2391- inspection & testing (advanced)

Upload: grandammar

Post on 02-Jun-2018

236 views

Category:

Documents


4 download

TRANSCRIPT

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    1/135

    1

    www.ElectaCourse.com

    Inspection Testingnspection Testing

    dvanced

    dvanced

    ElectaCourse.com

    2005 Last Updated August 2006

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    2/135

    2

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    3/135

    3

    www.ElectaCourse.com

    This presentation is suitable for those studying for the

    City & Guilds 2391 and 2400 courses

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    4/135

    4

    www.ElectaCourse.com

    The presentation includes guidance and

    continuous self-assessment

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    5/135

    5

    www.ElectaCourse.com

    In order to work through this presentation you will need copies

    Of the following publications

    BS 7671:2001 (16th Edition IEE Wiring Regulations)

    Guidance Note 3 (Inspection and Testing

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    6/135

    6

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    7/135

    7

    www.ElectaCourse.com

    To ensure the safety of any electrical installation it should be

    inspected, tested and the necessary certification completed:

    Before being put into service (initial verification)

    At regular intervals thereafter (Periodic Inspection Report)

    On completion of any alteration or addition

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    8/135

    8

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    9/135

    9

    www.ElectaCourse.com

    For an initial verification

    BS 7671:2002 states:

    Installed equipment to an appropriate standard, i.e. BS, BS EN

    Correctly selected and erected

    Not visibly damaged or defective as to impair safety

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    10/135

    10

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    11/135

    11

    www.ElectaCourse.com

    The Periodic Installation Report (PIR)

    BS 7671:2001 states:

    Periodic inspection and testing of an electrical installation

    shall be carried out to determine, so far as is reasonably

    practicable, whether the installation is in a satisfactory condition

    for continued service

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    12/135

    12

    www.ElectaCourse.com

    Generally, the main reason for undertaking an inspection and

    test is to ensure that the installation is safe to use

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    13/135

    13

    www.ElectaCourse.com

    What Are the likely reasons for an installation failing to be safe?

    Age

    Wear and tear

    Damage, i.e. fire, flooding etc

    Electrical overload

    DIY enthusiasts

    Unscrupulous contractors

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    14/135

    14

    www.ElectaCourse.com

    What factors would influence the need for a PIR

    Expiry of current certificate

    Change of ownership or use of the installation

    As a result of damage or electrical overloading

    Mortgage/insurance purposes

    Compliance with current regulations

    Local bylaw requirements

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    15/135

    15

    www.ElectaCourse.com

    What factors would influence the safety of an installation?

    Poorly installed equipment/accessories

    Loose connections giving rise to shock and or fire

    Inadequate overcurrent protection of equipment and circuits

    Underrated/overloaded circuit conductors

    Inadequate/non-existent earthing or bonding arrangements

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    16/135

    16

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    17/135

    17

    www.ElectaCourse.com

    Inspection always proceeds testing

    Prior to visual inspection the supply to the installation or part

    of the installation undergoing inspection should be

    disconnected from the supply

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    18/135

    18

    www.ElectaCourse.com

    Electrical installations which comply with BS 7671:2001 areregarded by the Health & Safety Executive as likely to achieve

    conformity with which statutory regulations?

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    19/135

    19

    www.ElectaCourse.com

    The Electricity at Work Regulations 1989

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    20/135

    20

    www.ElectaCourse.com

    Page 8BS 7671:2001 Note by the Health and Safety Executive

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    21/135

    21

    www.ElectaCourse.com

    Identify THREE areas which should be given consideration prior toundertaking alterations or additions to an existing electrical

    installation

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    22/135

    22

    www.ElectaCourse.com

    The ability of existing equipment including that of the supplier isadequate for the additional load

    The earthing arrangements are adequate

    The bonding arrangements are adequate

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    23/135

    23

    www.ElectaCourse.com

    Page 14130-07 Additions and alterations to an installation

    Regulation 130-07-01

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    24/135

    24

    www.ElectaCourse.com

    Identify SIX characteristics of the incoming electrical supply thatwould need to be ascertained by the person undertaking an

    inspection and test of an electrical installation

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    25/135

    25

    www.ElectaCourse.com

    (i) the nominal voltage(s)

