25410 fug ler
TRANSCRIPT
-
7/29/2019 25410 Fug Ler
1/5
3 2 A S H R A E J o u r n a l a s h r a e . o r g J u n e 2 0 0 5
energy retrofitting consisting of a 40%eduction in delivered fuels and elec-
ricity supplied to these houses. A 40%
eduction in delivered energy sounded
like a laudable, if somewhat improbable,
oal. The research described here shows
ow five houses in the mid-Canadian
province of Saskatchewan approached
his 40% goal.
In Saskatchewan energy efficiency is
seen as a means of self-defense. Think
North Dakota, only colder. Midwinter
emperatures of 40C (40F) are com-
on. Houses in Saskatchewan are typi-
cally the tightest in Canada, as any winter
wind whistling through the envelope is
apt to kill nearby plants.
Reducing HouseEnergy Costs by 40%By Don Fugler, P.E., Member ASHRAE, Rob Dumont, Ph.D., Member ASHRAE,
and Tom MacDermott, Associate Member ASHRAE
The Kyoto Protocol1 requires participating nations to limit growth
of greenhouse gases, or reduce them, with the GHG production
of 2010 to be compared to a baseline of 1990.
The next several years will be a challenge for countries that are
not meeting goals. In Canada, the federal government has accepted
the national challenge posed by Kyoto and is looking for ways to
reduce GHG emissions. This article describes a Canadian research
pilot project on achieving major energy reductions in housing.
The pilot project had a somewhat more
ambitious goal than that set by govern-
ment policy makers dealing with Kyoto
requirements. In a report published in
1996 by Canada Mortgage and Hous-
ing Corporation,2 the consultant used a
slightly longer timeline (1988 to 2030).
He calculated what sort of residential
retrofit measures would need to occur so
that total residential greenhouse gases
would be lower in 2030 than they were
in 1990, despite a significant growth in
the number of houses and people.
In one scenario, all new houses would
need to be built better than the current
R-2000 energy efficiency guidelines.3
Moreover, a high percentage (80%) of
the existing stock would require extensive
005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
w.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 6, June). This article may not be copied nor distributed in either paper or digital form without
RAEs permission.
About the AuthorsDon Fugler, P.E., is a senior researcher in the
Policy and Research Division of Canada Mortgage
and Housing Corp., Ottawa. Rob Dumont, Ph.D.,is section leader and Tom MacDermott is associ-
ate research engineer at the Building Performance
ection of the Saskatchewan Research Council in
askatoon, SK, Canada.
-
7/29/2019 25410 Fug Ler
2/5
J u n e 2 0 0 5 A S H R A E J o u r n a l 3 3
A productive low income weatherization program has existedfor the last two decades in American housing. Much of the
weatherization experience and knowledge comes from people
who have been energy retrofitting houses across the United
States, some in climates as severe as Canada. Heating season
savings of 15% to 30% in natural gas are achieved by the best
programs.4
The Canadian research was a little different in that both the
delivered natural gas and electrical energy were monitored, and
t was the annual use that counted. The houses
volunteered for the retrofit were not selected as
being high potential savers: all houses had attic
nsulation; all houses had some wall insulation;three of five houses had basement wall insulation;
all had at least storm windows; and three of five
already had setback thermostats. The houses represented typical
Canadian housing stock and its potential for retrofit.
The research agency of the consultant was large enough
to find five homeowners within its ranks to participate in the
study. Homeowners financed the retrofits themselves, based on
advice provided by the research team. They were given a small
honorarium in exchange for the disruption of their lives by the
team doing testing and monitoring. While the five houses may
more or less represent Canadian stock, it is likely that the fami-
lies selected from a research establishment are more willing to
participate in an energy retrofit than most other Canadians.The retrofit measures considered had to be commercially
available and have a simple payback of less than 15 years. The
nstalled measures could not compromise the health or safety
of the occupants, or degrade the indoor environment in the
pursuit of energy conservation. Preretrofit characterization
ncluded house airtightness testing by blower door, testing of
existing furnace and water heating efficiency, compilation of the
performance of various electrical appliances within the house,
and full documentation of house conditions to
permit modeling by the HOT2000 simulation
program.
