327.3 usermanual ceweprometera0172e-1a

Upload: himdad-tahir

Post on 02-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    1/76

    CewePrometer

    User Manual

    Ver. 1.0

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    2/76

    2

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    3/76

    Contents

    Introduct ion ........................................................................................................................5

    About this user manual.................................................................................................5Contacting us................................................................................................................5

    Product description ...........................................................................................................6

    Sealing of CewePrometer-W........................................................................................9

    Sealing of CewePrometer-R.......................................................................................10

    Connections................................................................................................................10

    Mechanical design......................................................................................................13

    Function modules .......................................................................................................16

    Measuring principles ..................................................................................................17

    Configuration, reading and maintenance ......................................................................18

    Connecting to CewePrometer.....................................................................................19

    Basic configuration.....................................................................................................20

    Overview of functions ................................................................................................22

    Changing configuration..............................................................................................24

    Working with configurations......................................................................................25

    Reading.......................................................................................................................25

    Information about the meter .......................................................................................26Versions and version conflicts ...................................................................................27

    Updating firmware .....................................................................................................27

    Language ....................................................................................................................28

    Resetting registers and logs ........................................................................................28

    Funct ions..........................................................................................................................29

    Meter clock.................................................................................................................29

    Energy registers ..........................................................................................................30

    Instant values..............................................................................................................31Digital inputs and outputs...........................................................................................33

    Display sequences ......................................................................................................36

    Communications and security ....................................................................................37

    Loggers.......................................................................................................................39

    Alarms ........................................................................................................................41

    Event log.....................................................................................................................43

    Maximum demand......................................................................................................44

    Historical registers......................................................................................................45

    Time of use.................................................................................................................46

    Transformer compensation.........................................................................................48

    3

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    4/76

    Contents

    Power quality..............................................................................................................50

    Miscellaneous.............................................................................................................52

    Using the display .............................................................................................................53

    Voltage order display layout ......................................................................................53

    Navigating in display sequences ................................................................................54

    Display layouts with active choices ...........................................................................54

    Using the display for communication diagnostics .....................................................56

    Appendix A Display Layouts .......................................................................................57

    Appendix B - Events ........................................................................................................61

    Appendix C Serial Communicat ion Port RS232/422 ..................................................63

    Appendix D - Module block d iagram ..............................................................................65

    Appendix E Frequently Asked Questions...................................................................66

    Appendix F Calculation Princip les ..............................................................................67

    Appendix G Material Declarat ion.................................................................................72

    Appendix H Connect ion Data ......................................................................................73

    4

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    5/76

    Introduction

    IntroductionThank you for choosing the CewePrometer.

    The CewesPrometer is a multi-functional, electronic, electricity energy meter. It provides very high

    accuracy in measuring electrical energy and also in measuring instantaneous quantities such as

    current, voltage, power, frequency etc. CewePrometers extensive configurable functional features

    together with the high accuracy enable application areas more numerous than for traditional electric

    meters. Besides having well-designed traditional features such as meter registers, data logging and

    tariff capability, there are also extensive functions for monitoring alarm conditions, harmonics,

    measuring sags and swells and other power quality quantities.

    About this user manualThis user manual describes the CewePrometers functions and provides the information needed to

    configure and use the meter. The manual covers all versions of the CewePrometer-R (rack-

    mounted) and CewePrometer-W (wall-mounted). Some of the described functional properties can

    be missing in certain meter versions. The CewePrometer is complemented with CeweConfig, a PC

    program for configuring, manual reading and maintenance.

    Contacting us

    For more information and technical support, please contact Cewe Instrument.

    Internet www.ceweinstrument.se

    E-mail technical support [email protected]

    E-mail order and product information [email protected]

    Telephone +46 (0)155 77500

    Address Cewe Instrument AB

    Box 1006

    SE-611 29 Nykping

    Sweden

    5

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    6/76

    Product description

    Product description

    7

    5

    3

    4

    1

    2

    8

    9

    6

    11

    13

    14

    15

    10

    12

    Figure 1 CewePrometer-W

    53 4

    1

    2 8 11

    13

    14

    15

    16

    12

    10

    Figure 2 CewePrometer-R

    6

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    7/76

    Product description

    1 Display

    2 Optical communication portThe optical port communicates in accordance with IEC62056-21/IEC1107.

    3 Alarm LED

    The alarm LED flashes when an alarm state has occurred. For alarms, such as

    for high or low voltage, phase balance or similar external errors, the LED stops

    flashing when the alarm state has passed. If the meter has had an internal error,

    the alarm must be acknowledged and manually reset.

    4 Calibration LED for active energy

    The LED is the source of the energy signal for accuracy testing of active energy.

    The light pulses have a 50% pulse width and a frequency proportional to the

    measured active power. A constant that specifies the total number of pulses perkWh can be configured. The same constant applies to active and reactive energy.

    5 Auxiliary power LED

    When the CewePrometer is receiving auxiliary power, the green LED turns on to

    indicate that the meter's power supply is working.

    6 Sealing points for terminal coverThe terminal cover can be sealed with lead seals (or comparable seals) and

    sealing wire through the sealing points.

    7 Terminal cover

    8 Sealing points for front panel windowThe front panel exterior window can be sealed with lead seals (or comparable

    seals) and sealing wire through the sealing points. The seal prevents access to

    the fourth button (sealed button) and the optional backup battery for the real-

    time clock.

    9 Meter cover

    10 Front panel window

    The front panel window has hooks for attaching the meter label. In addition, the

    window is provided with a pocket for inserting an extra label. The extra label

    can be used when transformer ratios are changed.

    11 Calibration LED for reactive energy

    The LED is the source of the energy signal for accuracy testing of reactive

    energy. The light pulses have a 50% pulse width and a frequency proportional to

    the measured reactive power. A constant that specifies the total number of pulses

    per kvarh can be configured. The same constant applies to active and reactive

    energy.

    12 Sealed button

    The button is hidden under the front panel window and provides access to a fifth

    configurable display sequence. Holding down the button for about two seconds

    opens a system menu.

    7

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    8/76

    Product description

    13 Step backward

    The button is used to step backward to a previous display layout in the selected

    display sequence, or to step downwards in a menu.

    14 Menu/Apply

    The Menu/Apply button is used to open the menu where one of four

    configurable display sequences can be chosen. The button confirms choices

    made or initiates other activities depending on the current display layout.

    15 Step forward

    The button is used to step forward to the following display layout in the selected

    display sequence, or to step upwards in a menu.

    16 Sealing points for rack mounting

    The rack mounting bracket for the CewePrometer-R can be sealed with lead

    seals (or comparable seals) and sealing wire through the sealing points.

    8

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    9/76

    Product description

    Sealing of CewePrometer-W

    See Figure 1 CewePrometer-Wfor location of the sealing points. The front panel window can besealed with lead seals (or comparable seals) and sealing wire through the sealing points. The seal

    prevents access to the fourth sealed button and the optional backup battery for the real-time clock.

    Battery cover

    Sealed button

    Figure 3 Under the front panel window is a fourth button and backup battery for the real-time clock.

    The terminal cover can be sealed with lead seals (or comparable seals) and sealing wire through the

    sealing points.

    The meter cover can be sealed with lead seals (or comparable seals) and sealing wire through the

    two sealing points under the terminal cover.

    Sealing point

    Figure 4 The meter cover can be sealed at the sealing rings on both sides under the terminal cover.

    9

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    10/76

    Product description

    Sealing of CewePrometer-R

    See Figure 2 CewePrometer-Rfor location of sealing points. The enclosure permits the meter to be

    sealed at three points. The top and bottom covers are normally each sealed with a lead seal and with

    sealing wire through a sealing screw and a fixed hole on the cover at the rear of the meter. The

    exterior window on the meter front can be sealed on a sealing point with a lead seal and sealing

    wire. In this way, the meter can be sealed so that it cannot be opened without breaking all the seals.

    One of the buttons on the front is protected from access behind the sealed exterior window.

    Sealed button

    Battery

    Under the front panel window is a fourth button and backup battery for the real-time clock.

    Connections

    Connections to the CewePrometer-W are made on the meter terminal under the terminal cover.

    Connections to the CewePrometer-R are made on the rear panel of the meter subrack. The

    connections are: measuring voltages, measuring currents, relay outputs, optically isolated digitalinputs, separate auxiliary power and connections to communication modules, if any.

