218091515 protection of tf gen
TRANSCRIPT
-
8/10/2019 218091515 Protection of TF Gen
1/84
Protection of Generators
& TransformersPresented By:Er. H.S. DhaliwalAssistant Professor,Deptt. Of Electrical EnggBHSBIET, Lehragaga.
1Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
2/84
Introduction
In a generating station the generator and transformerare the most expensive equipments and hence it isdesirable to employ a protective system to isolate thefaulty equipment as quickly as possible to keep thehealthy section in normal operation and to ensureuninterruptable power supply.
The basic electrical quantities those are likely tochange during abnormal fault conditions are current,voltage, phase angle and frequency . Protective relaysutilizes one or more of these quantities to detectabnormal conditions in a power system.
2Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
3/84
Protection ofTransformers
3Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
4/84
Transformer
A Transformer is a device that transferselectrical energy from one circuit to anotherthrough inductively coupled conductors thetransformer's coils. A varying current in the
first or primary winding creates a varyingmagnetic flux in the transformer's core, andthus a varying magnetic field through thesecondary winding. This varying magneticfield induces a varying electromotive force(EMF) or "voltage" in the secondary winding.This effect is called mutual induction.
4Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
5/84
-
8/10/2019 218091515 Protection of TF Gen
6/84
-
8/10/2019 218091515 Protection of TF Gen
7/84
-
8/10/2019 218091515 Protection of TF Gen
8/84
Why Protection is required ? A fault in electrical system is defined as a defect
in the electrical circuit due to which the flow ofcurrent is diverted from its intended path. Faultcurrents being excessive , they can damage notonly the faulty equipment, but also theinstallation through which the fault current isfed. Fault in important equipment like
transformer can effect the stability of powersystem. To improve the system stabilityprotection is required.
8Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
9/84
Transformer Fault Categories
1. Winding and terminal faults
2. Sustained or uncleared external faults
3. Abnormal operating conditions such asoverload, overvoltage and over fluxing.
4. Core faults
Punjab Edusat Society 9
-
8/10/2019 218091515 Protection of TF Gen
10/84
Faults on Transformer 10-12% of total faults occurring in the power
system are due to the faults on the Transformers.The following are the major causes of faults in
transformers: 1. Insulation Failure 2. Faults in tap-changer 3. Faults in bushing 4. Faults in protection circuit 5. Overloading, Overvoltage
10Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
11/84
-
8/10/2019 218091515 Protection of TF Gen
12/84
Transformer Connections
Punjab Edusat Society 12
-
8/10/2019 218091515 Protection of TF Gen
13/84
Transformer Connections
Punjab Edusat Society 13
-
8/10/2019 218091515 Protection of TF Gen
14/84
Phasor Diagrams of Transformerconnections
14Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
15/84
Pressure Relief and Pressure Relay
Pressure relay and pressure relief device is mountedon transformer tank. It releases gas pressure to theatmosphere during:
High overload peaks Prolonged overloads Arcing faults within oil
Pressure relief valve is spring loaded and has a
seal-seat. When the pressure inside the tankincreases above a certain value, the force onmovable sub-assembly exceeds spring force andthe valve operates. The alarm contacts are closed.
15Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
16/84
Pressure Relief and Pressure Relay
16Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
17/84
Buccholz Relay
Buchholz relay is a gas- actuated relayinstalled in oil-immersed transformers forprotection against all kind of faults. It is usedto gives an alarm in case of slow developing
faults or incipient faults in the transformerand to disconnect the transformer from thesupply in the event of severe internal faults. Itis installed in the pipe between theconservator and main tank as shown in fig11below. This relay is used in oil-immersedtransformers of rating above 750 kVA.
17Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
18/84
Buccholz Relay
18Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
19/84
Petcock
Counter balanceweight
Oil level
From transformer
Aperture adjuster
Deflector plateDrain plug
Trip bucket
To oilconservator
Mercury switch
Alarm bucket
Buchholz Relay
19Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
20/84
Mounting of Buccholz Relay
20Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
21/84
-
8/10/2019 218091515 Protection of TF Gen
22/84
-
8/10/2019 218091515 Protection of TF Gen
23/84
Differential Protection In a power transformer, the currents in primary and
secondary are to be compared. As these twocurrents are usually different, therefore the use ofidentical transformers will give differential currentand operate the relay even under no loadconditions. The difference in magnitude of currentsin primary and secondary of power transformers iscompensated by different turns ratios of C.T.s. If T isthe turns ratio of power transformer, then the turnsration of C.T.s on LV side is made T times the turns
ration of the C.T.s on HV side. When this condition isfulfilled the secondaries of the two C.T.s will carrysame current under normal conditions. And thus nocurrent will flow through the relay and it remainsinoperative.
Punjab Edusat Society 23
-
8/10/2019 218091515 Protection of TF Gen
24/84
Differential Protection
Punjab Edusat Society 24
Correct application of differential protection requires CT ratio and windingconnections to match those of transformer.
CT secondary circuit should be a replica of primary system. Consider :
(1) Difference in current magnitude(2) Phase shift(3) Zero sequence currents
-
8/10/2019 218091515 Protection of TF Gen
25/84
Differential Protection
25Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
26/84
Differential Connections
Punjab Edusat Society 26
-
8/10/2019 218091515 Protection of TF Gen
27/84
-
8/10/2019 218091515 Protection of TF Gen
28/84
Biased Differential Scheme
Punjab Edusat Society 28
-
8/10/2019 218091515 Protection of TF Gen
29/84
OVER CURRENT PROTECTION
The over current protection is needed toprotect the transformer from sustainedoverloads and short circuits. Induction typeover current relays are used which in additionto providing overload protection acts as backup relays for protection of transformer
winding fault.
Punjab Edusat Society 29
-
8/10/2019 218091515 Protection of TF Gen
30/84
OVER CURRENT PROTECTION
Requirements
Fast operation for primary short circuits
Discrimination with downstream protections Operation within transformer withstand
Non-operation for short or long term overloads Non-operation for magnetising inrush
Punjab Edusat Society 30
-
8/10/2019 218091515 Protection of TF Gen
31/84
OVER CURRENT PROTECTION
Punjab Edusat Society 31
-
8/10/2019 218091515 Protection of TF Gen
32/84
EARTH FAULT PROTECTION The earth fault protection is used to provide
protection against any earth fault in thewindings of the transformer. It works on the
principle that when the transformer winding issound the currents in all the three phases willbalance and no current will spill into the earthfault relay. The arrangement is such that the
relay does not respond to any out of balancecurrent between windings caused by tapchanging arrangement
32Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
33/84
-
8/10/2019 218091515 Protection of TF Gen
34/84
COMBINED OVER CURRENT ANDEARTH FAULT PROTECTION
34Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
35/84
Combined Differential andEarth Fault Protection
Punjab Edusat Society 35
-
8/10/2019 218091515 Protection of TF Gen
36/84
Frame leakage Protection
The transformer is lightly insulated from earthby mounting it on a concrete plinth. The tankis connected to earth through a CT acrosswhich an instantaneous earth fault relay isconnected. Earth fault current due toinsulation breakdown in any winding of the
transformer will flow through the tank andsingle earth connection, thus energizing thecurrent transformer and operating the relay.
36Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
37/84
Overfluxing Protection Generator transformers Grid transformers
Usually only a problem during run-up or shut down, but canbe caused by loss of load / load shedding etc.