All homeowners had to provide full utilityrecords and permit the collection of utility
data during the research period. The HOT2000
modeling for each house allowed for consideration of what
measures would be necessary to achieve the 40% target. In ret-
rospect, as homeowners managed the retrofit work themselves,
t would have been prudent to have set a goal somewhat higher
han 40%, so the target would be achieved even with partial
mplementation of measures.
Table 1 outlines some of the more common retrofits recom-
mended for the five houses. The D and G house nomenclature
s derived from the house selection process, and has been kept
only for congruence with the full report.6
The Canadian research was a little different in that both the delivered natural gas andelectrical energy were monitored, and it was the annual use that counted.
A 40% reduction in delivered
energy sounded like a laud-
able, if somewhat improb-
able, goal. The research de-
cribed here shows how five
ouses in the mid-Canadian
rovince of Saskatchewan
approached this 40% goal.
-
7/29/2019 25410 Fug Ler
3/5
3 4 A S H R A E J o u r n a l a s h r a e . o r g J u n e 2 0 0 5
easure
o es es es es
ondensing Induced Draft Furnace 60 kBtu/h 60 kBtu/h 60 kBtu/h 90 kBtu/h
Furnace 75 kBtu/h Input Input Input Input Input
22.0 kW, 80% 85% Efficient 17.5 kW 17.5 kW 17.5 kW 26.4 kW
ower ente o nsu ate esnsu ate esnsu ate es nsu ate esnsu ate
ater eater an an an an an
imney eave s s iminate iminate iminate iminate
asement aes es o o
es ninsuate
nsu ation ortions
es es es es
ttic nsu ation . . . .o
to at art
Windows Add Acrylic Pane In Living Room Add Acrylic Pane Add Acrylic Pane
ir ea ing es es es
New Major Appliances
e ri erator es o es oes ne se
ear
isconnect e rigeratorYes
es se
n asement ear
tove No No No No No
ot es as er es es es
ront oa ing
Dryer New
is was er ew
Existing Ones
Use 1472 kWh/Year and
reezers ear. ep ace
it nit
pprox. ear
ompact FluorescentYes Yes Yes Yes Yes
Lighting
ater onservat on easures
Toilet Dams Yes Yes Yes Yes Yes
ow ow ower ea s es es es es es
thernsta cient x aust ans es es es es es
Switch to IntermittentConsider Intermittent
urnace an peration,Furnace Fan Controller
onsi er ntermittent urnaceor ummer se
an ontro er
LandscapingRedirect SurfaceYes
Water Away From House
Table 1: Recommendations for common retrofits for the five houses.
The homeowners did follow through on most
recommendations. The predicted performance of
some retrofit measures far exceeded the energy
savings actually realized. Air sealing is a case inpoint. Two of the five houses (D1 and G3) were
very airtight, at less than two air changes per hour
at 50 Pa (0.2 in. w.g.) (ACPH ) during the blower
door test. No improvement to airtightness was rec-
ommended for these two houses. The other three
houses ranged from 6.26 to 7.71 ACPH 0. One cut
its air leakage rate in half through diligent retrofit
effort, but the other two houses only had marginal
improvements in airtightness. The lack of a robust
weatherization industry in Canada, unlike parts of
the United States, means that the expertise needed
for competent air sealing is uncommon.
Other shortcomings were due more to voli-
tion than expertise. At least one homeowner
pref er red the conve nien ce of computer s
constantly running to the energy savings ofturning them off during periods of non-use.
Some of the retrofits brought their own energy
penalties. Mechanically vented water heaters,
while helping to eliminate chimneys, had high
electrical power consumption. A replacement
furnace had a circulating fan that required twice
the power of the fan in the old furnace. These
inefficiencies had not been predicted in the
modeling exercises.
Figure 1 shows the comparison of natural gas
consumption of house G1 prior to and following
the retrofit work. The change in slope allowed
A do-it-yourself hot watertank insulation before the
retrofit.
