2015feb_028-039_olesen_pt-1
DESCRIPTION
ashareTRANSCRIPT
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 1/10
A S H RA E J O U RN A L a s h r a e . or g F E B R U A R Y 2 0 1 52 8
TECHNICAL FEATURE | Fundamentals at Work
Kwang Woo Kim, Arch.D., is a professor of architecture at Seoul National University, Seoul, South Korea, and president of Architectural Institute of Korea. B jarne W. Olesen, Ph.D., isdirector, professor, International Centre for Indoor Environment and Energy, Technical University of Denmark in Lyngby, Denmark, and vice president of ASHRAE.
BY KWANG WOO KIM, ARCH.D., MEMBER ASH RAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE
This two-part article describes basic knowledge of
radiant heating and cooling systems to give a principle
understanding of the design and operation of this
advantageous system including comfort, system load,
heating/cooling capacity, installation and application ofthe system with examples.
Embedded Radiant Heating and Cooling SystemEmbedded radiant systems are used in all types of
buildings. Due to the large surfaces needed for heat
transfer, the systems work with low water tempera-
ture for heating and high water temperature for
cooling. The water temperatures are operated at very
close to room temperature, and, depending on the
position of the piping, the system can take advan-
tage of the thermal storage capacity of the building
structure. Figure 1 shows the available types of embedded
hydronic radiant systems. The embedded radiant sys-
tems, except thermally active building systems (TABS),
are usually insulated from the main building structure
(floor, wall and ceiling), and the actual operation mode
(heating/cooling) of the systems depends on the heat
transfer between the water and the space.
This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/ordistributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 2/10
F E B R U A R Y 2 0 1 5 a s h r a e . or g A S H RA E J O U RN A L 2 9
The radiant system is defined as a system where at
least 50% of the heat transfer takes place by radiation.
Figure 2 shows the total heat transfer coefficients between
a heated-cooled surface and a room. The radiant heat
transfer is, in all cases, 5.5 W/m²·K (0.97 Btu/h·ft²·°F). The convective heat transfer then varies between 0.5
and 5.5 W/m²·K (0.09 and 0.97 Btu/h·ft²·°F), depend-
ing on the surface type and on heating or cooling mode.
This shows that the radiant heat transfer varies between
50% and 90% of the total heat transfer. The heat trans-
fer coefficient for cold ceiling and warm floor will vary
between 9 and 11 W/m²·K (1.59 and 1.94 Btu/h·ft²·°F),
depending on the temperature difference between sur-
face and room.
The radiant heat transfer does not directly affect the
room air temperature. The long wave radiation heats or
cools the surrounding surfaces, which then indirectly
heats or cools the room air.
Standard for Radiant Heating and Cooling Systems As the heat transfer process between water and room
is quite different from conventional air systems, an
international standard on radiant heating and cooling
systems has been developed based on system design and
existing standards from different countries and was
published in 2012.ISO 11855, Building Environment Design—Design,
Dimensioning, Installation and Control of the Embedded Radiant
Heating And Cooling Systems,6–11
consists of six parts:
Part 1: Definition, symbols, and comfort criteria;
Part 2: Determination of the design and heating and
cooling capacity;
Part 3: Design and dimensioning;
Part 4: Dimensioning and calculation of the dynamic
heating and cooling capacity of thermo active building
systems;
Part 5: Installation; and
Part 6: Control.
ComfortOccupants’ thermal comfort is the primary objec-
tive in radiantly heated or cooled space. To provide an
acceptable thermal environment for the occupants, the
requirements for general thermal comfort shall be taken
into account by using the index of predicted mean vote
(PMV) or operative temperature, t o, and local thermal
comfort, e.g., surface temperature, vertical air tempera-
ture differences, radiant temperature asymmetry, draft,
etc.For radiant or convective systems the comfort require-
ments are the same when expressed by the PMV-PPD
index (–0.5 < PMV <+0.5) or expressed as an operative
temperature range corresponding to: 20°C to 24°C (68°F
to 75.2°F) for heating season and 23°C to 26°C (73.4°F
to 78.8°F) for cooling season in spaces with sedentary
activity.12,13
The operative temperature14,15
is the combined influ-
ence of air temperature and mean radiant temperature.
