GIS – Gas Insulated Substation

Why GIS

Types of Substation Switchgears [AIS/HIS/GIS]

Space Reduction Analysis with AIS/HIS/GIS

Specifications for GIS & AISSpecifications for GIS & AIS

400 kV / 220 kV GIS

400 kV side GIS

Single Line Diagram & Components of GIS

220 kV side GIS

Visual Comparison Between AIS & GIS Components

2

Visual Comparison Between AIS & GIS Components

Techno - Economic Comparison Between AIS & GIS

Advancement in GIS

Life Cycle Cost Analysis – [AIS/HIS/GIS]

World Scenario -GIS

Page 3: 21548809 Gas Insulated Substation

Gas Insulated Substations (GIS) is a compact, multicomponent assembly enclosed in a ground metallic housing in which the primary insulating medium is compressedSulphur hexafluoride (SF6) gas.

SF6 acts as an insulation between live parts & the earthed metal closure.SF6 acts as an insulation between live parts & the earthed metal closure.

The introduction of SF6 gas has revolutionized not only the technology of circuit breakers but also the layout of substations.

The dielectric strength of SF6 gas at atmospheric pressure is approximately three times that of air.

It is incombustible, non toxic, colorless and chemically inert.It is incombustible, non toxic, colorless and chemically inert.

It has arc-quenching properties 3 to 4 times better than air at equal pressure.

Space requirement is only 10 to 25 percent of what is required is a conventional substation.

Page 4: 21548809 Gas Insulated Substation

� GIS has small ground space requirements.

� Gas insulated Substations have easy maintenance( nearly zero Maintenance Maintenance

� Less field erection time & less erection cost.

� For underground powerhouse of Hydro electric power project where space constraint is a major issue.

� For Fast Growing Major Cities where land availability is costlier.� For Fast Growing Major Cities where land availability is costlier.

� Non-Flammability & Non-Explosive , Oil-free & Less Pollution

4

Page 5: 21548809 Gas Insulated Substation
Page 6: 21548809 Gas Insulated Substation
Page 7: 21548809 Gas Insulated Substation

Surge Arrestor Bus Post InsulatorCurrent Transformer

Surge Arrestor Bus Post InsulatorCurrent Transformer

Capacitor Voltage Transformer Disconnector Live Tank-Circuit Breaker Dead Tank- CB

Page 8: 21548809 Gas Insulated Substation

8

Page 9: 21548809 Gas Insulated Substation

Surge ArrestorBus Post Insulator

Capacitor Voltage

Transformer

Page 10: 21548809 Gas Insulated Substation
Page 11: 21548809 Gas Insulated Substation

11

Page 12: 21548809 Gas Insulated Substation

12

Page 13: 21548809 Gas Insulated Substation

The weight and size of the GIS equipment do not change appreciably with the voltage class as the bulk of the current – carrying components and enclosures have identical dimensions for similar thermal and short time current.

The additional insulation required for the next voltage class is achieved by increased gas density.

Owing to these flexibilities, a few manufacturers offer the same equipment for two voltage classes (like 170/145 kV). voltage classes (like 170/145 kV).

Even when the GIS equipment is designed for an individual voltage class, the dimensions and weights of the equipment differ marginally.

Rated voltage Rated voltage Rated voltage Rated voltage 145 kV145 kV145 kV145 kV 170 kV170 kV170 kV170 kV 245 kV245 kV245 kV245 kV

Bay width, m Bay width, m Bay width, m Bay width, m 1.5 2.02.02.02.0 2.02.02.02.0

Bay Depth, mBay Depth, mBay Depth, mBay Depth, m 3.33.33.33.3 3.353.353.353.35 3.43.43.43.4

Table shows the dimensions, weight and floor loading for three voltage classes of GIS.

