Product Data Sheet
For technical support relating to 3MTM Fire Protection Products and Systems, call: 1-800-328-1687For more information on 3M Fire Protection Products, visit: www.3M.com/firestop
Division 7 Section 07 84 00 - FirestoppingSection 07 27 00 - Air Barriers
Related Sections Section 07 86 00 - Smoke Seals Section 07 87 00 - Smoke Containment Barriers Section 21 00 00 - Fire Suppression Section 22 00 00 - Plumbing Section 26 00 00 - Electrical
SMOKE SEAL
Meets Air LeakageRequirements
L RATE
D
RATED FOAM
Foam-In-Place Firestop
Fire Barrier
C O L O R
MAROON
P
R O D U C
T
#1 Brand Preferred by firestop contractors
TYPICAL APPLICATIONS: metal pipe, plastic pipe, cable, cable tray, busway, insulated pipe, HVAC duct penetrations.
TESTED IN ACCORDANCE TO:ASTM E 814 (UL 1479)ASTM E 84 (UL 723)
USED BY: mechanical, electrical, and plumbing contractors.
FIP 1-Step
FILL, VOID, OR CAVITY MATERIALS
FILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 50L6
Net 12.85 fl oz • 380 mL
THROUGH PENETRATION
DANGER! MAY CAUSE ALLERGIC RESPIRATORY AND SKIN REACTION. VAPOR HARMFUL. CAUSES EYE AND SKIN IRRITATION.Read carefully other cautions on the side/back panel.
SOUND BARRIER
57In STC 57-rated wall assembly
STC
FILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 50L6
FILL, VOID OR CAVITY MATERIAL
FIRE BARRIER
UP TO 2 HOURF RA
TED
TEMPERATURE
UP TO 1 HOURT RA
TED
PLEASE SEE APPROPRIATE UL SYSTEM FOR ASSOCIATED RATING.
™3M1. Product DescriptionProduct Data SheetFIP 1-Step
Fi™3M
1. Product DescriptionProduct Data SheetFIP 1-Step
e Barrier Rated Foam r Fi
e Barrier Rated Foam
NCEAANTTASIRESSTP SYYSTOEIRFORHTINUSER OF
OROIDV, LLIF
6L50Y RRYTOCDIREE IR UL FEESS STEM
N OTIAATRRATEETNEGH-PUOL AERITAATMY TVIAAVC
LAALIRTEAATMY ITTYVAAVCCARR ODIOV, FILL
times during installation and bonds to most construction substrates i
Barrier
p
s
Fire
M
otserreiFecalP-nI-maoFFop
AOFD ETAATR
R
MAROON
P
LOC
DO
contractorptos by firedPreferrednarra B1##1
mechanical, electrical, and plumbing contractors.
FIP 1-Ste
:YUSED B
ASTM E 84 (UL 723)ASTM E 814 (UL 1479)TESTED IN ACCORDANCE TO:
.tionsaat penetrtduccCVAACHHVd pipe, eulatsy, inay, buswwaacable tric pipe, cable,tal pipe, plassttame:SNOITAATCILPPAAPLAICCAPYT
NTIOAATTHROUGH PENETR
times during installation and bonds to most construction substrates i
ASTM E 814 & CAN/ULC S115Meets UL/ULC ListedIs a Rated Firestop Foam
FIP 1-StepTION:TTENAAT
R
MAROON
O
U
T
C
ncluding, but not limited times during installation and bonds to most construction substrates i
ASTM E 814 & CAN/ULC S115UL/ULC ListedIs a Rated Firestop Foam
CODE OFFICIALSTION:
ncluding, but not limited DUNOS
C
B
ST
l alawSTCn I5
REFI
FTOPU
L SEAESMOK
D
R
TEAATRRALsuirementtqeR
egar LeakkaAiseettsM
EIRRA BD
y
R
blemssaasdteaat-r57STC
7557ARRIE B
D
ERTUAATMPERET
TEAATRRAFRUO H2TO
DTEAATRT
RU HO1O TPU
Applications2.