    (ii) the nature of the current and frequency

    (iii) the prospective short circuit current at the origin

    (iv) the external earth fault loop impedance (Ze)

    (v) the suitability for the requirements of the installation

    including the maximum demand

    (vi) the type and rating of the overcurrent protective device

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    26/135

    26

    www.ElectaCourse.com

    Page 33313 Nature of Supply

    Regulation 313-01-01

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    27/135

    27

    www.ElectaCourse.com

    Identify two precautions that should be observed duringinspection and testing of an electrical installation

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    28/135

    28

    www.ElectaCourse.com

    avoid danger to persons

    avoid damage to property and installed equipment

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    29/135

    29

    www.ElectaCourse.com

    Page 170Chapter 71 - Initial Verification

    Regulation 711-01-01

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    30/135

    30

    www.ElectaCourse.com

    State the THREE requirements of BS 7671 with regard to installedelectrical equipment

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    31/135

    31

    www.ElectaCourse.com

    (i) in compliance with Section 511

    (ii) correctly selected and erected in accordance with the

    Regulations

    (iii) not visibly damaged or defective so as to impair safety

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    32/135

    32

    www.ElectaCourse.com

    Page 170 - Inspection

    Regulation 712 - 01 - 02

    Note: Section 511 deals with compliance with standards. All

    equipment should comply with the appropriate British Standard or

    Harmonized Standard - See page 84 - Selection and Erection of

    Equipment

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    33/135

    33

    www.ElectaCourse.com

    Identify TWO statutory, and FIVE non-statutory documents that aninspecting engineer may need to refer when undertaking an

    inspection and test on an electrical installation

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    34/135

    34

    www.ElectaCourse.com

    Statutory:

    Health and Safety at Work Act etc 1974

    Electricity at Work Regulation 1989

    Non-statutory:

    BS 7671:2001

    IEE Guidance Note 3 (Inspection and Testing

    IEE On-Site Guide

    GS 38 Equipment used by electricians (HSE Guidance) Memorandum of Guidance to The Electricity at Work Regulations

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    35/135

    35

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    36/135

    36

    www.ElectaCourse.com

    Visual inspection always precedes testing

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    37/135

    37

    www.ElectaCourse.com

    From the inspection check list within BS 7671 Identify THREE

    methods of protection against direct electric shock (contact)

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    38/135

    38

    www.ElectaCourse.com

    Insulation of live parts

    Barriers

    Enclosures

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    39/135

    39

    www.ElectaCourse.com

    Risk of direct contact. Barrier removed and not replaced

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    40/135

    40

    www.ElectaCourse.com

    Risk of direct contact. Barrier removed and not replaced

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    41/135

    41

    www.ElectaCourse.com

    Risk of direct contact.

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    42/135

    42

    www.ElectaCourse.com

    Page 170

    Regulation 712 - 01 - 03

    Two additional methods of protection against direct shock of a

    special nature are:

    Placing out of reach

    ObstaclesNote: this method of protection is intended to prevent

    inadvertent contact with live parts and therefore areas

    incorporating this type of protection should only be accessible to

    skilled persons only

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    43/135

    43

    www.ElectaCourse.com

    From the inspection check list within BS 7671 Identify THREE

    methods of protection against indirect contact

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    44/135

    44

    www.ElectaCourse.com

    EEBAD

    Class II

    Electrical Separation

    Non-conducting location

    Earth-free local equipotential bonding

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    45/135

    45

    www.ElectaCourse.com

    Page 170/171

    Regulation 712 - 01 - 03

    Note: Protection by non-conducting location and earth-free local

    equipotential bonding are both of a special nature and very rarely

    encountered

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    46/135

    46

    www.ElectaCourse.com

    From the inspection check list within BS 7671 Identify TWO methods

    of protection against both direct and indirect contact

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    47/135

    47

    www.ElectaCourse.com

    Separated extra-low voltage (SELV)

