37-105WP Type MMV-WP Medium Voltage Wind Power Cable Three-Conductor: 5kV & 15kV, 133% • Rated 105°C www. amercable.com • e-mail: [email protected] Applications AmerCable’s Type MMV-WP wind power medium voltage cables are for use as the service loop (drop) cable on the output side of the wind turbine generator at temperatures from -40°C to +105°C. Features Carries both NEC markings for onshore applications and marine markings for offshore applications. Two layer, reinforced thermoset jacket resists torsional movement. Withstands greater than 10,000 cycles of twist, 720 degrees in both directions. These cables utilize flexible stranded conductors and braided shields which make them very suitable for applications involving repeated flexing and twisting. These cables have a small minimum bending radius (6xOD) for easy installation. Optional uninsulated grounding conductors sized per UL 1072. The increased flexibility of this cable allows for termination of one end and coiling in the nacelle. Then coiling and terminating other end when nacelle is mated with the tower, thereby reducing installation time. Passes IEC 332-3 Category A and IEEE 1202/UL 1581 flame tests. Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL1072. Jacket Black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL 1072. Jacket is two layer reinforced on multi-conductor constructions. Colored jackets for signifying different voltage levels are also available on special request (ie. yellow = 5kV and red = 15kV). Metallic Shield Composite shield consisting of tinned copper braid with nylon providing 60% copper coverage meeting UL 1309, IEEE Std. 1580, ICEA S-68-516 and UL 1072. The nylon is colored for easy phase identification (three conductor = black, blue, red) without the need to remove the shield to find an underlying colored tape. Insulation Shield Semi-conducting tape, with overlap, for fast and easy termination meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL 1072. Conductors Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11 and UL 1072 Insulation Extruded thermosetting 105°C Ethylene Propylene Rubber (EPR), meeting UL 1309 (Type E), IEEE 1580 (Type E), ICEA S-68-516 and UL 1072. Grounding Conductor (optional) One uninsulated soft annealed flexible stranded tinned copper conductor per ASTM B 33 and sized according to Table 21.1 of UL 1072. Ratings & Approvals UL Listed as Marine Shipboard Cable (E111461) UL Listed as NEC Type MV-105 (E116415) American Bureau of Shipping (ABS) Det Norske Veritas (DNV) 105˚C Temperature Rating Voltage Rating: 5kV & 15kV Torsional Rating: +/- 27°/ft Termination Kits AmerCable recommends Raychem’s HVT-M series terminations for multi-conductor constructions. Renewable Energy Cables Hawke Gland Types Hawke P/N Industrial & Safe Area (IP68) 121 Increased Safety 501/421 “EExe” Explosion Proof 710 Class I, Div. 2 Class I, Zone 2 Flameproof 501/421 “EExd” Zone 1 & 2

Upload: phambao

Post on 08-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 37-105WP Type MMV-WP Medium Voltage Wind Power Cableliterature.puertoricosupplier.com/032/HN32041.pdf ·  · 2010-03-17kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000

37-105WP

Type MMV-WPMedium Voltage Wind Power CableThree-Conductor: 5kV & 15kV, 133% • Rated 105°C

www. amercable.com • e-mail: [email protected]

ApplicationsAmerCable’s Type MMV-WP wind powermedium voltage cables are for use as theservice loop (drop) cable on the output sideof the wind turbine generator at temperaturesfrom -40°C to +105°C.

Features� Carries both NEC markings for onshore

applications and marine markings foroffshore applications.

� Two layer, reinforced thermoset jacketresists torsional movement.

� Withstands greater than 10,000 cyclesof twist, 720 degrees in both directions.

� These cables utilize flexible strandedconductors and braided shields which makethem very suitable for applications involvingrepeated flexing and twisting.

� These cables have a small minimum bendingradius (6xOD) for easy installation.

� Optional uninsulated grounding conductorssized per UL 1072.

� The increased flexibility of this cable allowsfor termination of one end and coiling in thenacelle. Then coiling and terminating otherend when nacelle is mated with the tower,thereby reducing installation time.

� Passes IEC 332-3 Category A andIEEE 1202/UL 1581 flame tests.

