2391- inspection & testing (advanced)
TRANSCRIPT
-
8/10/2019 2391- Inspection & Testing (Advanced)
1/135
1
www.ElectaCourse.com
Inspection Testingnspection Testing
dvanced
dvanced
ElectaCourse.com
2005 Last Updated August 2006
-
8/10/2019 2391- Inspection & Testing (Advanced)
2/135
2
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
3/135
3
www.ElectaCourse.com
This presentation is suitable for those studying for the
City & Guilds 2391 and 2400 courses
-
8/10/2019 2391- Inspection & Testing (Advanced)
4/135
4
www.ElectaCourse.com
The presentation includes guidance and
continuous self-assessment
-
8/10/2019 2391- Inspection & Testing (Advanced)
5/135
5
www.ElectaCourse.com
In order to work through this presentation you will need copies
Of the following publications
BS 7671:2001 (16th Edition IEE Wiring Regulations)
Guidance Note 3 (Inspection and Testing
-
8/10/2019 2391- Inspection & Testing (Advanced)
6/135
6
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
7/135
7
www.ElectaCourse.com
To ensure the safety of any electrical installation it should be
inspected, tested and the necessary certification completed:
Before being put into service (initial verification)
At regular intervals thereafter (Periodic Inspection Report)
On completion of any alteration or addition
-
8/10/2019 2391- Inspection & Testing (Advanced)
8/135
8
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
9/135
9
www.ElectaCourse.com
For an initial verification
BS 7671:2002 states:
Installed equipment to an appropriate standard, i.e. BS, BS EN
Correctly selected and erected
Not visibly damaged or defective as to impair safety
-
8/10/2019 2391- Inspection & Testing (Advanced)
10/135
10
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
11/135
11
www.ElectaCourse.com
The Periodic Installation Report (PIR)
BS 7671:2001 states:
Periodic inspection and testing of an electrical installation
shall be carried out to determine, so far as is reasonably
practicable, whether the installation is in a satisfactory condition
for continued service
-
8/10/2019 2391- Inspection & Testing (Advanced)
12/135
12
www.ElectaCourse.com
Generally, the main reason for undertaking an inspection and
test is to ensure that the installation is safe to use
-
8/10/2019 2391- Inspection & Testing (Advanced)
13/135
13
www.ElectaCourse.com
What Are the likely reasons for an installation failing to be safe?
Age
Wear and tear
Damage, i.e. fire, flooding etc
Electrical overload
DIY enthusiasts
Unscrupulous contractors
-
8/10/2019 2391- Inspection & Testing (Advanced)
14/135
14
www.ElectaCourse.com
What factors would influence the need for a PIR
Expiry of current certificate
Change of ownership or use of the installation
As a result of damage or electrical overloading
Mortgage/insurance purposes
Compliance with current regulations
Local bylaw requirements
-
8/10/2019 2391- Inspection & Testing (Advanced)
15/135
15
www.ElectaCourse.com
What factors would influence the safety of an installation?
Poorly installed equipment/accessories
Loose connections giving rise to shock and or fire
Inadequate overcurrent protection of equipment and circuits
Underrated/overloaded circuit conductors
Inadequate/non-existent earthing or bonding arrangements
-
8/10/2019 2391- Inspection & Testing (Advanced)
16/135
16
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
17/135
17
www.ElectaCourse.com
Inspection always proceeds testing
Prior to visual inspection the supply to the installation or part
of the installation undergoing inspection should be
disconnected from the supply
-
8/10/2019 2391- Inspection & Testing (Advanced)
18/135
18
www.ElectaCourse.com
Electrical installations which comply with BS 7671:2001 areregarded by the Health & Safety Executive as likely to achieve
conformity with which statutory regulations?
