25410 fug ler

Upload: troscian7

Post on 14-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 25410 Fug Ler

    1/5

    3 2 A S H R A E J o u r n a l a s h r a e . o r g J u n e 2 0 0 5

    energy retrofitting consisting of a 40%eduction in delivered fuels and elec-

    ricity supplied to these houses. A 40%

    eduction in delivered energy sounded

    like a laudable, if somewhat improbable,

    oal. The research described here shows

    ow five houses in the mid-Canadian

    province of Saskatchewan approached

    his 40% goal.

    In Saskatchewan energy efficiency is

    seen as a means of self-defense. Think

    North Dakota, only colder. Midwinter

    emperatures of 40C (40F) are com-

    on. Houses in Saskatchewan are typi-

    cally the tightest in Canada, as any winter

    wind whistling through the envelope is

    apt to kill nearby plants.

    Reducing HouseEnergy Costs by 40%By Don Fugler, P.E., Member ASHRAE, Rob Dumont, Ph.D., Member ASHRAE,

    and Tom MacDermott, Associate Member ASHRAE

    The Kyoto Protocol1 requires participating nations to limit growth

    of greenhouse gases, or reduce them, with the GHG production

    of 2010 to be compared to a baseline of 1990.

    The next several years will be a challenge for countries that are

    not meeting goals. In Canada, the federal government has accepted

    the national challenge posed by Kyoto and is looking for ways to

    reduce GHG emissions. This article describes a Canadian research

    pilot project on achieving major energy reductions in housing.

    The pilot project had a somewhat more

    ambitious goal than that set by govern-

    ment policy makers dealing with Kyoto

    requirements. In a report published in

    1996 by Canada Mortgage and Hous-

    ing Corporation,2 the consultant used a

    slightly longer timeline (1988 to 2030).

    He calculated what sort of residential

    retrofit measures would need to occur so

    that total residential greenhouse gases

    would be lower in 2030 than they were

    in 1990, despite a significant growth in

    the number of houses and people.

    In one scenario, all new houses would

    need to be built better than the current

    R-2000 energy efficiency guidelines.3

    Moreover, a high percentage (80%) of

    the existing stock would require extensive

    005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

    w.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 6, June). This article may not be copied nor distributed in either paper or digital form without

    RAEs permission.

    About the AuthorsDon Fugler, P.E., is a senior researcher in the

    Policy and Research Division of Canada Mortgage

    and Housing Corp., Ottawa. Rob Dumont, Ph.D.,is section leader and Tom MacDermott is associ-

    ate research engineer at the Building Performance

    ection of the Saskatchewan Research Council in

    askatoon, SK, Canada.

  • 7/29/2019 25410 Fug Ler

    2/5

    J u n e 2 0 0 5 A S H R A E J o u r n a l 3 3

    A productive low income weatherization program has existedfor the last two decades in American housing. Much of the

    weatherization experience and knowledge comes from people

    who have been energy retrofitting houses across the United

    States, some in climates as severe as Canada. Heating season

    savings of 15% to 30% in natural gas are achieved by the best

    programs.4

    The Canadian research was a little different in that both the

    delivered natural gas and electrical energy were monitored, and

    t was the annual use that counted. The houses

    volunteered for the retrofit were not selected as

    being high potential savers: all houses had attic

    nsulation; all houses had some wall insulation;three of five houses had basement wall insulation;

    all had at least storm windows; and three of five

    already had setback thermostats. The houses represented typical

    Canadian housing stock and its potential for retrofit.

    The research agency of the consultant was large enough

    to find five homeowners within its ranks to participate in the

    study. Homeowners financed the retrofits themselves, based on

    advice provided by the research team. They were given a small

    honorarium in exchange for the disruption of their lives by the

    team doing testing and monitoring. While the five houses may

    more or less represent Canadian stock, it is likely that the fami-

    lies selected from a research establishment are more willing to

    participate in an energy retrofit than most other Canadians.The retrofit measures considered had to be commercially

    available and have a simple payback of less than 15 years. The

    nstalled measures could not compromise the health or safety

    of the occupants, or degrade the indoor environment in the

    pursuit of energy conservation. Preretrofit characterization

    ncluded house airtightness testing by blower door, testing of

    existing furnace and water heating efficiency, compilation of the

    performance of various electrical appliances within the house,

    and full documentation of house conditions to

    permit modeling by the HOT2000 simulation

    program.

