UltraConnect UC-351 Edition 09 Copyright UHS 2009

Installation Manual Page 1 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Installation, Maintenance and Operational Manual

Model UC-351GH, UC-351-3GH

UC-351

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 2 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

TABLE OF CONTENTS

1 INTRODUCTION .......................................................................................................................3

2 PARTS LIST..............................................................................................................................4

3 SAFETY WARNINGS AND OPERATING CONDITIONS ..........................................................5

4 MOUNTING AND WIRING ........................................................................................................6

5 CONFIGURING THE UC-351G ...............................................................................................11

6 NETWORK REGISTRATION AND COMMISSIONING............................................................16

7 COM IP....................................................................................................................................17

8 MAINTENANCE AND OPERATION........................................................................................18

9 SUPPORT CONTACT DETAILS .............................................................................................19

APPENDIX A INSTALLATION CHECKLIST ..............................................................................20

APPENDIX B UC-351GH GENERATED EVENTS......................................................................21

APPENDIX C TROUBLE SHOOTING ........................................................................................22

APPENDIX D DISPOSAL ...........................................................................................................23

APPENDIX E ABBREVIATIONS................................................................................................24

APPENDIX F REGULATORY APPROVALS..............................................................................25

PLEASE NOTE: THE TERM UC-351GH REFERRED TO THROUGHOUT THIS MANUAL DENOTES BOTH THE UC-351GH AND THE UC-351-3GH

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 3 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

1 Introduction

Figure 1 – UC-351GH Security Communicators

The UC-351GH is a multi-function security communicator from UHS. It combines:

- Alarm panel dial capture unit

- Serial alarm panel interface (RS.232 or TTL) compatible with the ASIAL Serial protocol

- Analog ASIAL interface

- Cellular (GSM-GPRS/3G) modem

- Ethernet (IP) uplink

- Dry contact alarm inputs configurable to default low or default high

- Control inputs

- Status outputs

- Battery power back up

- Mode 3 phone connection

- Phone line integrity monitoring

Typical applications include:

- Commercial alarm systems

- Fire alarm systems

- Residential alarm systems

GPRS

Ethernet

GPRS/3G

PSTN

Modem/Router

Network/I

nternet

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 4 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

2 Parts List

The UC-351GH can be mounted within the enclosure of the existing alarm control panel or can be mounted in a separate enclosure with a 12 Volt DC battery backed power supply. It is shipped with the following items:

UC-351GH with GPRS/3G Radio

Connector plugs

Four mounting stand-offs with adhesive pads

Whip antenna

ASIAL panel cabling

The following are required in order to complete the UC-351GH installation:

Cat 5 Ethernet Cable – to connect to the on-site LAN if required

The security company account information must be available to allow UltraConnect configuration

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 5 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

3 Safety Warnings and Operating Conditions

Qualified Personnel Only

Only qualified service personnel should install the UC-351GH and perform subsequent maintenance on the unit.

Battery Handling

Take care not to short the battery in the host alarm panel. A short-circuited battery can deliver large currents that could result in serious burns or create a fire hazard.

Dispose of used batteries according to local environmental regulations.

Power Requirements – When Powered from Alarm Panel

Voltage: 10 VDC to 30 VDC

Current: Average 420 mA @ 12 VDC

Peak 710 mA @ 12 VDC (during dial capture only - 0.1% duty cycle)

Ripple/noise: 200mVpp max.

Power Requirements – Dedicated Housing

Voltage: 16 VDC (use plug-pack provided)

Battery: 12 VDC 7AH Lead Acid

Low battery threshold: 10.8V +/- 0.2V.

Status Outputs: (on J1400)

Logic High = 12 V (nominal) @ 1mA max

Logic Low = 0.4 V @ 200mA max

These voltages are with respect to the 0V terminal on J800.

Dry Contact Alarm Inputs

Logic High = +3.5V to +30V

Logic Low = -0.5V to +0.8V

Physical Dimensions (Excludes Housing)

Size 163 x 102 x 36 mm

Mass = 135 g

SELV Connectors

Connectors J1300, J1301 (dry contact alarm inputs) J1400 (outputs), J1000 (alarm panel), J1501 (ASIAL input) and J800 (DC power) have been classified as SELV and must only be connected to approved SELV circuits. If the circuit to be connected to these terminals is not SELV, an isolation unit compliant with local regulatory requirements must be used. SELV circuits are determined in IEC60950 and equivalent national standards.