13

Bay Depth, mBay Depth, mBay Depth, mBay Depth, m 3.33.33.33.3 3.353.353.353.35 3.43.43.43.4

Bay height, m Bay height, m Bay height, m Bay height, m 3.2 3.43.43.43.4 3.43.43.43.4

Floor area, sq.mFloor area, sq.mFloor area, sq.mFloor area, sq.m 4.95 6.76.76.76.7 6.86.86.86.8

Volume,Volume,Volume,Volume, m3 m3 m3 m3 15.84 22.78 23.12

Weight,Weight,Weight,Weight, kg kg kg kg 3800 5000 5700

Floor loading,Floor loading,Floor loading,Floor loading,

kg/kg/kg/kg/sq.msq.msq.msq.m

765 750 840

Page 14: 21548809 Gas Insulated Substation

Clearances

132 Kv132 Kv132 Kv132 Kv 220 Kv220 Kv220 Kv220 Kv 400 Kv400 Kv400 Kv400 Kv 765 Kv765 Kv765 Kv765 Kv

Clearance

for 132 Kv

Diff in Clearance

with Next

Voltage class

Clearance

for 220 Kv

Diff in Clearance

with Next

Voltage Class

Clearance

for 400 Kv

Diff in Clearance

with Next

Voltage class

Mini.Clearance

B/W Ph – Ph

1.22 m 0.84 m0.84 m0.84 m0.84 m 2.06 m 1.94 m1.94 m1.94 m1.94 m 4.0 m 3.6 m3.6 m3.6 m3.6 m 7.6 mMini.Clearance

B/W Ph – Ph

1.22 m 0.84 m0.84 m0.84 m0.84 m 2.06 m 1.94 m1.94 m1.94 m1.94 m 4.0 m 3.6 m3.6 m3.6 m3.6 m 7.6 m

Mini.Clearance

B/W Ph - Ear

1.07 m 0.71 m0.71 m0.71 m0.71 m 1.78 m 1.72 m1.72 m1.72 m1.72 m 3.5 m 1.4 m1.4 m1.4 m1.4 m 4.9 m

Sectional

Clearance

3.50 m 0.78 m0.78 m0.78 m0.78 m 4.28 m 2.22 m2.22 m2.22 m2.22 m 6.5 m 3.83.83.83.8 10.3m

Ground

Clearance

4.6 m 0.9 m0.9 m0.9 m0.9 m 5.5 m 2.5 m2.5 m2.5 m2.5 m 8.0 m

14

Earth Clearance: this is the clearance between live parts and earthed structures, walls, screens and ground.

Phase Clearance: this is the clearance between live parts of different phases.

Section Clearance: this is the clearance between live parts and the terminals of a work section. The limits of this work section, or maintenance zone, may be the ground or a platform from which the man works.

Page 15: 21548809 Gas Insulated Substation

145 Kv (132 Kv)145 Kv (132 Kv)145 Kv (132 Kv)145 Kv (132 Kv) 245 Kv (220 Kv)245 Kv (220 Kv)245 Kv (220 Kv)245 Kv (220 Kv) 420 Kv420 Kv420 Kv420 Kv 800 Kv 800 Kv 800 Kv 800 Kv

(765 Kv)(765 Kv)(765 Kv)(765 Kv)

Clearance

for 132 Kv

Diff in Clearance

with Next

Voltage class

Clearance

for 220 Kv

Diff in Clearance

with Next

Voltage class

Clearance

for 420 Kv

Diff in Clearance

with Next Voltage

class

Minimum Clearance for Different Voltage Level [GIS]

Clearance

for 132 Kv

Diff in Clearance

with Next

Voltage class

Clearance

for 220 Kv

Diff in Clearance

with Next

Voltage class

Clearance

for 420 Kv

Diff in Clearance

with Next Voltage

class

Centre-to-

centre distance

of phases

0.37 m 0.09 m0.09 m0.09 m0.09 m 0.46 m 0.20 m0.20 m0.20 m0.20 m 0.66 m 0.15 m0.15 m0.15 m0.15 m 0.81 m

Right-of way

width

1.3 m 0.2 m0.2 m0.2 m0.2 m 1.5 m 0.60.60.60.6 mmmm 2.1 m 0.5 m0.5 m0.5 m0.5 m 2.6 m