-
7/29/2019 25410 Fug Ler
4/5
J u n e 2 0 0 5 A S H R A E J o u r n a l 3 5
calculation of gas reductions per degree day and permitted
normalization of the findings to a standard year.
The weather during the year following retrofit was milder
than most. Curiously, the incoming water temperature to the
house and water heater was 3C (5C) colder than normal. No
adjustment was made for the water temperature.
Table 2 shows the electrical and natural gas savings realized
n the project. The combined energy savings plus costs and pay-
back calculations are shown in Table 3 One house reached the
40% savings goal on total energy savings. The rest ranged from
24% to 31% improvement. The gas consumption savings werenormalized to account for variations
n weather during the monitoring
period that deviated from historical
averages. The data tabulated is from
the degree day correction. Data
modification by the control house
method showed even greater relative
energy savings.
In Table 3, costs do not include
labor contributed by the hom-
eowner, which was extensive in
some cases.
What Worked
The substitution of high-
efficiency furnaces in four of five houses for the original con-
ventional gas furnaces produced substantial and predictable
savings. Preretrofit instantaneous furnace efficiencies ranged
from 75% to 77.8%. The four high-efficiency furnaces had
measured efficiencies at the furnace of 90.9% to 92.6%. House
D1 had a mid-efficiency furnace installed, and its measured
efficiency was 78.8%.
Furnace electrical efficiency did not improve in a consistent
way. The motors providing the power venting for the high-effi-
ciency furnaces contributed 52 to 101 W when the burners were
on. The furnace circulating fans were sometimes higher and
sometimes lower in consumption than the fans in the replaced
furnaces. House G1 reduced the circulating fan high cycleconsumption from 703 to 323 W. House G3 saw a reduction of
420 to 230 W. However, in House G2 the consumption increased
from 290 to 380 W and in House G4 the furnace circulating
fan consumption jumped from 360 to 800 W with the furnace
replacement. House D1 and G3 ran their fans continuously for
ventilation purposes, despite the high energy costs that this
practice entails.
The water heaters originally located in the houses had
instantaneous efficiencies ranging from 74.1% to 82%. The
power-vented water heaters that replaced these units had slightly
higher efficiencies on average, 71.9% to 83.8%, but they also
contributed to an increase in electrical consumption with steadystate blower motor consumption of
65 to 95 W.
The sidewall vented water
heaters, combined with high-
efficiency furnaces, meant that the
existing chimneys could be sealed,
adding to the airtightness of the
house, likely reducing winter air
change rate, and reducing the risk of
combustion spillage. However, from
an energy consumption viewpoint,
the power vented water heatersmade marginal contributions to
savings, if any. A shortage exists
of inexpensive, energy-efficient
equipment for residential water heating. Instantaneously fired
units could be investigated for future retrofits.
The other reliable saving opportunity, besides furnaces, was
replacement of old electrical appliances with new, efficient units.
The original refrigerators consumed between 1100 to 1700 kWh
per year. The efficient units purchased were rated around 400 to
600 kWh/year. Similar savings were realized with freezer replace-
ments. House G3 replaced two old freezers with one new one,
dropping annual consumption from about 2300 kWh to just over
0 5 10 15 20 25 30 35 40
Heating Degree Days Per Day (C days/day)
30
20
15
10
5
NaturalGasConsumption(m
/day
reretro t
Post-Retrofit
Linear (Preretrofit)
Linear (Post-Retrofit)
otesPreretrofit data May 22, 1997 to June 9, 2001
Post-Retrofit data Feb. 17, 2002 to Dec. 31, 2002
Normalized Consumption = slope 6077 HDD + intercept 365 days
Pre = 0.6682 6077 + 0.2669 365 = 4158 m3
ost = . + . = . m3
avings = ost re =
Figure 1: Sample calculation for natural gas consumption.
Basement wall being insulated with the header in the midst of hav-ng foam board applied.
Table 2: Gas and electricity savings.
House Preretrofit Post-Retrofit Savings
as nnua u c eters
D1 4082 2842 30.4%
.
G2 4365 3100 29.0%
.
