4. the packages.pdf

Upload: ragh

Post on 06-Jul-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/16/2019 4. The packages.pdf

    1/38

     

    Page 149 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.0  THE PACKAGES

    4.1  Foreword

    With the technical term “package”, it is indicated by the Engineering

    Companies, but generally speaking in the industrial field, a small

    system constituted by two or more equipment, connected each others

    with piping, including some instruments and often electric components;

    therefore in this little plant, four of the six classic departments of the

    Engineering Company are present: Mechanical, Piping,

    Instrumentation, Electrical.

     The Civil work department is indirectly involved, in the sense that this

    small plant has, of course, to stand and to rest on a basement, but the

    Civil Word division could be directly concerned, for example, in case

    that the Package should include a steel structure; the Process

    department obviously, does not appear in evident manner, but it is

    upstream located, being the guide and the informing principle of all the

    equipment and complexes.

    We have repeated more times “little” plant, “small” system to indicate

    the package. But there are also significant units, for size and

    complexity, which can be considered as a package unit.

    Among these complex packages we will deal with, as examples, thePneumatic Transport System and Air Conditioning System.

    As far as the “small” packages are concerned we will consider, as

    examples, three of them: Solid Handling System – Oil Water Treatment

    Unit – Dosing Unit.

     Just for curiosity we want remind that the term package comes from

    the English word “package” that in the common acception means

    “parcel of things packed together”.

  • 8/16/2019 4. The packages.pdf

    2/38

     

    Page 150 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.2 

    Air Conditioning System

    4.2.1  Notes on the Psychrometry

     The atmosphere, in which we live, is constituted by a mixture of dry air

    and water vapour.

    Its moisture content is referred to as humidity. The proportion of

    moisture in the air, affects personal comfort.

     The psychrometry studies the properties of the mixture air-vapour, with

    particular regard to the ambient and technological necessities.

    4.2.1.1 Psychrometric Diagrams

    Since a conditioning system has to provide a proper thermo-hygrometric

    treatment of the air, it is convenient to use suitable charts for the

    calculation of such treatment. There are various types of these charts:

    Mollier’s diagram, Carrier’s diagram, Carr-Ashrae’s diagram.

    We will refer to the ASHRAE in the metric version provided by CARR

    group.

    4.2.1.2 

    Application of Psychrometric Chart

    It is sufficient to have two quantities, to get all the other ones.

    Example (see the attached diagram 2.1.2.F):

      dry air temperature 30°C

      wet bulb temperature 21,3°C

    We can read from the diagram:

      specific humidity 12,2 g/kg

      relative humidity 47%

      specific volume 0,875 m3/kg

      temperature of dew point 17,1°C

      enthalpy 14,7 kcal/kg

  • 8/16/2019 4. The packages.pdf

    3/38

     

    Page 151 of 462 

       S   T   P  -   0   1   1   /   1   3

  • 8/16/2019 4. The packages.pdf

    4/38

     

    Page 152 of 462 

       S   T   P  -   0   1   1   /   1   3

     4.2.2  Ambient Conditions for the Comfort

    4.2.2.1 Comfort, Industrial and Production Conditioning

    Purpose of the air conditioning is the one to generate, in the ambient,

    satisfactory conditions for the presence of people.

     The purpose of the industrial conditioning is the one to get artificial

    climate in order to permit the carrying out work particular cycles,

    dictated by requirement of technological process.

     The conditioning of production borns from the necessity to conciliate

    demands imposed by established technological process with the ones of

    comfort for the continuous presence of operators. We will analyzevarious cases, taking however into account that we can pass from a

    system to another one, for the calculation, only changing the

    parameters.

    4.2.2.2 Basic Parameters

     The basic parameters for the air conditioning are:

      Pureness of the air

     Velocity of the air near the people

       Temperature

      Relative humidity

    Pureness of the Air

     The impurities developed inside the air conditioned rooms as toxins,

    smokes, bad smells can be eliminated by means of air changes with

    external air.

    In the following table are indicated the air changes per hour for differentbuilding or room, with the note that air changes up to eight per hour,

    provide for removing contamination normally caused by human

    occupants.

     The higher rates of air changes provide for removing heat and steam in

    temperate zones.

  • 8/16/2019 4. The packages.pdf

    5/38

     

    Page 153 of 462 

       S   T   P  -   0   1   1   /   1   3

     

     The indicated table refers to the pure ventilation; it is clear that air

    changes higher than 8 can be reduced with a complete air conditioning.Other adopted criteria are:

      On the basis of the number of occupants (20 ÷ 80 m3 per

    occupant);

      On the basis of quantity of fresh air in relation to the volume air

    on work ambient ( 1 – 2 air changes per hour, till to 8 changes);

      On the basis of surface of the floor (2 – 8 m3/h per square meter

    of floor).

    Velocity of the Air near to the People

     The range of the values of the air velocity near the person is limited

    between 10 – 20 cm/sec. Of course, these values have nothing to do

    with the velocity at the outlet of the diffuseurs or grilles.

    Temperature and Relative Humidity of the Air

    Statistics and various experiences suggest the following values for

    temperature and relative humidity:

      for the R.U. on assume a value between 40% and 70% (normally

    50%) both in summer and in winter

      for the temperature on assume a value limited between 18°C and

    20°C (max. limit of 20°C has been fixed in order to reduce the

    energetic consumption) while, in summer the suggested

    temperature is connected to the external one, by means of the

    relation

    te

    ti = + 10

    2

    that means that, with the increasing of the external temperature also

    the internal temperature rises, and this is not only for energy saving

    reasons, but also in order to limitate the ∆  (delta) between inside and

    outside, since the human organism well tolerates positive sudden

    changes of temperature, while does not tolerate negative sudden

  • 8/16/2019 4. The packages.pdf

    6/38

     

    Page 154 of 462 

       S   T   P  -   0   1   1   /   1   3

    changes. Always for comfort reasons, the difference of the temperature

    of the entering air and the air present in the room, has to be controlled.