The operative temperature can be approximated with
FIGURE 1 Examples of water based radiant systems.3
Floor Ceiling Wall TABS
FIGURE 2 Heat transfer coefficients between heated/cooled surface and room.4,5
Btu/h·ft2·°F
2.03
1.85
1.671.50
1.32
1.14
0.97Heating
Cooling FloorCeiling
Wall
1.94
1.23
1.94
1.411.06
1.41
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 3/10
A S H RA E J O U RN A L a s h r a e . or g F E B R U A R Y 2 0 1 53 0
the simple average of air and mean radiant temperature
in spaces with low air velocities (<0.2 m/s [39 fpm]), or
with a small difference between mean radiant tempera-
ture and air temperature (<4K, 7°F).
The operative temperature (t o) is in spaces with low air
velocities determined from the following expression:
t o = 0.5(t a + t r )
Where
t a
= air temperature °F (°C)
t r = mean radiant temperature °F (°C)
The occupants can maintain the same comfort level
with a lower air temperature in a radiantly heated
space, and the same comfort level with a higher air
temperature in a radiantly cooled space in comparison
to convective heating and cooling systems. Therefore,
reduction of the energy loss due to ventilation and infil-
tration is possible while maintaining the same comfort
level compared with conventional heating and cooling
systems.
As the reference temperature for the transmission heatloss is closer to the operative temperature than to the air
temperature, there will not be any significant difference
of transmission heat loss between radiantly heated or
cooled spaces.
Interestingly enough, the difference between air- and
mean radiant temperature is normally smaller in radi-
antly heated or cooled spaces. This is due to the fact
that in winter the windows will have a lower surface
temperature than the air temperature, which is com-
pensated by a higher surface temperature of the radiant
system and vice-versa in summer. With air systems the
colder window temperatures in winter will be com-
pensated by a higher air temperature, which will result
in an air temperature higher than the mean radiant
temperature.For rooms with sedentary and/or standing occupants,
the maximum permissible floor temperature for heating
is 29°C (84°F), and the minimum floor temperature for
cooling is 19°C (66°F). For spaces with occupants in bare
feet (bathrooms, swimming pools, dressing rooms, etc.),
the optimal floor temperature for comfort also depends
on the floor covering material.
For wall heating, a maximum surface temperature
range of 35°C to 45°C (95°F to 113°F) is recommended.
The maximum may depend on whether the occupants
FIGURE 3 Local thermal discomfort caused by vertical air temperature difference.6
0°F 3.6°F 7.2°F 10.8°F 14.4°F 18°F
80%60%
40%
20%
10%8%6%
4%
2%
1%
Y
X
X = Air Temperature Difference Between Head and Feet Y = Dissatisfied
0°F 9°F 18°F 27°F 36°F 45°F 54°F 63°FY
1 2
3 4
X
X = Radiant Temperature Asymmetry Y = Dissatisfied 1 = Warm Ceiling
2 = Cool Wall 3 = Cool Ceiling 4 = Warm Wall
FIGURE 4 Local thermal discomfort caused by radiant temperature asymmetry.6
80%60%
40%
20%
10%8%6%
4%
2%
1%
100
80
60
40
20
0
–1
–0.3
–0.2
–0.1
0.0
0.1
0.2
0.3
1.0
A c c e p t a b i l i t y
D i s s a t i s fi e d ( % )
20 30 40 50 60 70 80
Relative Humidity (%)
50.4°F
41.4°F
32.4°F
FIGURE 5 Human satisfaction with the IAQ depending on relative humidity and airtemperature.3
TECHNICAL FEATURE | Fundamentals a t Work
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 4/10
Adverti sement formerly in this space.
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 5/10
A S H RA E J O U RN A L a s h r a e . or g F E B R U A R Y 2 0 1 53 2
may easily get contact with the surface or whether occu-
pants are more sensitive persons such as children or the
elderly. Wall cooling is limited by the risk of condensa-tion and the development of a downdraft of cold air.
A vertical air temperature difference between head
and feet of less than 3K (5.4°F) is recommended. Most
heating and cooling systems will, in modern buildings,
normally have vertical air temperature differences
within this limit. In high ceiling spaces it is, for energy
reasons, important to avoid large vertical temperature
differences. This is why floor heating is especially rec-
ommended here (atrium, foyer, industrial space, etc.)
People are very sensitive to radiant temperature
asymmetry from a cold window and a warm ceiling.
Occupants may feel discomfort caused by a temperature
asymmetry of 5K (9°F) for warm ceiling, and a tempera-
ture asymmetry of 10K (18°F) for walls or windows ( Figure
4, Page 30). The critical factor at cold surfaces (windows,
walls) is, however, the risk of downdraft that may cause
discomfort.