External

diameter

240 310 470 620

Gas pressure at

20 C

420 420 420 420

15

Gas pressure at

20 C

420 420 420 420

Page 16: 21548809 Gas Insulated Substation

Specifications for 400 KV GIS (ELK-3)

1 Rated Voltage 420 Kv420 Kv420 Kv420 Kv

2 Rated Power Frequency withstand voltage 650 Kv650 Kv650 Kv650 Kv

3 Rated Lightning impulse withstand voltage 1425 Kv1425 Kv1425 Kv1425 Kv

4 Rated Switching Impluse withstand voltage 1052 Kv1052 Kv1052 Kv1052 Kv

5 Rated Frequency 50 Hz50 Hz50 Hz50 Hz5 Rated Frequency 50 Hz50 Hz50 Hz50 Hz

6 Busbar current 6300 A6300 A6300 A6300 A

7 Feeder Current 4000 A4000 A4000 A4000 A

8 Rated Short time Withstand Current 63 KA63 KA63 KA63 KA

1 Rated Voltage UptoUptoUptoUpto 300300300300 KvKvKvKv

Specifications for 220 KV GIS (ELK-14)

16

1 Rated Voltage UptoUptoUptoUpto 300300300300 KvKvKvKv

2 Rated Power Frequency withstand voltage 460 Kv460 Kv460 Kv460 Kv

3 Rated Lightning impulse withstand voltage 1050 Kv1050 Kv1050 Kv1050 Kv

4 Rated Switching Impluse withstand voltage 850 Kv850 Kv850 Kv850 Kv

5 Rated Frequency 50 Hz50 Hz50 Hz50 Hz

6 Rated Continuous Current 4000 A4000 A4000 A4000 A

7 Rated Short time Withstand Current 50505050 kkkkAAAA

Page 17: 21548809 Gas Insulated Substation

400 kV/ 220 kV Substation with 5 bays at 400 kV and 7 bays at 220 kV

2 nos. 315 MVA, 400/220/33 kV three phase Auto Transformers

Gas Insulated Switchgear type ELK -3 at 400 kV and ELK-10 at 220 KV from ABB Switzerland

Substation commissioned in 2007.

Power received from ##### & ***** at 400 KV.Power received from ##### & ***** at 400 KV.

Power supplied to Delhi Transco at 220 KV.

Page 18: 21548809 Gas Insulated Substation

To ICT 1 To ICT 2

18From # # # From * * * *Bus Coupler Bay

Page 19: 21548809 Gas Insulated Substation

19

Page 20: 21548809 Gas Insulated Substation

20

Page 21: 21548809 Gas Insulated Substation

1. Barrier insulator2. Busbar Gas Compartment3. Feeder Gas Compartment4. CB Gas compartment5. Voltage transformer

21

Page 22: 21548809 Gas Insulated Substation

� Bus bars

� Circuit Breakers

� Disconnecting switches

� Earthing switches

� Current transformers

� Voltage transformers

� Cable and boxes

� Gas supply and gas monitoring equipment

1.Circuit Breaker2.Operating mechanism

(CB)3.Current Transformer4.Disconnector

5.Maintenance earthing switch6.Fast acting earthing switch7.Voltage transformer8.SF6 Bushing 22

Page 23: 21548809 Gas Insulated Substation

23

Page 24: 21548809 Gas Insulated Substation

A circuit breaker is an automatically-operated electrical switch designed to protect an electrical from damage caused by overload or short circuit.

Its basic function is to detect a fault condition and, by interrupting continuity, to immediately discontinue electrical flow.immediately discontinue electrical flow.

Unlike a fuse, which operates once and then has to be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation

Current interruption in a high-voltage circuit-breaker is obtained by separating two contacts in a medium, such as SF6, having excellent dielectric and arc quenching properties.

After contact separation, current is carried through an arc and the arc is interrupted & cooled by a gas blast of sufficient intensity.

Page 25: 21548809 Gas Insulated Substation

Each CB comprises three single-phase metal enclosed breaker poles.

Each Pole consists of operating mechanism, the interrupter column with 2 interrupting chambers in series & the enclosure with the basic support series & the enclosure with the basic support structure.