    Limitation of discharge energy

    El C

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    48/135

    48

    www.ElectaCourse.com

    Page 170/171

    Regulation 712 - 01 - 03

    El t C

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    49/135

    49

    www.ElectaCourse.com

    From the inspection check list within BS 7671 Identify FOUR types of

    protective conductor

    El t C

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    50/135

    50

    www.ElectaCourse.com

    earthing conductor

    circuit protective conductor (CPC)

    main equipotential bonding conductor

    supplementary equipotential bonding conductor

    www ElectaCourse com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    51/135

    51

    www.ElectaCourse.com

    Page 170/171

    Regulation 712 - 01 - 03

    www ElectaCourse com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    52/135

    52

    www.ElectaCourse.com

    Presence of main equipotential bonding conductors

    www ElectaCourse com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    53/135

    53

    www.ElectaCourse.com

    One requirement from Regulation 712-01-03 is the selection of

    equipment and protective measures appropriate to external

    influences. List the external influences likely to be encountered by

    an electrical installation located within a commercial greenhouse

    accessible to the general public.

    www ElectaCourse com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    54/135

    54

    www.ElectaCourse.com

    Ultra-violet radiation

    Extremes of temperature

    Mechanical damage

    Water/moisture/humidity

    Rodent attack

    Chemicals

    Corrosion

    Vandalism

    www ElectaCourse com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    55/135

    55

    www.ElectaCourse.com

    Page 170/171

    Regulation 712 - 01 - 03

    www ElectaCourse com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    56/135

    56

    www.ElectaCourse.com

    Regulation 712 - 01 - 03 requires visual inspection to ensure

    cables are routed in safe zones and also considers erection

    methods.

    Here are some examples of non-compliance

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    57/135

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    58/135

    58

    Regu

    lations

    5

    22-08

    Routing of cables

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    59/135

    59

    Regu

    lation

    52

    2-08

    Routing of cables

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    60/135

    60

    Regu

    lations

    5

    22-08

    Routing of cables

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    61/135

    61

    Regu

    lations

    522-08

    Routing of cables

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    62/135

    62

    Regu

    lations

    522-08

    Routing of cables

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    63/135

    63

    Selection of conductors for current carrying capacity

    Identification of conductors

    Selection of conductors for voltage drop

    Requirements for circuit conductors

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    64/135

    64

    Regulation 712 - 01 - 03 requires visual inspection to ensure

    cables are correctly and adequately identified

    Here are some examples of non-compliance

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    65/135

    65

    Regu

    lation

    514-01-01/0

    2

    Identification of conductors

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    66/135

    66

    Regu

    lation

    514-01-01/0

    2

    Identification of conductors

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    67/135

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    68/135

    68

    Regu

    lation

    514-01-01/0

    2

    Identification of conductors

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    69/135

    69

    Regulation

    514-01-01/0

    2

    Identification of conductors

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    70/135

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    71/135

    71

    Regulation

    52

    6-01-01

    Connection between conductors

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    72/135

    72

    Regulation

    52

    6-01-01

    Taped joint between PVC and VRI cables

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    73/135

    73

    Regulation

    52

    6-01-01

    Taped joint between PVC and VRI cables

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    74/135

    74

    Regulation

    52

    6-01-01

    Faulty conductor termination

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    75/135

    75

    Result of insecure/loose connection

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    76/135

    76

    Result of insecure/loose connection

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    77/135

    77

    The Regulations require that connections and joint be accessible

    for inspection, testing and maintenance. There are however FOUR

    situations where this regulation does not apply. Identify these

    FOUR situations.