The radiant heating and cooling system operates with
less dust transportation, as it is not a convective system,
and does not require the cleaning of heat emitters or
filters. With the radiant floor heating systems, carpetsare not necessary. Thus, the possible allergen sources of
emitting pollutants and a sink source can be eliminated.
The higher mean radiant temperature in radiantly
heated space means that the air temperature can be
kept lower than in convectively heated space. This has
the advantage that the relative humidity in winter may
be a little higher. Studies show that lower air tempera-
ture and lower air humidity have a significant effect
on perceived air quality ( Figure 5 3
). Due to the higher
heating surface temperatures, there is less chance
for condensation and mold growth. The relationship
between air temperature and humidity is one of impor-
tant comfort issues in radiantly cooled spaces. Wherethe humidity is not controlled by the air system, as in
naturally ventilated spaces, radiant cooling capacity will
be limited to avoid the forming of condensation on the
radiant surface (see section on control in Part 2 of this
article in next month’s Journal).
With air heating or cooling system more air has to
be circulated than the amount needed for providing
acceptable air quality. This may increase the noise level
in a space and also increase the risk for complaints
related to draft. When a part of sensible heating and/
or cooling load is taken care of by a water-based radi-
ant system, the ventilation system may have reduced
duct size and lower air velocity because it will only
treat the air renewal for required IAQ and, if needed,
dehumidification.
In buildings with thermally active building systems
(TABS) you will normally prefer to have free access to
the concrete surface to increase the heat transfer with
the room. This may require special solutions for the
acoustics. Acoustic panels on the ceilings and suspended
ceiling panels will reduce heat transfer. It will be moreefficient to hang down vertical acoustical panels.
16
The
application of the raised floor or the thermal/acoustic
insulation in floor will decrease the upper heat flow
from the TABS, which normally is much less than the
heat exchange from the ceiling.
Load Calculations and Heating/Cooling Capacity At a given average surface temperature and indoor
temperature (operative temperature, t o), a surface
will deliver the same amount of heat flux to a space
FIGURE 6 Embedded radiant system types.7
Type A and C Type B Type D Type G
1 = Floor Covering 2 = Weight Bearing and Thermal Diffusion Layer (Cement Screed, Anhydrite Screed, Asphalt Screed or Wood)
3 = Thermal Insulation 4 = Structural Base 5 = Heat Diffusion Device
1
2
3
4
1
2
3
4
5 Flooring Material
Joist
1
2
3
4
TECHNICAL FEATURE | Fundamentals a t Work
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 6/10
Adverti sement formerly in this space.
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 7/10
A S H RA E J O U RN A L a s h r a e . or g F E B R U A R Y 2 0 1 53 4
regardless of the embedded radiant system type.
Therefore, it is possible to establish basic formulas or
characteristic curves of heating and cooling for the all
heating and cooling surfaces independent of the embed-
ded system types. The heat transfer between the surface
and the space do, however, depend on the different sur-
face heat transfer coefficients ( Figure 2).
The heat transfer between the water and surface is differ-
ent for each system configuration. Therefore, the estima-
tion of heating/cooling capacity of systems is very important
for the proper system design. Two calculation methods
included in ISO 11855-27
are simplified calculation meth-
ods depending on the type of system, and finite element
method (FEM) or finite difference method (FDM). Given
system types are Types A and C, Type B, Types D and G.
The simplified calculation methods are specific for the
given system types within boundary conditions. Based
on the calculated average surface temperature at givenheat transfer medium temperature and space tempera-
ture, it is possible to determine the steady state heating
and cooling capacity. In case a simplified calculation
method is not applicable for the considered system,
either two- or three-dimensional finite element or finite
difference method, or laboratory testing may be applied.
The temperature distribution in floor cooling system,
calculated using FEM software, is shown in Figure 7.
Heat exchange coefficient is the parameter that
determines the amount of heat transferred between
surface and the space in relation with the system type.
Acceptable surface temperature is determined based on
comfort considerations and the risk of condensation.
Heating/cooling capacity of the systems is:7
Floor heating and ceiling cooling, q = 8.92 (t o − t S,m )1.1;
Wall heating and wall cooling, q = 8 (|t o − t S,m |);
Ceiling heating, q = 6 (|t o − t S,m |);
Floor cooling, q = 7 (|t o − t S,m |).