    Digital outputs Digital inputs

    Output #1 Input #4

    Separate aux. power

    (Uaux

    )

    I'L1

    UL1

    IL1

    N

    Output #8 Input #1

    I'L2

    UL2

    IL2

    I'L3

    UL3

    IL3

    Connections for CewePrometer-W

    10

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    11/76

    Product description

    Connections for CewePrometer-R

    Digital I/O variants6 outputs, 4 inputs

    OUT1 C0, C5 IN1 C4, C9

    OUT2 C1, C6 IN2 C3, C8

    OUT3 C2, C7 IN3 D4, D9

    OUT4 D0, D5 IN4 D3, D8

    OUT5 D1, D6

    OUT6 D2, D7

    10 outputs, 2 inputs

    OUT1 C0, C5 IN1 C4, C9

    OUT2 C1, C6 IN2 C3, C8

    OUT3 C2, C7

    OUT4 D0, D5OUT5 D1, D6

    OUT6 D2, D7

    OUT7 D3, D8

    OUT8 D4, D9

    OUT9 B7, B8

    OUT10 B4, B9

    ConnectionsUL1 B1 IL1 A01

    UL2 B2 I'L1 A1

    UL3 B3 IL2 A02

    N B0 I'L2 A2

    IL3 A03

    Uaux1 B5 I'L3 A3

    Uaux2 B6

    Current, voltage and auxiliary power connections

    for CewePrometer-R.

    12 outputs, 0 inputs

    OUT1 C0, C5

    OUT2 C1, C6

    OUT3 C2, C7

    OUT4 D0, D5

    OUT5 D1, D6

    OUT6 D2, D7

    OUT7 D3, D8

    OUT8 D4, D9

    OUT9 B7, B8

    OUT10 B4, B9

    OUT11 C3, C8

    OUT12 C4, C9

    Connector for CewePrometer-R

    A standardised Entrelec Essailec plug-in connector is used, of the same type as for other meters

    according to standard DIN 43862. The cable connection is made in the subrack. The meter is

    connected via the contact pins after insertion. The connector has a short-circuit protection featurefor electrical circuits, permitting the meter to be withdrawn and inserted into the subrack during

    operation.

    Auxi liary power

    The CewePrometer is supplied with separate auxiliary power. Auxiliary power can be supplied both

    with alternating current and polarity-independent direct current within a specified range. There are

    two versions that have either a high or a low auxiliary voltage range.

    Digital outputs

    The CewePrometer's outputs are solid-state MOS-FET bipolar semiconductor relays, with normally

    open contact function. Internal current limit protects the relay from being damaged by excessively

    high current.

    11

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    12/76

    Product description

    Digital inputs

    The optically isolated digital inputs consist of opto couplers, where the LED is powered from an

    external voltage signal through series resistance to limit the current. This means that an externalvoltage must be connected between the passive pulse and level transmitter and the opto coupler's

    LED, or the transmitter must deliver an active voltage signal to send pulses that are detected by the

    optical input. The optically isolated inputs are unaffected by reverse polarity. Both DC and 50/60

    Hz AC can be used.

    Serial communication ports

    The CewePrometer is always equipped with one optical port and is available in versions with or

    without additional communication ports. A meter can be equipped with up to two extra ports, either

    with the RS232 or RS422 interface.

    Communications through the infrared IEC62056-21/IEC1107 optical port are transferredvia an optical read/write adapter, an optical head. The optical head is positioned and

    secured over the optical port by a magnet on the head and a steel plate around the opening

    of the optical port.

    The RS232 standard communication port is used to connect communication equipment

    (computers, modems) through a serial cable with a standard D-sub, 9-pin connector.

    The RS422 serial communication port is intended to be used to connect the CewePrometer

    to a network for multi-drop communications. The CewePrometer is connected to the

    communication equipment (RS422 converter) with two twisted-pair wires connected to a

    5-pole connector.

    For information on pin configuration, see Appendix C Serial Communication Port RS232/422

    (pg. 63).

    Communication port #2 Communication port #1

    Numbering of the communication ports from right to left on the CewePrometer-W.

    Communication port #1

    Communication port #2

    Numbering of the communication ports on the CewePrometer-R

    12

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    13/76

    Product description

    Mechanical design

    Alternative

    mounting

    Dimensions for CewePrometer-W.

    13

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    14/76

    Product description

    Dimensions for CewePrometer-R.

    14

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    15/76

    Product description

    Dimensions for CewePrometer-R subrack.

    The subrack is also available in alternative connector versions that will fit other brands of meters

    with the same type of connector. Contact Cewe Instrument for more information.

    Enclosure and protective earth

    CewePrometer-W

    The enclosure consists of a meter base, meter cover, terminal cover and a plastic exterior window.

    The meter is not connected with protective earth. There is also an optional 19 inch rack/panel

    mounting kit available for to CewPrometer-W to be mounted side by side.

    CewePrometer-R

    Enclosure fits for installation of two meters in a 19" subrack in compliance with DIN438862. The

    enclosure consists of a box made of surface-finished steel sheet and a front with a plastic window.The meter is designed for protective earthing through the 19" subrack.

    Isolation and personal safety

    The electronic circuits are isolated from all connections to the supply mains with transformers.

    Digital I/O connections are isolated with opto couplers and solid state relays. The communication

    ports are also isolated but for a lower voltage.

    15

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    16/76

    Product description

    Function modules

    Modulisation

    The CewePrometer is made up of function modules. Modulisation is primarily used to make it easy

    to produce different versions with the same basic design, and to enable development of new

    modules for the basic design to add or replace functions. Modulisation is not primarily intended for

    being able to switch plug-in modules in the field the meter must be opened and the seals broken to

    switch modules.

    Modules

    The CewePrometer consists of the following basic modules, which are necessary for a functioning

    meter in its simplest version:

    Measurement module

    Power module

    Display and register module

    Moreover, the meter is normally equipped with the following modules for additional functionality:

    Digital I/O module

    Communication module

    There is also space for additional function modules for expansion of function properties to meet

    future market needs.

    For more information, see Appendix D - Module block diagram(pg. 65).

    16

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    17/76

    Product description

    Measuring princip les

    The measuring circuit in CewePrometer consists of current and voltage transformers that providesignals to six parallel AD converters (analogue to digital converters) that are synchronised by a

    common clock signal. The digital signals are thereafter processed by a DSP. Using voltage

    transformers makes the electronics in the meter galvanically isolated from the measurement voltage,

    which provides good personal safety and protection for connected equipment, such as modems.

    Calculation flow

    All values are calculated in the CewePrometer based on calibrated current and voltage values.

    Current and voltage amplitudes and phase angles are fully compensated in regards to accuracy,

    harmonics, frequency and temperature. Adjustments for accuracy are made throughout the dynamic

    range for both voltage and current. Based on these individually compensated current and voltage

    signals, power, energy, power factor and all other quantities that the CewePrometer can present, aresubsequently calculated. This means that accuracy for instant values is good and that active and

    reactive power are correctly calculated, including harmonic power. For more information on

    calculation principles and the formulas used, see Appendix F Calculation Principles(pg. 67).

    3-element meter

    On the 3-element CewePrometer, phase voltages and neutral wires are connected to the meter. The

    voltages measured are phase voltages. Power and energy are calculated from three phase voltages

    and three currents. Harmonic measurement, alarm monitoring and transformer corrections are made

    on phase voltages. The phase to phase voltage is calculated from the phase voltages.

    2-element meter

    On the 2-element CewePrometer, the neutral conductor is not connected to the meter and the three

    voltages are internally D-connected. The voltages measured are subsequently phase to phase

    voltages. Power and energy are calculated based on two phase to phase voltages (U12 and U23) and

    two currents (I1 and I3) according to the 2-watt meter method. The 2-element meter is primarily

    used for D-connected systems (3-wire). Harmonic measurement, alarm monitoring and transformer

    corrections are made on phase to phase voltages.

    17

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    18/76

    Configuration, reading and maintenance

    Configuration, reading and maintenance

    CeweConfig is a PC program that makes all CewePrometer functions available. With CeweConfig,you can:

    ConfigureConfiguring means that parameters affecting meter function can be set. Examples of

    parameters that can be configured are: transformer ratios, logging interval and limits for

    alarms.