Operating Conditions

The UC-351GH is rated to operate under the following conditions:

- Indoor operation

- Ambient temperature: -5oC (23oF) to +55oC (131oF)

- Humidity: 5% to 95%

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 6 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

4 Mounting and Wiring

Figure 2 - UC-351GH Layout

UC-351GH LED functionality:

Wireline Up Flashing means the UC-351GH unit has obtained an IP address on the wireline (e.g. LAN) network.

Solid means the UC-351GH is registered on the UltraAgent network server over its wireline interface.

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 7 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Wireless Up Flashing means the UC-351GH has acquired an IP address on the wireless network (e.g. GPRS/3G).

Solid means the UC-351GH is registered on the UltraAgent network over its wireless interface.

SSx Wireless signal strength indicators, refer to Table 2 in section 6.

Ethernet Flashing means the Ethernet port is detecting traffic,

Solid means the Ethernet Port is connected to the LAN

Selecting the Mounting Location

When surveying the site, please remember that the UC-351GH operates in a similar way to an ordinary mobile telephone, therefore any restrictions on the use of mobile telephones in the area will also apply to the UC-351GH.

Install the UC-351GH in such a way that a separation of at least 3 meters is maintained from any other Radio sources.

Mounting the UC-351GH

Important: Ensure the alarm system is powered down (switch off mains power and disconnect the battery) before starting the installation.

Use the four adhesive stand-offs supplied to attach the UC-351GH unit to the inside surface of the lid or to a convenient location inside the main enclosure. Ensure that the surface to which the stand-offs are to be attached is flat and free of dust or grease. Insert the four adhesive stand-offs into the four mounting holes. Peel off the paper covering the adhesive pad and firmly attach the pad to the surface at the chosen location.

Phone Line Connection

The UC-351GH supports mode-3 cabling.

The phone line from the exchange is connected to the ‘PSTN LINE’ port of J400; the line connected to the premises phones is connected to the ‘Phone’ port of J400.

If an Alarm Panel is already connected to the telephone line, disconnect the line and reconnect it to the UC-351GH’s dial capture port (J1000).

Ethernet Connection

Run an RJ45 cable from a convenient network connection to the UC-351GH unit's Ethernet connector, J600.

The UC-351GH unit’s Ethernet port auto-senses, so that either a straight-through or cross-over Ethernet cable can be used.

Only ready-made, certified cables should be used when connecting the UC-351GH unit to network equipment. If cabling has to be made on site then testing and certification to EN 50173 Class D should be performed. Failure to use certified network cabling can lead to intermittent and spurious faults that are difficult to trace without specialist equipment.

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 8 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Power Connection (J800)

Ensure power is off when cabling the power connectors. If the ASIAL panel is powering the UC-351GH use terminal J1501 for the power connection (See Alarm Panel Connection below for further details). For all other instances the power connection is via screw terminal J800. Connect the +12V to the terminal labelled +V (PIN 1 of J800), and 0V to the terminal labelled 0V (PIN 2 of J800).

The power wiring must be less than 3m in length and use wires having a core area of at least 1mm2.

Battery Connection (J401)

The UC-351GH is equipped with a battery charging circuit. If the primary power supply is removed the UC-351GH will be powered from the connected battery. When the power supply is connected the battery will be charged from the primary power connection.

Antenna

A magnetically attached whip antenna is provided. It must be mounted indoors, on a flat horizontal surface, sufficiently close that it can be connected to the UC-351GH. The base of the antenna is equipped with a strong magnet which will attach firmly to any ferrous surface such as the top of the alarm panel enclosure (see Figure 3 ). Run the antenna cable to the UC-351GH via an existing knock-out or make a suitable hole, (typically 11mm diameter) in the top of the enclosure. Prevent metal filings and shavings from entering the enclosure as it could cause internal short circuits.

Remove any burrs from the hole, pass the RF cable through it and place the antenna in position.

Do not permanently fix the antenna until a Signal Strength Test has been performed.

Figure 3 – Antenna Mounting

Extension Antenna

A high gain antenna with an extension cable can be used in the event that the Receive Signal strength at the location is inadequate, and changing locations is not an option.

General Purpose Pins

To interface to a panel with dry contact alarm outputs, connect the alarm panel outputs to the UC-351GH pin terminals on J1300 and J1301. Pins 1-8 are general purpose inputs and will raise E/R323 alarms on zones 901 to 908.