     The advised values are:

    ∆ te = 8 ÷ 12°C summer

    ∆ ti = 12 ÷ 14°C winter

    As far as the allowance on the thermo-hygrometric conditions is

    concerned, usually on assume a value of ± 5% for the U.R., and ± 1%

    for the temperature, in accordance with the normes UNI 5104.

    Ventilation Requirements

     TABLE 1 – Air Changes per Hour

    Situation Air changes per hour

    Assembly Halls 4-6

    Bakeries 20-30

    Banks 2-4

    Banquet Halls 6-10

    Billiards Rooms 6-8

    Boiler Houses 20-30

    Cafés and Coffee Bars 10-12

    Canteens 4-6

    Churches ½ -1

    Cinemas 10-15

    Club Rooms 8-10

    Dance Halls 6-8

    Dye Works 20-30

    Engine Rooms 20-30

    Factories (Workshops) 6-10

    Foundries 20-30

    Furnace Shops 30-60

  • 8/16/2019 4. The packages.pdf

    7/38

     

    Page 155 of 462 

       S   T   P  -   0   1   1   /   1   3

    Garages 6-8

    Hospitals: General Wards 4-6

    Hotel Bars 4-6

    Kitchens (Commercial or School) 15-20

    Kitchens (Domestic) 10-15

    Laboratories 4-6

    Lavatories 10-15

    Laundries 20-30

    Machine Shops 6-10

    Mushroom Houses 10-20

    Offices 4-6

    Paint Shops 30-60

    Photographic Darkrooms 10-15

    Pig Houses 6-10

    Poultry Houses: Deep Litter 6-10

    Residences 1-2

    Restaurants 6-10

    School Classrooms 2-3

    Ships’ Accomodation Lounges 10-20

    Ships’ Apple Storage 20-30

    Ships’ Cargo Holds (general) 6-10

    Ships’ Holds carrying Eggs, Meat, etc. 10-20

    Swimming Baths 20-30

     Theatres 10-15

  • 8/16/2019 4. The packages.pdf

    8/38

     

    Page 156 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.2.3  Types of Air Conditioning Plants

    4.2.3.1 General

    All types of plant have, as common unit, equipment called “air

    treatment unit”.

     The air treatment units have the task to provide for the air, to be sent

    into various rooms, different treatments according to the project

    requirements.

     The obtaining of these results is reached by means of modular

    construction of particular equipment called as already said “airtreatment units” (ATU or in Italian Language UTA).

     The linking of different sections, each of these able to develop a

    determinate operation, allows to obtain the necessary performance for

    the plant with high precision.

     These units do not usually include the components for the production

    of hot and cold fluids; such machines, refrigeration units and heat

    generators, have to be provided separately.

     The air treatment units, are normally constituted of the following

    sections:

      Mixing sections of fresh air and recirculated air

      Filtration section

      Pre-heating coil section

      Humidification section

      Cooling and dehumidification coil section

      Post-heating section(*)

      Ventilation section

    Now we will examine the main air conditioning plants, with the remarks

    that the combination of these, can give place to many other systems,

    each of them with its particular characteristics.

    (*) According to various cases, the post-heating battery, can be located

    into ducting.

  • 8/16/2019 4. The packages.pdf

    9/38

     

    Page 157 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.2.3.2 Conditioning Systems for Single Zone

     This is the more simple type of the air treatment unit. From the unit,the air is supplied, at the required conditions controlled by thermostat

    and/or humidistat of zone, to the various rooms.

     The air, so distributed can treat a zone (constituted by one or more

    rooms) where the thermo-hygrometric conditions are uniforms.

    4.2.3.3 Conditioning of “Multiple Zones” Type

     The air conditioning system of multiple zones type, is the natural

    extension of the single zone one, when the various rooms, to be

    conditioned, have different thermo-hygrometric requests.Substantially on dials of only one conditioning group, but the ducting of

    which, is splitted into various ducts, each of them serves one room (or

    one group of room). At the beginning of the ducts post-heating coils are

    installed; these coils are controlled by their respective thermostats.

    Usually, a pilot room (the more binding one for extension and for

    thermal loads) is selected to demand and control the cold requirement,

    while, for the other rooms, the regulation is obtained by the post-

    heating the air at the required temperature.

     Therefore it can happen that in summer, the maximum cooling power,

    on the basis of which the plant has been dimensioned, is neutralized by

    means of these post-heating treatments. We understand very well as theexercise cost, for this type of plant, can considerably raise, in

    comparison with the plant of single zone type.

    4.2.3.4 Conditioning System of “Multi-Zones” Type

     The systems of air conditioning of multizone type, as the ones of

    multiple zones, permit the simultaneous air conditioning of more rooms

    or groups of rooms which present different thermic internal loads.

    But, while the air conditioning plants of multiple zone type,substantially born from the single zone system, with subsequent

    splitting of the air supply ducting into additional ducts, the multi zone

    systems consist of centralized air treatment units of “package” type that

    contain just inside the unit, the splitting into zones.

  • 8/16/2019 4. The packages.pdf

    10/38

     

    Page 158 of 462 

       S   T   P  -   0   1   1   /   1   3

    In detail, the conditioners are constituted of mixing section of fresh air

    and recirculated air, a filtering section, a fan section, one treatment

    section including, in parallel, one cooling coil and one heating coil, and

    at the end a set of mixing dampers (one for each foreseen zone) for thevariation of mixture ratio between the hot air and the cold air, with a

    constant flow rate for each zone.

     These dampers are located at the outlet of the unit and each couple of

    dampers is at the head of one independent duct.

    4.2.3.5 Conditioning System of “Air-Water Mixed Type”

    In this type of plant, the supply of heat and cold into rooms tocompensate the thermic-hygrometric load is given both to the air and to

    the water.

     The water at the required temperature is sent, by piping to the local

    unit that include one coil, one filter and one fan, called “fan coil”, while

    the primary air is sent to the various rooms by ducting.