Quick cure & eliminates the need for mineral wool and caulk•Paintable with primer•Excellent adhesion •Sag-resistant formulation •Re-enterable / repairable •
6L05YRORECTTOIDNCEAANTASIESRRE I FLUEE STEMS SYYSSPOTESRIF
NTIOATRENEP-HOUGRTHE IN S UROFALIRTEAMYVITTYACRD OOIV,LLIF
TERIALSAATMVITY AC OR ,D VOI,FILL
Applications
Quick cure & eliminates the need for mineral wool and caulkPaintable with primerExcellent adhesion Sag-resistant formulation Re-enterable / repairable
Quick cure & eliminates the need for mineral wool and caulk
EASEPL
.INGTAATRD ETACISOASRFO
M ETS UL SYTEAATIROPRAPPEESEASE
ypical applicatioTTyApplications2.
3. Specifications
ASTM E 90 Standardest MeTTeStandard
TMethod for Fire 1-Step shall be tested to the criteria ofPFI
, metal pipe, cables include: blank openingsypical applicationApplications
3. Specifications
est Method for Laboratory MTTeASTM E 90 Standardest Method for Surface Burning Characteristics of Building M
ests of Penetration Firestop Systems,TCAN/ULC S115 Standard 1-Step shall be tested to the criteria of
ulated pipe, combination penets, inyaayr, cable ts, metal pipe, cable
Airborne est Method for Laboratory Measurement ofaterials, est Method for Surface Burning Characteristics of Building M 723 LASTM E 84 / Uests of Penetration Firestop Systems,
estTTeCAN/ULC S115 Standard
ough concr thsationrulated pipe, combination penet
Section 07 86 00 - Smoke Seals Related Sections
Air Barriers Section 07 27 00 -Section 07 84 00 - FirestoppingDivision 7
e etrough conc
ransmission Loss of Building Partitions and Elements, andTSoundASTM E 90 Standard
the IBC, IRC, IFC, IPC, IMC, NF
fLiffelSh
eoragStgarSto. 4
I
ransmission Loss of Building Partitions and Elements, andest Method for Laboratory MTTeASTM E 90 Standard
5000, NEC (NAAPPAthe IBC, IRC, IFC, IPC, IMC, NF
iffliffheltep -S1PPFI
ed anwully thaawffut be smuerus expoweeze / thaawfrshould be step -S1PP FI
efLiffhelS & e
ASTM E 413 ransmission Loss of Building Partitions and Elements, andAirborne est Method for Laboratory Measurement of
101 and NBCC.AAPPA 70), NFAAPPA 5000, NEC (NF
pened coinal uiin hs t2 1
tem ideal applicationotghtrou bded anthe packaginn till ishile wtep1-SP FIehtf ose
w betsnoitid condryin oors indd ertos
Section 26 00 00 - ElectricalSection 22 00 00 - Plumbing Section 21 00 00 - Fire Suppression Section 07 87 00 - Smoke Containment Barriers
heningkof ate d frtai
5)n oectiSee (Sesuo trio preruuratreptemneht,seezefrduct proIfg.the packagin
30°Cd °C anF (5°85d naF0° 4eenw
Section 21 00 00 - Fire Suppression Section 07 87 00 - Smoke Containment Barriers
d then
.5)t crodu pn
d voiAAv).30°C
tmaro inferor moFupport sl ahniccetFor
effeLiffelSh
I
vi,stection Producote Prrion on 3M Fitrotection PrPe r FiMTMting to 3aelrupport
(***Note: Expiration Date marked on cSixth and Seventh digit = (Batch #)Fifth digit = 4 (Production Code)Lot numbering: First to fourth digit = D
and bel)20°C(Fabove 68°se iffeliffhelstep -S1PP FI
posterfim//fio.3M.cw ww:tis vi32-800-1: call,msestynd Sas tducorotection Pr
artridge)(***Note: Expiration Date marked on cSixth and Seventh digit = (Batch #)Fifth digit = 4 (Production Code)
ate of Production (YYMM)Lot numbering: First to fourth digit = D
.)°C22.F (3°90ow and belpened conoinal ugiorin hs tn mo2 1s
788-16
ate of Production (YYMM)
hen winggakpacof ate dom frss rentainpened co
d eort shen
5. Performance & Typical Physical PropertiesColours Available: MaroonApplication Temperature Range: 50° to 120°F (10° to 49°C) Surface Burning (ASTM E 84): Flame Spread 10 Smoke Development 50STC Acoustic Barrier 57 when tested in STC 57 rated(ASTM E 90 and ASTM E 413): wall assemblyUnit Volume: VOC Less H2O and Exempt Solvents: <250 g/LCure: Foam becomes tack-free in about one minute. Full cure depends upon ambient conditions and volume of foam. Typical cure at 75°F (24°C) is approximately 2 minutes.Air Leakage (UL 1479 Section 6): <1 CFM/Sq FtYield: Up to 116 cubic inchesLeed: Meets the intent of LEED VOC regulations. <250 g/L VOCcontents (less H2O and exempt solvents). 6. Installation Techniques Consult a 3M Authorized Fire Protection Products Distributor or Sales Representative for applicable drawings and details.