    Reading

    Examples of information that can be read are: registers, logged values, alarms and

    harmonics. The information can be printed out or saved to a file.

    MaintenanceExamples of maintenance tasks are: resetting the event log and updating the firmware in the

    meter.

    ToolbarMenu

    Configuration formStatus barStructure tree

    18

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    19/76

    Configuration, reading and maintenance

    Connecting to CewePrometer

    To be able to configure or read values in the CewePrometer, CeweConfig must be connected andhave authorisation to access the meter. The meter has five different authorisation levels that can be

    configured with passwords. See the section Communications and security(pg. 37). With the meter's

    factory settings, no password is configured, and subsequently no password is necessary when you

    connect.

    To communicate with a meter, the PC must be physically connected to the CewePrometer in one of

    the following ways:

    PC Optical head Meter

    PC Crossed serial cable (null modem) Meter

    PC Straight serial cable RS422 converter Daisy chained meters

    PC Modem Modem Meter

    How to connect to the meter

    1. Connect to Meter

    Choose Connect to Meterfrom the Filemenu or by clicking the toolbar button.

    2. Communication channel

    Click the Settingstab and choose either Optical Port, Serial Portor Modem. If the serial port or a

    modem is used, the baud rate must be selected. For meters with factory settings, the baud rate is

    9600. When the optical port is used, CeweConfig adapts itself to the baud rate the meter is

    configured for, making selection of the baud rate unnecessary.

    Note: The selectable communication ports can be changed by changing the XML file Settings.xml

    that is in CeweConfig's installation directory.

    3. Modem

    If a modem connection is used, a modem must be chosen. The modems available are those installed

    in Windows. Click the Commontab and enter the telephone number to be called.

    19

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    20/76

    Configuration, reading and maintenance

    4. Password

    Click the Commontab. A password is entered if one is configured in the meter. With the meter's

    factory settings, no password is configured, and subsequently no password is necessary when you

    connect.

    5. Serial number

    Serial number is only required if a special meter is to be addressed when several meters are

    connected together with RS422.

    6. Trace to file

    Under the Settingstab, a box can be checked to activate tracing to a file. A file named

    SerialTrace.log is then created in CeweConfig's installation directory. All communications between

    CeweConfig and the meter are presented in the file. The function can be used to analyse

    communication problems.

    7. Click the Connectbutton.

    Problems w ith connecting

    If the meter cannot be connected, an error message is displayed. Depending on the reason, the

    message can suggest corrective actions, such as changing the port or port baud rate.

    Tip: When communication problems occur, the trace feature on the meter's display can be used to

    see if that which has been sent has been registered by the meter. See the section Using the display

    for communication diagnostics(pg. 56).

    Basic configuration

    Some basic settings may be required before the CewePrometer will be able to measure and operate

    correctly in a system.

    Note: Settings are only necessary if they have not been made at the factory prior to delivery.

    Meters supplied without backup batteries retain the time setting for a maximum of three days. For

    time-dependent functions such as logging and event logging to work, the clock may need to be

    adjusted.

    To change the configuration for a meter, you must be connected to it. Click the Configuration

    folder in the structure tree to the left in CeweConfig to display the various functions that can be

    configured. For more information see the section Changing configuration(pg. 24).

    Tip: You can save a configuration from a meter to a file. A summary of the configuration can also

    be printed out. You can also create a configuration without being connected to a meter. For more

    information, see Working with configurations(pg. 25).

    20

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    21/76

    Configuration, reading and maintenance

    Meter clock:To configure the meter clock, choose the node Meter Configuration -

    Clockin the structure tree. Find out how the meter clock works and how it can be

    configured in the section Meter clock(pg. 29).

    Transformer ratios: For the meter to measure accurately, the ratios must be correct. To

    configure the transformer ratio in CeweConfig, choose the node Meter Configuration

    Measuringin the structure tree. Click the Generaltab in the window that opens. Fill in

    the primary and secondary values for current and voltage.

    Note: The values you choose as primary and secondary values will be considered as the

    nominal values. These nominal values are used by several functions in the meter: alarms,

    voltage monitoring and transformer compensation.

    Presentation format for energy registers: To configure the presentation format for

    energy registers, choose the node Meter Configuration Measuringin the structure

    tree. Choose the prefix and number of decimals for energy registers. Based on the nominal

    values, a capacity is calculated for how long the meter can measure without registersresetting. Read about energy registers in the section Energy registers(pg. 30).

    Pulse constants for pulse outputs (Digital I/O): To configure pulse constants for pulse

    outputsin CeweConfig, choose the node Meter Configuration Digital I/Oin the

    structure tree. Find out how Digital I/Oworks and how it can be configured in the section

    Digital inputs and outputs(pg. 33).

    Display sequences: To configure display sequences in CeweConfig, choose the node

    Meter Configuration Display sequencesin the structure tree. Find out how display

    sequences work and how they can be configured in the section Display sequences(pg. 36).

    21

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    22/76

    Configuration, reading and maintenance

    Overview of funct ions

    The following is a brief overview of the functions available in CewePrometer. All functions in the

    meter can be both configured and read in CeweConfig. In many cases, CeweConfig can also export

    data to a file or print out data.

    Function Configuration location inCeweConfig

    Section in handbook describingthe function.

    Communication speed

    Set the baud rate for the meter'soptical or serial port.

    Meter Configuration Communication

    Communications and security(pg.37)

    Passwords

    Regulate access to data in 5levels with passwords orhardware strap.

    Meter Configuration Communication

    Communications and security(pg.37)

    Data loggingLog energy or instant values.

    Meter Configuration Loggers Loggers(pg. 39)

    Alarms

    Activate alarms for events suchas voltage unbalance. Determinehow alarms will be presented.

    Meter Configuration Alarm Alarms(pg. 41)

    Maximum demand

    Determine values that are to bestored as maximum averagevalues.

    Meter Configuration Maximum Demand

    Maximum demand(pg. 44)

    Historical registers

    Choose how a historical periodwill be finished.

    Meter Configuration Historical Registers

    Historical registers(pg. 45)

    Time of use

    Determine how rates shift overthe course of a day and whichregisters will be divided by rates.

    Meter Configuration Time ofuse

    Time of use(pg. 46)

    Transformer compensation

    Compensate errors and losses forinstrument and powertransformers.

    Meter Configuration Measuring, TransformerCompensation tab

    Transformer compensation(pg.48)

    Power quality

    Activate monitoring of voltagesags, swells and interrupts.

    Meter Configuration Measuring, Power Quality tab

    Power quality(pg. 50)

    Language on display

    Choose between severalavailable languages for thedisplay.

    Meter Configuration Misc. Miscellaneous(pg. 52)

    Information texts

    Enter information texts that canbe read on the display and viacommunications.

    Meter Configuration Misc. Miscellaneous(pg. 52)

    Calibration LED

    Set a pulse constant for thecalibration LED. This is used totest meter accuracy.

    Meter Configuration Measuring, General tab

    Product description(pg. 6)

    Accumulate incoming pulses

    Configure registers to accumulatepulses representing a selectablequantity.

    Meter Configuration DigitalI/O, Inputs tab

    Digital inputs and outputs(pg. 33)

    22

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    23/76

    Configuration, reading and maintenance

    Indicate alarms via pulseoutput

    Choose a pulse output to be

    activated in case of alarms.

    Meter Configuration DigitalI/O, Outputs tab

    Digital inputs and outputs(pg. 33)

    Synchronise clock viaincoming pulse

    Set an interval that the clock shallbe synchronised to uponincoming pulses.

    Meter Configuration Clock

    Meter Configuration DigitalI/O, Inputs tab

    Meter clock(pg. 29)

    Digital inputs and outputs(pg. 33)

    Adjusting the clock for daylightsaving time

    Set date and time for daylightsaving time.

    Meter Configuration Clock Meter clock(pg. 29)

    23

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    24/76

    Configuration, reading and maintenance

    Changing configuration

    To open a configuration form, click the folder Configurationin the structure tree and then click

    one of the nodes: Display Sequences, Measuring, Clock, etc. Configuration changes can be made

    in all configuration form. In the lower right corner, there is an Applybutton. If a meter is connected

    and you click Apply, changes to the configuration will be immediately transferred to the meter. If

    the changes affects registers or measurement, a warning dialog will be displayed. You can choose

    not to send a portion of the configuration by clearing checkboxes in the dialog.

