22 guide tender specifications - ups manufacturers india
TRANSCRIPT
22G
UID
E TE
ND
ER
SPEC
IFIC
ATIO
NS
22-1
22-2
Scope:
This general specification lays down the functional requirements, performance characteristics, quality of
installation required of a ___KVA uninterruptable power system (UPS) with IGBT rectifier and inverter with
inbuilt isolation transformer and with ___mins backup time.
Description of the system
The UPS system shall consist of rectifier/charger, batteries, inverter, static bypass, manual bypass, protective
devices and accessories that automatically provides continuous supply of electric power to its load within the
tolerance as set out in this specifications sheet.
Project Requirement:
The proposed UPS configuration is ___nos of ___KVA operating in standalone configuration or parallel
redundant configuration with ___minutes backup time using sealed maintenance free VRLA battery on each
UPS.
Operation Modes
“Normal” Mode: This is the most frequent operating condition. The energy is drawn from the primary mains
power supply and is converted and used by the inverter to generate the output voltage to power the loads
connected. The inverter is constantly synchronised with the auxiliary mains to enable load transfer (due to an
overcurrent or inverter shutdown) without any break in the power supply to the load. The battery charger
supplies the energy required to maintain or recharge the battery.
Bypass Mode: In case of inverter failure, the load is automatically transferred onto the auxiliary mains without
any interruption in the power supply. This procedure may occur in the following situations:
• In the event of a temporary overload, the inverter continues to power the load. If the condition persists,
output is switched onto the auxiliary mains via the automatic bypass.
• Normal operation, which is from inverter, returns automatically a few seconds after the overload
disappears.
• When the voltage generated by the inverter goes out of tolerances due to a major overload or a fault on
the inverter
• When the internal temperature exceeds the maximum value allowed.
GUIDE SPECIFICATIONSTRANSFORMER BASED
© Copyrights Reserved
22-3
Battery mode: In the event of a mains failure (micro interruptions or extended black-outs), UPS continues to
power the load using the energy stored in the battery. The expert battery system keeps the user constantly
informed on the battery status and on the remaining backup time adapted permanently according to the
battery capacity and the load rate.
Mechanical Characteristics
The UPS and batteries shall be installed in cabinet(s) with an IP-20 degree of protection
(standard IEC 60529)
The system shall be of modular construction and access to the subassemblies making up the system shall
be exclusively through the front.
System cooling shall be by forced air ventilation and be equipped with a redundant ventilation
© Copyrights Reserved
GUIDE SPECIFICATIONSTRANSFORMER BASED
• The UPS system shall be of online, double conversion type conforming to IEC 62040-3
• The general & safety requirements of the UPS system shall be complied with IEC 62040-1
• The system shall be classified as VFI-SS-III as per IEC 62040 such that UPS output is independent of
supply mains voltage and frequency variations
• The UPS system shall be designed to interface & operative with generator or EB mains to maintain an
uninterrupted power to the loads
• The UPS System shall be constructed in heavy duty metal enclosures and designed for floor mounting
• All materials and parts comprising the UPS shall be new, of current manufacture of high grade and free
from all imperfections and shall not have been in prior service, expect as required during factory testing.
• The UPS modules shall not incur permanent damages to itself or loads under all predictable fault
conditions
• Static transfer switch shall be provided in the UPS. In the event of failure of UPS, the loads should be
supported by static bypass without interruption
Functional & Performance Requirement
The UPS, not including the battery, shall be capable of operating under the following environmental
conditions without loss of performance:
• Temperature range during continuous operation: 0°C to 40°C(without derating)
• Maximum relative humidity: 95%
• Maximum altitude without derating: 1000 m.
• Noise level: <75 dbA
Environment Conditions
22-4
• The inverter shall be a transistorized solid state type, IGBT, which is designed with SVM Modulation
Technology
• The battery shall be equipped with a self-test that can be run manually or automatically according to
user-set time intervals and with configurable discharge power.
• The UPS system should have an provision to perform equalisation charging automatically on a predefined
interval to maintain the healthiness of the battery
• The UPS system should be able to deliver 10% more power at 25 deg C
• The UPS shall have selfregulating and selfprotection against following conditions
• Overvoltage
• Powerline surges
• Under voltage and overcurrent induced by the mains
• Sudden changes in the output load and short circuits at the output
• Transient, surges, voltage spikes shall be suppressed and shall be removed from the
output of UPS
• The overall AC-AC efficiency of the UPS shall not be less than 94%. The efficiency shall be measured
under the following conditions
• The UPS System is operating at 50% load
• The battery is fully charged and floating on the system
• The input voltage is within the specifications
• The load power factor shall be 0.9 lagging
• The UPS system shall comply with IEC 62040-2 for electromagnetic compatibility requirements
• UPS shall be compatible to take nonlinear loads and capable to handle high crest load.
• UPS shall be provided with a harmonic of less than 5% and input PF of 0.99.
• The UPS shall be designed to work in following environmental conditions:
• Operating temperature 0-40 deg C, continuously
• Relative humidity 0-95%
• Storage temperature: - 25°C to 50°C
• Operating altitude 1000 m above MSL
• The battery charger of the UPS should be able to adapt the battery charging based on the
real time information of the status or condition of battery in terms of temprature, battery voltage,
charge status etc.
• UPS shall be designed for minimumover load of 150% for 1 mins and 125% for 10 mins
• The rectifier should meet with the following specification in addition to other requirements stated herein.
• Input RYB phase reversal protection and correction circuit to be provided as standard to avoid UPS
transferring to battery mode in case of phase sequence change at input. The UPS should continue to
work in mains mode. (If the input phase is interchanged, even then UPS has to work in double
conversion mode without changing to battery mode)
© Copyrights Reserved
GUIDE SPECIFICATIONSTRANSFORMER BASED
22-5
• The inverter shall be a transistorized solid state type, IGBT, which is designed with SVM Modulation
Technology
• The battery shall be equipped with a self-test that can be run manually or automatically according to
user-set time intervals and with configurable discharge power.
• The UPS system should have an provision to perform equalisation charging automatically on a predefined
interval to maintain the healthiness of the battery
• The UPS system should be able to deliver 10% more power at 25 deg C
• The UPS shall have selfregulating and selfprotection against following conditions
• Overvoltage
• Powerline surges
• Under voltage and overcurrent induced by the mains
• Sudden changes in the output load and short circuits at the output
• Transient, surges, voltage spikes shall be suppressed and shall be removed from the
output of UPS
• The overall AC-AC efficiency of the UPS shall not be less than 94%. The efficiency shall be measured
under the following conditions
• The UPS System is operating at 50% load
• The battery is fully charged and floating on the system
• The input voltage is within the specifications
• The load power factor shall be 0.9 lagging
• The UPS system shall comply with IEC 62040-2 for electromagnetic compatibility requirements
• UPS shall be compatible to take nonlinear loads and capable to handle high crest load.
• UPS shall be provided with a harmonic of less than 5% and input PF of 0.99.
• The UPS shall be designed to work in following environmental conditions:
• Operating temperature 0-40 deg C, continuously
• Relative humidity 0-95%
• Storage temperature: - 25°C to 50°C
• Operating altitude 1000 m above MSL
• The battery charger of the UPS should be able to adapt the battery charging based on the
real time information of the status or condition of battery in terms of temprature, battery voltage,
charge status etc.
• UPS shall be designed for minimumover load of 150% for 1 mins and 125% for 10 mins
• The rectifier should meet with the following specification in addition to other requirements stated herein.
• Input RYB phase reversal protection and correction circuit to be provided as standard to avoid UPS
transferring to battery mode in case of phase sequence change at input. The UPS should continue to
work in mains mode. (If the input phase is interchanged, even then UPS has to work in double
conversion mode without changing to battery mode)
© Copyrights Reserved
Nominal voltage 415 V, 3 - phase
Voltage range ±15% (AC)
Nominal frequency 50 Hz
Frequency range ± 5% (± 2.5 Hz)
Input power factor 0.98 lagging or more at full load (pf improvement)
Input harmonic current THD <5% typical 100% load <8% maximum at 50% load
Cooling Forced cooling using
Progressive walk in Should be present
Phase Sequence Should have inbuilt phase sequence correction
• The battery may be taken out of service for maintenance, during period it shall be possible for the
inverter to continue operation by drawing power from the rectifier. Ripple content at the DC link
shall not exceed 2% even with battery disconnected
• The rectifiers / chargers shall be designed to completely charge the battery in a maximum time of 8 to
10 hours (Refer datasheet) after complete discharge. Facilities shall be provided to initiate battery
boost charge operation by Manual or automatic means.