    All homeowners had to provide full utilityrecords and permit the collection of utility

    data during the research period. The HOT2000

    modeling for each house allowed for consideration of what

    measures would be necessary to achieve the 40% target. In ret-

    rospect, as homeowners managed the retrofit work themselves,

    t would have been prudent to have set a goal somewhat higher

    han 40%, so the target would be achieved even with partial

    mplementation of measures.

    Table 1 outlines some of the more common retrofits recom-

    mended for the five houses. The D and G house nomenclature

    s derived from the house selection process, and has been kept

    only for congruence with the full report.6

    The Canadian research was a little different in that both the delivered natural gas andelectrical energy were monitored, and it was the annual use that counted.

    A 40% reduction in delivered

    energy sounded like a laud-

    able, if somewhat improb-

    able, goal. The research de-

    cribed here shows how five

    ouses in the mid-Canadian

    rovince of Saskatchewan

    approached this 40% goal.

  • 7/29/2019 25410 Fug Ler

    3/5

    3 4 A S H R A E J o u r n a l a s h r a e . o r g J u n e 2 0 0 5

    easure

    o es es es es

    ondensing Induced Draft Furnace 60 kBtu/h 60 kBtu/h 60 kBtu/h 90 kBtu/h

    Furnace 75 kBtu/h Input Input Input Input Input

    22.0 kW, 80% 85% Efficient 17.5 kW 17.5 kW 17.5 kW 26.4 kW

    ower ente o nsu ate esnsu ate esnsu ate es nsu ate esnsu ate

    ater eater an an an an an

    imney eave s s iminate iminate iminate iminate

    asement aes es o o

    es ninsuate

    nsu ation ortions

    es es es es

    ttic nsu ation . . . .o

    to at art

    Windows Add Acrylic Pane In Living Room Add Acrylic Pane Add Acrylic Pane

    ir ea ing es es es

    New Major Appliances

    e ri erator es o es oes ne se

    ear

    isconnect e rigeratorYes

    es se

    n asement ear

    tove No No No No No

    ot es as er es es es

    ront oa ing

    Dryer New

    is was er ew

    Existing Ones

    Use 1472 kWh/Year and

    reezers ear. ep ace

    it nit

    pprox. ear

    ompact FluorescentYes Yes Yes Yes Yes

    Lighting

    ater onservat on easures

    Toilet Dams Yes Yes Yes Yes Yes

    ow ow ower ea s es es es es es

    thernsta cient x aust ans es es es es es

    Switch to IntermittentConsider Intermittent

    urnace an peration,Furnace Fan Controller

    onsi er ntermittent urnaceor ummer se

    an ontro er

    LandscapingRedirect SurfaceYes

    Water Away From House

    Table 1: Recommendations for common retrofits for the five houses.

    The homeowners did follow through on most

    recommendations. The predicted performance of

    some retrofit measures far exceeded the energy

    savings actually realized. Air sealing is a case inpoint. Two of the five houses (D1 and G3) were

    very airtight, at less than two air changes per hour

    at 50 Pa (0.2 in. w.g.) (ACPH ) during the blower

    door test. No improvement to airtightness was rec-

    ommended for these two houses. The other three

    houses ranged from 6.26 to 7.71 ACPH 0. One cut

    its air leakage rate in half through diligent retrofit

    effort, but the other two houses only had marginal

    improvements in airtightness. The lack of a robust

    weatherization industry in Canada, unlike parts of

    the United States, means that the expertise needed

    for competent air sealing is uncommon.

    Other shortcomings were due more to voli-

    tion than expertise. At least one homeowner

    pref er red the conve nien ce of computer s

    constantly running to the energy savings ofturning them off during periods of non-use.

    Some of the retrofits brought their own energy

    penalties. Mechanically vented water heaters,

    while helping to eliminate chimneys, had high

    electrical power consumption. A replacement

    furnace had a circulating fan that required twice

    the power of the fan in the old furnace. These

    inefficiencies had not been predicted in the

    modeling exercises.

    Figure 1 shows the comparison of natural gas

    consumption of house G1 prior to and following

    the retrofit work. The change in slope allowed

    A do-it-yourself hot watertank insulation before the

    retrofit.