Pins 9-16 have specific purposes as follows::

Input 9: Vibration Sensor Input

Input 10: Vibration Sensor Gnd

Input 11: Vibration Sensor Pwr

Input 12: Tamper Input

Input 13: Tamper Gnd

Input 14: Unused

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 9 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Input 15: Used as GPOP4 (General Purpose Output) indicating primary path OK if low

Input 16: used as GPOP5 indicating secondary path OK if low.

Alarm Panel Connection Overview

There are two wiring positions for connecting alarm panels, Dial Capture and ASIAL Serial. Only one wiring position is allowed per installation. The Dial Capture position uses connector J1000 and the ASIAL Serial connection uses J1501.

Alarm Panel Connection – Dial Capture

To use dial-capture, connect the alarm panel’s PSTN dialler interface to the UC-351GH’s Alarm Panel port J1000.

Pins 1,2 - Panel Line – this provides feed towards the alarm panel’s PSTN connection

Pins 3,4 - Panel Phone – this connects to the return pair from the alarm panel’s PSTN connection.

Pins 5,6 - Unused

Alarm Panel Connection – Serial

This is a fully monitored connection to the alarm panel. It uses the ASIAL serial alarm reporting format.

The connector is compatible with the four- wire STU RS-232 and TTL cabling. Please note that the format of ASIAL being used by the panel, whether TTL or RS-232, must be determined. The table below indicates which panels support RS-232 and which panels support TTL.

If the panel can support the current requirements of the UC-351GH (710mA @12VDC) connect the 12V wire between the panel and the UC-351GH. Otherwise the power connector J800 will need to be connected to an external power supply.

If using the 12V connector on J1501 please ensure the 12V wire is connected to the correct connector. On unmarked panels find the 12V wire using a multimeter. The voltage should be approximately 13.8V with reference to Ground.

The Ground, Rx and Tx cables need to be connected between the panel and the UC-351GH. Connect the transmit wire from the panel to the appropriate Rx port on the UC-351GH. Likewise connect the receive wire

RS232 TTL

MCM Icon16 MCM Icon 32 MCM Icon48 Concept 2000 Concept 3000

Tecom Challenger GE Nx

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 10 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

from the panel to the appropriate Tx port on the UC-351GH.

If the UC-351GH is supporting ComIP then the phone line from the Alarm Panel must be connected to the Alarm Panel connector J1000.

Outputs

Three open collector outputs are provided with onboard pull-up to 12V. The outputs are rated to 30V and terminate on J1400 as shown below.

Note: G denotes the 0V connection.

By default, the outputs have the following specific purposes:

Output1 - J1400 Pin 1: Standard Line Fault Indication

Output2 - J1400 Pin 2: Remote controlled

Output3 - J1400 Pin 3: RPS function (in conjunction with alarm input 4)

WARNING

Connectors J1000, J1300, J1301 and J1400 have been classified as SELV and shall only be connected to approved SELV circuits.

If the circuit to be connected to these terminals is not SELV, a regulatory authority compliant isolation unit must be used. SELV circuits are determined in IEC60950.

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 11 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

5 Configuring the UC-351GH

Important Note: Always check the Quick

Installation Guide if provided before changing UC-351G configuration.

Methods for configuration

There are two methods available to configure the UC-351GH. The UC-351GH can be configured with either a DTMF phone or with the web console.

Method 1. Configuration with DTMF Phone

Initial Power-Up

1. Prepare wiring as described in Section 4.

2. For initial power-up and configuration, the following minimum connections are required:

A. DC Power

B. Antenna (for wireless operation)

3. During start-up, two headers on the UC-351GH allow configuration: * J902 – Learn Header * J903 – Config Header Either or both headers can be shorted. If both headers are shorted the UC-351GH will perform PIN learning first, followed by DTMF configuration. The procedures are described below.

Learning Procedure for PINS and Initial Power-On

Please note that if the PINs are not used then the LEARN procedure will not need to be undertaken.

1. Short out Learn header J902 with a link.

2. Power up or power-cycle the unit.

3. Wait around 30 seconds until the LED’s flash in the learn ready pattern (left to right scrolling pattern).

4. Connect all 16 dry alarm inputs in the Normal state (ensure that alarm input 4 is in the closed state for RPS. See section 4)

5. Remove the header from J902. The UC-351GH will flash all LED’s off-on-off to indicate learning has completed and will store this information in non-volatile memory.

The boot sequence will then continue.