Where
t o (°C) is the operative temperature in the space
t S,m (°C) is the average surface temperature
The ceiling has the capacity up to 100 W/m² (31.7
Btu/h·ft²) for sensible cooling and 40 to 50 W/m² (12.7
to 15.9 Btu/h·ft²) for heating. The floor has the capac-
ity up to 100 W/m² (31.7 Btu/h·ft²) for heating and
40 W/m² (12.7 Btu/h·ft²) for sensible cooling. Whendirect sunlight strikes on the floor, the sensible cooling
capacity of the floor may be more than 100 W/m² (31.7
Btu/h·ft²). This is why floor cooling is often adopted in
spaces with large window area like airports, atria and
lobby halls.
For the thermally active building systems (TABS), the
steady-state heating/cooling capacity calculation is not
sufficient, and analysis with a dynamic computational
program that can predict the dynamic behavior and
performance of the system together with the building
FIGURE 7 Temperature distribution and cooling effect up and down for a floor system calculated by FEM software for a floor cooling system with 19°C (66.2°F) water tem-peratures and 26°C (78.8°F) room temperature.
Structure S4
Materialq = 0 q = 0
qup =112.6 Btu/h
qdown =22.3 Btu/h
Temperature (°F)
78.8
77
75.2
73.4
71.6
69.8
68
66.2
64.4
Floor Coveringλ = 0.08 Btu·in/h·ft2·°Fs = 0.6 in.
Screedλ = 0.40 Btu·in/h·ft2·°Fs = 2.4 in.
Thermal Insulationλ = 0.01 Btu·in/h·ft2·°Fs = 1.2 in.
Concreteλ = 0.70 Btu·in/h·ft2·°Fs = 7.1 in.
TECHNICAL FEATURE | Fundamentals a t Work
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 8/10
F E B R U A R Y 2 0 1 5 a s h r a e . or g A S H RA E J O U RN A L 3 5
is needed.17,1
Several programs exist such
Energy Plus, TRNSYS and IDA-ICE.
One of the main advantages of TABS are
reduced building height. For each story, you
may save 500 to 600 mm (1.8 to 2 ft) of build-
ing height, which for a seven-story build-
ing amounts to an entire story and related
building materials. As no suspended ceiling
is needed to cover air ducts, significant sav-
ing of building materials is possible. It is also
possible to operate the system at 30% to 50%
lowered peak loads allowing reduced plants’
sizes and possible operation of heating/cool-
ing systems with temperatures close to room
temperature, allowing increased plants’ effi-
ciency and use of renewable energy sources(ground heat exchanger, evaporative cool-
ing, etc.).
over 24 hours and by an air system normally over 8 to
10 hours. After the water circulation in the slab may
have been stopped during the day and will be started
again in the evening, there will be a high peak cool-
ing load between the heated slab and the cool water;
but this should not be used to size the chiller as it is a
very short peak and the capacity needed will after some
minutes decrease significantly. It can be somewhat com-
plicated to calculate the needed capacity on the water
side (chiller, heat pump); therefore, a dynamic building
simulation is recommended.
System DesignRadiant system design requires determining heat-
ing/cooling surface area, type, pipe size, pipe spacing,
supply temperature of the heat transfer medium, and
design medium flow rate. The design steps are as follows
(ISO 11855-38
):
1. Calculate the design heating and sensible cooling
load in accordance with a standard for heating and cool-
ing load calculation based on operative temperature.2. Determine the minimum supply air quantity
needed for ventilation and dehumidification. In cooling
application, calculate latent cooling and sensible cooling
available from supply air. Determine remaining sen-
sible cooling load to be satisfied by radiant system. Also,
designate or calculate the relative humidity and dew
point, because the cooling system should operate within
a surface temperature range above the dew point, which
shall be specified depending on the respective climate
conditions in the country. By limiting supply water
Thermally active building systems exploit the high
thermal inertia of the slab to perform peak shaving. The
peak shaving reduces the peak in the required cooling
power,7 so that it is possible to cool the structures of the
building during a period in which the occupants are
absent (during nighttime in office premises). This way,
the cooling can be delayed and lower nighttime electric-
ity rates can be used. At the same time, a reduction in
the size of heating/cooling system components (includ-
ing the chiller) is possible.
During daytime, the heat is extracted from the occu-
pied space by the ventilation system and stored in the
concrete slabs. Then, during nighttime, the level of ven-
tilation is reduced and the circulation of cool water in
the slabs will remove the stored heat.
