Vibro-Acoustics Consortium HVAC Duct Aspect Ratio Sensitivity Study Caoyang Li University of Kentucky March 18, 2021

Upload: others

Post on 26-Aug-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium

HVAC Duct Aspect Ratio Sensitivity Study

Caoyang LiUniversity of Kentucky

March 18, 2021

Page 2: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 2

Overview

• Simulation Approach in Siemens Simcenter

• Aspect Ratio Sensitivity Study

• Improving the Attenuation with Large Aspect Ratios

Page 3: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 3

𝐼𝐿 𝐿 , 𝐿 ,

Source

Source

𝐿 ,

𝐿 ,

Insertion Loss

Page 4: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 4

ASTM E477 Test setup

20 Monopoles Rigid Ductwork Structure FEM

Poroelastic FEM

Automatically Matched Layer Automatically Matched Layer

Test Setup

Page 5: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 5

20 Monopoles Duct Air FEM

Structure FEM

Poroelastic FEM

Automatically Matched Layer

Automatically Matched Layer

Siemens Simcenter FEM Model10 ft test section (total length 20 ft). Duct wall thickness is 0.034 in (21 gage). Sound absorption is fiber with flow resistivity of 17,700 Rayls/m.

Page 6: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 6

Poroelastic MeshStructural Mesh (with beam brace support)

Cross-section view of mesh (left) and schematic (right).

Siemens Simcenter FEM ModelStep 1 Insertion Loss

Page 7: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 7

Structural FEM

Automatically Matched Layer

Acoustic FEM

Acoustic FEMAutomatically Matched Layer

Structural FEM

Siemens Simcenter FEM ModelStep 2 Breakout Transmission Loss

Page 8: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 8

‐10

0

10

20

30

40

50

60

70

50 100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

16 in x 48 in Duct of 20 ft long with 10 ft lining (2 in glass fiber at all sides) 

Simcenter

Virtual.Lab

Insertion Loss

Page 9: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 9

Breakout Transmission Loss

0

10

20

30

40

50

60

70

50 100 200 400 800 1600 3200

Breakout Transmission Loss (d

B)

Frequency  (Hz)

16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) 

Simcenter

Virtual.Lab

Page 10: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 10

Overview

• Simulation Approach in Siemens Simcenter

• Aspect Ratio Sensitivity Study

• Improving the Attenuation with Large Aspect Ratios

Page 11: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 11

18”

48”

22”

48”

48”16”

48” 48”

Sensitivity Study Constant Height

ℎ𝑤 3 ℎ

𝑤 2.67ℎ𝑤 2.18

𝑡 2"

ℎ𝑤 1

2𝑡𝑤

14

2𝑡𝑤

29

2𝑡𝑤

211

2𝑡𝑤

212

Page 12: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 12

‐10

0

10

20

30

40

50

60

70

80

90

50 100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

16in x 48in

18in x 48in

22in x 48in

48in x 48in

Insertion Loss Constant Height

Page 13: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 13

18”

48”

Note: 2 inch fiber on sides.

𝑡 2"

18”

24”

18”

30”

18”

36”

18”

42”

ℎ𝑤 1.33

ℎ𝑤 1.67

ℎ𝑤 2

ℎ𝑤 2.33

ℎ𝑤 2.67

2𝑡𝑤

29

2𝑡𝑤

29

2𝑡𝑤

29

2𝑡𝑤

29

2𝑡𝑤

29

Sensitivity Study Constant Width

Page 14: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 14

‐10

0

10

20

30

40

50

60

70

80

90

50 100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

18in x 24in18in x 30in18in x 36in18in x 42in18in x 48in18in x 54in

Insertion Loss Constant Width

Page 15: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 15

Overview

• Simulation Approach in Siemens Simcenter

• Aspect Ratio Sensitivity Study

• Improving the Attenuation with Large Aspect Ratios

Page 16: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 16

2 in lining on all sides

Improvements Increase Absorption

16”

48”

𝑡 2"

4 in lining on top / bottom

16”

48”

𝑡 4"

Page 17: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 17

‐10

0

10

20

30

40

50

60

50 100 200 400 800 1600

Insertion Loss  (dB

)

Frequency  (Hz)

2 in on All Sides

4 in Top / Bottom

Insertion Loss Thicker Absorption

Page 18: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 18

2”4” 6”

8”18”

48”

2” on all sides 4” on top / bottom 6” on top / bottom 8” on top / bottom

2” 2” 2”2”

Improvements Increase Absorption

Page 19: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 19

‐10

0

10

20

30

40

50

60

70

50 100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

2in at all sides

4in at short sides

6in at short sides

8in at short sides

Insertion Loss Thicker Absorption

Page 20: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 20

‐10

0

10

20

30

40

50

60

70

50 100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

2in at all sides

8in at short sides

10in at short sides

12in at short sides

Insertion Loss Thicker Absorption

Page 21: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 21

10 ft

20 ft

Improvements Add Length

Page 22: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 22

0

20

40

60

80

100

100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

10ft 2in at all sides

20ft 2in at all sides

0

20

40

60

80

100

100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

10ft 4in at short sides

20ft 4in at short sides

0

20

40

60

80

100

100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

10ft 6in at short sides

20ft 6in at short sides

0

20

40

60

80

100

100 200 400 800 1600 3200

Insertion Loss  (dB

)

Frequency  (Hz)

10ft 12in at short sides20ft 12in at short sides

Insertion Loss Add Length

Page 23: 27 VAC HVAC Duct Sensitivity Study · 2021. 4. 29. · Virtual.Lab Insertion Loss. ... Frequency (Hz) 16 in x 48 in Duct with 10 ft lining (2 in thick glass fiber) Simcenter Virtual.Lab

Vibro-Acoustics Consortium 23

Summary

• FEM Simcenter was used successfully to predict the insertion loss and breakout transmission loss.

• The smallest cross-sectional dimension drives the insertion loss performance.

• Performance can be improved by increasing the sound absorption thickness at the top / bottom of the duct assuming the height is the longest dimension.