Configuring the UC-351GH with a DTMF Phone

1. Ensure you have a DTMF phone connected to the UC-351GH unit’s alarm panel dial capture input port (J1000 PINs 1 and 2).

2. Power up or power-cycle the unit with the Configuration header J903 shorted with a link.

3. Around 30 seconds after power on (or just after the learning procedure has completed if being done), the LEDs will flash for a period of 20 seconds. During this time lift the telephone receiver, receive dial tone and press the '#' key to enter Installer Mode.

The UC-351GH requires the following minimum parameters to be entered in order to connect to the UltraSec network. These parameters should have been provided by your Central Station:

- Locale Code

- Agency Number

- Account Number

- Check Digit

To enter the Basic Configuration parameters, enter installer mode, then press:

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 12 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

* Locale * Agency # Account # Check Digit

Example * 2 * 1 # 1000 # 7

Example * 261 * 20 # 1000 # 5

Example * 201 * 31 # 1000 # 8

UltraConnect sends a soft acceptance tone after each ‘#’ and after the Check Digit. Four sharp beeps means the data has been incorrectly entered. Re-enter the full command.

Installer Mode is terminated after five minutes, or when the phone is hung-up. After Installer Mode is terminated, ensure the config header is removed before proceeding with the installation.

Configuring Fallback mode for the panel

* 99 * 0 Automatic Fallback * 99 * 1 No Fallback to PSTN Automatic Fallback mode connects the panel to the PSTN line if both wireline and GPRS/3G paths are down.

Configuring UC-351 With Static IP

These settings are required when the UC-351GH’s LAN address is not supplied from a DHCP server (ie when a network administrator assigns a specific static IP address for the UC-351GH).

Disable dynamic IP (DHCP) mode by entering installer mode, then pressing:

* 13 * 0

UltraConnect sends two soft acceptance tones.

To enter the static IP address for the UC-351GH press:

* 10 * aaa * aaa * aaa * aaa # xxx * xxx * xxx * xxx #

where: aaa.aaa.aaa.aaa is the assigned static IP

address xxx.xxx.xxx.xxx is the assigned netmask

To enter the gateway IP address details for the UC-351, press:

* 11 * ggg * ggg * ggg * ggg #

ggg.ggg.ggg.ggg is the assigned gateway IP address

Example

To set the UC-351GH’s IP settings to:

IP Address: 192.168.1.10 Netmask: 255.255.255.0 Gateway Address: 192.168.1.1

enter configuration mode then enter:

*13* 0 *10* 192 * 168 * 1 * 10 # 255 * 255 * 255 * 0 # *11* 192 * 168 * 1 * 1 #

In each case, UltraConnect sends two soft acceptance tones after the command. Four sharp beeps means data has been incorrectly entered. Re-enter the full command.

Configuring UC-351 For Dynamic IP (Default Mode)

You can return the UC-351GH to the default Dynamic IP (DHCP) mode at any time by entering installer mode, then pressing:

* 13 * 1

UltraConnect sends two soft acceptance tones after the 1.

Configuring Panel Format

By default, the UC-351GH is configured in Contact ID mode. To change the panel format, use the * 15 * option: * 15 * 1 # ContactID * 15 * 10 # High Speed (fast format) * 15 * 20 # SIA * 15 * 30 # Pin only mode * 15 * 40 # ASIAL serial

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 13 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

The UC-351GH supports other several other less common alarm panel formats listed below: * 15 * 2 # ContactID with Double Knock * 15 * 11 # High Speed with Double Knock * 15 * 21 # SIA with V.21 modem tones

Configuring the Outputs

By default, the UC-351G’s Outputs operate as follows: Output Default

Function Default Polarity

Output1 Standard Line Fault 2 (Active High)

High to indicate both paths failed

Output2 Remotely Controlled (Automation System)

1 from AS sets output High, 0 from AS sets output Low

Output3 RPS function (in conjunction with alarm input 4)

Alarm sent sets output High, Alarm ack’d sets output Low

Table 1 - UC-351GH Reported Events

The following commands can be used via the phone configuration to set the behaviour of the Outputs:

Output1 * 91 * 20 BSIA Form 175 Mode * 91 * 30 Standard Line Fail Mode Active

Low(Failure of any communications path causes a Low on GPOP1)

* 91 * 31 Standard Line Fail Mode Active

High (Failure of any communications path causes a High on GPOP1)