Flux Vf
Effects of overfluxing : Increase in magnetising current Increase in winding temperature Increase in noise and vibration Overheating of laminations and metal parts
Protective relay responds to V/f ratio Stage 1 - lower A.V.R. Stage 2 - Trip field
Punjab Edusat Society 37
-
8/10/2019 218091515 Protection of TF Gen
38/84
m2
Ie
m
V = kf
Overfluxing Basic Theory
CAUSES Low frequency High voltage Geomagnetic disturbances
EFFECTS Tripping of differential element (Transient
overfluxing) Damage to transformers (Prolonged overfluxing)
38Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
39/84
-
8/10/2019 218091515 Protection of TF Gen
40/84
Inter-Turn Fault Protection
Punjab Edusat Society 40
-
8/10/2019 218091515 Protection of TF Gen
41/84
Protection of
Generators
41Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
42/84
-
8/10/2019 218091515 Protection of TF Gen
43/84
Alternator design
43Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
44/84
44Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
45/84
Principle of operation Alternators generate electricity using the same
principle as DC generators, namely, when the magneticfield around a conductor changes, a current is inducedin the conductor. Typically, a rotating magnet, calledthe rotor turns within a stationary set of conductorswound in coils on an iron core, called the stator. Thefield cuts across the conductors, generating an inducedEMF(Electro-Magnetic Field), as the mechanical inputcauses the rotor to turn.
The rotating magnetic field induces an AC voltage in
the stator windings. Often there are three sets of statorwindings, physically offset so that the rotatingmagnetic field produces a three phase current,displaced by one-third of a period with respect to eachother.
45Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
46/84
Alternating current (AC) flows
46Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
47/84
Faults on Alternator
6-8% of total faults occurring in the power systemis due to the alternator faults. The following arethe major causes of fault on an alternator:
1. Stator Faults 2. Rotor Faults 3. Abnormal conditions 4. Faults in associated equipment 5. Faults in protective system
47Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
48/84
Alternator Protection The following types of protection can be provided to the
alternators:- Differential Protection- Stator Earth fault protection- Negative phase sequence protection- Protection against unbalanced loading- Inter-turn fault protection- Reverse power protection- Field failure protection- Rotor earth fault protection
- Temperature sensors in slots- Over current relays in stator & rotor circuits-Surge arrestors for surge overvoltage
48Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
49/84
Differential Protection CTs are provided at each end of the generator
winding which is to be protected.(as shown infig.)
When there is no fault the differential current (I1-I2) through the relay is zero. So the relay will notoperate.
When the fault occurs the balance is disturbed
and differential current (I1-I2) flows through theoperating coil of the relay causing relay operationand the trip circuit of the circuit breaker is closed.
49Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
50/84
Differential Protection
Punjab Edusat Society 50
ff l b l
-
8/10/2019 218091515 Protection of TF Gen
51/84
Differential Protection using balancingresistor
Punjab Edusat Society 51
-
8/10/2019 218091515 Protection of TF Gen
52/84
Modified Differential Protection
Generally protection is made for 80 to 85% of thewinding. If any fault occurs near the neutral point then the
fault current is very small and relay does not
operate. Modified differential protection scheme is used
to over come this. Two phase elements (PC and PA) and balancing
resistor(BR) is connected in star and the earthrelay(ER) is connected between the star point andneutral pilot wire.
52Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
53/84
-
8/10/2019 218091515 Protection of TF Gen
54/84
Percentage Differential protection
54Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
55/84
Percentage Differential protection
The disadvantage of the current differentialprotection is that current transformers mustbe identical, otherwise there will be current
flowing through the current relays for faultsoutside of the protected zone or even undernormal conditions. Sensitivity to the
differential current due to the currenttransformer errors is reduced by percentagedifferential relays.
55Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
56/84
Percentage Differential protection
In percentage differential relays, the current fromeach current transformer flows through arestraint coil. The purpose of the restraint coil isto prevent undesired relay operation due tocurrent transformer errors. The operating coilcurrent | i 1 - i2 | required for tripping is apercentage of the average current through therestraint coils. It is given by
where k is the proportion of the operating coilcurrent to the restraint coil current. For exampleif k = 0.1, the operating coil current must be morethan 10% of the average restraint coil current inorder for the relay to operate.
56Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
57/84
Restricted or balanced Earth fault Protection
In case of small size generators star point isnot available because it is made inside thegenerator and grounded through some low
resistance then percentage differential relayfor ground fault is provided and is known asrestricted earth fault protection.
This scheme can be used only for groundfaults but not for phase faults.
57Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
58/84
M P i i
-
8/10/2019 218091515 Protection of TF Gen
59/84
Merz Price protection This type of protection provides a continuous check on
faults within the points, where the C.T.s are used. Thereare two sets of C.T.s; each set is mounted on either end ofthe stator phase. The secondaries of these currenttransformer sets are connected in star and their ends areconnected together through pilot wires. The over currentinverse time relay is connected across the equipotentialpoints in the pilot wires, which will naturally be in centerof these wires. These relays are kept adjacent to the maincircuit breaker; by inserting balancing resistance in serieswith the pilot wires to achieve equipotential point nearthe main circuit breaker. If there is no fault in thegenerator, same current will pass through the C.T.s atboth the ends and there will be no current spilling intothe relay.
59Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
60/84
-
8/10/2019 218091515 Protection of TF Gen
61/84
Stator Winding Faults
The stator fault includes the following:1. Phase-to-phase fault2. Phase-to-earth fault3. Stator inter-turn fault
The most common fault of the above is the phase-to-earth fault. This fault is sensed and protected by theearth fault protection.
From these phase faults and inter turn faults are lesscommon ,these usually develop into an earth faults.
This causes- Arcing to core Damage of conductor and insulation
61Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
62/84
-
8/10/2019 218091515 Protection of TF Gen
63/84
Cross Differential Protection
Used in case of hydro-electric generator havingdouble winding armature.
As shown in figure relayRc provides protectionagainst phase to groundand phase to phase fault.
The relay R1 providesprotection against inter-turn faults.
63Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
64/84
Rotor Faults Faults in the rotor circuit may be either earth
faults or between the turns of the field winding . Field circuits are normally operated un-earthed.
So a single earth fault will not affect its operation. But when a second fault arises then field winding
is short circuited and produce unsymmetricalfield system which leads to unbalanced forces onrotor and results in excess pressure and bearingand shaft distortion.
64Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
65/84
Rotor Earth fault Protection The rotor earth fault protection is done by dc
injection method or ac injection method . The dc or ac voltage is impressed between the
field circuit and ground through a sensitiveovervoltage relay and current limiting resistor orcapacitor(in case of ac).
But dc source is generally used as over-current
relay in case of dc is more sensitive than ac. A single earth fault in rotor circuit will complete
the path and the fault is sensed by the relay.
65Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
66/84
Rotor Earth fault Protection
Punjab Edusat Society 66
-
8/10/2019 218091515 Protection of TF Gen
67/84
Rotor Temperature alarm
It is provided in largegenerators.
It indicates the level oftemperature but not theactual hot spottemperature.
The relay measures thetemperature bymeasuring the resistance(as shown in fig)
67Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
68/84
Loss of Excitation Protection
When the excitation of generator is lost it operate as aInduction generator. It derives excitation from thesystem and supply power at leading power factor.Which may cause-
A fall in voltage & so loss of synchronism & systeminstability.Over heating of rotor due to induction current on it.
A protection having MHO characteristicis used to detect loss of field.
68Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
69/84
Overvoltages Atmospheric surge voltages are caused by direct
lightening strokes to the aerial lines in the HVsystem. These high voltage surges can reach tothe generator via transformer. To protect the
generator from severe voltage surges, surgearrestors and surge capacitors may be used.
Switching surges may cause high transient
overvoltage if the restriking occurs across thecontacts of the circuit breakers. These surges canalso be eliminated by surge arrestors.
69Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
70/84
Over Voltage Protection
Overvoltage protection is required in case of hydro-electric or gas turbine generators but not in case ofturbo generators.