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    78/135

    78

    Page 100

    Regulation 526-04-01

    (i) A compound-filled or encapsulated joint

    (ii) A connection between a cold tail and a heating element

    (iii) A joint made by welding, soldering, brazing or compression

    tool

    (iv) A joint forming part of the equipment complying with the

    appropriate product standard

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    79/135

    79

    Page 100Regulation 526-04-01

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    80/135

    80

    Erection of wiring systems

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    81/135

    81

    Lid/covers not fitted

    www.ElectaCourse.com

    R

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    82/135

    82

    Regulation

    522

    08

    Lid/covers not fitted

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    83/135

    83

    Lid/covers not fitted

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    84/135

    84

    Enclosure door not secured

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    85/135

    85

    Equipment door forced open to defeat interlock

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    86/135

    86

    Enclosure not secured to wall

    www.ElectaCourse.com

    I

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    87/135

    87

    Intern

    ationalP

    rotection

    www.ElectaCourse.com

    I

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    88/135

    88

    Enclosure not secured to wall

    Intern

    ationalP

    rotection

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    89/135

    89

    A visual inspection is to be carried out on a domestic installation.

    Detail FIVE specific areas of visual inspection at the origin of thisinstallation.

    For the purpose of this exercise the PES supply has been isolated

    by the removal of the service head fuse.

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    90/135

    90

    Presence and size of earthing conductor

    Presence and size of main equipotential bonding conductors

    Type and rating of overcurrent protective devices

    Prospective breaking capacity of overcurrent devices

    Circuit and conductor identification

    Type of earthing arrangement

    IP rating of distribution board

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    91/135

    91

    A miniature circuit breaker within the distribution board is marked

    as a Type 2, M6 device.

    Describe the characteristics of this device and state to which

    Standard it complies.

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    92/135

    92

    As the device carries an M rating its has been manufactured to

    BS 3871 (now replaced by BS EN 60898 device)

    M indicates its maximum prospective fault current value M6 = 6kA

    6000A.

    Type 2 indicates the instantaneous tripping characteristic4.07.0In.

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    93/135

    93

    Page 60 Guidance Note 3

    Table 4.2 Rated short-circuit capacities

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    94/135

    94

    State TWO functional tests that may be applied at the distribution

    board

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    95/135

    95

    Operation of circuit breakers

    Operation of the main switch

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    96/135

    96

    State the hand lighting would you use if working in a confined

    damp location?

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    97/135

    97

    Hand lighting provided from an SELV (Separated Extra-Low Voltage)

    supply

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    98/135

    98

    Separated Extra-Low Voltage (SELV)

    Supplied from a recognised safety source - Regulation

    ELV conductors NOT referenced to earth - Regulation

    Within voltage constraints - Regulation

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    99/135

    99

    The following information relates to a circuit breaker complying

    with BS EN 60898.

    Type B

    Icn 10

    Ics 7.5

    State the meaning of each of the above terms

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    100/135

    100

    Type B relates to the instantaneous tripping characteristic of

    the device. In this case 3 - 5 In (where In is the rating of thedevice in amperes

    Icn - the rated short-circuit capacity (indicted on the device)

    Ics the service short-circuit capacity.

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    101/135

    101

    Page 60 Guidance Note 3

    Table 4.2 Rated short-circuit capacities

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    102/135

    102

    State TWO characteristics of the incoming supply that may be

    determined by enquiry or measurement

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    103/135

    103

    Prospective fault current

    External earth fault loop impedance

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    104/135

    104

    Page 33

    313 Nature of supply

    Regulation 313-01-01

    Any of the following characteristics may be obtained bymeasurement or enquiry:

    Nominal voltage, nature of current and frequency. Generally

    however the two most common characteristics determined by

    enquiry and calculation are Ze (external earth fault loop

    impedance) and prospective fault current Ip.

