3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
3M Water Renewal3MTM ScotchkoteTM Pipe Renewal Liner 2400
Claudio Galbiati – 3M Italia
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 2© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400 is..
… a two part, quick curing polyurea formulation
… a spray applied, trenchless solution
… approved for contact with drinking water in
countries in North America, Asia and Europe
… for use on pipes between 4” (100 mm) and
36” (1000 mm) in diameter
… for pipes made of a variety of ferrous
materials and asbestos-cement
… a solution to protect water quality and extend
the service life in existing potable water pipes
without the cost and community impacts of
full pipe replacement.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 3© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote 2400
• Resina a base di poliurea
• Reazione dei due componenti direttamente in fase di spruzzatura
• Nessun residuo di sostanze organiche (neanche bis-fenolo)
• Nessun metallo pesante contenuto nella formulazione
• Approvata per contatto con alimenti/acqua ad uso umano dal Ministero della
Salute Italiano
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 4© 3M 2015. All Rights Reserved. 3M Confidential.
Pipe lined annually has grown 119% in 2 years*
Approved & Installed
Regulatory Approval
US: 14.7 km/9.1 miles
CAN: 19.1 km/11.9 miles
CEE: 22.2 km/13.8 miles
APAC: 13.8 km/8.6 miles
3M Scotchkote Liner 2400 is a unique water quality and structural enhancement solution that resonates around the world
WE: 22.0 km/13.7 miles
Mexico: 1.4 km/0.9 miles
* As of end of year 2015, 93 km/58 miles have been lined
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 5© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400
Scotchkote Liner 2400 Addresses Multiple Problems
Corrosion barrier Inhibit future tuberculationand corrosion-related leaks. Protect clean water from the effects of corrosion and tuberculation
Structural enhancement Internal pressure containment that can with-stand the formation of 2 in (5 cm) corrosion holes
Thick coating
Thin coating
Some pipes have tuberculation, corrosion, and brown water
Some pipes are moredeteriorated and require a structural enhancement solution
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 6© 3M 2015. All Rights Reserved. 3M Confidential.
Spray Lining Rehabilitation:
1 giorno
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 7© 3M 2015. All Rights Reserved. 3M Confidential.
Sostenibilità
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
Principio di funzionamento: 3M design machine
© 3M 2010. All
Rights Reserved.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 9© 3M 2015. All Rights Reserved. 3M Confidential.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 10© 3M 2015. All Rights Reserved. 3M Confidential.
Case Study – Water QualityTown of Rothesay, New Brunswick, Canada
Challenge:
• Water quality and hydraulic issues
from scale buildup in lines
• Poor water pressure
• Flushing programs did not solve
the problem
Solution: Scotchkote Liner 2400
• Improved water quality problems
• Returned each section to service at
the end of each day, with boil
notices
• Water pressure improvement
Pipe description:
• Six inch (150 mm) unlined cast
iron, circa 1960’s.
• Length: 3,000 ft (1,000 meters)
“The 3MTM ScotchkoteTM Pipe Renewal Liner 2400 product was the perfect application for the needs of the Town of Rothesay. The town has experienced water quality and hydraulic issues with the buildup of scale in the lines. Flushing programs in the past have been implemented with little or no improvements. The use of the Scotchkote Liner 2400 allowed the town to do the project with only daytime shutdowns. All water was put back into service at the end of each day with only boil advisory required until sample results were returned and the advisory removed. The cure time for the ScotchkoteLiner 2400 was a major advantage in allowing the system to be turned back on each day.”
Kent Tays, Project ManagerCBCL Limited Consulting Engineers
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 11© 3M 2015. All Rights Reserved. 3M Confidential.
Case Study – Water PressureBangor Water District, Bangor, ME
Challenge:
• Improve water flow for fire
requirements in pipes with severe
corrosion and tuberculation
• Improve water quality
• Minimize project time
• Minimize excavation and fill
Solution: Scotchkote Liner 2400
• Improved water quality and flow by
inhibiting corrosion and tuberculation
• Completed in 3 days, 400 - 435 ft
sections/day
• Use of 8’ x 10’ excavation pits reduced
needed excavation
Pipe description:
• Sixteen inch (410 mm) unlined cast iron;
installed mid-1920’s
• Length: 1,100 feet (367 m)
*C-factor is a value used to indicate the smoothness of the interior of a pipe. The higher the C-factor, the smoother the pipe, the greater the carrying capacity, and the smaller the friction or energy loss from water flowing in the pipe.