     The fresh air is submitted to the same treatments in an air treatments

    centralized unit already described. It is clear that in this case the unit,

    treating only external air, is smaller, under similar conditions than ones

    which have to treat fresh and recirculated air.

     This type of plant permits, in comparison of other types, great flexibilityin the design and in the planimetric arrangement.

    For example the fan-coils can be visible (under the windows for

    example) or located in the false ceiling.

     There is also the possibility to carry out an air conditioning plant

    without the use of centralized air treating unit, simply by providing the

    local units by means of external air intake.

     The limits of this simplified system are easy to individuate.

  • 8/16/2019 4. The packages.pdf

    11/38

     

    Page 159 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.2.3.6 Conditioning System of “Double Duct” Type

    With this system the cooling and heating coils are properly placed in

    order to feed two separated ducts which depart from the unit.

    One duct conveys the cooled air, the other one the hot air, both arriving

    to the rooms which have to be air conditioned. In each room, a mixing

    box is installed provided with conjugated dampers which provide for the

    mixing of the two air flows coming from the conditioners, according to

    the ambient thermostat.

    Generally speaking this air distribution is made at high speed (mainly

    for space reasons) and therefore the mixing boxes have also the

    function to attenuate the velocity and the noise. The system of double

    duct type, is a system of quality, particularly suitable for largecomplexes both civil and industrial.

    4.2.4  Filtration of The Air

    As already said one of the purpose of the air conditioning plants, is the

    one to maintain in the served rooms, a proper pureness of the air; the

    above is usually got, by means of adequate changes of fresh air, but in

    the mean time, by cleaning fresh air and recirculated air by means of

    proper filtration system. The choice of the more suitable filter depends from various factors,

    mainly connected to the characteristics of impurities present in the air

    and to final destinations of the conditioned places.

     The main characteristics of the filter are: the efficiency, the retention

    capacity and load losses.

     The filter efficiency is measured by the ratio:

    up stream concentration – down stream concentration

    eff. = x 100up stream concentration 

  • 8/16/2019 4. The packages.pdf

    12/38

     

    Page 160 of 462 

       S   T   P  -   0   1   1   /   1   3

    4.2.5  Equipment of the HVAC Systems

     The main equipment used in the HVAC system, in addition to the air

    treatment unit, already described, are mentioned here below,accompanied with a very short description: for more detailed

    specification, man has to refer to specialised literature.

    4.2.5.1 Monoblock Self-Contained Conditioning Units

     These equipment, foreseen for inside or outside installation, are

    constituted by two parts assembled in the same box:

     

    One moto condensing unit composed by compressor,condensation coil and fans for the cooling of the coil if

    condensation is made by air, or by heat exchanger if the

    condensation is of water type.

      One evaporating section composed by a cooling coil, of direct

    expansion type, a centrifugal fan for the supply and return of the

    air, filters and the necessary piping and valves. A control panel is

    also provided.

     Therefore it is realised a complete and hermetically closed refrigerating

    circuit. In this case the unit require only to be connected to the supplyand return air ducts and the electric and hydraulic feeding.

     These monoblock units are available on the market for a powers range

    from 10 to 200 Kw.

  • 8/16/2019 4. The packages.pdf

    13/38

     

    Page 161 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.2.5.2 Self-Contained Conditioning Unit, Roof Top Type

     These units, belonging to the self-contained type previously seen, are

    foreseen for outside installation to be positioned on the roofs of the

    building, for the direct climatization of the below rooms. Depending

    from the refrigerating requested capacity, these conditioners can be

    equipped with one, two or more compressor, with the condensating and

    evaporating coils in one or more sections.

    4.2.5.3 HVAC System, Split Type

     The air conditioning machine of split type are constituted by a moto-condensing unit air cooled for outside installation and by a

    ventilating/evaporating unit (that can be provided with ducting) to be

    positioned inside. Both the units have to be connected each to other

    with 2 refrigerating lines (one for the refrigerating liquid, the other one

    for the gas). Of course, electrical lines have to be also provided.

     These split units originated for the cooling, can be today used for the

    heating, on the basis of the heat-pump principle.

    We can find on the market, split units of various capacity:

      Split units of 1,5 ÷ 15 Kw refrigerating power.

     They are employed for residential and light commercial

    applications.

      Split units with a refrigerating power till 80 Kw.With these

    capacities it is possible to carry out systems provided with a

    certain extensive ducting or it is possible to carry out VFR

    systems (Variable Refrigerant Volume) of minor power but that

    can be connected to a greater number of internal units. This type

    can be used also for minor industrial buildings.

  • 8/16/2019 4. The packages.pdf

    14/38

     

    Page 162 of 462 

       S   T   P  -   0   1   1   /   1   3

    4.2.5.4 Refrigerant Groups of Compression Type

    Of course, in addition to the self-contained equipment, previouslynoted, refrigerant groups of compression and absorption type are used,

    especially for high refrigerating capacity.

    Here below we give short notice on the refrigerant groups of compressed

    type for capacities till 200 Kw compressors, scroll type are used.

    For higher capacities till to 900 Kw the screw compressors are

    employed.

    Over these capacities the centrifugal compressor are used.

     The refrigerating fluids, now given up the Freon, are the HFC 410 A for

    the refrigerating groups of scroll type and HFC 134 A for refrigerating

    groups, screw and centrifugal type.

    4.2.6  Data and Information to be given to the HVAC’s Supplier

    4.2.6.1 General

    Purpose of an air conditioning plant consists, as already said, of the

    simultaneous control of the temperature, relative humidity, ventilation

    and pureness of the air.

    Before starting in the design it is necessary to gather and to organize all

    the information and the available data, to be transmitted, attached to

    the Material Requisition to the suppliers of HVAC System, intended as

    Package Unit.