For the conventional air system, the space load will
be the instantaneous system load, because all the heat
delivered to the space is immediately removed by the
air system. For the radiant system and especially fora TABS the calculated design space load should not be
used as system load. For both an air system and a TABS,
it is important that the room load over a 24-hour day
(Curve 1 in Figure 8) is removed within the 24 hours, else
the room will get warmer and warmer day by day if the
weather stays the same. The difference is that with a
TABS this load is removed from the space in three ways:
absorption in the concrete slab, removed by the ventila-
tion system and removed by the water circulating in the
slabs. Therefore, the load is removed by a slab system
C o o l i n g P o w e r ( B t u / h )
4
1
2
3
1 = Heat Gain 2 = Power Needed for Conditioning the Ventilation Air
3 = Power Needed on Water Side 4 = Peak Heat Gain Reduction
FIGURE 8 Example of peak-shaving (reducing the peak load) effect (time vs. cooling power).17
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 9/10
A S H RA E J O U RN A L a s h r a e . or g F E B R U A R Y 2 0 1 53 6
temperature to be maintained above
dew point, the risk of condensation
can be easily avoided.
3. Determine the surface area for
radiant system, excluding any area
covered by objects immovable or
fixed to the building structure.
4. Establish a maximum permis-
sible surface temperature and a mini-
mum permissible surface tempera-
ture in consideration of the dew point.
5. Determine the design heat flux,
including the design heat flux of pe-
ripheral area and the design heat flux
of occupied area. For the design of the
cooling systems, determine the room with the maximum design heat flux.
6. Determine the radiant system
such as the pipe spacing and the cov-
ering type, and design heating and
cooling medium differential temper-
ature based on the maximum design
heat flux and the maximum and
minimum surface temperature from
the field of characteristic curves.
7. If the design heat flux cannot
be obtained by any pipe spacing
alternatives for the room of design, it
is recommended to provide supple-
mentary heating/cooling equipment.
In this case, the maximum design
heat flux for the embedded system
may now occur in another room.
8. Determine the thermal resis-
tance of backside insulating layer
and the design heating/cooling
medium flow rate.9. Estimate the total length of
circuit.
Hydronic radiant surface systems
are very often coupled with an air-
handling system. The air-handling
system usually operates only with
the amount of air needed for accept-
able indoor air quality, the required
IAQ standard, or amount of air
needed to remove latent heat from
TABLE 1 System design example for panel cooling.
STEP FIND EXAMPLE
0 A = 10 m2 (108 ft2), V = 30 m3 (1,059ft3) Room is Given to be Installed with
Radiant System and HVAC System1 Calculate Cooling Load Based on Opera-
tive TemperatureCooling Load (Latent)
Cooling Load (Sensible)
Qc,latent = 150 W (512 Btu/h)Qc,sensible = 1,000 W (3,416 Btu/h)
2 Determine Minimum Supply Air Quantity
Calculate Latent Cooling Available FromSupply Air
Sensible Cooling Available From SupplyAir
Design the Relative HumidityAnd Dew Point
Determine Remaining Sensible CoolingLoad to be Satisfied by Radiant System
V HVAC,min = 0.7 ACH = 21 CMH (12.4 CFM)
QHVAC,latent = Qc,latent = 150 W (512 Btu/h)
Assuming the SHF (Sensible Heat Factor) of HVAC, SHF =
(QHVAC,sensible / QHVAC,total ) = 0.7
QHVAC,total = QHVAC,latent / (1 - SHF)
= QHVAC,latent / 0.7 = 500 W (1,708 Btu/h)
Then, QHVAC,sensible = QHVAC,total – QHVAC,latent = 500 W – 150 W = 350 W
(1,196 Btu/h) is available from
supply air of HVAC
RH = 50 %, T dew = 14.8°C (58.6°F)
Remaining Qc,sensible = Qc,sensible - QHVAC,sensible
= 1,000W – 350 W
= 650 W (2,220 Btu/h)
3 Determine the Available Surface Area Aavailable = 5 m2 (53.8 ft2), 50% of ceiling area is availablefor radiant system
4 Establish a Minimum PermissibleSurface Temperature
T surf,min = 17°C (62.6°F) is acceptable for cooled ceiling* (which is higher than dew point temperature)
5 Determine Maximum Design Heat Flux Qc,max = 99 W/m2 (31.4 Btu/h·ft2) is allowed for cooledceiling*
6 Determine Radiant System
Pipe Spacing
Covering Type
Design Cooling Medium Differential
TemperatureDesign heating capacity of radiant
system,
Selected Radiant System has cooling capacity of 80 W/m2 (25.4 Btu/h·ft2).
mT = 0.2 m (8 in.)
punched aluminum sheet
T m = 2°C (3.6°F)
5 m2 = 400 W (1,366 Btu/h)
7 Select SupplementaryCooling Equipment
Required cooling capacity of SupplementaryCooling Equipment
Qout = Remaining Qc,sensible – Qdes
= 650 W – 400 W = 250 W (854 Btu/h)
8 Determine Thermal Resistance ofBackside Insulating Layer
Cooling Medium Flow Rate
R cover = 0.021 m2·K/W (0.12 h·ft2·°F/Btu)
m = 0.0478 kg/s (6.3 lb/min),
ensured of fully developed flow in pipe
If the resistance of backside insulation is high, the cooling
medium flow rate could be lowered.