Conductor ShieldA combination of semi-conductingtape and extruded thermosettingsemi-conducting material meetingUL 1309, IEEE 1580, ICEA S-68-516and UL1072.

JacketBlack, arctic grade, flameretardant, oil, abrasion, chemicaland sunlight resistantthermosetting compoundmeeting UL 1309, IEEE 1580,ICEA S-68-516 and UL 1072.Jacket is two layer reinforced onmulti-conductor constructions.Colored jackets for signifyingdifferent voltage levels are alsoavailable on special request(ie. yellow = 5kV and red = 15kV).

Metallic ShieldComposite shieldconsisting of tinnedcopper braid withnylon providing 60%copper coveragemeeting UL 1309,IEEE Std. 1580,ICEA S-68-516 andUL 1072. The nylonis colored for easyphase identification(three conductor =black, blue, red)without the need toremove the shield tofind an underlyingcolored tape.

Insulation ShieldSemi-conducting tape, with overlap,for fast and easy termination meetingUL 1309, IEEE 1580, ICEA S-68-516and UL 1072.

ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11and UL 1072

InsulationExtruded thermosetting105°C Ethylene PropyleneRubber (EPR), meetingUL 1309 (Type E),IEEE 1580 (Type E), ICEA S-68-516 andUL 1072.

Grounding Conductor(optional)One uninsulated soft annealedflexible stranded tinned copperconductor per ASTM B 33 andsized according to Table 21.1of UL 1072.

Ratings & Approvals� UL Listed as Marine Shipboard Cable (E111461)� UL Listed as NEC Type MV-105 (E116415)� American Bureau of Shipping (ABS)� Det Norske Veritas (DNV)� 105˚C Temperature Rating� Voltage Rating: 5kV & 15kV� Torsional Rating: +/- 27°/ft

Termination KitsAmerCable recommendsRaychem’s HVT-M seriesterminations for multi-conductorconstructions.

Renewable Energy Cables

HawkeGland Types Hawke P/N

Industrial & Safe Area (IP68) 121Increased Safety 501/421“EExe”Explosion Proof 710

Class I, Div. 2Class I, Zone 2

Flameproof 501/421“EExd” Zone 1 & 2

Page 2: 37-105WP Type MMV-WP Medium Voltage Wind Power Cableliterature.puertoricosupplier.com/032/HN32041.pdf ·  · 2010-03-17kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000

37-105WP

Type MMV-WPMedium Voltage Wind Power CableThree-Conductor: 5kV & 15kV, 133% Insulation Level. Rated 105°C

Ordering Type MMV-WP Medium Voltage CablesExample:

• 3-conductor power cable• 15kV 133%• #2 AWG• Ground

AmerCable TypeMMV Prefix

Specific Cable Number(from charts)

Ground ConductorG – with ground

Blank – no ground

37–105 – 357WP G

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

Single Banked Inductive MaximumSize Nominal Weight In Free (No Spacing) DC Resistance AC Resistance Reactance Voltage Drop Optional Suspended

AWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding Lengthkcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor (ft.)

1/02/03/04/0

262313373444535646777

5070-

95120150185

-240300400

-306WP-307WP-308WP-309WP-310WP-311WP-312WP-313WP-314WP-315WP-316WP

2.1462.2902.3722.5142.6862.8502.9663.2133.3633.5953.752

320433943787445551585966676480279130

1050511959

201232266306348386429455528584647

171197226260296328365387449496550

0.1170.0930.0740.0580.0480.0400.0340.0280.0240.0200.016

0.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025

0.0340.0330.0320.0310.0300.0290.0290.0280.0280.0270.027

0.2390.1960.1630.1360.1180.1040.0920.0830.0740.0670.062

4433322111

1/0

302366401434455474497503530551585

Three-Conductor Type MMV-WP5kV, 100/133% Insulation Level

Three-Conductor Type MMV-WP15kV, 133% Insulation Level

Ampacity

Single Banked Inductive MaximumSize Nominal Weight In Free (No Spacing) DC Resistance AC Resistance Reactance Voltage Drop Optional Suspended

AWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding Lengthkcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor (ft)