G4 6552 4855 25.4%
ectrc ty / ear
D1 9728 8847 9.1%
.
G2 8454 7155 15.4%
.
G4 7945 7440 6.4%
= .
y= 0.351x+ 0.4179
R2 = 0.9711
-
7/29/2019 25410 Fug Ler
5/5
3 6 A S H R A E J o u r n a l a s h r a e . o r g J u n e 2 0 0 5
400 kWh. The cheapest and ostensibly
easiest savings were simply to unplug the
beer fridge in the basement and save
the 1100 kWh that it used annually. Such
savings are more certain if the appliance
is actually thrown away or recycled, rather
than just unplugged. Substitution of com-
pact fluorescent lights (CFL) for com-
monly used incandescent bulbs shouldreduce energy consumption but the individual fixtures were not
monitored. Some premature CFL failures occurred with one
purchased brand.
Savings from house or water heater insulation, air sealing,
door replacement, low flow showerheads, and other improve-
ments could not be specifically attributed.
ouse otaTotal Simple
Cost, Payback,$Can Years
D1 26.5% 4,420 8.4
. , .
G2 26.9% 9,415 16.5
. , .G4 23.9% 7,225 11.5
Table 3: Retrofit costs and payback.
New HVAC and laundry equipment.
Lessons Learned
For houses without high-efficiency equip-
ment, saving 40% on energy bills or green-
house gas production can be achieved.
These research results suggest that the
recommended saving opportunities should
be in the 50% range for the 40% goal to be
realized for most homeowners.
The projected costs for such retrofits will be
$5,000 to $10,000 ($Can), and possibly more
f the homeowner contracts out all the labor.
The return on investment typically will be
better than found in mutual funds or bonds of
the last several years. The five homeowners in
the Saskatchewan project were satisfied with
the savings realized and the ancillary benefits
(e.g., more habitable basements).
Easy savings can be achieved through the
replacement of inefficient furnaces and majorappliances, particularly refrigeration equipment. Savings on water
heating equipment were more elusive. Computer modeling needs
to account for the electrical energy consumed by the motors on
gas appliances. This data may be hard to obtain from conventional
sources but is critical in the projection of electricity use.
This small project does not have enough data on the effects
of wall or attic re-insulation, or on envelope tightening to
quantify these effects. It is likely that retrofit work spurred by
the EnerGuide for Houses program7 will lead to contractors
having more experience and skills in these domains, which
will be more effective.
Homeowners may benefit from documentation that disag-gregates electrical loads, showing the impact of choices such
as maintaining a second refrigerator, continuous running of the
furnace circulating fan, or keeping electronic equipment such
as computers in constant operation. Electrical savings in this
pilot ranged from negligible to substantial. The gas savings
was more consistent.
References1. 1997. Full text of the Kyoto Protocol is available at www.emis-
sionstrategies.com/GHG/kpeng.htm.2. Cooper, K. 1996. Res ent a Retro t Potent a n Cana a. SAR
Eng neer ng report or Cana a Mortgage an Hous ng Corporat on.
. NRCan. 2004. Deta s on t e Natura Resources Cana a R-2000program can e oun at ttp: oee.nrcan.gc.ca res ent a personanew-homes/r-2000/About-r-2000.cfm?attr=12.
. Berry, L. and M. Schweitzer. 2003. Meta-evaluation of NationalWeatherization Assistance Program Based on State Studies, 19932002. Oak Ridge National Laboratory report (ORNL/CON-488) forthe U.S. Department of Energy.
5. NRCan. 2004. Down oa t e HOT2000 computer s mu at on pro-gram at www. u ngsgroup.nrcan.gc.ca so tware ot2000_e. tm .
6. Dumont, R.S., et a . 2003. Case Stu es o Ma or Home EnergyRetro ts. Sas atc ewan Researc Counc report or Cana a Mortgageand Housing Corporation.
7. NRCan. 2004. Details on the EnerGuide for Houses program canbe found at http://oee.nrcan.gc.ca/residential/energystar-energuide-
r2000.cfm?attr=4.
Advertisement formerly in this space.