The C-factor on this pipe went from the mid-50’s to over 130 and helped to restore fire flow requirements. We plan on using this product for another project in 2013.
Rick Pershken, City Engineer of Bangor Bangor, ME
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
s
Manage Asbestos-cement Pipes
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 13© 3M 2015. All Rights Reserved. 3M Confidential.
Protect Asbestos-cement Pipes
Protect cement matrix – 2.75 mm lining
• Inhibit calcium leaching
• Protect the matrix from deterioration by organic acids from microbiological activity
• Span small holes (6 mm), cracks and gaps (5 mm)
Provide structural enhancement – lining to various thicknesses
• Carry the internal pressure of the pipe
• Resist external hydrostatic pressure due to ground water
• Resist internal negative pressure during transient events
There may be certain rules and regulations governing work related to asbestos containing materials at the local, state, and federal levels. It is the responsibility of the authorized applicator (or their subcontractor) to interpret and comply with local, state, and federal regulations, obtain any required permits and complete any notification to regulatory agencies for any activities considered to be covered under such regulations before any project is begun.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 14© 3M 2015. All Rights Reserved. 3M Confidential.
Case Study –Leaks in Asbestos-cement and Cast Iron PipesMexico City, Iztapalapa
Challenge:
• Almost 40% of potable water was
being lost due to corrosion-related
leaks
• Corrosion was causing service
interruptions in a district of 1.8
million residents
• Pipe replacement was expensive
and interrupted service and traffic
for up to 2 days.
Solution: Scotchkote Liner 2400
• Avoided replacing pipes
• Improved cleaning with abrasives,
water pressure
• Trained the authorized applicator
• Awarded additional project phases
Pipe description:
4” asbestos-cement and cast iron pipes 40 to 80 years old.
Length: 3 km (9,800 ft)
“It’s amazing the impact in the water quality was visible immediately.”“We were able to reconnect the water service in less than 8 hours. Before it took at least 24 hours.”“It’s possible to give new life to the pipelines. We didn’t know we could do that.”
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 16© 3M 2015. All Rights Reserved. 3M Confidential.
Reduce Leaks
On average, utilities lose 20% of water to leaks
Source: Global Water Intelligence
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 17© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400 can span holes up to 6 mm in diameter and gaps up to 5 mm wide (0.2”)
Scotchkote Liner 2400 Can Reduce Leaks
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 18© 3M 2015. All Rights Reserved. 3M Confidential.
Case Study – Structural EnhancementYorkshire Water, United Kingdom
Challenge:
• Pilot to evaluate corrosion void
and split filling
• Evaluate water pressure
Solution: Scotchkote Liner 2400
• Successfully filled cuts and holes
with 3.5 mm lining
• Pressure testing on-site with 8 mm
lining holding 10 bar
Pipe description:
• Eight inch (203 mm) cast iron
pipe
“Yorkshire Water maintains 32,000km of pipe length in total, including some aging assets, and serviceability is a big issue for us. The liner will be hugely beneficial in allowing us to repair rather than replace, allowing us to treat more lines and spend money more effectively as well as reducing interruptions for our customers.”
Ian Johnson, Yorkshire Water
“We are excited about the prospect of using Scotchkote Liner 2400 as part of our AMP6 strategy. We are very happy with how the trial came together on the day, and the performance of the 2400 exceeded our expectations.”
Steve Taylor, Yorkshire Water
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
s
Extend Asset Life by Enhancing Pipe Structure
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 20© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400 Can Enhance Pipe Structure and Extend Asset Lives
• Reduce corrosion-related leaks
• Provide internal pressure containment
• Mitigate effects of through-wall corrosion in the pipe system
• Design with 50-year projected material properties to extend the life of existing water assets*
* Based on ASTM F1216-09
Once the pipe is cleaned, Scotchkote Liner 2400 can be applied at a thickness that will enhance pipe structure and fill holes up to 6 mm in diameter, gaps up to 5 mm.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 21© 3M 2015. All Rights Reserved. 3M Confidential.