To guarantee simultaneous interruption, the chambers are mechanically connected in series.

One grading capacitor guarantees an equalized voltage distribution.

Assembly of Metal enclosed Breaking poles 25

Page 26: 21548809 Gas Insulated Substation

26

Page 27: 21548809 Gas Insulated Substation

Making use of arc energy to produce the pressure necessary to quench the arc and obtain current interruption. Low current interruption, up to about 30% of rated short-circuit current, is obtained by a puffer blast.

A valve between the expansion and compression volumes.

When interrupting low currents the valve opens under the effect of the overpressure generated When interrupting low currents the valve opens under the effect of the overpressure generated in the compression volume. The blow-out of the arc is made as in a puffer circuit breaker by compression of the gas obtained by the piston action.

In the case of high currents interruption, the arc energy produces a high overpressure in the expansion volume, which leads to the closure of the valve and thus isolating the expansion volume from the compression volume.

The overpressure necessary for breaking is obtained by the optimal use of the thermal effect.27

Page 28: 21548809 Gas Insulated Substation

Each Pole of the CB is equipped with the Hydraulic spring operating mechanism.

It combines the advantages of both Hydraulic operating mechanism & Spring energy storage type.

A Hydraulic pump moves oil from low pressure reservoir to high pressure reservoirside of the energy piston.

Opening & Closing of CB is initiated by trip coil actuation. 28

Page 29: 21548809 Gas Insulated Substation

29

Page 30: 21548809 Gas Insulated Substation

Current transformer (CT) is used for measurement of electric currents. Current transformers are also known as instrument transformers.

Current transformers are commonly used in metering and protective relays in the electrical power industry.

When current in a circuit is too high to directly apply to measuring instruments, a current transformer produces a reduced current accurately proportional to the current in the circuit, which can be conveniently connected to measuring and recording instruments.

Page 31: 21548809 Gas Insulated Substation

Voltage transformers (VTs), also referred to as “Potential transformers" (PTs), are used in high-voltage circuits.

They are designed to present a negligible load to the supply being measured, to allow protective relay equipment to be operated at lower voltages, and to have a allow protective relay equipment to be operated at lower voltages, and to have a precise winding ratio for accurate metering

Page 32: 21548809 Gas Insulated Substation

The single pole inductive voltage transformer is connected to switch gear with the connecting flanges with a barrier insulator.

The primary winding is insulated The primary winding is insulated with SF6 gas & connected to high voltage terminal.

The primary winding is wounded on the top of the core & secondary windings.

The secondary winding is connected

32

The secondary winding is connected to the terminals in the external terminal box through a gas tight multiple bushing.

Page 33: 21548809 Gas Insulated Substation

33

Page 34: 21548809 Gas Insulated Substation

Disconnector and Earthing switches are safety devices used to open or to close a circuit when there is no current through them.

They are used to isolate a part of a circuit, a machine, a part of an overhead line or an underground line so that maintenance can be safely conducted.an underground line so that maintenance can be safely conducted.

The opening of the line isolator or busbar section isolator is necessary for safety, but not sufficient. Grounding must be conducted at both the upstream and downstream sections of the device under maintenance. This is accomplished by earthing switches.

34

Page 35: 21548809 Gas Insulated Substation

Disconnect switches are designed to continuously carry load currents and momentarily carry short circuit currents for a specified duration.

They are designed for no-load switching ,

35

They are designed for no-load switching , opening , or closing circuits where negligible currents are made or interrupted (including capacitive current and resistive or inductive current , or when there is no significant voltage across the open terminals of the switch.

Page 36: 21548809 Gas Insulated Substation

Fast earth switch and maintenance earth switch are the two types of earth switches used for gas insulated sub-station systems.

Fast earth switch is used to protect the circuit-connected instrument voltage transformer from core saturation caused by direct current flowing through its primary as a consequence of from core saturation caused by direct current flowing through its primary as a consequence of charge stored online during isolation / switching off the line.

Use of fast earth switch provides a parallel (low resistance) path to drain the residual static charge quickly, thereby protecting the instrument voltage transformer from the damages that may otherwise be caused. The basic construction of these earth switches is identical.