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    105/135

    105

    Regulation 313-01-01 requires that the supply characteristics from

    whatever source be verified. Give TWO examples of sources otherthan that of the PES supply that may supply an installation

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    106/135

    106

    Those of:

    standby generators (alternators

    Uninterruptible Power Supplies (UPS)

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    107/135

    107

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    108/135

    108

    An RCD protected A2 radial circuit feeds five 13A socket outlets to

    BS 1363. The circuit has been added to an existing installationwithin domestic premises.

    identify the relevant document that should be completed for this

    installation

    The sequence of tests, in the correct order that should beapplied to this circuit

    If the supply to the installation is TN-S state the main purpose of

    the RCD

    In the correct sequence identify the tests that should be applied

    to the RCD

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    109/135

    109

    Minor Works Certificate

    Continuity of CPCs

    Provide supplementary protection against direct contact

    x In

    1 x I n

    5 x In

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    110/135

    110

    Page29GN3

    2.7.4 The sequence of tests

    Page 171

    Regulation 713-01-01 (sequence of tests)

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    111/135

    111

    State the action you would take if ONE of the tests undertaken in

    question 22 indicated a defect

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    112/135

    112

    Determine whether fault would have any adverse effect on any

    previous tests result

    When rectified repeat any tests that may have been adversely

    affected

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    113/135

    113

    Explain why applying a functional test only, to a residual current

    device is unacceptable during a periodic inspection (PIR)

    How often should an RCD undergo functional testing

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    114/135

    114

    Functional testing relies upon an imbalance between phase and

    neutral within the toroidal winding of the device. It does not verify:

    the presence of earthing conductor

    the presence of any CPCs

    the presence of any earthing arrangements

    does not verify operating time or current

    Functional testing applied at three month intervals

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    115/135

    115

    Page 61 GN

    32.7.16 Operation of residual current devices

    Page 173

    Regulation 713-13-01 Functional testing

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    116/135

    116

    Explain why an insulation resistance test instrument is required to

    produce a current of 1 mA when loaded at the minimum acceptablevalue of insulation as permitted by BS 7671?

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    117/135

    117

    Effect of instrument loading on output (terminal) voltage

    0.5M 1.0M 10M

    Terminal voltage

    500V d.c.

    Insulation resistance M

    Minimum acceptable value for 230/400V circuits

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    118/135

    118

    Page 86 GN

    4.4 Insulation resistance testers

    Page 172

    Regulation 713-04-03

    An effective test for insulation can only be made if the outputvoltage is maintained by the instrument

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    119/135

    119

    Explain the possible danger of removing test probes from a circuit

    under test before releasing the test button of an insulationresistance tester

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    120/135

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    121/135

    121

    Page 86 GN

    4.4 Insulation resistance testers

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    122/135

    122

    Explain the term standing voltage and the electrical test that may

    give rise to this situation

    Describe TWO methods of reducing the risk of shock from these

    standing voltages

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    123/135

    123

    Restrict duration of instrument test currents

    Place warning notices in location of test area

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    124/135

    124

    Page 86 GN

    4.6 Earth fault loop impedance testers

    Restrict test currents to 40mS

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    125/135

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    126/135

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    127/135

    127

    Page 86 GN

    4.6 Earth fault loop impedance testers

    Instruments to BS EN 61557-3 will comply with the requirements of

    BS 7671 with regard to impedance testers

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    128/135

    128

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    129/135

    129

    State the requirements of the Electricity @ Work Regulations 1989

    with regard to access and lighting whilst undertaking a visualinspection of the distribution board.

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    130/135

    130

    Working space

    Adequate to allow to pull back away from live conductors

    without hazard

    Adequate to allow persons to pass one another safely

    Lighting

    Natural light preferred. Where this is impractical permanent

    lighting arrangements of an acceptable design should be

    provided. At times, lighting may need to be temporary, i.e.

    torches or hand lamps. Whichever method is employed the level

    of lighting must be adequate to avoid injury

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    131/135

    131

    Page 38

    Regulation 15 Working space, access and lighting

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    132/135

    132

    Means of escape in the event of an emergency

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    133/135

    133

    Means of escape blocked in the event of an emergency

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    134/135

    134

    Safe access and exit from workplace?

    www.ElectaCourse.com

  • 8/10/2019 2391- Inspection & Testing (Advanced)

    135/135

    A safe and tidy workplace!