Over voltage may be caused due to-
Transient over voltage in the transmission line due tolightening.Defective operation of the voltage regulator.Sudden loss of load due to line tripping.The protection is provided with an over voltage relay.It is usually of induction pattern with an IDMTCharacteristic
70Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
71/84
Reasons for Overvoltage
Overvoltage may occur in the vehicle electricalsystem as the result of:
- Regulator failure- Influences originating from the ignition- Switching off of devices with a predominantly
inductive load- Loose contacts- Cable breaks
71Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
72/84
Overload Protection Overloading of the machine causes overheating
in the stator winding. This can be prevented by using over-current relay
with time delay adjustment. But overheating not only depends on over-
current but also the failure of the cooling systemin the generator.
So temperature detector coils such as thermistorsor thermocouples are used at various points instator winding for indication of the temperature.
72Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
73/84
Thermal Overloading
Continuous overloading may increase thewinding temperature to such extent that theinsulation will be damaged.
Temperature rise can also be caused by thefailure of cooling system. In large machinedthe cooling system is utmost requirement.
Failure of cooling system will cause severe risein temperature of winding.
73Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
74/84
Unbalanced loading Continuous unbalance loads equal to the rated
current can cause dangerous heating of thecylindrical rotor in turbo-generators.Unbalanced loading on generator may be due to:- unsymmetrical faults near the generatingstation- mal-operation of a circuit-breaker near thegenerating stationNegative sequence protection senses theunbalanced loading of alternator.
74Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
75/84
Reverse Power Protection
When prime-mover fails machine startsmotoring and draws electrical power from thesystem and this is known as inverted
operation . The generator can be protected from inverted
operation by using single-element directional
power relay(reverse power relay) whichsenses the direction of power flow.
75Punjab Edusat Society
Negative Phase Sequence
-
8/10/2019 218091515 Protection of TF Gen
76/84
Negative Phase SequenceProtection
Unbalance may cause due to single phasefault or unbalanced loading and it gives rise tonegative sequence current .
This current in rotor causes rotor overheatingand damage to the rotor.
This can be protected by negative sequence
current filter with over current relay.
76Punjab Edusat Society
Negative Phase Sequence
-
8/10/2019 218091515 Protection of TF Gen
77/84
Negative Phase SequenceProtection
Punjab Edusat Society 77
-
8/10/2019 218091515 Protection of TF Gen
78/84
Over current & Earth fault protection
78Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
79/84
Field Winding Faults
Rotor faults include rotor inter turn faults andconductor-to-earth faults. These are caused bymechanical and temperature stresses. Theunbalanced loading on generator gives rise to
negative sequence currents, which gives rise tonegative sequence field & this negative sequencefield rotates in opposite direction of the mainfield and gives rise to rotor heating. Rotor
temperature indicators are used for detection ofrotor overheating due to unbalanced loading ofgenerator.
79Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
80/84
Cooling and noise Due above all to the heat developed by the alternator when
converting mechanical power into electrical power, and alsodue to the effects of heat from the engine compartment(engine and exhaust system), considerable increases in thealternator component temperature take place.
In the interests of functional reliability, service life, and
efficiency, it is imperative that this heat is dissipatedcompletely. Depending upon alternator version, maximum permissible
ambient temperature is limited to 80...120
C, and futuretemperatures are expected to reach to 135
C.
Cooling must guarantee that even under the hostile under-hood conditions encountered in everyday operation,component temperatures remain within the specified limits("worst-case" consideration).
80Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
81/84
-
8/10/2019 218091515 Protection of TF Gen
82/84
-
8/10/2019 218091515 Protection of TF Gen
83/84
Other Protections
Rotor temperature alarm Stator heating protection Loss of field protection Over speed protection Bearing insulation
Vibration protection Bearing overheating protection
83Punjab Edusat Society
-
8/10/2019 218091515 Protection of TF Gen
84/84
THANKSPresented By:
Er. H.S. [email protected] 098150-74800
mailto:[email protected]:[email protected]