    It remains understood that an engineering company can design, define

    and purchase the single items constituting the HVAC plant, without

    applying to the specialised supplier of HVAC system; this choice

    depends from the internal resources of the engineering company

    (availability of specialists in this field) from the complexity of the system

    and for the timing. It is a fact that, apart little systems as electricalsubstations or offices, it is always more convenient to address to

    specialised Vendors, the sole responsible of the HVAC plant.

  • 8/16/2019 4. The packages.pdf

    15/38

     

    Page 163 of 462 

       S   T   P  -   0   1   1   /   1   3

     These data and information will include:

     

    Drawings of the buildings and of the rooms to be conditioned(plants and sections)

      Design external conditions (temperature, relative humidity, in

    winter and summer)

      Design internal conditions (temperature, relative humidity, with

    the required tolerances, filtration level)

       Type and thickness of the walls, floors, ceilings and roofs

      Characteristics of doors, windows, rolling shutters or curtains

      Internal sources of heat (for each room) gains from:

    - lighting : w

    - crowding: n° of people

    - fluid evaporating: kg/h

    - stoves, heater, dryer: kcal/h

      characteristics of the utilities:

    - water, compressed air, steam, electric power

      use of the rooms (offices, laboratory, control room, etc.)

      type of the required system:

    - all air, air and fancoils, air and split units, etc.

      Number of the required air changes

      Room foreseen for the installation of air conditioning equipment

      Foreseen daily hours of operation.

  • 8/16/2019 4. The packages.pdf

    16/38

     

    Page 164 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.2.6.2 External Thermohigrometric Design Conditions

     The external design conditions change for the different geographic

    locations. It is not reasonable to dimension the plants for the heaviest

    conditions that happen during only few hours in a certain year’s

    number; this should cause additional costs with the limited benefits.

    Standard tables indicating external design conditions are generally

    adopted, in case of lack or other requests and indications.

    4.2.6.3  The Heat Transmission through the External Structures due to the

     Temperature’s Difference

     The transmitted heat, in regime condition, through a wall because of

    the different temperatures between external and internal air, is given

    by:

    q = K S (te – ti)

    where

    S = wall area m2

    te = external temperatureti = internal temperature

    K = global coefficient of thermic transmission kcal/m2 °Ch

    Where K is given by:

    1 1 s 1

    = + +

    K  ai  c ae

    or more generally for composite structures

    1 1 S1  S2 Sn 1

    = + + + …. +

    K  ai  c1 

    c2  cn ae 

    ai, ae = unit surface conductances in kcal/h m2°C

  • 8/16/2019 4. The packages.pdf

    17/38

     

    Page 165 of 462 

       S   T   P  -   0   1   1   /   1   3

    s1, s2,…sn = thicknesses of the various layers of structure in m

    c1, c2,…cn = coefficients of thermal internal conductivity of materials per

    kcal/m h°C

  • 8/16/2019 4. The packages.pdf

    18/38

     

    Page 166 of 462 

       S   T   P  -   0   1   1   /   1   3

    Thermal Internal Conductivity c (kcal/m h°C) for some materials

    Materials c Specific weight kg/m 3  

    Construction Materials

    Asphalt 0,6 2.400

    Bitumen 0,15 1.050

    Concrete:

    - cement, sand, gravel, armor Fe  1,2 2.100

    - cement, sand gravel 1,0 1.800

    - pumice 0,31 1.150

    - cellular 0,2 700

    Cement 0,78 820 + 1.950

    Cardboard 0,23 1.300

    Bitumen cardboard 0,16 1.100

    Roofing sheet:

    - ribbed plates in Al (i.e. “coverrar” from TML “alusio”from

    SICIT alucover” from ASA)

    1,8 2.700

    Resin laminate 0,10/0,15 600

    Plast 0,35/0,80 1.000 + 1.200

    Gres 2 2.650

    Natural or synthetic rubber plates 0,14 1.000

    Coating:

    - with lime mortar 0,8 1.900

    - with cement mortar 1,2 2.200

    - with plast mortar 0,6 1.200

    Pattern:

    - full bricks 0,7 1.800

    - hollow bricks 0,45 800

    - cutting stones 1,4/2,2 1.400 + 2.800

    - tuff 0,7/1,0 1.100 + 1.900

    Panels:

    - plywood 0,1 550

  • 8/16/2019 4. The packages.pdf

    19/38

     

    Page 167 of 462 

       S   T   P  -   0   1   1   /   1   3

    - plast 0,14 970

    Floors:

    - linoleum 0,16 1.200

    - rubber 0,26 1.600

    - P.V.C. 0,25 2.000

    - asphalt and resin (i.e. “vinilom AT”) 0,47 1.950

    Sand:

    - dry 0,45 1.600

    - moist 1,0 2.000

    Land:

    - clayey 2,0 2.000

    - dry 0,45 1.400 + 1.900

    Glass 0,50/0,80 2.400 + 2.800

    Insulating materials

    Expanded elastomers i.e.:

    - “Armaflex” 0,037 112

    - foam 0,026 73

    - ultrafoom 0,035 100

    Felt

    Fiberglass (mattresses, panels, chapels) i.e.:

    - “Fiberglass” 0,030 80

    - Ultralite 0,036 160

    Rock wool 0,031/0,032 80/112

    Insulating bricks:

    - 29% clay, 28% sawdust, 43% coke 0,2 750

    - pumice 0,135 630

    - cork 0,04 200

     Thermal insulating panels:

    - plast light panels 0,14 800

    - wood fibers with MgSO4  0,06 800

  • 8/16/2019 4. The packages.pdf

    20/38

     

    Page 168 of 462 

       S   T   P  -   0   1   1   /   1   3

    Expanded elastic poliuterano 0,03 20

    Cork:

    - dissolved cork 0,033 85

    - cork slabs with bituminous binder 0,05 220

    4.2.7  Figures to be used for Quick Estimates

    Here below we give some data, to be considered only indicative, but

    certainly useful for preliminary estimates of costs and services

    consumption.