9 Estimate Total Length Of Circuit Lcir = Aavailable / mT = 5 m2 / 0.2 m = 25 m (82 ft)
*ISO 11855-2: Building environment design – Design, dimensioning, installation and control of embedded radiantheating and cooling systems Part 2: Determination of the design heating and cooling capacity.
TECHNICAL FEATURE | Fundamentals a t Work
7/21/2019 2015Feb_028-039_Olesen_pt-1
http://slidepdf.com/reader/full/2015feb028-039olesenpt-1 10/10
F E B R U A R Y 2 0 1 5 a s h r a e . or g A S H RA E J O U RN A L 3 7
the space and control air humidity level, while the hydronic
system supplies or removes the sensible heat depending on
the seasonal conditions. In the cooling mode, the air system
can play a key role in avoiding surface condensation.
Part 2 of this article will cover control, operation,
installation and application of the system.
Acknowledgments This article was supported by VELUX guest professorship, and a grant
from the National Research Foundation of Korea (NRF) funded by the
Korean government (MEST) (No. 2014-050381).
References1. Bean, R., Olesen, B.W., Kim, K. W. 2010. “History of Radiant
Heating & Cooling Systems, Part 1.” ASHRAE Journal (1):40–46.2. Bean, R., Olesen, B.W., Kim, K. W. 2010. “History of Radiant
Heating & Cooling Systems, Part 2.” ASHRAE Journal (2):50–55.
3. REHVA. 2007. “Guidebook No 7: Low Temperature Heating andHigh Temperature Cooling.”
4. Olesen, B.W. 1997. “Possibilities and limitations of radiant floorcooling.” ASHRAE Transactions 103(1):42–48.
5. Olesen, B.W., Michel, E., Bonnefoi, F., De Carli, M. 2000. “Heatexchange coefficient between floor surface and space by floor cool-ing: theory or a question of definition.” ASHRAE Transactions, Part I.
6. ISO 11855-1:2012, Building environment design - Design, dimension-
ing, installation and control of the embedded radiant heating and cooling
systems – Part 1: Definition, symbols, and comfort criteria.
7. ISO 11855-2:2012, Building environment design - Design, dimension-
ing, installation and control of the embedded radiant heating and cooling sys-
tems – Part 2: Determination of the design and heating and cooling capacity.
8. 8. ISO 11855-3:2012, Building environment design - Design, dimen-
sioning, installation and control of the embedded radiant heating and cooling
systems – Part 3: Design and dimensioning.9. ISO 11855-4:2012, Building environment design - Design, dimension-
ing, installation and control of the embedded radiant heating and cooling
systems – Part 4: Dimensioning and calculation of the dynamic heating and
cooling capacity of Thermo Active Building Systems (TABS).
10. ISO 11855-5:2012, Building environment design - Design, dimension-
ing, installation and control of the embedded radiant heating and cooling
systems – Part 5: Installation.
11. ISO 11855-6:2012, Building environment design - Design, dimension-
ing, installation and control of the embedded radiant heating and cooling
systems – Part 6: Control.
12. ASHRAE Standard 55-2010, Thermal Environmental Conditions for
Human Occupancy.
13. ISO EN 7730-2005, Moderate thermal environments—determination of
the PMV and PPD indices and specification of the conditions for thermal comfort.14. 2012 ASHRAE Handbook—HVAC Systems and Equipment.
15. ISO EN 7726-1998, Ergonomics of the thermal environment- Instru-
ments for measuring physical quantities.
16. Weitzmann, P., Pittarello, E., Olesen, B.W. 2008. “The coolingcapacity of the thermo active building system combined with acous-tic ceiling.” Presented at Nordic Symposium on Building Physics.
17. Olesen, B.W. 2012. “Thermo active building systems usingbuilding mass to heat and cool.” ASHRAE Journal 54(2):44–52.
Advertisement formerly in this space. Advertisement formerly in this space.