• Boost and float charging shall be automatically controlled to recharge the battery to 100% capacity.
After battery is fully charged or after a pre-selected time (adjustable through 0 - 24 hours timer)
whichever is earlier – the unit shall revert to float charge mode automatically. Also charge voltage
compensation for the battery operating temperature shall be provided.
• The UPS should be capable of performing an automatic equalisation charging of the battery to
improve the performance of battery
• The rectifier should meet the following specifications in addition to other requirements stated herein.
• The battery shall be of sealed maintenance free battery and shall be designed to support a full load for
mins.An output power factor of 0.9 has to be considered for battery sizing with an ageing factor of
0.8 at an end cell voltage of 1.7V/cell
• A battery charging current of 10% of offered AH capacity has to be provided for battery charging.
GUIDE SPECIFICATIONSTRANSFORMER BASED
22-6
Inverter technology
Voltage input
Nominal voltage output 415V,3 Phase,4 wire
Output power factor 0.9(min)
Inverter capacity KVA/KW
Voltage regulation
For 0 to 100% loading Less than ± 1%
Less than ± 1%
Environmental conditions given below Less than ± 1%
Transient voltage regulation
At 100% step load change Less than ± 5%
At loss of return of AC input Less than ± 5%
At load transfer from bypass to inverter Less than ± 5%
Time to recover from transient to normal voltage
<20 milliseconds
Wave form Pure Sinusoidal
Normal frequency 50 Hz
Frequency regulation for all conditions of
supplies, loads and temperature occurring
simultaneously or in any combination
(automatically controlled)
Synchronization limit for synchronization between inverter and standby AC source
49 Hz to 51 Hz
Field adjustment range for above 50±0.25 Hz to 50±1.5 Hz
Less than 2% THD fo linear load
Less than 2% THD for non - linear load
Duty Continuous
Cooling Forced cooling using fans
Total voltage harmonic distortion
The inverter should meet the following specifications in addition to other requirements
stated herein.
© Copyrights Reserved
Short circuit capability on inverter (phase
to phase, phase to netural, phase to
ground & 3 Phase)
Should be min 2.5 times the rated
current for 100 ms
Inverter DC input voltage varies frommaximum to minium
Range as per manufacuture design,
maximum DC bus voltage during
charging the batteries.
Shall be a transistorized solid
state type
Yes
22-7
Control Annunciation and Indication Devices: The UPS system shall have LCD Display for
monitoring the parameters and status of alarm. The UPS shall be provided with a mimic diagram
on the front door of cubicle housing the system.
Indications The following shall be provided:
• Monitoring of AC input voltage
• Monitoring of DC bus voltage
• Monitoring of DC charging/discharging current from the battery.
• Monitoring of output line voltage
• Monitoring of output line current
• Monitoring of input and output frequency
• Monitoring of AC bypass input voltage
• Monitoring of output power
Indications: Each UPS module shall be equipped with a mimic to indicate power flow to the critical
load along with an indication of the availability of the rectifier/charger, battery, automatic bypass,
inverter, and load. The mimic shall provide a quick and easy indication of the load level
(displayed on LCD), including for overload conditions (displayed on LCD). This power flow is
also shown in the LCD menu.
The display unit shall display the following UPS operational status
• Normal operation, load power ___%
• Battery operation, time ___minutes.
• Bypass operation.
• Standby
• LED indications for load level battery autonomy
• Indication Lamp shall be provided for Red LEDs shall be provided for ON indication,
Green for OFF indication and Amber for fault indication, Main ON, Battery ON, Inverter ON, and
low battery
© Copyrights Reserved
22-8
Annunciations :
Alarm annunciation shall be provided using either LED indicators or LCD display for depiction of fault
conditions in the UPS system along with audible alarm. The system shall have 'accept', 'reset' and 'test'
facility over separate push buttons. The annunciation system shall cover the faults described earlier for the
entire UPS system including in the following
• Overload
• DC overvoltage
• Emergency shutdown
• Rectifier fault
• Battery low condition
• Mains failure
• Cooling fan failure, where provided
• Fuse failure
• Static bypass ready/fault
• Static bypass inhibited
• Inverter fault
• Output voltage error
• UPS fail
• Short circuit
• Battery charging
System Earthing and Equipment Earthing
Two independent and distinct earth electrodes shall be provided for equipment earthing of UPS connections
comprising 50 x 6-mm GI strips/or as required/approved. Each of these earth electrodes shall
comprise a GI plate as per Code of Practice for Earthing IS 3043-1987 (latest version).
Testing and Commissioning
The UPS shall be thoroughly checked for correct operation and load tested in supplier works before
dispatch. All faults, control functions and site load conditions shall be simulated, checked and proved. The
equipment shall be dispatched after testing in presence of authorized representative of purchaser.
The UPS system should have intelligent test characteristic to perform a heat run test at full load and part
loads without any additional load bank.
The UPS should also have an inbuilt function to perform a discharge test of the battery without any need of
additional load bank.
© Copyrights Reserved
22-9
1 RATING KVA UPS
No.of set
Reference no. Vendor to Specify
Make Vendor to Specify
Model Vendor to Specify
2 INPUT
2.1 Nominal voltage
2.2
2.3
2.4
3
Frequency
< 5% on full load
OUTPUT
3.1 Voltage Configuration
3.2 Voltage Harmonic
3.3 Over load
3.4 Load power factor
3.5 Waveform True sine wave
3.6 Load CF
3.7
Vendor to specify
3.8 Duty Continuous
3.9 Static voltage regulation plus or minus 1%
FICHTNER CONSULTING E NGINEERS
FICHTNER CONSULTING E NGINEERS
FICHTNER CONSULTING E NGINEERS
3.10
3.11 Efficiency >92%
3.12
RECTIFIER
4.1 Type IGBT
© Copyrights Reserved
Datasheet
Description
Vendor to specifySl. No.
Three Phase : 415V, 3Phase+
Netural + Ground with +/-
15% tolerance
50 Hz(+/-3%)
Input Power Factor
Input harmonic Current
0.99
Three Phase : -415 V, # Phase
+Netural + Ground
<3% for linear & <5% for Non
linear Load.
< or =125% for 10 mins, <or
=150%for 60 sec
0.9 lag to unity within
KVA & KW rating
3:1
Dynamic response to 100% load Step
Max. Output current loading @ 0.9 PF Vector to specify( in AMP.)
Ripple voltage of battery Vendor to Specify
22-10
5.1
5
Type
CHARGER
For IGBT
5.2 Nominal voltage regulation +/-1%
5.3 Ripple (Without battery) < 1%
5.4 Charging method Constant Voltage Constant Current (CVCC)
5.5 Max. Charging Current Vendor to specify
5.6 Charger Protection
5.6.1 DC over current Required
5.6.2 DC over voltage Required
5.6.3 Input over voltage Required
5.6.4 Input under voltage Required
5.6.5 Battery charger rating Vendor to specify
5.6.5 Battery charging duration Vendor to specify
5.6.6 Phase Sequence Correction Required
5.6.7
6 BATTERY
6.1 Battery voltage 12 V
6.2
6.3 Battery capacity (in AH) Vendor to specify
6.4 Battery bus voltage - V DC Vendor to specify
6.5 Battery make
6.6 Battery Rack dimensions L x W X H (in mm )
6.7 Rack weight with battery (in Kgs) Vendor to specify
6.8 Battery circuit breaker Vendor to specify
6.9 0.9
6.10 Ageing factor 1.25
6.11 End cel voltage 1.7V
© Copyrights Reserved
7 INVERTER IGBT based space vector
modulation with inbuilt
transformer INVERTER PROTECTION
7.1 Low battery voltage Required
7.2 Output short circuit Required
Power factor Considered ofbattery sizzing
Type
Automatic Equalisation charging ofBattery
Sealed Maintenance Free(SMF)
22-11
© Copyrights Reserved
7.3 Output over curent Required
7.4 Output over voltage Required
7.5 Output under voltage Required
7.6 Thermal protection Required
8 BYPASS STATIC SWITCH SCR based, Bi directional ,
make before break type, fully
electronic.
8.1 Transfer (Inverter to bypass) In Sync.Mode – No break in transfer
8.2 Retransfer (Bypass to inverter)
9 MANUAL BYPASS FACILITY
9.1 Changeover from bypass to
manual bypass
Without break.