  • 7/29/2019 25410 Fug Ler

    4/5

    J u n e 2 0 0 5 A S H R A E J o u r n a l 3 5

    calculation of gas reductions per degree day and permitted

    normalization of the findings to a standard year.

    The weather during the year following retrofit was milder

    than most. Curiously, the incoming water temperature to the

    house and water heater was 3C (5C) colder than normal. No

    adjustment was made for the water temperature.

    Table 2 shows the electrical and natural gas savings realized

    n the project. The combined energy savings plus costs and pay-

    back calculations are shown in Table 3 One house reached the

    40% savings goal on total energy savings. The rest ranged from

    24% to 31% improvement. The gas consumption savings werenormalized to account for variations

    n weather during the monitoring

    period that deviated from historical

    averages. The data tabulated is from

    the degree day correction. Data

    modification by the control house

    method showed even greater relative

    energy savings.

    In Table 3, costs do not include

    labor contributed by the hom-

    eowner, which was extensive in

    some cases.

    What Worked

    The substitution of high-

    efficiency furnaces in four of five houses for the original con-

    ventional gas furnaces produced substantial and predictable

    savings. Preretrofit instantaneous furnace efficiencies ranged

    from 75% to 77.8%. The four high-efficiency furnaces had

    measured efficiencies at the furnace of 90.9% to 92.6%. House

    D1 had a mid-efficiency furnace installed, and its measured

    efficiency was 78.8%.

    Furnace electrical efficiency did not improve in a consistent

    way. The motors providing the power venting for the high-effi-

    ciency furnaces contributed 52 to 101 W when the burners were

    on. The furnace circulating fans were sometimes higher and

    sometimes lower in consumption than the fans in the replaced

    furnaces. House G1 reduced the circulating fan high cycleconsumption from 703 to 323 W. House G3 saw a reduction of

    420 to 230 W. However, in House G2 the consumption increased

    from 290 to 380 W and in House G4 the furnace circulating

    fan consumption jumped from 360 to 800 W with the furnace

    replacement. House D1 and G3 ran their fans continuously for

    ventilation purposes, despite the high energy costs that this

    practice entails.

    The water heaters originally located in the houses had

    instantaneous efficiencies ranging from 74.1% to 82%. The

    power-vented water heaters that replaced these units had slightly

    higher efficiencies on average, 71.9% to 83.8%, but they also

    contributed to an increase in electrical consumption with steadystate blower motor consumption of

    65 to 95 W.

    The sidewall vented water

    heaters, combined with high-

    efficiency furnaces, meant that the

    existing chimneys could be sealed,

    adding to the airtightness of the

    house, likely reducing winter air

    change rate, and reducing the risk of

    combustion spillage. However, from

    an energy consumption viewpoint,

    the power vented water heatersmade marginal contributions to

    savings, if any. A shortage exists

    of inexpensive, energy-efficient

    equipment for residential water heating. Instantaneously fired

    units could be investigated for future retrofits.

    The other reliable saving opportunity, besides furnaces, was

    replacement of old electrical appliances with new, efficient units.

    The original refrigerators consumed between 1100 to 1700 kWh

    per year. The efficient units purchased were rated around 400 to

    600 kWh/year. Similar savings were realized with freezer replace-

    ments. House G3 replaced two old freezers with one new one,

    dropping annual consumption from about 2300 kWh to just over

    0 5 10 15 20 25 30 35 40

    Heating Degree Days Per Day (C days/day)

    30

    20

    15

    10

    5

    NaturalGasConsumption(m

    /day

    reretro t

    Post-Retrofit

    Linear (Preretrofit)

    Linear (Post-Retrofit)

    otesPreretrofit data May 22, 1997 to June 9, 2001

    Post-Retrofit data Feb. 17, 2002 to Dec. 31, 2002

    Normalized Consumption = slope 6077 HDD + intercept 365 days

    Pre = 0.6682 6077 + 0.2669 365 = 4158 m3

    ost = . + . = . m3

    avings = ost re =

    Figure 1: Sample calculation for natural gas consumption.

    Basement wall being insulated with the header in the midst of hav-ng foam board applied.

    Table 2: Gas and electricity savings.

    House Preretrofit Post-Retrofit Savings

    as nnua u c eters

    D1 4082 2842 30.4%

    .

    G2 4365 3100 29.0%

    .

