50-SOCC-SM-VOLTS NON-DIMMABLE
I 4" ROUND WALL WASHER ZUMTOBEL BASYS CFL 4" BR4DCFL_FIF_330_VER_13W_DL
SUBSTITUTIONS TO ANY LIGHT FIXTURES ARE SUBJECT TO THE TENANT ARCHITECT'S WRITTEN APPROVAL, AND SHOULD BE EQUAL IN APPEARANCE,FUNCTION, VOLTAGE, DIMMING, QUALITY OF CONSTRUCTION, ETC. TO THOSE LISTED IN THE SCHEDULE ABOVE. SUBSTITUTIONS TO ANY FIXTURES
WILL NOT BE CONSIDERED ANY LATER THAN 5 BUSINESS DAYS PRIOR TO THE BID DUE DATE. SEE SPECIFICATIONS FOR SUBSTITUTION PROCEDUREREQUIREMENTS. SUBSTITUTIONS WITHOUT THE TENANT ARCHITECT'S WRITTEN APPROVAL ARE NOT PERMITTED.
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
1 REFLECTED CEILING PLAN1/8" = 1'-0"
-
FINISH SCHEDULE
TAG MATERIAL MANUFACTURER MODEL NO. COLOR REMARKS NOTES
B1RUBBER BASE
B2WOOD BASE
C1CARPET
C2CARPET
C3CARPET
C4 CARPET
G1GROUT
GL1
BACK PAINTED
GLASS
P1PAINT
P2PAINT
P3 PAINT
P4PAINT
PL1
PLASTIC
LAMINATE
PL2
PLASTIC
LAMINATE
PL3
PLASTIC
LAMINATE
PL4
PLASTIC
LAMINATE
PL5
PLASTIC
LAMINATE
TP1TACK PANEL
VCT1
RESILIENT
FLOORING
VCT2
RESILIENT
FLOORING
WD1WOOD FLOOR
WF1WINDOW FILM
SEE SPECIFICATIONS SHEETS FOR ADDITIONAL MATERIALS; SPECIFICATION REQUIREMENTS; AND SUSTAINABLE REQUIREMENTS
MANUFACTURER'S REPRESENTATIVES:
CARPETING
CONTACT: Robin Wasserman - [email protected]
WOOD FLOOR
CONTACT: Hertog - [email protected]
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
1 FINISH PLAN1/8" = 1'-0"
-
ELEVATORS ELEVATION3/8" = 1'-0"1
ELEVATORS ELEVATION3/8" = 1'-0"2
ENTRANCE3/8" = 1'-0"3
ENTRANCE3/8" = 1'-0"4
FEATURE WALL / CONF. 705A-B3/8" = 1'-0"5
MEDIUM CONFERENCE3/8" = 1'-0"6
COFFEE BAR & DISPLAY 7133/8" = 1'-0"8 GRAPHIC WALL - RECEPTION3/8" = 1'-0"7
OFFICE STORE FRONT - TYP3/8" = 1'-0"9
REFRIGERATORFRIGIDAIRE - FGHN2844L F
BY GC
STAFF BREAKROOM 7173/8" = 1'-0"10
STAFF BREAKROOM 7173/8" = 1'-0"11
FEATURE WALL - LOUNGE3/8" = 1'-0"12
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
-
LARGE CONF.3/8" = 1'-0"LARGE CONF. SEE DETAILS ON A0.33/8" = 1'-0"2 BENCH - LOUNGE 7183/8" = 1'-0"1
LARGE CONF.3/8" = 1'-0"LARGE CONF. AV WALL3/8" = 1'-0"3MOTHERS ROOM 7323/8" = 1'-0"4
PRINT / COPY 7403/8" = 1'-0"5
PRINT / COPY 7553/8" = 1'-0"6
EXEC. AREA 7573/8" = 1'-0"7
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
-
1
9 SECTION AT REFRIGERATOR WITH CABINET ABOVE1 1/2" = 1'-0" 8SECTION AT MICROWAVE TOWER W/ TRASH1 1/2" = 1'-0" 6