10 EFFICIENCY
SPECIFIC OVERLOAD TIME
ENVIRONMENTAL
10.1 Inverter Efficiency (DC to AC) Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
10.2
10.3
10.4
10.5
10.6
11
11.1
11.2
11.3
11.4
11.5
12
12.1
12.2
12.4 Humidity
12.5 Altitude
50 Deg C ambient designwithout derating
Upto 955 RH, Non-
condensing
13 PHYSICAL
13.1 Class IP 20
13.2 Forced Air
Enclosure Protection Grade
Cooling
In Asysnc.Mode- <5mSecIn Sync.Mode - No break inretransfer
(At full load & nominal inputVoltage)
Conv.Efficiency(AC to Dc)
Overall Efficiency(AC to AC)
At 50% load capacity
At 75% load capacity
At 110% Load
At 125% Load
At 150%Load
At 200%Load
At 250%Load
Acoustic noise level <65db @ 1 Mtr.
At 100% load capacity
Design temperature
13.3 Colour 13.4 Cable entry Bottom 13.5 Weight in Kg.
13.6
13.7
13.8
14
14.1
14.2
14.3
14.4
14.5
14.6
14.7
14.8
14.9
15
in
16
17
17.1
Type of I / P termination for UPS
ADDITIONAL FEATURES
Software for AC monitoring
14.10
14.11
14.12
14.13
14.14
17.2
17.3
17.4
17.5
17.6
17.7
17.8
18 OTHERS
18.1
22-12
© Copyrights Reserved
Inbuilt output isolation
transformer for individual UPS
Vendor to specify
Vendor to specify
Vendor to specify
Vendor to specify
Dimensions (in mm)(W x D x H)
Thickness of enclosure
Bottom farme with sufficientload bearing capacity
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
Required
METERING & DISPLAY
LCD DISPLAY
Input voltage
Output voltage
Output current
Input current
Power factor
Power (in Kw)
Output power (in Kw)
Load in %
Fault type
Frequency output
Frequency (Input or bypass)
DC voltage
DC current
Comprehensive LED Mimicrequired with the single linepower flow diagram
Vendor to specify
Vendor to specify
MODBUS protocol require
999 event data logger with date & time
Transisent voltage surgeprotection at UPS input
Maintenance bypass switch
Inbuilt incoming and outgoingisolator
Cable from battery bank tobattery circuit breaker
battery bank isolator (MCCB)
Cable from battery bank tobattery circuit breaker
Testing of UPS & battery without Vendor scope, any additional loadbank at full load and part loads
Vendor scope
Vendor to specifythe rating and model
Vendor to specifyand the required cable shallbe in the scope of vector
Scope:
This general specification lays down the functional requirements, performance characteristics, quality of
installation required for uninterruptable power supply(UPS)
Description of the system
The UPS system shall consist of rectifier/charger, batteries, inverter, static bypass, manual bypass,
protective devices and accessories that automatically provides continuous supply of electric power to its
load within the tolerance as set out in this specifications.
Project Requirement:
The critical loads covering the process load IT equipment, desktops and essential services will be backed
by the proposed UPS.
The proposed UPS configuration is nos of KVA operating in standalone or parallel configuration with
X minutes backup time using sealed maintenance free VRLA battery on each UPS
Operation Modes
“Normal” Mode: This is the most frequent operating condition. The energy is drawn from the primary mains
power supply and is converted and used by the inverter to generate the output voltage to power the loads
connected. The inverter is constantly synchronised with the auxiliary mains to enable load transfer (due to
an overcurrent or inverter shutdown) without any break in the power supply to the load. The battery charger
supplies the energy required to maintain or recharge the battery.
Bypass Mode: In case of inverter failure, the load is automatically transferred onto the auxiliary mains
without any interruption in the power supply. This procedure may occur in the following situations:
• In the event of a temporary overload, the inverter continues to power the load. If the condition
persists, output is switched onto the auxiliary mains via the automatic bypass.
• Normal operation, which is from inverter, returns automatically a few seconds after the
overload disappears.
• when the voltage generated by the inverter goes out of tolerances due to a major overload
or a fault on the inverter
• when the internal temperature exceeds the maximum value allowed.
GUIDE SPECIFICATIONSTRANSFORMERLESSUPS
22-13
© Copyrights Reserved
22-14
Battery Mode: In the event of a mains failure (microinterruptions or extended blackouts), UPS continues to
power the load using the energy stored in the battery. The Expert Battery System keeps the user constantly
informed on the battery status and on the remaining back-up time adapted permanently according to the
battery capacity and the load rate.
Mechanical Characteristics
• The UPS and batteries shall be installed in cabinet(s) with an IP 20 degree of protection
(standard IEC 60529)
• The system shall be of modular construction and access to the subassemblies making up the system
shall be exclusively through the front.
• System cooling shall be by forcedair ventilation and be equipped with a redundant ventilation
Environment Conditions
The UPS, not including the battery, shall be capable of operating under the following environmental
conditions without loss of performance:
• Temperature range during continuous operation: 0°C to 40°C
• Maximum relative humidity: 95%
• Mmaximum altitude without derating: 1000 m.
• Noise level: <70 dbA
© Copyrights Reserved
GUIDE SPECIFICATIONSTRANSFORMER LESSUPS
Battery Mode: In the event of a mains failure (microinterruptions or extended blackouts), UPS continues to
power the load using the energy stored in the battery. The Expert Battery System keeps the user constantly
informed on the battery status and on the remaining back-up time adapted permanently according to the
battery capacity and the load rate.
Mechanical Characteristics
• The UPS and batteries shall be installed in cabinet(s) with an IP 20 degree of protection
(standard IEC 60529)
• The system shall be of modular construction and access to the subassemblies making up the system
shall be exclusively through the front.
• System cooling shall be by forcedair ventilation and be equipped with a redundant ventilation
Environment Conditions
The UPS, not including the battery, shall be capable of operating under the following environmental
conditions without loss of performance:
• Temperature range during continuous operation: 0°C to 40°C
• Maximum relative humidity: 95%
• Mmaximum altitude without derating: 1000 m.
• Noise level: <70 dbA
22-15
© Copyrights Reserved
• The UPS System shall be of online, double conversion type conforming to IEC 62040-3
• The general & safety requirements of the UPS system shall be complied with IEC 62040-1
• The system shall be classified as VFI-SS-III as per IEC 62040 such that UPS output is
independent of supply mains voltage and frequency variations
• The UPS system shall be designed to interface & operative with generator or EB mains to
maintain an uninterrupted power to the loads
• The UPS System shall be constructed in heavy duty metal enclosures and designed for floor
mounting
• All materials and parts comprising the UPS shall be new, of current manufacture of high
grade and free from all imperfections and shall not have been in prior service, expect as required
during factory testing.
• The UPS modules shall not incur permanent damages to itself or loads under all predictable
fault conditions
• Static transfer switch shall be provided in the UPS.In the event of failure of UPS, the loads
should be supported by static bypass without interruption
• The Inverter shall be a transistorized solid state type, IGBT, which is designed with SVM
modulation technology
• The battery shall be equipped with a self-test that can be run manually or automatically
according to user-set time intervals and with configurable discharge power.
• The UPS system should have an provision to perform equalisation charging automatically
on a predefined interval to maintain the healthiness of the battery
• The UPS system should be able to deliver 10% more power at 25 deg C
• The UPS shall have self-regulating and self-protection against following conditions
Functional & Performance Requirement
• The overall AC-AC efficiency of the UPS shall not be less than 95%. The efficiency shall be
measured under the following conditions
• The UPS system is operating at 50% load
• The battery is fully charged and floating on the system
• The input voltage is within the specifications
• The load power factor shall be 0.9 lagging
GUIDE SPECIFICATIONSTRANSFORMER LESSUPS
• Over voltage
• Powerline surges
• Undervolatge and overcurrent induced by the mains
• Sudden changes in the output load and short circuits at the output
• Transient surges,voltage spikes shall be suppressed and shall be removed from
the output of UPS
• The battery shall be of sealed maintenance free battery and shall be designed to support a full load for
X mins. An output power factor of 0.9 has to be considered for battery sizing with an ageing factor of
0.8 at an end cell voltage of 1.7V/cell
• A battery charging current of 10% of offered AH capacity has to be provided for battery charging.