    G4 6552 4855 25.4%

    ectrc ty / ear

    D1 9728 8847 9.1%

    .

    G2 8454 7155 15.4%

    .

    G4 7945 7440 6.4%

    = .

    y= 0.351x+ 0.4179

    R2 = 0.9711

  • 7/29/2019 25410 Fug Ler

    5/5

    3 6 A S H R A E J o u r n a l a s h r a e . o r g J u n e 2 0 0 5

    400 kWh. The cheapest and ostensibly

    easiest savings were simply to unplug the

    beer fridge in the basement and save

    the 1100 kWh that it used annually. Such

    savings are more certain if the appliance

    is actually thrown away or recycled, rather

    than just unplugged. Substitution of com-

    pact fluorescent lights (CFL) for com-

    monly used incandescent bulbs shouldreduce energy consumption but the individual fixtures were not

    monitored. Some premature CFL failures occurred with one

    purchased brand.

    Savings from house or water heater insulation, air sealing,

    door replacement, low flow showerheads, and other improve-

    ments could not be specifically attributed.

    ouse otaTotal Simple

    Cost, Payback,$Can Years

    D1 26.5% 4,420 8.4

    . , .

    G2 26.9% 9,415 16.5

    . , .G4 23.9% 7,225 11.5

    Table 3: Retrofit costs and payback.

    New HVAC and laundry equipment.

    Lessons Learned

    For houses without high-efficiency equip-

    ment, saving 40% on energy bills or green-

    house gas production can be achieved.

    These research results suggest that the

    recommended saving opportunities should

    be in the 50% range for the 40% goal to be

    realized for most homeowners.

    The projected costs for such retrofits will be

    $5,000 to $10,000 ($Can), and possibly more

    f the homeowner contracts out all the labor.

    The return on investment typically will be

    better than found in mutual funds or bonds of

    the last several years. The five homeowners in

    the Saskatchewan project were satisfied with

    the savings realized and the ancillary benefits

    (e.g., more habitable basements).

    Easy savings can be achieved through the

    replacement of inefficient furnaces and majorappliances, particularly refrigeration equipment. Savings on water

    heating equipment were more elusive. Computer modeling needs

    to account for the electrical energy consumed by the motors on

    gas appliances. This data may be hard to obtain from conventional

    sources but is critical in the projection of electricity use.

    This small project does not have enough data on the effects

    of wall or attic re-insulation, or on envelope tightening to

    quantify these effects. It is likely that retrofit work spurred by

    the EnerGuide for Houses program7 will lead to contractors

    having more experience and skills in these domains, which

    will be more effective.

    Homeowners may benefit from documentation that disag-gregates electrical loads, showing the impact of choices such

    as maintaining a second refrigerator, continuous running of the

    furnace circulating fan, or keeping electronic equipment such

    as computers in constant operation. Electrical savings in this

    pilot ranged from negligible to substantial. The gas savings

    was more consistent.

    References1. 1997. Full text of the Kyoto Protocol is available at www.emis-

    sionstrategies.com/GHG/kpeng.htm.2. Cooper, K. 1996. Res ent a Retro t Potent a n Cana a. SAR

    Eng neer ng report or Cana a Mortgage an Hous ng Corporat on.

    . NRCan. 2004. Deta s on t e Natura Resources Cana a R-2000program can e oun at ttp: oee.nrcan.gc.ca res ent a personanew-homes/r-2000/About-r-2000.cfm?attr=12.

    . Berry, L. and M. Schweitzer. 2003. Meta-evaluation of NationalWeatherization Assistance Program Based on State Studies, 19932002. Oak Ridge National Laboratory report (ORNL/CON-488) forthe U.S. Department of Energy.

    5. NRCan. 2004. Down oa t e HOT2000 computer s mu at on pro-gram at www. u ngsgroup.nrcan.gc.ca so tware ot2000_e. tm .

    6. Dumont, R.S., et a . 2003. Case Stu es o Ma or Home EnergyRetro ts. Sas atc ewan Researc Counc report or Cana a Mortgageand Housing Corporation.

    7. NRCan. 2004. Details on the EnerGuide for Houses program canbe found at http://oee.nrcan.gc.ca/residential/energystar-energuide-

    r2000.cfm?attr=4.

    Advertisement formerly in this space.