SECTION AT UPPER CABINETS 1 1/2" = 1'-0"
COAT ROD AND SHELF DETAIL1 1/2" = 1'-0"14
7 UNDERCOUNTER ADA REFRIDGERATOR DETAIL1 1/2" = 1'-0"
13 ADJUSTABLE KV SHELVING TYP. 507C, 526B, 526C1 1/2" = 1'-0"
2 SECTION AT BASE CABINET WITH PULLOUT1 1/2" = 1'-0"3 SECTION AT SINK BASE CABINET1 1/2" = 1'-0"SECTION AT COUNTER WITH APPLIANCE1 1/2" = 1'-0"45
SECTION AT DRAWER CABINET1 1/2" = 1'-0"
SECTION AT BASE CABINET WITH DOOR1 1/2" = 1'-0"
10 SECTION AT REFRIGERATOR WITH CABINET ABOVE1 1/2" = 1'-0"
12 SECTION AT CONF. ROOM AV CABINET1 1/2" = 1'-0" 11BASE CABINET DRAWER W/PLAM TOP DETAIL1 1/2" = 1'-0"
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
-
1 ACT TO GYP CEILING DETAIL3" = 1'-0"2GYP BULKHEAD TO ACT - CONFERENCE DETAIL3" = 1'-0"3
GYP. SOFFIT TO GYP. CEILING DETAIL3" = 1'-0"4
SECTION DETAIL AT MECHANICAL SHADE: CONFERENCE ROOM3" = 1'-0"
6 GYP TO GYP3" = 1'-0"7DETAIL AT ACT CEILING AND EXPOSED CEILING3" = 1'-0"9
DETAIL AT TECHZONE CEILING3" = 1'-0" 8
DETAIL AT GYP CEILING AND EXPOSED CEILING3" = 1'-0"
5 PANTRY BANQUETTE DETAIL1 1/2" = 1'-0"
10 DETAIL AT MULLION3" = 1'-0"12DETAIL SECTION VIEW @ TYP. SHELF ASSEMBLY1 1/2" = 1'-0" 11
SHELF - SECTION VIEW1 1/2" = 1'-0"
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
MEP Engineer:
1412 E
ye S
treet, N
W W
ashington, D
C 20005
Tel 2
02.621.1000
Fax 2
02.621.1001
Web
w
ww
.otj.com
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
GPI Greenman-Pedersen, Inc.530 Gaither Road, Suite 100Rockville, MD 20850Ph: 240.268.1820Fax: 240.268.1821
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
1412
Eye
Stre
et,N
WW
ashi
ngto
n,D
C20
005
Tel2
02.6
21.1
000
Fax2
02.6
21.1
001
Web
ww
w.o
tj.co
m
2014 OTJ Architects, Inc.
1111 19th STREET7th FLOORWASHINGTON, D.C. 20036
-
C
B
A
1 2 3 4
NEW FRAMEDGLASS OPERABLEPARTITION
COLUMNCOLUMN
COLUMN COLUMN
SMALLCONFERENCE
PARTITIONSTACK AREA
1'-6"
3'-0"
TYP.
(U.N
.O.)
INDICATES NEWHANGER RODS *TYP,)
6"MIN.
INDICATES EXISTINGCONC. COL. (TYP.)
1'-6"3'-0"3'-0"3'-0"VIF.6"6"
INDICATESNEW HANGERRODS (TYP.)NEW OPERABLE
PARTITION
EXISTING PT BEAM(SEE NOTES)
1'-6"
L2x2x14 AT EACHEND OF CONT. PL
PARTITIONSTACK AREA
1'-6"
WIDTH OF EXISTP.T. BEAM (SEE"POST INSTALLEDANCHOR" NOTE-1THIS SHEET )
SMALLCONFERENCE
LARGECONFERENCE LOUNGE
NEW OPERABLEPARTITION
SIM.
