    PRODUCT DESCRIPTION The Series 7C7 Air Maintenance/Compressor assembly consists of a riser-mounted compressor,

    Series 757P Air Maintenance Device and flexible hoses for installation. It is designed to ensure the

    valve system can achieve operational air pressure within 30 minutes of discharge, in accordance with

    NFPA 13 requirements (7.2.6.2.2).

    The Series 757P Air Maintenance Device is UL Listed and FM Approved.

    The Series 7C7 Assembly is available with 1/6, 1/3 and horsepower compressors depending upon thesystem requirements.

    For FireLock NXT Series 768 Dry Valves, Series 769 Deluge and Preaction Valves,

    Series 764 Alternate Valves.

    Note: The Series 7C7 Air Maintenance/Compressor Assembly is designed for systems that do

    not require an accelerator to achieve the required system pressure performance. If an

    accelerator is required, a tank-mounted compressor with a regulated air maintenance device

    should be used.

    COMPRESSOR CAPACITIES

    The engineer/system designer is responsible for sizing the compressor so that the entire

    system is charged to the required air pressure within NFPA guidelines (30 minutes). DO

    NOT oversize the compressor to provide more airflow. An oversized compressor will slow

    down or possibly prevent valve operation.

    Hp

    NominalAC

    Voltage/Hz(+/- 10%)

    Pressurepsi/Bar

    TimeMinutes

    CapacityWITH

    AutoVentgallons/m3

    CapacityWITHOUTAutoVent

    gallons/m3AmpDraw

    008

    075 275 2. Amps

    .2 0.7 .

    008

    075 525

    4.4 Amps

    .2 .4 2.0

    220508

    00 25

    .2 0. 0.9

    220508

    0450 0

    .2 .7 2.5

    22008

    070 400

    .5.2 .4

    2 0508

    00 70

    . Amps.2 2.5 2.5

    2 008

    0780 80

    ..2 .0

    NOTE: Reer to the charts on the ollowing pages or minimum requiredfll capacities to psi0.9 Bar. Low air alarms will clear at psi0.9 Bar. Inaddition, these charts contain higher capacities to 8 psi.2 Bar that are notshown in the table above.

    30.22_1

    Air Maintenance/Compressor AssemblySERIES 7C7

    30.22FIRE PROTECTION PRODUCTS DEVICES

    JOB/OWNER CONTRACTOR ENGINEER

    System No. ______________________________ Submitted By ____________________________ Spec Sect _______________ Para ___________

    Location ________________________________ Date ___________________________________ Approved _______________________________

    Date ___________________________________

    www.victaulic.com

    VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2010VICTAULIC COMPANY. ALL RIGHTS RESERVED.

    REV_F

    SERIES 7C7

  • 7/29/2019 30.22_Compresor de Aire.pdf

    2/8

    ASSEMBLY DIMENSIONS

    Series 7C7 - 1/3HP Compressor

    Pipe Size A B C D

    4.5 5.00 .55 5.8

    2 4.78 5.00 .55 5.8

    2 & 7. 5.04 5.00 .55 5.8

    5. 5.00 .55 5.8

    4 5.88 5.00 .55 5.8

    & 5.5 .98 5.00 .55 5.8

    8 8.02 5.00 .55 5.8

    Series 7C7 - 1/3HP Compressor Series 7C7 - 1/6HP Compressor

    Series 7C7 - 1/6HP Compressor

    Pipe Size A B C D

    4.5 4.0 .55 5.8

    2 4.78 4.0 .55 5.8

    2 & 7. 5.04 4.0 .55 5.8

    5. 4.0 .55 5.8

    4 5.88 4.0 .55 5.8

    & 5.5 .98 4.0 .55 5.8

    8 8.02 4.0 .55 5.8

    A

    B

    C

    D

    A

    B

    C

    DD

    A

    B

    C

    Series 7C7 - 1/2HP Compressor

    Pipe Size A B C D

    4.5 4.8 .55 5.54

    2 4.77 4.8 .55 5.54

    2 & 7. 5.0 4.8 .55 5.54

    5. 4.8 .55 5.54

    4 5.94 4.8 .55 5.54

    & 5.5 .98 4.8 .55 5.54

    8 8.0 4.8 .55 5.54

    Series 7C7 - 1/2HP Compressor

    30.22

    30.22_2

    FIRE PROTECTION PRODUCTS DEVICES

    Air Maintenance/Compressor Assembly

    www.victaulic.com

    VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

    REV_F

    SERIES 7C7

  • 7/29/2019 30.22_Compresor de Aire.pdf

    3/8

    ASSEMBLY PERFORMANCE (1/2 HP Compressor)