    Warning dialog that sometimes is displayed when configurations are sent to the meter.

    24

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    25/76

    Configuration, reading and maintenance

    Working with configurations

    In CeweConfig, you can work with configurations as a collection of CewePrometer's settings andsave them in a file. On CeweConfig's Filemenu, are the commands Save configuration, Open

    configuration and New configuration. A configuration can either be for a 2- or 3-element meter.

    You cannot transfer a 2-element configuration to a 3-element meter or vice versa. Transformer

    corrections or passwords are not saved in configuration files. On the Filemenu, there is a command

    for creating a configuration summary. Below is a list of how you can use CeweConfig's functions to

    work with configurations.

    Creating a configuration file without being connected to a meter

    Choose New configuration when CeweConfig is not connected to create a configuration

    file offline. The configuration file can be either of the 2- or 3-element type. Make all settings

    that are to be included in the configuration file and save the file. The file's configuration canlater be transferred to a meter.

    Saving a meter's configuration to a fileChoose Save configuration when CeweConfig is connected to a meter to save the meter's

    configuration to a file. The configuration file can later be used as a backup or be transferred

    to another meter.

    Transferring a configuration file to a meter

    Choose Open configuration when CeweConfig is connected to a meter to transfer a

    configuration file to the meter. The changes in configuration cause a warning dialog box to

    open. The configuration file can either be created without being connected to a meter, or be

    saved from a meter; see the points above.

    Printing out a summary of a meter's configuration

    Choose View configuration Configuration summary when CeweConfig is connected to

    a meter to create a summary of the meter's entire configuration. Now choose Print.

    Printing out a summary of a configuration file

    Open a configuration file and choose View Configuration summary to create a summary

    of the configuration that is in the file. Now choose Print.

    Note: ChoosingNew configurationor Open configurationwhen CeweConfig is connected to a

    meter opens a warning dialog box with the message that the configuration in the meter will be

    written over if you continue.

    Reading

    If you are connected to a CewePrometer with an authorisation level between 1 and 5, several

    alternatives will be available in the structure tree under the node Reading. For the alternatives

    25

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    26/76

    Configuration, reading and maintenance

    Instant Valuesand Time, displayed values are constantly updated. The others are only updated

    when the window is opened or when the Updatebutton is clicked. Read values can be printed out

    and often also saved to files, this can be done by with buttons Printand Save.

    Information about the meter

    Information about the connected meter can be obtained by choosing View Information about the

    meter.Some of the information displayed is the same as what appears on the meter plate.

    Additionally, there is information on when the meter was manufactured and when the most recent

    configuration change was made.

    Under the Modules heading, the firmware currently used in the meter is listed. See the section

    Updating firmware(pg. 27).

    26

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    27/76

    Configuration, reading and maintenance

    Versions and version conflicts

    The latest version of CeweConfig can be used with all firmware versions of CewePrometer-R/W.The version number for CeweConfig is displayed on the application's title bar or under Abouton

    the Helpmenu. The version number for the meter's firmware can be viewed under View

    information about the meteron the Viewmenu.

    CewePrometer and CeweConfig have three-digit version numbers according to the format main

    version.sub-version.build number. As long as the main version and sub-version are the same,

    CeweConfig and the meter are compatible. If the meter is of a newer version than CeweConfig and

    the main version and/or sub-version are different, CeweConfig will display a message that

    connection is not possible. CeweConfig must be updated.

    Updating firmwareCewePrometer is designed with a number of modules that each have their own processors and their

    own firmware. The module firmware is distributed in a package file (.pkg) which is transferred to

    the meter using CeweConfig. Newly developed and improved functions can thus be added in a

    meter that lacked these functions when delivered.

    Note: Be sure to update CeweConfig to the latest version before updating the meter. There is

    otherwise the risk that CeweConfig will no longer be version-compliant after firmware updating.

    On the Toolsmenu, there is an Update firmwarecommand when the meter is connected with

    authorisation level 4 or higher.Begin by choosing the file that contains the update. The file name

    and version number will then be displayed, and sometimes a message. Click the Advancedbutton

    to view CeweConfig's version number by module for both the file and the meter. Additionally, you

    can force modules to be updated even if the file has the same version number. Click Updateto

    begin updating.

    27

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    28/76

    Configuration, reading and maintenance

    During the time the update is being installed, the meter stops measuring and registering energy.

    Depending on the size of the file to be transferred and the baud rate, the time for updating can vary

    from a few minutes to a half hour at the highest baud rate. If possible, connect at the highest baud

    rate (19200 bps) to speed updating. After updating, the meter is restarted to complete installation of

    the meter's new firmware.

    Updating can be performed via a modem but this should be avoided since reliability for this method

    of communication is too low. An interrupted update can leave a meter with incomplete firmware

    that cannot measure at all. If an update via a modem has failed, the next update must be made via

    RS232/422 or the optical head.

    Language

    CeweConfig can be set to different languages. The available languages can be seen under

    Languageon the Viewmenu.

    Resetting registers and logs

    CewePrometer's various registers and log data can be reset with CeweConfig if a meter is connected

    and you are connected with a sufficiently high authorisation level. You will find a number of

    choices under Reseton the Toolsmenu. Some options may be marked in grey if your authorisation

    level is not high enough. To reset energy registers, authorisation level 5 is required, and level 3 for

    other options. A warning dialog box opens before resetting.

    28

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    29/76

    Functions

    Functions

    Meter clock

    The CewePrometer has an integrated real-time clock for time-dependent functions. Information

    about time adjustment and daylight saving time status is recorded with tags on the logged values;

    see Loggers(pg.39). Time adjustments are also noted as an event in the event log; see Appendix B -

    Events(pg. 61).

    Instantaneous adjustment

    The meters date and time can be set to an absolute point in time. Instantaneous adjustment of the

    meters time can influence logged values. To avoid this, the meter's log memory is reset when doing

    instantaneous adjustment. For this reason, instantaneous adjustment of the meter clock is primarily

    intended for use at initial configuration of the meter.

    Sliding adjustment

    The meters time can be adjusted successively. Instead of the meter adjusting the clock

    instantaneously, the total adjustment is spread out over a longer period. A speed of adjustment can

    be chosen in the 140% range. With 40%-adjustment, the clock is adjusted 24 seconds for each

    minute until the total adjustment has been made.

    Daylight savings time

    CewePrometer offers the alternative of letting the meter clock follow daylight savings time. At a

    specified date, the meter clock is adjusted forward, and at another, adjusted backward.

    Example: On 28 March the clock is to be adjusted forward, from 02:00 to 03:00. The adjustment

    back to standard time is to occur on 31 October at 3:00 (daylight savings time) when the clock is to

    be set back to 02:00. The following is set in the meters: Begin March, 28, 02:00. End October, 31,

    03:00 and the standard time is to be adjusted by 60 minutes.

    External synchronisation

    The meter time can be adjusted by a pulse on one of the meters digital inputs. When a pulse is

    registred, the clock is adjusted to the closest multiple of a specified synchronisation interval. If the

    synchronisation interval is, for example, one hour and the time is 13:29, a pulse will adjust the clock

    to 13:00. If the time had instead been 13:31, the clock would have been adjusted to 14:00.

    Available synchronisation intervals are:

    10, 15, 20 and 30 minutes

    1 hour

    Times 12:00 and 00:00

    Time 00:00

    Besides specifying that the meter clock will synchronise via external pulses, a digital input must

    also be configured for clock synchronisation; see the section Digital inputs and outputs(pg. 33).

    29

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    30/76

    Functions

    Energy registers

    Energy registers in the CewePrometer are electronic counters that accumulate energy. Prefixes andnumber of decimals are configured which apply to all energy registers. Energy registers have a

    width of nine digits, regardless of the total number of decimals and the prefix configured. When an

    energy register has reached its maximum figure (for example, 999999.999 kWh), it resets to zero.

    Fewer decimals and larger prefixes give the energy registers space for more energy without

    resetting. Read more about how energy is calculated and defined by quadrants in Appendix F

    Calculation Principles(pg. 67).

    Overview

    The table shows the energy registers available in the meter.