719 718
706-A
706-B
NTS2
S1.0SECTION - FOLDING PARTITION SUPPORT
L4x4x14x0'-8"
L2x2x14 BRACE, SEE PLAN
PL 5 8"x11" WIDECONT, SEE PLAN
B/ (E) 8TH FLCONC SLAB
A325 3 4PL 5/8"x4x0'-8" LG
VERI
FYw/
ARC
H
A325 3 4(UNO ON PLAN)
CEILING MOUNT KIT. HGR BY MFRCOORD EL w/ ARCH
11
6" MIN COOKDINHTETHIS DIMENSIONw/ ATCH
SCALE AT FULL SIZE 3 4"=1'-0"
1' 0 1' 2' 3'3
S1.0SECTION
(2) HILTI KWIK BOLT TZ CS1
21
4" EMBED
L4x4x14x0'-8"
L2x2x14 BRACE,SEE PLAN
6"MIN
B/ (E) 8TH FLCONC SLAB
A325 3 4
8"MIN
A325 3 4
(2) 3 8COUPLED w/ 12BOLTS TZ CS w/ 3 14"EMBED, TYP. SEE PLANFOR SPCG
CEILING MOUNT KIT. HGRBY MFR COORD EL w/ ARCH
11
TYP
PL 5 8"x11" WIDECONT, SEE PLAN
L2x2x14 BRACE,SEE PLAN
S1.0
NEW FOLDINGPARTITIONSUPPORT
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
R4D PARTITION1111 19th Street, NWSte. 200Washington, DC 20036
14
12
E
ye
S
tre
et, N
W W
ash
in
gto
n, D
C 2
00
05
Tel 2
02
.6
21
.1
00
0Fa
x 20
2.6
21
.1
00
1W
eb w
ww
.o
tj.co
m
MEP Engineer:GHT LIMITED1110 N GLEBE RD, #300ARLINGTON, VA 22201Ph: 703.243.1200
SCALE AT FULL SIZE 14"=1'-0"
4' 0 4' 8'1
S1.0PARTIAL 7TH FLOOR PLAN
GENERAL1. The applicable building code is 2012 IBC.2. Contractor is solely responsible for means and methods during the course of the work. Do not
damage or endanger the structural integrity of the Work or Existing Structure.3. Use architectural drawings and drawings of other trades in conjunction with the structural drawings
to properly perform the work.4. Contractor is responsible for coordinating between trades.5. Do not scale drawings.6. Field dimensions
A. Verify all dimensions and accurately locate all existing columns, beams and other structuralmembers before beginning work or preparing shop drawings.
EXISTING BUILDING/STRUCTURE NOTES11. Utmost care shall be exercised at all times when working on existing structural members to avoid
impairing the carrying capacity of the existing structure.A. Should the Architect or Engineer determine that the carrying capacity of the existing structure
has been impaired by, or as a result of, the operations of the Contractor, or is otherwise not inconformance with the contract documents, appropriate remedial work shall be required.
B. Any damage resulting from the operations of the Contractor shall be repaired as directed by theOwner's representative at no additional cost to the Owner.
2. Notify Architect and Engineer before cutting or removal of any part of the existing structure notindicated to be modified or demolished.
STRUCTURAL STEEL1.
2. Structural steel design is based on the Allowable Strength Design (ASD) and Load and ResistanceFactor Design (LRFD) methodology. All loads shown on drawings are unfactored (service) loads,unless noted otherwise.
3. The structural steel detailer shall develop all elevations, plans, and sections without reproducingsame from the design drawings. Detailer shall adequately cross reference the structural drawings tothe satisfaction of the engineer. All shop drawings shall be submitted for review and reviewcomments incorporated prior to fabrication.
4. Materials shall conform to the following:ASTM A36 Rods, angles and platesASTM A992 W and WT shapesASTM A325 High strength boltsAWS A5.1 E70XX Welding electrodesASTM A36 All other structural shapes
5. Connections:A. Provide minimum weld sizes in accordance with AISC 360 Specification for Structural Steel
Buildings.B. Electrodes shall be suited to grade and weldability of base metal.C. Use AWS certified welders for structural welding.D. Field cutting or burning of structural steel is prohibited.E. See architectural drawings for additional steel not shown on structural drawings.F. Where plates, angles or other miscellaneous members require welding (either field or shop) or
slip-critical connections, mask connection surfaces prior to shop priming and touch-up withprimer after completing connection.
G. Provide adjustable connections for all members designated as AESS to facilitate adjustment toachieve the specified tolerance.
POST-INSTALLED ANCHORS1. Utmost care shall be exercised when drilling for the anchor installation to avoid impairing the
tendons or any other reinforcement of the existing concrete slab. Do not drill the existing concretebeam for any reason. Contractor shall conduct non-destructive testing of slab affected by the newwork, to locate such reinforcement prior to drilling for anchor installation or performing any coredrilling. Existing reinforcement shall not be cut, notched or otherwise compromised during thecourse of the work.