• The battery may be taken out of service for maintenance, during which period it shall be possible for
the inverter to continue operation by drawing power from the rectifier. Ripple content at the DC link shall
not exceed 2% even with battery disconnected
• The rectifiers/chargers shall be designed to completely charge the battery in a maximum time of 8 to
10 hours (Refer datasheet) after complete discharge. Facilities shall be provided to initiate battery
boost charge operation by manual or automatic means.
• Boost and float charging shall be automatically controlled to recharge the battery to 100% capacity.
After battery is full charged or after a pre-selected time (adjustable through 0- 24 hours timer) whichever
is earlier, the unit shall revert to float charge mode automatically. Also charge voltage compensation for
the battery operating temperature shall be provided.
• The rectifier should meet the following specifications in addition to other requirements stated herein.
Nominal voltage
Voltage range +15% (AC)
Nominal frequency 50 Hz
Frequency range ± 5% (± 2.5 Hz)
Input power factor 0.98 lagging or more at full load (pf improvement)
Input harmonic current THD <5% typical at 100% load <8% maximum at 50% load
Cooling Forced cooling using fans.
Progressive walk in Should be present
Phase Sequence Should have inbuilt phase sequence correction
22-16
© Copyrights Reserved
GUIDE SPECIFICATIONSTRANSFORMER LESSUPS
415 v, 3 - Phase
Inverter technology Shall be a transistorized solid state
type
Voltage input
Range as per manufacturer design,
maximum DC bus voltage during
charging the batteries.
Nominal voltage output 415V, 3 Phase, 4 wire
Output power factor 0.9(min)
Inverter capacity ___ KVA /___KW
Voltage regulation
For 0 to 100% loading Less than ± 1%
Inverter DC input voltage varies from
maximum to minimum Less than ± 1%
Environmental conditions given below Less than ± 1%
Transient voltage regulation
At 100% step load change Less than ± 5%
At loss of return of AC input Less than ± 5%
At load transfer from Bypass to Inverter Less than ± 5%
Time to recover from transient to normal
voltage <20 milliseconds
Waveform Pure Sinusoidal
Normal frequency 50 Hz
Frequency regulation for all conditions of
input supplies, loads and temperature
occurring simultaneously or in any
combination (automatically controlled)
Yes
Synchronization limit for synchronization
between inverter and standby AC source 49 Hz to 51 Hz
Field adjustment range for above 50±0.25 Hz to 50±1.5 Hz
Total voltage harmonic distortion Less than 2% THD for linear load
Less than 4% THD for non -linear load
Duty Continuous
Cooling Forced cooling using fans
Short circuit capability on inverter (phase
to phase, phase to neutral, phase to
ground & 3 Phases)
Should be min 2.5 times the rated
current for 100 ms
The inverter should meet the following specifications in addition to other requirements
stated herein.
22-17
© Copyrights Reserved
Control Annunciation and Indication Devices: The UPS system shall have LCD Display for monitoring the
parameters and status of alarm. The UPS shall be provided with a mimic diagram on the front door of cubicle
housing the system.
Indications : The following shall be provided
• Monitoring of AC input voltage
• Monitoring of DC bus voltage
• Monitoring of DC charging/discharging current from the battery.
• Monitoring of output line voltage
• Monitoring of output line current
• Monitoring of input and output frequency
• Monitoring of AC bypass input voltage
• Monitoring of output power
Indications: Each UPS module shall be equipped with a mimic to indicate power flow to the critical load along
with an indication of the availability of the rectifier/charger, battery, automatic bypass, inverter and load. The
mimic shall provide a quick and easy indication of the load level (displayed on LCD), including for overload
conditions (displayed on LCD). This power flow is also shown in the LCD menu.
© Copyrights Reserved
22-18
Annunciations :
Alarm annunciation shall be provided using either LED indicators or LCD display for depiction of fault
conditions in the UPS system along with audible alarm. The system shall have 'accept', 'reset' and 'test'
facility over separate push buttons. The annunciation system shall cover the faults described earlier for the
entire UPS system including in the following
• Overload
• DC overvoltage
• Emergency shutdown
• Rectifier fault
• Battery low condition
• Mains failure
The display unit shall display the following UPS operational status
• Normal operation, load power ___%
• Battery operation, time ___minutes.
• Bypass operation.
• Standby
• LED indications for load level battery autonomy
• Indication lamp shall be provided for Red LEDs shall be provided for ON indication,
Green for OFF indication and Amber for fault indication, Main ON, Battery ON, Inverter ON, and
low battery
22-19
• Cooling fan failure, where provided
• Fuse failure
• Static bypass ready/fault
• Static bypass inhibited
• Inverter fault
• Output voltage error
• Ups fail
• Short Circuit
• Batterycharging
System Earthing and Equipment Earthing
Two independent and distinct earth electrodes shall be provided for equipment earthing of UPS
connections comprising 50x6-mm GI strips/ or as required/ approved. Each of these earth electrodes shall
comprise a GI plate as per Code of Practice for Earthing IS 3043-1987 (latest version)
Testing and Commissioning
The UPS shall be thoroughly checked for correct operation and load tested in supplier works before
dispatch. All faults, control functions and site load conditions shall be simulated, checked and proved. The
equipment shall be dispatched after testing in presence of authorized representative of purchaser.
The UPS system should have intelligent test characteristic to perform a heat run test at full load and part
loads without any additional load bank
The UPS should also have an inbuilt function to perform a discharge test of the battery without any need of
additional load bank.
© Copyrights Reserved
SR.
NO. DESCRIPTION
Vendor to
specify
1 RATING KVA UPS
No. of set
Reference no. Vendor to specify
Make Vendor to specify
Model Vendor to specify
2 INPUT 2.1 Nominal voltage Three Phase : 415 V, 3Phase + Neutral +
Ground with +/ - 15% tolerance
2.2 Frequency 50 Hz( +/ -3%)
2.3 Input power factor 0.99 2.4 Input harmonic
current
< 5% on full load
3 OUTPUT
3.1 Voltage
Configuration Three Phase : -
415 V, 3Phase + Neutral + Ground
3.2 Voltage Harmonic <3% for linear & <5% for non linear load. 3.3 Over load < or =125% for 10 mins, <or =150% for 60
sec
3.4 Load Power Factor 0.9 lag to Unity within KVA & KW rating
3.5 Waveform True sinewave 3.6 Load CF 3 : 1
FICHTNER
CONSULTING E NGINEERS
FICHTNER
CONSULTING E NGINEERS
FICHTNER
CONSULTING E NGINEERS
FICHTNER
CONSULTING E NGINEERS
FICHTNER
CONSULTING E NGINEERS
FICHTNER
CONSULTING E NGINEERS
FICHTNER
CONSULTING E NGINEERS
FICHTNER
CONSULTING E NGINEERS
3.7 Dynamic response
to 100% load step
Vendor to specify
3.8 Duty Continious 3.9 Static voltage
Regulation
Plus or minus 1%
3.10 Max. output current
loading @ 0.9 PF
Vendor to specify( in Amp.)
3.11 Efficiency >92% 3.12 Ripple voltage of
Battery
Vendor to specify
4 RECTIFIER 4.1 Type IGBT
22-20
© Copyrights Reserved
22-21
6.7 Rack weight with
battery(in Kgs)
Vendor to specify
6.8 Battery circuit
breaker
Vendor to specify
6.9 Power Factor
Considered for
battery Sizing
0.9
6.10 Ageing factor 1.25 6.11 End Cell Voltage 1.7V
5 CHARGER
5.1 Type For IGBT 5.2 Nominal Voltage
Regulation
+/ - 1%
5.3 Ripple (Without
Battery)
< 1%
5.4 Charging method Constant Voltage Constant Current
(CVCC)
5.5 Max. charging
Current
Vendor to specify
5.6 CHARGER PROTECTION
5.6.1 DC over current Required 5.6.2 DC over voltage Required
5.6.3 Input over voltage Required
5.6.4 Input under voltage Required 5.6.5 Battery charger
rating
Vendor to specify
5.6.5 Battery charging
duration
Vendor to specify
5.6.6 Phase Sequence
Correction
Required
5.6.7 Automatic
Equlisation charging
of battery
Required
6 BATTERY
6.1 Battery voltage 12 V 6.2 Type Sealed Maintenance Free(SMF)
6.3 Battery capacity (in
AH)
Vendor to specify
6.4 Battery bus voltage - V DC
Vendor to specify
6.5 Battery Make
6.6 Battery Rack
dimentions
L X W X H (in mm)
© Copyrights Reserved
22-22
7
INVERTER
IGBT based Space vector modulation
INVERTER PROTECTION
7.1 Low battery voltage Required
7.2 Output short circuit Required
7.3 Output over curent Required
7.4 Output over voltage Required
7.5 Output under
voltage
Required
7.6 Thermal protection Required
8 BYPASS STATIC SWITCH
SCR based, Bi directional , make before
break type, fully electronics.