    Energy type Energy directi on Total values Per phase values Total numberActive energy Import, export Yes Yes (3-element

    meter only)8

    Reactive energy Import, export,quadrants I-IV,capacitive, inductive

    Yes No 8

    Apparent energy Import, export Yes No 2

    III

    III IV

    Active power import(+)

    Active power export(-)

    Reactive powerexport (-)

    Reactive power

    import (+)

    SQ

    P

    Capacitive

    Inductive

    Quadrants Phase angle Current relative to voltage

    I 0 to 90 Lagging

    II 90 to 180 Lagging

    III -180 to -90 Leading

    IV -180 to 0 Leading

    Storage in non-volatile memory

    All registers are saved in non-volatile memory once per second. Loss of auxiliary voltage therefore

    results in no more than one second of lost historical energy measurement data. For optimal

    safekeeping, all registers are saved in three alternating memory areas.

    30

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    31/76

    Functions

    Instant values

    Besides energy, the CewePrometer can also measure instant values. Instant values are constantlychanging values such as current, voltage, power and harmonics. The formulas and definitions used

    to calculate the values are presented in Appendix F Calculation Principles(pg. 67).

    Overview

    This table provides an overview of the instant values that can be read on the meter. Readings can be

    viewed with CeweConfig, on the display and with other software that has implemented

    CewePrometers communication protocol. Most instant values can be logged as average values; for

    more information, see section Loggers(pg. 39).

    Instant value Available on 3-element

    meter

    Availab le on 2-element

    meterFrequency Yes Yes

    Power factor total Yes Yes

    Power factor per phase Yes No

    Active power total Yes Yes

    Active power per phase Yes No

    Reactive power total Yes Yes

    Reactive power per phase Yes No

    Apparent power total Yes Yes

    Apparent power per phase Yes No

    Phase to phase voltage L12, L23, L31 Yes (calculated)1

    Yes

    Phase voltage Yes No

    THD voltage Yes (phase volt.) Yes (phase to phase volt.)2

    Amplitude voltage harmonics (231)4

    Yes (phase volt.) Yes (phase to phase volt.)2

    Phase symmetry voltage Yes (phase volt.) Yes (phase to phase volt.)

    Current Yes (L1, L2, L3) Yes (L1, L3)3

    THD current Yes (L1, L2, L3) Yes (L1, L3)

    Amplitude current harmonics (231)4

    Yes (L1, L2, L3) Yes (L1, L3)

    Phase symmetry current Yes Yes4

    Phase angle total Yes Yes

    Phase angle per phase Yes No

    Update frequency

    The update frequency for instant values is proportional to the frequency of the measuring voltage.With a 50 Hz measuring voltage, updating occurs 12.5 times per second, and at 60 Hz, 15 times per

    second. Instant values can be read up to twice per second via the serial port when it is set to 19200

    baud.

    1Calculated from the voltages fundamental vectors.2The harmonics for voltage on the 2-element meter are to be seen from the standpoint of the voltages being D-

    connected internally.3Current L2 is calculated internally in the 2-element meter for monitoring.

    4The value can be read in CeweConfig and via the communication protocol but cannot currently be presented on the

    display (meter firmware 1.2.0).

    31

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    32/76

    Functions

    Accuracy

    The table shows typical accuracy for a CewePrometer with accuracy class 0.2 for a selection ofinstant values.

    Instant value Range Accuracy better than:

    Voltage amplitude Umin - Umax 0.1% of reading

    Current amplitude 5 % of Imax - Imax 0.1 % of reading

    Current amplitude 15% of Imax 0.05 % of Imax

    Frequency 4763 Hz 0.02 % of reading

    Power 1 % of Imax - Imax Corresponds to meters classaccording to energy measurementstandard

    Power factor At PF=0.5 and current 5% of Imax- Imax

    0.1 % of reading

    Harmonics measurement

    Harmonics numbers 2 to 31 are measured for all currents and voltages. At a fundamental frequency

    of 50 Hz, the second harmonic is 100 Hz, the third harmonic is 150 Hz, etc. Both the harmonics

    amplitude and phase angle are measured and included in the calculation of power and energy, and

    can be read via the meters communication protocols. In CeweConfig, harmonic amplitudes are

    presented with a diagram.

    THD

    THD stands for Total Harmonics Distortion and is a measurement of the amount of harmonics

    present in a signal. Voltages and currents THD can be read via CeweConfig and on the display.

    Harmonics on 2-element meter

    The harmonics measurements of voltage on the 2-element meters should be seen from the

    standpoint of the voltages being D-connected internally in the meter. The harmonics measured are

    the vector sums of the phases harmonics.

    32

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    33/76

    Functions

    Digital inputs and outputs

    The CewePrometer has several inputs and outputs that can be configured to perform various tasks.Both inputs and outputs are protected against overvoltages by varistors. They also have an isolated

    interface between the electronics and the surroundings to ensure personal safety. For electrical data

    on the meters inputs and outputs, see Appendix H Connection Data(pg. 73).

    Inputs

    The inputs can be configured as follows:

    Not used

    The input is not used.

    Finish historical period

    An incoming pulse will result in the present period ending and registers being copied tohistorical registers. For a pulse to finish historical period, it is also necessary that the

    historical registers be configured to allow this. For more information, see the section

    Historical registers(pg. 45).

    Pulse input

    To register pulses from pulse-producing units, such as energy meters or water meters, pulse

    inputs are used. Incoming pulses are accumulated in registers called external registers. There

    is an external register connected to each input on the meter. For external registers, a factor is

    configured by which the number of incoming pulses is multiplied. Prefixes and the number

    of decimals can also be configured for the registers. Moreover, the registers can be

    configured with descriptive texts.

    Time synchronisation

    When incoming pulses are received, the meters clock is synchronised at a specific interval

    For available synchronisation intervals and more detailed information on time

    synchronisation, see the section Meter clock(pg. 29).

    Registration of pulses

    The meter registers pulses on positive or negative flanks, depending on if the input is set to inverted

    or not. A pulse must be at least 16 ms long to be guaranteed of being detected by the meter. The

    maximum pulse width that the meter can handle is 60 s. By setting limits for maximum and

    minimum pulse lengths, the meter can be limited as to what it detects as a valid pulse. Pulses withlengths beyond the established limits are ignored. The occurrence of to long or to short pulses can

    also be configured to be recorded in the event log.

    Pulse

    length

    GND

    VCC

    Pulse length

    (inverted input)

    The figure shows pulse lengths when an input is inverted or non-inverted, respectively.

    33

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    34/76

    Functions

    Outputs

    The outputs can be configured as follows:

    Not usedThe output is not used.

    Pulse output

    The output is used to pulse an energy type that the meter is measuring. A pulse constant is

    specified for the output as pulses/unit, primary or secondary, and the pulse length is

    specified for all pulse outputs. The shortest possible pulse length is 40 ms. Pulses are not

    allowed not come too often, and because of this, there is a relationship between the pulse

    length and the specified pulse constant that maximises the pulse frequency to 1000/(pulse

    length(ms) * 2).

    Pulse Gap

    Maximum pulse frequency at outputs limited so that the gap is at least as long as the pulse

    length.

    Remote control

    With this function, the output can be made active or inactive by sending commands to themeter via the IEC62056-21/IEC1107 protocol. This functions could be used control

    anything that can be controlled with a digital relay output.

    Alarm outputWhen an output is set to functions as an alarm output, one or more of the user-defined

    alarms can be chosen to indicate at the output. When an alarm occurs, the output switches to

    active, and when the alarm state ceases, the output returns to inactive. In the section Alarms

    (pg. 41), user-defined alarms are described and how they can be configured.

    In contrast to the other selectable functions for outputs, alarm outputs can be inverted. Note

    that outputs are inverted via firmware. If the meter loses its auxiliary power, the relay willopen, regardless of it is inverted or not.

    End of MD period (maximum demand period)

    At the end of a set MD period, the output will go active for one second before returning to

    the inactive state. See the section Maximum demand(pg. 44).

    Output states

    An active output means a closed relay when the output is not inverted. When the output is inverted,

    the active relay is open. Only when the output is used as an alarm output can it be inverted. The

    CewePrometer outputs are of the solid-state type and when the meter is turned off, they are open.