* 91 * 50 Standard Line Fail Mode 2 Active

Low (Failure of both

communications paths causes a Low on GPOP1)

* 91 * 51 Standard Line Fail Mode 2 Active

High (Failure of both communications paths causes a High on GPOP1) – default mode

Output2 * 92 * 10 Remotely (Automation System)

Controlled Active Low (0 from AS sets output High, 1 from AS sets output Low)

* 92 * 11 Remotely (AS) Controlled Active High (1 from AS sets output High, 0 from AS sets output Low) – default mode

Output3 * 93 * 10 RPS function Active Low (Alarm

sent sets output Low, Alarm ack’d sets output High)

* 93 * 11 RPS function (Alarm sent sets output High, Alarm ack’d sets output Low) – default mode

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 14 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Method 2. Advanced Set-up by Web Browser

Initial Power-Up

1. Prepare wiring as described in Section 4.

2. For initial power-up and configuration, the following minimum connections are required:

C. DC Power

D. Antenna (for wireless operation)

3. During start-up, two headers on the UC-351GH allow configuration: * J902 – Learn Header * J903 – Config Header Either or both headers can be shorted. If both headers are shorted the UC-351GH will perform PIN learning first, followed by web configuration. The procedures are described below.

Learning Procedure for PINS and Initial Power-On

Please note that if the PINs are not used then the LEARN procedure will not need to be undertaken.

1. Short out Learn header J902 with a link.

2. Power up or power-cycle the unit.

3. Wait around 30 seconds until the LED’s flash in the learn ready pattern (left to right scrolling pattern).

4. Connect all 16 dry alarm inputs in the Normal state (ensure that alarm input 4 is in the closed state for RPS. See section 4)

5. Remove the header from J902. The UC-351GH will flash all LED’s off-on-off to indicate learning has completed and will store this information in non-volatile memory.

The boot sequence will then continue.

Configuring the UC-351GH with the Web Console

The UC-351GH’s management console is available at http://192.168.222.222/ only when the Configuration header, J903, is shorted. Note that the UC-351GH does not run a DHCP server, so you must configure the PC with a static address on the same subnet as the UC-351GH. For example, configuring the PC to have IP address 192.168.222.10 would allow connection to the UC-351GH.

Once connected, surf to the Quick start link (see Figure 4). From here you can configure:

Account number This is the number used to identify the site in UHS’ network.

DRN / Agency ID This identifies the agency in the UHS network.

Wireline (IP) Settings including DHCP Client or static local IP and gateway.

Wireless (GPRS/3G) Settings including APN, username and password and server IP addresses.

Dial Up Settings Can be configured as

-Backup/As required : When the primary path fails the UC-351GH will dial up for an alarm or a poll and then disconnect.

-Always On : The Dial Up connection is always connected to the server.

-Fallback/When GPRS fails : When the primary path fails the Dial Up connection will connect and remain connected.

-DTMF : When the primary path fails the UC-351GH will send DTMF signals to a receiver.

Panel Type This is the alarm panel protocol. This must match the protocol configured in the alarm panel if connected to a dialler alarm panel.

Output Settings including the definition of the operation and polarity of the General Purpose Outputs (1-3).

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 15 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Figure 4 - Screenshot of Quick Start Menu

Once the settings have been correctly entered press the Save/Reboot button to save the settings to the UC-351GH. Warning: Wait two minutes before removing the ethernet cable or config header after pressing

the Save/Reboot button

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 16 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

6 Network Registration and Commissioning

Remove Short on Config Header

If Config Header (J903) is shorted, the UC-351GH will not attempt to register on the UltraAgent network. The header short should be removed once configuration is complete.

Network Registration

On startup, the UC-351GH will immediately attempt to register on UHS’ UltraAgent network with all available interfaces:

- GPRS/3G

- Internet

If either the Wireline or Wireless network connection is available (i.e. respective LED is flashing), but does not become solid for 30 seconds, then the UC-351GH is not registering with the UHS UltraAgent network server. This could be due to an error in activation. Contact UHS Helpline for assistance.

Signal Strength Test

LEDs SS1,SS2 and SS3 provide a signal strength indication. Signal strength is indicated as shown in the following table. A signal strength test can be run at any time by shorting the Config header. Note that communications with the network server and alarm transmission will cease while in Installer mode.