8.1 Transfer (Inverter to
bypass)
In Sync.Mode – No break in transfer
In Async.Mode - < 5mSec
8.2 Retransfer (Bypass
to Inverter)
In Sync.Mode – No break in Retransfer
9 MANUAL BYPASSFACILITY
9.1 Changeover from
static bypass to
manual bypass
Without break.
10 EFFICIENCY (At full load & nominal input voltage)
10.1 Inverter efficiency
(DC to AC)
Vendor to specify
10.2 Conv. efficiency (AC
to DC)
Vendor to specify
10.3 Overall
efficiency(AC to AC)
Vendor to specify
10.4 at 50% load
capacity
Vendor to specify
10.5 at 75% load
capacity
Vendor to specify
10.6 at 100% load
capacity
Vendor to specify
11 SPECIFIC
OVERLOAD TIME
11.1 at 110% Load Vendor to specify
11.2 at 125% Load Vendor to specify
11.3 at 150% Load Vendor to specify
11.4 at 200% Load Vendor to specify
11.5 at 250% Load Vendor to specify
© Copyrights Reserved
22-23
12 ENVIRONMENTAL
12.1 Acoustic noise
level
< 65db @ 1 Mtr.
12.2 Design
temperature
50 Deg C Ambient design without
derating
12.4 Humidity Up to 95% RH, Non Condensing
12.5 Altitude
13 PHYSICAL
13.1 Enclosure
protection grade
Class IP 20
13.2 Cooling Forced Air
13.3 Colour Vendor to Specify
13.4 Cable entry Bottom
13.5 Weight in Kg. (Vendor to specify)
13.6 Dimensions (in mm)
(W x D x H)
( Vendor to specify)
13.7 Thickness of enclosure
(Vendor to specify)
13.8 Bottom frame with
sufficient load
bearing capacity
required.
14 METERING &
DISPLAY
LCD display Required
14.1 Input voltage Required
14.2 Input current Required
14.3 Power factor Required
14.4 Power (in Kw) Required
14.5 Output voltage Required
14.6 Output Current Required
14.7 Output power (in Kw)
Required
14.8 Load in % Required
14.9 Fault type Required
14.5 Frequency (Output) Required
14.6 Frequency (Input or bypass)
Required
14.7 DC Voltage Required
14.8 DC Current Required
14.9
Comprehensive LED
mimic required
with the single line
Power Flow
Diagram
Required
© Copyrights Reserved
15 Inbuilt output
isolation
transformer for
individual UPS
Required.
16 Type of I/P
Termination For UPS
Vendor to specify
17 ADDITIONAL FEATURES
17.1 Software For Pc
Monitoring
MODBUS protocol require
17.2 999 event data
logger with date &
time
Required.
17.3 Transient volatge
surge protection at
UPS input
Required.
17.4 Maintanance
bypass switch Required.
17.5 Inbuilt incoming
and outgoing
isolator
Required.
17.6 Cable from battery
bank to battery
circuit breaker
Cable from battery
bank to battery
circuit breaker
Vendor to specify
17.7 Battery bank
islolator (MCCB) Vendor to specify the Rating and model
17.8 Vendor to specify the cable and the
required cable shall be in the scope of
vendor
18 OTHERS
18.1 Testing of UPS &
battery without any
additional load
bank at full laod
and part loads
Vendor scope
22-24
© Copyrights Reserved
22-25
Description
The UPS shall consist of rectifier/charger, battery, inverter, static transfer switch, maintenance bypass
Switch, Synchronizing Equipment, Protective Device and other Accessories. The UPS shall provide
continuous electric power within specified tolerance, without interruption, to the critical loads.
Normally electrical energy from normal plant power source shall be supplied to UPS System.
The Solid State Rectifier/charger shall convert incoming AC power to DC power. The rectifier / charger
output shall be fed to Solid State Inverter. The inverter shall convert the DC power into AC power, which shall
supply the load.Upon failure of AC power, input power for inverter shall automatically be supplied from the
battery with no interruption/disturbance in inverter output in excess of limits specified herein (in these
specifications).
At the same time, UPS shall energize an alarm circuit. The duration for which Battery shall supply A/C power
to O/P shall be minimum 15 minutes.
When A/C power is restored, the input power for the inverter and for recharging the battery shall
automatically be supplied from rectifier / charger output without interruption/disturbance in inverter output
in excess of limits specified herein (in these specifications).
The Solid State Circuitry used for both rectifier & inverter shall be IGBT technology.
Intelligent RS-232 Communication shall be possible which will Provide UPS status indications, electrical
parameters such as Input & Output Voltage, Load levels etc and unattended shutdown.
User-friendly LCD Display to indicate all important UPS parameters such as input voltage, output voltage,
battery level and load level shall be provided.
The UPS system shall consist of the following modular architecture
MODULAR UPS SYSTEM
© Copyrights Reserved
MODULAR UPS SYSTEM
22-26
Bypass Mode: In case of inverter failure, the load is automatically transferred in to the auxiliary mains without
any interruption in the power supply. This procedure may occur in the following situations:
• In the event of a temporary overload, the inverter continues to power the load. If the condition
persists,output is switched in to the auxiliary mains via the automatic bypass.
• Normal operation, which is from inverter, returns automatically a few seconds after the overload
disappears.
• when the voltage generated by the inverter goes is out of tolerances due to a major overload
or a fault on the inverter
• when the internal temperature exceeds the maximum value allowed.
Battery Mode: In the event of a mains failure (micro interruptions or extended blackouts), UPS continues to
power the load using the energy stored in the battery. The expert battery system keeps the user constantly
informed on the battery status and on the remaining backup time adapted permanently according to the
battery capacity and the load rate.
ARCHITECTURE
© Copyrights Reserved
Operation Mode
“Normal” mode. This is the most frequent operating condition. The energy is drawn from the primary mains
power supply and is converted and used by the inverter to generate the output voltage to power the loads
connected. The inverter is constantly synchronised with the auxiliary mains to enable load transfer (due to
an overcurrent or inverter shutdown) without any break in the power supply to the load.The battery charger
supplies the energy required to maintain or recharge the battery.
The system should not have an centralised control modules, the control modules has to be built in each
power module to improve the reliability of the system
Static Switch
The modular UPS system that the bidders provide shall use concentrated bypass and the bypass module
shall be hot swappable. A built-in bypass shall be provided
Control Modules
Architecture
MODULAR UPS SYSTEM
Module Management:
The modular UPS shall offer the ability to scale its capacity and/or redundancy by automatically shifting load
to fewer power modules and selectively place unnecessary modules in the “hibernate mode” based on the
sensed output load level. This is in order to drive the load higher on the remaining modules. Therefore, with
multiple modules, a UPS shall achieve 2-3% higher efficiencies than conventional operation when loaded
less than 50% of system rating. In case of instantaneous addition of full load on the bus, this modules should
assume load without any interruption to the total load.
A power module shall not be restricted to any specific slot. Power modules can be installed without having
to pre-configure. Configuration shall be entirely automated.
Eco Mode:
In bypass operation, an even higher operating efficiency may be achieved without sacrificing protection
when there are good power conditions. Depending on configuration, efficiency can exceed 99%.The load
remains in bypass mode until the input voltage exceeds tolerance levels, and then enters full protection
mode. This setting is disabled by default and can be configured using the display.
22-27
© Copyrights Reserved
Scalable Power Modules
The system shall be comprised of 25/30 kVA power modules and shall be capable of being configured for
N+X redundant operation and power modules should be hot swappable to facilitate the scalability without
any disturbance to load.
Load Test at Site:
UPS should have the ability to perform a full load test in double conversion mode without the connection of a
load bank.
PHASE SEQUENCECORRECTION
22-28
© Copyrights Reserved
Phase Sequence Correction
The system should have inbuilt phase sequence correction and should continue to operate in mains mode.
The UPS system shall have LCD Display for monitoring the parameters and status of alarm. The UPS
shall be provided with a mimic diagram on the front door of cubicle housing the system. The failure of
display should not lead to the system failure. The system should work normally without the display.