    34

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    35/76

    Functions

    Meter variants

    Meter No of inputs No of outputs

    CewePrometer-R 4 6CewePrometer-R 2 10

    CewePrometer-R 0 12

    CewePrometer-R 0 0

    CewePrometer-W 4 8

    CewePrometer-W 0 0

    35

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    36/76

    Functions

    Display sequences

    The following is a description of the function properties of CewePrometers display sequences. Thesection Using the display(pg. 53) describes how to navigate in the display sequences via the

    meters buttons, and Appendix A Display Layouts(pg. 57) lists all of the CewePrometers

    available display layouts.

    Menu for choosing one of the four display sequences. The names of the sequences can be configured.

    The CewePrometer is equipped with a graphic display that can show the information available inthe meter. To organise the information, there can be up to five display sequences with a maximum

    of 40 selectable display layouts in each. Each display sequence can be given a name that will be

    presented on the display.

    Display sequence five is only accessible via the sealed button under the front panel window. The

    front panel window can be sealed to provide additional security. For this reason, it is appropriate

    that display layouts with sensitive information and sensitive functions be placed in display sequence

    five.

    Automatic disp lay cycl ing

    Automatic display cycling means that the display layouts in one or more display sequences areautomatically cycled by the meter. If, for example, display sequences 1 and 3 are configured for

    automatic display layout cycling, the meter will first cycle the display layouts in sequence 1 from

    the first to last layout, and then continue with sequence 3. After the last layout in sequence 3,

    cycling restarts with the first layout in sequence 1. The display layouts cycle with a configurable

    delay of 1 to 30 seconds. If a user manually navigates in the display sequences via the meter's

    buttons, cycling automatically stops and continues again after one minute.

    Passwords and security

    The display sequences can be configured to be password protected to limit access for various users.

    When a user chooses a password-protected display sequence via the meters buttons, a password

    entry field is displayed. Only a correctly entered password gives access to the display sequence andto the display layouts that are included in it. A password can be up to six characters long and

    include the characters A-Z, 0-9 and :;=?@. Passwords are not case-sensitive.

    Note: If a password-protected display sequence is configured for automatic display layout cycling,

    password protection is deactivated.

    Automatic return to f irst display layout

    One minute after a user has stopped navigating in the display sequences, the CewePrometer returns

    to the first display layout in display sequence 1 if automatic display layout cycling is not activated

    for any display sequence.

    36

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    37/76

    Functions

    Communications and security

    All CewePrometers are equipped with an optical port for communication. The meter can beoptionally equipped with one or two additional communication ports with RS232 or RS422

    interfaces. The communication protocol used is IEC62056-21, or as the older version of the

    standard is called, IEC1107. For more information on how the protocol is implemented, see the

    document CewePrometer IEC1107/IEC62056-21 meter reading.

    Communication speed

    The meters optical port always starts with a baud rate of 300 bps, regardless of what is configured,

    before shifting over to the specified communication speed. This means that software (for example,

    CeweConfig) that communicates with the meter via the optical port does not need to know the

    speed that the meters optical port is set to. The optional ports designated as communication ports

    #1 and #2 differ in this respect. They start at the specified baud rate from the beginning, whichmeans that connected software must be aware of the speed to be able to communicate.

    Communication port #1 can be set at a speed of between 300 bps and 19200 bps, and

    communication port #2 can be set at a speed of between 1200 and 19200 bps. The optical port can

    be set at a speed of between 300 and 9600 bps.

    Modem initiation

    If a modem is connected to one of the optional ports, a modem initiation string can be configured

    that the meter sends via the serial port. The initiation string can be used to set the correct

    communication settings for the modem and can consist of AT-Commands. The meter sends the

    initiation string when the meter is turned on and thereafter every tenth minute. During ongoingcommunications, the meter waits to send the initiation string until communications has stopped.

    Security

    The meter has five authorisation levels that can limit access to the meter during communication via

    any of the meters communication ports. Authorisation levels 1 and 2 are password-protected.

    Authorisation levels 3 to 5 may be protected by passwords or by a circuit board jumper.

    Authorisation levels

    1 Provides access to reading.

    2 Provides access to everything in level 1 plus

    access to set the clock and finish historicalperiods (also resets maximum demand

    values).

    3 Provides access to everything in level 2 plus

    access to configure the meter.

    4 Provides access to everything in level 3 plus

    access to transfer new firmware to the meter.

    5 Provides access to everything in level 4 plus

    access to calibrate the meter and reset

    registers.

    37

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    38/76

    Functions

    Limitation of total access attempts

    The meter limits the total number of access attempts to six when incorrect passwords are entered.

    At the seventh attempt, the meter blocks access whether the password is correct or not. The block isin effect until the next hour shift. After that, new password attempts may be made.

    Passwords

    A password consists of up to 12 case insensitive alfa-numerical characters. The authorisation check

    may be deactivated for a level by deleting the password. When connecting to the meter, access is

    granted to the highest level that is lacking password regardless of the password given by the user.

    Access restriction via circuit board jumper

    Inside the CewePrometer, there is space for a circuit board jumper that provides access to

    authorisation level 5 when fitted. If the meter is connected with authorisation at level 5, the functionof the jumper can be modified. Security can be heightened by requiring the jumper even for lower

    authorisation levels down to level 3. Security can also be relaxed by making authorisation level 5

    accessible via a password. Cewe Instrument can provide a technical fact sheet, tfcr0004, that

    describes the procedure for opening the meter and fitting the jumper.

    38

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    39/76

    Functions

    Loggers

    The CewePrometer has two identical, parallel and individually configurable loggers. That which isdescribed in this section applies both to logger 1 and logger 2.

    Overview

    A logger in a CewePrometer can log average values for instant quantities, energy registers and

    external registers. Some quantities can be logged both by phase and as total values for all three

    phases, others only as total values. The table provides an overview of quantities that can be logged.

    Certain instant values in the table are not available in 2-element meters and thus cannot be logged;

    see the section Instant values(pg. 31).

    Quantity By phase Total

    Active energy import Yes YesActive energy export Yes Yes

    Reactive energy import No Yes

    Reactive energy export No Yes

    Reactive energy inductive No Yes

    Reactive energy capacitive No Yes

    Reactive energy QI No Yes

    Reactive energy QII No Yes

    Reactive energy QIII No Yes

    Reactive energy QIV No Yes

    Apparent energy import No Yes

    Apparent energy export No Yes

    Phase voltage Yes Yes

    Phase to phase voltage Yes Yes

    Current Yes Yes

    Active power Yes Yes

    Reactive power Yes Yes

    Apparent power Yes Yes

    Frequency Not applicable Yes

    Phase angle Yes Yes

    Power factor Yes Yes

    THD voltage Yes Yes

    THD current Yes Yes

    External registers 18 Not applicable Yes

    Energy is logged as register values, i.e. at each logging occasion the current registers values is

    logged. Based on these register values, the reading software can present the energy as register

    values, periodic energy or as average power. CeweConfig provides all three alternatives.

    Logging interval and total channels

    A logger can store data in 1 to 10 channels. Common for all channels in a logger is that that the

    logging interval that can be configured from one minute up to one hour. A loggers capacity is

    dependent on number of channels and logging interval. When the logger is full, the oldest values

    will be written over. The table shows the capacity in number of days before the oldest value is

    written over.

    39

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    40/76

    Functions

    Capacity in days

    Number of l ogging channels

    Logging interval

    (min) 1 2 3 4 5 6 7 8 9 101 21 14 10 8.6 7.2 6.2 5.4 4.8 4.3 3.9

    2 43 28 21 17 14 12 10 9.6 8.6 7.9

    5 108 72 54 43 36 31 27 24 21 19

    10 217 144 108 86 72 62 54 48 43 39

    15 326 217 163 130 108 93 81 72 65 59

    30 652 434 326 260 217 186 163 144 130 118

    60 1304 869 652 521 434 372 326 289 260 237

    Storage of logged values

    Logged values are saved with time stamps, tariff information and flags that indicate events that haveoccurred during the logging interval.

    The time stamp indicates the end-time. If the logging interval is configured to one hour, a

    value with the time stamp 15:00 refers to the period 14:00 to 15:00.

    Tariff information indicates active rates for energy and power during the past interval.

    To indicate events or states during an interval, a logged value can be stored with one or

    more flags.

    Event or state Name of flag Explanation

    Time adjusted T During the past interval, the meter clock has been adjusted either instantaneous or a slidingadjustment is in progress.