2. Contractor shall be solely responsible for means and methods during the course of the work. Do notdamage or endanger the structural integrity of the existing structure.
3. Drill and install post-installed anchors according to manufacturer's printed installation instructionsand per manufacturer's on-site training.
4. All post-installed anchors shall meet ICC-es compliance for each type of application.5. Expansion anchors in concrete shall be hilti kwik bolt TZ, or approved equal.6. Provide standard AISC holes in all steel members receiving post-installed anchors. If oversized
holes are provided to ease installation of the anchors, a plate washer (1/4"x2"x2") with an AISCstandard hole shall be installed and 1/8" fillet welded (all around) to the member.
7. Testing: 10% of each type and size of drilled-in anchor shall be proof loaded by the independenttesting laboratory. Adhesive anchors and capsule anchors shall not be torque tested unlessotherwise directed by the engineer. If any of the tested anchors fail to achieve the specified torqueor proof load within the limits as defined in the drawings, all anchors of the same diameter and typeas the failed anchors shall be tested, unless otherwise instructed by the engineer.A. Perform tension testing in accordance with ASTM E488.B. Apply torque with a calibrated torque wrench.
-
GENERAL NOTES:
1. ANALYSIS PROCEDURE PER ASCE 7-10 APPENDIX 11B.3, SEISMIC REQUIREMENTS FOR NEW STRUCTURES DOES NOT APPLY
*PER GENERAL NOTES ON SHEET S1AND PLAN NOTES ON SHEETS S7FROM STRUCTURAL DRAWINGSSUBMISSION "CONSTRUCTION -MKJ" DATED APRIL 13, 1972 BYMICHAEL K. JOHNS
2. THE USE FOR THIS SPACE IS EXISTINGOFFICE. PER CURRENT ASCE 7, THE OFFICE LIVELOAD IS 50 PSF. WE HAVE REVIEWED THE EXISTINGFRAMING BASED ON THE DRAWINGS PRODUCED BYMICHAEL K. JOHNS DATED APRIL 13, 1972 AND CERTIFY THAT THE EXISTING FRAMING TO BE SUFFICIENT FOR PROPOSED WORK.
C 2015 KEAST & HOOD CO.
STRUCTURAL TESTING & INSPECTION PROGRAM NOTES:
1. THE INTENTION OF THIS TABLE IS TO IDENTIFY THE CONSTRUCTION REQUIRING SPECIAL INSPECTION AS REQUIRED BY THE 2012INTERNATIONAL BUILDING CODE (IBC). EACH SPECIAL INSPECTOR IS RESPONSIBLE FOR JOB SPECIFIC ITEMS AS DEFINED INCHAPTER 17 OF THE IBC (AND IN ACCORDANCE WITH THE SPECIFICATIONS).
2. INSPECTIONS OF FABRICATORS IS NOT REQUIRED IF THE FABRICATOR IS APPROVED IN ACCORDANCE TO IBC SECTION 1704.2.5AND CERTIFIES COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS.
3. THE ITEMS CHECKED WITH AN "X" SHALL BE INSPECTED IN ACCORDANCE WITH IBC CHAPTER 17 BY A CERTIFIED SPECIALINSPECTOR FROM AN ESTABLISHED TESTING AGENCY. FOR MATERIAL SAMPLING AND TESTING REQUIREMENTS, REFER TO THEMATERIAL SAMPLING AND TESTING SECTION OF THE PROJECT SPECIFICATIONS AND THE GENERAL NOTES. THE TESTINGAGENCY SHALL SEND COPIES OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS DIRECTLY TO THE ENGINEER,CONTRACTOR AND BUILDING OFFICIAL. ANY CONSTRUCTION WHICH FAILS TO MEET THE PROJECT SPECIFICATIONS AND IBCREQUIREMENTS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION AND THEENGINEER IF UNCORRECTED. SPECIAL INSPECTION TESTING REQUIREMENTS APPLY EQUALLY TO ALL BIDDER DESIGNEDCOMPONENTS.