-
8/10/2019 2391- Inspection & Testing (Advanced)
19/135
19
www.ElectaCourse.com
The Electricity at Work Regulations 1989
-
8/10/2019 2391- Inspection & Testing (Advanced)
20/135
20
www.ElectaCourse.com
Page 8BS 7671:2001 Note by the Health and Safety Executive
-
8/10/2019 2391- Inspection & Testing (Advanced)
21/135
21
www.ElectaCourse.com
Identify THREE areas which should be given consideration prior toundertaking alterations or additions to an existing electrical
installation
-
8/10/2019 2391- Inspection & Testing (Advanced)
22/135
22
www.ElectaCourse.com
The ability of existing equipment including that of the supplier isadequate for the additional load
The earthing arrangements are adequate
The bonding arrangements are adequate
-
8/10/2019 2391- Inspection & Testing (Advanced)
23/135
23
www.ElectaCourse.com
Page 14130-07 Additions and alterations to an installation
Regulation 130-07-01
-
8/10/2019 2391- Inspection & Testing (Advanced)
24/135
24
www.ElectaCourse.com
Identify SIX characteristics of the incoming electrical supply thatwould need to be ascertained by the person undertaking an
inspection and test of an electrical installation
-
8/10/2019 2391- Inspection & Testing (Advanced)
25/135
25
www.ElectaCourse.com
(i) the nominal voltage(s)
(ii) the nature of the current and frequency
(iii) the prospective short circuit current at the origin
(iv) the external earth fault loop impedance (Ze)
(v) the suitability for the requirements of the installation
including the maximum demand
(vi) the type and rating of the overcurrent protective device
-
8/10/2019 2391- Inspection & Testing (Advanced)
26/135
26
www.ElectaCourse.com
Page 33313 Nature of Supply
Regulation 313-01-01
-
8/10/2019 2391- Inspection & Testing (Advanced)
27/135
27
www.ElectaCourse.com
Identify two precautions that should be observed duringinspection and testing of an electrical installation
-
8/10/2019 2391- Inspection & Testing (Advanced)
28/135
28
www.ElectaCourse.com
avoid danger to persons
avoid damage to property and installed equipment
-
8/10/2019 2391- Inspection & Testing (Advanced)
29/135
29
www.ElectaCourse.com
Page 170Chapter 71 - Initial Verification
Regulation 711-01-01
-
8/10/2019 2391- Inspection & Testing (Advanced)
30/135
30
www.ElectaCourse.com
State the THREE requirements of BS 7671 with regard to installedelectrical equipment
-
8/10/2019 2391- Inspection & Testing (Advanced)
31/135
31
www.ElectaCourse.com
(i) in compliance with Section 511
(ii) correctly selected and erected in accordance with the
Regulations
(iii) not visibly damaged or defective so as to impair safety
-
8/10/2019 2391- Inspection & Testing (Advanced)
32/135
32
www.ElectaCourse.com
Page 170 - Inspection
Regulation 712 - 01 - 02
Note: Section 511 deals with compliance with standards. All
equipment should comply with the appropriate British Standard or
Harmonized Standard - See page 84 - Selection and Erection of
Equipment
-
8/10/2019 2391- Inspection & Testing (Advanced)
33/135
33
www.ElectaCourse.com
Identify TWO statutory, and FIVE non-statutory documents that aninspecting engineer may need to refer when undertaking an
inspection and test on an electrical installation
-
8/10/2019 2391- Inspection & Testing (Advanced)
34/135
34
www.ElectaCourse.com
Statutory:
Health and Safety at Work Act etc 1974
Electricity at Work Regulation 1989
Non-statutory:
BS 7671:2001
IEE Guidance Note 3 (Inspection and Testing
IEE On-Site Guide
GS 38 Equipment used by electricians (HSE Guidance) Memorandum of Guidance to The Electricity at Work Regulations
-
8/10/2019 2391- Inspection & Testing (Advanced)
35/135
35
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
36/135
36
www.ElectaCourse.com
Visual inspection always precedes testing
-
8/10/2019 2391- Inspection & Testing (Advanced)
37/135
37
www.ElectaCourse.com
From the inspection check list within BS 7671 Identify THREE
methods of protection against direct electric shock (contact)
-
8/10/2019 2391- Inspection & Testing (Advanced)
38/135
38
www.ElectaCourse.com
Insulation of live parts
Barriers
Enclosures
-
8/10/2019 2391- Inspection & Testing (Advanced)
39/135
39
www.ElectaCourse.com
Risk of direct contact. Barrier removed and not replaced
-
8/10/2019 2391- Inspection & Testing (Advanced)
40/135
40
www.ElectaCourse.com
Risk of direct contact. Barrier removed and not replaced
-
8/10/2019 2391- Inspection & Testing (Advanced)
41/135
41
www.ElectaCourse.com
Risk of direct contact.