Challenge:
• Extend potable water pipe life
• Improve fire flows and system
hydraulics
• Increase system reliability
• Protect water quality and eliminate
discolored water complaints
Solution: Scotchkote Liner 2400
• Used acoustic-based pipe assessment
• Worked with Authorized Applicator
to determine
rehabilitation/replacement
• Reduced project cost, time and
disruption using Scotchkote Liner
2400 where feasible
Case Study – Structural EnhancementNew Jersey American Water, Maplewood and Millburn, New Jersey
Pipe description:
• Six in. (150 mm) cast iron pipe, circa 1910-1918
• Length: 19,263 ft (4,846 m)
“New Jersey American Water was one of the first companies to work with 3M on polyurea linings in cast iron pipe and is excited to be using the current product (Scotchkote Liner 2400) on multiple pipeline rehabilitation projects. This product allows NJAW to cost effectively invest in renewing our pipelines, restoring full flow and pressure and eliminating water quality issues with minimal service disruption to our customers.”
Donald Shields, Vice President of EngineeringNew Jersey American Water
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
s
Manage Multiple Issues
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 23© 3M 2015. All Rights Reserved. 3M Confidential.
Case Study –Water Quality, Structural EnhancementOswego Water Department, Oswego, NY
Challenge:
• Severe water discoloration due to
tuberculation
• Three emergency repairs/splices in
two years
• Time and budget constraints
Solution: Scotchkote Liner 2400
• Improved water quality issues
• Improved pipe integrity by spanning
pitting, pin holes and gaps
• Returned to service each day by 6
p.m., with boil notices
• Provided significant cost savings by
eliminating the use of bypass pipes
• Project was 5 days, 350 – 490 ft/day
Pipe description:
• Six inch (150 mm) cast iron pipe, installed in 1923
• Length: 2,265 feet (690 m)
“The City of Oswego had a water main with a section where residents experienced severe water discoloration due to tuberculation and also an adjacent section with a history of excessive line breaks. 3M's Scotchkote Liner 2400 was the perfect solution to address the dual application of improving water quality and pipe integrity. The ability to return water service in the same day (with boil water notices) was of particular benefit to our customers and significantly reduced cost by eliminating the need for bypass lines.”
Brian J. Folgherait, Plant ManagerCity of Oswego Water Dept.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
s
Case Studies
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
Posizione
Field trial: via Bocconi Milano, Italia
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
Field trial: via Bocconi Milano, Italia
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
Derivazioni
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
Report dell’applicazioneMateriale e dati dell'applicazione:
Total: BASE ACT
Warm 211.7L 210.4L (totale caricato per l'applicazione)
Spin 0.9L 0.8L (utilizzato per i campioni di verifica prima della spruzzatura)
Line 162.7L 161.8L (quantità utilizzata)
Pipe Dia. 200mm
System Length 145.29M
Spessore:
Auto Lining Thickness: 3.6 mm
Dati di applicazione:
potete vedere i dati completi registrati lungo il tubo, che sono espressi come:
Time (orario progressivo) Lined (metri dalla partenza) Press B A Flow Speed (in m/min) MR TK (spessore)
Luogo dell'applicazione:
Milano, via Bocconi
coordinate GPS: N45.447666 E009.190526
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 30© 3M 2015. All Rights Reserved. 3M Confidential.
Applicazioni in ItaliaMilano: MM pozzi adduzione acqua potabile
diametri ad 250mm, 300mm, 350mm, 400mm – lunghezza >600m
materiale: ghisa, ghisa sferoidale, acciaio
pressione nominale di progetto: 10bar
Carpi: AIMAG rete distribuzione acqua potabile – lunghezza 150m
diametro: 150mm
materiale: cemento-amianto
pressione: 3bar
Monselice: Centro Veneto Servizi rete distribuzione acqua potabile – lunghezza 60mm
diametro: 150
materiale: cemento-amianto
pressione: 4bar
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 31© 3M 2015. All Rights Reserved. 3M Confidential.
Challenge:
• Repeated water quality complaints
from residents
• Pipe corrosion and dead end street
location
• Several flushings each year did not
solve the problem
Solution: Scotchkote Liner 2400
• Improved water quality problems
• Returned each section to service the
same day; completed entire project in
15 days
• Tested satisfactorily and remained
consistent
• Saved costs as bypass pipes and
annual flushings were eliminated
Case Study –Veolia Prague, Czech Republic
Pipe description:
• Six inch (150 mm) cast iron, circa 1960-70’s.