    Disturbed D The past interval is incomplete. For example, an interval shortened by the meter beingwithout auxiliary power or if the logging memory has been reset. The first value after thelogging memory having been configured will thus always be indicated with "Faulty value(the logging memory is reset in conjunction with reconfiguration).

    Alarm A In conjunction with user-defined alarms being configured, it may be specified that an alarmwill also be indicated with logged values. When a user-defined alarm has triggered duringthe past interval, this is indicated with the flag Alarm.

    Parameter changed P The CewePrometers configuration, calibration or initiation has changed. Which of thesethree the flag refers to can be seen in the event log.

    Incorrect energydirection

    R The CewePrometer can be configured for a normal energy direction, import or export. If themeters energy direction deviates from this, this is indicated with the flag Incorrect energydirection.

    Daylight savingstime

    S Daylight saving time has been in effect during the past interval.

    Voltage

    loss/missing

    V During the past interval all measuring voltages have been lost or missing.

    Invalid value C To be able to guarantee that a logged value is correct, it is logged with a control sum. If thecheck sum is incorrect when the value is read, this is indicated with Invalid value. This is arare event, but could occur if the meter is subjected to powerful, external electromagneticinterference.

    For several of the flags, additional information can be viewed in the event log. A more exact

    time for events is specified in the log.

    Note: When power is calculated from logged energy values, the resulting values will be somewhat

    more precise than when power is logged directly. This is because power is logged as an average

    value of instant values. The instant values are read twice per second, while energy is accumulated

    continuously.

    40

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    41/76

    Functions

    Alarms

    The CewePrometer is equipped with alarms to be able to indicate when measured quantities areover or under a configurable limit value. The meter enters the alarm state when the limit value is

    reached. An alarm is generated only after the alarm state has continued for a configurable time

    (delay). Alarms are configurable by the user and are therefore called user-defined alarms. For the

    CewePrometer 1.2.0 or earlier, the maximum delay is 64 seconds.

    Note: There are alarms and events that cannot be configured, but instead, are always active.

    Examples of such alarms are indication that the clock has been changed or that an auxiliary power

    loss has occurred. For more information, see the sectionEvent log(pg. 43).

    Overview

    For most user-defined alarms, the limit value is specified as a percentage of the nominal value,which is the configured, nominal primary value (current, voltage or power). For 3-element meters,

    the limit value corresponds to phase voltage, and for 2-element meters, phase to phase voltage. The

    following table provides an overview of available alarms.

    Alarm Alarm state appl ies when Comm ents

    Low voltage The average value of the voltages is beneath thenominal voltage limit value.

    High voltage The average value of the voltages is above thenominal voltage limit value.

    Low power factor The power factor for the 3-phase system isbeneath the limit value.

    Voltage unbalance A voltage deviates percentage-wise from theaverage value of all voltages more than the limitvalue.

    Current unbalance A current deviates percentage-wise from theaverage value of all currents more than the limitvalue.

    Low active power The 3-phase systems total power is beneath thenominal power limit value.

    High active power The 3-phase systems total power is above thenominal power limit value.

    High THD voltage The average value of THD for all voltage phasesexceeds the limit value.

    High THD current The average value of THD for all current phasesexceeds the limit value.

    High harmonic voltage An overtone (2nd to 31st) relative to the basic

    tone on same voltage phase exceeds the limitvalue.

    The event log identifies the

    phase and harmonic no.

    High harmonic current An overtone (2nd to 31st) relative to the basictone on same current phase exceeds the limitvalue.

    The event log identifies thephase and harmonic no.

    Reverse energy direction The phase angle for a phase deviates by morethan 90 degrees from another phase.

    The event log identifies thephase with the deviating energydirection. This alarm is notavailable on 2-element meters.

    Voltage phase missing One or more voltage phases is missing The event log identifies themissing phase or phases.

    Internal error See the section Event log(pg. 43).

    41

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    42/76

    Functions

    Indication

    Alarms are always stored in the event log. Alarms can also be configured to indicate in one or moreof the following ways:

    Alarm LED on meter front

    Changed digital output level

    Indication of a logged value with a flag

    The alarm LED stops flashing and the digital output returns to inactive low after the alarm state

    passes.

    42

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    43/76

    Functions

    Event log

    The CewePrometer has a number of defined events and alarms that are stored in the meters eventlog when they occur. The event log can contain a maximum of 40 events. Thereafter, the oldest will

    be removed to make room for the new. The meter has a counter for the total number of events that

    have occurred since the latest reset.

    An event is represented by a time stamp and a code that indicates what has occurred. See Appendix

    B - Events(pg. 61) for a complete list of all events. For certain events, data is also stored for the

    events, for example, which phase the event concerns.

    Events are divided into three categories:

    User-defined alarmsThe meter has a number of alarms that when they occur, generate an event in the event log.

    The alarms each have an individual configuration that determines the conditions for when an

    alarm is to be activated. See the section Alarms(pg. 41).

    Meter events

    The meter is also equipped with a number of alarms that are not configurable by the user,

    so-called meter events. These have set conditions and are stored only in the event log.

    Examples of meter events are auxiliary power loss and clock resetting. A complete list of

    meter events is in Appendix B - Events(pg. 61).

    Internal errors

    The contents of the internal data structures, such as configuration and energy registers, arechecked by the meter. If an error is detected in one of the data structures, it is designated as

    an internal error. If an internal error is indicated, the event log should be checked for related

    information, and suitable actions should be taken. Internal errors are listed in Appendix B -

    Events(pg. 61).

    Display of events

    The event log can be viewed on the meters display if the display layout Eventsis configured to be

    included in one of the meters display sequences. Only the time stamp and event code are shown on

    the display. A more detailed description of the meter's events can be viewed in CeweConfig, which

    converts the code into plain text and displays any related data. Via CeweConfig, the event log can

    also be printed out or saved to a file.

    43

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    44/76

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    45/76

    Functions

    Historical registers

    Historical registers are used by the CewePrometer to store current register values at defined pointsso as to be able to read them later. Stored in historical registers are all maximum demand values,

    external registers, TOU registers and energy registers, with the exception of energy registers by

    phase. The historical registers are time stamped to indicate when storage occurred. The

    CewePrometer can store up to 14 historical registers.

    Date and time

    Energy registers Maximum demandvalues

    Time of use registers External registers

    Historical register includes a number of stored registers, and dates/times when they were stored.

    Finish historical periods

    By finishing a historical period, the current registers values are stored in historical registers and the

    maximum demand values are reset. When a period is finished, an event is stored in the meters

    event log. Periods can be finished in various ways:

    Via meter button The period is finished when the meters Menu/Apply button

    is held down for more than two seconds when the display

    layout Finish periodis active.

    This requires both that the historical registers are configured

    to permit finish via the meter button and that a display

    layout for this is entered in a display sequence.

    Via CeweConfig The period is finished when a command is given from

    CeweConfig or third-party software.

    At the end of the

    month

    The period is finished when the meter clock reaches the end

    of the month.

    Via digital input. The period ends when a pulse is received at a digital inputon the meter.

    This requires both that the historical registers are configured

    to permit ending via a digital input and that an input is

    configured for this purpose.

    Note: The display layoutFinish periodwill only work if the meter is configured to permit ending a

    period via a button.

    45

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    46/76

    Functions

    Time of use

    Time of use is a function that enables energy to be divided up into various registers depending onthe rate that applied when the energy was measured. In the CewePrometer, tariff structures can be

    stored that switch rates at predetermined times according to a configurable pattern. A tariff structure

    consists of seasons, day types and special days. The maximum number of rates is eight.

    Day types specify how rates change during a 24-hour day.

    Seasons specify the day types that apply during the days of the week, Monday to Sunday.

    Special days specify the day type that applies on a certain date.

    Tariff structures

    In the CewePrometer, there are two separate tariff structures. Both tariff structures have a set of daytypes, seasons and special days. By setting a starting date for a tariff structure, it can be configured

    before it goes into force.

    Day type

    In the CewePrometer, there are 16 day types (AP). A day type specifies witch rate, from a

    maximum of eight, should apply when during the day. 16 changing points per day may be specified.

    A day type can be connected to a day of the week in a season or to a special day.

    Season

    A season refers to a period. During this period, the season defines the day types that will apply

    during the days of the week. In the CewePrometer, there are 16 seasons per tariff structure. The

    seasons are arranged in a sequence where one season replaces the previous at a predetermined date.