21

1/02/03/04/0

35-

5070-

95

-357WP-358WP-359WP-360WP-361WP-362WP

2.5172.5582.7112.8372.9643.159

331135214076461951946033

156178205234269309

133151174199229263

0.1840.1470.1170.0930.0740.058

0.2300.1840.1470.1170.0940.075

0.0440.0430.0410.0390.0380.037

0.3640.2990.2460.2030.1700.142

644433

180216237269293321

Ampacity

Renewable Energy Cables

Order Your Cable withFactory InstalledTermination Kits

and Lugs

SAVETIME

SAVEMONEY

Page 3: 37-105WP Type MMV-WP Medium Voltage Wind Power Cableliterature.puertoricosupplier.com/032/HN32041.pdf ·  · 2010-03-17kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000

37-105WP

Type MMV-WPMedium Voltage Wind Power CableSingle-Conductor: 5kV, 15kV & 35kV • Rated 105°C

www. amercable.com • e-mail: [email protected]

ApplicationsAmerCable’s Type MMV-WP wind power medium voltage cables are for use as the service loop (drop) cable on the output side of the wind turbine generator at temperaturesfrom -40°C to +105°C.

Features� Carries both NEC markings for onshore

applications and marine markings for offshore applications.

� Withstands greater than 10,000 cycles of twist, 720 degrees in both directions.

� These cables utilize flexible strandedconductors and braided shields which makethem very suitable for applications involvingrepeated flexing and twisting.

� These cables have a small minimum bendingradius (6xOD) for easy installation.

� The increased flexibility of this cable allows for termination of one end and coiling in thenacelle. Then coiling and terminating otherend when nacelle is mated with the tower,thereby reducing installation time.

� Passes IEC 332-3 Category A and IEEE 1202/UL 1581 flame tests.

Conductor ShieldA combination of semi-conductingtape and extruded thermosettingsemi-conducting material meetingUL 1309, IEEE 1580, ICEA S-68-516and UL1072.

JacketBlack, arctic grade, flameretardant, oil, abrasion, chemicaland sunlight resistantthermosetting compoundmeeting UL 1309, IEEE 1580,ICEA S-68-516 and UL 1072.Colored jackets for signifyingdifferent voltage levelsare also available on specialrequest (ie. yellow = 5kV,and red = 15kV & 35kV).

Metallic ShieldComposite shieldconsisting of tinnedcopper braid withnylon providing 60%copper coveragemeeting UL 1309,IEEE Std. 1580,ICEA S-68-516 andUL 1072.

Insulation ShieldSemi-conducting tape, with overlap,for fast and easy termination meetingUL 1309, IEEE 1580, ICEA S-68-516and UL 1072.

ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11and UL 1072

InsulationExtruded thermosetting105°C Ethylene PropyleneRubber (EPR), meetingUL 1309 (Type E), IEEE 1580 (Type E), ICEA S-68-516 and UL 1072.

Ratings & Approvals� UL Listed as Marine Shipboard Cable (E111461)� UL Listed as NEC Type MV-105 (E116415)� American Bureau of Shipping (ABS)� Det Norske Veritas (DNV)� 105˚C Temperature Rating� Voltage Rating: 5kV, 15kV & 35kV� Torsional Rating: +/- 27°/ft

Termination KitsAmerCable recommendsRaychem’s HVT seriesterminations for single-conductorconstructions.

Renewable Energy Cables

HawkeGland Types Hawke P/N

Industrial & Safe Area (IP68) 121Increased Safety 501/421“EExe”Explosion Proof 710

Class I, Div. 2Class I, Zone 2

Flameproof 501/421“EExd” Zone 1 & 2

Page 4: 37-105WP Type MMV-WP Medium Voltage Wind Power Cableliterature.puertoricosupplier.com/032/HN32041.pdf ·  · 2010-03-17kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000

37-105WP

Type MMV-WPMedium Voltage Wind Power CableSingle Conductor: 5kV, 15kV & 35kV • Rated 105°C

Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009

Diameter DC Inductive MaximumSize Over Nominal Weight In Free Triangular Single Banked Resistance AC Resistance Reactance Voltage Drop Suspended

AWG/ Part No. Insulation Diameter (Lbs./ Air Configuration in Tray at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Lengthkcmil mm2 37-105 (inches) (inches) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) (ft.)