• Length: 7,649 ft (2,331 meters)
“This quick solution enabled substantial cost savings since no bypasses were needed; the water supply to residents was facilitated by water tanks. Just after returning the water service, lab tests of the water quality were performed. The results were excellent, above our expectations and to residents’ full satisfaction. This was our third project with SK 2400 and we plan on doing more in the future."
Technical managerVeolia Prague
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 32© 3M 2015. All Rights Reserved. 3M Confidential.
Challenge:
• Repeated water quality complaints
from residents
• Pipe corrosion and dead end street
location
• Several flushings each year did not
solve the problem
Solution: Scotchkote Liner 2400
• Improved water quality problems
• Returned each section to service the
same day; completed entire project in
15 days
• Tested satisfactorily and remained
consistent
• Saved costs as bypass pipes and
annual flushings were eliminated
Case Study – Water Quality Veolia Prague, Czech Republic
Pipe description:
• Six inch (150 mm) cast iron, circa 1960-70’s.
• Length: 7,649 ft (2,331 meters)
“This quick solution enabled substantial cost savings since no bypasses were needed; the water supply to residents was facilitated by water tanks. Just after returning the water service, lab tests of the water quality were performed. The results were excellent, above our expectations and to residents’ full satisfaction. This was our third project with SK 2400 and we plan on doing more in the future."
Technical managerVeolia Prague
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 33© 3M 2015. All Rights Reserved. 3M Confidential.
Case Study –Water Quality, Structural EnhancementOswego Water Department, Oswego, NY
Challenge:
• Severe water discoloration due to
tuberculation
• Three emergency repairs/splices in
two years
• Time and budget constraints
Solution: Scotchkote Liner 2400
• Resolved water quality issues
• Improved pipe integrity by spanning
pitting, pin holes and gaps
• Returned to service each day by 6
p.m., with boil notices
• Provided significant cost savings by
eliminating the use of bypass pipes
• Project was 5 days, 350 – 490 ft/day
Pipe description:
• Six inch (150 mm) cast iron pipe, installed in 1923
• Length: 2,265 feet (690 m)
“The City of Oswego had a water main with a section where residents experienced severe water discoloration due to tuberculation and also an adjacent section with a history of excessive line breaks. 3M's Scotchkote Liner 2400 was the perfect solution to address the dual application of improving water quality and pipe integrity. The ability to return water service in the same day (with boil water notices) was of particular benefit to our customers and significantly reduced cost by eliminating the need for bypass lines.“
Brian J. Folgherait, Plant ManagerCity of Oswego Water Dept.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 34© 3M 2015. All Rights Reserved. 3M Confidential.
Challenge:
• Corrosion, tuberculation led to water
quality issues
• Two pipe breaks previous year due to
corrosion
• Objectives – restore water quality,
extend pipe service life, increase flow
rate
Solution: Scotchkote Liner 2400
• Restored internal pipe diameter,
increasing water flow
• Restored and improved water quality by
eliminating tuberculation and mitigating
future build up and additional corrosion
• Reduced water loss through certain
pinholes, cracks and gaps
Case Study – Water Quality, Structural EnhancementMUP Vodokanal Saint Petersburg Municipal Water Utility, Russia
Pipe description:
• 600 mm (24 in) diameter steel, 1970’s
• Length: 1000 meters (3,280 ft)
• Plans to add new connections to existing pipe
• Three layers, 7 mm of lining total
• First commercial application in 24" pipe
• 1,000 meters of pipe lined in 20 days
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 35© 3M 2015. All Rights Reserved. 3M Confidential.
Challenge:
• Corrosion and tuberculation led to
water quality and pressure issues
• Objectives – restore water quality,
increase flow rate
Solution: Scotchkote Liner 2400
• Restored internal pipe diameter,
increasing water flow
• Restored and improved water
quality by eliminating
tuberculation and mitigating future
build up and additional corrosion
Case Study – Water Quality and FlowRosemerah Town Project, Johor Bahru, Malaysia
Pipe description:
• 150 mm (6 in) and 200 mm (8 in) diameter cast iron, late 1980’s
• Length: 2000 meters (6000 ft) 6 in, 500 meters (1500 ft) 8 in.
Syarikat Air Johor (SAJ) was the first water authority in Malaysia to work with 3M using Scotchkote Liner 2400 for water pipe rehabilitation. This lining allows SAJ to cost effectively renew their water pipelines without major traffic disruption at the highly congested Rosemerah Town. Elimination of discoloration, restoration of water flow and pressure has received excellent feedback from the end users.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
s
Project Design
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 37© 3M 2015. All Rights Reserved. 3M Confidential.