-
8/10/2019 2391- Inspection & Testing (Advanced)
42/135
42
www.ElectaCourse.com
Page 170
Regulation 712 - 01 - 03
Two additional methods of protection against direct shock of a
special nature are:
Placing out of reach
ObstaclesNote: this method of protection is intended to prevent
inadvertent contact with live parts and therefore areas
incorporating this type of protection should only be accessible to
skilled persons only
-
8/10/2019 2391- Inspection & Testing (Advanced)
43/135
43
www.ElectaCourse.com
From the inspection check list within BS 7671 Identify THREE
methods of protection against indirect contact
-
8/10/2019 2391- Inspection & Testing (Advanced)
44/135
44
www.ElectaCourse.com
EEBAD
Class II
Electrical Separation
Non-conducting location
Earth-free local equipotential bonding
-
8/10/2019 2391- Inspection & Testing (Advanced)
45/135
45
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
Note: Protection by non-conducting location and earth-free local
equipotential bonding are both of a special nature and very rarely
encountered
-
8/10/2019 2391- Inspection & Testing (Advanced)
46/135
46
www.ElectaCourse.com
From the inspection check list within BS 7671 Identify TWO methods
of protection against both direct and indirect contact
-
8/10/2019 2391- Inspection & Testing (Advanced)
47/135
47
www.ElectaCourse.com
Separated extra-low voltage (SELV)
Limitation of discharge energy
El C
-
8/10/2019 2391- Inspection & Testing (Advanced)
48/135
48
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
El t C
-
8/10/2019 2391- Inspection & Testing (Advanced)
49/135
49
www.ElectaCourse.com
From the inspection check list within BS 7671 Identify FOUR types of
protective conductor
El t C
-
8/10/2019 2391- Inspection & Testing (Advanced)
50/135
50
www.ElectaCourse.com
earthing conductor
circuit protective conductor (CPC)
main equipotential bonding conductor
supplementary equipotential bonding conductor
www ElectaCourse com
-
8/10/2019 2391- Inspection & Testing (Advanced)
51/135
51
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
www ElectaCourse com
-
8/10/2019 2391- Inspection & Testing (Advanced)
52/135
52
www.ElectaCourse.com
Presence of main equipotential bonding conductors
www ElectaCourse com
-
8/10/2019 2391- Inspection & Testing (Advanced)
53/135
53
www.ElectaCourse.com
One requirement from Regulation 712-01-03 is the selection of
equipment and protective measures appropriate to external
influences. List the external influences likely to be encountered by
an electrical installation located within a commercial greenhouse
accessible to the general public.
www ElectaCourse com
-
8/10/2019 2391- Inspection & Testing (Advanced)
54/135
54
www.ElectaCourse.com
Ultra-violet radiation
Extremes of temperature
Mechanical damage
Water/moisture/humidity
Rodent attack
Chemicals
Corrosion
Vandalism
www ElectaCourse com
-
8/10/2019 2391- Inspection & Testing (Advanced)
55/135
55
www.ElectaCourse.com
Page 170/171
Regulation 712 - 01 - 03
www ElectaCourse com
-
8/10/2019 2391- Inspection & Testing (Advanced)
56/135
56
www.ElectaCourse.com
Regulation 712 - 01 - 03 requires visual inspection to ensure
cables are routed in safe zones and also considers erection
methods.
Here are some examples of non-compliance
-
8/10/2019 2391- Inspection & Testing (Advanced)
57/135
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
58/135
58
Regu
lations
5
22-08
Routing of cables
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
59/135
59
Regu
lation
52
2-08
Routing of cables
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
60/135
60
Regu
lations
5
22-08
Routing of cables
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
61/135
61
Regu
lations
522-08
Routing of cables
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
62/135
62
Regu
lations
522-08
Routing of cables
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
63/135
63
Selection of conductors for current carrying capacity
Identification of conductors
Selection of conductors for voltage drop
Requirements for circuit conductors
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
64/135
64
Regulation 712 - 01 - 03 requires visual inspection to ensure
cables are correctly and adequately identified
Here are some examples of non-compliance
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
65/135
65
Regu
lation
514-01-01/0
2
Identification of conductors
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
66/135
66
Regu
lation
514-01-01/0
2
Identification of conductors
-
8/10/2019 2391- Inspection & Testing (Advanced)
67/135
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
68/135
68
Regu
lation
514-01-01/0
2
Identification of conductors
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
69/135
69
Regulation
514-01-01/0
2
Identification of conductors
-
8/10/2019 2391- Inspection & Testing (Advanced)
70/135
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
71/135
71
Regulation
52
6-01-01
Connection between conductors
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
72/135
72
Regulation
52
6-01-01
Taped joint between PVC and VRI cables
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
73/135
73
Regulation
52
6-01-01
Taped joint between PVC and VRI cables
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
74/135
74
Regulation
52
6-01-01
Faulty conductor termination
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
75/135
75
Result of insecure/loose connection
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
76/135
76
Result of insecure/loose connection
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
77/135
77
The Regulations require that connections and joint be accessible
for inspection, testing and maintenance. There are however FOUR
situations where this regulation does not apply. Identify these
FOUR situations.