36

Page 37: 21548809 Gas Insulated Substation

Wave Trap

Capacitance Voltage Transformer

Lightening Arrestor

37

Capacitor Voltage Transformers convert transmission class voltages to standardized low and easily measurable values, used for metering, protection and control of the high voltage system.

Additionally, Capacitor Voltage Transformers serve as a coupling capacitor for coupling high frequency power line carrier signals to the transmission line.

Page 38: 21548809 Gas Insulated Substation

Lightning Arresters or Surge Arresters are always connected in Shunt to the equipment to be protected, they provide a low impedance path for the surge current to the ground current to the ground

Line trap also is known as Wave trap. It traps Hi-frequency communication signals sent on the line from the remote substation and diverting them to the telecom/ tele protection panel in the substation control room (through coupling capacitor

38

tele protection panel in the substation control room (through coupling capacitor and LMU).

This is relevant in Power Line Carrier Communication (PLCC) systems for communication among various substations without dependence on the telecom company network.

Page 39: 21548809 Gas Insulated Substation

SF6 – Air Bushings are used for connecting to open terminal equipment & Overhead transmission lines.

SF outdoor bushings allow the enclosed switchgear to be connected to overhead lines. lines.

39

Page 40: 21548809 Gas Insulated Substation

CABLE TERMINATION (Fig - a): High-Voltage cables of various types are connected to SF6 switchgear via cable connection assembly & also it enables the GIS & Cables to be tested separated

40

Transformer connection (Fig - b) consists of Oil/SF6 bushing, the enclosure, the main circuit end terminal & removable connection.

For Hi-Voltage test on GIS, transformer is isolated from switchgear by dismantling the removable connection

Fig - b Fig - a

Page 41: 21548809 Gas Insulated Substation

The insulating and interrupting capability of the SF6 gas depends on the density of the SF6 gas .

The pressure of the SF6 gas varies with temperature, so a mechanical or electronic temperature compensated pressure switch is used to monitor the equivalent of gas density.

Gas Density Monitor is directly mounted on the enclosure. The gas pressure acts on metal bellows, with a reference volume for compensation of the temperature.

In case of gas leakage a micro-switch is actuated. Thresholds for refilling (first stage) or lock-out alarm(second stage) can be mechanically set. The response character is shown in the Molier diagramme.

41

Page 42: 21548809 Gas Insulated Substation

Isolating Gas Pressure is generally 350-450 Kpa at 20 deg cel.cel.

Quenching gas pressure is about 600-700 Kpa

Outdoor Equipment exposed to arctic conditions contains a mixture of SF6 & N2.mixture of SF6 & N2.

42

Page 43: 21548809 Gas Insulated Substation

An autotransformer is an electrical transformer with only one winding.

The winding has at least three electrical connection points called taps. The voltage source and the load are each connected to two taps.

One tap at the end of the winding is a common connection to both circuits (source and load). Each tap corresponds to a different source or load voltage.

432 nos. 315 MVA, 400/220/33 kV three phase Auto Transformers

Page 44: 21548809 Gas Insulated Substation

An autotransformer for power applications is typically lighterlighterlighterlighter and less less less less

costly costly costly costly than a two-winding transformer, up to a voltage ratio of about 3:1 voltage ratio of about 3:1 voltage ratio of about 3:1 voltage ratio of about 3:1 -

beyond that range a two-winding transformer is usually more economical.

In an autotransformer a portion of the same winding same winding same winding same winding acts as part of both

the primary and secondary winding.

44

Page 45: 21548809 Gas Insulated Substation

To Line-4 To Line-3 To Line-2 To Line-1Bus Coupler

Bay

From ICT 1 From ICT 2

Page 46: 21548809 Gas Insulated Substation

46

Page 47: 21548809 Gas Insulated Substation

47

Page 48: 21548809 Gas Insulated Substation

48

Page 49: 21548809 Gas Insulated Substation

49

Page 50: 21548809 Gas Insulated Substation

50

Page 51: 21548809 Gas Insulated Substation

51

Page 52: 21548809 Gas Insulated Substation

52

Page 53: 21548809 Gas Insulated Substation

53

Page 54: 21548809 Gas Insulated Substation

(For Further Space reduction)

� Gas Insulated Transformer (GIT) Instead of Oil Immersed Transformer (OIT).