Design Considerations
Pipe Diameter
Pipe Bury Depth
Pipe Substrate Material
Asbestos-cement
PVC
Unlined cast iron
Unlined ductile iron
Steel
Cement mortar lined ductile iron/cast iron*
Lined ductile iron*
Lining Type
Structural lining
Barrier coating only (water quality lining)
Pipe Condition
Partially deteriorated gravity pipe
Partially deteriorated pressure pipe
Fully deteriorated gravity pipe
Fully deteriorated pressure pipe
For Structural Linings Only:
MAOP (Maximum allowable operating pressure)
Post-lining corrosion hole size
Desired design life
Desired safety design factor
Location of water table (above or below pipe invert)
Pipe Diameter
Pipe Bury Depth
Pipe Substrate Material
Asbestos-cement
PVC
Unlined cast iron
Unlined ductile iron
Steel
Cement mortar lined ductile iron/cast iron*
Lined ductile iron*
Lining Type
Structural lining
Barrier coating only (water quality lining)
Pipe Condition
Partially deteriorated gravity pipe
Partially deteriorated pressure pipe
Fully deteriorated gravity pipe
Fully deteriorated pressure pipe
For Structural Linings Only:
MAOP (Maximum allowable operating pressure)
Post-lining corrosion hole size
Desired design life
Desired safety design factor
Location of water table (above or below pipe invert)
* Asphaltic or coal tar linings must be completely removed prior to lining.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 38© 3M 2015. All Rights Reserved. 3M Confidential.
• Corrosion Barrier
• Smaller than 24” ferrous pipe -- 1.2 mm
• 24” and greater ferrous pipe – 2.0 mm
• 3M Scotchkote Pipe Renewal Liner 2400 Design and Application Guide Rev 5, pg 14
• Barrier Coating (AC pipe)
• 2.75 mm (not intended for fiber containment)
• Technical Bulletin available
• Structural Enhancement
• Thickness varies based on pipe condition and type
• Design with 50-year projected material properties, according to ASTM F1216-09
Appendix X1
• 3M Scotchkote Pipe Renewal Liner 2400 Design and Application Guide
Lining Thickness
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 39© 3M 2015. All Rights Reserved. 3M Confidential.
Structural Enhancement
3M Scotchkote Pipe Renewal Liner 2400 Design and
Application Guide (Design Guide)
• Follows the guidance of ASTM F1216-09
• Long term creep properties given in Table 13
• Transient vacuum may also be considered
Scotchkote Liner 2400 Liner Thickness Determination
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 40© 3M 2015. All Rights Reserved. 3M Confidential.
ASTM F1216-09 defines four pipe conditions
#1 Partially Deteriorated Gravity Pipe
• Lining may be subject to external pressure due to ground water
• Not directly applicable to Scotchkote Liner 2400, which is only approved for pressure pipes
• Can be easily evaluated if ground water is a concern
• Short term modulus is appropriate
Lining Thickness Design – ASTM F1216-09
t = liner thicknessD = pipe diameterC = ovality factor = 0.84EL = 50 year estimated flexural modulusPext = hydrostatic pressurev = Poisson’s ratio = 0.3K = enhancement factor= 6.5N= safety design factor
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 41© 3M 2015. All Rights Reserved. 3M Confidential.
ASTM F1216-09 defines four pipe conditions
#2 Partially Deteriorated Pressure Pipe
• Host pipe may have corrosion holes, cracks gaps.
• Lining must be capable of retaining internal pressure over corrosion holes
• Your designer specifies hole diameter anticipated after lining and before the end of
rehabilitated pipe's life
• Flexure creep rupture strength projections available in Table 13 of the Design Guide
t = liner thicknessD0 = pipe diameterDh = hole diameterSL = long term strengthPi = pressureN = safety ractor
Lining Thickness Design – ASTM F1216-09
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 42© 3M 2015. All Rights Reserved. 3M Confidential.