Display and Metering
The overall AC-AC efficiency of the UPS shall be not be less than 95%.The efficiency shall be measured under
the following conditions
• The UPS System is operating at 50% load
• The battery are fully charged and floating on the system
• The input voltage is within the specifications
• The load power factor shall be 0.9 lagging
Efficiency
Environmental Conditions
The UPS shall be designed to work in following environmental conditions:
• Operating temperature 0-40 deg C
• Relative Humidity 0-95%
• Storage temperature : - 25°C to 50°C
• Operating altitude 1000m above MSL
Fault Tolerance:
The combination of the modular UPS and the parallel redundant architecture shall confine the component or
PCB failures to a single power module. The remainder of the system power modules shall not be affected and
shall continue to provide protection to the critical load. With the N+1 parallel redundant architecture, the UPS
faulty power module is isolated from the working units thus providing the system fault tolerance.
The display unit shall display the following UPS operational status
• Normal operation, load power ____% • Battery operation, time ____minutes. • Bypass operation.
• Standby
• LED indications for load level battery autonomy
Indication Lamp shall be provided for Red LEDs shall be provided for ON indication, Green for OFF
indication and Amber for fault indication, Main ON, Battery ON, Inverter ON, and Low Battery. Each power
module shall also have its own display, the following parameters of each power module.
• Monitoring of AC input voltage
• Monitoring of DC bus voltage
• Monitoring of DC charging/discharging current from the battery.
• Monitoring of output line voltage
• Monitoring of output line current
DISPLAY ANDMETERING
22-29
© Copyrights Reserved
Indications: Each UPS module shall be equipped with a mimic to indicate power flow to the critical
load along with an indication of the availability of the rectifier/charger, battery, automatic bypass,
inverter and load. The mimic shall provide a quick and easy indication of the load level (displayed on LCD),
including for overload conditions (displayed on LCD). This power flow is also shown in the LCD menu.
• Monitoring of AC input voltage
• Monitoring of DC bus voltage
• Monitoring of DC charging/discharging current from the battery.
• Monitoring of output line voltage
• Monitoring of output line current
• Monitoring of input and output frequency
• Monitoring of AC bypass input voltage
• Monitoring of output power
Reference Standards
ISOLATED POWERSUPPLY
22-30
© Copyrights Reserved
The static uninterruptible power system must be designed and produced in compliance with the following
international standards
• EN 62040-1 “General and safety requirements for UPS used in operator access areas"
• EN 62040-2 “Electro Magnetic Compatibility requirements (EMC)”
• EN 62040-3 “Performance requirements and test methods”
• Overload
• DC overvoltage
• Emergency shutdown
• Rectifier fault
• Battery low condition
• Mains failure
• Cooling fan failure, where provided
• Fuse failure
• Static bypass ready/fault
• Static bypass inhibited
• Inverter fault
• Output voltage error
• Ups fail
• Short circuit
• Battery charging
Alarm annunciation shall be provided using either LED indicators or LCD display for depiction of fault
conditions in the UPS system along with audible alarm. The system shall have 'accept', 'reset' and 'test'
facility over separate push buttons. The annunciation system shall cover the faults described earlier for
the entire UPS system including in the following
Annunciations :
Datasheet
The UPS system shall have nominal output voltage of 230/400V and shall be
designed for parallel ope ration with and charging of stationery batteries. The
UPS system must be double conversion online UPS to support the load
requirement 24x7 for number of years without any problem/ issue. The UPS
system shall include:
- Connection points for at least 2 st ring of batteries.
- UPS modules with a nominal output voltage of 230V/ 400V AC
- Battery charging automation.
- Control unit and User Display unit
- Static By pass unit with bypass voltage selectable
- Maintenance bypass unit
- Double conversion, IGBT converters, three level converters
Associated installation materials including connecting cables, runways etc.
complete set.
UPS capacity Modular UPS with installed capacity of 400 kVA or near (± 5%)
Power
saving/
Energy saving
technology
The UPS system must have module management system. This features works to
optimize the efficiency and maximum output .This system will automatically
suspend/ engages the modules based on the load requirement.
Rating
standard
IEC 62040 – 1, 2 & 3 for electrical safety, EMC and performance & voltage
stability in transient state
Hotswappable
The proposed UPS system should have features for the plug and play for all
parts during live operation
Requirement Must have equipped with both static bypass & maintenance bypass switch.
Bypass
Transfer
In case of major fault, the UPS must automatically transfer to static bypass
without much affecting the UPS system
Modular &
Scalable
The UPS system must be modular one with scalable & expandable. Modules are
connected in parallel and shall have a function for sharing the load equally.
Individual
Module
Capacity
The Capacity of individual module should not be more than 30 kVA
Efficiency
When designing the UPS modules as well as the entire UPS system, the criteria
should be good overall coefficient of efficiency. The target value shall be >95%
for the entire system when the load is >40% with double conversion and >98%
with energy saving mode.
Technology UPS must be double conversion online UPS with IGBT converters
Battery fuse
unit
The UPS system shall have at least 2 battery string connection and
corresponding connections for connecting batteries. An alarm signal indicating
blown battery fuse shall be send to the systems supervision unit
Parallel
operation The UPS system must support to make external paralleling of minimum 3 units
Surge
Protection
All connections of the modules (including alarm contacts) shall have overvoltage
protection. The system should be equipped with relavant SPD devices
Reverse
connection
protection
The UPS system shall be able to start if connected to a battery with the positive
and negative branch reversed, without taking any permanent damage
22-31
© Copyrights Reserved
Features &
Functional
SpecificationsEvaluation pointers Compliance
22-32
Construction The rack should be constructed with minimum of 1.6 mm thick steel sheet, dually powder coated after 7/10 tank process.
Equipment mounting
The inside mounting should be done in such a way that the cooling is not significantly hindered. The supplier must state the minimum distances between mounted cases in all direction. However the distance between cases and also
between any case and nearby walls must be not less than 60mm.
Ingress protection
The UPS system (any type) cabinet should be compatible to use for both indoor/ outdoor application. The recommended IP rating class for indoor is IP 21/22
Rated input voltage
Rectifier system 230/400V AC (Selectable 220 – 240V/ 380 – 430V) bypass System 230/400V AC (Selectable 220 – 240V/ 380 – 430V)
Voltage tolerance
range
280V – 480V ( -30%, +20%) at 70% load
Input frequency
50 Hz with tolerance level of 45 Hz to 55 Hz
Input THD % < 5% (non linear load) <1% (100% linear load)
Inrush current
Less than 100% of rated current
Input power factor
>0.99@full load
AC output 230/400, 220/ 380/ 240/ 415 Vac.configurable. If the input voltage will derate to 50% then output of the UPS should not derate more than 40% of actual
capacity.
Rated output frequency
50 Hz with maximum variation of ± 0.1 Hz slew rate of 1 Hz/s
Voltage stability
Should comply with IEC/ EN 62040 – 3, class 1 for transient state & ± 1% for steady state
Output voltage
distortion
Must be <1% for l inear load and <5% for Non - linear load
Load power factor
> 0.98 at 40% load or more
Short circuit capacity
200% of rated current
There should be Inrush current l imitation facility so that output current shall increase slowly to protect UPS system
Current l imitation
The UPS must have a provision for l imiting the output current from 20% to 100% of the full rated load (adjustable). However the UPS must be capable of withstanding 110% of full rated capacity.
Overload capacity
Capacity must be without Bypass. 10 min upto 125% Load and 1 Min for >125% load. Continuous runn ing upto 109% load.
UPS
controller
The UPS systems control unit shall supervise the different units in the UPS systems. It also control over the functional operation of the system for reliable
and smooth operation
UPS controller/ control system must control more modules if added to increase the capacity without any change in software configuration.
Display and
measurement
The control unit must be equipped with an alphanumeric LCD/ LED display and the language used in the display shall be english. The display unit must provide
the information related to UPS operation and electrical parameter. The same can be monitored via remote monitoring as well
Slow / Soft
Start of module
© Copyrights Reserved
22-33
Real time
remote
monitoring
The controller unit should have built in RMS for the designed power solution
capable of monitoring & controll ing UPS/battery/Load management to
ensure the proper or extend running of storage batteries and UPS system such
as load shedding, load sharing, charging batteries etc. All defined alarms and all
relevant par ameters must be readable from the display unit or dash board for
real time updates,PUE etc and monthly report extraction.