    4.2.7.1 Costs

    A system very convenient for quick estimates, could be the one to fix the

    cost, of the conditioning plant per m3, empty for full of the building; in

    this respect, we must immediately say that the fluctuation of this cost is

    rather wide according to the type of installation; in fact, a part the

    carrying out modalities of the building, particularly as regards the

    thermal insulation, its destination, the availability of cooling water, etc.,

    the cost per m3 varies greatly, up to fluctuations in the range of 100%,

    depending from the building’s size.

    So while for a building of normal dimensions, cubature for example of5.000 m3, the cost per m3 could be around 90,00 €, for small rooms,

    on the contrary, with volume around to the 500 + 800 m3 (typical case

    of the control room) the cost could raise up to 110,00 + 130,00 € per

    m3.

    With the increase of the size of the building and therefore of the

    importance of the plant, the cost per m3 tends to reduce; still today also

    for large air-conditioning plant from several hundreds of thousands of

    frigories/hour, it is difficult to decrease under 50 ÷ 60 € per m3.

     The above mentioned prices are inclusive of all: design, materials

    supply and installation.

  • 8/16/2019 4. The packages.pdf

    21/38

     

    Page 169 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.2.7.2 Services Consumption

    Electrical Power

     The requirements of frigories can be fixed with sufficient accuracy

    around 30 - 50 frigories/hour per m3 of the building; therefore

    estimated 1 kw for each 3.000 + 3.500 Fr/hour (values valid for

    medium-high potential) the electrical power required, it is easy, on the

    basis of the only cubature, to estimate, with sufficient approximation,

    the power absorbed by the cooling system.

    Cooling Water

     The preliminary evaluation of the water rate, necessary for the cooling

    of the condenser, can be immediately calculated from the knowledge of

    electrical power absorbed by the cooling system. In fact a reliable

    parameter is the one that sets in 0.5 + 0.8 m3/h for kW installed, the

    required water rate. Note that this water rate is reflected in a real

    consumption only in the case in which the water, at the outlet of the

    condenser, is recycled and is therefore "lose".

    In the case in which the plant is provided with cooling tower or

    condenser cooler with air, the consumption of water, may set around

    3% + 4% of the water rate above established.

    Steam

     The requirements of heat, for winter conditions, can change from a

    minimum of 15 + 20 Kcal/h per m3 to a maximum of 30 + 35 Kcal/h.

    Knowing the building’s cubature is immediate to get a reasonable

    estimate of the necessary steam.

    Engine Room

     The practice shows that many times it overlooks, in the design of a

    building, to provide adequate space for the engine and the equipment

    room. In principle we can consider that the engine room should have,

    with a height of 3 + 4 meters, a surface of 0, 6 + 1 m2 for each 100 m3

    of conditioned space.

  • 8/16/2019 4. The packages.pdf

    22/38

     

    Page 170 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.3 

    Pneumatic Transport Systems

    With the technical term “Pneumatic Transport”, we define a particular

    transport system that uses a flowing gas in order to transport different

    kind of products, such as: dry solid material of different shape and size

    (chips, granules, powdery, etc.).

    4.3.1 

    Definitions

    As follows the definitions of the most frequently quantities and terms

    used in Pneumatic Transport field are listed.

    4.3.1.1 Equivalent length

    It concerns the effective length of the circuits, which is appropriating

    increased in order to consider the localized resistances.

    4.3.1.2 Concentration

    It concerns the relation between the weight of the transported product

    and the weight of the gas constituting the vehicle which is involved inthe transport.

    4.3.1.3 Velocity of Support or Flotation

    It is the velocity for which the thrust induced on the product particles,

    balances their weight.

    4.3.1.4 Specific Gravity in Bulk

    It concerns the apparent specific gravity that considers the existing

    voids among the particles. In order to assure a good evaluation of this

    quantity, it is necessary to indicate as well the context in which the

    measure has been performed (in condition of aeration, whether

    compacted etc.)

  • 8/16/2019 4. The packages.pdf

    23/38

     

    Page 171 of 462 

       S   T   P  -   0   1   1   /   1   3

    4.3.1.5 Angle of Repose

    It is the angle for which the material free surface, let free to glide,assumes the final position in comparison with the horizontal level.

    4.3.1.6 Granulometry

    It gives the dimensions of the granules or of the particles that constitute

    the material. It is determined from the quantity in percentage of the

    granules that have defined dimensions.

    4.3.1.7 Flowability

    It is the characteristic of the material obtainable from laboratory

    research. It gives useful guidelines about the transportability of the

    material.

    It is function of the following parameters:

      Humidity

      Density in bulk

     

    Compressibility  Angle of repose

      Uniformity coefficient

    4.3.1.8 Floodability

    It is the characteristic of the material obtainable from laboratory

    research. It gives useful guidelines about the possibility to be

    maintained in suspension.

    It is function of the following parameters:

       Transport aptitude

      Angle of fall

      Aptitude to dispersion

  • 8/16/2019 4. The packages.pdf

    24/38

     

    Page 172 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.3.1.9 Electro-excitability

    It is the tendency of the material to acquire an electric charge due to

    wiping.

    4.3.1.10 Explosiveness

    It is the possibility of the material, in determined conditions of

    temperature, pressure and humidity, to create explosive mixture.

    4.3.2  Classification

     The pneumatic transport can be essentially divided into two main

    categories:

       Transport of powdery and granulate material by means of

    horizontal and vertical ducting, using pressure or suction

    pressure gas.

      Transport of suitable material easily to be fluidized by means akind of a little sloping duct with bottom constituted by a porous

    septum crossed by gas.

     The pneumatic transport that belongs to the first category, can be

    classified in function of the following parameters.

