MEIM - 06/13 SERIES CONFIGURATION GROUP MEGABARRE 400A ÷ 5000A The Impact busbar trunking system is available in four distinctive configurations in which the neutral conductor’s cross- section and the protection cross- section change according to needs. 154 Neutral cross-section equal to 100% of the phase cross-section. Insulated protection cross-section(FE) equal to 100% of the phase cross-section. Equivalent casing cross-section (PE) grea- ter than 100% of the phase cross-section. FE N L1 L2 L3 154 Fe/2 N L1 L2 L3 3P + N + PE (4P) Neutral cross- section equal to 100% of the phase cross- section. Equivalent casing cross-section (PE) greater than 100% of the phase cross-section. (AAA) 3P + N + FE + PE (5P) (BAA) 132 N L1 L2 L3 154 Neutral cross- section equal to 200% of the phase cross-section. Equivalent casing cross-section (PE) grea- ter than 100% of the phase cross-section. N N L1 L2 L3 3P + N + FE/2 + PE (5P) Neutral cross- section equal to 100% of the phase cross-section. Protection cross-section (FE) (connected to the casing) equal to 50% of the phase cross-section. Equivalent casing cross-section (PE) greater than 100% of the phase cross-section. (GAA) 3P + 2N + PE (5P) (DAA) L1 L2 L3 N N clean extra Pe 100% 200% earth earth involucro FE 100% FE 50% casing AAA BAA GAA DAA Nominal rating A (50°C) 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 Reference Standard IEC 439-1 - IEC 439-2 Rated Operational Voltage - U e V 1000 Rated Insulation Voltage - U i V 1000 Frequency Hz 50/60 Protection degree IP IP 55 - IP 66 - IP 67 MIDDLE EAST MEGABARRE MIDDLE EAST LOPV02 Office No. 114 Po. Box 17560, Jebel Ali Free Zone - Dubai - UAE Tel. +9714 8808332 Fax +9714 8808336 [email protected]

Upload: yasinyasin

Post on 28-Sep-2015

218 views

Category:

Documents


4 download

DESCRIPTION

3 Ante Middle East

TRANSCRIPT

  • MEI

    M -

    06

    /1

    3SERIES CONFIGURATION

    GROUP

    MEGABARRE

    400A5000A

    The Impact busbar trunking system is available in four distinctive configurations in which the neutral conductors cross- section and the protection cross- section change according to needs.

    154

    Neutral cross-section equal to 100% of the phase cross-section.Insulated protection cross-section(FE) equal to 100% of the phase cross-section.Equivalent casing cross-section (PE) grea-ter than 100% of the phase cross-section.

    FE N L1 L2 L3

    154

    Fe/2 N L1 L2 L3

    3P + N + PE (4P)

    Neutral cross- section equal to 100% of the phase cross- section.Equivalent casing cross-section (PE) greater than 100% of the phase cross-section.

    (AAA)3P + N + FE + PE (5P)

    (BAA)

    132

    N L1 L2 L3

    154

    Neutral cross- section equal to 200% of the phase cross-section.Equivalent casing cross-section (PE) grea-ter than 100% of the phase cross-section.

    N N L1 L2 L3

    3P + N + FE/2 + PE (5P)

    Neutral cross- section equal to 100% of the phase cross-section.Protection cross-section (FE) (connected to the casing) equal to 50% of the phase cross-section.Equivalent casing cross-section (PE) greater than 100% of the phase cross-section.

    (GAA)3P + 2N + PE (5P)

    (DAA)

    L1 L2 L3 N N clean extra Pe 100% 200% earth earth involucro FE 100% FE 50% casing AAA BAA GAA DAA

    Nominal rating A (50C) 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000Reference Standard IEC 439-1 - IEC 439-2

    Rated Operational Voltage - Ue V 1000

    Rated Insulation Voltage - Ui V 1000

    Frequency Hz 50/60

    Protection degree IP IP 55 - IP 66 - IP 67

    MIDDLE EAST

    MEGABARRE MIDDLE EAST

    LOPV02 Office No. 114Po. Box 17560, Jebel AliFree Zone - Dubai - UAETel. +9714 8808332Fax +9714 [email protected]