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
78/135
78
Page 100
Regulation 526-04-01
(i) A compound-filled or encapsulated joint
(ii) A connection between a cold tail and a heating element
(iii) A joint made by welding, soldering, brazing or compression
tool
(iv) A joint forming part of the equipment complying with the
appropriate product standard
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
79/135
79
Page 100Regulation 526-04-01
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
80/135
80
Erection of wiring systems
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
81/135
81
Lid/covers not fitted
www.ElectaCourse.com
R
-
8/10/2019 2391- Inspection & Testing (Advanced)
82/135
82
Regulation
522
08
Lid/covers not fitted
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
83/135
83
Lid/covers not fitted
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
84/135
84
Enclosure door not secured
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
85/135
85
Equipment door forced open to defeat interlock
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
86/135
86
Enclosure not secured to wall
www.ElectaCourse.com
I
-
8/10/2019 2391- Inspection & Testing (Advanced)
87/135
87
Intern
ationalP
rotection
www.ElectaCourse.com
I
-
8/10/2019 2391- Inspection & Testing (Advanced)
88/135
88
Enclosure not secured to wall
Intern
ationalP
rotection
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
89/135
89
A visual inspection is to be carried out on a domestic installation.
Detail FIVE specific areas of visual inspection at the origin of thisinstallation.
For the purpose of this exercise the PES supply has been isolated
by the removal of the service head fuse.
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
90/135
90
Presence and size of earthing conductor
Presence and size of main equipotential bonding conductors
Type and rating of overcurrent protective devices
Prospective breaking capacity of overcurrent devices
Circuit and conductor identification
Type of earthing arrangement
IP rating of distribution board
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
91/135
91
A miniature circuit breaker within the distribution board is marked
as a Type 2, M6 device.
Describe the characteristics of this device and state to which
Standard it complies.
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
92/135
92
As the device carries an M rating its has been manufactured to
BS 3871 (now replaced by BS EN 60898 device)
M indicates its maximum prospective fault current value M6 = 6kA
6000A.
Type 2 indicates the instantaneous tripping characteristic4.07.0In.
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
93/135
93
Page 60 Guidance Note 3
Table 4.2 Rated short-circuit capacities
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
94/135
94
State TWO functional tests that may be applied at the distribution
board
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
95/135
95
Operation of circuit breakers
Operation of the main switch
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
96/135
96
State the hand lighting would you use if working in a confined
damp location?
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
97/135
97
Hand lighting provided from an SELV (Separated Extra-Low Voltage)
supply
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
98/135
98
Separated Extra-Low Voltage (SELV)
Supplied from a recognised safety source - Regulation
ELV conductors NOT referenced to earth - Regulation
Within voltage constraints - Regulation
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
99/135
99
The following information relates to a circuit breaker complying
with BS EN 60898.
Type B
Icn 10
Ics 7.5
State the meaning of each of the above terms
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
100/135
100
Type B relates to the instantaneous tripping characteristic of
the device. In this case 3 - 5 In (where In is the rating of thedevice in amperes
Icn - the rated short-circuit capacity (indicted on the device)
Ics the service short-circuit capacity.
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
101/135
101
Page 60 Guidance Note 3
Table 4.2 Rated short-circuit capacities
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
102/135
102
State TWO characteristics of the incoming supply that may be
determined by enquiry or measurement
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
103/135
103
Prospective fault current
External earth fault loop impedance
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
104/135
104
Page 33
313 Nature of supply
Regulation 313-01-01
Any of the following characteristics may be obtained bymeasurement or enquiry:
Nominal voltage, nature of current and frequency. Generally
however the two most common characteristics determined by
enquiry and calculation are Ze (external earth fault loop
impedance) and prospective fault current Ip.