    4.3.2.1 Classification according to the Operating Requirements

     

     Transports of suction type

       Transports of pressure type

       Transports of suction-pressure type (combined)

  • 8/16/2019 4. The packages.pdf

    25/38

     

    Page 173 of 462 

       S   T   P  -   0   1   1   /   1   3

    4.3.2.2 Classification on Concentration Basis

     Low concentration transports on pressure

      Low concentration transports on suction

      Medium concentration transports on pressure

      Medium concentration transports on suction

      Low and medium concentration transports on suction-pressure

      High concentration transports on pressure

    4.3.2.3 Classification according to Pressure Level

     The transports on pressure can be classified as follows:

      Low pressure transports (≤ 10.000 mm w.c.)

      Medium pressure transports (10.000 – 30.000 mm w.c.)

      High pressure transports (≥ 30.000 mm w.c.)

    4.3.2.4 Classification according to the Machines and/or Equipment Used

       Transports carried out by means of fan ∗ 

       Transports carried out by means of blowers, Root type ∗ 

       Transports carried out by means of compressors ∗∗ 

       Transports carried out by means of “liquid ring pumps” ∗ 

    ∗  with the use of rotary valves for the loading

    ∗∗  with the use of launch pots for the loading

    4.3.2.5 Classification according to the Type of Circuit

       Transports by means of open circuit

       Transports by means of closed circuit

  • 8/16/2019 4. The packages.pdf

    26/38

     

    Page 174 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.3.3  Selection

    4.3.3.1  The use of pneumatic transport for solid or powdered materials, in place

    of other type of transport, is mandatory, a part of any other

    consideration, when:

       There is the demand to make the transport, without the

    contamination of the surrounding environment.

       There is the requirement to make the transport, avoiding any loss

    of product even if occasional.

      Man has to send and/or to take the product to/from points not

    otherwise accessible.

      Man has to transport products perishable on contact with

    atmosphere; in this case man resorts the transport in close

    circuit, with inert gas, or in close circuit with air properly treated.

    4.3.3.2  The use of pneumatic transport, instead of other types of transport, is

    suggested when:

      Complicated and tortuous courses have to be followed because of

    various facilities (railway and for pedestrian crossing, harbourdocks, big equipment and existing structures etc.)

      Man has to take the products from points of not easy accessibility

    (corners of storehouse, wagons and trucks, unloading, bags

    breakers etc.)

      Man has to avoid forced stops of product (which could cause

    fermentations) that could require expensive action for cleaning

    and maintenance.

    4.3.3.3 Selection among the various types of pneumatic transport

     The logistic configuration and the number of the loading and unloading

    points of the plant establish the basis choice of transport type; therefore

    the following transports will be used:

  • 8/16/2019 4. The packages.pdf

    27/38

     

    Page 175 of 462 

       S   T   P  -   0   1   1   /   1   3

     

       Transports of suction type, when we have to pick up the product

    from more points and we have to send it to an only one point(provided that the transport distance and flow rate allow this type

    of transport)

       Transport of pressure type, when we have to convey the product

    from one loading point to various unloading points.

       Transport of suction-pressure type, when we have to take the

    product from various points and we have to send it to various

    unloading points

    4.3.4  Design Criteria

    4.3.4.1 Dust exhausting and filtering

    Whether for the treated product the maximum quantity of dust, which

    is given out from the dust exhausting system, it is not in accordance

    with the Standard or it is not plainly indicated, it shall be specified by

    the supplier (mass flow for unitary transporting air volume). In any case

    it shall not be higher than 25 mg/m3.

     The dust exhausting system shall be built up with not combustible

    stuff.

     The filtering suction hose material shall be dealt with the operative

    requirements and also with the transported product type. In particular

    provided that the powders can produce explosive mixtures, the suction

    hoses shall be made with electro-conductive material in order to avoid

    the accumulation of static electricity.

     The use of hoses filters with mechanical shaking, it is allowed only for

    transports with an operation purely discontinuous.

    If the supplier has forecast only one cyclone system in the vacuum

    system, as dust exhausting system, the fan (or the blower) that is used,

    shall be formally guaranteed against the wear.

  • 8/16/2019 4. The packages.pdf

    28/38

     

    Page 176 of 462 

       S   T   P  -   0   1   1   /   1   3

    4.3.4.2 Materials

    All the ducts will be realized with the use of not combustible stuff. If,there is the possibility that the product could be damaged by the

    ferrous pollution, it will be used stainless steel or aluminium.

    Diameters

     The diameter of the ducts will be estimated depending on the effective

    volume of the gas. In case of transports with high compression ratio,

    the variation of the ducts diameter shall be provided.

     Thickness The thickness of the ducts will depend on the diameter, on the operative

    conditions and at last, on the type of the material. If it is not specified,

    the selection of the suitable thickness will be a supplier duty.

    Bend

     The minimum radius of the bends, carried out in only one piece, will be

    equal to:

     10 diameters concerning the transport supply lines

      1,5 diameters concerning the dust exhaust lines

     The lines that are realized with segments, shall be constituted, at least,

    by 10 stub pipes when the angle of the bend measures 90°.

    Whether it is possible, it would be better to avoid, between two

    consecutive bends, the intermediate lengths (sections), if it is lower than

    10m.

  • 8/16/2019 4. The packages.pdf

    29/38

     

    Page 177 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    Connections

     

    Flanged connections

    In conformity with the to ducting, the flanges will be in

    accordance with, if it is possible, the Standard ANSI, excepted the

    thickness, that would be a supplier duty.

      Welded connections

    In case of ducts butt-welded, the execution of the welding shall

    ensure the absence of distortions especially for thickness of a

    modest entity.

    Supports

      Vertical Ducting

     The supports for vertical ducting shall be positioned at distance

    not higher than 7m.

      Horizontal Ducting

     The supports for horizontal ducting shall be made with the

    following distances:

    diameter span

    up to 3″  3 m

    4″ + 8″  4,5 m

    10″ + 14″  6 m

    Whether the realisation of the ducting supports should not be a duty of

    the supplier of the pneumatic system, anyhow in his design, the

    supplier shall provide and therefore permit a correct and safe anchorage

    of the supports, for instance considering beams or supports for the

    consequents overloads.