  • GENERAL DATA TECHNICAL FEATURES

    The IMPACT busbar trunking system is designed for power transport and distribution and is especially suitable in the electrical switch room both as a transformer-switchboard or switchboard-switchboard connection and as the main power distribution system for industrial, residential, commercial and service industry.The IMPACT busbar trunking system is offered in current ratings from 400A to 5000A with copper conductors.The casing is made from an aluminium alloy extruded profile that gives to the product light weight high mechanical strength.The standard product is offered in the 3P+N+Pe with the neutral and the phase being of the same cross-sectional area and the earth (Pe-casing) cross-section more than 100% of the phase cross-section.Phase and neutral conductors are made by one or two bars depending on the rated current in the two bars version, the bars are opportunely connected at each junction.Available are also the 3P+N+Fe/2+Pe version with a dedicated earth conductor with a cross-section equal to 50% of the phase cross-section, the 3P+N+Fe+Pe version with a dedicated earth conductor with cross-section equal to 100% of the phase cross-section and the 3P+2N+Pe version with the neutral conductor equal to 200% of the phase cross section.Copper conductors can be galvanically tin-or silver-plated along their entire length. The IMPACT busbar trunking system is offered in the standard version painted RAL 7037.The IMPACT busbar trunking systems are made with sandwich technology (COMPACT); the conductor bars are compacted without any space inside the casing and are fully insulated using a no hygroscopic halogen free polyester sheath (thermal class 150 C). This technology guarantees the products high performance in relation to voltage dropvalues even in high current and long runs.The standard protection degree is IP55 (IP66 for feeder busbar). For outdoor installations an extra protection (canopy) can be used.The electrical connection is achieved by a monoblock system with one or more bolts (depending of the busbar trunking rated current) guaranteeing the electrical continuity between the units of the run. The self-breakable bolt is double headed; the first head is used for the installation (breaking at 85 Nm torque moment) carried out without anyspecial tool, while the second head will be available for future maintenances and inspections. A visual signal (red tag) confirms the correct torque on the monoblock.The mechanical connection is achieved when the joint cover unit is completely installed, thus guaranteeing that the IP protection degree is achieved. A mechanical interlock device prevents the installer from completing the mechanical connection until the electrical connection is correctly completed.

    ADVANTAGES

    - Nominal rating guaranteed both for flat and edgewise installations ( no derating)- Protection degree guaranteed both for flat and edgewise installations- Painted aluminium extruded alloy casing with high mechanical strength characteristics- Maintenance free monoblock joint- Smaller- Lighter- Customized on request- An engineering department at your disposal for site measurements, trunking run evaluations and electrical equipment connection study (switchboard, transformer etc...).

    Test to verify the no propagation of flame according to the IEC 60332 norm.This tests certifies that, when the IMPACT bus-bar trunking system is subjected to a direct flame, the flame itself does not propagate to a longer distance than 2,5 m.

    Test to verify the flame-resistance with mechanical shock according to the IEC 60331 norm.This test certifies that, when the IMPACT bus-bar trunking system (straigth elements and joints) is subjected to both a direct flame and a provoked impact, it insures the continuity of the energy distribution for a given period of time.Test time: 45 minutes 120 minutes 180 minutesCertified time: 45 minutes (standard trunking system);120 minutes (specially insulated trunking system);180 minutes (specially insulated trunking system).

    Vibrations test according to the IEC 60068 norm.This test certifies that the IMPACT busbar trunking system subjected to vibrations of 0,7 g and to 2 g along the three axis confirms its compliance with both the dielectric tests and the mechanical functioning tests.Test value: 0,7 g / 2 g (acceleration)

    The mapping of the electromagnetic field level according to the CEI 211-6 / 2001 norm. The test verifies the emission of the electromagnetic field at variable distances from the trunking at a specified nominal rating.

    PRODUCTION

    Production plants with automatic machinelly in order to assurance quality and short delivery terms

    CERTIFICATION

    Certifications type teast (IEC 439 1-2)

    Temperature rise limits Dielectric properties Short-circuit strength Effectiveness of the protective circuit Clearances and creepage distances Mechanical operating Protection degree verification Electrical characteristics Structural strength Crushing resistance Abnormal heating Flame propagation

    PATENTED