Preparatory Work The surface of the opening and any penetrating items should be cleaned to allow for the proper adhesion of the 3M™ Fire Barrier Rated Foam (FIP 1-Step). Ensure that the surface of the substrates are not wet and are free from dust, debris and frost. Foam can be installed with either the manual or battery powered dispenser.
Installation Details Install the applicable depth of the FIP 1-Step as detailed within the applicable 3M ULC listed system. Please reference FIP 1-Step Installation Guide for further installation details. The FIP 1-Step may be trimmed after installation to be
Limitations Do not apply FIP 1-Step when the cartridge temperature is less than 50°F (10°C), damage may occur to cartridge or dispensing equipment. Do not apply FIP 1-Step to building materials that bleed oil, plasticizers or solvent (e.g. impregnated wood, oil-based sealants, or green or partially-vulcanized rubber). Do not apply FIP 1-Step to wet or frost-coated surfaces or areas that are continuously damp or immersed in water. This product is not acceptable for use with chlorinated polyvinylchloride (CPVC) pipes.
7. MaintenanceNo maintenance is expected when installed in accordance with manufacturer's installation guidelines. Once installed, if any section of the FIP 1-Step is damaged, the following procedure will apply: remove and reinstall the damaged section in accordance with the applicable FIP 1-Step UL Listed system.
8. AvailabilityTM Fire Protection
9. Safe Handling InformationConsult product's Material Safety Data Sheet (MSDS) prior to handling and disposal.
© 3M 2014. All Rights Reserved.1406-01200E
3M is a trademark of 3M Company. Used under license in Canada. All other trademarks are the property of their respective owners.
0
20
40
60
80
100
120
40 50 60 70 80 90 100 110 120 130
Tim
e (s
econ
ds)
FIP 1-Step Temperature
FIP 1-Step Temperature
Foam expansion start
Dry to touch time
10 20 15 5 25 30 35 40 45 50
(ºF)
(ºC)
Foam Expansion Start Time / Dry to Touch Timeat various FIP 1-Step temperatures
*Note: Expansion Start Time and Dry to Touch Times are NOT dependent on ambient air temperature. Expansion Start Time and Dry to Touch Times are dependent on FIP 1-Step temperature.
Industrial Adhesives and Tapes Division 3M Canada CompanyPost Office Box 5757London, Ontario N6A 4T1Canada1 800-364-3577www.3M.ca
Product Use: All statements, technical information and recommendations contained in this document are based upon tests or experience that 3M believes are reliable. However, many factors beyond 3M’s control can affect the product in a particular application, including the conditions under which the 3M product is used and the time and environmental conditions in which the product is expected to perform. Since these factors are uniquely within the user’s knowledge and control, it is essential that the user evaluate the 3M product to determine whether it is fit for a particular purpose and suitable for the user’s method of application. Warranty and Limited Remedy: 3M warrants that each 3M product meets the applicable specifications at the time 3M ships the product. 3M MAKES NO OTHER WARRANTIES OR CONDITIONS, EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OR CONDITION OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR ANY IMPLIED WARRANTY OR CONDITION ARISING OUT OF A COURSE OF DEALING, CUSTOM OR USAGE OF TRADE. User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user’s application. If the 3M product is defective, your exclusive remedy and 3M’s and seller’s sole obligation will be, at 3M’s option, to repair or replace the product or refund the purchase price. Limitation of Liability: Except where prohibited by law, 3M and seller will not be liable for any loss or damage arising from the 3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, condition, contract, negligence or strict liability.