  • 8/16/2019 4. The packages.pdf

    30/38

     

    Page 178 of 462 

       S   T   P  -   0   1   1   /   1   3

    4.3.5  Rotary Valves

     The maximum difference of pressure that it is allowed for the rotary

    valves is 6.000 mm w.c.

    Within the systems under pressure, the rotary valves shall be supplied

    with a breather pipe to allow the correct loading of the alveoli and to

    avoid the formation of air pockets above the valve.

     The minimum number of the radial blades shall not be lower than eight.

    Moreover the number of blades from the side “air” that are used in the

    seal, has to be higher than the side “product”.

     The rotary open valves are operating only for pressure values that are

    lower than 2.500 mm w.c. and never for granulated products or anyhow

    brittles.

     The rotary valves will be normally activated by means of a chain. In case

    of complex or a not well known product, the rotary valves of feeding will

    be provided of speed variators.

    4.3.6  Switches Valves

     The choice of the type of the switch valve, if otherwise not specified, is

    left to the supplier. In any case the following prescriptions shall be

    observed.

    4.3.6.1 Switches Valves of Elastic Strain Type

     These types of valves are not usable when:

       The system has been used for transports of several products that

    can not be in contact

       The temperature overcomes 100°C.

    4.3.6.2  Two Way Valves, Blade Type

    Usable only for the transport of granules.

  • 8/16/2019 4. The packages.pdf

    31/38

     

    Page 179 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.3.6.3 Switches Valves with Flexible Hydraulically Operated Devices

     These types of valves are not usable for products that can not be in

    contact with the atmosphere.

    4.3.6.4  Two Way Valves, Drum Type

     To be used only in extreme case.

    4.3.7 

    Operating Equipment

     The selection of the suitable equipment provided with all the necessary

    devices, such to make the system safe and reliable, shall be at the

    manufacturer care if not otherwise indicated. In any case the following

    guidelines shall be considered:

    Rotary compressors, blade type, shall not be used in case of the product

    does not accept oil traces even if minimal.

    In case the product can generate explosive mixtures and the plant is

    under pressure, the blower blades shall be in anti-sparking execution.

    Fans and blowers shall be provided with the belt transmission in order

    to vary the characteristics, if any.

    4.3.8  General Criteria for Installation

    4.3.8.1 Operative Accessibility

     The supplier shall assure the operative accessibility of all the

    equipment. In case of mandatory logistic or process reasons, the

    ducting should completely contain the equipment positioned at ground

    level; the supplier shall provide the space for a proper settlement ofoverpasses.

     The roofs of the silos and the service levels of the structure supporting

    the transport equipment shall be accessible by means of ladders with

    interruption point positioned at maximum of 9 meters of high.

  • 8/16/2019 4. The packages.pdf

    32/38

     

    Page 180 of 462 

       S   T   P  -   0   1   1   /   1   3

    When the silos, connected to pneumatic transport, are grouped in such

    way to constitute a battery (adjoining or reasonably close) the roofs of

    these silos shall be connected each other by means of platforms. In this

    case possible differential gradient between the silos shall be dulyconsidered.

    On the top of the silos served by pneumatic transport it shall be

    foreseen the space and the support for the arm of the hoist intended for

    the lifting of the heaviest piece to be handled during the maintenance

    operation.

    Such hoist shall be suitable to permit the descent inside the silo of a

    crate apt to contain one person.

    4.3.9 

    Safety Rules

    Design of silos, filters and of any other possible vessel and/or

    equipment to the pneumatic transport assigned for product that can

    cause explosive mixtures.

    A part of specific rules on the matter, the following provisions have to be

    considered as prescriptions of good engineering:

       To provide proper discharge holes (vents) which allow to limit the

    pressure values in case of explosions

     

     To carry out the vessel adopting a design pressure such as itscomponents (roof, bottom and shell) can, in case of explosion,

    cause warping without constituting danger for the surrounding

    environment.

     The vents can be of the following type:

      Hinged hatch covers; to be used in case the product is not subject

    to deterioration to the though least contact with the atmosphere.

      Diaphragms; to be used in case the contact of the product with

    the atmosphere is absolutely to be avoided.

    In lack of other specific guidelines, the vents surface, shall be

    calculated on the bases of what recommended by “National Fire Codes”

    last edition.

    In case the roofs of the silos, provided by the pneumatic transport

    system, are also partly realized with diaphragms, immediately under the

    roof shall be provided an opportune safety net.

  • 8/16/2019 4. The packages.pdf

    33/38

     

    Page 181 of 462 

       S   T   P  -   0   1   1   /   1   3

     The silos provided by the pneumatic transport, shall be supplied with a

    taking gate for the fireproof plant (sprinkler).

    In case the transported product can cause explosive mixture or in casethe plant, also transporting product that does not cause explosive

    mixture, comes to be, also partially, in classified area, the grounding of

    the ducting and of the equipment, shall be assured.

    4.3.10 Tests

    4.3.10.1 Dimensional Check by the Shop

     This check will be carried out in shop during the fabrication of theequipment and ducting to verify the correspondence of the various

    components with the working and detailed drawing approved for the

    construction.

    4.3.10.2 Working Test by the Shop

    For all that components, for which it is demanded the seal to the dusts

    and the air, as switches, filters, tank of discharge etc. a resistance test

    to water and/or air will be carried out according to the modalities that

    will be agreed between the engineering company and the manufacturer.

    4.3.11 

    Material Requisition

    Since a Pneumatic Transport is a package rather complex for the

    number of the involved items, for the ducting routes, sometimes very

    meandering for the installation and safety problems, particular

    attention and care have to be given in the preparation of the material

    requisition for quotation.

     The following data, information and drawings, to not be considered,anyhow, exhaustive, have to be supplied to the Vendors of these units:

      Physical and chemical properties of the material to be

    pneumatically conveyed.

      Size of maximum lump size.

      Maximum rate.

       Temperature and moisture content.