Control
interface
remote
monitoring
The UPS Controller unit should support all the connection interfaces to connect
remote monitoring & control to communicate with different supervision
management system via for performence & fault management system
• GSM modem
• RS/EIA485 (with modbus RTU protocol)
• CAN Bus
• SNMP/ TCPIP
SNMP Version
The control unit shall be compatible with the latest versions of SNMP:
- SNMPv2c, RFC1901-RFC1908
- SNMPv3, RFC3411 - RFC3418
MIB Version
The control unit shall be compatible with the latest MIB versions:
- MIB -I, RFC1156
- MIB -II, RFC1213
Communication
Protocol
The communication protocol for the proposed controller system must be open
and standard one compatible to any centralized monitoring system for
integration. This system must need to integrate to fault management system
Low voltage &
high voltage
protection
The control unit shall have a function for overvoltage/undervoltage protection. If the
system output voltage rises/ decreases above permitted value an alarm shall
be sent. The limit for the overvoltage protection and lower voltage shall be
adjustable. An alarm shall be activated in both the cases.
User Interface
Software
Supplier must have to provide user interface software for free of cost to
integrate in service engineer’s laptop for either site connection or remote
connection.
Alarm / event
log
Controller must be capable to store the history data for a minimum of 3 months
(more is better)
Sleep mode The controller should have sleep mode operation features for the UPS system
to reduce the energy consumption in case of less load demand
Periodic
charging
Periodic charging feature Provision for equalizing charge in order to keep the
batteries completely charged in case of long floating period must be available
Alarm test
facil ity
The facil ity for testing the general alarms and lamps shall be provided with the
power system in operation.
Switches and
function
adjustments
(i) It shall be possible to adjust and check the control l imits from the front side
of the UPS control system.
(i i) The following switches or similar functions shall be accessible in the control
unit:
• Start/stop UPS operation
• Reset of fault alarm
• Parameter setting
Alarm signals
The alarm signals generated by the UPS system/ power plant shall be
indicated to maintenance center/ NOC. Audible & visible alarm shall be
provided in the control unit panel. The alarm shall be sent via relays, modem
or LAN/WAN (i.e. TCP/IP), GSM, dry contact or equivalent to RMS connectivity
connection to different supervision management systems.
© Copyrights Reserved
• Output AC overvoltage/undervoltage
• Battery fuse tripped
• Grid/ Mains Failure
• UPS module not charging
• UPS module faulty
• Battery boost charging in progress
• Plug out alarm indication for UPS, fuse breakers etc.
• Battery discharging
• Battery undervoltage alarm
• Battery disconnect
• Mains overvoltage/ undervoltage
• Main phase missing
• UPS module fan fault
• High temperature
UPS system
controller
alarms
The UPS system controller should be compatible for the remote monitoring and
control features: Supplier to confirm.
Alarm
display/
Monitoring
All alarm shall produce both a local and remote indication. Remote indication is
given by a closing contact. Remote indications shall be wired to terminal blocks
Relay points
The UPS system shall have at least eight (12) relays for remote alarms. The relays
shall have potential free alarm contacts and change (shift) in case of alarm. All
possible alarms shall be freely configurable to the alarm relays
Lifting lock The UPS system shall have proper l ifting points and additional l ift pockets for
ease of transportation.
Disassembly
and assembly
(Optional)
The UPS system shall be preferably able to be split in portable, dismountable
parts for carrying the system in difficult terrain. By disassembling and
assembling of the internal components/ parts the warranty of the UPS system
should not be violated. The supplier shall state if disassembly and assembly is
possible by certified Implementation teams in the field.
Packaging
The UPS modules, the system and cabinets shall be packed in suitable, frame
reinforced packages that provide protection against dust and humidity and are
suitable for handling with fork lift trucks and transporting by lorry.The packages
shall bear the following outside markings on top and two sides:
"UPS system”, type and serial No.
Electrical
enviroment
The contractor shall provide to the buyer with approved test protocols of the
electrical safety and EMC tests of the equipment
Operating
temperature
UPS system completely should operate in full load condition in an ambient
temperature of 0°C to +45°C where as individual module can operate in an
ambient temperature of - 5°C to+50°C
Altitude(max) 1000m above sea level at 40°C . Max 2000 m with 1% derating per each
increasing 100m
22-34
© Copyrights Reserved
22-35
Transport &
storage
conditions
It shall be possible to transport and store the UPS systems without risk of
damage following conditions specified in ETSI EN 300 019 -1-2, Class 2.3. During
transport, the system must be able to withstand all ambient temperatures
ranging from - 20°C to +50°C for a maximum of 60 full days
Spare
The supplier must ensure the availability of the spares part for at least 10 years
or for 5 years after EoP (end of production) of offered equipment / product
model.
Service
Support
The bidder must have their offices/service partners at Nepal having experience on
similar field for 2 Years.
Warranty for
UPS system
The manufacturer warranty for the UPS system shall be a minimum of 2 Years.
Warranty will start from the date of PAC issued.
© Copyrights Reserved
ISOLATED POWERSUPPLY
22-36
© Copyrights Reserved
Design, Manufacture, Testing, Supply and supervision for installation and commissioning of 5KVA,
8KVA & 10KVA Medical Isolation Panel for OTs, ICU/ICCUs & NICUs as per IEC 60364-7-710 & BIS SP-30
Part-3 Section-IV consisting of following:
A medical ungrounded (IT) system shall be designed with 230VAC 63A, 10KA input MCB, Input Voltmeter
& Ammeter, 5KVA/8KVA/10KVA 230/230 VAC single phase Medical isolation transformer according to IEC
61558-2-15 (safety of power transformers, power supply units and similar – part 2 – 15: Particular
requirements for isolating transformers for the supply of medical locations.) in conformance to additional
requirements of IEC 60364-7-710 (Electrical installations of buildings – requirements of special installations
or locations – Medical locations) for low leakage at secondary side including provision for overload and high
conformance to IEC 61557-8 (Electrical safety in low voltage distribution systems upto 1000V AC and 1500
VDC – Equipment for Testing, Measuring or monitoring of protecvtive measures – part 8: Insulation monitoring
devices for IT systems.) and IEC 60364-7-710, 12nosof 230 VAC, 20A, 1KA, DP MCB for load distribution,
with on-line 12- channel insulation fault location system in conformance to IEC 61557-9 for medical locations.
All the above devices shall be installed and prewired in MS CRCS fabricated Panel painted to Grey Shade,
fan cooled, cable entry from top ready for installation at hospital premises. Separate Remote Alarm Indicator
for display of Insulation, transformer Overload and temperature alarm and other status indications at remote
suitable location.
1.0 Scope:
This specification covers the design and requirements for electrical safety in critical rooms (Group 2) like
Operation Theatres,
Intensive Care Units, Anaesthetic Rooms and Premature Baby Rooms in hospitals and medical
establishments as per
IEC 60364-7-710 and Provision P5 as per IS-SP30-Part 3Section 4-2011.
Isolated Power Supply
22-37
© Copyrights Reserved
2.0 Reference Standards:
IEC 60364-7-710: Electrical installation of buildings – Requirements for special installations or
locations – Medical locations IS SP30 2011-India: Part-3, Section-4: Medical establishments
3.0 Introduction:
In hospitals and in medical locations safe and secure power supply to mains supplied
equipment intended to be used for life-saving and life-supporting measures which affect the
health and safety of patients in case of failure or by current passing through the human body due
to leakage.
Medical locations are divided into 3 groups as per IEC-60364-7-710 considering the
application of medical technical equipment on the patient. Group 0, Group 1 and Group 2. In
IS- NEC-SP-30-2011 all Hospital locations are categorised under seven groups of safety
provisions namely P0 to P7. Operation Theatres, Intensive Care Units, Premature Baby Rooms,
Anesthetic Rooms etc. are categorized under safety provision P5. Therefore P5 category
locations as per NEC & Group 2 medical locations as per IEC are critical areas, because a failure
of the power supply or leakage currents higher than 10 ìA passing through the dissected human
body & discontinuity (failure) of the supply can lead to an immediate threat to the life and limb of
the patient.Group 2 or P5 category locations are Anaesthetic rooms, Operating theatres, Heart
catheterization rooms, Angiographic room, Intensive care rooms, Premature baby rooms etc.