SIG3 SIG2 SIG1 Signal Strength

Off Off Off No reading available (eg modem is being reset)

Off Off FLASH Attempting to register on network

Off Off On <-89dBm Unacceptable

Off FLASH On -89dBm to -83dBm Acceptable

Off On On -83dBm to –77dbm Good

FLASH On On -77dBm to -70dBm Very Good

On On On > -70dBm Excellent

Table 2 – Wireless Signal Strength

Commissioning

Once the UC-351GH is registered with the UHS UltraAgent network, perform the following tests:

1. Send an alarm from one of the alarm inputs on the UC-351GH. Check with the Automation System that the alarm has been received over the GPRS path and the IP path.

2. Send a set of alarms from the alarm panel. Check with the Automation System that the alarms are received over the GPRS/3G path and the IP path.

If the Automation System receives a Bad Checksum Error or Panel Type Mismatch Error, the panel is not transmitting in the format expected by the UC-351GH.

3. Disable the GPRS/3G interface. Send a set of alarms from the alarm panel. Check with the Automation System that these are received over the wireline path.

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 17 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

7 Com IP

Com IP enables secure, remote download to the alarm panel over a GPRS/3G or IP connection. Figure 5 shows the key network elements.

The process for Panel downloads utilizing Com IP is as follows. 1. The UC-372-UAR emulates a modem and receives a request from the Server to establish

a session with the alarm panel. 2. The UC-372-UAR receives this request and establishes a session with the UltraConnect

over the WAN. 3. The UltraConnect at the client site calls the Alarm Panel over the Dial Capture or Serial

Interface and mimics a modem establishing a download session. 4. Once the call has been established the link between the Server and the Alarm Panel is

complete and the software will be downloaded.

For the Com IP functionality to work the Virtual Tunnel information on the UC-372-UAR must be correctly configured and the UC-372-UAR must have access to the UltraAgent Servers. For access to the UltraAgent Servers, ports may need to be opened on firewalls between the UltraAgent Servers and UC-372-UAR. At the time of writing this manual the Virtual Tunnel uses port 9091 and the TCP protocol.

Figure 5 - Com IP Example

Monitoring Software

GPRS/3G

UltraConnect Alarm Panel (Concept/ Challenger)

Dial Capture

Server (Titan/ Wdirect)

UC - 372 - UAR

UltraAgent

Servers

WA N UC - 372 - UAR

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 18 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

8 Maintenance and Operation

The UltraAgent servers manage the UC-351GH and appropriate alarms are raised to alert the Automation System to faults (see appendix B). This section describes the operational and maintenance activities that may be required.

Internal Access

The UC-351GH is usually installed in a tamper monitored alarm system, so in general it is necessary to obtain authorisation with the control room before opening the unit. Once authorised:

1. Remove all watches, rings or other metal objects from your hands.

2. Use ESD protection

Unit Replacement

To replace the unit, perform the following actions:

1. Switch off and disconnect the mains supply of the host alarm system.

2. Remove all watches, rings or other metal objects before opening the lid.

3. Disconnect and remove the battery of the host alarm system.

4. Disconnect the wiring from the existing UC-351GH unit

5. Mount the replacement unit and replace cable as per Section 4.

6. Reconnect the mains supply and switch on.

7. Contact the Control Room. Unit will be required to be disabled and then re enabled to bring back into service

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 19 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

9 Support Contact Details

For assistance with your UC-351GH installation, contact UHS at [email protected] or call +61 2 9663 2299.

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 20 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Appendix A Installation Checklist

Before leaving the premises, complete the following Installation Checklist.

UC-351GH securely mounted in host alarm system.

UC-351GH powered up.

UC-351GH communicating with UHS UltraAgent network over wireline path.

Wireless signal strength in acceptable range or better.

UC-351GH communicating with UHS UltraAgent network over wireless interface.

Alarm panel connected to UC-351GH via dial-capture, ASIAL or PIN interface as required.

Alarms sent and received at Automation System over all available interfaces.

� Remove the PSTN line and ensure that a PSTN Network Failure alarm is raised.

� Premises phones working and there are no PSTN Network Failure alarms when other phones go off-hook.

� Battery connected. AC fail test completed.

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 21 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Appendix B UC-351GH Generated Events

The UC-351GH generates events for system alarms. The values listed in the table below are default codes for the UC-351GH configured in ContactID, Ademco Fast and SIA Formats.

Alarms sent over wireline are differentiated from those sent over wireless with the Receiver Number field in the Automation Protocol.