  • 8/16/2019 4. The packages.pdf

    34/38

     

    Page 182 of 462 

       S   T   P  -   0   1   1   /   1   3

      Possible abrasiveness, stiking, gumming, etc, of the product.

       Type of the transport to be adopted (to be confirmed by the

    Vendor).  Suggested lay-out of the system (to be confirmed by the Vendor).

      Data Sheet or technical description of all required equipment and

    materials as: storage silos, feeding hoppers, bag breaker (if any),

    intermediate and final silos, cooling coils (if any), pneumatic

    transport screw conveyors (if any), rotary valves, exhausting

    systems.

      Battery limits. As far as the battery limits are concerned, they can

    be fixed in very short and simple modality; in fact, the battery

    limits of the product generally are: the first loading hopper at the

    beginning of the transport system and the last silo at the end ofthe same.

    For the utilities the battery limits shall be:

      for the electrical part, the cables glands on the power and control

    panel(s) supplied by the Vendor. All the connections to the other

    electrical users, starting from the control panel shall be at Vendor

    care and charge.

     

    in case of need of water to cool the transported product, thebattery limits shall be flanged connection to each exchangers or

    coil; it is not convenient, even if possible of course, to let Vendors

    make the connection among the various exchangers or coils with

    piping of their supply. In other words the piping distribution will

    be at the Contractor care and charge.

      In case of instrument air need, the same considerations, made for

    the cooling water, are still valid.

  • 8/16/2019 4. The packages.pdf

    35/38

     

    Page 183 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.4 

    Material Handling Systems

     These systems have the purpose to transport dry material of different

    origin, shape and size; they are employed in various industrial fields as

    coal-mine, pharmaceutical industries, food industries, plastic materials

    production plants, etc..

    In this chapter, we will not deal with dusty or granular products of

    which we will refer to the pneumatic transport systems.

     Therefore we are considering Belt Conveyor, Bucket Belt Elevator,

    Chain Conveyor etc..

    Manufacturer’s literature on conveyors usually contains suggestions for

    the selection of more convenient and useful handling system.In any case the process engineer, the project engineer and the

    mechanical specialist, always in close contact, have to supply to the

    Manufacturer all the necessary data and information as:

      Physical and chemical properties of the material to be handled

      Maximum rate

      Size with the indication of maximum lump size

       Temperature and moisture content

     

    Bulk and real density

      Possible abrasiveness, chemical reactivity, sticking, gumming etc.

      Length and location of the conveyor including sketch showing the

    proposed path, the equipment directly connected in the operation,

    as sylos, mixers, etc.; of course type of the building or shelter has

    to be specified with the indication of the internal temperature and

    humidity.

  • 8/16/2019 4. The packages.pdf

    36/38

     

    Page 184 of 462 

       S   T   P  -   0   1   1   /   1   3

     

    4.5 

    Oily Water Treatment Unit

     The oily water treatment unit, CPI type (corrugated plates interceptor),

    of contained dimensions, can be considered a typical “skid mounted”

    package.

    With the term “skid mounted” we intend an unit package completely

    assembled in the manufacturer shop, installed on skid.

     The unit, after the transport on site, has to be only connected to the

    inlet and outlet piping, while the local control panel has to be

    electrically fed.

     The system is used to eliminate the oil from the water.

     The water to be treated is sent, for gravity, to the CPI unit in order to

    avoid the formation of emulsion due to the action of the pumps.

     The oil is separated for the differences of specific weights; the

    separation is favoured by means of the action of the coalescent plates,

    located in the basin of separation.

     The oil is removed by means of a skimmer and discharged into a tank

    and, from this, transferred by a pump of screw type.

     Then the water is sent to a second tank and discharged by a floodway,

    adjustable along the height. Finally the water is transferred into a vessel

    in order to be discharged by the action of a centrifugal pump.

     The slush, formed for the sedimentation of the suspended solids, can be

    discharged by a manual valve.

    Differently from other equipment and units, for this kind of package

    particular knowledge and studies are not required by the process and

    project engineers since this type of units is enough standardized.

     The necessary data and information to be supplied to the

    manufacturers are the following:

      Flow rate of the water to be treated

      Oil content (in mg/l) at the inlet

      Oil specific gravity

      Suspended solids (in mg/l) at the inlet

      Oil content in the water (in mg/l) at the outlet

      Max dimension of the separated oil drop (in mm value, if

    indicated, to be confirmed by the Vendor)

  • 8/16/2019 4. The packages.pdf

    37/38

     

    Page 185 of 462 

       S   T   P  -   0   1   1   /   1   3

       Temperature of the water

      Environmental conditions

  • 8/16/2019 4. The packages.pdf

    38/38

     

    Page 186 of 462 

    S   T   P  -   0   1   1   /   1   3

     

    4.6 

    Dosing Units

    Also a dosing unit, as well as the Oil Treatment Unit, of CPI type,

    previously examined, can be considered a typical example of package

    unit, completed shop assembled, mounted on skid, complete with

    drivers and all the other necessary accessories.

    As example we will consider an Antifoam Dosing Unit for the Injection

    and Measuring of an antifoam product into an amine liquid flow.

     The unit, taken into consideration, is very simple and of limited

    dimensions; it is mainly constituted by:

      N° 1 atmosphere tank, SS made, for the storage of the product

    solution

      N° 2 dosing pumps (one as spare)

      N° 1 calibration pot

      Oscillation dampers

      Connecting piping and the necessary instrumentation

    Also in this case, since the package of this type are largely

    standardized, the only care and attention that the process engineer andproject engineer have to be given are the completeness of data and

    information to be furnished to the manufacturer, they are:

      Flow rate of the dosing pump (in lt/h)

      Material of the dosing pump (SS)

      Codes for the pumps (f.i. API 675)

      0 ÷ 100 % with the pump in operation

      Outlet pressure (bar g)

      Capacity and material of the tank

       Type of antifoam product (f.i. Chimec 8049 or equivalent)