� SMART GIS - Integration of Electronic CT’s & PT’s

� Combined Earthing Switch & Disconnector

54

Page 55: 21548809 Gas Insulated Substation

55

Page 56: 21548809 Gas Insulated Substation

Natural Cooled type

56Forced-Gas-Circulated , Forced-Air-Cooled

Forced-Gas-Circulated , Natural-Air-Cooled

Page 57: 21548809 Gas Insulated Substation

57

Page 58: 21548809 Gas Insulated Substation

58

GIT OIT

Medium SF6 Insulating oil

Turn Insulation PET film Cellulose paper

Conservator Not Required Necessary

Pressure Relief Device Not required Necessary

Others Fundamentally Same

Page 59: 21548809 Gas Insulated Substation

59

Page 60: 21548809 Gas Insulated Substation

� Nonflammability – Gas insulated transformers , using incombustible SF6 gas as insulation and cooling medium, enable to remove a fire fighting equipment from transformer room.transformer room.

� Non Tank – explosion - Pressure tank enables to withstand the pressure rise in case of internal fault.

� Compactness – Since conservator or pressure relief equipment is not necessary, height of transformer room can be reduced approximately 2 – 2.5 meters.

� Easy installation – oil or liquid purifying process is not necessary in case of gas-insulated

60

� Easy installation – oil or liquid purifying process is not necessary in case of gas-insulated transformer.

� Easy inspection and maintenance work -Only SF6 gas pressure shall be basically monitored during periodically inspection.

Page 61: 21548809 Gas Insulated Substation

61

Page 62: 21548809 Gas Insulated Substation

62

Page 63: 21548809 Gas Insulated Substation

The Combined sensors are the Rogowski coil for current measurement and the capacitive divider for voltage measurement

A combined current and voltage sensor has been developed to replace the A combined current and voltage sensor has been developed to replace the conventional current and voltage transformers in GIS.

63

1. Serial Optic Link 2. Voltage sensor 3. Rogowski Coil

Page 64: 21548809 Gas Insulated Substation

Why Combined Voltage & current Sensor ?

Advanced CT’s without a magnetic core (Rowgowski coil) & Capacitive sensor have been developed to save space and reduce the cost of GIS.

The output signal is at a low level, so it is immediately converted by an enclosure mounted device to a digital signal

� Small size - Helps to optimize the use of space in the switchgear

� Lighter weight means less material usage and lower life cycle costs (LCC)

� Large dynamic range - permits minimization of number of sensor types needed and

64

� Large dynamic range - permits minimization of number of sensor types needed and improvement of some protection functions.

� Protection and measurement functions combined.

� Lower losses mean lower LCC (Life Cycle Cost)

Page 65: 21548809 Gas Insulated Substation

Current Measurement – Current Sensor instead of Current Measurement – Current Sensor instead of Current Transformer

The current sensor is based on a Rogowski coil (a coreless inductive current transformer).

Voltage Measurement – Voltage Sensor instead of Voltage Transformer

65

The voltage sensor is based on a capacitive electrical field sensor (Capacitive ring sensor).

The capacitive ring, which acts as a voltage sensor, also has a linear characteristic and is very simple in terms of the insulation.

Page 66: 21548809 Gas Insulated Substation

66

Page 67: 21548809 Gas Insulated Substation

1. Busbar with Combined DS & ES2. Circuit-breaker3. Current sensor (Rogowski coil)4. Electro-optical voltage transformer4. Electro-optical voltage transformer6. Make-proof earthing switch7. Control cubicle

67

1. Busbar with Combined DS & ES 2. Circuit Breaker3. Current Transformer4. Voltage transformer 5. Combined DS & ES with cable sealing

end 6. Hi-Speed ES7. Control Cubicle

Page 68: 21548809 Gas Insulated Substation

The DSES incorporates the two functions of a disconnector and a maintenance earthing switch as a result saving the space in GIS.

