3-phase transformer report 2
DESCRIPTION
3 phase transformerTRANSCRIPT
Group 7- Three-phase transformer 1
Group 7 :
1. Võ Quốc Cường (20900328)
2. Trương Hoàng Trí (80902940)
3. Nguyễn Tiến Khoa (40901248)
4. Lê Nguyễn Anh Nga (60901653)
Group 7- Three-phase transformer 2
Contents
1. Introduction .......................................................................................... 3
- Usage ..................................................................................................... 5
- Structure ................................................................................................ 6
2. Three-phase transformer bank .......................................................... 8
- Introduction
- Advantages and Defects
3. Three Phase Transformer Winding Configurations ....................... 9
4. Problems .............................................................................................. 11
Group 7- Three-phase transformer 3
1. Introduction
Three-phase power
The power company generators produce electricity by rotating 3 coils or windings through a magnetic
field within the generator . These coils or windings are spaced 120 degrees apart. As they rotate
through the magnetic field they generate power which is then sent out on three lines as in three-
phase power.
Three–phase transformer
- 3 coils or windings connected in the proper sequence.
- to match the incoming power.
- transform the power company voltage to the level of voltage we need and maintain the proper
phasing or polarity.
Group 7- Three-phase transformer 4
Usage
- Electricity transmission and distribution systems.
- Industrial electricity network.
Structure
- Three-legged iron core.
- Each leg has a respective primary and secondary winding.
Steel core: 3 cylinder to wrap wire and yoke to close the magnetic circuit.
Steel core is made of steel foil, both sides painted for electricity-insulation and merge them
into a cylinder.
Wires: windings (copper) are insulated, wrapped around steel core.
(AX, BY,CZ):primary windings.
(ax, by, cz):secondary windings.
Group 7- Three-phase transformer 5
2. THREE-PHASE TRANSFORMER BANK
- Connect 3 similar single-phase transformer.
- The primary and secondary windings may be connected in either star or delta configurations.
Group 7- Three-phase transformer 6
Advantages
- Ease of transportation.
- 1 phase of the transformer at fault, the other 2 are not affected.
Defects
- Inefficient magnetic circuit.
- Higher capital cost than a single one.
2. Three Phase Transformer Winding Configurations
Transformer design concept
Group 7- Three-phase transformer 7
Two ways to configure
Delta
(∆)
Wye (Y)
Group 7- Three-phase transformer 8
(positive pole of coil is marked by a dot)
Group 7- Three-phase transformer 9
(positive pole of coil is marked by a dot)
Group 7- Three-phase transformer 10
Combining the Winding Configurations
Wye-Delta
Y/∆
Wye-Wye with neutral
Y/Y0
Group 7- Three-phase transformer 11
Delta-Delta
∆ /∆
Delta-Wye
with neutral
∆/Y0
Group 7- Three-phase transformer 12
The voltage transformation ratio K
� Phase transformation ratio:
� Winding transformation ratio:
Group 7- Three-phase transformer 13
a. Case 1: Transformer Wye-Wye with neutral (Y/Yo)
Primary is Wye configuration: Ud1 = √3Up1
Secondary is Wye configuration : Ud2 =√3Up2
So:
Kd =���
���=
√����
√����=
���
���=Kp
b. Case 2: Transformer Wye-Delta with neutral (Y/∆∆∆∆)
Primary is Wye configuration: Ud1 = √3Up1
Secondary is Wye configuration : Ud2 =Up2
So:
Kd =���
���=
√����
���=
√����
���=√3Kp
c. Case 3: Transformer Delta-Delta (∆∆∆∆/∆∆∆∆)
Primary is Wye configuration: Ud1 = Up1
Secondary is Wye configuration : Ud2 =Up2
So:
Kd =���
���=
���
���=Kp
d. Case 4: Transformer Delta-Wye with neutral (∆∆∆∆/Yo)
Primary is Wye configuration: Ud1 = Up1
Secondary is Wye configuration : Ud2 =√3Up2
So:
Kd =���
���=
���
√����=
√�Kp
Group 7- Three-phase transformer 14
4.Problem:
1) Three one-phase transformers 10kVA, 2300/460V, connected together,
make a three-phase transformer .It supplies 18kW to a three-phase load,
balanced 460V. Power factor 0,8 (lagging).
�� ����� ��, ���, ��, ���, ��, ���?
Each one-phase transformer has apparent power is 10kVA, primary voltage 2300V, secondary 460V.
So we have:
��=2300V; ���=460V
Primary connection is Y, and secondary connection is ∆. So:
��=��√3 � 3988�; ���=���=460V
��=��=√3������ �� �
⇒ ���="#
√����$%&'#=
()))
√�.+,).),(=18,1A
• ���=-��
√�=
(,
√�=10,5A (connection ∆)
We have: ����=������ ⇒ ��=���-��
���=2,1A
��=��=2,10 (connection Y)
Group 7- Three-phase transformer 15
2) A three-phased motor ,50hp, 440 V, having
performance 0,88 and power factor 0,82 is
supplied by a three-phase transformer 6600/440
V. Connection ∆-Y
2) Caculate ��?
3)Caculate ��, ���, ��, ���?
2) When we write a three-phase motor 50hp,440V. It means the power motor supplies to Load is
�2=50hp, and voltage source supplies to motor is 440V
��="3
4=
5)67+,8
),((=42386W
3) Similar to exercise 1.
��=√3������ �� �
Suy ra ���="�
√����$%&'#=
+��(,
√�6++)6),(�=67,83A
���=���
√�=254V; ���=���= 67,83A
��=��=6600V
����=������ ⇒ ��=�5+6,7,(�
,,))=2,61A
Group 7- Three-phase transformer 16
4) A three-phase transformer is combinated from three ideal one-phase transformers, supplied by
three-phase power –supply 2400V .Connection Y-Y. It supplies 600kVA to a three-phase load,
balanced at 240V. Caculate ��?
We
have
9�=9�=√3������
⇒ ���=:�
√����=
,)))
√�.�+)=1443A
���=���=1443A (connect Y)
���=���
√�=139V; ��=2400V; ��=1385,6V
����=������ ⇒ ��=�;6++�
�(5,,=144,76A
5) a combinating three-phase transformer, connection Y-∆, supplies 500kW to to a three-phase load,
balanced at 1100V, power factor 0,85 (late). ��= 11000V. Caculate ��? (Circuit is the same as circuit
in exercise 1)
We have: �<�=1100V
���="#
√�.���.$%&'#=
5)))))
√�6))6),(5=223A
���= -��
√� =129A
��=���
√�=6351V
�� � ��=))6�;
,5�=22,3A
Group 7- Three-phase transformer 17
With this data: a combinating three-phase transformer, connection ∆-Y, decreases voltage from
12600V to 660V and supplies 55kVA to load, having power factor 0,866 (late)
6) Calculate the transformer ratio of each one-phase transformer (=�) ?
7) Caculate apparent power (9�> (kVA) and effective power (��) (kW) of each one-phase transformer?
8)Caculate ��?
• 9�=55kVA; cos �=0,866
We have :��=12600V; ���=660V
��=��=12600V; ���=���/√3=381V
6) =�=��/���=12600/381=33
7) 9� � 55/3=18,3kVA
��=9�.cos �=18,3x0,866=15,9kW
8) 9�=√3x���x���
So ���=55000/(√3x660)=48,1A=���
�D � E381x48,1)/12600=1,45A
�< � √3�D=1,92A