    - For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

    18 psi

    13 psi

    System Size (gallons)

    Time(minutes)

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 50 Hz) Compressor and Auto Vent

    0

    5

    10

    15

    20

    25

    30

    35

    40

    50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000

    45

    50

    18 psi

    13 psi

    System Size (gallons)

    Time(minutes)

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 60-Hz) Compressor and Auto Vent

    0

    5

    10

    15

    20

    25

    30

    35

    40

    50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200

    0

    10

    20

    30

    40

    50 18 psi

    13 psi

    System Size (gallons)

    Time(minutes)

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 50 Hz) Compressor and No Auto Vent

    50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100

    0

    10

    20

    30

    40

    50

    18 psi

    13 psi

    System Size (gallons)

    Time(minutes)

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 60 Hz) Compressor and No Auto Vent

    25 75 125 175 225 275 325 375 425 475 525 575 625 675 725 775 825 875 925 975 1025 1075 1125 1175 1225

    30.22

    30.22_3

    FIRE PROTECTION PRODUCTS DEVICES

    Air Maintenance/Compressor Assembly

    www.victaulic.com

    VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

    REV_F

    SERIES 7C7

  • 7/29/2019 30.22_Compresor de Aire.pdf

    4/8

    ASSEMBLY PERFORMANCE (1/3 HP Compressor)

    - For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

    0

    10

    20

    30

    40

    50

    60

    System Size (cubic meters)

    Tim

    e(minutes)

    0.6 1.0 1.4 1.80.2 2.2 2.6 3.0

    1.2 Bar 0.9 Bar

    Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220-240 VAC, 50-Hz) Compressor and Auto Vent

    0

    10

    20

    30

    40

    50

    60

    System Size (cubic meters)

    Time(minutes)

    0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8

    1.2 Bar

    0.9 Bar

    Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220-240 VAC, 60-Hz) Compressor and Auto Vent

    0

    10

    20

    30

    40

    50

    60

    70

    Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220 - 240 VAC, 50 Hz) Compressor and No AutoVent

    Tim

    e(minutes)

    System Size/Volume (cubic meters)

    0 0.5 1.0 1.5 2.0 2.5 3.0

    1.2Bar

    0.9Bar

    0

    10

    20

    30

    40

    50

    60

    Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220 - 240 VAC, 60 Hz) Compressor and No Auto Vent

    0 0.5 1.0 1.5 2.0 2.5 3.0

    Time(minutes)

    System Size/Volume (cubic meters)

    1.2Bar

    0.9Bar

    0

    10

    20

    30

    40

    50

    60

    System Size (Gallons)

    Time(Minutes)

    50 100 150 200 250 300 350 400 450 500 550 600 650 700 750

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/3-hp (110 VAC) Compressor and Auto Vent

    13 psi

    18 psi

    50 100 150 200 250 300 350 400 450 500 550 600 650 700 7500

    10

    20

    3018 psi 13 psi

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/3-hp (110 VAC) Compressor and No Auto Vent

    System Size (gallons)

    Time(minutes)

    NOTE: Reer to the ollowing page or charts relecting the 220-volt -hp option.

    30.22

    30.22_4

    FIRE PROTECTION PRODUCTS DEVICES

    Air Maintenance/Compressor Assembly

    www.victaulic.com

    VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

    REV_F

    SERIES 7C7

  • 7/29/2019 30.22_Compresor de Aire.pdf

    5/8

    0

    10

    20

    30

    40

    50

    60

    70

    System Size (Gallons)

    Time(Minutes)

    50 100 150 200 250 300 350 400

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/6-hp (110 VAC) Compressor and Auto Vent

    13 psi

    18 psi

    50 100 150 200 250 300 350 4000

    10

    20

    3018 psi 13 psi

    Estimated Time to Reach Various Pressures -Series 7C7 with 1/6-hp ( 110 VAC) Compressor and No AutoVent

    System Size (gallons)

    Time(minutes)

    ASSEMBLY PERFORMANCE (1/6 HP Compressor)