This is achieved by a sliding contact characterized by three defined positions: - disconnector open / earthing switch closed

- disconnector closed / earthing switch open

-disconnector open / earthing switch open

The use of one moving contact for the disconnector and the earthing switch inhibits simultaneous closed position of both switches.

68Busbar with Combined Disconnector & Earthing Switch

Page 69: 21548809 Gas Insulated Substation

69

Page 70: 21548809 Gas Insulated Substation

Depending on the direction of movement the contacts act as disconnector or earthing

Combined disconnector and earthing switch is mounted at the front, and acts via bevel gears and an insulating shaft on the three parallel contact pins.

the contacts act as disconnector or earthing switch (maintenance earthing switch).

By means of a crank handle, manual operation of the combined disconnector and earthing switch is also possible.

70

Page 71: 21548809 Gas Insulated Substation

71

Page 72: 21548809 Gas Insulated Substation

72

Page 73: 21548809 Gas Insulated Substation

73

Page 74: 21548809 Gas Insulated Substation

74

Page 75: 21548809 Gas Insulated Substation

(O & M)

75

Page 76: 21548809 Gas Insulated Substation

76

Page 77: 21548809 Gas Insulated Substation

77

Page 78: 21548809 Gas Insulated Substation

Life cycle cost

AIS GIS

Planning and engineering 100% 80%

Real estate 100% 40%

Primary equipment 100% 120%Primary equipment 100% 120%

Secondary equipment 100% 100%

Earthwork, civil work, structures 100% 60%

Electrical assembly and erection 100% 70%

Maintenance 100% 50%

78

Maintenance 100% 50%

Outage 100% 50%

Life cycle costs after 10 years 100% Max. 70%

Page 79: 21548809 Gas Insulated Substation

79

Page 80: 21548809 Gas Insulated Substation

Optimizing of acquisition costs

Acquisition costs are mainly influenced by the layout, the redundancy concept and the requirement area for the installation.

The optimization of the layout and the redundancy can be supported by LCC analysis which take into account the different reliability figures of the different technologies.

Cost of Acquisition

The goal is to achieve optimal availability of the substation with minimized costs.

Optimizing of costs of ownership

The costs of ownership are dominated by the maintenance strategy and the reliability of the switchgear. By means of LCC analysis, the different maintenance strategies can be simulated.

Pure corrective maintenance can be compared with time-based or reliability – centered maintenance.

Cost of Ownership

Cost of Ownership

80

Optimizing of renewal costs

LCC calculations assist in determining the optimal date for replacing an existing substation.

Aged equipment requires intensified maintenance, more specialized experts and spare parts.

The effect of investment costs of new equipment with reduced maintenance costs can be balanced with the increased expenditure for intensified maintenance of the old equipment

Cost of Ownership

Page 81: 21548809 Gas Insulated Substation

� Cost of GIS is high.

� The life of GIS is affected by certain factors such as: conductive particles, � The life of GIS is affected by certain factors such as: conductive particles, partial discharges and contamination (decomposition products, water, etc

� Gas Insulated Substations (GIS) can be used for longer times without any periodical inspections.

� However, conducting contamination (i.e. aluminum, copper and silver particles) could seriously reduce the dielectric strength of gas-insulated system.system.

� SF6 has been identified as a greenhouse gas, safety regulations are being introduced in order to prevent its release into atmosphere.

81

Page 82: 21548809 Gas Insulated Substation

The first GIS’s were put in operation in 1967 in Switzerland and Germany.

The GIS in Germany is still in operation, whereas the GIS in Switzerland were The GIS in Germany is still in operation, whereas the GIS in Switzerland were recently decommissioned after 35 years of operation without major fault or gas leak.

An assessment made on SF6 gas leakage over the lifetime of the first GIS and concluded that overall leakage rate was about 0.4% per year.

82

Page 83: 21548809 Gas Insulated Substation
Page 84: 21548809 Gas Insulated Substation

THANKING YOUTHANKING YOU