Description CID (zone) SIA E/R (zone)

Fast (zone)

Time to Active

AC Fail 301 (999) AT/AR (999) 6(1) E – 7 Min; R – 7 Min

Low Battery Level 302 (999) YT/YR 6 (2) E – 7 Min; R – Immediate

Bad Packet Count Threshold Exceeded

352 (999) ET/ER (999) 6 (3) E – Exceed Count;

Bad Checksum 311 (999) ET/ER (993) 6 (3) E – Exceed Count;

Missing Heartbeat 312 (999) ET/ER (991) 6 (3) E – 10 days; R – Immediate

Off Hook Timeout 313 (999) ET/ER (989) 6 (3) E – 10 Min; R – Immediate

Dial Fail 314 (999) ET/ER (987) 6 (3) E – 10 Sec; R – Immediate

Runaway Panel 316 (999) ET/ER (983) 6 (3) E – 10 Min; R – Immediate

GPIP1- 8 323 (901-908) BA/BR (901-908) 7 (1) E – Immediate; R – Immediate

Vibration Sensor 323 (909) BA/BR (909) 7 (1) E – Immediate; R – Immediate

Tamper 323 (912) BA/BR (912) 7 (1) E – Immediate; R – Immediate

Panel Connection (Serial Interface)

356 (997) N/A N/A E – 5 Sec; R – Immediate

Panel Account No. Changed (Serial Interface)

306 (999) N/A N/A E- Immediate

Table 3 - UC-351GH Reported Events

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 22 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Appendix C Trouble Shooting

UC-351GH does not start up

Ensure that the DC power is connected, and that no headers have been left inserted on the board

UC-351GH doesn’t connect to UHS UltraAgent network

Check that the account has been activated in the UHS UltraAgent network server.

Ensure that this UC-351GH unit has not already been connected under a different account.

Check that no headers have been left inserted on the board.

Alarm panel does not break dial tone

Check the connection to the alarm panel.

Check if the alarm panel has been set to DTMF dialling

Plug a standard DTMF phone into the UC-351GH unit’s dial capture port (J1000 Pins 1 and 2) and dial a digit to check that it can break dial tone

No alarms sent to AS

Check that the dialler receiver and account number have been programmed.

Ensure that the panel is configured to report using a supported format (ContactID, Ademco High Speed, SIA).

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 23 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Appendix D Disposal

The symbol shown here and on the product, means that the product is classed as Electrical or Electronic Equipment and should not be disposed of with other household or commercial waste at the end of its working life. The Waste Electrical and Electronic Equipment (WEEE) Directive (2002/96/EC) has been put in place to recycle products using the best available recovery and recycling techniques to minimise the impact on the environment, treat any hazardous substances and avoid the increasing landfill.

Product disposal instructions for residential users:

When you have no further use for it, please dispose of the product as per your local authority’s recycling processes. For more information please contact your local authority or retailer where the product was purchased. Product disposal instructions for business users:

Business users should call +61 2 9663 2299 to determine correct address to send the product to for disposal.

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 24 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Appendix E Abbreviations

ADSL asynchronous digital subscriber line GSM Global System for Mobile communication GPRS General Packet Radio Service PSTN Public Switched Telephone Network CCTV closed circuit television IP Internet Protocol HDD Hard Disk Drive SELV Safety Extra Low Voltage TNV-3 Higher than SELV voltage standard (70.7Vp-p or 120VDC) Ah Amp hour mVp millivolts peak to peak GND ground AS Automation System RPS Remote Programming Software

UC-351GH Edition 09 Copyright UHS 2009

Installation Manual Page 25 of 25 All rights reserved.

UltraConnect UC-351GH

www.uhssystems.com

Appendix F REGULATORY APPROVALS

EN54-4:1997 LIABILITY The services and products provided by UHS, when installed and commissioned, are only intended to provide a communications path between the equipment and a supervision centre to the extent that is reasonably practicable by use of such goods and services.

DISCLAIMER The manufacturer or his agents disclaim responsibility for any damage, financial loss or injury caused to any equipment, property or persons resulting from any use of this equipment. The manufacturer is not liable for any purely economic loss arising from any use of this equipment. All responsibility and liability in the use of UHS products are assumed by the user. This unit is designed to be used in customer premises. Use of this equipment in other locations may void warranty. This unit is not intended for use in marine environments or water borne vessels. UHS may make changes to features and specifications at any time without prior notification in the interest of ongoing product development and improvement.

N13454