4.0 Requirements:
For Group 2 or P5 category locations medical IT (Ungrounded) system shall be used for
circuits
ISOLATED POWER SUPPLY
22-38
© Copyrights Reserved
supplying medical electrical equipment and systems used for life support, surgical applications and other
electrical equipment located in patient environment excluding circuits of operating tables, X-ray units and
large equipment greater than 5 KVA.
The above excluded circuits of operating tables, X-ray units and large equipment greater than 5 KVA can be
supplied from a grounded (TN-S) system with an RCD/ELCB with a rated residual-operating current not
exceeding 30 mA.
As a standard practice separate medical IT (Ungrounded) system shall be used for power supply sockets for
electrical surgical & life support equipment and that for supplying to operation theatre lamps. Preferably
different power source shall be used for both the independent medical IT system.
4.1 Design of Medical IT (Ungrounded) System:
The advantage of an ungrounded system is increased availability and continuity of power supply and
reducing the magnitude of leakage current thereby avoiding shock and fire. Care shall be taken that the
conventional touch voltage in the group2 location does not exceed 25 V by providing very low resistance
earthing and equipotential bonding of non-active conductive parts.
4.1.1 Medical IT (Ungrounded) System
The ungrounded power distribution system panel shall consist of the following.
The input circuit breaker shall be double pole, single phase type. Rating of input CB shall be 300 VAC, 63A
with breaking capacity 10KA. Only short circuit protection without overload protectionshall be provided.
A single-phase isolating transformer according to IEC 61558-2-15 shall be provided with a maximum rated
power of 10 kVA as specified in IEC 60364-7710. The isolation transformer shall be two winding with earthed
isolation shield between the two windings. Further specifications are: secondary voltage of AC 250 V and a
maximum transformer secondary leakage current of 0.5 mA to earth. In order to protect the transformer and
the connecting leads between the primary and secondary terminals and the distribution bus against
overload and over temperature, monitoring the load and temperature of the transformer is required. A visual
and acoustic alarm shall be issued when the permissible load current and/or temperature are exceeded. For
monitoring, a combination of temperature monitoring (PTC thermistors in the winding of the transformer) and
current monitoring through CT shall be utilized in order to detect both a gradual heating of the transformer as
well as the occurrence of a transient load when connecting high-capacity electrical equipment.
ISOLATED POWERSUPPLY
22-39
© Copyrights Reserved
ISOLATED POWER SUPPLY
The transformer shall be fan cooled. The isolation transformer shall be installed near the critical medical
room as close as possible. It shall be enclosed in cabinet or enclosures to prevent unintentional contact
with live parts. Considering the load diversity in a typical OT, 10KVA isolation transformer is sufficient. If
the total load in one medical room or location, like in a larger ICU, is more than 10 KVA then more than
one transformer with individual transformer rating of 10 KVA maximum to cater to the loads shall be used.
The output circuit breaker shall be double pole, single phase type. Rating of output CB shall be 300 VAC,
63A with breaking capacity 10KA. Only short circuit protection without overload protection shall be
provided.
In case of an ungrounded system, an insulation monitoring device shall be provided at the secondary
side of the isolation transformer to indicate the occurrence of a first fault from live part to
exposed-conductive-parts or to earth. This device shall initiate an audible and/or visual signal which
shall continueas long as the fault persists. It is recommended that a first fault be eliminated with the
shortest practicable delay.
According to IEC 60364-7-710 & IS-NEC-SP-302011, an ungrounded (IT) system shall be equipped
with an insulation monitoring device with the following requirements:
• The AC internal impedance shall be at least 100 kÙ
• The test voltage shall not be greater than DC 25 V
• The test current shall, even under fault conditions, not be greater than 1 mA
• The response value shall be ≥ 50 kÙ
• The indication shall take place, if the earth or wiring connection is lost.
The measuring technology shall be universal for all ungrounded distribution systems with AC, AC/DC,
DC loads. Further the measuring technology shall adapt to the changing load conditions in a modern OT,
ICU and ICCU in hospital. The measuring technology along with special filtering system shall be highly
accurate and very robust without generating spurious or missed alarms even in the presence of modern
electronic and processor based equipment. Only DC voltage injection based measurement technology
shall be avoided as it is prone to inaccurate measurements and spurious alarms leading to unreliable
measurements.
22-40
© Copyrights Reserved
For testing the insulation monitoring device a test button shall be provided directly at the device and in the
remote alarm indicator and test combination. Self diagnostics shall be provided. In this way interruptions in
connecting leads to the system and to earth are immediately recognized and indicated. The insulation
monitoring devices shall comply with IEC 61557-8. Following indication & alarm shall be provided.
• A green lamp to indicate normal operation
• A yellow lamp and audible alarm to indicate insulation fault below set value
The number of load distribution feeders shall be limited for smaller size of distribution system. 12/16 nos.
Of load feeder MCBs shall be provided for each isolation transformer. The MCBs shall be double pole single
phase type. The rating shall be 300 VAC, 20 A maximum with breaking capacity 10KA. The load MCBs shall
have both short circuit protection and overload protection.
In operation theatres & intensive care units, it is advantageous to use insulation fault location systems.
The insulation fault location system is recommended as per IEC60364-4-41.Insulation fault location systems
are recommended to be used in Group 2 locations like in OTs, ICUs & Premature Baby Rooms for the
following reasons.
• A large number of socket-outlets are installed in an operation theatre/intensive care room so that the
detection of defective devices or faulty circuits involves a lot of time and costs.
• Often, the OT & intensive care bed cannot be used during fault location, since devices which support
vital body functions have to be disconnected. Therefore on-line fault location is recommended.
• Available personnel resources do not allow immediate fault location.
The earth fault location system shall consist of on-line insulation monitor integrated with test pulse device,
earth fault evaluator, number of special CTs(Sensors) depending on number of branch feeders.
The on-line insulation monitor shall continuously measure the insulation resistance of the entire galvanically
connected ungrounded system including all connected loads. Whenever the insulation of the system drops
below the presetvalue an alarm shall be generated and a test current driven by the system being monitored
shall be generated alternately between each phase conductor and earth. This test current shall be detected
selectively by means of special residual current transformers with evaluators. The design of the system shall
be such that it rejects the noises in the power supply and distribution systems and shall be sensitive to the
test current generated by the system. The system shall be robust and reliable without generating nuisance
alarms. For safety reasons the test current shall be limited to 1 mA. The sensitivity ofsensors shall be 0.1 mA
minimum and measuring range between 0.1 mA – 1 mA. The earth fault location system shall comply with
IEC61557-9.
ISOLATED POWERSUPPLY
22-41
© Copyrights Reserved
The distribution cabinet/panel shall house the input CB, output CB, insulation monitor, load
distribution MCBs, insulation fault location system. The cabinet shall be fabricated out of
14-gauge stainless steel or CRCA sheet steel in cubicle compartmentalized wall mounted,
dust and vermin proof with reinforcement of suitable size angle iron, channels T sections and / or
flats wherever necessary including 2 mm thick stainless steel door fitted with stainless screws
(Degree of protection IP30 minimum). Knockouts shall be provided at the top / bottom of the panel.
Panels shall be treated with all anti-corrosive process before painting. Paint shade shall be light grey
or as approved. Cabinet/Box shall be with all components mounted and pre-wired.
Incoming & outgoing cables shall be directly wired to Switches & Breakers or through terminals.
4.2 Remote Alarm Indicator for Medical/Technical Staff:
Due to insulation, load and temperature monitoring and fault location, the medical staff is informed
at an early stage, before a critical failure in the power supply occurs.
The following conditions shall be monitored and reported to the medical/technical staff by a remote
alarm indicator and test combination:
1. If a faulty piece of equipment is plugged in, the system will detect the insulation fault and
issue an alarm alerting the user to unplug the equipment and have it repaired.
2. Should excessive load be placed on the system, it will display the increasing load and will
sound an alarm as the load approaches 100%.
3. Should an overload or fault cause the transformer temperature to rise above normal levels
will sound an alarm and indicate the problem.
The information shall be indicated by an remote alarm indicator and test combination at a suitable
place in the medical location so that it can be permanently monitored (audible and visual signals) by
the medical staff (normal operation: green LED, alarm: yellow LEDs).
The information regarding the faulty feeder shall also be indicated in the remote alarm indicator
for ease in maintenance and troubleshooting.
4.3 Environmental Qualification:
Ambient Temperature : - 10 deg.C to 55 deg.C
Relative Humidity : 95% non-condensing
ISOLATED POWER SUPPLY