4. FREQUENCY OF INSPECTIONS
A. CONTINUOUS SPECIAL INSPECTION MEANS THAT THE SPECIAL INSPECTOR SHALL BE ON SITE AT ALL TIMES OBSERVING THEWORK REQUIRING SPECIAL INSPECTION. FOR STRUCTURAL STEEL, INSPECTION TASK MUST BE COMPLETED FOR EACHMEMBER OR CONNECTION.
B. PERIODIC SPECIAL INSPECTION MEANS THAT THE SPECIAL INSPECTOR IS ON THE SITE AT THE TIME INTERVALS NECESSARYTO CONFIRM THAT ALL WORK REQUIRING SPECIAL INSPECTIONS IS IN COMPLIANCE. OPERATIONS NEED NOT BE DELAYEDPENDING THESE INSPECTIONS.
5. ALL WELDS SHALL BE VISUALLY INSPECTED BY AN AWS CERTIFIED WELDING INSPECTOR. ALL PROVISIONS OF AWS D1.1/D1.1M"STRUCTURAL WELDING CODE - STEEL" SHALL APPLY TO STEEL CONSTRUCTION. NON-DESTRUCTIVE TESTING OF WELDEDJOINTS SHALL BE IN ACCORDANCE WITH AISC 360 SECTION N5.
SPECIAL INSPECTIONS PROGRAM - STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC2012 IBC
REFERENCESECTION
REFERENCESTANDARD COMMENTS
GENERAL INSPECTION OF FABRICATORS X 1704.2.5 SEE NOTE 2.
SPECIAL INSPECTIONS PROGRAM - STRUCTURAL STEEL (AISC 360 CHAPTER N)
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC2012 IBC
REFERENCESECTION
AISC 360REFERENCE COMMENTS
GENERAL INSPECTION OF FABRICATORS X 1704.2.5 SEE NOTE 2.
DOCUMENT ACCEPTANCE OR REJECTION OF INSPECTED ITEMS X TABLES N5.4-3,N5.6-3, N6.1
ANCHOR RODS,EMBEDMENTS,ANDPOST-INSTALLEDANCHORS
PLACEMENT OF ANCHOR RODS AND OTHER EMBEDMENTSSUPPORTING STRUCTURAL STEEL SECTION N5.7
VERIFY DIAMETER, GRADE, TYPE AND LENGTH OF THE ANCHOR RODOR EMBEDDED ITEM SECTION N5.7
VERIFY EXTENT OR DEPTH OF EMBEDMENT INTO CONCRETE PRIOR TOCONCRETE PLACEMENT SECTION N5.7
INSPECTION OFSTEEL FRAMEJOINT DETAILSFOR COMPLIANCEw/CONSTRUCTIONDOCUMENTS
DETAILS SUCH AS BRACING & STIFFENING X SECTION N6
MEMBER LOCATIONS X SECTION N6
APPLICATION OF JOINT DETAILS AT EACH CONNECTION X SECTION N6
PRIOR TOWELDING WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE X TABLE N5.4-1
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLESAVAILABLE X TABLE N5.4-1
MATERIAL IDENTIFICATION (TYPE/GRADE) X TABLE N5.4-1
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY) - JOINT PREPARATION - DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) - CLEANLINESS (CONDITION OF STEEL SURFACES) - TACKING (TACK WELD QUALITY AND LOCATION) - BACKING TYPE AND FIT (IF APPLICABLE)
X TABLE N5.4-1
CONFIGURATION AND FINISH OF ACCESS HOLES X TABLE N5.4-1
FIT-UP OF FILLET WELDS - DIMENSIONS (ALIGNMENT, GAPS AT ROOT) - CLEANLINESS (CONDITION OF STEEL SURFACES) - TACKING (TACK WELD QUALITY AND LOCATION)
X TABLE N5.4-1
DURING WELDINGUSE OF QUALIFIED WELDERS X TABLE N5.4-2
INSPECTOR TO OBTAIN COPY OFWELDER CERTIFICATIONS PRIOR TOSTART OF WORK
CONTROL AND HANDLING OF WELDING CONSUMABLES - PACKAGING - EXPOSURE CONTROL
X TABLE N5.4-2
NO WELDING OVER CRACKED TACK WELDS X TABLE N5.4-2
ENVIRONMENTAL CONDITIONS - WIND SPEED WITHIN LIMITS - PRECIPITATION AND TEMPERATURE
X TABLE N5.4-2
WPS FOLLOWED - SETTINGS ON WELDING EQUIPMENT - TRAVEL SPEED - SELECTED WELDING MATERIALS - SHIELDING GAS TYPE/FLOW RATE - PREHEAT APPLIED - INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.) - PROPER POSITION (F, V, H, OH)