ASTM F1216-09 defines four pipe conditions
#3 Fully Deteriorated Gravity Pipe
𝑡 = 0.721𝐷o (𝑁𝑃𝑡/𝐶)2
𝐸𝐿𝑅𝑊𝐵′𝐸′
13
𝑃𝑡 = 𝑃𝑤′ + 𝑃𝑠 + 𝑃𝐿
𝑅𝑤= 1- 0.33 𝐻𝑤
𝐻𝑠 ≥ 0.67
𝐵′= 1
1+4𝑒−0.065𝐻𝑠
t = liner thicknessDO = pipe diameterPt = total external pressureN = safety design factorEL = long term flex modulusC = ovality factor=0.84RW = water buoyancy factorB’ = coefficient of elastic supportE’ = elastic support from soil = 800 psiHS = height of soilHW’ = height of water
Lining Thickness Design – ASTM F1216-09
• Host pipe may be subject to collapse from
soil, traffic, or external water pressure
• Lining must be able to carry these external
loads
• Not directly applicable to Scotchkote
2400, which is only approved for
pressure pipes
• Can be evaluated at designer’s discretion
• Short term modulus is appropriate
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 43© 3M 2015. All Rights Reserved. 3M Confidential.
ASTM F1216-09 defines four pipe conditions
#4 Fully Deteriorated Pressure Pipe
• Host pipe may be subject to longitudinal rupture due to internal pressure
• Lining must be able to contain hoop stress due to internal pressure
• Tensile creep rupture strengths available in Table 13 of the Design Guide
• ASTM F1216-09 also recommends a dimension ratio (DR) of no more than 100
• Ratio of pipe diameter to liner thickness
• Applicable to all cases
t = liner thicknessD = pipe diameterStL = long term tensile strengthPi = normal pipe pressureN = safety design factor
Lining Thickness Design – ASTM F1216-09
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 44© 3M 2015. All Rights Reserved. 3M Confidential.
Protect Asbestos-cement Pipes
Protect cement matrix – 2.75 mm lining
• Inhibit calcium leaching
• Protect the matrix from deterioration by organic acids from microbiological activity
• Span small holes (6 mm), cracks and gaps (5 mm)
Provide structural enhancement – lining to various thicknesses
• Carry the internal pressure of the pipe
• Resist external hydrostatic pressure due to ground water
• Resist internal negative pressure during transient events
There may be certain rules and regulations governing work related to asbestos containing materials at the local, state, and federal levels. It is the responsibility of the authorized applicator (or their subcontractor) to interpret and comply with local, state, and federal regulations, obtain any required permits and complete any notification to regulatory agencies for any activities considered to be covered under such regulations before any project is begun.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 45© 3M 2015. All Rights Reserved. 3M Confidential.
Follows procedure outlined in 3M
Scotchkote Pipe Renewal Liner 2400
Design and Application Guide (Design
Guide)
http://solutions.3m.com/wps/myportal/3M/en_U
S/Water-Infrastructure_NA/water/Product-
Calculator/
Scotchkote Liner 2400 Online Thickness Calculator
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential.
s
Applying 3M™ Scotchkote™ Pipe Renewal Liner 2400
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 47© 3M 2015. All Rights Reserved. 3M Confidential.
Spin-Cast Application© 3M 2016 All Rights Reserved.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 48© 3M 2015. All Rights Reserved. 3M Confidential.
Spin-Cast Application© 3M 2016 All Rights Reserved.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 49© 3M 2015. All Rights Reserved. 3M Confidential.
Retrieval© 3M 2016 All Rights Reserved.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 50© 3M 2015. All Rights Reserved. 3M Confidential.
© 3M 2014 All Rights Reserved.
Post-Lining Inspection
© 3M 2016 All Rights Reserved.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 51© 3M 2015. All Rights Reserved. 3M Confidential.
Corporation Inspection© 3M 2016 All Rights Reserved.
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 52© 3M 2015. All Rights Reserved. 3M Confidential.
Applying Scotchkote Liner 2400Service Connection Reinstatement
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 53© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400 – Restoration of Services
Debris in service connections should be “blown back” to clear the connection before lining
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 54© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400 – Restoration of Services
Debris in service connections can lead to blockage of service
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 55© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400 – Restoration of Services
Thick coatings may create some obstruction of the service
3MTM ScotchkoteTM Pipe Renewal Liner 2400
© 3M 2016. All Rights Reserved. 3M Confidential. 56© 3M 2015. All Rights Reserved. 3M Confidential.
Scotchkote Liner 2400 – Restoration of Services
A remotely operated cutter is used to clear blocked services