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
105/135
105
Regulation 313-01-01 requires that the supply characteristics from
whatever source be verified. Give TWO examples of sources otherthan that of the PES supply that may supply an installation
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
106/135
106
Those of:
standby generators (alternators
Uninterruptible Power Supplies (UPS)
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
107/135
107
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
108/135
108
An RCD protected A2 radial circuit feeds five 13A socket outlets to
BS 1363. The circuit has been added to an existing installationwithin domestic premises.
identify the relevant document that should be completed for this
installation
The sequence of tests, in the correct order that should beapplied to this circuit
If the supply to the installation is TN-S state the main purpose of
the RCD
In the correct sequence identify the tests that should be applied
to the RCD
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
109/135
109
Minor Works Certificate
Continuity of CPCs
Provide supplementary protection against direct contact
x In
1 x I n
5 x In
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
110/135
110
Page29GN3
2.7.4 The sequence of tests
Page 171
Regulation 713-01-01 (sequence of tests)
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
111/135
111
State the action you would take if ONE of the tests undertaken in
question 22 indicated a defect
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
112/135
112
Determine whether fault would have any adverse effect on any
previous tests result
When rectified repeat any tests that may have been adversely
affected
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
113/135
113
Explain why applying a functional test only, to a residual current
device is unacceptable during a periodic inspection (PIR)
How often should an RCD undergo functional testing
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
114/135
114
Functional testing relies upon an imbalance between phase and
neutral within the toroidal winding of the device. It does not verify:
the presence of earthing conductor
the presence of any CPCs
the presence of any earthing arrangements
does not verify operating time or current
Functional testing applied at three month intervals
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
115/135
115
Page 61 GN
32.7.16 Operation of residual current devices
Page 173
Regulation 713-13-01 Functional testing
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
116/135
116
Explain why an insulation resistance test instrument is required to
produce a current of 1 mA when loaded at the minimum acceptablevalue of insulation as permitted by BS 7671?
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
117/135
117
Effect of instrument loading on output (terminal) voltage
0.5M 1.0M 10M
Terminal voltage
500V d.c.
Insulation resistance M
Minimum acceptable value for 230/400V circuits
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
118/135
118
Page 86 GN
4.4 Insulation resistance testers
Page 172
Regulation 713-04-03
An effective test for insulation can only be made if the outputvoltage is maintained by the instrument
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
119/135
119
Explain the possible danger of removing test probes from a circuit
under test before releasing the test button of an insulationresistance tester
-
8/10/2019 2391- Inspection & Testing (Advanced)
120/135
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
121/135
121
Page 86 GN
4.4 Insulation resistance testers
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
122/135
122
Explain the term standing voltage and the electrical test that may
give rise to this situation
Describe TWO methods of reducing the risk of shock from these
standing voltages
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
123/135
123
Restrict duration of instrument test currents
Place warning notices in location of test area
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
124/135
124
Page 86 GN
4.6 Earth fault loop impedance testers
Restrict test currents to 40mS
-
8/10/2019 2391- Inspection & Testing (Advanced)
125/135
-
8/10/2019 2391- Inspection & Testing (Advanced)
126/135
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
127/135
127
Page 86 GN
4.6 Earth fault loop impedance testers
Instruments to BS EN 61557-3 will comply with the requirements of
BS 7671 with regard to impedance testers
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
128/135
128
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
129/135
129
State the requirements of the Electricity @ Work Regulations 1989
with regard to access and lighting whilst undertaking a visualinspection of the distribution board.
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
130/135
130
Working space
Adequate to allow to pull back away from live conductors
without hazard
Adequate to allow persons to pass one another safely
Lighting
Natural light preferred. Where this is impractical permanent
lighting arrangements of an acceptable design should be
provided. At times, lighting may need to be temporary, i.e.
torches or hand lamps. Whichever method is employed the level
of lighting must be adequate to avoid injury
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
131/135
131
Page 38
Regulation 15 Working space, access and lighting
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
132/135
132
Means of escape in the event of an emergency
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
133/135
133
Means of escape blocked in the event of an emergency
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
134/135
134
Safe access and exit from workplace?
www.ElectaCourse.com
-
8/10/2019 2391- Inspection & Testing (Advanced)
135/135
A safe and tidy workplace!