    - For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

    30.22

    30.22_5

    FIRE PROTECTION PRODUCTS DEVICES

    Air Maintenance/Compressor Assembly

    www.victaulic.com

    VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

    REV_F

    SERIES 7C7

  • 7/29/2019 30.22_Compresor de Aire.pdf

    6/8

    ExPLODED VIEW DRAWING -

    SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 1/2-HP COMPRESSOR

    1

    4

    23

    6

    142

    3

    10

    7

    14

    11

    To Actuator

    Trim

    9

    8

    5

    15

    1925

    24

    18

    16

    17

    12

    13

    20

    21

    22

    26

    Bill of Materials

    Item Qty. Description

    1 1 Compressor

    2 1 Mounting Bracket

    3 1 Series 757P Air Maintenance Trim Assembly with Pressure Switch

    4 1 Stainless Steel Braided Flex Hose (-inch NPT Male x Female)

    5 2 Split Hanger for -inch Pipe

    6 2 Hose Clamp

    7 1 Close Nipple (-inch NPT)

    8 3 Close Nipple (-inch NPT)

    9 3 90 Female Elbow (-inch NPT)

    10 2 Hex-Head Bolt ( - 16 x -inch Long)

    11 4 Lock Washer ( inch)

    12 2 Lock Washer ( inch)

    13 4 Hex Nut ( - 20 UNC)

    14 2 Straight Conduit Connector (-inch)15 1 Liquid-Tight Conduit ( inch x 9 inches Long)

    16 1 14 AWG, 3-Strand Cable (25 inches Long)

    17 3 #8 U-Style Wire Connector

    18 1 Identication Tag

    19 1 Compressor Air Intake Filter

    20 1 Nipple (-inch NPT x 10 inches Long)

    21 1 Nipple (-inch NPT x 4 inches Long)

    22 1 Union (-inch NPT)

    23 1 Reducing Bell (-inch NPT x -inch NPT)

    24 1 14 AWG Grounded Cord with Plug (5 feet Long)*

    25 1 Strain Relief Connector*

    26 1 Identication Label*

    * NOTE: Items 24 - 26 apply only to the CSA version

    Exaggerated for Clarity

    30.22

    30.22_6

    FIRE PROTECTION PRODUCTS DEVICES

    Air Maintenance/Compressor Assembly

    www.victaulic.com

    VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

    REV_F

    SERIES 7C7

  • 7/29/2019 30.22_Compresor de Aire.pdf

    7/8

  • 7/29/2019 30.22_Compresor de Aire.pdf

    8/8

    WARNING

    Thisproductmustbe installedbyanexperienced,trainedinstaller,

    inaccordancewiththeinstructionsprovidedwitheachvalve.These

    instructions contain important information.

    Failuretofollowtheseinstructionsmayresultinseriouspersonalinjury,

    propertydamage,orvalveleakage.

    Ifyouneedadditionalcopiesofthisproductliteratureorthevalve

    installationinstructions,orifyouhaveanyquestionsaboutthesafe

    installationanduseofthisdevice,contactVictaulicCompany,P.O.

    Box31,Easton,PA18044-0031USA,Telephone:001-610-559-3300.

    WARNING

    WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.

    This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be

    installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the

    right to change product specifications, designs and standard equipment without notice and without

    incurring obligations.

    NOTE

    ELECTRICAL INFORMATION

    DANGER

    Onlyqualifiedelectriciansshouldconnect

    incomingpowertotheSeries7C7Air

    Maintenance/Compressor Assembly.

    Toreducetheriskofelectricshock,check

    theelectricalsourceforpropergrounding.

    Failuretofollowtheseinstructionscouldresultin

    deathorseriouspersonalinjury.

    Ground

    Connection

    ELECTRICAL CONNECTION

    LINE LOAD LINELOAD

    L1 L2

    L 1 T 1 T 2 L 2

    T 1 T 2

    MOTOR

    INCOMING POWER SUPPLY(REFERENCE COMPRESSOR

    DATA PLATE)

    NOTE: NEMA Enclosure - intended only or indoor use

    Only qualified electricians should make the connection to theincoming power supply. All wiring shall be completed in accordance

    with requirements of the local authority having jurisdiction and any

    applicable electrical codes.

    30.22

    Air Maintenance/Compressor Assembly

    30.22FIRE PROTECTION PRODUCTS DEVICES

    For complete contact information, visit www.victaulic.com

    30.224847REV F UPDATED 08/2010

    VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2010 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

    SERIES 7C7