X TABLE N5.4-2
WELDING TECHNIQUES - INTERPASS AND FINAL CLEANING - EACH PASS WITHIN PROFILE LIMITATIONS - EACH PASS MEETS QUALITY REQUIREMENTS
X TABLE N5.4-2
AFTER WELDING WELDS CLEANED X TABLE N5.4-3
SIZE, LENGTH AND LOCATION OF WELDS X TABLE N5.4-3WELDS MEET VISUAL ACCEPTANCE CRITERIA - CRACK PROHIBITION - WELD/BASE-METAL FUSION - CRATER CROSS SECTION - WELD PROFILES - WELD SIZE - UNDERCUT - POROSITY
X TABLE N5.4-3
ARC STRIKES X TABLE N5.4-3k-AREA INSPECTION AT DOUBLER PLATES, CONTINUITY PLATES, ORSTIFFENER PLATES X TABLE N5.4-3
BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) X TABLE N5.4-3
REPAIR ACTIVITIES X TABLE N5.4-3
PRIOR TOBOLTING
MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENERMATERIALS X TABLE N5.6-1
FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS X TABLE N5.6-1
PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE,BOLT LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE) X TABLE N5.6-1
PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL X TABLE N5.6-1
CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYINGSURFACE CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEETAPPLICABLE REQUIREMENTS
X TABLE N5.6-1
PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATIONPERSONNEL OBSERVED AND DOCUMENTED FOR FASTENERASSEMBLIES AND METHODS USED
X TABLE N5.6-1
PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS ANDOTHER FASTENER COMPONENTS X TABLE N5.6-1
DURING BOLTINGFASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALLHOLES AND WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED X TABLE N5.6-2
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THEPRETENSIONING OPERATION X TABLE N5.6-2
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTEDFROM ROTATING X TABLE N5.6-2
FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSCSPECIFICATION, PROGRESSING SYSTEMATICALLY FROM THE MOSTRIGID POINT TOWARD THE FREE EDGES
X TABLE N5.6-2
3. SUPPORT HANGER SYSTEM DESIGNED TO SUPPORT 12" THICK GLASS PARTITION WALL AND GLASS DOOR SYSTEM FOR BOTH A OPENED AND STACKED CONDITION. L/360 DEFLECTION LIMITATION WAS USED IN DESIGN OF HANGER SUPPORT SYSTEM.
Drawing Scale
ISSUES
SEAL / SIGNATURE
CLIENT
CONSULTANTS
SHEET NAME
FILE INFORMATION
Project No:Drawn By:Checked By:Date:
R4D PARTITION1111 19th Street, NWSte. 200Washington, DC 20036
14
12
E
ye
S
tre
et, N
W W
ash
in
gto
n, D
C 2
00
05
Tel 2
02
.6
21
.1
00
0Fa
x 20
2.6
21
.1
00
1W
eb w
ww
.o
tj.co
m
MEP Engineer:GHT LIMITED1110 N GLEBE RD, #300ARLINGTON, VA 22201Ph: 703.243.1200
S2.0
DESIGN CRITERIA& SPECIAL
INSPECTIONSPROGRAM
20150330_Results 4 Develpment - Permit Arch Set2015 0330 Results for Development Mechanical - Peer Review201504400M0.030x42 Plan
201504400M1.030x42 Plan
201504400M2.030x42 Plan
201504400M3.030x42 Plan
2015 0330 Results for Development Plumbing - Peer Review201504400P0.030x42 Plan
201504400P2.030x42 Plan
2015 0330 Results for Development Electrical - Peer Review201504400E0.030x42 Plan
201504400E1.030x42 Plan
201504400E2.030x42 Plan
201504400E3.030x42 Plan
201504400E4.030x42 Plan
201504400E5.030x42 Plan
201504400E6.030x42 Plan
201504400E7.030x42 Plan
S1.0S2.0