21

1/02/03/04/0

262313373444535

35-

5070-

95120150185

-240

-104WP-105WP-106WP-107WP-108WP-109WP-110WP-111WP-112WP-113WP-114WP

0.5600.5970.6490.7200.7550.8200.8990.9701.0161.1081.161

0.7650.8050.8920.9520.9951.0571.1361.2021.2671.3421.423

458539672803928

110812971496172620072340

186214247285328381435486544606682

159184212244281325371413460510570

158182210242279324370413462515580

0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.022

0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033

0.0410.0400.0390.0380.1430.0350.0340.0330.0320.0320.031

0.3610.2960.2450.2020.2780.1410.1220.1080.0950.0860.077

433470480576546582604630650670690

5kV, 100/133% Insulation Level

15kV, 133% Insulation Level

35kV, 100% Insulation Level

Ampacity

Diameter DC Inductive MaximumSize Over Nominal Weight In Free Triangular Single Banked Resistance AC Resistance Reactance Voltage Drop Suspended

AWG/ Part No. Insulation Diameter (Lbs./ Air Configuration in Tray at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Lengthkcmil mm2 37-105 (inches) (inches) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) (ft.)

21

1/02/03/04/0

262313373444535

35-

5070-

95120150185

-240

-164WP-165WP-166WP-167WP-168WP-169WP-170WP-171WP-172WP-173WP-174WP

0.8200.8510.9050.9631.0081.0721.1591.2301.2641.3641.423

1.1471.1851.2301.2881.3531.4151.4941.5601.6251.7621.839

786880989

11341292149017031922217525922947

186214247284327378431481536598672

164189217250288332377418464514574

158182210241278321366409456508571

0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.022

0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033

0.0500.0490.0470.0450.0440.0420.0400.0390.0380.0380.037

0.3700.3050.2520.2090.1760.1480.1290.1140.1010.0930.084

252288326366372433460490515519548

Ampacity

Diameter DC Inductive MaximumSize Over Nominal Weight In Free Triangular Single Banked Resistance AC Resistance Reactance Voltage Drop Suspended

AWG/ Part No. Insulation Diameter (Lbs./ Air Configuration in Tray at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Lengthkcmil mm2 37-105 (inches) (inches) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) (ft.)

21

1/02/03/04/0

262313

35-

5070-

95120150

-180WP-181WP-182WP-183WP-184WP-185WP-186WP-187WP

1.0801.1241.1711.2261.2761.3421.4221.469

1.3891.4481.4951.5501.6001.6651.8041.851

10471168128514321588179721152333

182209241278319371421467

167192220250288332376416

155178205236271315358397

0.1750.1400.1110.0890.0700.0560.0460.038

0.2300.1840.1470.1170.0940.0750.0630.053

0.0550.0540.0520.0500.0480.0460.0450.043

0.3750.3100.2570.2140.1800.1520.1340.118

190217250289319359370404

Ampacity

Renewable Energy Cables

Single-Conductor Type MMV-WP

Page 5: 37-105WP Type MMV-WP Medium Voltage Wind Power Cableliterature.puertoricosupplier.com/032/HN32041.pdf ·  · 2010-03-17kcmil mm2 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000

www. amercable.com • e-mail: [email protected]

Ampacities are based on API RP 14F (June 1999) Table 3. Ampacitiesare based on a 90°C conductor temperature and a 45°C ambienttemperature. The 105°C ampacities from this table may be used aspermitted. Ampacities covered by NEC article 328.80 may also be used (90°C or 105°C as permitted).Inductive reactance and voltage drop values are based on a 90°Cconductor temperature and 60 Hz operation.Please consult AmerCable on values based on other parameters.

MMV-WP Ampacities & Electrical Data

Individual Closest UninsulatedSize Size Number Strand Dia. IEEE 45 Conductor

AWG/kcmil mm2 of Strands (inches) Std. Size Dia. (inches)

21

1/02/03/04/0

262313373444535646777

35-

5070-

95120150185

-240300400

133209266342418532646777925

1110133215911924

0.0223 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201

6683

106133168212262313373444535646777

0.324 0.361 0.407 0.461 0.510 0.575 0.654 0.720 0.785 0.860 0.941 1.029 1.132

MMV-WP Stranding Profile

Renewable Energy Cables