    Special days

    Days that change rates according to a pattern that is not covered by linking day types to seasons

    (such as holidays) are called special days. A special day specifies the day type that applies on a

    certain date. Special days can be configured to apply every year on the same date or for a single

    year. In the CewePrometer, up to 30 special days per tariff structure can be configured.

    TOU registers

    An energy register or external register that is chosen to be divided into the rates is a TOU register.There are eight TOU registers and each TOU register has separate registers for eight rates.

    Maximum demand values and tariffs

    Maximum demand values are stored together with information on which rate applied when

    registered. For one and the same day, there can be separate day types for energy and maximum

    demand values.

    46

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    47/76

    Functions

    Example:The conditions are Monday to Saturday, rate 2 applies from 7:00 in the morning until

    17:00 in the afternoon. For the rest of the day, rate 1 applies. On Sundays, rate 1 applies around

    the clock. During the summer months, 1June to 31 August, rate 1 applies around the clock. On

    Christmas Eve, 24 December, rate 1 applies around the clock. For maximum demand values, rate 3

    always applies. It is active energy import that is divided in to different rates.

    Day types

    Three day types must be configured. Day type A to apply to energy during the autumn, winter and

    spring. Day type B to apply during the summer months, and day type C for maximum demand

    values throughout the year.

    Day type A Day type B Day type C00:00 Rate 1 00:00 Rate 1 00:00 Rate 3

    07:00 Rate 2

    17:00 Rate 1

    Seasons

    Two seasons must be configured. The first season will apply during the summer period and the

    second the rest of the year. The season that applies from 1 September will also apply from 1

    January to 31 May.

    06-01 Energy A A A A A A B

    MD C C C C C C C

    09-01 Energy B B B B B B B

    MD C C C C C C C

    Special day

    For rate 1 to apply all of Christmas Eve, a special day must be configured. Because no year is

    specified, the special day will apply every year.

    12-24 Energy C

    MD C

    TOU register

    A TOU register is configured to accumulate active energy in several registers for the different

    rates.

    47

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    48/76

    Functions

    Transformer compensation

    Transformer compensation is a function for compensating for measurement errors in instrumenttransformers and for losses in power transformers. The function enables the CewePrometer to

    present measurement values for which errors and losses have been compensated. The formulas used

    in the meter are presented in Appendix F Calculation Principles(pg. 67).

    Overview

    The tables present an overview of the transformer compensations in CewePrometer.

    Instrument transformer compensations

    Name Value to entered

    Amplitude error as percentVoltage error L1, L2, L3

    Phase angle in minutesAmplitude error as percentCurrent error L1, L2, L3

    Phase angle in minutes

    Power transformer compensations

    Name Value to entered

    Active loss as percent of nominal powerCopper losses, Total values

    Reactive loss as percent of nominal power

    Active loss as percent of nominal powerIron losses, Total values

    Reactive loss as percent of nominal power

    Instrument transformer compensations

    To compensate for errors in instrument transformers, their amplitude error in percent and phase

    angle error in minutes are configured in the meter. One minute is equal to the angle 1 /60. The

    errors can be specified separately for all voltages and currents. When instrument transformer

    compensations are used, current and voltage are affected, as well as all quantities that arise from

    these: power, energy, etc.

    2-element meter

    When voltage errors are compensated on a 2-element meter, this is done on phase to phase voltages

    L12, L23 and L31 instead of on phase voltages. Only L12 and L23 are included in the calculation of

    power and energy. Compensation of L31 has no significance in this respect. In compensation of

    current errors for 2-element meters, only L1 and L3 can be compensated for because they are theonly currents measured.

    Power transformer losses

    Power transformer losses consist of copper and iron losses. They are expressed as percentages of

    nominal power. One value is specified for active loss and one for reactive. When compensation of

    losses is configured, power, energy, power factor, etc. are affected but not current and voltage.

    48

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    49/76

    Functions

    Calculating loss values

    Based on the nominal total power and the measured loss value in watts, a loss value can be

    calculated as a percentage of nominal power. It is the loss value that is configured in the meter.

    Nominal power is calculated with configured nominal current and voltage.

    Nominal power: 3= nomnomnom voltageLineCurrentPower

    Loss value: 100/ = nomPowerLossvalueLoss

    49

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    50/76

    Functions

    Power quality

    Power quality encompasses voltage monitoring and harmonics measurement. Harmonicsmeasurement is described in the section Instant values(pg. 31).

    Voltage monitoring

    Voltage monitoring monitors three states: swells (overvoltage), sags (undervoltage) and interrupts.

    Monitoring is activated by configuring the limit values for sags and swells, and is deactivated by

    setting the limits to zero. The limits are expressed as percentages of configured nominal voltage.

    Example: For an upper limit of 110% and a lower limit of 90%, and the configured nominal

    primary voltage of 10 kV, the limits attained are 9 kV and 11 kV primary.

    For 3-element meters, the average value for phase voltage is monitored, and for 2-element meters,the average value for phase to phase voltage is monitored.

    Sags and swells

    Sags and swells shorter than one second are registered by accumulating registers. If the state lasts

    longer than one second, it is instead registered in the event log with a time stamp and duration. The

    accumulating counters and the event log can be read in CeweConfig.

    Interrupts

    When the average value for voltage falls to under 10% of the configured nominal voltage, this is

    registered as an interrupt in the event log with a time stamp and duration. Duration for an interruptof less than three seconds, and down to 10 ms, is presented as "< 3 s".

    State Duration Registered in Duration presented as

    Sags and swells 160 ms51 s Accumulating counter Duration not specified

    Sags and swells > 1s Event log Duration of state

    Interrupt 10 ms6 3 s Event log < 3 s

    Interrupt > 3 s Event log Duration of state

    5Applies to basic frequency 50 Hz. Corresponding time at 60 Hz is 130 ms.

    6Applies to basic frequency 50 Hz. Corresponding time at 60 Hz is 8.3 ms.

    50

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    51/76

    Functions

    Hysteresis

    Hysteresis means that the limit for a state and the limit for when it is restored are different. This to

    avoid several states being registered when the voltage level varies around a limit. The hysteresislimit is always midway between the low or high limit and nominal voltage.

    110%

    105%

    100%

    95%

    90%

    Limit for swells

    Nominal voltage

    Hysteresis limit

    Limit for sags

    Hysteresis limit

    11 kV

    10 kV

    9 kV

    9,5 kV

    10,5 kV

    Limit for interrupt

    Duration sag

    Duration

    interrupt

    10%1 kV

    PercentPrimary vol tage (example)

    51

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    52/76

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    53/76

    Using the display

    Using the display

    This section describes how the CewePrometers display can be used to read measurement valuesand also to control certain functions in the meter. The display layouts are arranged in display

    sequences. For details on display sequences, see Display sequences(pg. 36). A complete listing of

    display layouts is presented in Appendix A Display Layouts(pg. 57).

    Quadrant indicator

    In most display layouts, a quadrant indicator is shown in the lower-right corner. The quadrant

    indicator shows the quadrant in which energy is currently being measured. See Appendix F

    Calculation Principles(pg. 67) for a definition of quadrants.

    Quantity

    Measurement value

    Unit

    Phase

    Quadrant indicator Display layout

    Quadrant I

    Quadrant II

    Quadrant III

    Quadrant IV

    Voltage order display layout

    When the CewePrometer starts, the display layout Voltage Orderis always shown for about 15

    seconds. The display layout shows the order of the connected measurement voltages. If the voltage

    order is correct, the current direction is indicated with a + or a -. If not all voltages are connected,

    Phase missing is shown on the display. The current direction is indicated with a + if the currents

    phase angle is following its voltage with a maximum deviation of 90; if it is not, a - is displayed.

    Correct voltage order and current direction.

    Reversed current direction on phase 1.

    Reversed voltage order (no current direction shown).

    53

  • 8/10/2019 327.3 Usermanual CewePrometerA0172e-1a

    54/76

    Using the display

    Navigating in display sequences

    Use the buttons on the front of the CewePrometer to step through the display sequences. For moreinformation, see the Product description(pg. 6) section for button placement.

    Step forwardStep to next layout in the display sequence or moves upward in a menu.

    Menu/Apply

    The Menu/Apply button is used to open the menu where one of four configurable display sequences

    can be chosen. The button is used to confirm choices or initiate other activities depending on the